PLEASE NOTE
The power meter should be installed, operated, serviced and
maintained only by qualified personnel. No responsibility is
assumed by the manufacturer for any consequences arising
out of the use of this material.
DISCLAIMER
Mikro shall not be liable for errors contained herein including
any incidential and/or consequential damages arising from
the use of this material. Mikro also reserves the right to vary
the product from that described in this material without prior
notice.
COPYRIGHT
The licensed software contaioned in the product is proprietary
software owned by Mikro or its third party suppliers and shall
be used solely in connection with the product.
BEFORE YOU BEGIN
• Apply appropriate personal protective equipment and
follow safe electrical work practices.
• NEVER work alone.
• Turn-off all power supplying the power meter and the
equipment in which it is installed before working on it.
• Always use a properly rated voltage sensing device to
confirm that all power is off.
• Before closing all covers and doors, carefully inspect the
work area for tools and objects that may have been left
inside the equipment.
• NEVER bypass external fusing.
• NEVER open circuit a CT; use the shorting block to short
circuit the leads of the CT before removing the connec-
tion from the power meter.
• Before performing hi-pot testing on any equipment in
which the power meter is installed, disconnect all input
and output wires to the power meter. High voltage test-
ing may damage electronic components contained in
the power meter.
• The power meter should be installed in a suitable electri-
cal enclosure.
1. Introduction 1
1.1.Content of box 1
1.2.Part of power meter 2
2. Installation Guide 4
2.1.Precautions 4
2.2.Mounting 4
2.3. Wiring 7
3. Meter parameters 11
5. Function 13
6. Setting up 15
6.1.Access programming mode 15
6.2.Setup CT ratio 16
6.3.Setup PT ratio 17
6.4.Neutral current 18
6.5.Setup communication configuration 19
6.6.Demand setting 20
6.7.System setting 21
6.8. Reset all energy register 22
6.9. Reset demand register 23
6.10. Reset maximum & minimum value 24
6.11. Remote set 25
6.12. Scroll mode setting 26
6.13. Scroll delay setting 27
6.14. Reset Hour on register 28
6.15. Backlight setting 29
6.16. Exit from programming mode 30
6.17. Setup new password 31
7. Specifications 33
8. Modbus table 36
10. Dimensions 51
11. Appendix 53
11.1. Demand calculation 53
11.2. Data read format from modbus 54
FIGURES
TABLE
1. Parts list 1
2. Location and part label 2
3. Model information 3
4. Specification 33
5. Data length nomenclature 36
6. Device and communication register 37
7. Operation data registers 37
8. Setting data registers 49
1.Introduction
Thank you for purchasing the DPM380 Digital Power Meter.
This multifunction power meter measuring the following
parameters:
5
6
1 2
CURRENT INPUTS ... / 5A (6A MAX.)
I1 I2 I3 In
6 1
S1
2
S2
3
S1
4
S2
57
S1
6
S2 S1
8
S2
Modbus RTU RS485
9 10 11 12 13 14
Gnd
- +
2
Model Information
DPM380-415AD Auxiliary 90~415VAC or
100~300VDC; with Modbus
3
2. Installation Guide
2.1. PRECAUTIONS
2.2. MOUNTING
a) Provide a cut out hole on the switchgear panel according
to the dimension below.
0.5mm
91
91
0.5mm
4
b) Insert the power meter through the hole and slide in the
retainer clip along the slots on left and right sides or bottom
and top sides of the power meter until the device is tightly
secured on the switchgear panel. The orientation of the
retainer clips is shown in figure 1.
5
e) When connecting the power meter, please make sure the
polarity to the terminal is correctly aligned.
6
2.3. WIRING
19
20
1
2
3
4
5
6
7
8
15
13
16
14
17 12
18
7
19
20
1
2
3
4
5
6
7
8
13
15 14
12
16
17
18
8
19
20
1
2
3
4
5
6
7
8
13
15
14
16 12
17
18
9
19
20
1
2
3
4
5
6
7
8
13
15
14
16 12
17
18
10
3. Meter parameters
Before commencing operation, the meter has to be set up. To
do this, the meter must be powered up by the meter control
power supply.
• CT ratio
• PT ratio
• Neutral current input
• Modbus-RTU setting
• Demand setting
• System setting
• Scroll mode setting and delay time
• Backlight setting
11
4. Display and Buttons
m a
b
c
d
l
e
f
k j i h
12
5. Function
Figure 7 below shows menu map for the power meter. It
includes the setting and measurement display for the power
meter. These menus can be accessed by pressing NEXT, UP,
PROG & DOWN buttons.
Current Current
Line Current (A) Max. (A)
Min. (A)
Total Real Total Neg.Real Total Reactive Total Neg. Reac. Total Apparent
Energy (Wh) Energy (-kWh) Energy (VARh) Energy (-VARh) Energy (VAh)
THD
THD Current (A)
Voltage (V)
Hour On
(Days, Hrs, Mins)
13
PROG Mode
Neutral Current
Setting (Ln)
Demand
Setting
System Setting
Reset All
Reset (Yes/No)
Energy Regsiter
Reset
Reset (Yes/No)
Max/Min
Remote Set
Scroll Delay
To set interval time for scroll display (1-10secs)
Time
Reset Hour-
Reset (Yes/No)
On Register
Backlight
Setting
d. Press the NEXT button for the next digit. Repeat step (b)
& (c) to change, or else press NEXT button till the digit
stop blinking.
16
6.3. SETUP PT RATIO
b. Press the NEXT button. The “PROG” and “-” symbol next
to “ID” will blink. Use the UP or DOWN button to change
the device ID.
22
6.9. RESET DEMAND REGISTER
23
6.10. RESET MAXIMUM AND MINIMUM VALUE
24
6.11. REMOTE SET
25
6.12. SCROLL SETTING
28
6.15. BACKLIGHT SETTING
If select
“Yes”
30
6.17. SETUP THE PASSWORD
b. After pressing the PROG button, the “new id” window will
be displayed. At this stage, the user needs to key in the
new password. Use the UP or DOWN button to change
the digit value and the NEXT button to shift to next digit.
Once confirmed, press the PROG button.
31
c. Next, the “SAVE SEt” will be displayed. Use the UP or
DOWN buttons to toggle the ”YES“ and ”NO“ symbols
to save the new password. Once confirmed, press the
PROG button and the meter will return to normal display
mode.
32
7. Specification
Electrical Characteristic
System 3P3W & 3P4W
Current
Display Three phase current &
neutral(selectable)
CT Primary 5-9995A
CT Secondary 5A
Accuracy 0.5% (from 1A to 6A
secondary)
Sustained overload 6A
Voltage measurement
PT Primary 100-33kV
PT Secondary 100-250V, no PT
Secondary Phase Voltage 20~300VAC
Accuracy 0.5%
Power (kW,kVAR,kVA) measurement
Display each phase & total
Accuracy 1%
Power factor measurement
Display each phase & total
Accuracy 1%
Table 4 : Specification
33
Table 4: Specification (cont)
Frequency measurement
Range 45~65Hz
Accuracy 0.5%
Energy measurement
Active IEC62053-21:Class 1
Reactive IEC62053-23:Class 2
Demand measurement
Demand interval 60 to 1800 seconds
Demand sub-interval 1 to 120
Communication
Hardware Interface Isolated RS485
Protocol Modbus-RTU
ID 1 to 255
Baudrate 2400, 4800, 9600, 19200,
38400
Parity None, even, odd
Operating Condition
Auxiliary Supply 90~415VAC or 100~300VDC
Operating Temperature -10 C ~ +55 C
Storage Temperature -20 C ~ +70 C
Operating time (on hour) Up to 9999 days, 23 hours,
59 minutes.
34
Table 4: Specification (cont)
Mechanical Characteristic
Dimension
Case L96mm x W96mm x H105mm
Mounting type Panel
LCD view area 76mmx56.5mm
Weight 480g
Electromagnetic Compatibility (EMC)
Part 6-2: Generic Immunity for industrial
Standards IEC61000-6-2 environments
Part 6-4: Generic Emission standard for
Standards IEC61000-6-4 industrial environments
35
8. Modbus Data Register
8.1 Data Type
By default, the data format in each register is unsigned 16-
bit word. Shorter data may be encoded in the unsigned 8-bit
byte format whereas longer data may be encoded either in
the unsigned 32-bit double word format, signed 32-bit integer
format or signed 64-bit long integer format. Two’s comple-
ment is used to represent signed numbers. The nomencla-
ture used in this manual is shown in Table 5.
36
Table 6: Device and communication register
Read Only (Function 0x03 or 0x04)
0-1 Reserved
2-3 Device Type
4-5 Version
Read Only (Function 0x03 or 0x04)
1000 Device ID 1-255
1001 Parity 1=none 2=even
3=odd
1002 Baudrate 1=2400
2=4800
3=9600
4=19200
5=38400
37
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
4020- Instantaneous
dword 0.001A 0~999.9kA
4021 Current L1
4022- Instantaneous
dword 0.001A 0~999.9kA
4023 Current L2
4024- Instantaneous
dword 0.001A 0~999.9kA
4025 Current L3
4026- Instantaneous
dword 0.001A 0~999.9kA
4027 Current Ln
4028-
Voltage Phase L12 dword 0.1V 0~999.9kV
4029
4030-
Voltage Phase L23 dword 0.1V 0~999.9kV
4031
38
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
4032- Voltage Phase
dword 0.1V 0~999.9kV
4033 L31
4034-
Voltage Phase L1 dword 0.1V 0~999.9kV
4035
4036-
Voltage Phase L2 dword 0.1V 0~999.9kV
4037
4038-
Voltage Phase L3 dword 0.1V 0~999.9kV
4039
4040-
Real Power L1 int 1W -2000M~2000M
4041
4042-
Real Power L2 int 1W -2000M~2000M
4043
4044-
Real Power L3 int 1W -2000M~2000M
4045
4046- Apparent Power
dword 1VA 0 ~999.9M
4047 L1
4048- Apparent Power
dword 1VA 0~999.9M
4049 L2
4050- Apparent Power
dword 1VA 0~999.9M
4051 L3
4052- Reactive Power
int 1VAR -2000M~2000M
4053 L1
4054- Reactive Power
int 1VAR -2000M~2000M
4055 L2
4056- Reactive Power
int 1VAR -2000M~2000M
4057 L3
39
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
4058- Total Demand
int 1VAR -2000M~2000M
4059 Reactive Power
4060- Max.Total Demand
int 1VAR -2000M~2000M
4061 Reactive Power
4062-
Reserved
4063
4064- Total Demand Real
int 1W -2000M~2000M
4065 Power
4066- Max. Total Demand
int 1W -2000M~2000M
4067 Real Power
4068-
Reserved
4069
4070- Total Demand
dword 1VA 0~2000M
4071 Apparent Power
4072- Max. Total Demand
dword 1VA 0~2000M
4073 Apparent Power
4074-
Reserved
4075
Displacement Power
4076 word 0.001 0 ~ 1.000
Factor L1
Displacement PF 0=Resistive;
4077 word -
sign L1 1=ind; 2=cap
Displacement Power
4078 word 0.001 0 ~ 1.000
Factor L2
Displacement PF 0=Resistive;
4079 word -
sign L2 1=ind; 2=cap
40
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
Displacement Power
4080 word 0.001 0 ~ 1.000
Factor L3
Displacement PF 0=Resistive;
4081 word -
sign L3 1=ind; 2=cap
4082 THD Current L1 word 0.1% 0 ~ 1000
4083 THD Current L2 word 0.1% 0 ~ 1000
4084 THD Current L3 word 0.1% 0 ~ 1000
4085 THD Voltage L1 word 0.1% 0 ~ 1000
4086 THD Voltage L2 word 0.1% 0 ~ 1000
4087 THD Voltage L3 word 0.1% 0 ~ 1000
*Energy flag
bit 7 to 5 =
reserved
bit 4 = (-)kVARh
4088 Energy Full Flag word bit 3 = (-) kWh
bit 2 = kVAh
bit 1 = (+)kVARh
bit 0 = (+)kWh
4089 Power Factor L1 word 0.001 0 ~ 1.000
Sign Power Factor 0=Resistive;
4090 word -
L1 1=ind; 2=cap
4091 Power Factor L2 word 0.001 0 ~ 1.000
Sign Power Factor 0=Resistive;
4092 word -
L2 1=ind; 2=cap
4093 Power Factor L3 word 0.001 0 ~ 1.000
Sign Power Factor 0=Resistive;
4094 word -
L3 1=ind; 2=cap
*if the energy is full, the bit is set to 1, else bit is 0.
41
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
Sign Total Power 0=Resistive;
4095 word -
Factor 1=ind; 2=cap
4096-
Current L1 Max. dword 0.001A 0~999.9kA
4097
4098-
Reserved
4099
4100-
Current L2 Max. dword 0.001A 0~999.9kA
4101
4102-
Reserved
4103
4104-
Current L3 Max. dword 0.001A 0~999.9kA
4105
4106-
Reserved
4107
4108- 0.001A
Current Ln Max. dword 0~999.9kA
4109
4110-
Reserved
4111
4112-
Voltage L1 Max. dword 0.1V 0~999.9kV
4113
4114-
Reserved
4115
4116-
Voltage L2 Max. dword 0.1V 0~999.9kV
4117
4118-
Reserved
4119
42
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
4120- Voltage L3
dword 0.1V 0~999.9kV
4121 Max.
4122-
Reserved
4123
4124- Voltage L12
dword 0.1V 0~999.9kV
4125 Max.
4126-
Reserved
4127
4128- Voltage L23
dword 0.1V 0~999.9kV
4129 Max.
4130-
Reserved
4131
4132- Voltage L31
dword 0.1V 0~999.9kV
4133 Max.
4134-
Reserved
4135
4136- Total Real
int 1W -2000M~2000M
4137 Power Max.
4138-
Reserved
4139
4140- Total Apparent
dword 1VA 0~2000M
4141 Power Max.
4142-
Reserved
4143
4144- Total Reactive
int 1VAR -2000M~2000M
4145 Power Max.
43
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
4146-
Reserved
4147
4148- Max. Real
int 1W -2000M~2000M
4149 Power L1
4150-
Reserved
4151
4152- Max. Real
int 1W -2000M~2000M
4153 Power L2
4154-
Reserved
4155
4156- Max. Real
int 1W -2000M~2000M
4157 Power L3
4158-
Reserved
4159
4160- Max. Apparent
dword 1VA 0~2000M
4161 Power L1
4162-
Reserved
4163
4164- Max. Apparent
dword 1VA 0~2000M
4165 Power L2
4166-
Reserved
4167
4168- Max. Apparent
dword 1VA 0~2000M
4169 Power L3
44
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
4170-
Reserved
4171
4172- Max. Reactive
int 1VAR -2000M~2000M
4173 Power L1
4174-
Reserved
4175
4176- Max. Reactive
int 1VAR -2000M~2000M
4177 Power L2
4178-
Reserved
4179
4180- Max. Reactive
int 1VAR -2000M~2000M
4181 Power L3
4182-
Reserved
4183
4184- Current L1
dword 0.001A 0~999.9kA
4185 Min.
4186-
Reserved
4187
4188- Current L2
dword 0.001A 0~999.9kA
4189 Min.
4190-
Reserved
4191
4192- Current L3
dword 0.001A 0~999.9kA
4193 Min.
4194-
Reserved
4195
45
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
4196-
Current Ln Min. dword 0.001A 0~999.9kV
4197
4198-
Reserved
4199
4200-
Voltage L1 Min. dword 0.1V 0~999.9kV
4201
4202-
Reserved
4203
4204-
Voltage L2 Min. dword 0.1V 0~999.9kV
4205
4206-
Reserved
4207
4208-
Voltage L3 Min. dword 0.1V 0~999.9kV
4209
4210-
Reserved
4211
4212-
Voltage L12 Min. dword 0.1V 0~999.9kV
4213
4214-
Reserved
4215
4216-
Voltage L23 Min. dword 0.1V 0~999.9kV
4217
4218-
Reserved
4219
4220- Voltage L31 dword 0.1V 0~999.9kV
4221 Min.
46
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
4222-
Reserved
4223
4224- Total Real
int 1W -2000M~2000M
4225 Power Min.
4226-
Reserved
4227
4228- Total Apparent
dword 1VA 0~2000M
4229 Power Min.
4230-
Reserved
4231
4232- Total Reactive
int 1VAR -2000M~2000M
4233 Power Min.
4234-
Reserved
4235
4236- Real Power
int 1W -2000M~2000M
4237 Min. L1
4238-
Reserved
4239
4240- Real Power
int 1W -2000M~2000M
4241 Min. L2
4242-
Reserved
4243
4244- Real Power
int 1W -2000M~2000M
4245 Min. L3
4246-
Reserved
4247
47
Table 7: Operation data register (cont)
Read Only (Function 0x03 or 0x04)
Min.
Register Description Type Range
Unit
4248- Apparent
dword 1VA 0~2000M
4249 Power Min. L1
4250-
Reserved
4251
4252- Apparent
dword 1VA 0~2000M
4253 Power Min. L2
4254-
Reserved
4255
4256- Apparent
dword 1VA 0~2000M
4257 Power Min. L3
4258-
Reserved
4259
4260- Reactive
int 1VAR -2000M~2000M
4261 Power Min. L1
4262-
Reserved
4263
4264- Reactive
int 1VAR -2000M~2000M
4265 Power Min. L2
4266-
Reserved
4267
4268- Reactive
int 1VAR -2000M~2000M
4269 Power Min. L3
4270-
Reserved
4271
48
Read or write (Function 0x03,0x04 or 0x06)
Register Description Range
100 PT ratio primary 100~33kV
101 PT ratio secondary 100~250V
102 CT ratio primary 5~9995A
103 CT ratio secondary 5A
104 Interval Demand 60~1800s
105 Sub-Interval Demand 1~120
106 System Configuration 3P4W/ 3P3W
107 Backlight setting ON/OFF
108 System scroll setting ON/OFF
109 Scroll interval 1-10 secs
110 Neutral setting ON/OFF
111 Minutes 0-59mins
112 Hours 0-23hrs
113 Days 0-9999day
Table 8: Setting data register
NOTE:
Register list is based on firmware version 1.0
49
9. Maintenance and Troubleshooting
NOTE:
We reserve the right to alter or modify the information
contained herein at any time in line with our product de-
velopment without prior notification. We also reserve the
right to discontinue production & delivery of product.
50
10. Meter Dimension
96mm
96mm Front
90.5mm
17.5mm
105mm Rear
51
1 2 3 4 5 6 7 8
9 10 11 12 13 14 90.5mm
15 16 17 18 19 20
Back
90.5mm
52
11. Appendix
11.1. DEMAND CALCULATION
--------- is1
60s
is2
60s is3
60s
is4
60s is5 ---------
60s
--------- id1=(is1+is2+is3)/3
id2=(is2+is3+is4)/3
id3=(is3+is4+is5)/3 ---------
53
11.2. DATA READ FORMAT FROM MODBUS