Sunteți pe pagina 1din 17

1.

8 Wiring Practices and Signal Conditioning


C. H. KIM (1970) R. G. DITTMER (1985) B. G. LIPTÁK (1995, 2005)

INTRODUCTION Although a multitude of signal noise sources exist, the


four main sources are:
Although a variety of signal transmission methods are dis-
cussed in Chapter 3 of this handbook, the majority of mea- 1. Uncontrollable process disturbances that are too rapid
surement signals are still transmitted over wires. These wires to be reduced by control action
can be dedicated or shared as in the case of buses in digital 2. Measurement noise resulting from such factors as tur-
networks, which are described in Volume 3 of this handbook. bulence around flow sensors and instrument noise
Consequently, proper wiring practices play an important 3. Stray electrical pickup, such as from AC power lines,
role in the total performance of process control systems, and pulses from power switching, or RF (radio frequency)
this section is dedicated to that topic. The goal of signal interference
conditioning is to protect the information content of the signal 4. A/D conversion error
from various forms of noise and interference. The types of
noise and some methods of noise protection have already Reduction of Noise
been discussed in Volume 1, in Section 4.13, which covers
Noise adversely affects both analog and digital electronic
the subject of thermocouple noise protection.
equipment, but in digital systems the noise effects are com-
In this section, a systematic discussion of the many aspects
pounded because of the scanning or snapshot nature of digital
of electric signal protection and conditioning will be provided.
systems.
It will start with the definitions of the types of noise encountered
The typical frequency ranges of some noise components
and will continue with the description of many applications of
are shown in Figure 1.8a. Stray electrical pickup can be min-
noise reduction. These discussions will cover the protection of
imized by good engineering and installation practices such as
grounds and wiring, the guarding of amplifiers and power
proper shielding, screening, grounding, and routing of wires.
transformers, common-mode rejection in amplifiers, and the
Even so, noise will still exist at the input, but its effect on the
protection of some specific components, such as thermocou-
controlled and manipulated variables can be significantly
ples, multiplexers, and A/D (analog-to-digital) converters. The
reduced through judicious selection of filtering.
discussion will follow a system approach, which will start from
the transducer through the signal transmission line to the
signal conditioner, multiplexer, and/or A/D converters. Useful Controllable disturbances
information
Uncontrollable disturbances
ELECTRIC NOISE Measurement noise
Noise
Stray electrical pickup
The ability of a process control system to perform is directly
dependent upon the quality of the measured variables. This
quality is dependent upon the elimination or attenuation of Analog filter rejection
All-analog
noise that can deteriorate the actual transducer signal. The Control range
filtering
amount of noise present is expressed as the signal-to-noise Analog filter rejection
Input range
ratio, which is the ratio of signal amplitude to noise amplitude, Analog
& digital Digital filter rejection
where these amplitudes are expressed as either peak or RMS
filtering Control range
values. In the worst case, the noise can actually be of higher
amplitude than the transducer signal. This type of signal, of
course, would be of no value, because its useful control infor- 0 10–4 10–3 10–2 10–1 1 10 102 107
Frequency (Hz)
mation content is undetectable. The wiring practices and sig-
nal conditioning techniques described here are meant to FIG. 1.8a
remove the noise signal from the transducer signal, ensuring Frequency ranges of normal input signals, noise, and different filter
an accurate measured variable signal for process control. types.

71

© 2006 by Béla Lipták


72 General

In most cases, relatively high-frequency noise (i.e., above +


approximately 5 Hz) is removed by conventional analog fil-
ters while the remaining noise occupying the range of 0.002 +
to 5 Hz may require either special analog filtering and/or NMV Device
Input
digital filtering.

It is good practice to follow these three steps to reduce
noise: –

1. Estimate the dynamic characteristics (amplitude and FIG. 1.8c


bandwidth) of the noise. Definition of normal-mode voltage (NMV).
2. Determine its effect on the controlled and manipulated
variables. Interference that enters the signal path as a differential
3. Select the best filtering option (analog and/or digital voltage across the two wires is referred to as normal-mode in-
filtering). terference (Figure 1.8c). The normal-mode noise cannot be
distinguished from the signal, which is coming from the
This section is devoted to a close examination of noise transducer.
suppression techniques. Noise suppression is a system problem, Common-mode voltage is a voltage of the same polarity
and its discussion therefore should not be limited to signal on both sides of a differential input relative to ground
transmission only but must be applied consistently from the (Figure 1.8d). Interference that appears between ground and
transducer through the signal transmission line to the signal both signal leads, as an identical voltage, is referred to as
conditioner, multiplexer, and/or analog-to-digital converters. common-mode interference. Common-mode rejection is the
There are several ways to reduce the effects of noise on ability of a circuit to discriminate against a common-mode
control systems, including line filtering, integrating, digital voltage. This can be expressed as a dimensionless ratio, a
filtering, and improving the signal-to-noise ratio, but none of scalar ratio, or in decibels as 20 times the log10 of that ratio.
these will completely solve the problem without proper cable
selection and installation. Noise Sources
Careful examination of the various sources of noise shows
that some can be eliminated by proper wiring practice. This The most common sources of noise interference are described
implies good temperature compensation, perfect contacts and below:
insulation, carefully soldered joints, use of good-quality sol-
der flux, and use of the same wire material. However, addi- Inductive Pickup This category includes 60-Hz noise from
tional precautions are needed to eliminate pickup noise power lines and 120-Hz noise from fluorescent lighting, as
entirely. well as high-frequency noise generated by electric arcs and
pulse transmitting devices. The worst man-made electrical
Noise Types noise results from the opening or closing of electrical circuits
that contain inductance. The amplitude of the transients gen-
As shown in Figure 1.8b, signal leads can pick up two types of erated in an inductive circuit is given in Equation 1.8(1) below:
external noises: normal-mode and common-mode interference.
Ei = L (di /dt ) 1.8(1)

~ ~ ~
+

Sensor es Signal leads em Measured Device


Signal Input

e″cm –
e′cm
+
~ ~
CMV
Ground
Normal mode noise = em – es –
Common mode noise = e′cm – e″cm

FIG. 1.8b FIG. 1.8d


Electrical noise interference on signal leads. Definition of common-mode voltage (CMV).

© 2006 by Béla Lipták


1.8 Wiring Practices and Signal Conditioning 73

TABLE 1.8e
Average Noise Conditions in Various Industries
Industry

Description Chemical Steel Aerospace

Normal signal levels (mV) 10 to 100 10 to 100 10 to 1000


Possible or expected noise level Normal mode (mV) 1 to 10 2 to 7 1 to 10
Common mode (V) 4 to 5 4 to 5 4 to 5
3 3 3
Desired noise rejection Normal mode 10 :1 10 :1 10 :1
6 6 6
Common mode 10 :1 10 :1 10 :1

This amplitude is calculated as the inductance (L) times Ineffective temperature compensation. Ineffective tem-
the rates of change in the switched current. Closing an induc- perature compensation in transducers, lead wire sys-
tive circuit can cause a transient of twice the input voltage, tems, amplifiers, and measuring instruments can
and opening such a circuit can cause a transient as high as create changes in system sensitivity and drift in their
10 times the supply voltage. When switching inductive loads zero. This is especially important in strain gauge
from an AC supply, the noise transients are proportional to transducers, resistance-type temperature sensors,
the instantaneous value of the AC supply. and other balanced-bridge devices.
Loading the signal source. When a transducer or other
Common-Mode Noise Inadequate common-mode rejection signal source is connected in parallel with an ampli-
due to line unbalance will convert the common-mode noise fier or measuring device with low input impedance,
interference into a normal-mode noise signal. the signal voltage is attenuated because of the shunt-
Table 1.8e shows the average noise conditions that exist ing effect. This can considerably decrease the sen-
in various industries. Some chemical plants have experienced sitivity of the system.
as high as 60 volts common-mode noise interference. Elec- Variable contact resistance. All resistance-type trans-
trical noise interference can be a severe problem in industries ducers, as well as bridge-type circuits, are suscep-
such as steel, power, and petroleum, where power consump- tible to changes in contact resistance. The measuring
tion is high and complex electrical networks exist. instrument is unable to distinguish between a resis-
tance change in the sensor and a resistance change
Other Noise Sources Other noise sources include: in the external wiring.
Conducted AC line transients. Large voltage fluctua-
Failure to distinguish between a ground and a common tions or other forms of severe electrical transients
line. The ground currents that exist in a “daisy- in AC power lines (such as those caused by light-
chain” equipment arrangement are primarily noise ning) are frequently conducted into electronic sys-
signals induced into the equipment, or perhaps gen- tems by AC power supply cords.
erated by some equipment, and they find their way Conduction pickup. Conduction pickup refers to inter-
back to earth. The resulting voltage drops in the fering signals that appear across the input terminals
ground wire place each piece of equipment at a of the receiver, because of leakage paths caused by
different potential with respect to earth. This poten- moisture, poor insulation, etc.
tial difference is easily coupled into the signal lines Thermoelectric drift. The junction of two dissimilar
between equipment. metal wires will create thermoelectric drift, which
Common impedance coupling “ground loops.” Placing varies with changes in temperature. This is more
more than one ground on a signal circuit produces critical in DC circuits, which operate at the micro
a ground loop that is a very good antenna, and noise volt level.
signals induced in the loop are easily coupled into Electrochemically generated corrosion potentials.
the signal lines. This can generate noise that will These potentials can often occur, especially at care-
completely obscure the useful signal. lessly soldered junctions.
Electrostatic coupling to AC signals. The distributed Use of the same common line. Using the same common
capacity between signal conductors and from signal line for both power and signal circuits or between
conductors to ground provides a low-impedance two different signal lines can cause the appearance
path for cross-talk and for signal contamination of transients on the signal and can also cause cross-
from external sources. talk between the two signals.

© 2006 by Béla Lipták


74 General

GROUNDING, WIRING, FILTERING grounding system, no current flows in the ground reference,
and if the signal cable is properly selected, noise due to large
Ground Systems and hard-to-handle low-frequency magnetic fields will not
exist. It should be emphasized that a signal circuit should be
Good grounding is essential for normal operation of any mea- grounded at one point and at one point only, preferably at
surement system. The term “grounding” is generally defined the signal source (Figure 1.8g).
as a low-impedance metallic connection to a properly By connecting more than one ground to a single signal
designed ground grid, located in the earth. In large equipment, circuit, as shown in Figure 1.8f, a ground loop is created.
it is very difficult to identify where the ground is. Two separate grounds are seldom, if ever, at the same poten-
On standard all-steel racks less than 6 ft (1.8 m) in length, tial. This differential generates a current flow that is in series
differences in potential of up to 15 volts peak to peak have with the signal leads. Thus the noise signal is combined with
been measured. Stable, low-impedance grounding is neces- the useful signal. These ground loops are capable of gener-
sary to attain effective shielding of low-level circuits, to pro- ating noise signals that can be 100 times larger than the
vide a stable reference for making voltage measurements, typical low-level signal.
and to establish a solid base for the rejection of unwanted In off-ground measurements and recording, the cable
common-mode signals. shield is not grounded, but it is stabilized with respect to the
In a relatively small installation, two basic grounding useful signal though a connection to either the center tap or
systems should be provided. First, all low-level measure- the low side of the signal source. Appropriate insulation is
ments and recording systems should be provided with a stable needed between the shield and the outside of the cable because
system ground. Its primary function is to assure that elec- the shield is driven by a voltage, which is off ground.
tronic enclosures and chassis are maintained at zero potential. It is important that electric racks and cabinets be con-
A satisfactory system ground can usually be established by nected to a proper system ground and not be allowed to
running one or more heavy copper conductors to properly contact any other grounded element in the building. Guide-
designed ground grids or directly to earth grounding rods. lines on grounding can be summarized as follows:
Signals can be measured with respect to the system ref-
erence ground only if the input signals are fully floating with
respect to ground. In this case, the stable system ground 1. Intentional or accidental ground loops in either the
fulfills the task of providing a base for common-mode noise signal circuit or the signal cable shield will produce
rejection. excessive electrical noise in all low-level circuits and
will destroy the useful signal.
Signal Ground The other important ground is the signal 2. Every low-level data system should have a stable sys-
ground. This system is necessary to ensure a low-noise signal tem ground and a good signal ground.
reference to ground. This ground should be a low-impedance 3. The signal circuit should be grounded at only one
circuit providing a solid reference to all low-level signal sources point.
and thus minimizing the introduction of interference voltages 4. The signal cable shield should not be attached to more
into the signal circuit. than one grounding system.
The signal ground should be insulated from other ground- 5. A floating signal circuit and its signal cable shield
ing systems, and it is generally undesirable to connect it to should always be grounded at the signal source only.
the system ground at any point (Figure 1.8f ). In a single-point

Shield Shield

Floating Floating
Signal Signal
input input
source source
amplifier amplifier

No path for
Circulating current to circulate
current

Potential difference Potential difference

Signal System Signal System


ground ground ground ground

FIG. 1.8f FIG. 1.8g


An example of the incorrect grounding of floating signal circuit. Illustration for showing the correct grounding of a floating signal
The ground loop is created by multiple grounds in a circuit and by circuit. By grounding the shield at the signal end only, the ground
grounding the shield at both ends. loop through the signal lead is eliminated.

© 2006 by Béla Lipták


1.8 Wiring Practices and Signal Conditioning 75

Grounding and Safety A low-resistance, noncurrent-carrying In less demanding low-frequency systems, where the sig-
metallic connection to ground should be established and main- nal bandwidth is virtually steady state and system accuracy
tained from every exposed metallic surface that can possibly requirements are not very high, two-wire signal leads will
become connected to an electrical circuit. Electrical connection normally suffice. Otherwise, a third wire, or shield, becomes
could occur because of a fault, such as a loose wire making necessary.
electrical contact, or as a result of leakage of current through
insulation. Shielding Where top performance is required, the shield is
Grounding is usually accomplished by bonding all ele- run all the way from the signal source to the receiving device.
ments together in a system terminated at the ground connec- As already mentioned, the shield should be grounded at the
tion where power enters the premises. It may be a bare or signal source and not at the receiver because this arrangement
green insulated wire. More often it is the conduit enclosing provides maximum rejection of the common-mode noise.
the wires. It must be securely joined, electrically and mechan- The cable shield reduces electrostatic noise pickup in the
ically, to each piece of equipment. It is connected at the signal cable, improves system accuracy, and is indispensable
service entrance to the grounded circuit conductor (white in low-level signal applications where high source imped-
wire) and to ground. Instead of connection to a ground at the ance, good accuracy, or high-frequency response is involved.
entrance connection, other suitable earth ground connections As the signal frequency approaches that of the noise, which
are acceptable. Equipment mounted directly on the structural is usually at 60 Hz, filtering can no longer be used to separate
steel of a building is considered effectively grounded. Water noise from the useful signal. Therefore, the only practical
pipes have been considered effective grounds. However, solution is to protect the signal lines and prevent their noise
because of the increasing use of plastic pipe for water con- pickup in the first place.
nection, this is no longer an unquestionable ground.
Elimination of noise interference due to magnetic fields
Grounding serves two distinct safety-related purposes.
can be accomplished by wire-twisting (transpositions). If a
First, since the ordinary power circuit has one side grounded,
signal line consisting of two parallel leads is run along with
a fault that results in electrical contact to the grounded enclo-
a third wire carrying an alternating voltage and an alternating
sure will pass enough current to blow a fuse. Second, the
current, the magnetic field surrounding the disturbing line
possibility of a shock hazard is minimized since the low-
will be intercepted by both wires of the signal circuit. Since
resistance path of a properly bonded and grounded system
these two wires are at different distances from the disturbing
will maintain all exposed surfaces at substantially ground
line, a differential voltage will be developed across them. If
potential.
the signal wires are twisted (Figure 1.8h), the induced dis-
Grounding is effective against hazards from leakage cur-
turbing voltage will have the same magnitude and cancel out.
rents. All electrical insulation is subject to some electrical
leakage. This may rise to a significant level as insulation
deteriorates with age or as layers of conductive dust accu-
mulate in the presence of high humidity. A proper grounding IN Disturbance wire
system with low electrical resistance will conduct leakage
currents to ground without developing significant potential C1 C2 d1 d2

on exposed surfaces. Signal Ecm


Ia Em Amplifier
Grounding of exposed metal surfaces is distinct from the source
grounded conductor of ordinary power wiring. The latter is
a current-carrying ground, capable of developing significant
Ground
potential, particularly on long lines and with surge or even Where d1 ≠ d2. Thus, C1 ≠ C2, ∴ difference in distance from disturbance
short-circuit currents. Grounding systems are substantially wire creates a differential voltage, and a noise signal will be induced into
noncurrent carrying, except for possible leakage currents. the signal leads.
Potential can build up only during the time required for IN Disturbance wire
a fuse to blow as a result of a specific fault that results in C1 C2 d
1 d2
direct contact between power and grounding systems.
Grounding is customarily not required for signal circuits Signal Amplifier
source
where either maximum voltage is 30 V, or maximum current
under any circumstance cannot exceed 5 mA.
Ground
Where d1 = d2. Thus C1 = C2, ∴ the induced disturbing voltages
Wiring will have the same magnitude and cancel out when twisted wires
are used.
Another important aspect of reducing noise pickup involves FIG. 1.8h
the wiring system used to transmit the signal from its source The use of twisted wires eliminates the noise interference that might
to the measuring device or computer. otherwise be caused by the magnetic fields of disturbing wires.

© 2006 by Béla Lipták


76 General

In order to prevent noise pickup from electrostatic fields,


an effective shield must surround the low-level signal con- 4 C14 C24
2
ductors. One type of shield consists of a woven metal braid
around the signal pair, which is placed under an outside layer 1
of the insulation. This type of shield gives only 85% coverage
of the signal line and is adequate for some applications if the
signal conductors have at least ten twists per foot (33 twists
per meter). Its leakage capacity is about 0.1 picofarad per
foot (0.3 picofarad per meter).
3
At the microvolt signal levels, this kind of shielding is
C34
not satisfactory. Another type of signal cable is shielded with
a lapped foil (usually aluminum-Mylar tape) type shield, plus
a low-resistance drain wire. This type of shielding provides
100 % coverage of the signal line, reducing the leakage capac- FIG. 1.8i
ity to 0.01 picofarad per foot (0.03 picofarads per meter). To When the shield is ungrounded, the single-ended amplifier will
be most effective, the wires should have six twists per foot receive feedback currents.
(20 twists per meter).
The lapped foil shield is covered with an insulating jacket
to prevent accidental grounding of the shield. Care should be 4 C14 C24
2
exercised to prevent the foil from opening at bends.
This type of low-level signal cable provides the following 1
benefits:

1. There is an almost perfect shield between the signal


leads and ground. 3
3
2. Magnetic pickup is very low because the signal leads C34
are twisted. C45
3. Shield resistance is very low because of the low- 5
resistance drain wire.
FIG. 1.8j
The feedback current problem is not solved by grounding the com-
Feedback Currents and Shield Grounding In most measure-
mon conductor if the shield is not grounded.
ments a voltage difference is detected relative to a reference
potential. This is usually achieved by sending the signal
through an amplifier, which provides the required gain. Such Digital Communication Shielding Some 20 digital control
single-ended amplifiers will change the measurement signal system buses are in use worldwide. Table 1.8l lists their
in relation to the same reference potential, which is main- requirements for shielding. Most use unshielded twisted pair
tained both at their inputs and outputs. wiring (UTP). While only a minority requires the use of
With charge- and voltage-detecting single-ended amplifi- shielded twisted pairs (STP), shielding will improve the per-
ers, the nonsignal related and unbalanced current flow, which formance of all of them.
is normal-mode noise pickup and is flowing in the zero refer-
ence conductor, must be limited. When such an amplifier and 4 C24
its power supply are suspended within a shield that they do 2
not contact, capacitive couplings will occur. As it is shown in 1
Figure 1.8i, because these couplings are at different voltages,
they will cause a current flow back to the inputs (feedback) of
the amplifier.
If the signal zero reference is grounded (as in Figure 1.8j)
and allowing the shield to float does not solve the problem. 3
This is because a current flow will be produced in the input
side of conductor 3 by the potential difference of the earth
between conductor 3 and the shield capacitance at the oppo-
site end.
Figure 1.8k shows the solution to eliminating such feed- FIG. 1.8k
back currents. Directly referencing the signal common to the The solution is to properly ground both the shield and the common
shield will eliminate the capacitive feedback to the amplifier. conductor.

© 2006 by Béla Lipták


1.8 Wiring Practices and Signal Conditioning 77

TABLE 1.8l
Digital Network Cable Specifications
Network Name Associated Standards Cable

PROFIBUS DP/PA EN 50170/DIN 19245 part 3 (DP), UTP


part 4(PA), IEC 1158-2(PA)
INTERBUS-S DIN 19258, EN50.254 UTP
ControlNet COAX
DeviceNet ISO 11898 and 11519 UTP, COAX
Remote I/O UTP
ARCNET ANSI/ATA 878.1 UTP
AS-I UTP
Foundation Fieldbus—H1 ISA SP50/IED 61158 UTP
Foundation Fieldbus—HSE IEEE 802.3u, TCP and UDP UTP
IEC/ISA SP50 Fieldbus IEC 1158/ANSI 850 UTP
Seriplex 4 wire shielded
WorldFTP IEC 1158-2 UTP
SDS ISO 11989 UTP
CANopen UTP
Ethernet IEEE 802.3 UTP
Modbus Plus UTP
Modbus EN 1434-3, IEC 870-5 UTP
Genius Bus STP

Often, whole cabinets or complete rooms are also shielded. serious limitation is in obtaining or selecting a single ground
Raised computer floors with electrically bonded stringers are point. If the conduit could be insulated from its supports, it
regularly used to help with this task. Zero signal reference would provide a far better electrostatic shield. The following
grids (ZSRG) are also provided by such building structural general rules should be observed in installing low-level signal
elements as Q-decking and rebar. The proper bonding of non- circuits:
continuous grids, the use of special gaskets, and wave-guide
ventilation covers are usually also desirable. 1. Never use the signal cable shield as a signal conductor,
Shielded rooms should usually be grounded at a single and never splice a low-level circuit.
point with respect to the outside world. This requires the 2. The signal cable shield must be maintained at a fixed
installation of surge protectors so that bridging is provided potential with respect to the circuit being protected.
for the isolation gaps during lightning strikes. 3. The minimum signal interconnection must be a pair
of uniform, twisted wires, and all return current paths
Wire Costs and Installation Typical costs of the three types must be confined to the same signal cable.
of twisted signal wires are shown in Table 1.8m. The use of 4. Low-level signal cables should be terminated with
ordinary conduit is not likely to reduce noise pickup. Its short, untwisted lengths of wire, which expose a min-
imum area to inductive pickup.
5. Reduce exposed circuit area by connecting all signal
pairs to adjacent pins in the connector.
TABLE 1.8m
Costs of Three Twisted Signal Wire Designs 6. Cable shields must be carried through the connector
on pins adjacent to the signal pairs.
Recommended for Cost ($) 7. Use extra pins in the connector as a shield around
the Following Type Single Pair per Foot
Noise Source Cable Type (per Meter)
signal pairs by shorting pins together at both ends and
by connecting to the signal cable shield.
Magnetic fields Twisted .20 (.60) 8. Separate low-level circuits from noisy circuits and
Magnetic and Twisted with metal braid; 85% .40 (1.20) power cables by a maximum physical distance of up
electrostatic shield coverage to 3 ft (0.9 m) and definitely not less than 1 ft (0.3 m).
Magnetic and Twisted with aluminum/Mylar; .25 (.75) 9. Cross low-level circuits and noisy circuits at right
electrostatic 100% shield coverage angles and at the maximum practical distance.

© 2006 by Béla Lipták


78 General

10. Use individual twisted shielded pairs for each trans- Inductance-capacitance
ducer. Thermocouple transducers may be used with filter
a common shield when the physical layout allows
Signal L Amplifier
multiple pair extension leads. C
source L
11. Unused shielded conductors in a low-level signal
cable should be single-end grounded with the shield
grounded at the opposite end. Signal System
ground ground
12. High standards of workmanship must be rigidly
enforced. FIG. 1.8o
The use of an inductance–capacitance filter reduces the time delay
while maintaining filtering efficiency.
Filtering

Filtering is required to stabilize the input signal and to remove APPLICATIONS


AC noise components (particularly 60-Hz noise) resulting
from direct connection of normal-mode AC signals, from The following paragraphs discuss the application of noise
normal-mode noise pickup, or from conversion of common- protection techniques to transducers, thermocouples, multi-
mode noise to normal-mode noise due to line unbalance. plexers, and A/D converters.
A reliable, low-cost, and effective filter for analog inputs
is the balanced resistance–capacitance filter, shown in Transducer Signals
Figure 1.8n. Its ability to eliminate AC components increases
exponentially with the frequency of the noise signal compo- The common-mode rejection of a good low-level signal ampli-
6
nents. Common-mode noise rejection of about 40 decibels is fier is on the order of 10 to 1. This value is always decreased
possible with this type of filter, with decibel defined as when the signal source and input signal leads are connected to
the amplifier. Signal source impedance and signal lead imped-
ance have a shunting effect on the signal input to the amplifier.
inlet noise amplitude From the point of view of maximum power transfer, equal
decibel = 20 log 1.8(2)
outlet noise amplitude impedance on both sides of a circuit is an ideal termination.
In the transmission of voltage signals, however, current
flow has to be reduced to as close to zero as possible. This
Filtering action causes a time delay (time constant, T =
is achieved by selecting amplifiers with high input impedance
RC) between a signal change at the transducer and the time
and using transducers with low output impedance. Good
of recognition of this change by the measuring device. As
instrumentation practice dictates that the input impedance of
the time delay may be on the order of 1 s or more, there are
the amplifier be at least ten times the output impedance of
situations in which this has to be reduced (systems with high-
the signal source.
frequency response). In order to decrease only the time delay
However, low signal source impedance has an adverse
but not the filtering efficiency, inductance–capacitance filters
effect on the pickup signal, because the low impedance of
may be used (Figure 1.8o). This increases the filter cost.
the transducer will shunt it. An additional step is to ground
Since a filter limits the bandwidth of the transmitted
the transducer whenever possible and to run a balanced signal
signal, it might be desirable to use more complicated and
line to the amplifier input.
expensive filters when higher-frequency AC transducer sig-
There are three basic techniques to condition transducers
nals are involved. Fortunately, this type of situation seldom
with high output impedance: high-impedance voltage ampli-
occurs.
fiers, charge amplifiers, and transducer-integrated unloading
amplifiers.

Resistance-capacitance Voltage Amplifiers Voltage amplifiers must have an ampli-


filter fier input impedance that is very high compared with the
source impedance. In this way, the amplifier’s effect on the
Signal R
C Amplifier phase and amplitude characteristics of the system is mini-
source R
mized. A typical transducer with output amplifier is shown
in Figure 1.8p. High impedance is practical for an amplifier,
Signal System but an equally significant portion of the load is in the inter-
ground ground connecting cable itself, and it does not take much cable to
FIG. 1.8n substantially lower the available voltage.
For analog signals, a low-cost and effective filter design is the In applying a voltage amplifier, low-frequency system
balanced resistance–capacitance one. response must be considered. The voltage amplifier input

© 2006 by Béla Lipták


1.8 Wiring Practices and Signal Conditioning 79

Ct Output
Es ~ Cc Ca Ra
EIN
Transducer Voltage amplifer
input
Remote amplifier Coupler

FIG. 1.8p FIG. 1.8r


A typical transducer with voltage output amplifier. Es = transducer In comparison to voltage or to charge amplifiers, the unloading
voltage source; Ct = transducer capacitance; Cc = signal cable amplifier, which is located at the transducer, reduces the input
shunt capacitance; Ca = amplifier input capacitance; Ra = amplifier capacitance.
input resistance.

resistance (Ra ) in combination with the total shunt capaci- available from transducer manufacturers because neither volt-
tance forms a high-pass first-order filter with a time constant age amplifiers nor charge amplifiers offer a very satisfactory
(T ) defined by solution to the conditioning problem for systems with very
high input capacitance (usually a result of very long lines).
T = Ra (Ct + Cc + Ca ) 1.8(3) With the voltage amplifier, signal-to-noise ratio suffers,
because capacitance loading decreases the available signal. In
Cut-off frequency can become a problem when it
a charge amplifier, the signal-to-noise ratio suffers because of
approaches information frequency at low source capacitance
the increased noise level (input noise is a direct function of
(short cable or transducers with very low capacitance) or at lower
input capacitance). Thus, remote signal conditioning appears to
amplifier-input resistance.
offer a satisfactory solution to the accommodation of long data
lines. If closely located to the transducer, voltage-responding
Charge Amplifiers Charge amplifiers have been widely
or charge-responding amplifiers are equally effective.
used in recent years. This approach avoids the cable capaci-
However, these techniques decrease the dynamic range
tance effects on system gain and frequency response. The
capability (changing input amplifier gain to accomplish a
typical charge amplifier shown in Figure 1.8q is essentially
range change is not possible) and restrict the high-frequency
an operational amplifier with integrating feedback. A charge
response signal amplitudes due to the limited current capa-
amplifier is a device with a complex input impedance that
bility of the remote amplifier. When these two limitations are
includes a dynamic capacitive component so large that the
overcome, almost all of the signal-conditioning equipment
effect of varying input shunt capacitance is swamped, and will be at the remote location.
the output is the integral of the input current.
In summary, the following steps are recommended for
Filtering of the resultant signal on both the low and high low-level signals:
ends of the information band is desirable at times so that it
is possible to get a rather high order of rejection without
1. Select a signal source with low output impedance.
affecting information by using band pass filters. The addition
2. Select an amplifier (or measuring device) with high
of a resistor in parallel with the feedback capacitor in a charge
output impedance.
amplifier will decrease the closed-loop gain at low frequen-
3. Use a balanced line from signal source to amplifier
cies, resulting in the desired high-pass filter characteristics.
input (maximum allowable unbalance is 100
ohm/1000 ft or 0.33 ohm/m).
Unloading Amplifiers Unloading amplifiers integrally
4. Keep signal cables as short as possible.
mounted in a transducer housing (Figure 1.8r) have become
5. Use remotely located amplifiers when long signal
cables are required (except for thermocouple and RTD
signals).
Cf 6. Select a signal source that can be grounded (thermo-
Output
–A couples, center-tapped sensors, etc.).
Is ~ Ct Cc
It is evident that common-mode rejection must be main-
tained at a high level in order to attain noise-free results from
Transducer Charge amplifier low-level signal sources.
FIG. 1.8q
Transducer with charge output amplifier. Is = transducer current Differential Amplifier An example where two zero refer-
source; Cf = feedback capacitance; Ct = transducer capacitance; ences exist is a detector in a self-powered transmitter, which
Cc = signal cable shunt capacitance. is interfaced to a digital I/O system. Other systems requiring

© 2006 by Béla Lipták


80 General

Differential amplifier Measurement


Shield (Isolator) Shield equipment
A
Transducer Signal Rc
source
B

Ecm Cg Rg
Guard shield
C D

Signal ground System ground


FIG. 1.8s
The application of a differential amplifier, which is also called an FIG. 1.8u
isolator. The design of a guard-shielded measuring system. Rc = cable unbal-
ance resistance; Cg = measuring circuits/system ground capaci-
tance; Rg = measuring circuits/system ground resistance; Ecm =
differential amplifiers are grounded thermocouples, strain common-mode voltage.
gauges, and data link applications.
It often happens that a common signal is the I/O reference
to earth, while a self-powered transmitter generates an output, cable shield are stabilized with respect to the signal
which is referenced to the ground of its own power supply. from the source.
The difference between the zero references of the I/O and 3. Connect the signal cable shield and its tap to the signal
the transmitter’s power supply will appear as common mode source and also to the signal ground, which should be
noise, which can cause normal-mode pickup. as close as possible to the signal source. This will limit
In such cases, one should use a differential and not a the maximum common-mode voltage. The signal pair
single-ended I/O. If a differential I/O cannot be used, an must not be connected to ground at any other point.
external differential amplifier, also called an isolator, can be 4. Connect the amplifier chassis, the equipment enclo-
installed in the signal lines. In that case, each side of this sure, the low side of amplifier output, and the output
isolator should be independently shielded and each shield cable shield to the system ground.
should be grounded to its respective signal ground. Figure 1.8s
illustrates the application of a differential amplifier. Power Transformer Guard It is important to avoid strong
magnetic fields emanating from the power supply trans-
Amplifier Guard In a normal measuring device, a signal line former. To avoid capacitive coupling, the transformer should
is connected to a differential DC amplifier with floating inputs. be provided with at least two or three shielding systems. The
Generally, these amplifiers are provided with an internal float- third or final shield should be connected to the power supply
ing shield that surrounds the entire input section, as shown output common. The inner shield should be connected to the
in Figure 1.8t. This floating internal shield is called a “guard signal ground.
shield” or simply a “guard.”
The guard principle requires that the amplifier guard be Common-Mode Rejection Measurement
driven at the common-mode voltage appearing at the ampli- A typical configuration of a guard-shielded measuring system
fier inputs. The most effective way to do this is as follows: is shown in Figure 1.8u. The common-mode rejection of the
system is measured by taking the ratio of the common-mode
1. Connect the amplifier guard to the signal cable shield voltage (Ecm between points C and D) divided by the portion
and make sure that the cable shield is insulated from of Ecm that appears at the amplifier inputs A and B. Almost
the chassis ground or from any extension of the system all of the remainder of the voltage Ecm will appear across Cg
ground. and Rg, in which case the common-mode rejection (CMR) is
2. Connect the ground of the signal source to the signal approximately:
cable shield. In this way, the amplifier guard and signal
CMRAC = 1/2FCgRc 1.8(4)
CMRDC = Rg /Rc 1.8(5)
Preamplifier Amplifier guard shield
Amplifier It can be seen from these relations that the common-mode
Shield
rejection is dependent on the value of Rc, which is the unbal-
High
Signal ance of the transducer and signal lines. In an ideal case, when
source Low Rc is zero, the common-mode rejection will be infinite.
Measuring by direct methods that portion of Ecm that
Signal System appears across Rc is not possible since it is unlikely that any
ground ground
instrument could be connected to the source to measure the
FIG. 1.8t voltage across Rc without also changing the current through
Correct grounding of an isolating amplifier. it. Thus, when testing the guarding of a system, the component

© 2006 by Béla Lipták


1.8 Wiring Practices and Signal Conditioning 81

rejection will be the product of the actual common-mode


Digital rejection and the filter rejection. In the earlier example, if a
Signal
source
volt filter with 10:1 normal-mode rejection were inserted in front
meter
of the amplifier input, the apparent common-mode rejection
7
Signal
would increase to 10 :1 (Ref. 2).
generator
100 V, 60 HZ
System ground
Thermocouple Signals
Signal ground
(disconnected)
The thermocouple signal is very weak — a 1-degree change
FIG. 1.8v in temperature results in only a few millionths of a volt
A method for measuring common-mode rejection. change in output. Because of this, precautions must be taken
against errors due to stray currents resulting from the prox-
due to Ecm at the amplifier output is measured. This value is imity of electrical wiring (common-mode noise) or from
divided by the amplifier gain, and it is assumed that the quo- capacitive secondary grounds (normal-mode interference).
tient is a good measure of the voltage across Rc.
A practical setup for measuring rejection in a common- Common-Mode Noise Common-mode noise (Figure 1.8w)
mode system is shown in Figure 1.8v. With the signal source appears on both thermocouple signal wires and therefore can
disconnected from the signal ground, a 100-V, 60-Hz signal be filtered out as 60-Hz (or 50-Hz) harmonic noise.
from a signal generator is applied between the system ground The filter does reduce the interference dramatically, but
and signal source. The change in the digital voltmeter (DVM) it also causes the voltmeter to be sluggish when responding
reading will show the effect of this common-mode signal on to a step change. It is also possible to eliminate the common-
the system. To obtain the effective voltage across the amplifier mode interference by using twisted wire leads, because each
inputs, this change is divided by the amplifier gain. The com- time the wire is twisted, the flux-induced current is inverted.
mon-mode rejection is then obtained by dividing the signal Another recommended form of protection against any
generator voltage with the assumed voltage at the amplifier type of common-mode noise is guarding and shielding. If the
input. For example, shield surrounding the lead wires is connected to the guard
surrounding the voltmeter, the interfering current caused by
Amplifier gain (G) = 1000 AC interference does not flow through the thermocouple lead
Signal generator voltage (E′cm) = 100 V resistance but instead is shunted.
DVM reading before applying Ecm (e′cm) = 2.0 V Naturally, when thermocouples are scanned, the scanner
guard must be switched to the shield of the thermocouple
DVM reading after applying Ecm (e′′cm) = 2.1 V
being read to eliminate ground loops. Harmonics can also be
removed by integrating the incoming signal over the power
The increase in voltage at the amplifier output (ecm) due
line cycle in an integrating analog-to-digital converter or
to Ecm is:

ecm = ecm
′′ − ecm
′ = 2.1 − 2.0 = 0.1 volts 1.8(6)
HI
The voltage at the amplifier input (e′cm) due to Ecm is: + Rs −
LO

′ =
ecm
ecm
=
0.1
= 0.0001 volts 1.8(7)
~
G 1000
Therefore, the common-mode rejection of the system is:
Normal mode
E 100 1, 000, 000
CMR = cm = = = 10 6 : 1 1.8(8)

ecm 0.0001 1
HI
When dealing with AC common-mode signals applied to
DC measuring instruments, it is important to consider the effect ~
of inherent noise rejection in the measuring instrument (or LO
amplifier). Many DC instruments have an input filter that
allows the undisturbed measurement of DC signals in the pres- Common mode
ence of AC noise. Such instruments are said to have normal- FIG. 1.8w
mode interference rejection. Normal-mode noise that enters only one of the lead wires is more
Thus, if common-mode rejection is measured by the indi- difficult to remove than common-mode noise, which acts on both
rect method just described, the apparent common-mode leads.

© 2006 by Béla Lipták


82 General

it can only be separated from the useful signal by selective


240 VRMS filtering.
Thermocouple signals are susceptible to noise problems
because they are often in contact with the process or structure
being measured. Additional thermoelectric potentials devel-
oped in the bimetallic leads should be accounted for when
measuring a signal from a thermocouple. The best thermo-
couple materials are not the best electrical conductors, yet
HI lead wires must be made of thermocouple materials all the
Rs way back to the reference junction.
LO
120 VRMS ∼ Cstray
To eliminate the need to account for each bimetallic wire
junction, one can compare the output of the thermocouple
Noise current
with the output of an identical thermocouple in a controlled-
temperature environment. The balance of the circuit in that
case can be made of copper wires creating an identical couple
HI
in each lead and producing a zero net effect when both
Rs
LO couples are at the same temperature.
The use of a constant-temperature reference junction is
∼ Guard the most accurate method of compensation, but it is not the
Noise most convenient. A simulated constant-temperature reference
current
can be obtained with devices containing compensating junc-
tions, millivolt sources, and temperature-sensitive resistors.
FIG. 1.8x
3 These devices can also permit the use of copper lead wires
The normal-mode noise is reduced by the addition of a guard wire.
instead of thermocouple leads.
A more complex conditioning circuitry is shown in
voltmeter. In short, common-mode noise is relatively easy to Figure 1.8y, which performs the functions of thermocouple
remove. signal conditioning, noise discrimination, balancing, ranging,
and standardizing. This circuit must be tied to a calibration
scheme for the system output. The balance circuit shown
Normal-Mode Noise The same cannot be said about normal-
accomplishes both variable offset and calibration.
mode noise. Normal-mode noise interference can occur in the
The signal-conditioning circuitry makes it possible to
measurement of the temperature in a molten metal bath, which
convert the transducer output to make use of the optimum
is heated by electric current. In this case, the thermocouple
range of the measuring system for the best linearity, accuracy,
junction is in direct contact with a common-mode noise source.
and resolution.
In addition, the capacitive ground (C-stray) from the LO ter-
Because thermocouples are often in electrical contact
minal of the thermocouple to the chassis causes a current flow
with the device or structure of which the temperature is being
in the low lead and an associated normal-mode noise voltage
measured and with an intentional ground at the sensor, dif-
across the resistance Rs (Figure 1.8x).
ferential input amplifiers with very good common-mode
If a guard lead wire is connected directly to the thermo-
rejection are required to effectively discriminate against noise
couple, the current flowing in the LO lead through the resis- 1
in the structure or grounding system.
tance Rs is drastically reduced. Therefore, the worst form of
interference is DC offset caused by a DC leakage current;
Low-Level Signal Multiplexing
whatever normal-mode noise remains in the system cannot
be distinguished from the measurement and, in case of weak Conventional noise rejection techniques, such as twisting
signals, even a small amount of noise can represent a large leads, shielding, and single-point grounding, have been dis-
amount of interference. cussed. It was pointed out that input guarding involves isolating
the transducer input signal from the common-mode voltage
Complex TC Conditioning One of the important practices between signal leads and ground. This change from differential
in eliminating noise in low-level signal systems is the to single-ended signal can occur at any place in the system
arrangement of external circuits so that noise pickup will after the multiplexer. Early versions of multiplexing systems
appear equally on both sides of the signal pair, remain equal, employed crossbar switches, relays, and similar electrome-
and appear simultaneously at both input terminals of the chanical devices for low-level input signal multiplexing.
differential amplifier (or measuring device). In this case it
can be rejected by common-mode protection without affect- Electromechanical Multiplexing Mercury-wetted relays,
ing the frequency response or the accuracy of the system. If which are actuated by rotating magnets, can be used as elec-
a noise signal is allowed to combine with the useful signal, tromechanical multiplexers. They have the advantage of high

© 2006 by Béla Lipták


1.8 Wiring Practices and Signal Conditioning 83

Iron

Hot measurement junction


Rq Rs Output
Constantan Iron
R1 R2
Cold Rc E Rf
reference
junction Constant
temperature
reference

FIG. 1.8y
A complex thermocouple conditioner performs the functions of TC signal conditioning, noise discrimination, balancing, ranging, and
standardizing. E = a precision isolated power supply; R1 and R2 = precision bridge resistors, low values (5 or 10 ohms); Rc = balance
control variable resistor, large resistance value; Rf = reference resistor, large resistance value; Rq = equivalent line resistor for use during
stabilizing and calibrating; Rs = span adjustment potentiometer.

14
cross-talk isolation, because of their high (10 ) ratio of open- Three multiplexing techniques are commonly used: (1)
circuit to closed-circuit resistance. They are also accurate flying capacitor multiplexer, (2) three-wire multiplexer, and
because of their very low contact resistance. (3) solid-state multiplexer.
Their disadvantages include their low speed (a few hundred
points per second) and their vibration sensitivity, if it exceeds
0.75 g. DCS multiplexers, operating on analog process signals, Flying Capacitor Multiplexing The capacitive-transfer (fly-
in the past often used such electromechanical multiplexers. ing capacitor) switching arrangement, shown in Figure 1.8aa,
is simple, economical, and capable of great noise rejection
Passive Filter Multiplexing A simple passive filter (RC) (including random noise spikes). This system is limited to
circuit, as shown in Figure 1.8z, can be designed to reject applications where signal bandwidth requirements are narrow
common-mode noise from about 40 decibels, at the selected (on the order of 0.5 to 1 Hz), due to a necessarily large
frequency. More sophisticated passive networks (such as par- transfer capacitance to minimize the effect on system reso-
allel T or notch filters) improve noise rejection, but it is hard lution of charge losses and of delays during charging, settling,
to obtain 60-decibel noise rejection with passive circuits. and digitizing.
Because of deficiencies in the noise rejection capabilities In the capacitive transfer circuit, between scans, a set of
of the earlier approaches, the limitations in scan rates, and normally closed contacts connects the low-leakage transfer
the ever-increasing use of data acquisition systems, many capacitor across the input signal. Common practice is to short
devices have been developed with extended capability to the amplifier input during this between-scan period to avoid
cover the spectrum of present-day requirements. Each general stray pickup (due to a high-impedance open circuit).
category contains subsets of devices using the same basic When the multiplexer selects the input for scan, the
switching element but offering application-dependent varia- amplifier input short is removed, and the contacts switch to
tions. The most important variations are the programmable connect the transfer capacitor to the amplifier input. This
range (i.e., gas chromatograph signal) switching and input transfer circuit introduces input attenuation and phase lag,
grounding. which must be considered in circuit design. An additional

Noise filter
Noise filter
Input Transfer
Input channel “A”
channel “A” capacitance
(not on scan)
(not on scan)
Low-level
Low-level
amplifier
amplifier
Input
Input channel “B” To A/D
channel “B” To analog-to-
(on scan) converter
(on scan) digital
converter
Additional
Additional
channels
channels

FIG. 1.8z FIG. 1.8aa


Circuit showing the passive filter multiplexer. Circuit describing the flying capacitor multiplexer.

© 2006 by Béla Lipták


84 General

Guard To output
register
Input
amplifier
Analog-to-
Input digital
converter
Channel
“A”

6 Additional Pulse
mercury wetted transformer
or reed relays

To relay Timing
coils and
Input control
To additional
Channel
multiplexer
“B” modules
8-Channel
multiplexer module

FIG. 1.8bb
Circuit describing the three-wire multiplexer, which provides high common-mode voltage rejection.

RC filter is usually necessary to achieve acceptable common- the address of the next channel can be programmed in any
mode rejection of 100 to 120 decibels. order desired.
A solid-state multiplexing system is shown in
Three-Wire Multiplexing The three-wire multiplexing sys- Figure 1.8cc. In a typical high-performance solid-state mul-
tem requires the transducer lead wires to be shielded with tiplexer, each input has a matched pair of transistor switches
the shield terminated at the signal ground. This guard shield terminating at the primary of shielded input transformers,
must be carried through the multiplexer, at each point, up which are driven through an isolation transformer. One cycle
where the differential signal is transferred to a ground-refer- of a square wave of peak amplitude equal to the input signal
enced signal. level is transferred across the transformer by alternately puls-
In Figure 1.8bb the input amplifier and analog-to-digital ing the switches.
converter are enclosed within the guard. The serial digital
data are transmitted through a shielded pulse transformer to Channel address
an output register for presentation in parallel form. Relay (phase 1)
coils are matrixed and controlled by address logic.
This system is used when input signal bandwidths of
several hertz are required, since filtering is not essential to
obtain good common-mode rejection. Common-mode rejec-
tion from DC to 60 Hz is about 100 decibels at reduced input To A/D
bandwidth. converter
Low-level
input Integrate
Solid-State Multiplexing Compared to electromechanical and hold
multiplexers, solid-state units do not have speed- or vibration- amplifier
related limitations, but their early models did suffer from
cross-talk due to their low open-circuit resistance. The
Multiplex
switches in most newer multiplexers are MOSFET (metallic bus
oxide semiconductor field-effect transistor) and are satisfac-
tory for multiplexing digital signals. The costs of solid-state Channel address Channel address
multiplexers using large-scale IC (integrated circuitry) cir- (phase 2) (both phases)
cuits is lower than that of the electromechanical ones. Simi- FIG. 1.8cc
larly, their power consumption and size are also smaller. Solid-state multiplexing system for high common-mode rejection
Another advantage is that because their switching is electronic, provided with integrate and hold amplifier.

© 2006 by Béla Lipták


1.8 Wiring Practices and Signal Conditioning 85

TABLE 1.8dd
Feature Summary of Commonly Used Multiplexers
Features Capacitive-Transfer Three-Wire Solid-State

Cost Low Low High


Input signal ranges ±50 to ±500 mV ±5 mV to ±5 V From 5 mV full scale to 100 mV
full scale
a
Scan rates (points per second) Up to 200 Up to 200 Up to 20,000
Operable common-mode Up to 200 to 300 Up to 200 to 300 Up to 500
environment (volts)
b
Common-mode rejection 100 to 120 100 to 120 120
from DC to 60 Hz (decibels)
±0.1% full scale at 1 to 10 samples ±0.1% full scale for all scan rates ±0.1% full scale
c
Accuracy
per second scan rate; ±0.25% full
scale at 10 to 50 samples per second
a
10-mV resolution in high common-mode environments.
b
With a two-section filter.
c
Overall accuracy.

This signal is synchronously rectified to preserve original where one analog-to-digital converter (ADC) is used for each
input polarity integrated over the cycle period, and it is amplified channel. The outputs of the converters are connected to a
and held for digitizing by an integrator and hold amplifier. common bus through interface units.
The cost of the system is relatively high, making the applica- In such a configuration, the digital processor, which is
tion economically impractical unless high common-mode tol- used to process the digital outputs of the converters, uses the
erance is required. Common-mode rejection from DC to 60 Hz same bus. This way the digital processor can alternately
of 12 decibels is easily obtained. access the outputs of each ADC and thereby can multiplex
Selection of any multiplexing system should be based on their output signals.
the performance, reliability, and cost of a particular application.
Table 1.8dd summarizes the features of the discussed systems. Data Acquisition Boards The data acquisition board allows
a computer to access a set of analog signals that are connected
Digital Multiplexing When there are many channels, the mul- to that plug-in board. Most of these boards operate on signals
tiplexer must be fast even if the incoming signals are slow. that have already been filtered and amplified, although some
Figure 1.8ee illustrates such a fast multiplexer configuration, boards can directly accept the output signals of sensors.

Ch 1 Signal
Sensor S/H ADC Interface
conditioner

Signal
Ch 2 Sensor S/H ADC Interface
conditioner

Digital
processor
Signal
Ch N Sensor S/H ADC Interface
conditioner

Bus

FIG. 1.8ee
Multi-channel data acquisition using digital multiplexing.

© 2006 by Béla Lipták


86 General

ANALOG

Input 1

Input 2

Input 3 Analog Digital


multiplexer Amplifier S/H ADC
output

Input N

FIG. 1.8ff
Data acquisition boards commonly allow access digital computers to reach 8 or 16 analog inputs.

Such boards are provided with the required signal conditioning Continuously monitored pulse train.
Signal
circuits. The area is proportional to the counts.
Usually 8 or 16 analog inputs can be connected to a data
acquisition board. Figure 1.8ff illustrates such a system, Area
Measurement =
which consists of an analog multiplexer, an amplifier, a sam- (signal level) Time base
ple and hold circuit, and an analog-to-digital converter. Some
Signal level
data acquisition boards also provide (usually two) analog
output channels for control purposes.

A/D Converters
Measurement time
Just as microprocessors have evolved in sophistication, so Time
have A/D converters. Eight-bit resolution devices common
in the 1960s provided a resolution of about +/– 0.4%. In the FIG. 1.8gg
year 2000 the first 21-bit resolution A/D was used in a tem- Line frequency noise reduction by integrating the input signal of
an A/D converter.
perature transmitter, providing a resolution of +/– 0.00005%.
D/A converters have also evolved with resolutions increasing
from 8-bit up to the 18-bit versions used in the better trans-
mitters beginning in the year 2000. in process monitoring and control where high sampling fre-
The result of combining these technologies is a universal quencies are not required. In appropriate situations, it pro-
transmitter that accepts inputs from any TC, RTD, mV, resis- vides noise rejection of about 1000 to 1 (or 60 decibels) at
tance, or potentiometer signal, checks its own calibration on 60 Hz and offers good rejection of other frequency noises.
every measurement cycle, has minimal drift over a wide
ambient temperature range, incorporates self-diagnostics,
and is configured using pushbuttons or simple PC software. CONCLUSIONS
The reconfiguration process is quick and convenient, and it
tends to allow for lower inventories by making the transmit- Electrical noise problems are not unique to new installations.
ters interchangeable. Even systems that were in satisfactory operation can develop
noise as a result of burned or worn electrical contacts, defec-
Noise Rejection in A/D Converters The dominant noise in tive suppressors, loose connections, and the like. Any equip-
A/D converters is line frequency noise. One approach toward ment used to identify the noise source must have the fre-
reducing this noise is to integrate the input signal. The inte- quency response and rise time capability to display noise
grating technique relies on A/D converter hardware. The signals. Minimum requirements would be 10 MHz bandwidth
operation of the A/D converter is such that it converts the and 35 nanosecond rise time.
continuously monitored measurement into a pulse train and Once the noise signal or a shielding problem is identified,
totals the number of pulses it receives. If the measurement its elimination involves applying the basic rules discussed
time is equal to the period of the line frequency, integration earlier. The most important ones are listed below:
yields the true value of signal level, and the line frequency
noise effect becomes zero, as shown in Figure 1.8gg. 1. Select signal sources with low output impedance and
This method is usually applied to slow multiplexers (e.g., with grounding capability. Never use the shield as a
40 points per second scan rate) and is suitable for applications signal conductor and never splice a low-level circuit.

© 2006 by Béla Lipták


1.8 Wiring Practices and Signal Conditioning 87

2. Use only top-quality signal cable, in which the signal References


pair is twisted and protected with a lapped foil shield,
plus a low-resistance drain wire. Low-level signal 1. Lovuola, V. J., “Preventing Noise in Grounded Thermocouple Mea-
cables must be terminated with short, untwisted wire, surements,” Instruments and Control Systems, January 1980.
2. Deavenport, J. E., “EMI Susceptibility Testing of Computer Systems,”
which expose a minimum area to inductive pickup. Computer Design, March 1980.
3. Provide a good low-resistance system ground and a 3. Hewlett-Packard Application Note 290, “Practical Temperature Mea-
stable signal ground located near the signal source. surement,” Palo Alto, CA, Latest revision.
Use individual twisted shielded pairs for each trans-
ducer. Unused shielded connector in a low-level sig-
nal cable should be single-end grounded with the Bibliography
shield grounded at the opposite end.
4. Ground the signal cable shield and signal cable cir- Adler, C. B., “Reliability Aspects of Temperature Measurement,” ISA Con-
cuit at the source only, and keep them from contact- ference, Chicago, 2001.
ing ground at any other point. Signal cable shield Demler, M. J., High Speed Analog-to-Digital Conversion, New York: Aca-
demic Press, 1991.
must be maintained at a fixed potential with respect
Denny, H., “Grounding for the Control of EMI,” Virginia: DWCI, 1983.
to the circuit being protected. Hoeschelle, D. F., Analog-to-Digital and Digital-to-Analog Conversion
5. Thermocouple transducers may be used with com- Techniques, New York: John Wiley & Sons, 1994.
mon shield when the physical layout allows multiple Johnson, R., “Measuring the Hot, Difficult and Inaccessible,” Control Engi-
pair extension leads. neering, June 2001.
Kaufman, A. B., “Third Party Junctions in TCs,” Instruments and Control
6. Connect all signal pairs to adjacent pins in a connec-
Systems, December 1981.
tor and carry the cable shields through it on adjacent Klipec, B., “Reducing Electrical Noise in Instrument Circuits,” IEEE Trans-
pins. Provide shield around signal pairs in the con- actions on Industry and General Applications, 1967.
nector by shorting pins together at both ends and by Lovoula, V. J., “Preventing Noise in Grounded Thermocouple Measure-
connecting to signal cable shields. ments,” Instruments and Control Systems, January 1980.
Michalski, L., et al., Temperature Measurement, 2nd ed., London: John
7. Separate low-level circuits from power cables by 3
Wiley & Sons, 2001.
ft if possible (1 ft minimum), and cross noisy circuits Morrison, R., and Lewis, W. H., Grounding and Shielding in Facilities, New
at right angles and at a maximum practical distance. York: John Wiley & Sons, 1990.
8. Select appropriate multiplexing and amplifier cir- Nalle, D. H., “Signal Conditioning,” Instruments and Control Systems,
6 February 1969.
cuits having input guarding systems of at least 10 :1
National Electrical Code, National Fire Protection Association, Art.
common-mode rejection at 60 Hz.
500—503, Quincy, MA, 2002.
9. Provide triple-shielded power supplies for measuring Schmid, H., Electronic Analog/Digital Conversions, New York: Van Nos-
devices. trand Reinhold, 1970.
10. Measure the common-mode rejection of the system Simmons, J. P., Soares Book on Grounding, 7th ed., Dallas, TX: IAEI, 1999.
by an indirect method whenever the rejection capa- Stoffel, J., “DCS Melds Analog, Digital I/O,” Control Engineering, October
1991.
bility is in doubt.
Van de Plassche, R., Integrated Analog-to-Digital and Digital-to-Analog
11. Pay particular attention to the quality of the work- Converters, Dordrecht, The Netherlands: Kluwer Academic Publishers,
manship and system wiring practices. 1994.
12. Perform the analog-to-digital conversion as close to Volbrecht, A., and Gordon, W., “Temperature Measurement: Making Sense
the signal source as practical. of it All,” Sensors, June 1998.

© 2006 by Béla Lipták

S-ar putea să vă placă și