Documente Academic
Documente Profesional
Documente Cultură
Summary
1
Location & company information
Location Company
Name ORPIC TX Company Ray International
Region SOHAR Department Service
Division OIL & GAS Address Alquaire
Area SOHAR City Muscat
Plant ORPIC AMP State/Province Muscat
Address Postal code PC:134
City Country Oman
State/Province Oman Phone No.
Postal code Fax No.
Country OMAN E-mail
Geo coordinates
Comment
Voltage ratings
Winding Voltage L-L Voltage L-N Insul. level L-L
Prim 33.000 kV kV kV
Sec 6.900 kV 3.984 kV kV
Power ratings
Rated power Cooling class Temp. rise wind.
8.000 MVA ONAN 58
Winding
Prim Sec Rated power
139.900 A 669.300 A 8.000 MVA
Short-circuit rating
Max. short-circuit current kA s
2
Impedances
Ref. temp. 75 °C
Others
Status In operation
Tank type Nitrogen blanketed
Insulation medium Mineral oil
Fluid insulation volume l
Fluid insulation weight kg
Total weight kg
Pos. Serial No. Manufact. Manufacturer type Man. year Voltage L-ground Max. system voltage Rated current
A kV kV A
B kV kV A
C kV kV A
a1 kV kV A
b1 kV kV A
c1 kV kV A
n1 kV kV A
Pos. Insul. level LL Cap. (C1) PF (C1) Cap. (C2) PF (C2) Insulation type Tap type
A V pF % pF %
B V pF % pF %
C V pF % pF %
a1 V pF % pF %
b1 V pF % pF %
c1 V pF % pF %
n1 V pF % pF %
3
Tap Changers nameplate data
DETC
Serial number
Manufacturer
Manufacturer type
Winding Prim
Tap scheme 1...N
No. of taps 5
Tap Voltage
1 34650.0 V
2 33825.0 V
3 33000.0 V
4 32175.0 V
5 31350.0 V
4
Tx-TTR Prim-Sec
Test voltage 150 V Use CP SB1 Yes
Type of tap changer DETC Mode Auto switching of phases
IEC 61378-1 No
Comments
Standard test
5
6
(2) DC Winding Resistance Prim
Test current 5.0 A Use CP SB1 Yes
Winding temperature 40 °C Mode Auto switching of phases
Temperature corr. factor (K) 1.128
Type of tap changer DETC
Comments
Standard test
1 573.182 mΩ 0.113 % 646.549 mΩ 574.963 mΩ 0.190 % 648.558 mΩ 568.144 mΩ 0.138 % 640.866 mΩ Pass
1 Ω % Ω Ω % Ω Ω % Ω Not ass.
2 548.189 mΩ 0.136 % 618.357 mΩ 553.356 mΩ 0.194 % 624.186 mΩ 549.120 mΩ 0.137 % 619.407 mΩ Pass
3 535.742 mΩ 0.164 % 604.317 mΩ 539.086 mΩ 0.179 % 608.089 mΩ 540.516 mΩ 0.145 % 609.702 mΩ Pass
4 539.478 mΩ 0.169 % 608.531 mΩ 534.441 mΩ 0.146 % 602.850 mΩ 533.867 mΩ 0.131 % 602.202 mΩ Pass
5 536.817 mΩ 0.177 % 605.530 mΩ 531.750 mΩ 0.125 % 599.814 mΩ 525.756 mΩ 0.142 % 593.053 mΩ Fail
5 513.783 mΩ 0.138 % 579.547 mΩ 517.303 mΩ 0.146 % 583.518 mΩ 513.675 mΩ 0.143 % 579.425 mΩ Pass
4 525.475 mΩ 0.159 % 592.736 mΩ 528.354 mΩ 0.143 % 595.983 mΩ 526.773 mΩ 0.137 % 594.200 mΩ Pass
7
DC Winding Resistance Sec
Test current 5.0 A Use CP SB1 Yes
Winding temperature 40 °C Mode Auto switching of phases
Temperature corr. factor (K) 1.128
Type of tap changer None
Comments
Standard test