MARCOBRE S.A.C.

MINA JUSTA PROJECT

DATA SHEET

SUBSTATION

Document No.JU-001-06-AUS-0000-06-26-0201

10194601-DS-0201
REV DATE DESCRIPTION AUTHOR MECH ENG PROCESS ELEC ENG APPROVED
ENG
A 31/01/2017 Issued for Internal Review WA MV
B 09/02/2017 Issued for Client Review WA MV RH
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
SUPPLIER/CONTRACTOR: By vendor
PLANT AREA: 4713
Required
MODEL No. / DESIGNATION
1.00 SITE CONDITIONS
1.01 Altitude msnm 825
1.02 Ambient temperature max °C 30
1.03 Ambient temperature min °C 8.4
Peruvian Seismic Code Standard
1.04 Seismic Conditions
E.030
1.05 Average annual precipitation mm 27.1
1.06 Minimum annual precipitation mm 13.7
1.07 maximum annual precipitation mm 50.5
1.08 Maximum wind speed km/h 90
2.00 STRUCTURAL REQUIREMENTS
2.01 GENERAL
2.02 Instalation Exterior
1 (Split If there is a restriction on Both facilities must have
2.03 Switchgear Electrical Room
transportation ) similar dimensions
1 (Split If there is a restriction on Both facilities must have
2.04 Electrical Room SCADA ICCP, SSAA, Comunications, protection and control & Batery Bank
transportation ) similar dimensions
2.05 Grade protection Nema 4
2.06 Type Modular
2.07 Minimum average load at base kg/m2 1220
2.08 Minimum roof overload kg/m2
2.09 Spot overload on the roof One person of 113 kg
2.10 Maximum deflection of the room during the lift 12.7 mm per 3 m
2.11 Structural calculation report Required
Continuous welding beads MIG or
2.12 Welding type main structures
TIG
2.13 Interior Dimensions Required
2.14 Width (mm) Required
2.15 Length (mm) Required
2.16 High (mm) Required
2.17 Exterior dimensions. Required
2.18 Width (mm) Required
2.19 Length (mm) Required
2.20 High (mm) Required
2.21 Weight of room without equipment (kg) Required
2.22 Weight of room with equipment (kg) Required
2.23 Lifting accessories (we can remove it) Required
2.24 BASE STRUCTURE
2.25 Type of beam Type I or H
2.26 Metallic cast iron bases for anchoring Required
2.27 EyeBolt Required, minimum 4, removable
Required and coordinated with
2.28 Detailed map of the structural base engineering plan that shows the
electrical passes
2.29 STRUCTURE OF THE ROOM
2.30 Type Steel tubes of square section
2.31 Dimension steel tubes By vendor
2.32 FLOOR
2.33 Cold rolled steel sheets 6 mm minimum thickness
2.34 Non-slip surface Required
2.35 SIDE COVERS
2.36 Plates of steel outside 1.9 mm minimum thickness
2.37 Plates of steel inside 1.5 mm minimum thickness
2.38 CEILING AND ROOF
2.39 Cold rolled steel sheets 1.5 mm minimum thickness
2.40 Roof slope 2 gabled, 8.5 %
2.41 Drainage channels Required
2.42 DOORS AND ACCESSES
2.43 Quantity at least 2
2.44 Minimum access dimensions of persons 1000 mm wide x 2200 mm high
2.45 Minimum Equipment Access Dimensions 2000 mm wide x 2500 mm high
2.46 Panic bar Required
2.47 Automatic closing, pneumatic Required
2.48 Insulation R11
Not Required
2.49 Floor

Page 2 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
2.50 Walls Required
2.51 Roof Required
2.52 Doors Required
2.53 PAINT
2.54 Painting procedure Required
2.55 Color outer walls White Winter, RAL 1015
2.56 Interior walls color White, RAL 9003
2.57 Floor Color Gray, ANSI 61
2.58 Color roof White Winter, RAL 9002
2.59 Color Celing White, RAL 9003
2.60 Color Exterior doors White Winter, RAL 9002
2.61 Color Interior doors White, RAL 9003
2.62 Color structures Light Gray, RAL 7035
2.63 STAIRS ANS HANDRAILS REQUIRED BY VENDOR
2.64 Color rails Yellow, RAL 1023
2.65 Color grids and steps Black, RAL 9011
2.66 WINDOWS JUST SCADA ELECTRICAL CONTROL ROOM
2.67 Transparent Required
2.68 Minimum dimensions 30 - 35% sides with external view Required
2.69 Adequate display for 220kV key yard Required
3.00 PRESSURIZATION AND REFRIGERATION SYSTEM
3.01 Manufacturer Required
3.02 Model Required
3.03 Catalogue Required
3.04 Positive pressure required mm.c.a 6.35
3.05 Amount of equipment Required
3.06 KW required per equipment Required
3.07 Progressive air filtration Required, disposable and washable
3.08 Calculation memory pressurizing system Required
3.09 Pressurization and refrigeration requirements Required
4.00 FIRE DETECTION AND SUPPRESSION SYSTEM
4.01 Category Room with respect to the impact on the environment Required
4.02 DETECTION SYSTEM
4.03 Fire Detection Panel Required
4.04 Optical transceiver Required
4.05 Early detection system Required
4.06 Amount of Early Detection Systems Required
4.07 Smart smoke detectors Required
4.08 Number of Smart Smoke Detectors By vendor, according to NFPA -72
4.09 Manual Stations Required
4.10 Number of manual stations 2 (1 on each door)
4.11 Horn strobe light Required
4.12 Number of sirens strobe 2 (1 outside of each door)
4.13 SUPPRESSION SYSTEM
4.14 System of suppression based on FM-200 Required
4.15 Amount of FM-200 for the total volume of the room (kg) Required
4.16 Manual Abortion Stations Required
4.17 Number of manual abortion stations Required
4.18 Fire extinguishers portable type C02 (15 kg each) Required
4.19 Number of portable fire extinguishers 2 (1 outside of each door)
5.00 ELECTRICAL SERVICES
5.01 POWER AND CONTROL WIRING
Control wiring between cells 22.9kV to Mimico board measuring and controlling cells 220 /
5.02 Required
22.9kV
5.03 Wiring between Auxiliary board and system rectifiers 380VAC / 120VDC Required

5.04 Wiring of power between auxiliary board and distribution system SCADA / DATA CENTER etc Required

5.05 SCADA / ICCP and DATA CENTER communication wiring. Required

Wired UTP and / or multimode fiber optic cable between the communications switch, relays,
5.06 Required
controllers, meters, regulators of taps, indicators of position,

Wired UTP and / or multimode fiber optic cable between communications switch, SCADA /
5.07 Required
ICCP servers
5.08 LIGHTING
5.09 Interior lighting level Lux 500
5.10 Type internal luminaires Fluorescent 2 x 40 W
5.11 External luminaires type HPS, 100 W

Page 3 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
5.12 Emergency Lighting Required, By Vendor
5.13 General Purpose Plugs Required, 220 V, 15 A
5.14 EARTHING
5.15 Two external grounding plates for grid connection Required
Internal grounding bar interconnected with outer plates and capable of landing all indoor
5.16 Required
electrical equipment (including futures)
Required according to reference
5.17 Power Wiring and Control Inside
planes

5.18 Wiring of power between auxiliary board and distribution system SCADA / DATA CENTER etc Required

5.19 Communications Wiring SCADA / DATA CENTER etc Required


6.00 LIST OF COMPARTIMENTS
6.01 Switchgear Electrical Room Required
6.02 Electrical Room SCADA ICCP Required
6.03 Batery storage Required
6.04 Fire System Required
6.05 Dry type auxiliary service transformer Required
6.06 Communication and RTU boards Required
6.07 Data Center Board 1000x1000x2000 (2 Unts) Required
6.08 Protection and measuring board Line 220kV (1 Unts) Required
6.09 Protection and measurement board Transformer 220kV (1 Unts) Required
6.10 Protection boards Capacitors Bank (5 Unts) Required
6.11 Mimico board measuring and controlling cells 220 / 22.9kV Required
6.12 Control center for electrical system operations Required
7.00 FURNITURE
7.01 Operations Console Required
7.02 Chairs Required
7.03 Rack for monitors I see Wall Required
8.00 DRAWINGS
8.01 Layout Required
8.02 Typical cut, equipment and environments layout Required
8.03 Front view of mimic board measuring and controlling cells 220 / 22.9kV Required
9.00 NETWORK COMUNICATION
Required / 2 Lawer
9.01 Switch
9.02 Model By vendor
9.03 Manufacturer RUGGEDCOM
9.04 Protocol IEC 61850
Single mode 8 chanels,
9.05 Network Ports
conectors SC
According to IED´s Meters, relay
9.06 Network Ports
and controlers
10.00 ELECTRICAL SYSTEM SWITCHGEAR GIS 22.9kV
10.01 ELECTRICAL SYSTEM
10.02 Rated Operating Voltage kV 22.9
10.03 Maximum Operating Voltage kV 24
10.04 Frecuency Hz 60
10.05 Grounding
10.06 Phase 3
10.07 Insulation
10.08 BIL site conditions (AIS) 125
Short-time withstand voltage at industrial frequency, at site conditions
10.09 kV pico 50
(For GIS equipment)
10.10 Short circuit Capacity 31.5
10.11 Delay Short circuit kA 1
10.12 Minimum leak distance specified Seg 54
10.13 Phase Tag mm/kV R,S, T
10.14 AUXILIARY SERVICES SYSTEM CHARACTERISTICS
10.15 AUXILIARY SERVICES
10.16 DC Voltage
10.17 Rated Operating Voltage VDC 125
10.18 Voltage variation % +/-5
10.19 SWITCHGEAR (INCOMING 4000 A)
10.20 DESIGN AND CONSTRUCTION SWITCHGEAR GIS 22.9 kV
10.21 Type Metalclad
10.22 Quantity 1
10.23 Degree of Power Protection IP 65
10.24 Degree of Protection Control IP 52

Page 4 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
10.25 Seismicity Class Zona 4
10.26 Insulation Medium SF6
10.27 Maintenance Free Si
10.28 Rated Voltage kV 22.9
10.29 Nominal Current A 4000
10.30 Short circuit Capacity kA 31.5
10.31 No gas filling in the field Required
10.32 Voltage detector Capacitive
10.33 Gas Pressure Controller Required
10.20 DESCRIPTIÓN
10.21 Rated short-time rated voltage
10.22 Phase / Ground, open contact distance kV 50
10.23 Through the separation distance kV 60
10.24 Rated impulse withstand voltage
10.25 Phase / Ground, open contact distance kV 125
10.26 Through the separation distance kV 145
10.27 Operation mode Local and remote
10.28 Plug-in bars for the interconnection of cells Required
10.29 Wraparound material inox steel
10.30 Internal arc proof rating IAC 1sec. By Vendor
10.31 IAC 1seg. kA 31.5
10.32 Installed toroidal voltage and current transformers Required
10.33 Protection System, supervision and control Required, Box BT
10.34 Measuring system Required
10.21 interlock Door when the unit is energized Required
10.22 Switch three positions local off remote Required
10.23 Cables way Required
10.24 Entrada de Cables Frontal Inferior
10.25 Ductos para salida de gases y/o de presiones internas afuera de By Vendor
10.26 de la caseta del Switchgear By Vendor
10.27 Location of pipelines of the pressure relief system of cells By Vendor
10.28 GIS By Vendor
10.29 Dimentions WxHxD mm. By Vendor
10.30 Color RAL 9003
10.31 TOTAL DIMENSION SWITCHGEAR 22,9 Kv
10.32 Max Depth mm. By Vendor
10.33 Maximum height mm. By Vendor
10.34 Total width mm. By Vendor
10.35 SURGE ARRESTERS 24kV Not required
10.36 Type
10.37 Fabrication Norm and Tests
10.38 Energy Absorption Capacity
10.39 Rated Voltage kV
10.40 Maximum continuous operating voltage MCOV kV
10.41 Impulse holding voltage 1.2us / 50 us BIL
10.42 Insulator material
10.43 Nominal discharge current kA
10.44 MAIN BUS Required
10.45 Bus
10.46 4000 A A Yes, 4000
10.47 Material
10.48 Copper-Silver Alloy Cu Required
10.49 Cross section Circular Bus
10.50 Insulation bar By Vendor
10.51 Protection Degree IP68
10.52 Grouding Bar (Minimum) mm 50x6
10.53 INCOMING 4000A - 22.9 kV
10.54 POTENCIAL TRANSFORMER (PT)
10.55 Type Inductive
10.56 Model By Vendor
10.57 Aplication Protection and Measurement
10.58 Frecuency Hz 60
10.59 Primary Voltage VAC 22900/√3 (Conetion Y)
10.60 Secondary Voltage 1 VAC 110/√3 (Conetión Y)
10.61 Secondary Voltage 2 VAC 110/3 (Conexión Delta Abierto)
10.62 BIL kV 125
10.63 Low Voltage Protection Required
10.64 Grouding Swicth Required
10.65 Class Precision 1 (Y-winding) 0.5
10.66 Class Precision 2 (Open Delta Connection Winding) 3P

Page 5 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
10.67 Mounting Inferior, out of tub SF6
10.68 POWER CIRCUIT BREAKER 4000 A
10.69 DESIGN AND CONSTRUCTION CIRCUIT BREAKER
10.70 Type By Vendor
10.71 Quantity 1
10.72 Model / Manufacture By Vendor
10.73 Protection grade IP 65
10.74 Type Vacio
10.75 Insulation Isolated on SF6
10.76 Material cube Stainless steel
10.77 Maintenance free Si
10.78 Rated Voltage kV 24
10.79 Rated current A 4000
10.80 Short circuit opening capacity 1sec. kA 31.5
10.81 Not gas filling in the field By Vendor
10.82 Relief Overpressure Required
10.83 Rated short-time rated voltage
10.84 industrial
10.85 Phase / Ground, open contact distance kV 50
10.86 Through the separation distance kV 60
10.87 Rated impulse withstand voltage
10.88 Phase / Ground, open contact distance kV 125
10.89 Through the separation distance kV 145
10.90 Control
10.91 Openig Winding VDC 125
10.92 Closing Winding VDC 125
10.93 Motor charger VDC 125
10.94 MAIN SWITCH AND EARTHSWITCH
10.95 Type Isolated on SF6
10.96 Model / Type By Vendor
10.97 Caracteristics kV 22.9 ± 5%
10.98 Rated Voltage kV 24
10.99 Bil kV 125
11.00 Support bracket for short duration to frequency kV 50
11.01 Industrial, 1 min.
11.02 Rated current of the equipment A 4000
11.03 Frecuency Hz 60
11.04 Breaking capacity by short circuit kA 31.5
11.05 Spring mechanism located outside SF6 filled tub Required
11.06 Manual Mechanism for Sectional and Grouding Required
11.07 Spare auxiliary contacts 14 Polos
11.08 Opening and closing by motorized control r
11.09 Operating Engine Consumption W 200
11.10 Digital display of the 3-position disconnector By Vendor
11.11 Control
11.12 Openig Winding VDC 125
11.13 Closing Winding VDC 125
11.14 Motor charger VDC 125
11.15 CURRENT TRANSFORMER (CT) 2 WINDINGS
11.16 Type Toroidal
11.17 Model CMA 248/78 CA
11.18 Aplication Protection and Measurement
11.19 Frecuency Hz 60
11.20 Rated short-time AC voltage Kv kV 3Kv
11.21 Manufacturing standards IEC 60044-1
11.22 Certification IEC
11.23 Location Out of the SF6 tank
11.24 Secondary connection via test terminals Confirmed
11.25 Maximum permissible temperature °C 60
11.26 Permanent Overcurrent Factor 1.2 Ir
11.27 Secondary winding (Protection and measurement)
11.28 Ratio A 4000-1000 / 5-5
11.29 Class measurement accuracy 0,5
11.30 Class of precision protection 5P10
11.31 Power consumption VA 10
11.32 Overcurrent protection factor 10
11.33 Short-term thermal current kA 40
11.34 Short-term thermal current time s 3
11.35 CURRENT TRANSFORMER (CT) HOMOPOLAR Not required
11.36 Type

Page 6 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
11.37 Model
11.38 Aplication
11.39 Frecuency
11.40 Rated short-time AC voltage Kv
11.41 Manufacturing standards
11.42 Certification
11.43 Location
11.44 Secondary connection via test terminals
11.45 Maximum permissible temperature
11.46 Permanent Overcurrent Factor
11.47 Secondary winding (Protection and measurement)
11.48 Ratio VA
11.49 Class measurement accuracy
11.50 Class of precision protection
11.51 Overcurrent protection factor
11.52 Short-term thermal current
11.53 Short-term thermal current time
11.54 SECONDARY COMPONENTS
11.55 Imput Cable Grids and clamps
11.56 Number of plug by phase By Vendor
11.57 Protection voltage secondary circuit Required
11.58 Type Capacitive with Display / IVIS
11.59 Heater and thermostat Required
11.60 Lighting Required
11.61 Test terminals for voltage and current Required ESSAILEC CC-D-VA
11.62 ARC FLASH SYSTEM Not required
11.63 Type
11.64 Model
11.65 Version
11.66 Manufacturer
11.67 Number of sensors
11.68 Assembly / Use
11.69 RELAY PROTECTION
11.70 Type Microprocesador
11.71 Model GE-F60-XXXX-XXXXX
11.72 Version By Vendor
11.73 Manufacturer GE-MULTILINK
11.74 Power Supply VDC 125
11.75 Power supply variation % +/-12
11.76 consumption W 34.1
11.77 Quantity 1
11.78 Assembly / Use Built-in
11.79 Communication protocol IEC 61850
11.80 Number of communication ports 1
11.81 Number of voltage and current input signals 1
11.82 Voltage of input signals (Tension) VAC 50-130
11.83 Number of entries type Rele 30
11.84 Number of programmable output contacts 6
11.85 Software and relay configuration Si
11.86 METER
11.87 Type Microprocessor
11.88 Model ION 7650
11.89 Version By Vendor
11.90 Manufacturer Schneider Electric
11.91 Supplier Tensión VDC 125
11.92 Permissible supply voltage variation % +/-10
11.93 Precision Class 0.2
11.94 Consumption W By Vendor
11.95 Quantity By Vendor
11.96 Assembly / Use Built-in
11.97 Measurement and Energy Analysis Functions Note 2
11.98 Communication protocol Modbus TCP/IP
11.99 Number of communication ports 1
12.00 Number of voltage and current input signals 3
12.01 Voltage of input signals (Tension) VAC 50-130
12.02 Number of entries 3
12.03 Number of programmable output contacts 3
13.00 SWITCHGEAR (FEEDERS 1200 A) GIS 22.9 kV
13.01 DESIGN AND CONSTRUCTION SWITCHGEAR GIS 22.9 kV

Page 7 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
13.02 Type Metalclad
13.03 Quantity 16
13.04 Degree of Power Protection IP 65
13.05 Degree of Protection Control IP 52
13.06 Seismicity Class Zone 3 - Z=0,4 (RNE / E-030)
13.07 Insulation Medium SF6
13.08 Maintenance Free YES
13.09 Rated Voltage kV 24
13.10 Nominal Current A 1200
13.11 Short circuit Capacity kA 31.5
13.12 No gas filling in the field Required
13.13 Voltage detector Capacitive
13.14 Gas Pressure Controller Required
13.15 DESCRIPTIÓN
13.16 Rated short-time rated voltage
13.17 Phase / Ground, open contact distance kV 50
13.18 Through the separation distance kV 60
13.19 Rated impulse withstand voltage
13.20 Phase / Ground, open contact distance kV 125
13.21 Through the separation distance kV 145
13.22 Operation mode Local and remote
13.23 Plug-in bars for the interconnection of cells Required
13.24 Wraparound material Inox Steel
13.25 Internal arc proof rating IAC 1sec. By Vendor
13.26 IAC 1seg. kA 31.5
13.27 Installed toroidal voltage and current transformers Required
13.28 Protection System, supervision and control Required, Box BT
13.29 Measuring system Required
13.30 interlock Door when the unit is energized Required
13.31 Switch three positions local off remote Required
13.32 Cables way Required
13.33 Entrada de Cables Frontal Inferior
13.34 Ductos para salida de gases y/o de presiones internas afuera de By Vendor
13.35 de la caseta del Switchgear By Vendor
13.36 Location of pipelines of the pressure relief system of cells By Vendor
13.37 GIS By Vendor
13.38 Dimentions WxHxD mm. By Vendor
13.39 Color RAL 9003
13.4 SURGE ARRESTERS 24kV Not required
13.41 Type
13.42 Fabrication Norm and Tests
13.43 Energy Absorption Capacity
13.44 Rated Voltage kV
13.45 Maximum continuous operating voltage MCOV kV
13.46 Impulse holding voltage 1.2us / 50 us BIL
13.47 Insulator material
13.48 Nominal discharge current kA
13.49 MAIN BUS Required
13.50 Bus
13.51 4000 A A Yes, 4000
13.52 Material
13.53 Copper-Silver Alloy Cu Required
13.54 Cross section Circular Bus
13.55 Insulation bar By Vendor
13.56 Protection Degree IP68
13.57 Grouding Bar (Minimum) mm 50x6
13.58 CIRCUIT BREAKER
13.59 DESIGN AND CONSTRUCTION CIRCUIT BREAKER GIS 22.9 kV
13.60 Model / Manufacture By Vendor
13.61 Protection grade IP 65
13.62 Type Vacio
13.63 Insulation Isolated on SF6
13.64 Material cube Stainless steel
13.65 Maintenance free Required
13.66 Rated Voltage kV 24
13.67 Rated current A 1200

Page 8 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
13.68 Short circuit opening capacity 1sec. kA 31.5
13.69 Not gas filling in the field By Vendor
13.70 Relief Overpressure Required
13.71 Rated short-time rated voltage
13.72 industrial
13.73 Phase / Ground, open contact distance kV 50
13.74 Through the separation distance kV 60
13.75 Rated impulse withstand voltage
13.76 Phase / Ground, open contact distance kV 125
13.77 Through the separation distance kV 145
13.78 Control
13.79 Openig Winding VDC 125
13.80 Closing Winding VDC 125
13.81 Motor charger VDC 125
13.82 MAIN SWITCH AND EARTHSWITCH
13.83 Type Isolated on SF6
13.84 Model / Type By Vendor
13.85 Caracteristics kV 22.9 ± 5%
13.86 Rated Voltage kV 24
13.87 Bil kV 125
13.88 Support bracket for short duration to frequency kV 50
13.89 Industrial, 1 min.
13.90 Rated current of the equipment A 1200
13.91 Frecuency Hz 60
13.92 Breaking capacity by short circuit kA 31.5
13.93 Spring mechanism located outside SF6 filled tub Required
13.94 Manual Mechanism for Sectional and Grouding Required
13.95 Spare auxiliary contacts 14 Contact
13.96 Opening and closing by motorized control Required
13.97 Operating Engine Consumption W 200
13.98 Digital display of the 3-position disconnector Required
13.99 Control
14.00 Openig Winding VDC 125
14.01 Closing Winding VDC 125
14.02 Motor charger VDC 125
14.03 CURRENT TRANSFORMER (CT) 2 WINDINGS
14.04 Type Toroidal
14.05 Model By Vendor
14.06 Aplication Protection and Measurement
14.07 Frecuency Hz 60
14.08 Rated short-time AC voltage Kv kV By Vendor
14.09 Manufacturing standards IEC 60044-1
14.10 Certification IEC
14.11 Location Out of the SF6 tank
14.12 Secondary connection via test terminals Required
14.13 Maximum permissible temperature °C 60
14.14 Permanent Overcurrent Factor 1.2 Ir
14.15 Secondary winding (Protection and measurement)
14.16 Ratio A 1200 - 600-300 / 5-5
14.17 Class measurement accuracy 0,5
14.18 Class of precision protection 5P10
14.19 Power consumption VA 10
14.20 Overcurrent protection factor 10
14.21 Short-term thermal current kA 40
14.22 Short-term thermal current time s 3
14.23 CURRENT TRANSFORMER (CT) HOMOPOLAR Not Required
14.24 Type
14.25 Model
14.26 Aplication
14.27 Frecuency
14.28 Rated short-time AC voltage Kv
14.29 Manufacturing standards
14.30 Certification
14.31 Location
14.32 Secondary connection via test terminals
14.33 Maximum permissible temperature

Page 9 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
14.34 Permanent Overcurrent Factor
14.35 Secondary winding (Protection and measurement)
14.36 Ratio VA
14.37 Class measurement accuracy
14.38 Class of precision protection
14.39 Overcurrent protection factor
14.40 Short-term thermal current
14.41 Short-term thermal current time
14.42 TRANSFORMADOR DE TENSIÓN (PT)
14.43 Type Inductive
14.44 Quantity 2 Untits, See Drawing Single Line
14.45 Model By Vendor
14.46 Aplication Protection and Meter
14.47 Frecuency 60
14.48 Primary Voltage 22900/√3 (Conexión Y)
14.49 Secondary Voltage 1 110/√3 (Conexión Y)
14.50 Secondary Voltage 2 110/3 (Open Delta Conexión )
14.51 BIL 125
14.52 Low Voltage Protection Required
14.53 Grouding Swicth Required
14.54 Class Precision 1 (Y-winding) 0.5
14.55 Class Precision 2 (Open Delta Connection Winding) 3P
14.56 Mounting Within, out cuba SF6
14.57 Version By Vendor
14.58 Manufacturer By Vendor
14.59 Number of sensors By Vendor
14.60 Assembly / Use
14.61 RELAY PROTECTION
14.62 Type Microprocesador
14.63 Model GE-F60-XXXX-XXXXX
14.64 Version By Vendor
14.65 Manufacturer GE-MULTILINK
14.66 Power Supply VDC 125
14.67 Power supply variation % +/-12
14.68 consumption W 34.1
14.69 Quantity 1
14.70 Assembly / Use Built-in
14.71 Funciones de protección IEC 61850
14.72 Communication protocol 1
14.73 Number of communication ports 50-130
14.74 Number of voltage and current input signals 30
14.75 Voltage of input signals (Tension) VAC 6
14.76 Number of entries type Rele Si
14.77 Number of programmable output contacts 6
14.78 Software and relay configuration Required
14.79 METER
14.80 Type Microprocesador
14.81 Model PM8000
14.82 Version PM8240
14.83 Manufacturer Schneider Electric
14.84 Supplier Tensión VDC 125
14.85 Permissible supply voltage variation % +/-10
14.86 Precision Class 0.2
14.87 Consumption W 17
14.88 Quantity 1
14.89 Assembly / Use Interior empotrado
14.90 Measurement and Energy Analysis Functions By Vendor
14.91 Communication protocol Modbus TCP/IP
14.92 Number of communication ports 1
14.93 Number of voltage and current input signals 3
14.94 Voltage of input signals (Tension) VAC 50-130
14.95 Number of entries
14.96 Number of programmable output contacts
15.00 SWITCHGEAR GIS 22.9 Kv FOR POWER CAPACITOR 1200 A
15.01 DESIGN AND CONSTRUCTION SWITCHGEAR GIS 22.9 kV
15.02 Type Metalclad

Page 10 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
15.03 Sync closing power circuit breaker Required
15.04 Quantity 5
15.05 Degree of Power Protection IP 65
15.06 Degree of Protection Control IP 52
15.07 Seismicity Class Zone 3 - Z=0,4 (RNE / E-030)
15.08 Insulation Medium SF6
15.09 Maintenance Free YES
15.10 Rated Voltage kV 24
15.11 Nominal Current A 1200
15.12 Short circuit Capacity kA 31.5
15.13 No gas filling in the field Required
15.14 Voltage detector Capacitive
15.15 Gas Pressure Controller Required
15.16 DESCRIPTIÓN
15.17 Rated short-time rated voltage
15.18 Phase / Ground, open contact distance kV 50
15.19 Through the separation distance kV 60
15.20 Rated impulse withstand voltage
15.21 Phase / Ground, open contact distance kV 125
15.22 Through the separation distance kV 145
15.23 Operation mode Local and remote
15.24 Plug-in bars for the interconnection of cells Required
15.25 Wraparound material Inox Steel
15.26 Internal arc proof rating IAC 1sec. By Vendor
15.27 IAC 1seg. kA 31.5
15.28 Installed toroidal voltage and current transformers Required
15.29 Protection System, supervision and control Required, Box BT
15.30 Measuring system Required
15.31 interlock Door when the unit is energized Required
15.32 Switch three positions local off remote Required
15.33 Cables way Required
15.34 Entrada de Cables Frontal Inferior
15.35 Ductos para salida de gases y/o de presiones internas afuera de By Vendor
15.36 de la caseta del Switchgear By Vendor
15.37 Location of pipelines of the pressure relief system of cells By Vendor
15.38 GIS By Vendor
15.39 Dimentions WxHxD mm. By Vendor
15.40 Color RAL 9003
15.41 DIMENSION TOTAL DE SWITCHGEAR 22,9 Kv, SE PRINCIPAL
15.42 Max Depth By Vendor
15.43 Maximum height By Vendor
15.44 Total width By Vendor
15.45 SURGE ARRESTERS 24kV Not required
15.46 Type
15.47 Fabrication Norm and Tests
15.48 Energy Absorption Capacity
15.49 Rated Voltage kV
15.50 Maximum continuous operating voltage MCOV kV
15.51 Impulse holding voltage 1.2us / 50 us BIL
15.52 Insulator material
15.53 Nominal discharge current kA
15.54 MAIN BUS Required
15.55 Bus
15.56 4000 A A Yes, 4000
15.57 Material
15.58 Copper-Silver Alloy Cu Required
15.59 Cross section Circular Bus
15.60 Insulation bar By Vendor
15.61 Protection Degree IP68
15.62 Grouding Bar (Minimum) mm 50x6
15.63 CIRCUIT BREAKER
15.64 DESIGN AND CONSTRUCTION CIRCUIT BREAKER GIS 22.9 kV
15.65 Model / Manufacture By Vendor
15.66 Protection grade IP 65
15.67 Type Vacio
15.68 Insulation Isolated on SF6

Page 11 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
15.69 Material cube Stainless steel
15.70 Maintenance free Required
15.71 Rated Voltage kV 24
15.72 Rated current A 1200
15.73 Short circuit opening capacity 1sec. kA 31.5
15.74 Not gas filling in the field By Vendor
15.75 Relief Overpressure Required
15.76 Rated short-time rated voltage
15.77 industrial
15.78 Phase / Ground, open contact distance kV 50
15.79 Through the separation distance kV 60
15.80 Rated impulse withstand voltage
15.81 Phase / Ground, open contact distance kV 125
15.82 Through the separation distance kV 145
15.83 Control
15.84 Openig Winding VDC 125
15.85 Closing Winding VDC 125
15.86 Motor charger VDC 125
15.87 MAIN SWITCH AND EARTHSWITCH
15.88 Type Isolated on SF6
15.89 Model / Type By Vendor
15.90 Caracteristics kV 22.9 ± 5%
15.91 Rated Voltage kV 24
15.92 Bil kV 125
15.93 Support bracket for short duration to frequency kV 50
15.94 Industrial, 1 min.
15.95 Rated current of the equipment A 1200
15.96 Frecuency Hz 60
15.97 Breaking capacity by short circuit kA 31.5
15.98 Spring mechanism located outside SF6 filled tub Required
15.99 Manual Mechanism for Sectional and Grouding Required
16.00 Spare auxiliary contacts 14 Contact
16.01 Opening and closing by motorized control Required
16.02 Operating Engine Consumption W 200
16.03 Digital display of the 3-position disconnector Required
16.04 Control
16.05 Openig Winding VDC 125
16.06 Closing Winding VDC 125
16.07 Motor charger VDC 125
16.08 CURRENT TRANSFORMER (CT) 2 WINDINGS
16.09 Type Toroidal
16.10 Model By Vendor
16.11 Aplication Protection and Measurement
16.12 Frecuency Hz 60
16.13 Rated short-time AC voltage Kv kV By Vendor
16.14 Manufacturing standards IEC 60044-1
16.15 Certification IEC
16.16 Location Out of the SF6 tank
16.17 Secondary connection via test terminals Required
16.18 Maximum permissible temperature °C 60
16.19 Permanent Overcurrent Factor 1.2 Ir
16.20 Secondary winding (Protection and measurement)
16.21 Ratio A 1200 - 600-300 / 5-5
16.22 Class measurement accuracy 0,5
16.23 Class of precision protection 5P10
16.24 Power consumption VA 10
16.25 Overcurrent protection factor 10
16.26 Short-term thermal current kA 40
16.27 Short-term thermal current time s 3
16.28 CURRENT TRANSFORMER (CT) HOMOPOLAR Not Required
16.29 Type
16.30 Model
16.31 Aplication
16.32 Frecuency
16.33 Rated short-time AC voltage Kv
16.34 Manufacturing standards

Page 12 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
16.35 Certification
16.36 Location
16.37 Secondary connection via test terminals
16.38 Maximum permissible temperature
16.39 Permanent Overcurrent Factor
16.40 Secondary winding (Protection and measurement)
16.41 Ratio VA
16.42 Class measurement accuracy
16.43 Class of precision protection
16.44 Overcurrent protection factor
16.45 Short-term thermal current
16.46 Short-term thermal current time
16.47 TRANSFORMADOR DE TENSIÓN (PT)
16.48 Type Inductive
16.49 Quantity 2 Untits, See Drawing Single Line
16.50 Model By Vendor
16.51 Aplication Protection and Meter
16.52 Frecuency 60
16.53 Primary Voltage 22900/√3 (Conexión Y)
16.54 Secondary Voltage 1 110/√3 (Conexión Y)
16.55 Secondary Voltage 2 110/3 (Open Delta Conexión )
16.56 BIL 125
16.57 Low Voltage Protection Required
16.58 Grouding Swicth Required
16.59 Class Precision 1 (Y-winding) 0.5
16.60 Class Precision 2 (Open Delta Connection Winding) 3P
16.61 Mounting Within, out cuba SF6
16.62 Version By Vendor
16.63 Manufacturer By Vendor
16.64 Number of sensors By Vendor
16.65 Assembly / Use
16.66 RELAY PROTECTION
16.67 Type Microprocesador
16.68 Model GE-F60-XXXX-XXXXX
16.69 Version By Vendor
16.70 Manufacturer GE-MULTILINK
16.71 Power Supply VDC 125
16.72 Power supply variation % +/-12
16.73 consumption W 34.1
16.74 Quantity 1
16.75 Assembly / Use Built-in
16.76 Funciones de protección IEC 61850
16.77 Communication protocol 1
16.78 Number of communication ports 50-130
16.79 Number of voltage and current input signals 30
16.80 Voltage of input signals (Tension) VAC 6
16.81 Number of entries type Rele Si
16.82 Number of programmable output contacts 6
16.83 Software and relay configuration Required
16.84 METER
16.85 Type Microprocesador
16.86 Model PM8000
16.87 Version PM8240
16.88 Manufacturer Schneider Electric
16.89 Supplier Tensión VDC 125
16.90 Permissible supply voltage variation % +/-10
16.91 Precision Class 0.2
16.92 Consumption W 17
16.93 Quantity 1
16.94 Assembly / Use Interior empotrado
16.95 Measurement and Energy Analysis Functions By Vendor
16.96 Communication protocol Modbus TCP/IP
16.97 Number of communication ports 1
16.98 Number of voltage and current input signals 3
16.99 Voltage of input signals (Tension) VAC 50-130
17.00 Number of entries

Page 13 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
17.01 Number of programmable output contacts
18.00 BATTERY CHARGER
18.01 Manufacturer By Vendor
18.02 Quantity 2
18.03 Model / Catalog N° By Vendor
18.04 Type SCR
18.05 Enclosure Nema 12
18.06 Mounting Floor
18.07 Float Voltage (adjustable) V/cell 2.33
18.08 Equalize Voltage (adjustable) V/cell 2.33
18.09 Recharge time (maximum) 8 hours
18.10 Nominal DC Output Current Rating By Vendor
18.11 Maximum ripple 100 mV rms
18.12 Audible noise (maximum) 65 dB at 1.5 m
18.13 Measurement, Protection relays, Control, Alarms and Lights
18.14 Output Voltmeter Required
18.15 Output Ammeter Required
18.16 Low DC Voltage Relay Required
18.17 High DC Voltage Relay Required
18.18 DC Surge Protection Required
18.19 DC Output Circuit Breaker Required
18.20 Electronic short circuit and Overload protection Required
18.21 Manufacturer's multifunction standard control/display Unit Acceptable
18.22 Alarms (minimum)
18.23 AC Failure Required
18.24 DC Failure Required
18.25 High VDC Required
18.26 Low VDC Required
18.27 Ground Detection Required
18.28 Overload Required
18.29 High or Equalize ON Pilot Light Required
18.30 BATTERY SUPPORT
18.31 Type Rack
18.32 Mounting Back to Wall
18.33 Tier Two or Three / By Vendor
18.34 Finish Color ANSI 61
18.35 Dimensions and Weight
18.36 Width (mm) By Vendor
18.37 Height (mm) By Vendor
18.38 Depth (mm) By Vendor
18.39 Weight (kg) By Vendor
18.40 BATTERY BANK
18.41 Type Sealed Maintenance Free
7.1.3H.09 Quantity 1
18.42 Application Switchgear Control Power
18.43 Manufacturer By Vendor
18.44 Model / Catalog N° By Vendor
18.45 Cell Container By Vendor
18.46 Time life 15 years
18.47 Nominal Voltage VDC 125
18.48 Maximum Voltage VDC 140

Page 14 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
18.49 Minimum Voltage VDC 105
18.50 Equalize Voltage (Volt Per Cell) 2.37
18.51 Flotation Voltage (Volt Per Cell) 2.25
18.52 End-of Discharge Cell Voltage (Volt Per Cell) 1.75
18.53 Minimum Amper-hour Rating Calculated 300
18.54 Amper hour Capacity at 8 hr rate o discharge to 1.75 Volts per Cell By Vendor
18.55 Battery constant-current discharge Table, in A (@25°C) By Vendor
19.00 DRY TYPE TRANSFORMER (Auxiliary Services)
19.01 General
19.02 Manufacturer By Vendor
19.03 Place of Manufacture By Vendor
19.04 Type High Efficiency Dry type
19.05 Installation Type Indoor Floor Mounted
19.06 Enclosure NEMA 12
19.07 Rated Ambient Temperature (Maximum) By Vendor
19.08 Rated Ambient Temperature (Minimum) By Vendor
19.09 Rated Ambient Temperature (24 hrs mean Max) By Vendor
19.10 Height above sea level 1000 masl
19.11 Cooling By Vendor
19.12 Connection Dyn 11
19.11 Technical Data
19.12 Rated Power kVA 300
19.13 Primary - no load voltage kV 22.9
19.14 Secondary
Secondary
- no- load
no load
voltage
voltage 0.4 - 0.23
19.15 Number of Phases 3
19.16 Frequency Hz 60
19.17 Impedance at 167°F 0.04
19.18 HV- Phases By Vendor
19.19 LV- Phases By Vendor
19.20 Windings By Vendor
19.21 Tapchanging - Off Circuit/On Line By Vendor
19.22 Number of positions By Vendor
19.23 Voltage Rating kV By Vendor
19.24 No Load Primary Current A By Vendor
19.25 Magnetizing Inrush Current A By Vendor
19.26 Excitation Current at 100% Rated Volt % By Vendor
19.27 Excitation Current at 110% Rated Volt % By Vendor
19.28 Temperature Rises ⁰C By Vendor
19.29 Rating: kVA By Vendor
19.30 Secondary Lightning Arrester Class (kV) By Vendor
19.31 self air cooled ANN MCOV (kV) By Vendor
19.32 Regulation: % By Vendor
19.33 PF = 0.8 lagging % By Vendor
19.34 Efficiencies at: 125% full load % By Vendor
19.35 100% full load % By Vendor
19.36 75% full load % By Vendor
19.37 50% full load % By Vendor
19.38 25% full load % By Vendor
19.39 Load Losses at Full Load kW By Vendor
19.40 No Load Losses kW By Vendor

Page 15 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4713-SS-400
EQUIPMENT NAME Main Electrical Control Room
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
19.41 Resistance Per Phase @ 75°C For Each Winding OHMS By Vendor
19.42 Impedance Voltage (IZ) - Off-load Taps (@ 3 MVA) By Vendor
19.43 at centre tap % By Vendor
19.44 X/R Ratio (@base MVA): By Vendor
19.45 Impedance Voltage (IZ) guaranteed maximum deviation %± By Vendor
20.00 NOTES
20.01 BE CAREFULL WHEN EDITING DATA SHEETS. INSERT ONLY NECESSARY ADDITIONAL DETAILS FOR DATA AND PLACE THE REVISION CODE AT THE RIGHT MOST BOX

Page 16 of 50
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4371-SS-401
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
SUPPLIER/CONTRACTOR: By vendor
PLANT AREA: 4371
MODEL No. / DESIGNATION By vendor
1.00 SITE CONDITIONS
1.01 Altitude 825 msnm
1.02 Ambient temperature max °C 30
1.03 Ambient temperature min °C 8.4

1.04 Seismic Conditions Peruvian Seismic Code Standard E.030

1.05 Average annual precipitation mm 27.1


1.06 Minimum annual precipitation mm 13.7
1.07 maximum annual precipitation mm 50.5
1.08 Maximum wind speed km/h 90
2.00 STRUCTURAL REQUIREMENTS
2.01 General
2.02 Type of Substation Skid Mounted
2.03 Maximum dimension of skid mounted substation lxbxh (m) By vendor
2.04 Skid platform elevation from grade m By vendor
2.05 Maximum weight of skid mounted substation kg By vendor

2.06 Transformer mounted outdoor on the skid Required

2.07 Electrical room mounted on the skid Required

2.08 Separate Outdoor enclosure for equipment on skid By vendor

2.09 Enclusure protection of electrical room NEMA 4

2.10 Design life of the mobile substation 20 Years

2.11 BASE

2.12 Base Structural Steel Material ASTM A36 rigid H or I or U-Beam

2.13 Runners in each base structure Required

2.14 Minimum thickness of deck plates mm By vendor


2.15 Deck Loading kg / m2 By vendor
2.16 Minimum removable Lifting Lugs / Eyes per substation skid 4

2.17 Skid with E-Room and equipment designed for lifting, towing, skidding, andjacking Required

2.18 Design Safety factor for lifting, towing and skidding facilities 5

2.19 Pulling eyes for towing and skidding Required

2.20 External Finishing Color RAL 1015 (Beige)


2.21 E-ROOM FLOOR

2.22 Material Steel Plate

2.23 Material Minimum Thickness mm By vendor

2.24 Top Surface Coating Non-slip, anti-skid

2.25 E-ROOM WALLS


2.26 Wall Panels Seams Continuously Welded
2.27 External Walls Material Cold Rolled Steel Sheets
2.28 External Walls Material Minimum Thickness mm 1.9
2.29 External Finishing Color RAL 1015 (Beige)
2.30 Internal Walls Material Cold Rolled Steel Sheets
2.31 Internal Walls Material Minimum Thickness mm 1.5
2.32 Internal Finishing Color RAL 9001 (Off White)
2.33 Penetrations By vendor
2.34 Final Thickness of Walls mm By vendor
2.35 E-ROOM ROOF

Page 17 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4371-SS-401
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
Cold Rolled Steel Sheets
2.36 External Roof Cover Material

2.37 External Roof Cover Material Minimum Thickness mm 1.9


2.38 External Roof Cover Panel Seams Continuously Welded
2.39 External Roof Finishing Color RAL 1015 (Beige)
2.40 Slope Downward from middle to side 85 mm per meter
2.41 Sloped housing roof providing full drainage Required
2.42 Internal Ceiling Cover Material Cold Rolled Steel Sheets
2.43 Internal Ceiling Cover Material Minimum Thickness mm 1.5
2.44 Internal Ceiling Finishing Color RAL 9001 (Off White)
2.45 Final Maximum Thickness of Roof @ center Ridge mm By vendor
2.46 Roof Average Design Loading kg / m2 250
2.47 Roof Concentrated Design Loading kg / m2 125
2.48 E-ROOM DOORS
2.49 Material Seamless steel sheets
2.50 Equipment Door Size Height / Width mm By vendor
2.51 Personnel access doors size Height / Width mm 2200/1000
2.52 Stainless steel panic exit hardware w/ quick release latch mechanism to permit Required
2.53 Door locks Required
2.54 Automatic closures Required
2.55 Kick plates Required
2.56 Rain canopy Required
2.57 Doors removable for entering or removing equipments Required
2.58 Door with non-combustible R11 insulation & F60 1-hr fire resistance Required
2.59 Door finishing color (exterior) RAL 5010 (Blue)
2.60 Door finishing color (interior) RAL 9001 (Off White)
2.61 Final Thickness of Doors mm By vendor

3.00 OUTDOOR SECONDARY SECTION WALK-IN ENCLOSURE

3.01 Manufacturer By vendor


3.02 Enclosure Nema 4
3.03 Minimum working space mm By vendor
3.04 Lighting
3.05 Lighting type Industrial Fluorescent
3.06 Lighting intensity Lux 550
3.07 Lighting Panel Required
3.08 Lighting Panel Main feeder 220 V, 60 Hz, 1Ф (By buyer)
4.00 ELECTRICAL EQUIPMENT
4.01 PRIMARY POWER SYSTEM
4.02 Rated Voltage kV 22.9
4.03 Voltage variation % ± 10
4.04 Phase 3
4.05 Frequency Hz 60
4.06 Frequency variation % ±1%
4.07 Short circuit Capacity kA 25
4.08 SECONDARY POWER SYSTEM
4.09 Rated Voltage kV 0.38-0.23
4.10 Phase 3
4.11 Frequency Hz 60
4.12 Short circuit Capacity HV 20 kA
4.13 22.9 kV METAL ENCLOSED MAIN INCOMING SWITCH
4.14 Manufacturer By vendor
4.15 Quantity 1

Page 18 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4371-SS-401
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
4.15 Model / Catalog N° By vendor
4.16 Enclosure IEC
4.17 Type Metal Enclosed
4.18 Rated continuous current A 600
4.19 Maximum Symmetrical Interrupting Capability kA 25
4.20 Surge Protection manufacturer By vendor
4.21 Surge Protection Type Not Required
4.22 Surge Protection MCOV Not Required
Fuses Required
4.23 Switch General Characteristics
4.24 Manufacturer By vendor
Three poles, fixed, operated Without
4.25 Type
Load
4.26 Number trip coils 1
4.27 Padlocks Required
4.28 Auxiliary contacts 5 NO + 5 NC
4.29 Opening time (milliseconds) By vendor
4.30 BIL at sea level kV 125
4.31 Power frequency withstand at sea level By vendor
4.32 trip coils voltage 125 VDC (By buyer)
4.33 Heaters 220 VAC, 1 phase, 60 Hz (By buyer)
4.34 Cable Entrance Bottom
4.35 Cable Size 1 x (3/c N° 120mm + SHD)
4.36 Approximate overall dimension (WxDxH) mm By vendor
4.37 Approximate weight (kg) By vendor
5.00 TRANSFORMER SECTION
5.01 Manufacturer By vendor
5.02 Type PCB Free Mineral Oil liquid-filled
Standars IEC
5.03 Fluid Preservations Systems Sealed tank
5.04 Self cooled capacity (OA - 55° C) @ 1,000 m.a.s.l. (kVA) 2000
5.05 Self cooled capacity (OA - 65° C) @ 1,000 m.a.s.l. (kVA) Not Applicable
5.06 Force cooled capacity (FA - 55° C) @ 1,000 m.a.s.l. (kVA) Not Applicable
5.07 Force cooled capacity (FA - 65° C) @ 1,000 m.a.s.l. (kVA) Not Applicable
5.08 Transformer connection Dyn11
5.09 Primary Voltage (line to line) kV 22.9
5.10 Secondary Voltage (line to line) kV 0.4-0.23
5.11 Minimum Primary Bushings (three total) BIL kV 125
5.12 Minimum Primary Winding BIL kV By vendor
5.13 Minimum Secondary Bushings (four total) BIL kV By vendor
5.14 Minimum Secondary Winding BIL kV By vendor
5.15 Impedance on its self cooled capacity (OA - 55°C) 6.5
De-energized tap changer with padlock provision (Four full capacity 2 ½ percent taps, two
5.16 Required
above and two below rated voltage on the 22.9 kV winding)

5.17 Accessories
5.18 Magnetic liquid level gauge with alarm contacts Required
5.19 Oil dial type thermometer with alarm contacts Required
5.20 Winding thermometer (thermal image) with alarm contacts Required
5.21 Pressure vacuum gauge with trip and alarm contacts Required
5.22 Cover vent plug Required
5.23 Pressure test connection Required
5.24 Filling plug and filter press connection Required

Page 19 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4371-SS-401
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
5.25 Combination drain valve and bottom filter press connection Required
5.26 Sampling device Required
5.27 Diagrammatic name plate Required
5.28 Manhole or handhole in cover Required
5.29 Provision for lifting and jacking Required
5.30 Neutral resistor 100 A, 10 sec Required
5.31 Current transformer including with neutral resistor 50/5 A Required
5.32 Transformer Losses (Guaranteed)
5.33 Full Load (kW) By vendor
5.34 3/4 Full Load (kW) By vendor
5.35 1/2 Full Load (kW) By vendor
5.36 Transformer Efficiency (Guaranteed)
5.37 Full Load (%) By vendor
5.38 3/4 Full Load (%) By vendor
5.39 1/2 Full Load (%) By vendor
5.40 Approximate overall dimension (WxDxH) mm By vendor
5.41 Base Plate Dimensions and Anchors mm By vendor
5.42 Approximate weight with oil (kg) By vendor
5.43 Approximate weight without oil (kg) By vendor
5.44 TRANSFORMER TESTING
5.45 Normal tests (According to latest revision of IEC Standars)
5.46 Resistance measurements of all windings Required
5.47 Ratio tests Required
5.48 Polarity and phase relation test Required
5.49 No-load loss at rated voltage Required
5.50 Excitation current at rated voltage Required
5.51 Impedance and load loss Required
5.52 Applied potential test Required
5.53 Induced potential test Required
5.54 Mechanical leak test Required
5.55 Temperature test Not Required
5.56 Impulse test Not Required
5.57 Quality control impulse test Not Required
5.58 Front of wave impulse test Not Required
5.59 DGA FQ Analysis OIL Active Part Required
5.60 Frequency Response Analysis (FRA) in factory Not Required
5.61 Zero-phase sequence impedance test Not Required
5.62 Insulation resistance (megger) test Required
6.00 0.48 kV METAL CLAD SWITCHGEAR
6.01 INCOMING
6.02 Manufacturer By vendor
6.03 Model / Catalog N° By vendor
6.04 Enclosure Nema 12
6.05 Type Metal Clad
6.06 Main Bus Continuous Rating A 3,000
6.07 Quantity 1
6.08 Circuit Breaker General Characteristics
6.09 Manufacturer By vendor
6.10 Interrupter Type By vendor

Three poles, drawout, electrically


6.11 Circuit breaker Type
operated, stored energy operation

Page 20 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4371-SS-401
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
6.12 Protection LSIG
6.13 Number trip coils 1
6.14 Auxiliary contacts 5 NO + 5 NC
6.15 Interrupting time 5 cycles or less
6.16 Closing time (milliseconds) By vendor
6.17 Opening time (milliseconds) By vendor
6.18 Construction Rating Draw Out
6.19 BIL at sea level By vendor
6.20 Power frequency withstand at sea level By vendor
6.21 Close and trip coils voltage 125 VDC (By buyer)
6.22 Mechanism motors voltage 125 VDC (By buyer)
6.23 Control circuit breakers 125 VDC (By buyer)
6.24 Heaters 220 VAC, 1 phase, 60 Hz (By buyer)
6.25 Motor power consumption By vendor
6.26 Closing solenoid power consumption By vendor
6.27 Opening solenoid power consumption By vendor
6.28 Opening solenoid power consumption By vendor
6.29 Heaters consumption By vendor
6.30 METER
6.31 Type Microprocesador
6.32 Model PM8000
6.33 Version PM8240
6.34 Manufacturer Schneider Electric
6.35 Supplier Tensión VDC 125
6.36 Communication protocol Modbus TCP/IP
6.37 Number of communication ports 1
6.38 Phase Current transformer
6.39 Quantity 3
6.40 Manufacturer By vendor
6.41 Model / Catalog N° By vendor
6.42 Current ratio 3000:5
6.43 Class By vendor
6.44 Potential transformer
6.45 Quantity 1
6.46 Manufacturer By vendor
6.47 Model / Catalog N° By vendor
6.48 Voltage ratio 480/120 V
7.00 NETWORK COMUNICATION
Required / 2 Lawer
7.01 Switch
7.02 Model By vendor
7.03 Manufacturer RUGGEDCOM
7.04 Protocol IEC 61850

7.05 Network Ports Single mode 2 chanels

According to IED´s Meters, relay and


7.06 Network Ports
controlers
8.00 FEEDER CIRCUIT BREAKERS TERMOMAGNETICO
8.01 Voltage Kv 480
8.02 Quantity 10
8.03 Model / Catalog N° By vendor
8.04 Rated continuous current A 300
8.05 Phases 3
8.06 Protection Required Multiratio 0.5 -1
8.07 Cable Outgoing Bottom

Page 21 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4371-SS-401
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
8.08 Cable Size By vendor
8.09 Class By vendor
9.00 SPARES AND OPTIONAL ACCESSORIES
9.01 22.9 kV Spare Fuses / Quantity Required / 3
10.00 BATTERY CHARGER
10.01 Manufacturer By Vendor
10.02 Model / Catalog N° By Vendor
10.03 Type SCR
10.04 Enclosure Nema 12
10.05 Mounting Floor
10.06 Float Voltage (adjustable) V/cell 2.33
10.07 Equalize Voltage (adjustable) V/cell 2.33
10.08 Recharge time (maximum) 8 hours
10.09 Nominal DC Output Current Rating By Vendor
10.10 Maximum ripple 100 mV rms
10.11 Audible noise (maximum) 65 dB at 1.5 m
10.12 Measurement, Protection relays, Control, Alarms and Lights
10.13 Output Voltmeter Required
10.14 Output Ammeter Required
10.15 Low DC Voltage Relay Required
10.16 High DC Voltage Relay Required
10.17 DC Surge Protection Required
10.18 DC Output Circuit Breaker Required
10.19 Electronic short circuit and Overload protection Required
10.20 Manufacturer's multifunction standard control/display Unit Acceptable
10.21 Alarms (minimum)
10.22 AC Failure Required
10.23 DC Failure Required
10.24 High VDC Required
10.25 Low VDC Required
10.26 Ground Detection Required
10.27 Overload Required
10.28 High or Equalize ON Pilot Light Required
10.29 BATTERY SUPPORT
10.30 Type Rack
10.31 Mounting Back to Wall
10.32 Tier Two or Three / By Vendor
10.33 Finish Color ANSI 61
10.34 Dimensions and Weight
10.35 Width (mm) By Vendor
10.36 Height (mm) By Vendor
10.37 Depth (mm) By Vendor
10.38 Weight (kg) By Vendor
10.39 BATTERY BANK
10.40 Type Sealed Maintenance Free
10.41 Application Switchgear Control Power
10.42 Manufacturer By Vendor
10.43 Model / Catalog N° By Vendor
10.44 Cell Container By Vendor
10.45 Time life 5 years
10.46 Nominal Voltage VDC 125

Page 22 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4371-SS-401
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
10.47 Maximum Voltage VDC 140
10.48 Minimum Voltage VDC 105
10.49 Equalize Voltage (Volt Per Cell) 2.37
10.50 Flotation Voltage (Volt Per Cell) 2.25
10.51 End-of Discharge Cell Voltage (Volt Per Cell) 1.75
10.52 Minimum Amper-hour Rating Calculated By Vendor
10.53 Amper hour Capacity at 8 hr rate o discharge to 1.75 Volts per Cell By Vendor
10.54 Battery constant-current discharge Table, in A (@25°C) By Vendor
11.00 DRY TYPE TRANSFORMER (Auxiliary Services)
11.01 General
11.02 Manufacturer By Vendor
11.03 Place of Manufacture By Vendor
11.04 Type High Efficiency Dry type
11.05 Installation Type Indoor Floor Mounted
11.06 Enclosure NEMA 12
11.07 Rated Ambient Temperature (Maximum) By Vendor 62.75730495
11.08 Rated Ambient Temperature (Minimum) By Vendor
11.09 Rated Ambient Temperature (24 hrs mean Max) By Vendor
11.10 Height above sea level 1000 masl
11.11 Cooling By Vendor
11.12 Connection Dyn 11
11.11 Technical Data
11.12 Rated Power kVA 25
11.13 Primary - no load voltage kV 480
11.14 Secondary
Secondary
- no -load
no load
voltage
voltage 0.23
11.15 Number of Phases 3
11.16 Frequency Hz 60
11.17 Impedance at 167°F By Vendor
11.18 HV- Phases By Vendor
11.19 LV- Phases By Vendor
11.20 Windings By Vendor
11.21 Tapchanging - Off Circuit/On Line By Vendor
11.22 Number of positions By Vendor
11.23 Voltage Rating kV By Vendor
11.24 No Load Primary Current A By Vendor
11.25 Magnetizing Inrush Current A By Vendor
11.26 Excitation Current at 100% Rated Volt % By Vendor
11.27 Excitation Current at 110% Rated Volt % By Vendor
11.28 Temperature Rises ⁰C By Vendor
11.29 Rating: kVA By Vendor
11.30 Secondary Lightning Arrester Class (kV) By Vendor
11.31 self air cooled ANN MCOV (kV) By Vendor
11.32 Regulation: % By Vendor
11.33 PF = 0.8 lagging % By Vendor
11.34 Efficiencies at: 125% full load % By Vendor
11.35 100% full load % By Vendor
11.36 75% full load % By Vendor
11.37 50% full load % By Vendor
11.38 25% full load % By Vendor
11.39 Load Losses at Full Load kW By Vendor
11.40 No Load Losses kW By Vendor

Page 23 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4371-SS-401
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
11.41 Resistance Per Phase @ 75°C For Each Winding OHMS By Vendor
11.42 Impedance Voltage (IZ) - Off-load Taps (@ 3 MVA) By Vendor
11.43 at centre tap % By Vendor
11.44 X/R Ratio (@base MVA): By Vendor
11.45 Impedance Voltage (IZ) guaranteed maximum deviation %± By Vendor
12.00 PRESSURIZATION AND REFRIGERATION SYSTEM
12.01 Manufacturer Required
12.02 Model Required
12.03 Catalogue Required
12.04 Positive pressure required mm.c.a 6.35
12.05 Amount of equipment Required
12.06 KW required per equipment Required
12.07 Progressive air filtration Required, disposable and washable
12.08 Calculation memory pressurizing system Required
12.09 Pressurization and refrigeration requirements Required
13.00 FIRE DETECTION AND SUPPRESSION SYSTEM
13.01 Category Room with respect to the impact on the environment Required
13.02 DETECTION SYSTEM
13.03 Fire Detection Panel Required
13.04 Optical transceiver Required
13.05 Early detection system Required
13.06 Amount of Early Detection Systems Required
13.07 Smart smoke detectors Required
13.08 Number of Smart Smoke Detectors By vendor, according to NFPA -72
13.09 Manual Stations Required
13.10 Number of manual stations 2 (1 on each door)
13.11 Horn strobe light Required
13.12 Number of sirens strobe 2 (1 outside of each door)
13.13 SUPPRESSION SYSTEM
13.14 System of suppression based on FM-200 Required
13.15 Amount of FM-200 for the total volume of the room (kg) Required
13.16 Manual Abortion Stations Required
13.17 Number of manual abortion stations Required
13.18 Fire extinguishers portable type C02 (15 kg each) Required
13.19 Number of portable fire extinguishers 2 (1 outside of each door)
14.00 ELECTRICAL HOUSE DIMENSIONS
14.01 Total Nominal Length of Electrical House (between axis) mm By vendor
14.02 Total Nominal Width of Electrical House (between axis) mm By vendor
14.03 Exterior Overall Total Length of Electrical House mm By vendor
14.04 Exterior Overall Width of Electrical House mm By vendor
14.05 Maximum Overall Exterior Height of Electrical House mm By vendor
15.00 NOTES
15.01 BE CAREFULL WHEN EDITING DATA SHEETS. INSERT ONLY NECESSARY ADDITIONAL DETAILS FOR DATA AND PLACE THE REVISION CODE AT THE RIGHT MOST BOX

Page 24 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4372-SS-402
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
SUPPLIER/CONTRACTOR: By vendor
PLANT AREA: 4372
MODEL No. / DESIGNATION By vendor
1.00 SITE CONDITIONS
1.01 Altitude 825 msnm
1.02 Ambient temperature max °C 30
1.03 Ambient temperature min °C 8.4

1.04 Seismic Conditions Peruvian Seismic Code Standard E.030

1.05 Average annual precipitation mm 27.1


1.06 Minimum annual precipitation mm 13.7
1.07 maximum annual precipitation mm 50.5
1.08 Maximum wind speed km/h 90
2.00 STRUCTURAL REQUIREMENTS
2.01 General
2.02 Type of Substation Skid Mounted
lxbxh (m)
2.03 Maximum dimension of skid mounted substation By vendor
2.04 Skid platform elevation from grade m By vendor
2.05 Maximum weight of skid mounted substation kg By vendor
2.06 Transformer mounted outdoor on the skid Required
2.07 Electrical room mounted on the skid Required
2.08 Separate Outdoor enclosure for equipment on skid By vendor
2.09 Enclusure protection of electrical room NEMA 4
2.10 Design life of the mobile substation 20 Years
2.11 BASE
2.12 Base Structural Steel Material ASTM A36 rigid H or I or U-Beam
2.13 Runners in each base structure Required
2.14 Minimum thickness of deck plates mm By vendor
2.15 Deck Loading kg / m2 By vendor
2.16 Minimum removable Lifting Lugs / Eyes per substation skid 4
2.17 Skid with E-Room and equipment designed for lifting, towing, skidding, andjacking Required
2.18 Design Safety factor for lifting, towing and skidding facilities 5
2.19 Pulling eyes for towing and skidding Required
2.20 External Finishing Color RAL 1015 (Beige)
2.21 E-ROOM FLOOR

2.22 Material Steel Plate

2.23 Material Minimum Thickness mm By vendor

2.24 Top Surface Coating Non-slip, anti-skid

2.25 E-ROOM WALLS


2.26 Wall Panels Seams Continuously Welded
2.27 External Walls Material Cold Rolled Steel Sheets
2.28 External Walls Material Minimum Thickness mm 1.9
2.29 External Finishing Color RAL 1015 (Beige)
2.30 Internal Walls Material Cold Rolled Steel Sheets
2.31 Internal Walls Material Minimum Thickness mm 1.5
2.32 Internal Finishing Color RAL 9001 (Off White)
2.33 Penetrations By vendor
2.34 Final Thickness of Walls mm By vendor
2.35 E-ROOM ROOF
Cold Rolled Steel Sheets
2.36 External Roof Cover Material

2.37 External Roof Cover Material Minimum Thickness mm 1.9

Page 25 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4372-SS-402
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
2.38 External Roof Cover Panel Seams Continuously Welded
2.39 External Roof Finishing Color RAL 1015 (Beige)
2.40 Slope Downward from middle to side 85 mm per meter
2.41 Sloped housing roof providing full drainage Required
2.42 Internal Ceiling Cover Material Cold Rolled Steel Sheets
2.43 Internal Ceiling Cover Material Minimum Thickness mm 1.5
2.44 Internal Ceiling Finishing Color RAL 9001 (Off White)
2.45 Final Maximum Thickness of Roof @ center Ridge mm By vendor
2.46 Roof Average Design Loading kg / m2 250
2.47 Roof Concentrated Design Loading kg / m2 125
2.48 E-ROOM DOORS

2.49 Material Seamless steel sheets

2.50 Equipment Door Size Height / Width mm By vendor


2.51 Personnel access doors size Height / Width mm 2200/1000
2.52 Stainless steel panic exit hardware w/ quick release latch mechanism to permit Required
2.53 Door locks Required
2.54 Automatic closures Required
2.55 Kick plates Required
2.56 Rain canopy Required
2.57 Doors removable for entering or removing equipments Required
2.58 Door with non-combustible R11 insulation & F60 1-hr fire resistance Required
2.59 Door finishing color (exterior) RAL 5010 (Blue)
2.60 Door finishing color (interior) RAL 9001 (Off White)
2.61 Final Thickness of Doors mm By vendor

3.00 OUTDOOR SECONDARY SECTION WALK-IN ENCLOSURE

3.01 Manufacturer By vendor


3.02 Enclosure Nema 4
3.03 Minimum working space mm By vendor
3.04 Lighting
3.05 Lighting type Industrial Fluorescent
3.06 Lighting intensity Lux 550
3.07 Lighting Panel Required
3.08 Lighting Panel Main feeder 220 V, 60 Hz, 1Ф (By buyer)
4.00 ELECTRICAL EQUIPMENT
4.01 PRIMARY POWER SYSTEM
4.02 Rated Voltage kV 22.9
4.03 Voltage variation % ± 10
4.04 Phase 3
4.05 Frequency Hz 60
4.06 Frequency variation % ±1%
4.07 Short circuit Capacity kA 25
4.08 SECONDARY POWER SYSTEM
4.09 Rated Voltage kV 0.38-0.23
4.10 Phase 3
4.11 Frequency Hz 60
4.12 Short circuit Capacity HV 20 kA
4.13 22.9 kV METAL ENCLOSED MAIN INCOMING SWITCH
4.14 Manufacturer By vendor
4.15 Quantity 1
4.15 Model / Catalog N° By vendor
4.16 Enclosure IEC

Page 26 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4372-SS-402
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
4.17 Type Metal Enclosed
4.18 Rated continuous current A 600
4.19 Maximum Symmetrical Interrupting Capability kA 25
4.20 Surge Protection manufacturer By vendor
4.21 Surge Protection Type Not Required
4.22 Surge Protection MCOV Not Required
Fuses Required
4.23 Switch General Characteristics
4.24 Manufacturer By vendor
Three poles, fixed, operated Without
4.25 Type
Load
4.26 Number trip coils 1
4.27 Padlocks Required
4.28 Auxiliary contacts 5 NO + 5 NC
4.29 Opening time (milliseconds) By vendor
4.30 BIL at sea level kV 125
4.31 Power frequency withstand at sea level By vendor
4.32 trip coils voltage 125 VDC (By buyer)
4.33 Heaters 220 VAC, 1 phase, 60 Hz (By buyer)
4.34 Cable Entrance Bottom
4.35 Cable Size 1 x (3/c N° 120mm + SHD)
4.36 Approximate overall dimension (WxDxH) mm By vendor
4.37 Approximate weight (kg) By vendor
5.00 TRANSFORMER SECTION
5.01 Manufacturer By vendor
5.02 Type PCB Free Mineral Oil liquid-filled
Standars IEC
5.03 Fluid Preservations Systems Sealed tank
5.04 Self cooled capacity (OA - 55° C) @ 1,000 m.a.s.l. (kVA) 1000
5.05 Self cooled capacity (OA - 65° C) @ 1,000 m.a.s.l. (kVA) Not Applicable
5.06 Force cooled capacity (FA - 55° C) @ 1,000 m.a.s.l. (kVA) Not Applicable
5.07 Force cooled capacity (FA - 65° C) @ 1,000 m.a.s.l. (kVA) Not Applicable
5.08 Transformer connection Dyn11
5.09 Primary Voltage (line to line) kV 22.9
5.10 Secondary Voltage (line to line) kV 0.4-0.23
5.11 Minimum Primary Bushings (three total) BIL kV 125
5.12 Minimum Primary Winding BIL kV By vendor
5.13 Minimum Secondary Bushings (four total) BIL kV By vendor
5.14 Minimum Secondary Winding BIL kV By vendor
5.15 Impedance on its self cooled capacity (OA - 55°C) 6.5
De-energized tap changer with padlock provision (Four full capacity 2 ½ percent taps, two
5.16 Required
above and two below rated voltage on the 22.9 kV winding)
5.17 Accessories
5.18 Magnetic liquid level gauge with alarm contacts Required
5.19 Oil dial type thermometer with alarm contacts Required
5.20 Winding thermometer (thermal image) with alarm contacts Required
5.21 Pressure vacuum gauge with trip and alarm contacts Required
5.22 Cover vent plug Required
5.23 Pressure test connection Required
5.24 Filling plug and filter press connection Required
5.25 Combination drain valve and bottom filter press connection Required
5.26 Sampling device Required

Page 27 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4372-SS-402
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
5.27 Diagrammatic name plate Required
5.28 Manhole or handhole in cover Required
5.29 Provision for lifting and jacking Required
5.30 Neutral resistor 100 A, 10 sec Required
5.31 Current transformer including with neutral resistor 50/5 A Required
5.32 Transformer Losses (Guaranteed)
5.33 Full Load (kW) By vendor
5.34 3/4 Full Load (kW) By vendor
5.35 1/2 Full Load (kW) By vendor
5.36 Transformer Efficiency (Guaranteed)
5.37 Full Load (%) By vendor
5.38 3/4 Full Load (%) By vendor
5.39 1/2 Full Load (%) By vendor
5.40 Approximate overall dimension (WxDxH) mm By vendor
5.41 Base Plate Dimensions and Anchors mm By vendor
5.42 Approximate weight with oil (kg) By vendor
5.43 Approximate weight without oil (kg) By vendor
5.44 TRANSFORMER TESTING
5.45 Normal tests (According to latest revision of IEC Standars)
5.46 Resistance measurements of all windings Required
5.47 Ratio tests Required
5.48 Polarity and phase relation test Required
5.49 No-load loss at rated voltage Required
5.50 Excitation current at rated voltage Required
5.51 Impedance and load loss Required
5.52 Applied potential test Required
5.53 Induced potential test Required
5.54 Mechanical leak test Required
5.55 Temperature test Not Required
5.56 Impulse test Not Required
5.57 Quality control impulse test Not Required
5.58 Front of wave impulse test Not Required
5.59 DGA FQ Analysis OIL Active Part Required
5.60 Frequency Response Analysis (FRA) in factory Not Required
5.61 Zero-phase sequence impedance test Not Required
5.62 Insulation resistance (megger) test Required
6.00 0.48 kV METAL CLAD SWITCHGEAR
6.01 INCOMING
6.02 Manufacturer By vendor
6.03 Model / Catalog N° By vendor
6.04 Enclosure Nema 12
6.05 Type Metal Clad
6.06 Main Bus Continuous Rating A 1,500
6.07 Quantity 1
6.08 Circuit Breaker General Characteristics
6.09 Manufacturer By vendor
6.10 Interrupter Type By vendor

Three poles, drawout, electrically


6.11 Circuit breaker Type
operated, stored energy operation
6.12 Protection LSIG
6.13 Number trip coils 1

Page 28 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4372-SS-402
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
6.14 Auxiliary contacts 5 NO + 5 NC
6.15 Interrupting time 5 cycles or less
6.16 Closing time (milliseconds) By vendor
6.17 Opening time (milliseconds) By vendor
6.18 Construction Rating Draw Out
6.19 BIL at sea level By vendor
6.20 Power frequency withstand at sea level By vendor
6.21 Close and trip coils voltage 125 VDC (By buyer)
6.22 Mechanism motors voltage 125 VDC (By buyer)
6.23 Control circuit breakers 125 VDC (By buyer)
6.24 Heaters 220 VAC, 1 phase, 60 Hz (By buyer)
6.25 Motor power consumption By vendor
6.26 Closing solenoid power consumption By vendor
6.27 Opening solenoid power consumption By vendor
6.28 Opening solenoid power consumption By vendor
6.29 Heaters consumption By vendor
6.30 METER
6.31 Type Microprocesador
6.32 Model PM8000
6.33 Version PM8240
6.34 Manufacturer Schneider Electric
6.35 Supplier Tensión VDC 125
6.36 Communication protocol Modbus TCP/IP
6.37 Number of communication ports 1
6.38 Phase Current transformer
6.39 Quantity 3
6.40 Manufacturer By vendor
6.41 Model / Catalog N° By vendor
6.42 Current ratio 1500:5
6.43 Class By vendor
6.44 Potential transformer
6.45 Quantity 1
6.46 Manufacturer By vendor
6.47 Model / Catalog N° By vendor
6.48 Voltage ratio 480/120 V
7.00 NETWORK COMUNICATION
Required / 2 Lawer
7.01 Switch
7.02 Model By vendor
7.03 Manufacturer RUGGEDCOM
7.04 Protocol IEC 61850

7.05 Network Ports Single mode 2 chanels

According to IED´s Meters, relay and


7.06 Network Ports
controlers
8.00 FEEDER CIRCUIT BREAKERS TERMOMAGNETICO
8.01 Voltage Kv 480
8.02 Quantity 6
8.03 Model / Catalog N° By vendor
8.04 Rated continuous current A 300
8.05 Phases 3
8.06 Protection Required Multiratio 0.5 -1
8.07 Cable Outgoing Bottom
8.08 Cable Size By vendor
8.09 Class By vendor

Page 29 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4372-SS-402
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
9.00 SPARES AND OPTIONAL ACCESSORIES
9.01 22.9 kV Spare Fuses / Quantity Required / 3
10.00 BATTERY CHARGER
10.01 Manufacturer By Vendor
10.02 Model / Catalog N° By Vendor
10.03 Type SCR
10.04 Enclosure Nema 12
10.05 Mounting Floor
10.06 Float Voltage (adjustable) V/cell 2.33
10.07 Equalize Voltage (adjustable) V/cell 2.33
10.08 Recharge time (maximum) 8 hours
10.09 Nominal DC Output Current Rating By Vendor
10.10 Maximum ripple 100 mV rms
10.11 Audible noise (maximum) 65 dB at 1.5 m
10.12 Measurement, Protection relays, Control, Alarms and Lights
10.13 Output Voltmeter Required
10.14 Output Ammeter Required
10.15 Low DC Voltage Relay Required
10.16 High DC Voltage Relay Required
10.17 DC Surge Protection Required
10.18 DC Output Circuit Breaker Required
10.19 Electronic short circuit and Overload protection Required
10.20 Manufacturer's multifunction standard control/display Unit Acceptable
10.21 Alarms (minimum)
10.22 AC Failure Required
10.23 DC Failure Required
10.24 High VDC Required
10.25 Low VDC Required
10.26 Ground Detection Required
10.27 Overload Required
10.28 High or Equalize ON Pilot Light Required
10.29 BATTERY SUPPORT
10.30 Type Rack
10.31 Mounting Back to Wall
10.32 Tier Two or Three / By Vendor
10.33 Finish Color ANSI 61
10.34 Dimensions and Weight
10.35 Width (mm) By Vendor
10.36 Height (mm) By Vendor
10.37 Depth (mm) By Vendor
10.38 Weight (kg) By Vendor
10.39 BATTERY BANK
10.40 Type Sealed Maintenance Free
10.41 Application Switchgear Control Power
10.42 Manufacturer By Vendor
10.43 Model / Catalog N° By Vendor
10.44 Cell Container By Vendor
10.45 Time life 5 years
10.46 Nominal Voltage VDC 125
10.47 Maximum Voltage VDC 140
10.48 Minimum Voltage VDC 105

Page 30 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4372-SS-402
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
10.49 Equalize Voltage (Volt Per Cell) 2.37
10.50 Flotation Voltage (Volt Per Cell) 2.25
10.51 End-of Discharge Cell Voltage (Volt Per Cell) 1.75
10.52 Minimum Amper-hour Rating Calculated By Vendor
10.53 Amper hour Capacity at 8 hr rate o discharge to 1.75 Volts per Cell By Vendor
10.54 Battery constant-current discharge Table, in A (@25°C) By Vendor
11.00 DRY TYPE TRANSFORMER (Auxiliary Services)
11.01 General
11.02 Manufacturer By Vendor
11.03 Place of Manufacture By Vendor
11.04 Type High Efficiency Dry type
11.05 Installation Type Indoor Floor Mounted
11.06 Enclosure NEMA 12
11.07 Rated Ambient Temperature (Maximum) By Vendor
11.08 Rated Ambient Temperature (Minimum) By Vendor
11.09 Rated Ambient Temperature (24 hrs mean Max) By Vendor
11.10 Height above sea level 1000 masl
11.11 Cooling By Vendor
11.12 Connection Dyn 11
11.11 Technical Data
11.12 Rated Power kVA By Vendor
11.13 Primary - no load voltage kV 480
11.14 Secondary
Secondary
- no -load
no load
voltage
voltage 0.23
11.15 Number of Phases 3
11.16 Frequency Hz 60
11.17 Impedance at 167°F By Vendor
11.18 HV- Phases By Vendor
11.19 LV- Phases By Vendor
11.20 Windings By Vendor
11.21 Tapchanging - Off Circuit/On Line By Vendor
11.22 Number of positions By Vendor
11.23 Voltage Rating kV By Vendor
11.24 No Load Primary Current A By Vendor
11.25 Magnetizing Inrush Current A By Vendor
11.26 Excitation Current at 100% Rated Volt % By Vendor
11.27 Excitation Current at 110% Rated Volt % By Vendor
11.28 Temperature Rises ⁰C By Vendor
11.29 Rating: kVA By Vendor
11.30 Secondary Lightning Arrester Class (kV) By Vendor
11.31 self air cooled ANN MCOV (kV) By Vendor
11.32 Regulation: % By Vendor
11.33 PF = 0.8 lagging % By Vendor
11.34 Efficiencies at: 125% full load % By Vendor
11.35 100% full load % By Vendor
11.36 75% full load % By Vendor
11.37 50% full load % By Vendor
11.38 25% full load % By Vendor
11.39 Load Losses at Full Load kW By Vendor
11.40 No Load Losses kW By Vendor
11.41 Resistance Per Phase @ 75°C For Each Winding OHMS By Vendor
11.42 Impedance Voltage (IZ) - Off-load Taps (@ 3 MVA) By Vendor

Page 31 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 4372-SS-402
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
SKID
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
11.43 at centre tap % By Vendor
11.44 X/R Ratio (@base MVA): By Vendor
11.45 Impedance Voltage (IZ) guaranteed maximum deviation %± By Vendor
12.00 PRESSURIZATION AND REFRIGERATION SYSTEM
12.01 Manufacturer Required
12.02 Model Required
12.03 Catalogue Required
12.04 Positive pressure required mm.c.a 6.35
12.05 Amount of equipment Required
12.06 KW required per equipment Required
12.07 Progressive air filtration Required, disposable and washable
12.08 Calculation memory pressurizing system Required
12.09 Pressurization and refrigeration requirements Required
13.00 FIRE DETECTION AND SUPPRESSION SYSTEM
13.01 Category Room with respect to the impact on the environment Required
13.02 DETECTION SYSTEM
13.03 Fire Detection Panel Required
13.04 Optical transceiver Required
13.05 Early detection system Required
13.06 Amount of Early Detection Systems Required
13.07 Smart smoke detectors Required
13.08 Number of Smart Smoke Detectors By vendor, according to NFPA -72
13.09 Manual Stations Required
13.10 Number of manual stations 2 (1 on each door)
13.11 Horn strobe light Required
13.12 Number of sirens strobe 2 (1 outside of each door)
13.13 SUPPRESSION SYSTEM
13.14 System of suppression based on FM-200 Required
13.15 Amount of FM-200 for the total volume of the room (kg) Required
13.16 Manual Abortion Stations Required
13.17 Number of manual abortion stations Required
13.18 Fire extinguishers portable type C02 (15 kg each) Required
13.19 Number of portable fire extinguishers 2 (1 outside of each door)
14.00 ELECTRICAL HOUSE DIMENSIONS
14.01 Total Nominal Length of Electrical House (between axis) mm By vendor
14.02 Total Nominal Width of Electrical House (between axis) mm By vendor
14.03 Exterior Overall Total Length of Electrical House mm By vendor
14.04 Exterior Overall Width of Electrical House mm By vendor
14.05 Maximum Overall Exterior Height of Electrical House mm By vendor
15.00 NOTES
15.01 BE CAREFULL WHEN EDITING DATA SHEETS. INSERT ONLY NECESSARY ADDITIONAL DETAILS FOR DATA AND PLACE THE REVISION CODE AT THE RIGHT MOST BOX

Page 32 of 49
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

SUPPLIER/CONTRACTOR: By vendor

PLANT AREA: 1371

MODEL No. / DESIGNATION By vendor

N° DRAWING REFERENCE 9666-SE-02


1.00 SITE CONDITIONS
1.01 Altitude 825 msnm
1.02 Ambient temperature max °C 30
1.03 Ambient temperature min °C 8.4

1.04 Seismic Conditions Peruvian Seismic Code Standard E.030

1.05 Average annual precipitation mm 27.1


1.06 Minimum annual precipitation mm 13.7
1.07 maximum annual precipitation mm 50.5
1.08 Maximum wind speed km/h 90
2.00 STRUCTURAL REQUIREMENTS
2.01 General
2.02 Type of Substation Skid Mounted
2.03 Maximum dimension of skid mounted substation lxbxh (m) By vendor
2.04 Skid platform elevation from grade m By vendor
2.05 Maximum weight of skid mounted substation kg By vendor
2.06 Transformer mounted outdoor on the skid Required
2.07 Electrical room mounted on the skid Required
2.08 Separate Outdoor enclosure for equipment on skid By vendor
2.09 Enclusure protection of electrical room NEMA 4
2.10 Design life of the mobile substation 20 Years
2.11 BASE
2.12 Base Structural Steel Material ASTM A36 rigid H or I or U-Beam
2.13 Runners in each base structure Required
2.14 Minimum thickness of deck plates mm By vendor
2.15 Deck Loading kg / m2 By vendor
2.16 Minimum removable Lifting Lugs / Eyes per substation skid 4
2.17 Skid with E-Room and equipment designed for lifting, towing, skidding, andjacking Required
2.18 Design Safety factor for lifting, towing and skidding facilities 5
2.19 Pulling eyes for towing and skidding Required
2.20 External Finishing Color RAL 1015 (Beige)
2.21 E-ROOM FLOOR
2.22 Floor Color Gray, ANSI 61
2.23 Material Steel Plate
2.24 Material Minimum Thickness mm 6
2.25 Top Surface Coating Non-slip, anti-skid
2.26 E-ROOM WALLS
2.27 Wall Panels Seams Continuously Welded
2.28 External Walls Material Cold Rolled Steel Sheets
2.29 External Walls Material Minimum Thickness mm 1.9
RAL 1015 (Beige)
2.30 External Finishing Color

2.31 Internal Walls Material Cold Rolled Steel Sheets


2.32 Internal Walls Material Minimum Thickness mm 1.5
2.33 Internal Finishing Color RAL 9001 (Off White)
2.34 Penetrations By vendor
2.35 Final Thickness of Walls mm By vendor
2.36 E-ROOM ROOF
2.37 External Roof Cover Material Cold Rolled Steel Sheets
2.38 External Roof Cover Material Minimum Thickness mm 1.9
2.39 External Roof Cover Panel Seams Continuously Welded
2.40 External Roof Finishing Color RAL 1015 (Beige)
2.41 Slope Downward from middle to side 85 mm per meter
2.42 Sloped housing roof providing full drainage Required
2.43 Internal Ceiling Cover Material Cold Rolled Steel Sheets
2.44 Internal Ceiling Cover Material Minimum Thickness mm 1.5
2.45 Internal Ceiling Finishing Color RAL 9001 (Off White)
2.46 Final Maximum Thickness of Roof @ center Ridge mm By vendor
2.47 Roof Average Design Loading kg / m2 250

Page 33 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

2.48 Roof Concentrated Design Loading kg / m2 125


2.49 E-ROOM DOORS
2.50 Material Seamless steel sheets
2.51 Equipment Door Size Height / Width mm By vendor
2.52 Personnel access doors size Height / Width mm 2200/1000
2.53 Stainless steel panic exit hardware w/ quick release latch mechanism to permit Required
2.54 Door locks Required
2.55 Automatic closures Required
2.56 Kick plates Required
2.57 Rain canopy Required
2.58 Doors removable for entering or removing equipments Required
2.59 Door with non-combustible R11 insulation & F60 1-hr fire resistance Required
2.60 Door finishing color (exterior) RAL 5010 (Blue)
2.61 Door finishing color (interior) RAL 9001 (Off White)
2.62 Final Thickness of Doors mm By vendor
2.63 PLATFORMS, STAIRS, FENCE AND GATE
2.64 Platforms and stairs steel structures Required
2.65 Removable serrated type hot-dip galvanized steel grating for landings and stair Required
2.66 Expanded metal mesh steel gratings Not acceptable
2.67 Three level bodyguards removable handrails with kickplates By vendor
2.68 Platforms and stairs steel structures paint finishing color RAL 5010 (Blue)
2.69 Handrails, kickplates and balausters finishing safety color RAL 1023 (Yellow)
2.70 Platforms Average Loading kg / m2 500
2.71 Removable Fence around outdoor equipment on the skid/trailer No Required
2.72 Lockable access gate in the fenced area No Required
2.73 Material of the Fence and Gate No Required
2.74 LIGHTING
2.75 Interior lighting level Lux 500
2.76 Type internal luminaires Fluorescent 2 x 40 W
2.77 External luminaires type HPS, 100 W
2.78 Emergency Lighting Required, By Vendor
2.79 General Purpose Plugs Required, 220 V, 15 A
2.80 DETECTION SYSTEM
2.81 Fire Detection Panel Required
2.82 Optical transceiver Required
2.83 Early detection system Required
2.84 Amount of Early Detection Systems Required
2.85 Smart smoke detectors Required
2.86 Number of Smart Smoke Detectors By vendor, according to NFPA -72
2.87 Manual Stations Required
2.88 Number of manual stations 2 (1 on each door)
2.89 Horn strobe light Required
2.90 Number of sirens strobe 2 (1 outside of each door)
2.91 SUPPRESSION SYSTEM
2.92 System of suppression based on FM-200 Required
2.93 Amount of FM-200 for the total volume of the room (kg) Required
2.94 Manual Abortion Stations Required
2.95 Number of manual abortion stations Required
2.96 Fire extinguishers portable type C02 (15 kg each) Required
2.97 Number of portable fire extinguishers 2 (1 outside of each door)
3.00 ELECTRICAL EQUIPMENT
3.01 PRIMARY POWER SYSTEM
3.02 Rated Voltage kV 22.9
3.03 Voltage variation % ± 10
3.04 Phase 3
3.05 Frequency Hz 60
3.06 Frequency variation % ±1%
3.07 Short circuit Capacity kA 25
3.08 SECONDARY POWER SYSTEM
3.09 Rated Voltage kV 7.2
3.10 Phase 3
3.11 Frequency Hz 60
3.12 Short circuit Capacity 20 kA

Page 34 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1
3.13 22.9 kV METAL ENCLOSED INCOMING BREAKER
3.14 Manufacturer By vendor
3.15 Model / Catalog N° By vendor
3.16 Enclosure IEC or Higher
3.17 Type Metal Enclosed
3.18 Rated continuous current A 600
3.19 Maximum Symmetrical Interrupting Capability kA 31.5
3.20 Surge Protection manufacturer By vendor
3.21 Surge Protection Type Polymeric Metal Oxide
3.22 Surge Protection MCOV 24 kVRMS
3.23 Circuit Breaker General Characteristics
3.24 Manufacturer By vendor
3.25 Interrupter Type Vacuum or SF6
Three poles, fixed, electrically operated,
3.26 Circuit breaker Type
stored energy operation
3.27 Number trip coils 2
3.28 Capacitor trips Not Required
3.29 Operation counter Required
3.30 Padlocks Required
3.31 Auxiliary contacts 5 NO + 5 NC
3.32 Interrupting time 5 cycles or less
3.33 Closing time (milliseconds) By vendor
3.34 Opening time (milliseconds) By vendor
3.35 Construction Rating Draw Out
3.36 BIL at sea level kV 125
3.37 Power frequency withstand at sea level By vendor
3.38 Close and trip coils voltage 125 VDC (By buyer)
3.39 Mechanism motors voltage 125 VDC (By buyer)
3.40 Control circuit breakers 125 VDC (By buyer)
3.41 Heaters 220 VAC, 1 phase, 60 Hz (By buyer)
3.42 Motor power consumption By vendor
3.43 Closing solenoid power consumption By vendor
3.44 Opening solenoid power consumption By vendor
3.45 Opening solenoid power consumption By vendor
3.46 Heaters consumption By vendor
3.47 Phase Current transformer
3.48 Quantity 3
3.49 Manufacturer By vendor
3.50 Model / Catalog N° By vendor
3.51 Current ratio 600/300/5 A
3.52 Class By vendor
3.53 Cable Entrance Bottom
3.54 Cable Size By vendor
3.55 Approximate overall dimension (WxDxH) mm By vendor
3.56 Approximate weight (kg) By vendor
3.57 Main Incoming Switch
3.58 Quantity 1
3.59 Model / Catalog N° By vendor
3.60 Rated continuous current A 600
4.00 TRANSFORMER SECTION
4.01 Manufacturer By vendor
4.02 Type PCB Free Mineral Oil liquid-filled
4.03 Fluid Preservations Systems Sealed tank
4.04 Self cooled capacity (OA - 55° C) @ 1,000 m.a.s.l. (kVA) 10000
4.05 Self cooled capacity (OA - 65° C) @ 1,000 m.a.s.l. (kVA) 10000
4.06 Force cooled capacity (FA - 55° C) @ 1,000 m.a.s.l. (kVA) 12500
4.07 Force cooled capacity (FA - 65° C) @ 1,000 m.a.s.l. (kVA) 12500
4.08 Transformer connection Dyn11
4.09 Primary Voltage (line to line) kV 22.9
4.10 Secondary Voltage (line to line) kV 7.2
4.11 Minimum Primary Bushings (three total) BIL kV 200
4.12 Minimum Primary Winding BIL kV 150

Page 35 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

4.13 Minimum Secondary Bushings (four total) BIL kV 95


4.14 Minimum Secondary Winding BIL kV 60
4.15 Impedance on its self cooled capacity (OA - 55°C) 8.5
De-energized tap changer with padlock provision (Four full capacity 2 ½ percent taps, two
4.16 Required
above and two below rated voltage on the 22.9 kV winding)
4.17 Accessories
4.18 Magnetic liquid level gauge with alarm contacts Required
4.19 Oil dial type thermometer with alarm contacts Required
4.20 Winding thermometer (thermal image) with alarm contacts Required
4.21 Pressure vacuum gauge with trip and alarm contacts Required
4.22 Cover vent plug Required
4.23 Pressure test connection Required
4.24 Filling plug and filter press connection Required
4.25 Combination drain valve and bottom filter press connection Required
4.26 Sampling device Required
4.27 Diagrammatic name plate Required
4.28 Manhole or handhole in cover Required
4.29 Provision for lifting and jacking Required
4.30 Neutral resistor 100 A, 10 sec Required
4.31 Current transformer including with neutral resistor 50/5 A Required
4.32 Transformer Losses (Guaranteed)
4.33 Full Load (kW) By vendor
4.34 3/4 Full Load (kW) By vendor
4.35 1/2 Full Load (kW) By vendor
4.36 Transformer Efficiency (Guaranteed)
4.37 Full Load (%) By vendor
4.38 3/4 Full Load (%) By vendor
4.39 1/2 Full Load (%) By vendor
4.40 Approximate overall dimension (WxDxH) mm By vendor
4.41 Base Plate Dimensions and Anchors mm By vendor
4.42 Approximate weight with oil (kg) By vendor
4.43 Approximate weight without oil (kg) By vendor
4.44 TRANSFORMER TESTING
4.45 Normal tests (According to latest revision of IEC Standars)
4.46 Resistance measurements of all windings Required
4.47 Ratio tests Required
4.48 Polarity and phase relation test Required
4.49 No-load loss at rated voltage Required
4.50 Excitation current at rated voltage Required
4.51 Impedance and load loss Required
4.52 Applied potential test Required
4.53 Induced potential test Required
4.54 Mechanical leak test Required
4.55 Temperature test Required
4.56 Impulse test Required
4.57 Quality control impulse test Required
4.58 Front of wave impulse test Required
4.59 DGA FQ Analysis OIL Active Part Required
4.60 Frequency Response Analysis (FRA) in factory Required
4.61 Zero-phase sequence impedance test Required
4.62 Insulation resistance (megger) test Required
5.00 7.2 kV METAL CLAD SWITCHGEAR
5.01 FEEDER INCOMING
5.02 Manufacturer By vendor
5.03 Model / Catalog N° By vendor
5.04 Enclosure IEC or higher
5.05 Type Metal Clad
5.06 Main Bus Continuous Rating A 1,200
5.07 Quantity 1
5.08 Bus Bracing MVA By vendor
5.09 Circuit Breaker General Characteristics
5.10 Manufacturer By vendor

Page 36 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

5.11 Interrupter Type Vacuum or SF6

Three poles, drawout, electrically


5.12 Circuit breaker Type
operated, stored energy operation

5.13 Nominal 3-Phase MVA Class MVA By vendor


5.14 Number trip coils 2
5.15 Capacitor trips Not Required
5.16 Operation counter Required
5.17 Padlocks Required
5.18 Auxiliary contacts 5 NO + 5 NC
5.19 Interrupting time 5 cycles or less
5.20 Closing time (milliseconds) By vendor
5.21 Opening time (milliseconds) By vendor
5.22 Construction Rating Draw Out
5.23 BIL at sea level 95 kV
5.24 Power frequency withstand at sea level 36 kV
5.25 Close and trip coils voltage 125 VDC (By buyer)
5.26 Mechanism motors voltage 125 VDC (By buyer)
5.27 Control circuit breakers 125 VDC (By buyer)
5.28 Heaters 220 VAC, 1 phase, 60 Hz (By buyer)
5.29 Motor power consumption By vendor
5.30 Closing solenoid power consumption By vendor
5.31 Opening solenoid power consumption By vendor
5.32 Opening solenoid power consumption By vendor
5.33 Heaters consumption By vendor
5.34 7.2 kV FEEDER CIRCUIT BREAKERS
5.35 Quantity 3
5.36 Model / Catalog N° By vendor
5.37 Rated continuous current A 1,200
5.38 Surge Protection manufacturer By vendor
5.39 Surge Protection Type Polymeric Metal Oxide
5.40 Surge Protection MCOV 5.1 kV RMS
5.41 Cable Outgoing Bottom
5.42 Cable Size
5.43 Main Incoming Diferential Relay
5.44 Quantity
5.45 Brand Multilin
5.46 Model T60-G00-XXX-XXX-XXX-XXX
5.47 Feeder Relay
5.48 Quantity 3
5.49 Brand Multilin
5.50 Model F60-G00-VFH-F8F-H6E
5.51 Relay Ground-Fault Ground-Check Monitor
5.52 Quantity 3
5.53 Brand Starco
5.54 Model SE 135
5.55 Zero sequence current transformer
5.56 Quantity 3
5.57 Manufacturer By vendor
5.58 Model / Catalog N° Starco SE-CS10
5.59 Current ratio By vendor
5.60 Class By vendor
5.61 Lock-out relay (ANSI 86)
5.62 Quantity
5.63 Brand By Vendor
5.64 Model / Catalog N° By vendor
5.65 Phase Current transformer
5.66 Quantity 3
5.67 Manufacturer By vendor
5.68 Model / Catalog N° By vendor
5.69 Current ratio 1200/600: 5
5.70 Class By vendor
5.71 Potential transformer

Page 37 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

5.72 Quantity 1
5.73 Manufacturer By vendor
5.74 Model / Catalog N° By vendor
5.75 Voltage ratio 7200/120 V
5.76 Class 50VA / 0.2
5.77 7.2 kV METAL ENCLOSED AUXILIARY SERVICES SWITCH
5.78 Manufacturer By vendor
5.79 Quantity 1
5.79 Model / Catalog N° By vendor
5.80 Enclosure IEC
5.81 Type Metal Enclosed
5.82 Rated continuous current A 600
5.83 Maximum Symmetrical Interrupting Capability kA 25
5.84 Surge Protection manufacturer By vendor
5.85 Surge Protection Type Not Required
5.86 Surge Protection MCOV Not Required
Fuses Required
5.87 Switch General Characteristics
5.88 Manufacturer By vendor
Three poles, fixed, operated Without
5.89 Type
Load
5.90 Number trip coils 1
5.91 Padlocks Required
5.92 Auxiliary contacts 5 NO + 5 NC
5.93 Opening time (milliseconds) By vendor
5.94 BIL at sea level kV 125
5.95 Power frequency withstand at sea level By vendor
5.96 trip coils voltage 125 VDC (By buyer)

5.97 Heaters 220 VAC, 1 phase, 60 Hz (By buyer)

5.98 Cable Entrance Bottom


5.99 Cable Size 1 x (3/c N° 120mm + SHD)
6.00 Approximate overall dimension (WxDxH) mm By vendor
6.01 Approximate weight (kg) By vendor
7.00 NETWORK COMUNICATION
Required / 2 Lawer
7.01 Switch
7.02 Model By vendor
7.03 Manufacturer RUGGEDCOM
7.04 Protocol IEC 61850
7.05 Network Ports Single mode 2 chanels
According to IED´s Meters, relay and
7.06 Network Ports
controlers
8.00 PRESSURIZATION AND REFRIGERATION SYSTEM
Required
8.01 Manufacturer

8.02 Model Required


8.03 Catalogue Required
8.04 Positive pressure required mm.c.a 6.35
8.05 Amount of equipment Required
8.06 KW required per equipment Required
8.07 Progressive air filtration Required, disposable and washable
8.08 Calculation memory pressurizing system Required
Required
8.09 Pressurization and refrigeration requirements

8.10 SPARES AND OPTIONAL ACCESSORIES

8.11 22.9 kV Spare Fuses / Quantity Required / 3

8.12 Spare set of all types and ratings of control fuses Required
8.13 One test jumper for electrically operating the breaker while out of its compartment Required
8.14 One levering crank for moving the breaker between test and connected positions Required
8.15 One breaker lifting yoke used for attachment to breaker for lifting breaker on or of compartment rails Required
8.16 One set of rails extensions and rail clamps Required
8.17 One portable lifting device for lifting the breaker on or off the rails Required
8.18 One test cabinet for testing electrically operated breakers outside housing Required

8.19 One "dockable" transport dolly for moving breaker about outside its compartment Required

9.00 BATTERY CHARGER

Page 38 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

9.01 Manufacturer By Vendor


9.02 Model / Catalog N° By Vendor
9.03 Type SCR
9.04 Enclosure Nema 12
9.05 Mounting Floor
9.06 Float Voltage (adjustable) V/cell 2.33
9.07 Equalize Voltage (adjustable) V/cell 2.33
9.08 Recharge time (maximum) 8 hours
9.09 Nominal DC Output Current Rating By Vendor
9.10 Maximum ripple 100 mV rms
9.11 Audible noise (maximum) 65 dB at 1.5 m
9.12 Measurement, Protection relays, Control, Alarms and Lights
9.13 Output Voltmeter Required
9.14 Output Ammeter Required
9.15 Low DC Voltage Relay Required
9.16 High DC Voltage Relay Required
9.17 DC Surge Protection Required
9.18 DC Output Circuit Breaker Required
9.19 Electronic short circuit and Overload protection Required
9.20 Manufacturer's multifunction standard control/display Unit Acceptable
9.21 Alarms (minimum)
9.22 AC Failure Required
9.23 DC Failure Required
9.24 High VDC Required
9.25 Low VDC Required
9.26 Ground Detection Required
9.27 Overload Required
9.28 High or Equalize ON Pilot Light Required
9.29 BATTERY SUPPORT
9.30 Type Rack
9.31 Mounting Back to Wall
9.32 Tier Two or Three / By Vendor
9.33 Finish Color ANSI 61
9.34 Dimensions and Weight
9.35 Width (mm) By Vendor
9.36 Height (mm) By Vendor
9.37 Depth (mm) By Vendor
9.38 Weight (kg) By Vendor
9.39 BATTERY BANK
9.40 Type Sealed Maintenance Free
9.41 Application Switchgear Control Power
9.42 Manufacturer By Vendor
9.43 Model / Catalog N° By Vendor
9.44 Cell Container By Vendor
9.45 Time life 20 years
9.46 Nominal Voltage VDC 125
9.47 Maximum Voltage VDC 140
9.48 Minimum Voltage VDC 105
9.49 Equalize Voltage (Volt Per Cell) 2.37
9.50 Flotation Voltage (Volt Per Cell) 2.25
9.51 End-of Discharge Cell Voltage (Volt Per Cell) 1.75
9.52 Minimum Amper-hour Rating Calculated By Vendor
9.53 Amper hour Capacity at 8 hr rate o discharge to 1.75 Volts per Cell By Vendor
9.54 Battery constant-current discharge Table, in A (@25°C) By Vendor
10.00 DRY TYPE TRANSFORMER (Auxiliary Services)
10.01 GENERAL
10.02 Manufacturer By Vendor
10.03 Place of Manufacture By Vendor
10.04 Type High Efficiency Dry type
10.05 Installation Type Indoor Floor Mounted
10.06 Enclosure NEMA 12
10.07 Rated Ambient Temperature (Maximum) By Vendor

Page 39 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

10.08 Rated Ambient Temperature (Minimum) By Vendor


10.09 Rated Ambient Temperature (24 hrs mean Max) By Vendor
10.10 Height above sea level 1000 masl
10.11 Cooling By Vendor
10.12 Connection Dyn 11
10.11 TECNICAL DATA
10.12 Rated Power kVA 40
10.13 Primary - no load voltage kV 7.2
10.14 Secondary
Secondary
- no load
- no voltage
load voltage 0.23
10.15 Number of Phases 3
10.16 Frequency Hz 60
10.17 Impedance at 167°F 0.04
10.18 HV- Phases By Vendor
10.19 LV- Phases By Vendor
10.20 Windings By Vendor
10.21 Tapchanging - Off Circuit/On Line By Vendor
10.22 Number of positions By Vendor
10.23 Voltage Rating kV By Vendor
10.24 No Load Primary Current A By Vendor
10.25 Magnetizing Inrush Current A By Vendor
10.26 Excitation Current at 100% Rated Volt % By Vendor
10.27 Excitation Current at 110% Rated Volt % By Vendor
10.28 Temperature Rises ⁰C By Vendor
10.29 Rating: kVA By Vendor
10.30 Secondary Lightning Arrester Class (kV) By Vendor
10.31 self air cooled ANN MCOV (kV) By Vendor
10.32 Regulation: % By Vendor
10.33 PF = 0.8 lagging % By Vendor
10.34 Efficiencies at: 125% full load % By Vendor
10.35 100% full load % By Vendor
10.36 75% full load % By Vendor
10.37 50% full load % By Vendor
10.38 25% full load % By Vendor
10.39 Load Losses at Full Load kW By Vendor
10.40 No Load Losses kW By Vendor
10.41 Resistance Per Phase @ 75°C For Each Winding OHMS By Vendor
10.42 Impedance Voltage (IZ) - Off-load Taps (@ 3 MVA) By Vendor
10.43 at centre tap % By Vendor
10.44 X/R Ratio (@base MVA): By Vendor
10.45 Impedance Voltage (IZ) guaranteed maximum deviation %± By Vendor
10.46 FACTORY TESTS INCLUDED ON UNIT
10.47 Production Tests On Unit per ANSI C57.12.90 Required
10.48 Resistance Measurements On Windings Required
10.49 Ratio Tests Required
10.50 Polarity Tests Required
10.51 No-Load Loss Tests Required
10.52 Excitation Current Tests Required
10.53 Core And Copper Load Losses Required
10.54 High Potential Tests Required
10.55 Routine ANSI/IEEE Testing Required
10.56 Other By Vendor
11.00 MIMING PUG TYPE (7.2kV)
11.01 GENERAL
11.02 Manufacturer Ausproof Pty. Ltd.
11.03 Manufacturer country By Vendor
11.04 Electrical Standards for Design, Manufacturing and Testing IEEE Std. 48

Complies with: "Pin of last pilot wire to connect and first to disconnect" and "Ground pin first to
11.05 Required
connect and last to disconnect"

11.06 Insulation type Solid insulation, no air.


11.07 Plug type Hybrid, Not Plug/Soket
11.08 DETAILS MINE TYPE PLUG
11.09 Quantity Mounting plugs in cable c/u 3

Page 40 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

11.10 Quantity Mounting Plugs c/u 3

11.11 Includes accessories to use coupling and detach tool. Required

11.12 protection degree IP IP68


11.13 INSULATION
11.14 System Rated Voltage at 1,000 m.s.n.m. kV 7.2
11.15 Rated Voltage of the plug at 1,000 m.s.n.m. kV 7.2
11.16 Insulation class to 1,000msnm kV 7.2
11.17 Basic level of insulation to 1,000msnm (BIL) kV 95
11.18 Basic level of insulation to 5,000msnm (BIL) kV 95
11.19 Non-Disruptive Voltage at 1,000msnm (1min Dry Withstand (kV RMS)) kV 35
11.20 Non-Disruptive Voltage at 5,000msnm (1 min Dry Withstand (kV RMS)) kV 35
11.21 Non-Disruptive Voltage at 1,000msnm (6h min Dry Withstand (kV RMS)) kV 25
11.22 Non-Disruptive Voltage at 5,000msnm (6h min Dry Withstand (kV RMS)) kV 25
11.23 Partial discharges after 6h min Dry Withstand (kV RMS) pC 0.6pC @ 6.3kV
11.24 AMPACITY
11.25 Rated current at 1,000 m.s.n.m. Amp 800Amp
11.26 Short circuit current 40kA
11.27 Temperature rise (Δt with Tamb = 22 ° C @ 800Amp permanent regime)
11.28 Union Pin Contact & Conductor 41°C
11.29 Union Contact Pin & Phase Connector 41°C
11.30 Contact Pin with respect to the conductor at 1mt of the contact pin 36°C
11.31 MIMING CABLE
11.32 Mining Cable Type By Vendor
11.33 Gauge of Power cable MCM By Vendor
11.34 Gauge of Ground Wire AWG By Vendor
11.35 Control pilot cable AWG By Vendor
11.36 Cable O.D mm By Vendor
12.00 ELECTRICAL HOUSE DIMENSIONS
mm
12.01 Total Nominal Length of Electrical House (between axis) By vendor
mm
12.02 Total Nominal Width of Electrical House (between axis) By vendor
12.03 Exterior Overall Total Length of Electrical House mm By vendor
12.04 Exterior Overall Width of Electrical House mm By vendor
mm
12.05 Maximum Overall Exterior Height of Electrical House By vendor
13.00 NOTES
13.01 BE CAREFULL WHEN EDITING DATA SHEETS. INSERT ONLY NECESSARY ADDITIONAL DETAILS FOR DATA AND PLACE THE REVISION CODE AT THE RIGHT MOST BOX

Page 41 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

SUPPLIER/CONTRACTOR: By vendor

PLANT AREA: 1371


MODEL No. / DESIGNATION By vendor

N° DRAWING REFERENCE 9666-SE-02


1.00 SITE CONDITIONS
1.01 Altitude 825 msnm
1.02 Ambient temperature max °C 30
1.03 Ambient temperature min °C 8.4

1.04 Seismic Conditions Peruvian Seismic Code Standard E.030

1.05 Average annual precipitation mm 27.1


1.06 Minimum annual precipitation mm 13.7
1.07 maximum annual precipitation mm 50.5
1.08 Maximum wind speed km/h 90
2.00 STRUCTURAL REQUIREMENTS
2.01 General

2.02 Type of Substation Skid Mounted

2.03 Maximum dimension of skid mounted substation lxbxh (m) By vendor


2.04 Skid platform elevation from grade m By vendor
2.05 Maximum weight of skid mounted substation kg By vendor
2.06 Transformer mounted outdoor on the skid Required

2.07 Electrical room mounted on the skid Required

2.08 Separate Outdoor enclosure for equipment on skid By vendor

2.09 Enclusure protection of electrical room NEMA 4

2.10 Design life of the mobile substation 20 Years

2.11 BASE

2.12 Base Structural Steel Material ASTM A36 rigid H or I or U-Beam

2.13 Runners in each base structure Required

2.14 Minimum thickness of deck plates mm By vendor

2.15 Deck Loading kg / m2 By vendor

2.16 Minimum removable Lifting Lugs / Eyes per substation skid 4

2.17 Skid with E-Room and equipment designed for lifting, towing, skidding, andjacking Required

2.18 Design Safety factor for lifting, towing and skidding facilities 5

2.19 Pulling eyes for towing and skidding Required

2.20 External Finishing Color RAL 1015 (Beige)

2.21 E-ROOM FLOOR


2.22 Floor Color Gray, ANSI 61
2.23 Material Steel Plate

2.24 Material Minimum Thickness mm 6

2.25 Top Surface Coating Non-slip, anti-skid

2.26 E-ROOM WALLS

2.27 Wall Panels Seams Continuously Welded

2.28 External Walls Material Cold Rolled Steel Sheets

2.29 External Walls Material Minimum Thickness mm 1.9


RAL 1015 (Beige)
2.30 External Finishing Color

2.31 Internal Walls Material Cold Rolled Steel Sheets

2.32 Internal Walls Material Minimum Thickness mm 1.5


2.33 Internal Finishing Color RAL 9001 (Off White)
2.34 Penetrations By vendor
2.35 Final Thickness of Walls mm By vendor
2.36 E-ROOM ROOF

2.37 External Roof Cover Material Cold Rolled Steel Sheets

Page 42 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

2.38 External Roof Cover Material Minimum Thickness mm 1.9


2.39 External Roof Cover Panel Seams Continuously Welded
2.40 External Roof Finishing Color RAL 1015 (Beige)
2.41 Slope Downward from middle to side 85 mm per meter
2.42 Sloped housing roof providing full drainage Required
2.43 Internal Ceiling Cover Material Cold Rolled Steel Sheets
2.44 Internal Ceiling Cover Material Minimum Thickness mm 1.5
2.45 Internal Ceiling Finishing Color RAL 9001 (Off White)
2.46 Final Maximum Thickness of Roof @ center Ridge mm By vendor
2.47 Roof Average Design Loading kg / m2 250
2.48 Roof Concentrated Design Loading kg / m2 125
2.49 E-ROOM DOORS
2.50 Material Seamless steel sheets
2.51 Equipment Door Size Height / Width mm By vendor
2.52 Personnel access doors size Height / Width mm 2200/1000
2.53 Stainless steel panic exit hardware w/ quick release latch mechanism to permit Required
2.54 Door locks Required
2.55 Automatic closures Required

2.56 Kick plates Required

2.57 Rain canopy Required


2.58 Doors removable for entering or removing equipments Required
2.59 Door with non-combustible R11 insulation & F60 1-hr fire resistance Required
2.60 Door finishing color (exterior) RAL 5010 (Blue)
2.61 Door finishing color (interior) RAL 9001 (Off White)
2.62 Final Thickness of Doors mm By vendor
2.63 PLATFORMS, STAIRS, FENCE AND GATE
2.64 Platforms and stairs steel structures Required
2.65 Removable serrated type hot-dip galvanized steel grating for landings and stair Required
2.66 Expanded metal mesh steel gratings Not acceptable
2.67 Three level bodyguards removable handrails with kickplates By vendor
2.68 Platforms and stairs steel structures paint finishing color RAL 5010 (Blue)
2.69 Handrails, kickplates and balausters finishing safety color RAL 1023 (Yellow)
2.70 Platforms Average Loading kg / m2 500
2.71 Removable Fence around outdoor equipment on the skid/trailer No Required
2.72 Lockable access gate in the fenced area No Required
2.73 Material of the Fence and Gate No Required
2.74 LIGHTING
2.75 Interior lighting level Lux 500
2.76 Type internal luminaires Fluorescent 2 x 40 W
2.77 External luminaires type HPS, 100 W
2.78 Emergency Lighting Required, By Vendor
2.79 General Purpose Plugs Required, 220 V, 15 A

2.80 DETECTION SYSTEM

2.81 Fire Detection Panel Required


2.82 Optical transceiver Required
2.83 Early detection system Required
2.84 Amount of Early Detection Systems Required
2.85 Smart smoke detectors Required
2.86 Number of Smart Smoke Detectors By vendor, according to NFPA -72
2.87 Manual Stations Required
2.88 Number of manual stations 2 (1 on each door)
2.89 Horn strobe light Required
2.90 Number of sirens strobe 2 (1 outside of each door)
2.91 SUPPRESSION SYSTEM
2.92 System of suppression based on FM-200 Required
2.93 Amount of FM-200 for the total volume of the room (kg) Required
2.94 Manual Abortion Stations Required
2.95 Number of manual abortion stations Required
2.96 Fire extinguishers portable type C02 (15 kg each) Required
2.97 Number of portable fire extinguishers 2 (1 outside of each door)
3.00 ELECTRICAL EQUIPMENT
3.01 PRIMARY POWER SYSTEM

Page 43 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

3.02 Rated Voltage kV 22.9


3.03 Voltage variation % ± 10
3.04 Phase 3
3.05 Frequency Hz 60
3.06 Frequency variation % ±1%
3.07 Short circuit Capacity kA 25
3.08 SECONDARY POWER SYSTEM
3.09 Rated Voltage kV 7.2
3.10 Phase 3
3.11 Frequency Hz 60
3.12 Short circuit Capacity 20 kA
3.13 22.9 kV METAL ENCLOSED INCOMING BREAKER
3.14 Manufacturer By vendor
3.15 Model / Catalog N° By vendor
3.16 Enclosure IEC or Higher
3.17 Type Metal Enclosed
3.18 Rated continuous current A 600
3.19 Maximum Symmetrical Interrupting Capability kA 31.5
3.20 Surge Protection manufacturer By vendor
3.21 Surge Protection Type Polymeric Metal Oxide
3.22 Surge Protection MCOV 24 kVRMS
3.23 Circuit Breaker General Characteristics
3.24 Manufacturer By vendor
3.25 Interrupter Type Vacuum or SF6
Three poles, fixed, electrically
3.26 Circuit breaker Type
operated, stored energy operation
3.27 Number trip coils 2
3.28 Capacitor trips Not Required
3.29 Operation counter Required
3.30 Padlocks Required
3.31 Auxiliary contacts 5 NO + 5 NC
3.32 Interrupting time 5 cycles or less
3.33 Closing time (milliseconds) By vendor

3.34 Opening time (milliseconds) By vendor

3.35 Construction Rating Draw Out


3.36 BIL at sea level kV 125
3.37 Power frequency withstand at sea level By vendor
3.38 Close and trip coils voltage 125 VDC (By buyer)
3.39 Mechanism motors voltage 125 VDC (By buyer)
3.40 Control circuit breakers 125 VDC (By buyer)
3.41 Heaters 220 VAC, 1 phase, 60 Hz (By buyer)
3.42 Motor power consumption By vendor
3.43 Closing solenoid power consumption By vendor
3.44 Opening solenoid power consumption By vendor
3.45 Opening solenoid power consumption By vendor
3.46 Heaters consumption By vendor
3.47 Phase Current transformer
3.48 Quantity 3
3.49 Manufacturer By vendor
3.50 Model / Catalog N° By vendor
3.51 Current ratio 600/300/5 A
3.52 Class By vendor
3.53 Cable Entrance Bottom
3.54 Cable Size By vendor
3.55 Approximate overall dimension (WxDxH) mm By vendor
3.56 Approximate weight (kg) By vendor
3.57 Main Incoming Switch
3.58 Quantity 1
3.59 Model / Catalog N° By vendor
3.60 Rated continuous current A 600
4.00 TRANSFORMER SECTION
4.01 Manufacturer By vendor

Page 44 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

4.02 Type PCB Free Mineral Oil liquid-filled


4.03 Fluid Preservations Systems Sealed tank
4.04 Self cooled capacity (OA - 55° C) @ 1,000 m.a.s.l. (kVA) 10000
4.05 Self cooled capacity (OA - 65° C) @ 1,000 m.a.s.l. (kVA) 10000
4.06 Force cooled capacity (FA - 55° C) @ 1,000 m.a.s.l. (kVA) 12500
4.07 Force cooled capacity (FA - 65° C) @ 1,000 m.a.s.l. (kVA) 12500
4.08 Transformer connection Dyn11
4.09 Primary Voltage (line to line) kV 22.9
4.10 Secondary Voltage (line to line) kV 7.2
4.11 Minimum Primary Bushings (three total) BIL kV 200
4.12 Minimum Primary Winding BIL kV 150
4.13 Minimum Secondary Bushings (four total) BIL kV 95
4.14 Minimum Secondary Winding BIL kV 60
4.15 Impedance on its self cooled capacity (OA - 55°C) 8.5
De-energized tap changer with padlock provision (Four full capacity 2 ½ percent taps, two
4.16 Required
above and two below rated voltage on the 22.9 kV winding)
4.17 Accessories
4.18 Magnetic liquid level gauge with alarm contacts Required
4.19 Oil dial type thermometer with alarm contacts Required
4.20 Winding thermometer (thermal image) with alarm contacts Required
4.21 Pressure vacuum gauge with trip and alarm contacts Required
4.22 Cover vent plug Required

4.23 Pressure test connection Required

4.24 Filling plug and filter press connection Required


4.25 Combination drain valve and bottom filter press connection Required
4.26 Sampling device Required
4.27 Diagrammatic name plate Required
4.28 Manhole or handhole in cover Required
4.29 Provision for lifting and jacking Required
4.30 Neutral resistor 100 A, 10 sec Required
4.31 Current transformer including with neutral resistor 50/5 A Required
4.32 Transformer Losses (Guaranteed)
4.33 Full Load (kW) By vendor
4.34 3/4 Full Load (kW) By vendor
4.35 1/2 Full Load (kW) By vendor
4.36 Transformer Efficiency (Guaranteed)
4.37 Full Load (%) By vendor
4.38 3/4 Full Load (%) By vendor
4.39 1/2 Full Load (%) By vendor
4.40 Approximate overall dimension (WxDxH) mm By vendor
4.41 Base Plate Dimensions and Anchors mm By vendor
4.42 Approximate weight with oil (kg) By vendor
4.43 Approximate weight without oil (kg) By vendor
4.44 TRANSFORMER TESTING
4.45 Normal tests (According to latest revision of IEC Standars)
4.46 Resistance measurements of all windings Required
4.47 Ratio tests Required
4.48 Polarity and phase relation test Required
4.49 No-load loss at rated voltage Required
4.50 Excitation current at rated voltage Required
4.51 Impedance and load loss Required
4.52 Applied potential test Required
4.53 Induced potential test Required
4.54 Mechanical leak test Required
4.55 Temperature test Required
4.56 Impulse test Required
4.57 Quality control impulse test Required
4.58 Front of wave impulse test Required
4.59 DGA FQ Analysis OIL Active Part Required
4.60 Frequency Response Analysis (FRA) in factory Required
4.61 Zero-phase sequence impedance test Required
4.62 Insulation resistance (megger) test Required

Page 45 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

5.00 7.2 kV METAL CLAD SWITCHGEAR


5.01 FEEDER INCOMING

5.02 Manufacturer By vendor


5.03 Model / Catalog N° By vendor
5.04 Enclosure IEC or higher
5.05 Type Metal Clad
5.06 Main Bus Continuous Rating A 1,200
5.07 Quantity 1
5.08 Bus Bracing MVA By vendor
5.09 Circuit Breaker General Characteristics
5.10 Manufacturer By vendor
5.11 Interrupter Type Vacuum or SF6
Three poles, drawout, electrically
5.12 Circuit breaker Type
operated, stored energy operation
5.13 Nominal 3-Phase MVA Class MVA By vendor
5.14 Number trip coils 2
5.15 Capacitor trips Not Required
5.16 Operation counter Required
5.17 Padlocks Required
5.18 Auxiliary contacts 5 NO + 5 NC
5.19 Interrupting time 5 cycles or less

5.20 Closing time (milliseconds) By vendor

5.21 Opening time (milliseconds) By vendor


5.22 Construction Rating Draw Out
5.23 BIL at sea level 95 kV
5.24 Power frequency withstand at sea level 36 kV
5.25 Close and trip coils voltage 125 VDC (By buyer)
5.26 Mechanism motors voltage 125 VDC (By buyer)
5.27 Control circuit breakers 125 VDC (By buyer)
5.28 Heaters 220 VAC, 1 phase, 60 Hz (By buyer)
5.29 Motor power consumption By vendor
5.30 Closing solenoid power consumption By vendor
5.31 Opening solenoid power consumption By vendor
5.32 Opening solenoid power consumption By vendor
5.33 Heaters consumption By vendor
5.34 7.2 kV FEEDER CIRCUIT BREAKERS

5.35 Quantity 3
5.36 Model / Catalog N° By vendor
5.37 Rated continuous current A 1,200
5.38 Surge Protection manufacturer By vendor
5.39 Surge Protection Type Polymeric Metal Oxide
5.40 Surge Protection MCOV 5.1 kV RMS
5.41 Cable Outgoing Bottom
5.42 Cable Size
5.43 Main Incoming Diferential Relay
5.44 Quantity
5.45 Brand Multilin
5.46 Model T60-G00-XXX-XXX-XXX-XXX
5.47 Feeder Relay
5.48 Quantity 3
5.49 Brand Multilin
5.50 Model F60-G00-VFH-F8F-H6E
5.51 Relay Ground-Fault Ground-Check Monitor
5.52 Quantity 3
5.53 Brand Starco
5.54 Model SE 135
5.55 Zero sequence current transformer
5.56 Quantity 3
5.57 Manufacturer By vendor
5.58 Model / Catalog N° Starco SE-CS10
5.59 Current ratio By vendor
5.60 Class By vendor

Page 46 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

5.61 Lock-out relay (ANSI 86)


5.62 Quantity
5.63 Brand By Vendor
5.64 Model / Catalog N° By vendor
5.65 Phase Current transformer
5.66 Quantity 3
5.67 Manufacturer By vendor
5.68 Model / Catalog N° By vendor
5.69 Current ratio 1200/600: 5
5.70 Class By vendor
5.71 Potential transformer
5.72 Quantity 1
5.73 Manufacturer By vendor
5.74 Model / Catalog N° By vendor
5.75 Voltage ratio 7200/120 V
5.76 Class 50VA / 0.2
5.77 7.2 kV METAL ENCLOSED AUXILIARY SERVICES SWITCH
5.78 Manufacturer By vendor
5.79 Quantity 1
5.79 Model / Catalog N° By vendor
5.80 Enclosure IEC
5.81 Type Metal Enclosed
5.82 Rated continuous current A 600
5.83 Maximum Symmetrical Interrupting Capability kA 25
5.84 Surge Protection manufacturer By vendor
5.85 Surge Protection Type Not Required
5.86 Surge Protection MCOV Not Required
Fuses Required
5.87 Switch General Characteristics
5.88 Manufacturer By vendor
Three poles, fixed, operated Without
5.89 Type
Load
5.90 Number trip coils 1
5.91 Padlocks Required
5.92 Auxiliary contacts 5 NO + 5 NC
5.93 Opening time (milliseconds) By vendor
5.94 BIL at sea level kV 125
5.95 Power frequency withstand at sea level By vendor
5.96 trip coils voltage 125 VDC (By buyer)
5.97 Heaters 220 VAC, 1 phase, 60 Hz (By buyer)
5.98 Cable Entrance Bottom
5.99 Cable Size 1 x (3/c N° 120mm + SHD)
6.00 Approximate overall dimension (WxDxH) mm By vendor
6.01 Approximate weight (kg) By vendor
7.00 NETWORK COMUNICATION
Required / 2 Lawer
7.01 Switch
7.02 Model By vendor
7.03 Manufacturer RUGGEDCOM
7.04 Protocol IEC 61850
7.05 Network Ports Single mode 2 chanels
According to IED´s Meters, relay and
7.06 Network Ports
controlers
8.00 PRESSURIZATION AND REFRIGERATION SYSTEM
Required
8.01 Manufacturer
8.02 Model Required
8.03 Catalogue Required
8.04 Positive pressure required mm.c.a 6.35
8.05 Amount of equipment Required
8.06 KW required per equipment Required
8.07 Progressive air filtration Required, disposable and washable
8.08 Calculation memory pressurizing system Required
Required
8.09 Pressurization and refrigeration requirements
8.10 SPARES AND OPTIONAL ACCESSORIES
8.11 22.9 kV Spare Fuses / Quantity Required / 3

Page 47 of 48
10194601-DS-0201.xls
MARCOBRE S.A.C.

MINA JUSTA PROJECT

OFFERED/
DATA SHEET REQUIRED COMMENTS
GUARANTEED
DOCUMENT No: 101946-DS-0201
EQUIPMENT NUMBER/S 1371-SS-102
ELECTRICAL SUBSTATIONS TYPE
EQUIPMENT NAME
MOBILE
CONTRACT PACKAGE TITLE: SEPARATE PORTION 1

8.12 Spare set of all types and ratings of control fuses Required
8.13 One test jumper for electrically operating the breaker while out of its compartment Required
8.14 One levering crank for moving the breaker between test and connected positions Required
8.15 One breaker lifting yoke used for attachment to breaker for lifting breaker on or of compartment rails Required
8.16 One set of rails extensions and rail clamps Required
8.17 One portable lifting device for lifting the breaker on or off the rails Required
8.18 One test cabinet for testing electrically operated breakers outside housing Required
8.19 One "dockable" transport dolly for moving breaker about outside its compartment Required
9.00 BATTERY CHARGER
9.01 Manufacturer By Vendor
9.02 Model / Catalog N° By Vendor
9.03 Type SCR
9.04 Enclosure Nema 12
9.05 Mounting Floor
9.06 Float Voltage (adjustable) V/cell 2.33
9.07 Equalize Voltage (adjustable) V/cell 2.33
9.08 Recharge time (maximum) 8 hours
9.09 Nominal DC Output Current Rating By Vendor
9.10 Maximum ripple 100 mV rms
9.11 Audible noise (maximum) 65 dB at 1.5 m
9.12 Measurement, Protection relays, Control, Alarms and Lights
9.13 Output Voltmeter Required
9.14 Output Ammeter Required
9.15 Low DC Voltage Relay Required
9.16 High DC Voltage Relay Required
9.17 DC Surge Protection Required
9.18 DC Output Circuit Breaker Required
9.19 Electronic short circuit and Overload protection Required
9.20 Manufacturer's multifunction standard control/display Unit Acceptable
9.21 Alarms (minimum)
9.22 AC Failure Required
9.23 DC Failure Required
9.24 High VDC Required
9.25 Low VDC Required
9.26 Ground Detection Required
9.27 Overload Required
9.28 High or Equalize ON Pilot Light Required
9.29 BATTERY SUPPORT
9.30 Type Rack
9.31 Mounting Back to Wall
9.32 Tier Two or Three / By Vendor
9.33 Finish Color ANSI 61
9.34 Dimensions and Weight
9.35 Width (mm) By Vendor
9.36 Height (mm) By Vendor
9.37 Depth (mm) By Vendor
9.38 Weight (kg) By Vendor
9.39 BATTERY BANK
9.40 Type Sealed Maintenance Free
9.41 Application Switchgear Control Power
9.42 Manufacturer By Vendor
9.43 Model / Catalog N° By Vendor
9.44 Cell Container By Vendor
9.45 Time life 20 years
9.46 Nominal Voltage VDC 125
9.47 Maximum Voltage VDC 140
9.48 Minimum Voltage VDC 105
9.49 Equalize Voltage (Volt Per Cell) 2.37
9.50 Flotation Voltage (Volt Per Cell) 2.25
9.51 End-of Discharge Cell Voltage (Volt Per Cell) 1.75
9.52 Minimum Amper-hour Rating Calculated By Vendor
9.53 Amper hour Capacity at 8 hr rate o discharge to 1.75 Volts per Cell By Vendor

Page 48 of 48