Fire & Smoke Dampers

Static Fire Dampers


Dynamic Fire Dampers
Ceiling Radiation Dampers
Fire/ Smoke Dampers
Corridor Fire / Smoke Dampers
Smoke Dampers
Duct Access Doors
Static Fire Dampers

Tab-Lock Retaining Angles


Sleeves
Transitions & Collars
117A 1 1/2 hour rated no sleeve
117XA 1 1/2 hour rated with sleeve
117B 1 1/2 hour rated no sleeve100% free area
117XB 1 1/2 hour rated with sleeve100% free area
117C 1 1/2 hour rated no sleeve100% free area
117XC 1 1/2 hour rated with sleeve100% free area
117F 1 1/2 hour rated vert no sleeve narrow frame
317A 3 hour rated no sleeve
317B 3 hour rated no sleeve100% free area
317C 3 hour rated no sleeve100% free area
Installation (1-1/2 Hour Rated)
Installation (3 Hour Rated)
ASD-ANGLES-04.11

ARROW UNITED INDUSTRIES


TAB-LOCK RETAINING ANGLES

Tab-Lock Retaining Angles may be used to mount


Arrow United Fire or Combination Fire/Smoke Damp-
ers, both vertically and horizontally. UL approved for
dampers with a 1½ hour fire rating, they offer the flex-
ibility of attachment to the sleeve into the rated barrier.
The corner tabs can be bent 90 degrees in either
direction before or after attachment to the sleeve,
depending on jobsite preference.

Tab-Lock Retaining Angles are pre-punched for easy


attachment to the sleeve. Refer to the appropriate
Installation Instructions for details.
ACTUAL DAMPER WIDTH

ACTUAL DAMPER WIDTH

Meets requirements established


by: Underwriters Laboratories
UBC BOCA
CSFM SBCCI
SMACNA NFPA
City of Los Angeles

GENERAL INFORMATION
Maximum Size - 96” x 60” Material - Galvanized Steel (16 ga.)
Orientation - Vertical or Horizontal Dimensions - 1-1/2” x 7/8”
Angles are pre-punched and shipped loose for field attachment to the
sleeve. Refer to the appropriate Installation Instructions for details.

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-SLV-04.11

FIRE/SEAL® MODEL 117A, D17A,


317A, D37A
UL-CLASSIFIED FIRE DAMPER Vertical & Horizontal
WITH FACTORY SLEEVE

ACTUAL SLEEVE O.D. * *


SLEEVE GAUGE "A" "B"
20 + 18 W — 1 /8 H
1
16 W — /8 H
14 W — 1/16 H + 1/ 8
10 W H

NOTES:
1.W = Nominal duct width PROJECT:
2.H = Nominal duct height
* 3.SLEEVE IS NOT TO EXTEND OVER SIX LOCATION:
INCHES BEYOND WALL OR FLOOR ARCHITECT:
OPENING (PER UL 555). ENGINEER:
4.Assembly to dampers is per UL procedures.
1-1/2 hr. dampers may be toggle-locked, CONTRACTOR:
welded, bolted, or riveted. PO NUMBER:
3 hr. dampers may be welded only.
DATE:
* * 5.Tolerances are ± 1/8 ".

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA
FIRE/SEAL® MODEL 117B, D17B,
317B, D37B
UL-CLASSIFIED FIRE DAMPER Vertical & Horizontal
WITH FACTORY SLEEVE

ACTUAL SLEEVE O.D. * *


SLEEVE GAUGE A B C
20 + 18 W — 1 /8 OS H — 1/16
16 W — 1/8 OS H — 1/16
14 W — 1/16 OS + 1/8 H
10 W OS H + 1 /8
HEAD SIZING CHARTS
Vertical (Model 319BV)
Vertical & Horizontal (Model 119B) IF NOMINAL DUCT INCHES TO Horizontal (Model 319BH)
HEIGHT IS: ADD FOR HEAD:
IF DUCT INCHES TO IF NOMINAL DUCT INCHES TO
Galvanized SINGLE PANEL
HEIGHT IS: ADD FOR HEAD: or HEIGHT IS: ADD FOR HEAD:
Stainless 3" THRU 18" 2" Galvanized
3" THRU 18" 2" 19" THRU 28" 3" 3" THRU 18" 2" Steel
19 THRU 28" 3" 29" THRU 32" 4" 19" THRU 28" 3" Only
(Stainless

*{
29 THRU 40" 4" Stainless
33" THRU 40" 4" 29" THRU 40" 4" Steel
Not
41" THRU 55" 5" Only 41" 5" 41" THRU 43" 5" Available
42" 6"
Vertical
{
Multiple Units
Only
56" THRU 57"
58" THRU 76"
3"
4" MULTIPLE PANEL
Galvanized 33" THRU 37" 2"
(*) NOTE: MAXIMUM DUCT HEIGHT FOR HORIZONTAL UNITS: Only (Stainless
38" THRU 57" 3"
Single Panel Dampers: 43" DUCT Height. Not Available)
58" THRU 68" 4"
Multiple Panel (Wide) Dampers: 38" Height.

NOTES:
1. W = Nominal duct width
2. H = Nominal duct height PROJECT:
3. OS = Overall height (see Head Sizing Charts)
LOCATION:
* 4. SLEEVE IS NOT TO EXTEND OVER SIX INCHES
BEYOND WALL OR FLOOR OPENING (PER UL 555). ARCHITECT:
5. Assembly to dampers is per UL procedures. ENGINEER:
1-1/2 hr. dampers may be toggle-locked, welded,
bolted, or riveted. CONTRACTOR:
3 hr. dampers may be welded only. PO NUMBER:
* * 6. Tolerances are ± 1/8 ". DATE:
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA
ASD-T-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA
TRANSITIONS AND COLLARS
MODELS 117A, D17A & 117X, D17X TRANSITIONS AVAILABLE FOR EITHER:
FIRE DAMPERS FOR ROUND OR • 100% FREE AREA
(Frame & Blades out of the airstream),
OVAL DUCTWORK IN LOW or
PRESSURE HVAC SYSTEMS • 1” -LARGER DAMPER SIZE THAN DUCT SIZE
(Max. Pressure: 2 in. wg) (Blade-stack in the airstream).
TRANSITIONS AVAILABLE FOR EITHER:
VERTICAL DAMPERS SHOWN BELOW; TRANSI- • BOTH ENDS OF DAMPER,
TIONS AND COLLARS CAN BE SUPPLIED FOR or
HORIZONTAL UNITS, ALSO. • ONE END OF DAMPER

(Longer lengths are available.) (Longer lengths of 14” & 16” are available.)

IMPORTANT
For round duct diameters up to 36” and for oval duct sizes up to
71”W x 30”H, ABI’s 22 Ga. duct connection collar (crimped to
the damper transition) constitutes a UL approved duct-to-sleeve NOTES:
“Breakaway” connection, thus allowing a rigid connection joint 1.Rectangular collars are not avail-
to be utilized between the damper’s duct connection collar and able; an “A” or “B” Style damper
the round or oval ductwork. (without transitions) should be used.
If 100% free area for rectangular
UNDERWRITERS LABORATORIES INC.
DETAIL “A” ductwork is desired, a “C” Style
CLASSIFIED damper should be used.
FIRE DAMPERS 2.Sealed/caulked units are not avail-
FIRE RESISTANCE RATING 1-1/2 HR. able. Sealant/caulking indicates a
SEE UL CLASSIFIED BUILDING MATERIALS INDEX High Pressure HVAC System; there-
fore, a “‘C” Style damper should be
California State Fire Marshal used.
Listing No. 3225-1328:100

STANDARD MATERIALS & CONSTRUCTION:


DAMPER: Model 117A, D17A, or 117X, D17X.
PROJECT:
TRANSITION [“CAP”]: 20 Ga. galvanized steel, riveted to
LOCATION:
damper frame (or sleeve).
ARCHITECT:
DUCT CONNECTION COLLAR: 22 Ga. galvanized steel,
crimped to transition. ENGINEER:
Arrow United Industries CONTRACTOR:
A Division of Mestek, Inc. PO NUMBER:
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 DATE:
www.arrowunited.com

MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA
TRANSITIONS AND COLLARS
MODELS 117A, D17A & 117X, D17X FIRE DAMPERS FOR ROUND OR OVAL DUCTWORK

100%
1”
FREE
LARGER
AREA
OPTION
OPTION

(MODEL 117A SHOWN) (MODEL 117X SHOWN)

DIMENSIONAL DATA (DUCT DIMENSIONS):


MINIMUM SIZE: 4” Diameter (Vertical and Horizontal)
MAXIMUM SIZE - VERTICAL: MAXIMUM SIZE - HORIZONTAL:
117AVand117XVSinglePanel: 58”W x 54” H(100% Free Area), or 117AHand117XHSinglePanel: 46”W x 42”H (100% Free Area) or
59”W x 59”H (1” larger). 47”W x 47”H (1” larger).
D17AVandD17XVSinglePanel: 40”W x 37”H (100% Free Area), or D17AH and D17XH Single Panel: 34”W x 31”H (100% Free Area), or
41”W x 41”H (1” larger). 35”W x 35”H (1” larger).
117AVandD17AVMultiplePanel: 118”W x 75”H (100% Free Area), or 117AH Multiple Panel: 95”W x 37”H (100% free Area), or
119”W x 79”H (1” larger). 96”W x41”H (1” larger).
D17AH Multiple Panel: 95”W x 31”H (100% Free Area), or
96”W x 35”H (1” larger).
NOTE: Dampers should be ordered by nominal duct size.
Fractional duct dimension (1/8” min.) will require the same fractional addition to the corresponding damper transition dimension.

DAMPER SIZING CHART With 100% Free Area, Pressure Drop is determined by
FOR 100% FREE AREA OPTION FACE Area Velocity ( in lieu of Free Area Velocity)
WIDTH: Add 2” to Nominal Duct Width. FLOW [cfm]
HEIGHT: FACE AREA VELOCITY [fpm]
IF NOMINAL INCHES TO ADD FOR
FACE AREA [sq. ft.]
DUCT NOMINAL DAMPER
STATIC .20
HEIGHT IS: FRAME HEIGHT:
4” THRU 18” 3” PRESSURE
DROP
19” THRU 28” 4” [in.wg] .10
.09
29” THRU 40” 5” .08
.07
41” THRU 42” 6” .06

43” THRU 54” 6” .05

.04
55” THRU 57” 4”
58” THRU 75” 5” .03

.02

FOR 1”-LARGER OPTION, NOMINAL DAMPER FRAME DIMENSIONS


ARE ALWAYS 1” LARGER THAN NOMINAL DUCT DIMENSIONS.

.01
1000 2000 3000 4000 5 6

FACE AREA VELOCITY [fpm]


IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED
RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-117A-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL 117A


1-1/2 HR. STATIC RATED VERTICAL & HORIZONTAL
FIRE DAMPER
Classifed by Underwriters Laboratories as a 1-1/2 hour
fire protection rated Fire Damper, in accordance with
Standards UL-555 and NFPA-90A, for the protection
of openings in fire partitions having a fire resistance
rating of less than 3 hours.

UNDERWRITERS LABORATORIES, INC.

Arrow United
CLASSIFIED

Industries
FIRE DAMPERS
FIRE RESISTANCE RATING 1-1/2 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX

California State Fire Marshal


Listing No. 3225-1328:100

DIMENSIONAL DATA:
STANDARD MATERIALS & CONSTRUCTION:
MINIMUM SIZE: 4”W X 4”H.
FRAME: One-piece rollformed 22 Ga. galvanized steel.
MAXIMUM SIZE - VERTICAL (Model 117AV):
BLADES: 22 Ga. galvanized steel curtain-type. Single Panel: 60”W x 60”H.
FUSIBLE LINK: UL-listed 165°F; replaceable. Multiple Panel: 120”W x 120”H; in max. panels of 40”W x 60”H.
(Optional 212°F available at no additional charge). MAXIMUM SIZE - HORIZONTAL (Model 119AH):
CLOSURE SPRINGS (Horizontal Models): Heat- Single Panel: 48”W x 48”H.
treated Type 301 stainless steel constant force coiled negator Multiple Panel: 102”W x 48”H; in max. panels of 36”W x 48”H.
type.
NOTE: Unassembled multiple units do not include mullions.
PROJECT:
LOCATION:
Additional Information
ARCHITECT on reverse side
ENGINEER:
Arrow United Industries
CONTRACTOR: A Division of Mestek, Inc.
PO NUMBER: 314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
DATE: www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA
FIRE/SEAL® UL-CLASSIFIED MODEL 117A
1-1/2 HR. STATIC RATED FIRE DAMPER
FREE AREA (sq. ft.)
Duct Width (in.)
4 8 12 16 20 24 28 32 36 40 44 48 52 56 60
4 .03 .09 .16 .22 .28 .34 .40 .46 .52 .58 .64 .70 .76 .82 .89
8 .09 .26 .42 .58 .75 .91 1.08 1.24 1.40 1.57 1.73 1.89 2.06 2.22 2.39
12 .15 .41 .68 .94 1.21 1.47 1.74 2.00 2.27 2.53 2.79 3.06 3.32 3.59 3.85
DUCT HEIGHT (in.)

16 .21 .57 .94 1.30 1.67 2.03 2.40 2.76 3.13 3.49 3.86 4.22 4.59 4.95 5.32
20 .27 .74 1.21 1.69 2.16 2.64 3.11 3.58 4.06 4.53 5.00 5.48 5.95 6.43 6.90
24 .32 .90 1.47 2.05 2.62 3.20 3.77 4.35 4.92 5.49 6.07 6.64 7.22 7.79 8.37
28 .38 1.06 1.74 2.41 3.09 3.77 4.44 5.12 5.80 6.47 7.15 7.83 8.51 9.18 9.86
32 .44 1.21 1.99 2.77 3.55 4.32 5.10 5.88 6.66 7.43 8.21 8.99 9.77 10.54 11.32
36 .50 1.39 2.27 3.16 4.04 4.93 5.82 6.70 7.59 8.48 9.36 10.25 11.14 12.02 12.91
40 .56 1.55 2.54 3.52 4.51 5.50 6.49 7.48 8.47 9.46 10.45 11.44 12.43 13.42 14.41
44 .62 1.72 2.81 3.91 5.01 6.11 7.21 8.30 9.40 10.50 11.60 12.70 13.79 14.89 15.99
48 .68 1.88 3.08 4.28 5.48 6.68 7.88 9.08 10.29 11.49 12.69 13.89 15.09 16.29 17.49
52 .73 2.03 3.33 4.63 5.92 7.22 8.52 9.82 11.12 12.42 13.72 15.02 16.21 17.61 18.91
56 .79 2.19 3.59 4.99 6.40 7.80 9.20 10.60 12.01 13.41 14.81 16.21 17.61 19.02 20.42
60 .84 2.33 3.82 5.31 6.79 8.28 9.77 11.26 12.75 14.24 15.73 17.22 18.71 20.20 21.69

FLOW (cfm)
FREE AREA VELOCITY [FPM] =
FREE AREA (sq. ft.)
STATIC PRESSURE DROP (in. wg)

AVAILABLE OPTIONS:
1. Factory-supplied sleeves (20 Ga. through 10 Ga.).
2. Type 304 stainless steel construction.
3. 212°F fusible link. FREE AREA VELOCITY (fpm)
4. Electro Thermal Link [ETL®].
5. SPDT “closed damper” position indicator switch.
Arrow United Industries
A Division of Mestek, Inc.
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES 314 Riverside Drive . Wyalusing, PA 18853
RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE. Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-117XA-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL 117X


1½-HR. STATIC RATED FIRE DAMPER “A” STYLE
Vertical & Horizontal
WITH INTEGRAL SLEEVE FRAME

NO ADDITIONAL SLEEVE REQUIRED, PROVIDED DUCT Classified by Underwriters Laboratories as a 11/2-hour fire
THICKNESS IS 20 GA. OR LESS, AND U.L.-APPROVED protection rated Fire Damper, in accordance with Standards
BREAKAWAY DUCT-TO-SLEEVE CONNECTION JOINTS UL-555 and NFPA-90A, for the protection of openings in fire
ARE USED, PER UL-555. partitions having a fire resistance rating of less than 3 hours.

UNDERWRITERS LABORATORIES INC.


CLASSIFIED

Arrow United
Industries
FIRE DAMPERS
FIRE RESISTANCE RATING 11/2 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX

California State Fire Marshal


Listing No. 3225-1328:100

DIMENSIONAL DATA:
MINIMUM SIZE: 4" W x 4" H.
MAXIMUM SIZE - VERTICAL:
Single Panel: 60" W x 60" H (Duct). Multiple Panel: Not Available.
MAXIMUM SIZE - HORIZONTAL:
Single Panel: 48" W x 48"H. Multiple Panel: Not Available.

NOTE: Dampers should be ordered by nominal duct size.

STANDARD MATERIALS & CONSTRUCTION:


SLEEVE FRAME: One-piece rollformed 20-GA galvanized steel.
BLADES: 22-GA galvanized steel curtain-type.
FUSIBLE LINK: UL-listed 165OF; replaceable. (Optional 212OF PROJECT:
available at no additional charge.) LOCATION:
CLOSURE SPRINGS (Horizontal Models): Heat-treated Type 301
ARCHITECT:
stainless steel constant force coiled negator type.
ENGINEER:
Arrow United Industries CONTRACTOR:
A Division of Mestek, Inc. PO NUMBER:
314 Riverside Drive . Wyalusing, PA 18853
DATE:
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com Additional information
MEMBER OF AMCA on reverse side.
ARROW UNITED INDUSTRIES SUBMITTAL DATA
FIRE/SEAL® UL-CLASSIFIED MODEL 117X
11/2-HR. STATIC RATED FIRE DAMPER “A” STYLE
WITH INTEGRAL SLEEVE FRAME

FREE AREA [sq. ft.]


Duct Width (in.)
4 8 12 16 20 24 28 32 36 40 44 48 52 56 60
4 .03 .09 .1 .2 .3 .3 .4 .4 .5 .6 .6 .7 .7 .8 .9
8 .1 .2 .4 .6 .7 .9 1.0 1.2 1.4 1.5 1.7 1.8 2.0 2.2 2.3
12 .2 .4 .7 .9 1.2 1.5 1.8 2.0 2.3 2.6 2.8 3.1 3.4 3.6 3.9
16 .2 .6 .9 1.3 1.7 2.0 2.4 2.8 3.1 3.5 3.9 4.2 4.6 5.0 5.3
Duct Height (in.)

20 .3 .7 1.2 1.7 2.1 2.6 3.1 3.5 4.0 4.5 5.0 5.4 5.9 6.4 6.8
24 .4 .9 1.4 2.0 2.6 3.2 3.7 4.3 4.9 5.4 6.0 6.6 7.1 7.7 8.3
28 .4 1.0 1.7 2.4 3.0 3.7 4.4 5.0 5.7 6.4 7.0 7.7 8.4 9.0 9.7
32 .5 1.2 2.0 2.7 3.5 4.3 5.1 5.8 6.6 7.4 8.2 9.0 9.7 10.5 11.3
36 .5 1.3 2.2 3.1 4.0 4.8 5.7 6.6 7.4 8.4 9.2 10.1 11.0 11.8 12.7
40 .6 1.5 2.5 3.5 4.4 5.4 6.4 7.4 8.4 9.3 10.3 11.3 12.3 13.2 14.2
44 .6 1.7 2.7 3.8 4.9 6.0 7.0 8.1 9.2 10.3 11.4 12.4 13.5 14.6 15.7
48 .7 1.8 3.0 4.2 5.4 6.6 7.7 8.9 10.1 11.3 12.5 13.7 14.8 16.0 17.2
52 .8 2.0 3.3 4.5 5.8 7.1 8.4 9.7 11.0 12.2 13.5 14.8 16.1 17.4 18.7
56 .8 2.1 3.5 4.9 6.2 7.6 9.0 10.4 11.7 13.1 14.5 15.9 17.2 18.6 20.1
60 .9 2.3 3.8 5.3 6.8 8.2 9.7 11.2 12.7 14.2 15.7 17.2 18.6 20.1 21.6

FLOW [cfm]
FREE AREA VELOCITY [fpm] =
FREE AREA [sq. ft.]

.3
AVAILABLE OPTIONS:
.2
1. Sleeve frame length (“L” dimension) of 14" and 16".
2. 212OF fusible link.
3. Electro Thermal Link [ETL®].
STATIC PRESSURE DROP

.10
4. SPDT “closed damper” position indicator switch. .09
.08
5. Transitions and Collars for round or oval ductwork for Low Pressure .07
[in. wg.]

HVAC Systems - See Submittal Data Sheet SD-T. .06


.05
6. Transitions and Collars and Sealant/Caulking for rectangular, round, or
oval ductwork for High Pressure HVAC Systems (“C” Style Damper) - .04
See Submittal Data Sheet SD-119XC. .03

.02
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 .01
www.arrowunited.com 6 7 8 9 1000 2000 3000
FREE AREA VELOCITY [fpm]
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED
INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT
NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-117B-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL 117B


1-1/2 HR. STATIC RATED VERTICAL & HORIZONTAL
FIRE DAMPER
Classified by Underwriters Laboratories as a 1-1/2
hour fire protection rated Fire Damper, in accordance
Top Blade Riveted
To Frame with Standards UL-555 and NFPA-90A, for the pro-
tection of openings in fire partitions having a fire re-
See Head B sistance rating of less than 3 hours.
Sizing Chart Pan
1”
UNDERWRITERS LABORATORIES, INC.
Nominal

Arrow United
Fusible CLASSIFIED

Industries
Frame Link
Height FIRE DAMPERS
(without FIRE RESISTANCE RATING 1-1/2 HR.
sleeve) SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX

Nominal
Duct California State Fire Marshal Listing No.
Height 3225-1328:100
Less 1/4”

3”
3/4” (Sill and Jambs)

4-7/8”

Blade Lock*
Stainless Steel
Negator Closure
Spring

Nominal Duct Width


Less 1/4” (without
(*) Damper is to be installed with blade lock points
sleeve)
facing DOWNWARD and with access from above

STANDARD MATERIALS & CONSTRUCTION: DIMENSIONAL DATA:


FRAME: One-piece rollformed 22 Ga. galvanized steel. MINIMUM SIZE: 4”W X 3”H (Duct).
BLADES: 22 Ga. galvanized steel curtain-type.
MAXIMUM SIZE - VERTICAL (Model 119BV):
FUSIBLE LINK: UL-listed 165°F; replaceable Single Panel: 60”W x 55”H (Duct), 60”W x 60”H (Frame).
(Optional 212°F available at no additional charge). Multiple Panel: 120”W x 115”H (Duct), 120”W x 120”H (Frame);
in max. panels of 40”W x 60”H (Frame).
CLOSURE SPRINGS (Horizontal Models): Heat-
treated Type 301 stainless steel force coiled negator type. MAXIMUM SIZE - HORIZONTAL (Model 119BH):
Single Panel: 48”W x 43”H (Duct), 48”W x 48”H (Frame).
Multiple Panel: 102”W x 43”H (Duct), 102”W x 48”H (Frame);
PROJECT: in max. panels of 36”W x 43”H (Duct), 36”W x 48”H (Frame).
LOCATION: NOTE: Unassembled multiple units do not include mullions.
ARCHITECT
ENGINEER:
Additional Information
CONTRACTOR: Arrow United Industries on reverse side
A Division of Mestek, Inc.
PO NUMBER:
314 Riverside Drive . Wyalusing, PA 18853
DATE: Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA
FIRE/SEAL® UL-CLASSIFIED MODEL 117B
1-1/2 HR. STATIC RATED FIRE DAMPER
FREE AREA (sq. ft.)
Duct Width (in.)
4” 8” 12” 16” 20” 24” 28” 32” 36” 40” 44” 48” 52” 56” 60”
4” .06 .2 .3 .4 .5 .5 .6 .7 .8 .9 1.0 1.1 1.2 1.3 1.4
8” .2 .4 .6 .8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
12” .2 .5 .9 1.2 1.5 1.8 2.1 2.4 2.7 3.0 3.4 3.7 4.0 4.3 4.6
16” .3 .7 1.2 1.6 2.0 2.4 2.8 3.3 3.7 4.1 4.5 5.0 5.4 5.8 6.2
DUCT HEIGHT (in.)

20” .4 .9 1.4 2.0 2.5 3.0 3.6 4.1 4.7 5.2 5.7 6.3 6.8 7.3 7.9
24” .4 1.1 1.7 2.4 3.0 3.7 4.3 5.0 5.6 6.3 6.9 7.5 8.2 8.8 9.5
28” .5 1.2 2.0 2.8 3.5 4.3 5.0 5.8 6.5 7.3 8.0 8.8 9.5 10.3 11.0
32” .6 1.5 2.3 3.2 4.0 4.9 5.8 6.7 7.5 8.4 9.3 10.1 11.0 11.9 12.7
36” .7 1.6 2.6 3.6 4.6 5.5 6.5 7.5 8.5 9.5 10.4 11.4 12.4 13.4 14.4
40” .7 1.8 2.9 4.0 5.1 6.2 7.3 8.4 9.4 10.5 11.6 12.7 13.8 14.9 16.0
44” .8 2.0 3.2 4.4 5.6 6.8 8.0 9.2 10.4 11.6 12.8 14.0 15.2 16.4 17.6
48” .8 2.1 3.3 4.6 5.9 7.1 8.4 9.6 10.9 12.1 13.4 14.7 15.9 17.2 18.4
52” .9 2.4 3.8 5.2 6.6 8.0 9.5 10.9 12.3 13.7 15.2 16.6 18.0 19.4 20.9
55” .9 2.4 3.9 5.3 6.8 8.3 9.8 11.3 12.8 14.3 15.8 17.3 18.8 20.3 21.8

HEAD SIZING CHART FLOW (cfm)


If duct Inches to FREE AREA VELOCITY [FPM] =
FREE AREA (sq. ft.)
height is: add for head:
3” through 18” 2”
1.0
19” through 28” 3”
.9
29” through 40” 4” .8
.7
.6

* 41” through 55” 5” .5

{
56” through 57” 3” .4
STATIC PRESSURE DROP (in. wg)

VERTICAL
MULTIPLE .3
UNITS 58” through 84” 4”
ONLY
.2
85” through 115” 5”

(*) Note: Maximum duct height for horizontal units: .10


Single Panel Damper: 43” DUCT Height .09
.08
.07
See DIMENSIONAL DATA on front side. .06
.05
.04
.03

AVAILABLE OPTIONS: .02

1. Factory-supplied sleeves (20 Ga. through 10 Ga.). .01

2. Type 304 stainless steel construction. 1000 2000 3000 4 5000


3. 212°F fusible link.
4. Electro Thermal Link [ETL®]. FREE AREA VELOCITY (fpm)
5. SPDT “closed damper” position indicator switch.
Arrow United Industries
A Division of Mestek, Inc.
IN THE INTEREST OF PRODUCT DEVELOPMENT, 314 Riverside Drive . Wyalusing, PA 18853
ARROW UNITED INDUSTRIES RESERVES THE RIGHT Ph: (570) 746-1888 Fax: (570) 746-9286
TO MAKE CHANGES WITHOUT NOTICE. www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-117XB-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL 117X


1½-HR. STATIC RATED FIRE DAMPER “B” STYLE
Vertical & Horizontal
WITH INTEGRAL SLEEVE FRAME

NO ADDITIONAL SLEEVE REQUIRED, PROVIDED DUCT Classified by Underwriters Laboratories as a 1½ hour fire
THICKNESS IS 20 GA. OR LESS, AND U.L.-APPROVED protection rated Fire Damper, in accordance with Standards
BREAKAWAY DUCT-TO-SLEEVE CONNECTION JOINTS UL-555 and NFPA-90A, for the protection of openings in fire
ARE USED, PER UL-555. partitions having a fire resistance rating of less than 3 hours.

UNDERWRITERS LABORATORIES INC.


CLASSIFIED

Arrow United
Industries
FIRE DAMPERS
FIRE RESISTANCE RATING 3 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX

California State Fire Marshal


Listing No. 3225-1328:100

DIMENSIONAL DATA:
MINIMUM SIZE: 4" W x 3" H (Duct), 4"W X 5"H (Sleeve Frame).
MAXIMUM SIZE - VERTICAL:
Single Panel: 60" W x 55" H (Duct), 60" W x 60" H (Sleeve Frame).
Multiple Panel: Not Available.
MAXIMUM SIZE - HORIZONTAL:
Single Panel: 48" W x 43" H (Duct), 48" W x 48" H (Sleeve Frame).
Multiple Panel: Not Available.
STANDARD MATERIALS & CONSTRUCTION:
NOTE: Dampers should be ordered by nominal duct size.
SLEEVE FRAME: One-piece rollformed 20-GA galvanized steel.
BLADES: 22-GA galvanized steel curtain-type.
FUSIBLE LINK: UL-listed 165OF; replaceable. (Optional 212OF PROJECT:
available at no additional charge.) LOCATION:
CLOSURE SPRINGS (Horizontal Models): Heat-treated Type 301
ARCHITECT:
stainless steel constant force coiled negator type.
ENGINEER:
Arrow United Industries CONTRACTOR:
A Division of Mestek, Inc. PO NUMBER:
314 Riverside Drive . Wyalusing, PA 18853
DATE:
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com Additional information
on reverse side.
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED MODEL 117X


1-½-HR. STATIC RATED FIRE DAMPER “B” STYLE
WITH INTEGRAL SLEEVE FRAME

HEAD SIZING CHART


IF NOMINAL DUCT INCHES TO
HEIGHT IS: ADD FOR HEAD:
3" THRU 18" 2"
19" THRU 28" 3"
29" THRU 40" 4"
41" THRU 43" 5"
VERTICAL
ONLY 44" THRU 55" 5"

See DIMENSIONAL DATA on front side.

AVAILABLE OPTIONS:
1. Sleeve frame length (“L” dimension) of 14" and 16".
2. 212OF fusible link.
3. Electro Thermal Link [ETL®].
4. SPDT "closed damper" position indicator switch.

FLOW [cfm]
FREE AREA VELOCITY [fpm] =
FREE AREA [sq. ft.]
.3

.2
FREE AREA [sq. ft.]
Duct Width (in.)
4 8 12 16 20 24 28 32 35 40 44 48 52 56 60
STATIC PRESSURE DROP

4 .06 .2 .3 .4 .5 .5 .6 .7 .8 .9 1.0 1.1 1.2 1.3 1.4 .10


.09
8 .2 .4 .6 .8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0
.08
12 .2 .5 .9 1.2 1.5 1.8 2.1 2.4 2.7 3.0 3.4 3.7 4.0 .3 4.6 .07
[in. wg.]

16 .3 .7 1.2 1.6 2.0 2.4 2.8 3.3 3.7 4.1 4.5 5.0 5.4 5.8 6.2 .06
Duct Height (in.)

20 .4 .9 1.4 2.0 2.5 3.0 3.6 4.1 4.7 5.2 5.7 6.3 6.8 7.3 7.9 .05
24 .4 1.1 1.7 2.4 3.0 3.7 4.3 5.0 5.6 6.3 6.9 7.5 8.2 8.8 9.5 .04
28 .5 1.2 2.0 2.8 3.5 4.3 5.0 5.8 6.5 7.3 8.0 8.8 9.5 10.3 11.0
.03
32 .6 1.5 2.3 3.2 4.0 4.9 5.8 6.7 7.5 8.4 9.3 10.1 11.0 11.9 12.7
36 .7 1.6 2.6 3.6 4.6 5.5 6.5 7.5 8.5 9.5 10.4 11.4 12.4 13.4 14.4
40 .7 1.8 2.9 4.0 5.1 6.2 7.3 8.4 9.4 10.5 11.6 12.7 13.8 14.9 16.0 .02
44 .8 2.0 3.2 4.4 5.6 6.8 8.0 9.2 10.4 11.6 12.8 14.0 15.2 16.4 17.6
48 .8 2.1 3.3 4.6 5.9 7.1 8.4 9.6 10.9 12.1 13.4 14.7 15.9 17.2 18.4
52 .9 2.4 3.8 5.2 6.6 8.0 9.5 10.9 12.3 13.7 15.2 16.6 18.0 19.4 20.9 .01
1000 2000 3000
56 .9 2.4 3.9 5.3 6.8 8.3 9.8 11.3 12.8 14.3 15.8 17.3 18.8 20.3 21.8
FREE AREA VELOCITY [fpm]
Arrow United Industries
A Division of Mestek, Inc.
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW 314 Riverside Drive . Wyalusing, PA 18853
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE Ph: (570) 746-1888 Fax: (570) 746-9286
CHANGES WITHOUT NOTICE. www.arrowunited.com
ASD-117C-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA
FIRE/SEAL® UL-CLASSIFIED MODEL 117C
1-1/2 HR. STATIC RATED Vertical & Horizontal
FIRE DAMPER
RECTANGULAR, ROUND & OVAL Classified by Underwriters Laboratories as a 1-1/2 hour
fire protection rated Fire Damper, in accordance with
DESIGNED FOR HIGH PRESSURE HVAC SYSTEMS, Standards UL-555 and NFPA-90A, for the protection
AND PROVIDES 100% FREE AREA. PRESSURE of openings in fire partitions having a fire resistance
TESTED PER AMCA STANDARD 500 TO 6 in. wg. rating of less than 3 hours.

UNDERWRITER’S LABORATORIES, INC.


CLASSIFIED

Arrow United
Industries
FIRE DAMPERS
FIRE RESISTANCE RATING 1-1/2 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX

California State Fire Marshal Listing


No. 3225-1328:100

IMPORTANT
FOR ROUND DUCT DIAMETERS UP TO 36”,
AND FOR OVAL DUCT SIZES UP TO 71”W X
30”H, ARROW’S 22 GA. DUCT
CONNECTION COLLAR (CRIMPED TO THE
DAMPER HOUSING) CONSTITUTES A UL
APPROVED DUCT-TO-SLEEVE
“BREAKAWAY” CONNECTION, THUS
ALLOWING A RIGID CONNECTION JOINT TO
BE UTILIZED BETWEEN THE DAMPER’S
DUCT CONNECTION COLLAR AND THE
ROUND OR OVAL DUCTWORK.

DIMENSIONAL DATA:
MINIMUM SIZE: 4”W X 4”H (Duct), 6”W x 7”H (Frame).
MAXIMUM SIZE - Vertical (Model 117CV):
Single Panel: 58”W x 54”H (Duct), 60”W x 60”H (Frame).
Multiple Panel: 118”W x 114”H (Duct), 120”W x 120”H (Frame).
MAXIMUM SIZE - Horizontal (Model 119CH):
Single Panel: 46”W x 42”H(Duct), 48”W x 48”H (Frame).
Multiple Panel: 100”W x 42”H (Duct), 102”W x 48”H (Frame).
NOTE: Dampers should be ordered by nominal duct size. Frac-
tional duct dimension (1/8” min.) will require the same fractional
addition to the corresponding damper housing dimension.
PROJECT:
LOCATION:
ARCHITECT
ENGINEER:
STANDARD MATERIALS & CONSTRUCTION:
FRAME: One-piece rollformed 22 Ga. galvanized steel. CONTRACTOR:
BLADES: 22 Ga. galvanized steel curtain-type. PO NUMBER:
DUCT CONNECTION COLLAR: 22 Ga. galvanized steel. Additional Information
DATE: on reverse side
FUSIBLE LINK: UL-listed 165°F; replaceable. (Optional
212°F available at no additional charge. Arrow United Industries
A Division of Mestek, Inc.
CLOSURE SPRINGS (Horizontal Models): Heat-treated 314 Riverside Drive . Wyalusing, PA 18853
Type 301 stainless steel constant force coiled negator type. Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA
FIRE/SEAL® UL-CLASSIFIED MODEL 117C
1-1/2 HR. STATIC RATED FIRE DAMPER

DAMPER SIZING CHART


Width: Add 2” to Nominal Duct Width With 100% Free Area, Pressure Drop is determined by FACE
AREA VELOCITY (in lieu of Free Area Velocity).
Height: INCHES TO ADD FOR
IF NOMINAL DUCT NOMINAL DAMPER FLOW (cfm)
HEIGHT IS: FRAME HEIGHT: FACE AREA VELOCITY [FPM] =
FACE AREA (sq. ft.)
4” through 18” 3”
19” through 28” 4”
29” through 40” 5” .07
* 41” through 42”
43” through 54”
6”
6”
.06
.05
STATIC PRESSURE DROP (in. wg)

VERTICAL 55” through 57” 4”


UNITS ONLY 58” through 84” 5”
85” through 114” 6” .04

*
( ): NOTE: MAXIMUM DUCT HEIGHT FOR HORIZONTAL UNITS:
42” DUCT Height.
See DIMENSIONAL DATA on front side.
.03

.02
AVAILABLE OPTIONS:
1. 20 Ga. through 10 Ga. housing.
2. Housing length (“L” dimension) of 6” through 24”.
3. Type 304 stainless steel construction. .01
4. 212°F fusible link. 1000 2000 3000
5. Electro Thermal Link [ETL®]. FACE AREA VELOCITY (fpm)
6. SPDT “closed damper” position indicator switch. Arrow United Industries
IN THE INTEREST OF PRODUCT DEVELOPMENT, A Division of Mestek, Inc.
ARROW UNITED INDUSTRIES RESERVES THE RIGHT 314 Riverside Drive . Wyalusing, PA 18853
TO MAKE CHANGES WITHOUT NOTICE. Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-117XC-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL 117X


1½-HR. STATIC RATED FIRE DAMPER “C” STYLE
Vertical & Horizontal
WITH INTEGRAL SLEEVE FRAME
RECTANGULAR, ROUND & OVAL
DESIGNED FOR HIGH PRESSURE HVAC SYSTEMS, AND Classified by Underwriters Laboratories as a 11/2-hour fire
PROVIDES 100% FREE AREA. PRESSURE TESTED PER AMCA STAN- protection rated Fire Damper, in accordance with Standards
DARD 500 TO 6 in. wg. LEAKAGE PERFORMANCE OF TRANSITIONED
INTEGRAL SLEEVE FRAME WITH TAPE & SEALANT CAULKING IS EQUAL UL-555 and NFPA-90A, for the protection of openings in fire
TO THAT OF A WELDED SEAM “C” -TYPE HOUSING. partitions having a fire resistance rating of less than 3 hours.

VERTICAL MOUNT
Transition UNDERWRITERS LABORATORIES INC.
UL-APPROVED

Arrow United
BREAKAWAY CLASSIFIED

Industries
Total Transition CONNECTION
Height (Equals Sealant FIRE DAMPERS
Nominal Caulking Typ.
Damper Frame at Transition- Collar (For FIRE RESISTANCE RATING 11/2 HR.
Height Less to-Sleeve Connection to
0.07") Frame Joint Duct) SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX
Nominal on Interior
See Damper Duct
Sizing Chart Height
2" California State Fire Marshal
Damper Centered Typ.
Less 1/4"
Within Sleeve Frame
Listing No. 3225-206:014

3" 1" Typ. Three


Sides
IMPORTANT
3/4"(Sill&Jambs)
FOR ROUND DUCT DIAMETERS UP
TO 36", AND FOR OVAL DUCT SIZES
"L" (12" Length is Standard)
Longer Lengths of 14" and 16" are available
UP TO 58" X 30"H, ARROW U'S 22-GA
DUCT CONNECTION COLLAR
(CRIMPED TO THE DAMPER TRANSI-
HORIZONTAL MOUNT TION)CONSTITUTESAU.L.APPROVED
DUCT-TO-SLEEVE “BREAKAWAY”
CONNECTION, THUS ALLOWING A
RIGIED CONNECTION JOINT TO BE
UTILIZED BETWEEN THE DAMPER'S
DUCT CONNECTION COLLAR AND
THE ROUND OR OVAL DUCTWORK.
Blade
Lock

DIMENSIONAL DATA:
Stainless Steel Negator
Closure Spring MINIMUM SIZE: 4" W x 4" H (Duct), 6"W x 7"H (Sleeve Frame).
MAXIMUM SIZE - VERTICAL:
Single Panel: 58" W x 54" H (Duct), 60"W x 60"H (Sleeve Frame).
Multiple Panel: Not Available.
MAXIMUM SIZE - HORIZONTAL:
STANDARD MATERIALS & CONSTRUCTION: Single Panel: 46" W x 42"H (Duct), 48"W x 48"H (Sleeve
SLEEVE FRAME: One-piece rollformed 20-GA galva- Frame).
nized steel. Multiple Panel: Not Available.
BLADES: 22-GA galvanized steel curtain-type.
NOTE: Dampers should be ordered by nominal duct size.
TRANSITIONS [“CAPS”]: 20-GA galvanized steel,
riveted to sleeve frame.
DUCT CONNECTION COLLARS: 22-GA galvanized
steel, crimped to transitions. PROJECT:
SEALANT CAULKING: UL-listed high-temperature type. LOCATION:
TAPE: UL-listed high-temperature pressure-sensitive foil ARCHITECT:
type. ENGINEER:
FUSIBLE LINK: UL-listed 165OF; replaceable. (Optional CONTRACTOR:
212OF available at no additional charge.) PO NUMBER:
CLOSURE SPRINGS (Horizontal Models): Heat- DATE: Arrow United Industries
A Division of Mestek, Inc.
treated Type 301 stainless steel constant force coiled
314 Riverside Drive . Wyalusing, PA 18853
negator type. Ph: (570) 746-1888 Fax: (570) 746-9286
MEMBER OF AMCA www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED MODEL 117X


1½-HR. STATIC RATED FIRE DAMPER “C” STYLE
WITH INTEGRAL SLEEVE FRAME

With 100% Free Area, Pressure Drop is determined by


FACE Area Velocity ( in lieu of Free Area Velocity).
FLOW [cfm]
FACE AREA VELOCITY [fpm] =
FACE AREA [sq. ft.]
DAMPER SIZING CHART

WIDTH: Add 2" to Nominal Duct Width


.07
HEIGHT: IF NOMINAL DUCT INCHES TO ADD FOR
HEIGHT IS: NOMINAL DAMPER .06
FRAME HEIGHT:
STATIC PRESSURE DROP (in. wg)

.05
4" THRU 18" 3"
19" THRU 28" 4" .04
29" THRU 40" 5"
41" THRU 42" 6" .03
Vertical Only 43" THRU 54" 6"

.02

AVAILABLE OPTIONS:
1. Sleeve frame length (“L” dimension) of 14", or 16".
2. 212OF fusible link. .01
1000 2000 3000
®
3. Electro Thermal Link [ETL ].
FACE AREA VELOCITY (fpm)
4. SPDT “closed damper” position indicator switch.

Arrow United Industries


IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE
Ph: (570) 746-1888 Fax: (570) 746-9286
CHANGES WITHOUT NOTICE.
www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-117F-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL 117F


NARROW-FRAME [1-5/8” DEEP]
1-1/2 HR. STATIC RATED VERTICAL MOUNT ONLY
FIRE DAMPER
Classified by Underwriters Laboratories as a 1-1/2 hour
ABI’s Narrow-Frame Model 117F facilitates installa- fire protection rated Fire Damper, in accordance with
tion behind or between grilles and registers in narrow Standards UL-555 and NFPA-90A, for the protection
fire-rated partitions. of openings in fire partitions having a fire resistance
rating of less than 3 hours.

UNDERWRITER’S LABORATORIES, INC.

Arrow United
CLASSIFIED

Industries
FIRE DAMPERS
FIRE RESISTANCE RATING 1-1/2 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX

California State Fire Marshal Listing No.


3225-1328:100

STANDARD MATERIALS & CONSTRUCTION: PROJECT:


FRAME: One-piece rollformed 22 Ga. galvanized LOCATION:
steel.
BLADES: 22 Ga. galvanized steel curtain-type. ARCHITECT
FUSIBLE LINK: UL-listed 165°F; replaceable ENGINEER:
(Optional 212°F available at no additional charge). CONTRACTOR:
DIMENSIONAL DATA: PO NUMBER: Additional Information
MINIMUM SIZE: 4”W X 4”H. on reverse side
DATE:
MAXIMUM SIZE:
Single Panel: 40”W x 40”H. Arrow United Industries
Multiple Panel: Not available. A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA
FIRE/SEAL® UL-CLASSIFIED MODEL 117F
1-1/2 HR. STATIC RATED FIRE DAMPER

FREE AREA (sq. ft.)


Duct Width (in.)
4” 8” 12” 16” 20” 24” 28” 32” 36” 40”
4” .03 .08 .1 .2 .2 .3 .3 .4 .4 .5
8” .1 .2 .4 .5 .6 .8 .9 1.0 1.2 1.3
DUCT HEIGHT (in.)

12” .2 .4 .6 .8 1.1 1.3 1.5 1.8 2.0 2.2


16” .2 .5 .8 1.2 1.5 1.8 2.1 2.4 2.7 3.1
20” .3 .7 1.1 1.5 1.9 2.3 2.8 3.2 3.6 4.0
24” .3 .8 1.3 1.8 2.3 2.8 3.3 3.8 4.3 4.8
28” .4 1.0 1.6 2.2 2.8 3.5 4.1 4.7 5.3 5.9
32” .4 1.1 1.8 2.5 3.2 3.9 4.5 5.2 5.9 6.6
36” .5 1.3 2.1 2.8 3.6 4.4 5.2 6.0 6.8 7.5
40” .5 1.4 2.3 3.2 4.0 4.9 5.8 6.6 7.5 8.4

FLOW (cfm)
FREE AREA VELOCITY [FPM] =
FREE AREA (sq. ft.)
STATIC PRESSURE DROP (in. wg)

AVAILABLE OPTIONS:
1. Factory-supplied sleeves (20 Ga. through 10 Ga.).
2. 212°F fusible link

FREE AREA VELOCITY (fpm)


Arrow United Industries
IN THE INTEREST OF PRODUCT DEVELOPMENT, A Division of Mestek, Inc.
ARROW UNITED INDUSTRIES RESERVES THE 314 Riverside Drive . Wyalusing, PA 18853
RIGHT TO MAKE CHANGES WITHOUT NOTICE. Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
ASD-317A-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED MODEL 317A


3-HR. STATIC RATED Vertical & Horizontal

FIRE DAMPER Classified by Underwriters Laboratories as a 3-hour fire protection rated Fire
Damper, FOR USE IN STATIC SYSTEMS, in accordance with Standards UL-555
and NFPA-90A, for the protection of openings in fire partitions having a fire
resistance rating of 3 hours or more.
Top Blade Riveted
to Frame UNDERWRITERS LABORATORIES
INC.
CLASSIFIED
FIRE DAMPERS
FIRE RESISTANCE RATING 3 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX
Fusible Link California State Fire Marshal
Listing No. 3225-1328:101
Nominal
Duct
Height 1½" x 1½" x
Less ¼" 16GA Galv.
(without Steel Sill
sleeve) Angle (One
Side Only:
Vertical Units
Only)

3"
¾" (Sill & Jambs)
4-7/8"

Nominal Duct
Width Less ¼"
(without sleeve)
Blade Lock*
Stainless Steel Negator
Closure Spring DIMENSIONAL DATA:
MINIMUM SIZE: 4" W x 4"H.
MAXIMUM SIZE - VERTICAL (Galvanized Steel):
* Damper is to be installed with blade lock points
Single Panel: 36" W x 36" H.
facing DOWNWARD and with access from above.
Multiple Panel: 72" W x 72" H;
in max. panels of 36"W x 36"H.
MAXIMUM SIZE - VERTICAL (Stainless Steel):
Single Panel: 47" W x 48" H.
STANDARD MATERIALS & CONSTRUCTION: Multiple Panel: 93" W x 48" H;
in max. panels of 47" W x 48" H.
FRAME: One-piece rollformed 22-Ga. galvanized steel.
BLADES: 22-Ga. galvanized steel curtain-type. MAXIMUM SIZE - HORIZONTAL (Galvanized Steel):
FUSIBLE LINK: UL-listed 165OF; replaceable. (Optional 212OF available at Single Panel: 48" W x 48" H.
no additional charge.) Multiple Panel: 72" W x 36" H.
CLOSURE SPRINGS (Horizontal Models): Heat-treated Type 301 in max. panels of 36" W x 36" H.
stainless steel constant force coiled negator type. NOTE: Unassembled multiple units do not include mullions.

PROJECT:
LOCATION:
Arrow United Industries ARCHITECT:
A Division of Mestek, Inc. ENGINEER:
314 Riverside Drive . Wyalusing, PA 18853 CONTRACTOR:
Ph: (570) 746-1888 Fax: (570) 746-9286 PO NUMBER:
www.arrowunited.com
DATE:
Additional information
MEMBER OF AMCA on reverse side.
ARROW UNITED INDUSTRIES SUBMITTAL DATA
FIRE/SEAL® UL-CLASSIFIED
3-HR. STATIC RATED FIRE DAMPER MODEL 317A
14 Ga. “ZEE MULLION” required for Multiple Panel
Vertical Mount Dampers (Model 317AV) only.
Note: Minimum sleeve length is 9".

AVAILABLE OPTIONS:
1. Factory-supplied sleeves (20-Ga. through 10-Ga.).
2. Type 304 stainless steel construction
(available for Vertical Mount dampers only).
3. 212OF fusible link.
4. Electro Thermal Link [ETL®].
5. SPDT “closed damper” position indicator switch.
6. "Pull Ring" for ease of reopening closed damper.
(Horizontal Models Only.)

VERTICAL
(MODEL 317AV)
FREE AREA [sq. ft.] Duct Width (in.)
4 8 12 16 20 24 28 32 36 40 44 47
4 .02 .06 .08 .13 .16 .20 .22 .26 .30 .33 .37 .40
8 .08 .19 .32 .48 .59 .72 .85 1.0 1.2 1.3 1.4 1.5
12 .16 .35 .60 .75 1.0 1.2 1.5 1.7 2.0 2.2 2.4 2.6
Duct Height (in.)

16 .19 .52 .79 1.0 1.4 1.7 2.0 2.3 2.7 3.1 3.4 3.6
20 .27 .65 1.0 1.4 1.9 2.1 2.6 3.0 3.5 4.0 4.5 4.8
24 .33 .84 1.1 1.7 2.2 2.8 3.1 3.6 4.2 4.8 5.3 5.7
28 .37 .95 1.4 2.0 2.6 3.2 4.0 4.4 5.0 5.9 6.4 6.9
32 .45 1.1 1.7 2.2 3.0 4.0 4.7 5.1 5.7 6.5 7.2 7.8
36 .49 1.2 2.0 2.6 3.5 4.5 5.2 6.0 7.1 7.7 8.1 8.9
40 .54 1.4 2.3 3.0 4.0 5.0 6.0 6.8 7.9 8.7 9.0 10.0 FREE AREA VELOCITY [fpm] =
44 .58 1.6 2.5 3.3 4.4 5.4 6.6 7.7 8.5 9.5 10.2 11.1 FLOW [cfm]
48 .64 1.7 2.7 3.8 5.0 6.0 6.9 8.0 9.3 10.6 11.3 12.5 FREE AREA [sq. ft.]

HORIZONTAL
(MODEL 317AH)
FREE AREA [sq. ft.] Duct Width (in.)
4 8 12 16 20 24 28 32 36 40 44 48
4 .03 .09 .1 .2 .3 .3 .4 .4 .5 .6 .6 .7
8 .1 .2 .4 .6 .7 .9 1.0 1.2 1.4 1.5 1.7 1.8
STATIC
12 .2 .4 .7 .9 1.2 1.5 1.8 2.0 2.3 2.6 2.8 3.1
Duct Height (in.)

PRESSURE
DROP
16 .2 .6 .9 1.3 1.7 2.0 2.4 2.8 3.1 3.5 3.9 4.2 [in. wg.]
20 .3 .7 1.2 1.7 2.1 2.6 3.1 3.5 4.0 4.5 5.0 5.4
24 .4 .9 1.4 2.0 2.6 3.2 3.7 4.3 4.9 5.4 6.0 6.6
28 .4 1.0 1.7 2.4 3.0 3.7 4.4 5.0 5.7 6.4 7.0 7.7
32 .5 1.2 2.0 2.7 3.5 4.3 5.1 5.8 6.6 7.4 8.2 9.0
36 .5 1.3 2.2 3.1 4.0 4.8 5.7 6.6 7.4 8.4 9.2 10.1
40 .6 1.5 2.5 3.5 4.4 5.4 6.4 7.4 8.4 9.3 10.3 11.3
44 .6 1.7 2.7 3.8 4.9 6.0 7.0 8.1 9.2 10.3 11.4 12.4
48 .7 1.8 3.0 4.2 5.4 6.6 7.7 8.9 10.1 11.3 12.5 13.7
FREE AREA VELOCITY [fpm]

Arrow United Industries


IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE
Ph: (570) 746-1888 Fax: (570) 746-9286
CHANGES WITHOUT NOTICE.
www.arrowunited.com
ASD-317B-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED MODEL 317B


Vertical & Horizontal
3-HR. STATIC RATED
FIRE DAMPER Classified by Underwriters Laboratories as a 3-hour fire protection rated Fire
Damper, FOR USE IN STATIC SYSTEMS, in accordance with Standards UL-555
and NFPA-90A, for the protection of openings in fire partitions having a fire
resistance rating of 3 hours or more.

UNDERWRITERS LABORATORIES INC.


CLASSIFIED

Arrow United
Industries
FIRE DAMPERS
FIRE RESISTANCE RATING 3 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX

California State Fire Marshal


Listing No. 3225-1328:100
(CSFM Vertical Mount Only)

DIMENSIONAL DATA:
MINIMUM SIZE: 4" W x 3" H (Duct), 4" W x 5" H (Frame).
MAXIMUM SIZE - VERTICAL (Galvanized Steel):
Single Panel: 36" W x 32" H (Duct), 36" W x 36" H (Frame).
Multiple Panel: 72" W x 68" H (Duct), 72" W x 72" H (Frame);
in max. panels of 36"W x 32"H (Duct), 36"W x 36"H (Frame).
MAXIMUM SIZE - VERTICAL (Stainless Steel):
Single Panel: 47" W x 42" H (Duct), 47" W x 48" H (Frame).
Multiple Panel: 93" W x 42" H (Duct), 93" W x 48" H (Frame);
in max. panels of 47" W x 42" H (Duct), 47" W x 48" H (Frame).
MAXIMUM SIZE - HORIZONTAL (Galvanized Steel):
Single Panel: 48" W x 43" H (Duct), 48" W x 48" H (Frame).
Multiple Panel: 72" W x 32" H (Duct), 72" W x 36" H (Frame).
STANDARD MATERIALS & CONSTRUCTION: in max. panels of 36" W x 32" H (Duct), 36" W x 36" H (Frame).
FRAME: One-piece rollformed 22-GA galvanized steel. NOTE: Unassembled multiple units do not include mullions.
BLADES: 22-GA galvanized steel curtain-type.
FUSIBLE LINK: UL-listed 165OF; replaceable. (Optional 212OF available at
no additional charge.) PROJECT:
CLOSURE SPRINGS (Horizontal Models): Heat-treated Type 301 stainless
LOCATION:
steel constant force coiled negator type.
ARCHITECT:
Arrow United Industries ENGINEER:
A Division of Mestek, Inc.
CONTRACTOR:
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 PO NUMBER:
www.arrowunited.com DATE:
Additional information
on reverse side.
MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED
3-HR. STATIC RATED FIRE DAMPER MODEL 317B
14 Ga. “ZEE MULLION” required (field-supplied) for Multiple
Panel Vertical Mount Dampers (Model 317BV) only.
Note: Minimum sleeve length is 9".

AVAILABLE OPTIONS:
1. Factory-supplied sleeves (20-Ga. through 10-Ga.).
2. Type 304 stainless steel construction.
(available for Vertical Mount dampers only).
3. 212OF fusible link.
4. Electro Thermal Link [ETL®].
5. SPDT “closed damper” position indicator switch.
6. "Pull Ring" for ease of reopening closed damper.
(Horizontal Models Only.)

VERTICAL (Model 319BV)


HORIZONTAL (Model 317BH)
IF NOMINAL DUCT INCHES TO HEAD
HEIGHT IS: ADD FOR HEAD IF NOMINAL INCHES TO ADD
SINGLE PANEL SIZING DUCT FOR HEAD
GALVANIZED
OR
3" thru 18"
19" thru 28"
2"
3"
CHARTS HEIGHT IS:
STAINLESS 29" thru 32" 4" GALVANIZED
33" thru 40" 4" 3" THRU 18" 2" STEEL
STAINLESS
ONLY 41" 5" ONLY
42" 6" 19" THRU 28" 3" (STAINLESS
See STEEL
MULTIPLE PANEL DIMENSIONAL DATA 29" THRU 40" 4" NOT
GALVANIZED
ONLY
33" thru 37" 2" on front side. 41" THRU 43" 5" AVAILABLE)

(STAINLESS NOT 38" thru 57" 3"


AVAILABLE) 58" thru 68" 4"

VERTICAL FREE AREA [sq. ft.] Duct Width (in.)


(MODEL 317BV) 4 8 12 16 20 24 28 32 36 40 44 47 FREE AREA VELOCITY [fpm] =
4 .04 .09 .16 .22 .29 .35 .41 .47 .54 .58 .64 .70 FLOW [cfm]
8 .09 .27 .44 .62 .79 .97 1.1 1.3 1.5 1.6 1.8 1.9 FREE AREA [sq. ft.]
12 .16 .44 .73 1.0 1.3 1.6 1.9 2.1 2.4 2.6 2.9 3.2
Duct Height (in.)

.3
16 .22 .62 1.0 1.4 1.8 2.2 2.6 3.0 3.4 3.7 4.1 4.4
20 .29 .79 1.3 1.8 2.3 2.8 3.3 3.8 4.3 4.7 5.2 5.7 .2
24 .35 .97 1.6 2.2 2.8 3.4 4.1 4.7 5.3 5.8 6.4 6.9
28 .41 1.1 1.9 2.6 3.3 4.1 4.8 5.5 6.2 6.8 7.5 8.2
32 .47 1.3 2.1 3.0 3.8 4.7 5.5 6.3 7.2 7.8 8.7 9.4
36 .51 1.4 2.3 3.2 4.2 5.0 5.9 6.8 7.7 8.6 9.4 10.2 .10
40 .58 1.6 2.6 3.6 4.6 5.7 6.6 7.7 8.7 9.5 10.5 11.4 .09
42 .61 1.7 2.8 3.8 5.0 6.1 7.2 8.3 9.3 10.2 11.3 12.3 .08
STATIC .07
PRESSURE .06
VERTICAL
FREE AREA [sq. ft.] Duct Width (in.) DROP
[in. wg.] .05
(MODEL 317BH) 4 8 12 16 20 24 28 32 36 40 44 48 .04
4 .06 .2 .3 .4 .5 .5 .6 .7 .8 .9 1.0 1.1
.03
8 .2 .4 .6 .8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
Duct Height (in.)

12 .2 .5 .9 1.2 1.5 1.8 2.1 2.4 2.7 3.0 3.4 3.7


16 .3 .7 1.2 1.6 2.0 2.4 2.8 3.3 3.7 4.1 4.5 5.0 .02
20 .4 .9 1.4 2.0 2.5 3.0 3.6 4.1 4.7 5.2 5.7 6.3
24 .4 1.1 1.7 2.4 3.0 3.7 4.3 5.0 5.6 6.3 6.9 7.5
28 .5 1.2 2.0 2.8 3.5 4.3 5.0 5.8 6.5 7.3 8.0 8.8 .01
32 .6 1.5 2.3 3.2 4.0 4.9 5.8 6.7 7.5 8.4 9.3 10.1 1000 2000 3000
36 .7 1.6 2.6 3.6 4.6 5.5 6.5 7.5 8.5 9.5 10.4 11.4
FREE AREA VELOCITY [fpm]
40 .7 1.8 2.9 4.0 5.1 6.2 7.3 8.4 9.4 10.5 11.6 12.7
43 .7 1.9 3.0 4.1 5.3 6.5 7.6 8.8 9.9 11.1 12.3 13.4
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES
RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-317C-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL 317C


3-HR. STATIC RATED Vertical & Horizontal

FIRE DAMPER Classified by Underwriters Laboratories as a 3-hour fire protection rated Fire
Damper, FOR USE IN STATIC SYSTEMS, in accordance with Standards UL-555
RECTANGULAR, ROUND, & OVAL and NFPA-90A, for the protection of openings in fire partitions having a fire
resistance rating of 3 hours or more.

UNDERWRITERS LABORATORIES INC.


CLASSIFIED

Arrow United
Industries
VERTICAL MOUNT FIRE DAMPERS
FIRE RESISTANCE RATING 3 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX

Total Housing Height


(Equals nominal California State Fire Marshal
damper frame height
less 1/4", plus four Fusible Listing No. 3225-1328:101
times gauge of
housing.)
Link Housing (CSFM Vertical Mount Only)
(Four times std. 18-
Nominal
Breakaway IMPORTANT
duct
GA housing equals height
Connection FOR ROUND DUCT DIAMETERS
0.23") less 1/4" UP TO 36", AND FOR OVAL DUCT
(100% SIZES UP TO 71" W X 30" H,
See damper sizing free area.)
chart 1½" x ½" x 16-GA ARROW'S 22-GA DUCT CONNEC-
galv. steel angle
(one side only;
TION COLLAR (CRIMPED TO THE
Collar (for
vertical units only) connection to duct) DAMPER HOUSING) CONSTI-
TUTES A U.L.-APPROVED DUCT-
TO-SLEEVE "BREAKAWAY" CON-
¾" (Sill &
1" typ. NECTION,
2" three sides
Jambs) THUS ALLOWING A RIGID CON-
"L" (5" is std.)
Longer lengths thru 24" are NECTION JOINT TO BE UTILIZED
available BETWEEN THE DAMPER'S DUCT
CONNECTION COLLAR AND THE
ROUND OR OVAL DUCTWORK.
HORIZONTAL MOUNT
DIMENSIONAL DATA:
MINIMUM SIZE: 4" W x 4" H (Duct), 6" W x 7" H (Frame).

MAXIMUM SIZE - VERTICAL(Galvanized Steel):


Single Panel: 34" W x 31" H (Duct), 36" W x 36" H (Frame).
Blade Multiple Panel: 70" W x 67" H (Duct), 72" W x 72" H (Frame).
Lock*
MAXIMUM SIZE - VERTICAL(Stainless Steel):
Single Panel: 45" W x 41" H (Duct), 47" W x 48" H (Frame).
Multiple Panel: 91" W x 41" H (Duct), 93" W x 48" H (Frame).

MAXIMUM SIZE - HORIZONTAL(Galvanized Steel):


Stainless Steel Negator
Single Panel: 46" W x 42" H (Duct), 48" W x 48" H (Frame).
Closure Spring
Multiple Panel: 70" W x 31" H (Duct), 72" W x 36" H (Frame).

*Damper is to be installed with blade NOTE: Dampers should be ordered by nominal duct size.
lock points in the DOWNWARD position Fractional duct dimension (1/8" min.) will require the
same fractional addition to the corresponding damper
housing dimension.
STANDARD MATERIALS & CONSTRUCTION:
FRAME: One-piece rollformed 22-GA galvanized steel.
BLADES: 22-GA galvanized steel curtain-type. PROJECT:
WELDED-SEAM HOUSING: 18-GA galvanized steel (Std.). LOCATION:
DUCT CONNECTION COLLAR: 22-GA galvanized steel. ARCHITECT:
FUSIBLE LINK: UL-listed 165OF; replaceable. (Optional 212OF available at no ENGINEER:
additional charge.)
CLOSURE SPRINGS: Heat-treated Type 301 stainless steel constant force CONTRACTOR:
coiled negator type. PO NUMBER:
Arrow United Industries DATE:
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 MEMBER OF AMCA Additional information
www.arrowunited.com on reverse side.
ARROW UNITED INDUSTRIES SUBMITTAL DATA
FIRE/SEAL® UL-CLASSIFIED
3-HR. STATIC RATED FIRE DAMPER
UL Listed Hi-Temp Pressure Sensitive Foil Tape (typ.) MODEL 317C

Total Transition
Total Transition Width (Equals
Width (Equals Total Transition
Nominal Duct
Nominal Duct Width (Equals
Width Plus 1.93")
Width Plus 1.93") Nominal Duct Transition
Width Plus 1.93")

Transition Transition
Collar

Collar Collar

"L" "L" Nominal Duct "L"


Nominal Nominal Width Less
Duct Width Duct Width 1/4"
Less 1/4" Less 1/4"

“THW”: Total
Housing
Width
{
} Equals Nominal Duct Width less 1/4", Plus 2",
Plus Four Times Gauge of Housing:
(Four times standard 18-Ga. housing equals 0.23").

VERTICAL (Model 317CV) DAMPER HORIZONTAL (Model 317CH)


INCHESTOADDFOR
IF NOMINAL DUCT
HEIGHT IS:
NOMINALDAMPER
FRAMEHEIGHT:
SIZING IF NOMINAL INCHES TO ADD FOR
SINGLE PANEL CHARTS DUCT NOMINAL DAMPER
GALVANIZED 4" thru 18" 3"
HEIGHT IS: FRAME HEIGHT:
OR 19" thru 28" 4"
STAINLESS 29" thru 31" 5" Width: GALVANIZED
32" thru 40" 5" Add 2" to 4" THRU 18" 3" STEEL
STAINLESS
ONLY Nominal ONLY
41" 6" 19" THRU 28" 4" (STAINLESS
Duct Width. STEEL
MULTIPLE PANEL 29" THRU 40" 5" NOT
GALVANIZED 32" thru 36" 3"
ONLY See 41" THRU 42" 6" AVAILABLE)
37" thru 60" 4"
(STAINLESS NOT DIMENSIONAL DATA
AVAILABLE) 61" thru 67" 5" on front side.

FLOW [cfm]
With 100% Free Area, Pressure Drop is determined by FACE AREA VELOCITY [fpm] =
FACE Area Velocity (in lieu of Free Area Velocity). FACE AREA [sq. ft.]
.07
AVAILABLE OPTIONS:
.06

1. 16-GA through 10-GA housing. .05


2. Housing length ("L" dimension) of 6" through 24".
3. Type 304 stainless steel construction. .04
(available for Vertical Mount dampers only). STATIC
4. 212OF fusible link. PRESSURE
DROP
5. Electro Thermal Link [ETL®]. [in. wg.] .03
6. SPDT "closed damper" position indicator switch.
7. "Pull Ring" for ease of reopening closed damper.
.02
(Horizontal Models Only.)

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853 .01
Ph: (570) 746-1888 Fax: (570) 746-9286 MEMBER OF AMCA 1000 2000 3000
www.arrowunited.com FACE AREA VELOCITY [fpm]

IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
INSTALLATION AND MAINTENANCE INSTRUCTIONS II-117-04.11
1-1/2 HOUR RATED, UL CLASSIFIED FIRE DAMPER
FOR USE IN FIRE BARRIERS WITH RATINGS OF LESS THAN 3 HOURS
MODELS 117, D17

INSPECTION INSTALLATION
Inspect for shipping damage. The intent of a proper installation is to secure the fire
Inspect for proper size and model. damper in the opening in such a manner as to prevent
Inspect installed damper for proper orientation, as distortion and disruption of the damper operation by
stated on damper label. allowing the fire damper to expand and for the connect-
Inspect for obstructions which could interfere with free ing duct to separate in the event of the collapse of the
operation and complete closure. hanging system. The fire damper must be positioned
Manually cycle the damper to verify proper operation. within the masonry, block or gypsum wallboard fire
barrier (when vertically mounted) or masonry floor
(when horizontally mounted). Reference page 5 for
details of a suggested drywall partition. If the damper
uses an ETL (Electro-Thermal-Link) refer to the
TYPICAL INSTALLATION instructions packaged with the link.

MIN. 1" OVERLAP


DAMPER TO SLEEVE ATTACHMENT
ON ALL SIDES AND A sleeve shall be used unless the damper has an
CORNERS integral sleeve of sufficient length to permit direct
SEE NOTE ON attachment of perimeter mounting angles.
CLEARANCE This damper can be supplied by the factory mounted in
SEE NOTE ON a sleeve. If the sleeve is not factory supplied, it must
REVERSE ANGLE
be attached on both sides of the damper by one of the
following methods:
Secure with 1/4" dia. bolts and nuts or by welding with
beads 1/2" in length, or with No. 10 steel sheet metal
screws, or 3/16" steel rivets. Fasteners shall be 8"
maximum on centers. Fasteners cannot be placed
where they will interfere with damper operation.
Gaps at corners between the damper and its sleeve
SEE NOTE ON must be small enough to prohibit the passage of a 1/8"
DAMPER TO SLEEVE
ATTACHMENT AND diameter rod through the entire depth of the opening. A
1
SLEEVE GAUGE /4" diameter rod cannot pass through the gap between
REQUIREMENTS
two damper panels and its sleeve.
SEE NOTE ON SLEEVE THICKNESS
MOUNTING ANGLE
SEE NOTE
ATTACHMENT Sleeves shall be the same gauge or heavier as the duct
ON DUCT
CONNECTION to which it is attached. Gauges shall conform to
3" MIN. FOR DUCT
CONNECTION AND
SMACNA or ASHRAE duct standards. Damper sleeve
MTG. ANGLES can be no thicker than 10 GA steel.
6" MAX.
EXPANSION CLEARANCE
16" MAX. WHEN
FACTORY INSTALLED The opening in the wall or floor for the fire damper shall
ACCESS DOOR be sized so as to provide expansion clearance between
WALL MOUNT SHOWN, the sleeve and opening. Clearances do not vary with
FLOOR MOUNT SIMILAR walls constructed of different materials. A minimum of
1
/8" per foot of overall damper/sleeve width and height
is required. The maximum opening size shall not
exceed 1/8" per foot plus 1", minimum total clearance
shall be at least 1/4" larger than the overall assembly.
Example: a 36" x 36" damper will require a minimum
opening of 363/8" x 363/8".

1
MOUNTING ANGLES DUCT CONNECTION
Secure mounting angles to the sleeve and not to the The installation of the damper and all duct connections
wall or floor. Mounting angles are to frame the four to the damper sleeve shall conform to NFPA-90A and
sides of the sleeve on both faces. Where local codes the SMACNA Fire, Smoke and Radiation Damper In-
allow, corners of mounting angles can be welded for stallation Guide. All duct connections shall also con-
dampers 96"W x 60H" or smaller. When reverse form to UL555. Connecting ducts shall not be continu-
mounting angles are used, the size of the opening ous but shall terminate at the damper sleeve. Duct
must be increased to maintain the specified expansion connections to the sleeve will be either of the breakaway
clearance between the angle/fasteners and the open- or rigid types, breakaway types are listed below. The
ing. Angles shall be a minimum of 1 1/2" x 7/8" x 16 GA. following determines if the connections are to be rigid
Fasten angles to the sleeve using 1/4" dia. bolts and or breakaway. For rigid type duct connections, sleeve
nuts, or by welding with beads 1/2" in length, or with No. shall be a minimum of 16 GA on dampers not exceeding
10 steel sheet metal screws, or with 3/16" steel rivets. 36" wide or 24" high or 24" diameter and 14 GA on
Fasteners or weld beads shall be 8" maximum on larger units. Dampers supplied with thinner sleeves
centers. will require a breakaway connection of the following
type: Plain “S” slip, Double “S” slip, Inside slip, Hemmed
ACCESS “S” slip, Standing “S” slip (bar reinforced, angle rein-
forced or alternate bar), Standing “S” slip shown below,
Suitable access must be provided for damper inspec-
Ductmate type-connections as shown on page 6. All
tion and servicing. Where it is not possible to achieve
connections not listed as breakaway shall be consid-
sufficient size access, it will be necessary to install a
ered as rigid. Breakaway joints shall have no more than
removable section of duct.
two No. 10 sheet metal screws on each side and on the
bottom. The screws shall penetrate both sides of the
CAULKING
slip pocket. When a breakaway joint is used along the
Caulking is allowed between the mounting angles and top and bottom duct connection, a flat drive slip no
the damper sleeve, and between the mounting angles longer than 20 inches is permitted on the two sides.
and the floor or wall construction. Caulking is not
allowed between the damper sleeve and the wall or MAINTENANCE
floor inside the opening (annular space).
Dampers shall be maintained in intervals as stated in
Caulk shall be one of the following:
NFPA-90A, Annex B, unless local codes require more
Dow Corning RTV 732, General Electric IS 808,
frequent inspections. Check the fuse link, check the
Novagard RTV 300 or similar silicone sealants.
stainless steel closure springs where furnished, cycle
damper and check for free operation and complete
closure, clean with mild detergent or solvent, secure
damper open with fusible link.

PLAIN "S" SLIP DOUBLE "S" SLIP INSIDE SLIP JOINT HEMMED "S" SLIP

STANDING "S" SLIP STANDING "S" SLIP STANDING "S" SLIP STANDING "S" SLIP
(BAR REINFORCED) (ANGLE REINFORCED) (ALTERNATE BAR)

2
SLEEVE MOUNTING ANGLE

2 HOUR MAXIMUM
RATED WALL OR
PARTITION
EXPANSION CLEARANCE
METAL OR
SEE NOTE NO. 4
WOOD FRAME
FILLER NOT REQUIRED CONSTRUCTION
STEEL RETAINING ANGLE
WITH METAL FRAMING
SEE NOTE NO. 6

GRILLE-TO-FLANGE STEEL SLEEVE


FASTENERS NOT 13/16" FLANGE
TO PENETRATE (MINIMUM)
WALL FRAMING

TYPE "B" GRILLE BY OTHERS,


SEE NOTE NO. 2

DAMPER TO SLEEVE
MOUNTING ANGLE (MIN. 10 GA) ATTACHMENT, SEE
NOTE NO. 5.
2" MAX.

DUCT
CENTERLINE OF BLADES
MUST BE WITHIN PLANE
OF FIRE BARRIER
FIRE ALTERNATE
DAMPER SLEEVE TYPE "B"
MOUNTING

DUCT DAMPER BEHIND A GRILLE


MOUNTING ANGLE
These instructions illustrate an approved method of
mounting a Classified curtain-type fire damper behind
SLEEVE
a grille or register. Closed centerline of fire damper
blades must be within the plane of the fire barrier.
1. This installation is limited to a maximum size ver-
tically mounted damper of 36" wide x 42" high.
2. Grille: A minimum 26 ga. steel frame is required,
core of grille can be aluminum or nonmetallic. If a
thinner or non-steel grille frame is used, then open
corners of flanged sleeve must be closed off with
TYPE "C"
20 ga. (minimum) steel corner tabs (by others)
SEE NOTE 1
riveted to flanges.
3. Expansion Clearance: Minimum of an 1/8" per foot
TYPE "C" on damper width and height. The maximum open-
The factory supplied 22 GA collar to 18 GA cap ing size shall be no more than 1/4" greater than the
connection on type “C” dampers is a “breakaway” minimum opening size.
connection under the following conditions: 4. Duct Connections: See Duct Connection section.
1. Round duct diameters are no larger than 36". 5. Damper to Sleeve Attachment: Damper can be
stitch welded directly to the sleeve with 1/2" long
2. Oval duct sizes are no larger than 71"W x welds, on one side, at 6" maximum O.C. As an
30"H. alternate, a 16 ga. steel clip angle can be welded to
one side of the frame and attached to the sleeve
3. Duct gauges shall conform to the S M A C N A
with 3/16" bolts / nuts or sheet metal screws or
or ASHRAE duct standard.
rivets. Clips and fasteners are 6" maximum O.C.,
4. Duct to be attached to the 22 GA damper collar 3" maximum from corners.
with minimum #8 S.M.S. minimum of four screws 6. Retaining Angles: 1-1/2" x 7/8" x 16 ga. (minimum)
per connection. For round duct diameters greater steel retaining angles attached with 3/16" steel
than 24", a minimum of five #10 S.M.S. are bolts / nuts or sheet metal screws or rivets or by 1/
required per connection. 2" long welds. Fasteners 6" maximum O.C., 3"
Dampers outside of these restrictions must use a 4" maximum from corners.
wide drawband connection as shown in the SMACNA 7. Refer to supplemental installation instructions
Fire, Smoke and Radiation Damper Installation A33131 when damper blades are outside of the
Guide. 3 wall plane.
VERT. OR MAX. W x H MAX. W x H MAX. W x H
MODEL HORIZ. TYPE SINGLE SECTION OF ASSEMBLY MULLION
NO. MOUNT SECTION (in.) ASSEMBLY (in.) (in.) DETAILS

117V Vertical Static 60 x 60 40 x 60 120 x 120 1, 2

117FV Vertical Static 40 x 40 --- --- ---

117XV Vertical Static 60 x 60 --- --- ---

117H Horizontal Static 48 x 48 36 x 48 102 x 48 1

117XH Horizontal Static 48 x 48 --- --- ---

D17V, D17XV Vertical Dynamic 36 x 36 --- --- ---

D17H, D17XH Horizontal Dynamic 24 x 24 --- --- ---

NOTES:
1. In cases where the wall/floor opening is larger than the 3. Mullion details specified are based on the fire ratings qualifica-
approved maximum assembly size, an approved mullion tion tests. The user is responsible for additional structural
must separate the large opening into smaller openings. supports of multiple section dampers when required by el-
For use with static rated systems only. See Figure 6-3 evated air pressure differential in the closed position and in
from SMACNA's Fire Damper Installation Guide. some cases seismic loading.
2. Reference page 7 for approved fabricated galvanized 4. Unassembled multiple section assemblies are shipped without
steel mullion for use in oversized vertical wall openings. the mullions and are to be field fabricated per details provided
For use in static rated systems only. in these instructions.

DETAIL 1 DETAIL 1

2 PANELS WIDE 3 PANELS WIDE

DETAIL 1 DETAIL 1

DETAIL 2 DETAIL 2 DETAIL 2

2 PANELS HIGH 2 PANELS WIDE 3 PANELS WIDE


BY BY
2 PANELS HIGH 2 PANELS HIGH

1/2" LONG BEADS


8" MAX. ON CENTERS
ON BOTH FACES
OR
1/4" DIA. BOLTS AND NUTS
8" MAX. ON CENTERS ON
BOTH FACES

1/4" DIA. STEEL BOLTS AND NUTS, OR 1/2" LONG


14 GA STEEL MULLION WELDS, OR NO. 10 STEEL SHEET METAL SCREWS OR
PLATE, 4-7/8" WIDE 3/16" DIA. STEEL RIVETS, FASTENERS TO BE 8" MAX.
BY OPENING HEIGHT ON CENTERS.

DETAIL 1 DETAIL 2

4
INSTALLATION INSTRUCTIONS FOR 1-1/2 HOUR
UL CLASSIFIED FIRE DAMPERS INSTALLED INTO
METAL OR WOOD FRAMED 1 HOUR AND 2 HOUR RATED DRYWALL PARTITIONS

CEILING RUNNER

24" O.C. 16" O.C.


MAX. MAX.

12" B 2-1/2" MIN.


A A RUNNER
2-1/2" MIN.
B STUD
RUNNER
90º BEND PANHEAD SCREWS
LOCAL CODES MAY
(METAL STUDS)
REQUIRE DOUBLE
NAILS (WOODEN STUDS)
HEADER 4 PER 90º BEND

2 FASTENERS 2"

2"
SECTION A-A
2 FASTENERS

FLOOR RUNNER

MIN. 2-1/2" STUD


OR RUNNER
MIN. 1/2" THICK NOTES:
GYPSUM WALLBOARD

1. These illustrated partition designs have successfully been


DRYWALL SCREWS (METAL STUDS)
OVERLAP

NAILS (WOOD STUDS) tested in conjunction with 1-1/2 hour classified fire dampers,
MIN. 1"

RETAINING ANGLE. for additional designs, reference Underwriters Laboratories,


ONE SIDE MAY BE Inc. Fire Resistance Directory. Specific framing require-
REVERSED PROVIDING THAT
ADEQUATE CLEARANCE IS ments of openings may vary with the Local Authority that
MAINTAINED
has jurisdiction. Specific framing requirements should be
SEE NOTE 2
provided in the architectural and structural drawings.

FIRE DAMPER
2. Reference the damper's installation instructions regarding
MIN. 1/2" THICK FILLER
PIECE, SEE NOTES 4 & 5
SLEEVE the approved method of attaching the damper to the sleeve,
attaching the retaining angles to the sleeve, required
expansion clearances, sleeve gauge, etc. Type of framing
1 HOUR RATED PARTITION WALL does not affect the stated required expansion clearance.

SECTION B-B 3. Gypsum panels surrounding the opening are to be fastened


to all stud and runner flanges, 12" O.C. maximum.

MIN. 2-1/2" STUD


MIN. 1/2" THICK
4. When wooden studs are used, filler pieces must be installed
OR RUNNER
GYPSUM WALLBOARD around the entire opening. Filler pieces are optional when
metal studs are used (consult local codes to determine if
filler pieces are required). Filler pieces are to be double
DRYWALL SCREWS (METAL STUDS)
NAILS (WOOD STUDS) screwed (or nailed to wooden studs) on 12" max. centers to
MIN. 1"
OVERLAP RETAINING ANGLE. the web of runners and studs.
ONE SIDE MAY BE
REVERSED PROVIDING THAT
ADEQUATE CLEARANCE IS 5. Some local jurisdictions require filler pieces around both
MAINTAINED
SEE NOTE 2
wood and metal framed openings (no filler pieces around
concrete or masonry openings). These codes also require a
double header for wood framed openings, consult local code
MIN. 1/2" THICK FILLER
FIRE DAMPER authorities.
SLEEVE
PIECE, SEE NOTES 4 & 5

6. Double jamb studding shown and required when opening


2 HOUR RATED PARTITION WALL width or height exceeds 36". Single jamb studding
acceptable for openings 36" x 36" and smaller.

5
1" MINIMUM METAL STUD EXPANSION CLEARANCE OF
OVERLAP CONSTRUCTION 1/8" PER FOOT OF DAMPER
SEE NOTE ON DUCT WIDTH AND HEIGHT, 1/4"
CONNECTION MINIMUM. MAXIMUM CLEARANCE
OF 1/8" PER FOOT PLUS 1".

SEE NOTE #4 FOR


ATTACHMENT METHOD

NOTE: SEE SUPPLEMENTAL


INSTALLATION INSTRUCTIONS
A33129 FOR ONE-SIDE MOUNTING
WITH RETAINING ANGLE UNDER
THE GYPSUM WALLBOARD

1-1/2" x 7/8" x 16 GA.


(MINIMUM SIZE) STEEL
RETAINING ANGLES,
CLOSED CORNERS

16" MAXIMUM ON SIDE WITH


FACTORY INSTALLED
ACTUATOR OR FACTORY 6" MAXIMUM ON NON-
INSTALLED ACCESS DOOR MOTOR FACE OR NON-
WOOD STUD ACCESS-DOOR SIDE
CONSTRUCTION

WALL/PARTITION CONSTRUCTION
VARIES, PER TESTED DESIGN

ONE SIDE MOUNTING OUTSIDE


GYPSUM WALLBOARD

APPLICATION
These instructions illustrate alternate mounting of Classi- damper sleeve and to the partition framing on all four sides of
fied fire and fire/smoke dampers to a rated wall or partition this one face mounting method.
from one side only. The steel retaining angles are on the A. Damper sleeve to retaining angles attached 6" maximum
outside face of the gypsum board and on the outside of the on-centers, 3" maximum from each corner, minimum of two
masonry or concrete wall or partition. fasteners per side by the following means:
1. This installation is limited to the following: 1. 3/16" diameter steel bolts and nuts,
A. Two hour or less rated wall or partition. 2. Welding, 1/2" long beads,
B. Vertically mounted damper. 3. #10 steel sheet metal screws,
C. Wood stud/metal stud gypsum board construction as 4. 3/16" diameter steel rivets.
well as masonry/concrete construction. B. Retaining angles to gypsum board wall framing attached
D. Maximum side damper of 48" wide x 36" high or 36" using drywall screws 6" maximum on-centers, 3" maximum
wide x 48" high. from each corner, minimum of two fasteners per side.
2. See page 6 for opening framing details. C. Retaining angles to concrete or masonry attached using
3. Closed plane of damper blades must be within the plane 3/16" steel masonry fasteners 6" maximum on-centers, 3"
of the rated wall or partition. maximum from each corner, minimum of two fasteners per
4. Steel retaining angles must be attached to both the side.

6
MULLION INSTALLATION INSTRUCTIONS FOR FIRE DAMPERS
INSTALLED IN OVERSIZED WALL OPENINGS
(For use with Static Rated Systems only)

These fabricated galvanized steel mullions are intended to subdivide a large vertical wall
opening into smaller openings. These smaller openings are not to exceed the maximum
size restrictions of the UL Classified 1-1/2 hour galvanized steel fire damper assembly.

A DETAILS C, D, E

WALL
OPENING 2" 2"

3/4" 3/4"

B
3-1/2"
DETAILS A & B

3/8"
120" DETAILS A & B
MAXIMUM DETAILS C, D, E WALL
HEIGHT DETAIL F THICKNESS
3/16" BLIND RIVET
MULLION CROSS SECTION
OR 3/4" LONG WELDS
16 GA. GALVANIZED STEEL
12" C/C, 6" MAX.
FROM ENDS
HORIZONTAL
MULLION
VERTICAL DETAIL A
MULLION

RETAINING ANGLES ARE NOT


FASTENED TO MULLION TUBE
1"
MIN.

'A' and 'B' opening sizes are not to


exceed the damper's approved maxi-
mum multiple assembly size. Vertical,
horizontal, or vertical and horizontal mul- FIRE
DAMPER
lions can be used, depending on the
opening size.
MULLION
TUBE
EXPANSION
CLEARANCE

RETAINING
ANGLE
DAMPER
CONDITIONS & RESTRICTIONS SLEEVE

DETAIL B
— Fabricated from galvanized steel with a nominal yield
strength of 42,000 psi.

— Intended for use in concrete block or poured walls only


with a minimum wall thickness of 7" and a maximum
wall thickness of 12".

— To permit proper embedding of anchors, hollow con- Reference the damper's installation instruc-
crete block walls are to be filled at the opening by tions regarding the approved method of attach-
minimum 3,500 psi concrete. ing the damper to the sleeve, attaching the
retaining angles to the sleeve, required expan-
— Steel mullions are not to be inside the ductwork. For sion clearances, sleeve gauge, etc.
ducted systems, each sub-divided opening must be
individually ducted.

7
1/4" MIN.
END CAPS 1-1/4" MAX.
(SEE DETAILS)
MADE UP OF
TWO WELDED
1-13/16 2 ZEE SECTIONS

LL
RA
VE
OPENING 3 PLUS 1/8" PER

"O
/4
SPAN FOOT OF OPENING

-1
WIDTH OR HEIGHT

X
MULLION TUBE
LENGTH = OPENING
- 1/8" PER FOOT
3-1/4
1/8" WELD
ALL AROUND

COUNTERSUNK HOLES
FOR 1/4" DIA. FLAT
HEAD MACHINE SCREWS
5-13/16 OR 1" LONG WELDS
SEE DETAIL C
DETAIL C
The end caps are attached by means of 1" long
DETAIL D
x 3/8" dia. steel expansion anchors embedded
Top, bottom or side end caps
into the opening with 1/4" dia. flat head machine
12 GA galvanized steel
screws, eight per end cap. If a steel lintel is
used, four 1" long welds per end cap (two per
leg) may be used.

X = WALL THICKNESS

3-1/4
1-13/16

LL
RA
VE
COUNTERSUNK HOLES
"O

FOR 1/4" DIA. FLAT 3" PLUS 1/8" PER


/4

HEAD MACHINE SCREWS FOOT OF SPAN WIDTH


-1
X

X - 1/4"
1/8" FULL LENGTH
WELD ALL AROUND

X/4 S
G
LE
E
ID
NS
"I

X/8
16

1-1/2 x 3 x 6-1/4 LG
1/
+

ANGLES
X

1/2" SEE DETAILS FOR END


CAP DETAILS, CAP
MUST SLIP FIT INTO
MULLION
DETAIL F
DETAIL E
END CAP INSERTED INTO MULLION
HORIZONTAL TO VERTICAL MULLION END CAP 12 GA. GALVANIZED STEEL

Attach the horizontal mullion end caps to the vertical


mullion tube by means of (12) 3/16" dia. blind rivets or by
All horizontal and vertical mullion tubes must 1
/8" full length weld.
be terminated with an end cap. These end caps
may not be fastened to the mullion tube and
must slide freely inside the mullion tube. Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com

8
INSTALLATION AND MAINTENANCE INSTRUCTIONS II-317CDLG-04.11
3 HR., STATIC OR DYNAMIC RATED, UL CLASSIFIED FIRE DAMPER
FOR USE IN FIRE BARRIERS WITH RATINGS OF 3 HOURS OR MORE

INSPECTION INSTALLATION

Inspect for shipping damage. The basic intent of a proper installation is to secure
Inspect for proper size and model. the fire damper in, not to, the opening in such a
Inspect installed damper for proper orientation, as stated manner as to prevent distortion and disruption of the
on damper label. damper operation by allowing the fire damper in
Inspect for obstructions which could interfere with free openings to expand and for the connecting duct to
operation and complete closure. separate in the event of the collapse of the hanging
Manually cycle the damper to verify proper operation. system. The fire damper must be positioned within
the masonry or block fire barrier. If the damper uses
an ETL (Electro-Thermal-Link) refer to the instruc-
tion packaged with the link.
DAMPER TO SLEEVE ATTACHMENT
TYPICAL WALL INSTALLATION
A sleeve shall be used unless the damper has a
housing of sufficient width to permit direct attach-
ment of perimeter mounting angles.
This damper can be supplied by the factory mounted
in a sleeve. If the sleeve is not factory supplied, it
must be attached on both sides of the damper by the
following method:
Secure damper to sleeve with 1" long welds spaced
6“ max. on centers and staggered upstream to
downstream. Each side shall have welds no more
than 23/4” from each corner.
Gaps at corners between the damper and its sleeve
must be small enough to prohibit the passage of an
1
/8" diameter rod through the entire depth of the
opening. A 1/4" diameter rod cannot pass through
the gap between two damper panels and its sleeve.
SLEEVE THICKNESS
* Sleeve shall be the same gauge or heavier as the
duct to which it is attached. Gauges shall conform to
SMACNA or ASHRAE duct standards. Damper
sleeve can be no thicker than 10 GA steel. On type
C dampers, the sleeve must be 18 GA or heavier.
EXPANSION CLEARANCE
The opening in the wall or floor for the fire damper
shall be sized so as to provide expansion clearance
between the sleeve and opening. Clearances do not
vary with walls constructed of different materials. A
minimum of 1/8" (3/16" for stainless steel) per foot of
HORIZONTAL DAMPER TO BE INSTALLED WITH
overall damper/sleeve width and height is required.
*
BLADE LOCK POINTS FACING DOWNWARD AND The maximum opening size shall not exceed 1/8" (3/16"
WITH ACCESS FROM ABOVE. for stainless steel) per foot plus 1", minimum total
clearance shall be at least 1/4" larger than the overall
assembly.

Commercial Damper / Louver Group


MOUNTING ANGLES DUCT CONNECTION
Secure mounting angles to the sleeve and not to the The installation of the damper and all duct connections
wall or floor. Mounting angles to frame the four sides to the damper sleeve shall conform to NFPA-90A and the
of the sleeve on both faces. Where local codes allow, SMACNA Fire, Smoke and Radiation Damper Installa-
corners of mounting angles can be welded for damp- tion Guide. All duct connections shall also conform to
ers 24" x 24" or smaller. When reverse mounting UL555. Connecting ducts shall not be continuous but
angles are used, the size of the opening must be shall terminate at the damper sleeve. Duct connections
increased to maintain the specified expansion clear- to the sleeve will be either of the breakaway or rigid types,
ance between the angle/fasteners and the opening. breakaway types are listed below. The following deter-
Angles shall be a minimum of 11/2 x 11/2 x 1/8". Fasten mines if the connections are to be rigid or breakaway.
angles to the sleeve using the 1/4" dia. bolts and nuts, For rigid type duct connections, sleeve shall be a mini-
or by welding with beads 1" in length. Fasteners or mum of 16 GA on dampers not exceeding 36" wide or 24"
weld beads shall be 6" maximum on centers. Each high or 24" diameter and 14 GA on larger units. Dampers
side shall be connected no more than 2 3/4" from each supplied with thinner sleeves will require a breakaway
corner. connection of the following type: Plain “S” slip, Double
“S” slip, Inside slip, Hemmed “S” slip, Standing “S” slip
ACCESS (bar reinforced, angle reinforced or alternate bar), Stand-
ing “S” slip shown below. All Connections not listed as
Suitable access must be provided for damper inspec-
breakaway shall be considered as rigid. Breakaway
tion and servicing. Where it is not possible to achieve
joints shall have no more than two No. 10 sheet metal
sufficient size access, it will be necessary to install a
screws on each side and on the bottom. The screws
removable section of duct.
shall penetrate both sides of the slip pocket. When a
breakaway joint is used along the top and bottom duct
CAULKING
connection, a flat drive slip no longer than 20 inches is
Caulking is allowed between the mounting angles and permitted on the two sides.
the damper sleeve, and between the mounting angles
and the floor or wall construction. Caulking is not MAINTENANCE
allowed between the damper sleeve and the wall or floor
Dampers shall be maintained in intervals as stated in
inside the opening.
NFPA-90A, Appendix B, unless local codes require
Caulk shall be one of the following:
more frequent inspections. Check the fuse link, check
Dow Corning RTV 732, General Electric IS 808 or
the stainless steel closure springs where furnished,
Novagard RTV 300.
cycle damper and check for free operation and complete
closure, clean with mild detergent or solvent, secure
damper open with fusible link.

PLAIN "S" SLIP DOUBLE "S" SLIP INSIDE SLIP JOINT HEMMED "S" SLIP

STANDING "S" SLIP STANDING "S" SLIP STANDING "S" SLIP STANDING "S" SLIP
(BAR REINFORCED) (ANGLE REINFORCED) (ALTERNATE BAR)

2
The factory supplied 22 GA collar to 18 GA
cap connection on type “C” dampers is a
“breakaway” connection under the following
conditions:
1. Round duct diameters are no larger than
36".
2. Oval duct sizes are no larger than
71"W x 30"H.
3. Duct gauges shall conform to the
SMACNA or ASHRAE duct standard.
4. Duct to be attached to the 22 GA damper
collar with minimum #8 S.M.S. minimum
of four screws per connection. For round
duct diameters greater than 24", a mini-
mum of five #10 S.M.S. are required per
connection.
Dampers outside of these restrictions must
use a 4" wide drawband connection as shown
in the SMACNA Fire, Smoke and Radiation
Damper Installation Guide.
5. A sleeve shall be provided, unless a
damper has a frame of sufficient width, to
permit direct attachment of perimeter
mounting angles on each side of a wall or
floor opening.

3
DAMPER SIZE LIMITATION

DAMPER VERT. OR MAX. W X H MAX. W X H MAX. W X H MAX. W X H


FRAME HORIZ. SINGLE ASSEMBLY SECTION OF MULLION
TYPE MOUNT TYPE SECTION (in.) (in.) ASSEMBLY DETAILS

Standard Horizontal Static 48 X 48 72 X 36 36 X 36 1


Standard Vertical Static 36 X 36 72 X 72 36 X 36 2
Nuclear Vertical Static 36 X 36 74 X 74 36 X 36 3
Nuclear (STN) Vertical Static 47 X 48 95 X 48 47 X 48 3
Standard, STN Vertical Static 47 X 48 93 X 48 47 X 48 2
Standard Vertical Dynamic 36 X 36 -- -- --
Standard Horizontal Dynamic 24 X 24 -- -- --

Nuclear Vertical Dynamic 36 x 36 -- -- --

Nuclear Horizontal Dynamic 24 X 24 -- -- --

(STN) = Stainless Steel Construction

NOTES:
1. In cases where the wall/floor opening is larger than additional structural supports of multiple section dampers
the maximum listed assembly size, an approved when required by elevated air pressure differential in the
mullion must separate the large opening into smaller closed position and in some cases seismic loading.
openings. 4. Unassembled multiple section assemblies are shipped
2. Reference label on damper for velocity and pressure without the mullions and are to be field fabricated per details
ratings of dynamically rated dampers. provided in these instructions.
3. Mullion details specified are based on the fire ratings
qualification tests. The user is responsible for DETAIL 2, 3
(MULLION FULL HEIGHT)

DETAIL 2, 3 DETAIL 2, 3
DETAIL 1, 2, 3
(TWO LENGTHS
OF MULLIONS)

2 PANELS WIDE 2 PANELS HIGH 2 PANELS WIDE


OR
2 PANELS HIGH

1/2" LONG BEADS


8" MAX. ON CENTERS 7/8" X 7 X 7/8" X 14 GA
(2) 1" X 6-7/8" X 1-7/8" X 14 GA
ON BOTH FACES ZEE OF SAME MATERIAL AS
CHANNELS CONTINUOUSLY WELDED
OR DAMPER
TOGETHER OF THE SAME MATERIAL
1/4" DIA. BOLTS AND NUTS AS THE DAMPER
8" MAX. ON-CENTERS ON
BOTH FACES

1" LONG WELD, 7" MAX.


14 GA STEEL MULLION ON CENTERS, 2-3/4" MAX.
DETAIL 2 FROM ENDS STAGGERED ON DETAIL 3
DETAIL 1 PLATE, 4-7/8" WIDE 1" LONG WELD, 7" MAX.
BY OPENING HEIGHT BOTH FACES. MULLION TO
MULLION AND MULLION TO ON CENTERS, 2-3/4" MAX.
SLEEVE WELDS ARE CONTINUOUS FROM ENDS STAGGERED ON
BOTH FACES. MULLION TO
Arrow United Industries MULLION AND MULLION TO
A Division of Mestek, Inc. SLEEVE WELDS ARE CONTINUOUS

314 Riverside Drive . Wyalusing, PA 18853


Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com

MEMBER OF AMCA
4
Dynamic Fire Dampers

D17A 1 1/2 hour rated no sleeve


D17XA 1 1/2 hour rated with sleeve
D17B 1 1/2 hour rated no sleeve 100% free area
D17XB 1 1/2 hour rated w/sleeve 100% free area
D17C 1 1/2 hour rated no sleeve 100% free area
D17XC 1 1/2 hour rated w/sleeve 100% free area
D37A 3 hour rated no sleeve
D37B 3 hour rated no sleeve 100% free area
D37C 3 hour rated no sleeve
MD17 1 1/2 hour rated no sleeve multi-blade
MD37 3 hour rated no sleeve multi-blade
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-D17A-04.11

FIRE/SEAL® UL-CLASSIFIED
MODEL D17A
1½-HR. DYNAMIC RATED Vertical and Horizontal Mount
FIRE DAMPER
Classified by Underwriters Laboratories as a 1½-hour fire protection
rated Fire Damper, FOR USE IN DYNAMIC SYSTEMS, in accordance
VERTICAL MOUNT with Standards UL-555 and NFPA-90A, for the protection of openings
in fire partitions having a fire resistance rating of less than 3 hours.
TOP BLADE RIVETED
TO FRAME
UNDERWRITERS LABORATORIES, INC.
CLASSIFIED

FIRE DAMPERS
FIRE RESISTANCE RATING 1½ HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX
FUSIBLE
BLADE LINK
LOCK
California State Fire Marshal
NOMINAL
DUCT
Listing No. 3225-1328:100
HEIGHT
LESS 1/4”
(WITHOUT STAINLESS STEEL INTEGRAL SELF-LOCKING
SLEEVE) NEGATOR CORNER JOINT
CLOSURE
SPRING

3/4” (SILL AND JAMB)

3”
4-7/8”

HORIZONTAL MOUNT
NOMINAL DUCT
WIDTH LESS 1/4”
(WITHOUT SLEEVE)
BLADE LOCK
*
STAINLESS STEEL NEGATOR
CLOSURE SPRING DIMENSIONAL DATA:

MINIMUM SIZE: 6”W x 6”H

* DAMPER TO BE INSTALLED WITH BLADE LOCK POINTS


FACING DOWNWARD AND WITH ACCESS FROM ABOVE MAXIMUM SIZE - VERTICAL (Model D19AV):
Single Panel: 36”W x 36”H
HORIZONTAL (D19AH):
STANDARD MATERIALS & CONSTRUCTION:
Single Panel: 24”W x 24”H
FRAME: One-piece rollformed 22-GA galvanized steel.
PROJECT:
BLADES: 22-GA galvanized steel curtain-type.
LOCATION:
FUSIBLE LINK: UL-listed 165ºF; replaceable
ARCHITECT:
(Optional 212ºF available (Vertical Mount Only) at no
ENGINEER:
additional charge)
CONTRACTOR:
CLOSURE SPRINGS: Heat-treated Type 301 stainless
PO NUMBER:
steel constant force coiled negator type. DATE:
Arrow United Industries
A Division of Mestek, Inc. Additional information
314 Riverside Drive . Wyalusing, PA 18853 on reverse side.
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com

MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED MODEL D17A


1½-HR. DYNAMIC RATED FIRE DAMPER

.15
FREE AREA [sq. ft.]
Duct Width (in.) .10
8 12 16 20 24 28 32 36 .09
STATIC .08
8 .2 .4 .6 .7 .9 1.0 1.2 1.4
PRESSURE .07
12 .4 .7 .9 1.2 1.5 1.8 2.0 2.3
DROP
Duct 16 .6 .9 1.3 1.7 2.0 2.4 2.8 3.1 [in. wg.] .06
Height 20 .7 1.2 1.7 2.1 2.6 3.1 3.5 4.0 .05
(in.) 24 .9 1.4 2.0 2.6 3.2 3.7 4.3 4.9
.04
28 1.0 1.7 2.4 3.0 3.7 4.4 5.0 5.7
32 1.2 2.0 2.7 3.5 4.3 5.1 5.8 6.6 .03
36 1.3 2.2 3.1 4.0 4.8 5.7 6.6 7.4

.02

FLOW [cfm] .01


FREE AREA VELOCITY [fpm] = 1000 2000
FREE AREA [sq. ft.]
FREE AREA VELOCITY [fpm]

AVAILABLE OPTIONS:

1. Factory-supplied sleeves (20-GA through 10-GA)


2. 212ºF fusible link (Vertical Mount Only).
3. Electro Thermal Link (ETL®).
4. SPDT “closed damper” position indicator switch.
5. “Pull Ring” for ease of reopening closed damper.
(Horizontal Models only)

NOTES:
1. Rated at 2000 fpm, 4 in. wg.
2. When a dynamic fire damper closes under airflow conditions,
due to inertia, a momentary negative pressure spike (vacuum)
can occur on the downstream side of the closed damper. This
situation should be taken into consideration by the Engineer/
System Designer.

Arrow United Industries


A Division of Mestek, Inc.
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED 314 Riverside Drive . Wyalusing, PA 18853
INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITH- Ph: (570) 746-1888 Fax: (570) 746-9286
OUT NOTICE. www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-D17XA-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL D17X


1½-HR. DYNAMIC RATED FIRE DAMPER “A” STYLE
WITH INTEGRAL SLEEVE FRAME Vertical & Horizontal Mount

NO ADDITIONAL SLEEVE REQUIRED, Classified by Underwriters Laboratories as a 1½ hour fire protection


PROVIDED DUCT THICKNESS IS 20-GA. OR LESS, rated Fire Damper, FOR USE IN DYNAMIC SYSTEMS, in accordance with
AND U.L.-APPROVED BREAKAWAY DUCT-TO-SLEEVE Standards UL-555 and NFPA-90A, for the protection of openings in fire
CONNECTION JOINTS ARE USED, PER UL-555. partitions having a fire resistance rating of less than 3 hours.

VERTICAL MOUNT UNDERWRITERS LABORATORIES INC.

Arrow United
CLASSIFIED

Industries
FIRE DAMPERS
FIRE RESISTANCE RATING 1-1/2 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX
FUSIBLE
LINK California State Fire Marshal
Listing No. 3225-1328:100
DAMPERCENTERED
WITHIN SLEEVE FRAME
NOMINAL INTEGRAL SELF-LOCKING
DUCT INTEGRAL CORNER JOINT
HEIGHT SLEEVE FRAME
LESS ¼"

¾" SILL & JAMBS

"L" (12" LENGTH IS STANDARD)


LONGER LENGTHS OF 14" AND 16" ARE AVAILABLE NOMINAL DUCT "L"
WIDTH LESS ¼"
HORIZONTAL MOUNT

DIMENSIONAL DATA:

MINIMUM SIZE: 6"W x 6"H.

BLADE LOCK* MAXIMUM SIZE: VERTICAL


Single Panel: 36" x 36"
Multiple Panel: Not Available
HORIZONTAL
Single Panel: 24" x 24"
STAINLESS STEEL NEGATOR Multiple Panel: Not available
CLOSURE SPRING
NOTE: Dampers should be ordered by nominal
duct size.
*Dampers are to be installed with blade lock points
facing DOWNWARD and with access from above. PROJECT:
STANDARD MATERIALS & CONSTRUCTION: LOCATION:
SLEEVE FRAME: One-piece rollformed 20-GA galvanized steel. ARCHITECT:
BLADES: 22-GA galvanized steel curtain-type.
FUSIBLE LINK: UL-Listed 165°F; replaceable. (Optional 212°F available ENGINEER:
(Vertical Mount Only) at no additional charge). CONTRACTOR:
CLOSURE SPRINGS: Heat-treated Type 301 stainless steel constant PO NUMBER:
force coiled negator type. DATE:
Arrow United Industries
A Division of Mestek, Inc.
Additional information on
314 Riverside Drive . Wyalusing, PA 18853 reverse side.
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED
MODEL D17X
1 1/2-HR. DYNAMIC RATED FIRE DAMPER
"A" STYLE
WITH INTEGRAL SLEEVE FRAME

FREE AREA [sq. ft.]


Duct Width (in.)

8 12 16 20 24 28 32 36
8 0.2 0.4 0.6 0.7 0.9 1.0 1.2 1.4
12 0.4 0.7 0.9 1.2 1.5 1.8 2.0 2.3
16 0.6 0.9 1.3 1.7 2.0 2.4 2.8 3.1
Duct
Height 20 0.7 1.2 1.7 2.1 2.6 3.1 3.5 4.0
(in.) 24 0.9 1.4 2.0 2.6 3.2 3.7 4.3 4.9
28 1.0 1.7 2.4 3.0 3.7 4.4 5.0 5.7
32 1.2 2.0 2.7 3.5 4.3 5.1 5.8 6.6
36 1.3 2.2 3.1 4.0 4.8 5.7 6.6 7.4

AVAILABLE OPTIONS:

1. Sleeve frame length ("L" dimension) of 14" or 16". FLOW [cfm]


2. 212°F fusible link (Vertical Mount Only). FACE AREA VELOCITY [fpm] =
FACE AREA [sq. ft.]
3. Electro Thermal Link [ETL®].
4. SPDT "closed damper" position indicator switch.
5. Transitions & Collars for round or oval ductwork for Low
Pressure HVAC Systems - See Submittal Data Sheet ASD-T.
6. Transitions & Collars and Sealant/Caulking for rectangular,
round, or oval ductwork for High Pressure HVAC Systems ("C" .15
Style Damper) - See Submittal Data Sheet SD-D17XC.
7. "Pull Ring" for ease of reopening closed damper.
.10
(Horizontal Models Only.)
.09
.08
.07
STATIC .06
PRESSURE
DROP .05
[in. wg.]
NOTES: .04

1. Rated at 2000 fpm, 4 in. wg.


.03
2. When a dynamic fire damper closes under airflow condi-
tions, due to inertia, a momentary negative pressure spike
(vacuum) can occur on the downstream side of the closed
damper. This situation should be taken into consideration .02

by the Engineer/System Designer.


.01
6 7 8 9 1000 2000

FACE AREA VELOCITY


[fpm]

MEMBER OF AMCA
Arrow United Industries
A Division of Mestek, Inc.
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW 314 Riverside Drive . Wyalusing, PA 18853
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE Ph: (570) 746-1888 Fax: (570) 746-9286
CHANGES WITHOUT NOTICE. www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-D17B-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL D17B


11/2-HR. DYNAMIC RATED FIRE Vertical & Horizontal Mount
DAMPER Classified by Underwriters Laboratories as a 1 / -hour fire protection
rated Fire Damper, FOR USE IN DYNAMIC SYSTEMS, in accordance
1
2

with Standards UL-555 and NFPA-90A, for the protection of openings


in fire partitions having a fire resistance rating of less than 3 hours.
VERTICAL MOUNT
TOP BLADE RIVETED
UNDERWRITERS LABORATORIES INC.
TO FRAME
CLASSIFIED
FIRE DAMPERS
SEE HEAD
BPAN FIRE RESISTANCE RATING 11/2 HR.
SIZING CHART
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX
1"

California State Fire Marshal


FUSIBLE
BLADE LINK
Listing No. 3225-1328:100
NOMINAL FRAME LOCK
HEIGHT LESS 1/4"
(WITHOUT SLEEVE) INTEGRAL SELF-LOCKING
CORNER JOINT
STAINLESS STEEL
NEGATOR
NOMINAL CLOSURE SPRING
DUCT HEIGHT
LESS 1/4"

3/4" (SILL AND JAMBS)

3"
4-7/8"

NOMINAL DUCT
WIDTH LESS 1/4”
HORIZONTAL MOUNT (WITHOUT SLEEVE)

DIMENSIONAL DATA:
BLADE LOCK
*
STAINLESS STEEL NEGATOR MINIMUM SIZE: 6" W x 4" H (Duct), 6"W X 6"H (Frame).
CLOSURE SPRING
MAXIMUM SIZE : VERTICAL (Model D19BV):
Single Panel: 36"W x 32"H (Duct), 36"W x 36"H (Frame).
HORIZONTAL (Model D19BH):
Single Panel: 24"W x 21"H (Duct), 24"W x 24"H (Frame).

* DAMPER TO BE INSTALLED WITH BLADE LOCK POINTS


FACING DOWNWARD AND WITH ACCESS FROM ABOVE

STANDARD MATERIALS & CONSTRUCTION:


PROJECT:
FRAME: One-piece rollformed 22-GA galvanized steel.
LOCATION:
BLADES: 22-GA galvanized steel curtain-type.
FUSIBLE LINK: UL-listed 165OF; replaceable. (Optional ARCHITECT:
212OF available (Vertical Mount only) at no ENGINEER:
additional charge.) CONTRACTOR:
CLOSURE SPRINGS: Heat-treated Type 301 stainless steel PO NUMBER:
constant force coiled negator type. DATE:

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853 Additional information
Ph: (570) 746-1888 Fax: (570) 746-9286 on reverse side.
www.arrowunited.com
MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED MODEL D17B


11/2-HR. DYNAMIC RATED FIRE
DAMPER
.15
HEAD SIZING CHART
IF NOMINAL DUCT INCHES TO .10
HEIGHT IS: ADD FOR HEAD: .09
STATIC .08
3" THRU 18" 2" PRESSURE .07
DROP
19" THRU 28" 3" [in. wg.] .06

4" .05
29" THRU 32"
.04

.03

See DIMENSIONAL DATA on front side. .02

.01
1000 2000
FREE AREA VELOCITY [fpm]
AVAILABLE OPTIONS:
1. Factory-supplied sleeves (20-GA through 10-GA).
2. 212OF fusible link (Vertical Mount Only).
3. Electro Thermal Link [ETL®]. FLOW [cfm]
4. SPDT "closed damper" position indicator switch. FREE AREA VELOCITY [fpm] =
FREE AREA [sq. ft.]
5. "Pull-Ring" for ease of reopening closed damper.
(Horizontal Models Only)

FREE AREA [sq. ft.]


Duct Width (in.)

8 12 16 20 24 28 32 36
8 .4 .6 .8 1.0 1.2 1.4 1.6 1.8
12 .5 .9 1.2 1.5 1.8 2.1 2.4 2.7

Duct 16 .7 1.2 1.6 2.0 2.4 2.8 3.3 3.7


Height 20 .9 1.4 2.0 2.5 3.0 3.6 4.1 4.7
(in.) 24 1.1 1.7 2.4 3.0 3.7 4.3 5.0 5.6
28 1.2 2.0 2.8 3.5 4.3 5.0 5.8 6.5
32 1.5 2.3 3.2 4.0 4.9 5.8 6.7 7.5

NOTES:
1. Rated at 2000 fpm, 4 in. wg.
2. When a dynamic fire damper closes under airflow conditions, due to inertia, a momentary negative pressure
spike (vacuum) can occur on the downstream side of the closed damper. This situation should be taken into
consideration by the Engineer/System Designer.

Arrow United Industries


A Division of Mestek, Inc.
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW 314 Riverside Drive . Wyalusing, PA 18853
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE Ph: (570) 746-1888 Fax: (570) 746-9286
CHANGES WITHOUT NOTICE. www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-D17XB-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL D17X


11/2-HR. DYNAMIC RATED FIRE DAMPER “B” STYLE
Vertical & Horizontal Mount
WITH INTEGRAL SLEEVE FRAME

NO ADDITIONAL SLEEVE REQUIRED , PRO- Classified by Underwriters Laboratories as a 11/2-hour fire


protection rated Fire Damper, FOR USE IN DYNAMIC SYS-
VIDED DUCT THICKNESS IS 20 GA. OR LESS, AND TEMS, in accordance with Standards UL-555 and NFPA-90A,
U.L.-APPROVED BREAKAWAY DUCT-TO-SLEEVE for the protection of openings in fire partitions having a fire
CONNECTION JOINTS ARE USED, PER UL-555. resistance rating of less than 3 hours.

VERTICAL MOUNT Top Blade Riveted to Frame

See Head
1-3/4"
UNDERWRITERS LABORATORIES INC.
Sizing Chart

Arrow United
CLASSIFIED

Industries
B-Pan FIRE DAMPERS
Fusible
Link FIRE RESISTANCE RATING 11/2 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX
Damper Centered
Within Sleeve Frame
Nominal Sleeve Nominal California State Fire Marshal
Frame Height Duct
Less 1/4" Height
Listing No. 3225-1328:100
Less 1/4"

Integral
Integral Self-Locking
Sleeve Frame Joint
3/4" (Sill and Jambs)

"L" (12" Length is Standard)


Longer Lengths of 14", and 16" Are Available.

HORIZONTAL MOUNT

Blade Lock* Nominal "L"


Duct Width
Less ¼"

Stainless Steel
Negator Closure DIMENSIONAL DATA:
Spring

MINIMUM SIZE: 6"W X 4"H (Duct), 6"W x 6"H (Sleeve Frame)


*Damper is to be installed with blade lock points
facing DOWNWARD and with access from above.
MAXIMUM SIZE - VERTICAL:
Single Panel: 36"W x 32"H (Duct), 36"W x 36"H (Sleeve Frame)
STANDARD MATERIALS & CONSTRUCTION: Multiple Panel:Not Available
MAXIMUM SIZE - HORIZONTAL:
SLEEVE FRAME: One-piece rollformed 20-GA galvanized Single Panel: 24"W x 21"H (Duct), 24"W x 24"H (Sleeve Frame)
steel. Multiple Panel: Not Available
BLADES: 22-GA galvanized steel curtain-type.
FUSIBLE LINK: UL-listed 165OF; replaceable. (Optional PROJECT:
212OF (Vertical Mount Only) available at no additional
charge.) LOCATION:
CLOSURE SPRINGS: Heat-treated Type 301 stainless steel ARCHITECT:
constant force coiled negator type. ENGINEER:
Arrow United Industries CONTRACTOR:
A Division of Mestek, Inc. PO NUMBER:
314 Riverside Drive . Wyalusing, PA 18853 DATE:
Ph: (570) 746-1888 Fax: (570) 746-9286 Additional information
www.arrowunited.com MEMBER OF AMCA on reverse side.
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED MODEL D17X


11/2-HR. DYNAMIC RATED FIRE DAMPER “B” STYLE
WITH INTEGRAL SLEEVE FRAME

HEAD SIZING CHART


IF NOMINAL DUCT INCHES TO
HEIGHT IS: ADD FOR HEAD:
3" THRU 18" 2"
19" THRU 28" 3"
29" THRU 32" 4"
See DIMENSIONAL DATA on front side.
AVAILABLE OPTIONS:
1. Sleeve frame length (“L” dimension) of 14" or 16"
2. 212OF fusible link (Vertical Mount Only).
3. Electro Thermal Link [ETL®].
4. SPDT "closed damper" position indicator switch.
5. "Pull Ring" for ease of reopening closed damper.
(Horizontal Models Only.)

NOTES:
1. Rated at 2000 fpm, 4 in. wg.
2. When a dynamic fire damper closes under airflow conditions, due to inertia, a momentary negative pressure spike
(vacuum) can occur on the downstream side of the closed damper. This situation should be taken into consideration
by the Engineer/System Designer.

FLOW [cfm]
FREE AREA VELOCITY [fpm] =
FREE AREA [sq. ft.] .15

.10
.09
FREE AREA [sq. ft.] .08
STATIC PRESSURE DROP

Duct Width (in.) .07


8 12 16 20 24 28 32 36 .06
.05
8 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
.04
12 0.5 0.9 1.2 1.5 1.8 2.1 2.4 2.7
Duct Height (in.)

16 0.7 1.2 1.6 2.0 2.4 2.8 3.3 3.7 .03


20 0.9 1.4 2.0 2.5 3.0 3.6 4.1 4.7
24 1.1 1.7 2.4 3.0 3.7 4.3 5.0 5.6 .02
28 1.2 2.0 2.8 3.5 4.3 5.0 5.8 6.5
32 1.5 2.3 3.2 4.0 4.9 5.8 6.7 7.5
.01
1000 2000
FREE AREA VELOCITY [fpm]

Arrow United Industries


A Division of Mestek, Inc.
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW
314 Riverside Drive . Wyalusing, PA 18853
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE Ph: (570) 746-1888 Fax: (570) 746-9286
CHANGES WITHOUT NOTICE. www.arrowunited.com
ASD-D17C-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED MODEL D17C


Vertical & Horizontal
11/2-HR. DYNAMIC RATED FIRE Mount
DAMPER
1
Classified by Underwriters Laboratories as a 1 / -hour fire protection 2
rated Fire Damper, FOR USE IN DYNAMIC SYSTEMS, in accordance
with Standards UL-555 and NFPA-90A, for the protection of openings
RECTANGULAR, ROUND, & OVAL in fire partitions having a fire resistance rating of less than 3 hours.
BREAKAWAY
HOUSING UNDERWRITER’S LABORATORIES, INC.
CONNECTION

Arrow Unite
CLASSIFIED

Industries
VERTICAL MOUNT
FIRE DAMPERS
FIRE RESISTANCE RATING 1-1/2 HR.
COLLAR SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX
1/2" (FOR CONNECTION
TO DUCT)
California State Fire Marshal
Listing No. 3225-1328:100
NOMINAL
DUCT NOMINAL
HEIGHT DUCT
LESS 1/4" HEIGHT
LESS 1/4" IMPORTANT
TOTAL FOR ROUND DUCT DIAMETERS UP TO 31", FOR OVAL
TRANSITION DUCT SIZES UP TO 34"W X 31"H (VERTICAL
HEIGHT
(EQUALS
MOUNT),AND HORIZONTAL MOUNT 20" ROUND AND
NOMINAL 22"W X 20"H OVAL DUCT SIZES , ARROWI'S 22-GA
DUCT HEIGHT DUCT CONNECTION COLLAR (CRIMPED TO THE
PLUS 0.93") DAMPER HOUSING) CONSTITUTES A U.L.
A P P R O V E D D U C T - T O - S L E E V E
1" TYP. "BREAKAWAY"CONNECTION, THUS ALLOWING A
1/2" THREE SIDES RIGID CONNECTION JOINT TO BE UTILIZED BE-
TWEEN THE DAMPER'S DUCT CONNECTION COL-
"L"
(5" IS STD.)
LAR AND THE ROUND OR OVAL DUCTWORK.
LONGER LENGTHS ARE AVAILABLE
WITH A FACTORY-SUPPLIED SLEEVE

HORIZONTAL MOUNT

DIMENSIONAL DATA:
BLADE MINIMUM SIZE: 4"W x 4"H (Duct), 6"W x 7"H (Frame).
LOCK
MAXIMUM SIZE - VERTICAL (Model D19CV):
34"W x 31"H (Duct), 36"W x 36"H (Frame).
HORIZONTAL (Model D19CH):
STAINLESSSTEEL
NEGATORCLOSURESPRING
22"W x 20"H (Duct), 24"W x 24"H (Frame).

DAMPER TO BE INSTALLED WITH THE BLADE LOCK POINTS


FACING DOWNWARD AND WITH ACCESS FROM ABOVE
NOTE: Dampers should be ordered by nominal duct
size. Fractional duct dimension (1/8" min.) will require
the same fractional addition to the corresponding damper
STANDARD MATERIALS & CONSTRUCTION: housing dimension.

FRAME: One-piece rollformed 22-GA galvanized steel.


BLADES: 22-GA galvanized steel curtain-type. PROJECT:
HOUSING: 20-GA galvanized steel (Std.). LOCATION:
DUCT CONNECTION COLLAR: 22-GA galvanized
ARCHITECT:
steel.
FUSIBLE LINK: UL-listed 165OF; replaceable. ENGINEER:
(Optional 212OF (Vertical Mount Only) available at no CONTRACTOR:
additional charge.) PO NUMBER:
CLOSURE SPRINGS: Heat-treated Type 301 stainless DATE:
steel constant force coiled negator type.
Arrow United Industries Additional information
A Division of Mestek, Inc. on reverse side.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED
11/2-HR. DYNAMIC RATED FIRE DAMPER MODEL D17C
Vertical & Horizontal Mount

NOTES:
1. When a dynamic fire damper closes under airflow conditions, due to inertia,
a momentary negative pressure spike (vacuum) can occur on the down-
stream side of the closed damper. This situation should be taken into
consideration by the Engineer/System Designer.
2. Rated at 2000 fpm, 4 in. w.g.
With 100% Free Area, Pressure Drop is determined by
FACE Area Velocity (in lieu of Free Area Velocity).

DAMPER SIZING CHART


FLOW [cfm]
Width: Add 2" to nominal duct width. FACE AREA VELOCITY [fpm] =
FACE AREA [sq. ft.]
Height: IF NOMINAL DUCT INCHES TO
ADD FOR TOTAL
HEIGHT IS: DAMPER HEIGHT:

6" THRU 18" 3"


.2
19" THRU 28" 4"
29" THRU 31" 5"
.10
See DIMENSIONAL DATA on front side. STATIC .09
PRESSURE .08
DROP
[in. wg.] .07
.06
.05

.04

AVAILABLE OPTIONS: .03

1. 18-GA through 10-GA housing.


2. Housing Length ("L" dimension) of 6" through 24". .02

3. 212OF fusible link (Vertical Mount Only)


4. Electro Thermal Link [ETL®].
5. SPDT "closed damper" position indicator switch. .011000 2000
6. "Pull-Ring" for ease of reopening closed damper. FACE AREA VELOCITY [fpm]
(Horizontal Models Only.)
Arrow United Industries
A Division of Mestek, Inc.
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW 314 Riverside Drive . Wyalusing, PA 18853
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE Ph: (570) 746-1888 Fax: (570) 746-9286
CHANGES WITHOUT NOTICE. www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-D17XC-04.11

MODEL D17X
FIRE/SEAL® UL-CLASSIFIED “C” STYLE
1½-HR. DYNAMIC RATED FIRE DAMPER Vertical & Horizontal
WITH INTEGRAL SLEEVE FRAME RECTANGULAR, ROUND & OVAL

DESIGNED FOR HIGH PRESSURE HVAC SYSTEMS, AND Classified by Underwriters Laboratories as a 11/2-hour fire
PROVIDES 100% FREE AREA. PRESSURE TESTED PER AMCA STAN- protection rated Fire Damper, FOR USE IN DYNAMIC SYS-
DARD 500 TO 6 in. wg. LEAKAGE PERFORMANCE OF TRANSITIONED TEMS, in accordance with Standards UL-555 and NFPA-90A,
INTEGRAL SLEEVE FRAME WITH TAPE & SEALANT CAULKING IS EQUAL for the protection of openings in fire partitions having a fire
TO THAT OF A WELDED SEAM “C”-TYPE HOUSING. resistance rating of less than 3 hours.

VERTICAL MOUNT
Top Blade Riveted To Frame
UNDERWRITERS LABORATORIES INC.
CLASSIFIED
Total Transition FIRE DAMPERS
Sealant
Height (Equals Caulking Typ. Fusible FIRE RESISTANCE RATING 11/2 HR.
Nominal Damper at Transition- Link 2"
Frame Height Nominal To-Sleeve (Typ.) SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX
Frame Joint
Less 0.07") Duct Transition
on Interior
Height California State Fire Marshal
See Damper Less ¼"
UL-APPROVED BREAKAWAY
Sizing Chart CONNECTION Listing No. 3225-1328:100
Collar

1" Typ.
(For Connection to Duct) IMPORTANT
¾" Sill & Jambs Three Sides
Arrow's 22-GA Duct Con-
nection Collar (crimped to
"L" (12" Length is Standard)
Longer Lengths of 14" and 16" are available the damper transition) con-
stitutes a U.L. approved
HORIZONTAL MOUNT
duct-to-sleeve “Breakaway”
connection, thus allowing a
rigid connection joint to be
utilized between the
Blade Lock*
damper's duct connection
collar and the round or oval
Stainless Steel
ductwork.
Negator Closure Spring DIMENSIONAL DATA:

MINIMUM SIZE: 4" W x 4" H (Duct), 6"W X 7"H (Sleeve Frame).


*Damper is to be installed with blade lock points facing
DOWNWARD and with access from above. MAXIMUM SIZE:
VERTICAL:
STANDARD MATERIALS & CONSTRUCTION: Single Panel: 34"W x 31"H (Duct), 36"W x 36"H (Sleeve Frame).
SLEEVE FRAME: One-piece rollformed 20-GA Multiple Panel: Not Available.
galvanized steel. HORIZONTAL:
BLADES: 22-GA galvanized steel curtain-type. Single Panel: 22" W x 20" H (Duct), 24"W x 24"H (Sleeve Frame).
TRANSITIONS [“CAPS”]: 20-GA galvanized steel, riv- Multiple Panel: Not Available.
eted to sleeve frame. NOTE: Dampers should be ordered by nominal duct size.
DUCT CONNECTION COLLARS: 22-GA galvanized steel,
crimped to transitions.
PROJECT:
SEALANT CAULKING: UL-listed high-temperature type.
TAPE: UL-listed high-temperature pressure sensitive foil LOCATION:
type. ARCHITECT:
FUSIBLE LINK: UL-listed 165OF; replaceable. (Optional
ENGINEER:
212OF (Vertical Mount Only) available at no extra charge.)
CLOSURE SPRINGS: Heat-treated Type 301 stainless CONTRACTOR:
steel constant force coiled negator type. PO NUMBER:
DATE:
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 Additional information
www.arrowunited.com MEMBER OF AMCA on reverse side.
ARROW UNITED INDUSTRIES SUBMITTAL DATA
FIRE/SEAL® UL-CLASSIFIED MODEL D17X
11/2-HR. DYNAMIC RATED FIRE DAMPER “C” STYLE
WITH INTEGRAL SLEEVE FRAME

NOTES: With 100% Free Area, Pressure Drop is determined by


1. Rated at 2000 fpm, 4 in. wg. FACE Area Velocity (in lieu of Free Area Velocity).
2. When a dynamic fire damper closes under airflow FLOW [cfm}
conditions, due to inertia, a momentary negative pres- FREE AREA VELOCITY [fpm] =
FREE AREA [sq. ft.]
sure spike (vacuum) can occur on the downstream side
of the closed damper. This situation should be taken
into consideration by the Engineer/System Designer.

.04
DAMPER SIZING CHART
Width: Add 2" to Nominal Duct Width
.03
STATIC PRESSURE DROP

Height: HEAD SIZING CHART


IF NOMINAL DUCT INCHES TO
HEIGHT IS: ADD FOR HEAD:
[in. wg.]

.02
6" THRU 18" 3"
19" THRU 28" 4"
29" THRU 31" 5"
See DIMENSIONAL DATA on front side.

AVAILABLE OPTIONS: .01


1000 2000
1. Sleeve frame length (“L” dimension) of 14" or 16".
FACE AREA VELOCITY [fpm]
2. 212OF fusible link (Vertical Mount Only).
3. Electro Thermal Link [ETL®].
4. SPDT "closed damper" position indicator switch.
5. "Pull Ring" for ease of reopening closed damper.
(Horizontal Models Only.) Arrow United Industries
A Division of Mestek, Inc.
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW 314 Riverside Drive . Wyalusing, PA 18853
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE Ph: (570) 746-1888 Fax: (570) 746-9286
CHANGES WITHOUT NOTICE. www.arrowunited.com
ASD-D37A-04.11
ARROW UNITED INDUSTRIES UBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED MODEL D37A


3-HR. DYNAMIC RATED Vertical & Horizontal

FIRE DAMPER
Classified by Underwriters Laboratories as a 3-hour fire protection
rated Fire Damper, FOR USE IN DYNAMIC SYSTEMS, in accordance
VERTICAL MOUNT with Standards UL-555 and NFPA-90A, for the protection of openings
in fire partitions having a fire resistance rating of 3 hours or more.
TOP BLADE RIVETED
TO FRAME
UNDERWRITERS LABORATORIES
INC.CLASSIFIED
FIRE DAMPERS
FIRE RESISTANCE RATING 3 HR.
SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX

NOMINAL
FUSIBLE California State Fire Marshal
BLADE LINK
DUCT LOCK Listing No. 3225-1328:101
HEIGHT
LESS ¼” INTEGRAL SELF-LOCKING
(WITHOUT CORNER JOINT
STAINLESS STEEL
SLEEVE)
NEGATOR
CLOSURE
SPRING

1½" HIGH GALV.


STEEL SILL
ANGLE (VERTICAL
UNITS ONLY)

3/4” (SILL AND JAMB)

3”
4-7/8”

NOMINAL DUCT
HORIZONTAL MOUNT WIDTH LESS 1/4"
(WITHOUT SLEEVE)

BLADE LOCK
*
STAINLESS STEEL NEGATOR DIMENSIONAL DATA:
CLOSURE SPRING
MINIMUM SIZE: 6" W x 6" H.
MAXIMUM SIZE - VERTICAL
Single Panel: 36"W x 36"H.
* DAMPER TO BE INSTALLED WITH BLADE LOCK POINTS
FACING DOWNWARD AND WITH ACCESS FROM ABOVE HORIZONTAL
Single Panel: 24"W x 24"H
STANDARD MATERIALS & CONSTRUCTION:
FRAME: One-piece rollformed 22-GA galvanized steel.
BLADES: 22-GA galvanized steel curtain-type. PROJECT:
FUSIBLE LINK: UL-listed 165OF; replaceable.
(Optional 212OF (Vertical Mount Only) LOCATION:
available at no additional charge.) ARCHITECT:
CLOSURE SPRINGS: Heat-treated Type 301 stainless ENGINEER:
steel constant force coiled negator type. CONTRACTOR:
Arrow United Industries PO NUMBER:
A Division of Mestek, Inc.
DATE:
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com Additional information
on reverse side.
MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED
3-HR. DYNAMIC RATED MODEL D37A
FIRE DAMPER

AVAILABLE OPTIONS:
1. Factory-supplied sleeves (20-GA through 10-GA).
2. 212OF fusible link (Vertical Mount Only).
3. Electro Thermal Link [ETL®].
4. SPDT “closed damper” position indicator switch.
5. "Pull Ring" for ease of reopening closed damper.
(Horizontal Models Only.)

NOTES:
1. Rated at 2000 fpm, 4 in. wg.
2. When a dynamic fire damper closes under airflow
conditions, due to inertia, a momentary negative
pressure spike (vacuum) can occur on the down-
stream side of the closed damper. This situation
should be taken into consideration by the Engineer/
System Designer.

FREE AREA [sq. ft.]


Duct Width (in.)

8 12 16 20 24 28 32 36
8 0.2 0.3 0.5 0.6 0.7 0.8 1.0 1.2
12 0.4 0.6 0.8 1.0 1.2 1.5 1.7 2.0
FLOW [cfm]
16 0.5 0.8 1.0 1.4 1.7 2.0 2.3 2.7 FREE AREA VELOCITY [fpm] =
Duct Height

FREE AREA [sq. ft.]


20 0.7 1.0 1.4 1.9 2.1 2.6 3.0 3.5
(in.)

24 0.8 1.1 1.7 2.2 2.8 3.1 3.6 4.2


28 1.0 1.4 2.0 2.6 3.2 4.0 4.4 5.0
32 1.1 1.7 2.2 3.0 4.0 4.7 5.1 5.7
36 1.2 2.0 2.6 3.5 4.5 5.2 6.0 7.1
.15

STATIC .10
PRESSURE .09
DROP .08
.07
.06
.05

.04

.03

.02

.01
Arrow United Industries 6 7 8 9 1000 2000
A Division of Mestek, Inc. FREE AREA VELOCITY
314 Riverside Drive . Wyalusing, PA 18853 [fpm]
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE
MEMBER OF AMCA CHANGES WITHOUT NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-D37B-04.11

FIRE/SEAL® UL-CLASSIFIED MODEL D37B


Vertical & Horizontal Mount
3-HR. DYNAMIC RATED FIRE
DAMPER Classified by Underwriters Laboratories as a 3-hour fire protection
rated Fire Damper, FOR USE IN DYNAMIC SYSTEMS, in accordance
with Standards UL-555 and NFPA-90A, for the protection of openings
VERTICAL MOUNT
in fire partitions having a fire resistance rating of 3 hours or more.
TOP BLADE RIVETED
TO FRAME UNDERWRITERS LABORATORIES INC.
CLASSIFIED
SEE HEAD FIRE DAMPERS
BPAN
SIZING CHART
FIRE RESISTANCE RATING 3 HR.
1" SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX

FUSIBLE
California State Fire Marshal
BLADE
LINK
Listing No. 3225-1328:101
NOMINAL FRAME LOCK
HEIGHT LESS 1/4" INTEGRAL SELF-LOCKING
(WITHOUT SLEEVE) CORNER JOINT

STAINLESS STEEL
NEGATOR
NOMINAL CLOSURE SPRING
DUCT HEIGHT
LESS 1/4" 1-1/2" x 1/2" x 16 GA.
GALV. STEEL SILL ANGLE
(ONE SIDE ONLY-
VERTICAL UNITS ONLY)

3/4" (SILL AND JAMBS)

3"
NOMINAL DUCT
4-7/8" WIDTH LESS 1/4”
(WITHOUT SLEEVE)

HORIZONTAL MOUNT DIMENSIONAL DATA:


MINIMUM SIZE: 6" W x 4" H (Duct), 6"W X 6"H (Frame).
MAXIMUM SIZE - VERTICAL:
Single Panel: 36"W x 32"H(Duct), 36"W x 36"H(Frame).
BLADE LOCK
*
STAINLESS STEEL NEGATOR HORIZONTAL:
CLOSURE SPRING
Single Panel: 24"W x 21"H(Duct), 24"W x 24"H(Frame).

NOTES:
1. Rated at 2000 fpm, 4 in. wg.
* DAMPER TO BE INSTALLED WITH BLADE LOCK POINTS
FACING DOWNWARD AND WITH ACCESS FROM ABOVE
2. When a dynamic fire damper closes under airflow conditions, due
to inertia, a momentary negative pressure spike (vacuum) can
occur on the downstream side of the closed dampers. This
STANDARD MATERIALS & CONSTRUCTION: situation should be taken into consideration by the Engineer/
System Designer.
FRAME: One-piece rollformed 22-GA galvanized
steel.
BLADES: 22-GA galvanized steel curtain-type. PROJECT:
FUSIBLE LINK: UL-listed 165OF; replaceable. LOCATION:
(Optional 212OF available at no additional charge.) ARCHITECT:
CLOSURE SPRINGS: Heat-treated Type 301 ENGINEER:
stainless steel constant force coiled negator type. CONTRACTOR:
PO NUMBER:
Arrow United Industries
DATE:
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 Additional information
www.arrowunited.com on reverse side.

MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

FIRE/SEAL® UL-CLASSIFIED 3-HR. MODEL D37B


DYNAMIC RATED FIRE DAMPER
AVAILABLE OPTIONS:
1. Factory-supplied sleeves (20-GA through 10-GA).
2. 212OF fusible link (Vertical Mount Only).
3. Electro Thermal Link [ETL®].
4. SPDT "closed damper" position indicator switch.
5. "Pull Ring" for ease of reopening closed damper.
(Horizontal Models Only.)

HEAD SIZING CHART (See DIMENSIONAL DATA on front side).


NOMINAL INCHES TO
DUCT HEIGHT ADD FOR HEAD:
SINGLE PANEL
3" thru 18" 2"
19" thru 28" 3"
29" thru 32" 4"

FLOW [cfm]
FREE AREA VELOCITY [fpm] =
FREE AREA [sq. ft.]

FREE AREA [sq. ft.]


Duct Width (in.)
8 12 16 20 24 28 32 36
8 0.27 0.44 0.62 0.79 0.97 1.1 1.3 1.5
12 0.44 0.73 1.0 1.3 1.6 1.9 2.1 2.4
16 0.62 1.1 1.4 1.8 2.2 2.6 3.0 3.4
Duct .10
20 0.79 1.3 1.8 2.3 2.8 3.3 3.8 4.3
Height .09
(in.) 24 0.97 1.6 2.2 2.8 3.4 4.1 4.7 5.3 .08
28 1.1 1.9 2.6 3.3 4.1 4.8 5.5 6.2 .07
.06
32 1.3 2.1 3.0 3.8 4.7 5.5 6.3 7.2 STATIC
.05
PRESSURE
DROP .04
[in. wg.]
.03

.02

.01
1000 2000
FREE AREA VELOCITY [fpm]

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW Ph: (570) 746-1888 Fax: (570) 746-9286
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE www.arrowunited.com
CHANGES WITHOUT NOTICE.
MEMBER OF AMCA
ASD-D37C-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA

MODEL D37C
®
FIRE/SEAL UL-CLASSIFIED Vertical & Horizontal

3-HR. DYNAMIC RATED Classified by Underwriters Laboratories as a 3-hour fire protection


rated Fire Damper, FOR USE IN DYNAMIC SYSTEMS, in accordance
FIRE DAMPER with Standards UL-555 and NFPA-90A, for the protection of open-
ings in fire partitions having a fire resistance rating of 3 hours or
more.
HOUSING BREAKAWAY
CONNECTION

UNDERWRITERS LABORATORIES INC.


CLASSIFIED

Arrow United
VERTICAL MOUNT

Industries
FIRE DAMPERS
FIRE RESISTANCE RATING 3 HR.
1/2" COLLAR
(FOR CONNECTION SEE U.L. CLASSIFIED BUILDING MATERIALS INDEX
TO DUCT)
California State Fire Marshal
NOMINAL Listing No. 3225-1328:101
DUCT NOMINAL
HEIGHT DUCT
LESS 1/4" HEIGHT
LESS 1/4" IMPORTANT
TOTAL FOR ROUND DUCT DIAMETERS UP TO
TRANSITION 31", AND FOR OVAL DUCT SIZES UP TO 34"
HEIGHT 1½" x 16 GA GALV.
STEEL SILL ANGLE W x 31" H, ARROW's 22-GA DUCT CON-
(EQUALS
NOMINAL (VERTICAL UNITS NECTION COLLAR (CRIMPED TO THE
DUCT HEIGHT ONLY) DAMPER HOUSING) CONSTITUTES A U.L.-
PLUS 0.93")
APPROVEDDUCT-TO-SLEEVE
"BREAKAWAY" CONNECTION,THUS AL-
LOWING A RIGID CONNECTION JOINT TO
1" TYP.
1/2" THREE SIDES BE UTILIZED BETWEEN THE DAMPER'S
"L" DUCT CONNECTION COLLAR AND THE
(5" IS STD.)
LONGER LENGTHS ARE AVAILABLE ROUND OR OVAL DUCTWORK.
WITH A FACTORY-SUPPLIED SLEEVE

HORIZONTAL MOUNT
DIMENSIONAL DATA:
MINIMUM SIZE: 4"W x 4"H (Duct), 6"W x 7"H (Frame).

BLADE MAXIMUM SIZE - VERTICAL:


LOCK* Single Panel: 34"W x 31"H (Duct), 36"W x 36"H (Frame).
HORIZONTAL:
Single Panel: 22"W x 20"H (Duct), 24"W x 24"H (Frame).
STAINLESS STEEL
NEGATOR CLOSURE SPRING

NOTE: Dampers should be ordered by nominal duct size.


*DAMPER TO BE INSTALLED WITH THE BLADE LOCK POINTS
FACING DOWNWARD AND WITH ACCESS FROM ABOVE
Fractional duct dimension (1/8" min.) will require the same
fractional addition to the corresponding damper housing
STANDARD MATERIALS & CONSTRUCTION:
dimension.
FRAME: One-piece rollformed 22-GA galvanized steel.
BLADES: 22-GA galvanized steel curtain-type.
HOUSING: 20-GA galvanized steel (Std.).
DUCT CONNECTION COLLAR: 22-GA galvanized PROJECT:
steel. LOCATION:
FUSIBLE LINK: UL-listed 165OF; replaceable. (Op- ARCHITECT:
tional 212OF (Vertical Mount Only) available at no ENGINEER:
additional charge.)
CONTRACTOR:
CLOSURE SPRINGS: Heat-treated Type 301 stainless
PO NUMBER:
steel constant force coiled negator type.
DATE:
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 Additional information
www.arrowunited.com on reverse side.
MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

RECTANGULAR
FIRE/SEAL® UL-CLASSIFIED
3-HR. DYNAMIC RATED FIRE DAMPER
ROUND
MODEL D37C

OVAL

“THW”: Total
}{
Housing
Width
Equals Nominal Duct Width less 1/4", Plus 2",
Plus Four Times Gauge of Housing:

DAMPER SIZING CHART


Width: Add 2" to Nominal Duct Width

Height: IF NOMINAL DUCT INCHES TO ADD


HEIGHT IS: FOR NOMINAL
FRAME HEIGHT
With 100% Free Area, Pressure Drop is determined by
6" thru 18" 3" FACE Area Velocity (in lieu of Free Area Velocity).

19" thru 28" 4" FLOW [cfm]


FACE AREA VELOCITY [fpm] =
FACE AREA [sq. ft.]
28" thru 31" 5"
See DIMENSIONAL DATA on front side.
.07
NOTE: .06
1. When a dynamic fire damper closes under airflow conditions, due to
.05
inertia, a momentary negative pressure spike (vacuum) can occur on
the down-stream side of the closed damper. This situation should be .04
taken into consideration by the Engineer/System Designer. STATIC
PRESSURE
2. Rated at 2000 fpm, 4 in. w.g. DROP
[in. wg.] .03

.02
AVAILABLE OPTIONS:
1. 16-GA through 10-GA housing.
2. Housing length ("L" dimension) of 6" through 24".
3. 212OF fusible link (Vertical Mount Only). .01
4. SPDT "closed damper" position indicator switch. 1000 2000
FACE AREA VELOCITY [fpm]
5. "Pull Ring" for ease of reopening closed damper.
(Horizontal Models Only.)
Arrow United Industries
A Division of Mestek, Inc.
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW 314 Riverside Drive . Wyalusing, PA 18853
UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE Ph: (570) 746-1888 Fax: (570) 746-9286
CHANGES WITHOUT NOTICE. www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-MD17-04.11

MODEL MD17 MODEL MD17


VERTICAL & HORIZONTAL MOUNT
NON-MOTORIZED
1-1/2 HR. DYNAMICALLY RATED, Classified by Underwriters Laboratories as a 1-½ hour fire protection
rated Fire Damper, FOR USE IN DYNAMIC SYSTEMS, in accordance
UL CLASSIFIED FIRE DAMPER with Standards UL-555 and NFPA-90A, for the protection of openings in
VERTICAL AND HORIZONTAL INSTALLATION fire partitions having a resistance rating of less than 3 hours.

UNDERWRITERS LABORATORIES, INC.®


“A” WIDE CLASSIFIED
FIRE DAMPERS
FIRE RESISTANCE RATING 1-1/2 HR.
A IN ACCORDANCE WITH UL-555
SEE U.L. FIRE RESISTANCE DIRECTORY

California State Fire Marshal


Listing No. 3225-1328:113

RECTANGULAR DAMPERS
“B” HIGH

Minimum Size: 4"W x 4"H


NOTE: Dampers can be furnished with a duct size minimum
of 4"W x 4"H using a type B or C enclosure in a factory
furnished sleeve. The overall frame is 8"W x 8"H.
Maximum Size: Vertical Horizontal
GALVANIZED STEEL CONSTRUCTION
Single Panel: 36"W x 48"H 36"W x 48"H
Multiple Panel: 72"W x 60"H or 72"W x 48"H
126”W x 48”H
STAINLESS STEEL CONSTRUCTION
A 11-3/8” Single Panel: 32"W x 32"H 24"W x 24"H
Multiple Panel: N/A N/A

STANDARD MATERIALS AND CONSTRUCTION ROUND AND OVAL DAMPERS


FRAME: 5-1/2” x 7/8” x 16GA galvanized steel hat channel. (Type C Housing, Duct Dimensions)
BLADES: 16GA Galvanized steel, 6” nominal width, parallel action Frame Width = Duct Width + 2"
AXLES: Square, plated solid steel stub. Frame Height = Duct Height + 2"
BEARINGS: Oil Impregnated Bronze Minimum Size: 6" Diameter
LINKAGE: Plated steel angle and crank plates with stainless steel pivots, GALVANIZED STEEL CONSTRUCTION
in-jamb type. Maximum Size: Vertical Horizontal
STOPS: 18GA galvanized steel at head and sill. Single Panel Single Panel
JAMB SEALS: Stainless steel. Round: 34" Diameter 34" Diameter
FINISH: Mill on galvanized steel. Oval: 34"W x 46"H 34"W x 46"H
ACTUATOR: Non-motorized spring closure mechanism with 165ºF fusible link. Multiple Panel Multiple Panel
Round: 58" Diameter 46" Diameter
AVAILABLE OPTIONS: Oval: 70"W x 58"H 70"W x 46"H
(Must Be Specified) or 124"W x 46"H
1. 304 S.S. & 316 S.S. Construction (Sleeve and in- STAINLESS STEEL CONSTRUCTION
airstream parts only.) (Single Panel Only)
[Maximum 32” x 32” Vert., 24” x 24” Horiz.] Round: 30" Diameter 22" Diameter
2. Minimum 16” deep 20 GA sleeve. Longer sleeves
Oval: 30"W x 30"H 22"W x 22"H
and sleeves as thick as 10 GA also available.
3. Type C housing for round and oval ductwork.
4. 212ºF fusible link.
5. Dual position indication package (See note 5).
PROJECT:
Wall Recommended
Thickness Sleeve Length LOCATION:
4”, 6” 16”
ARCHITECT:
8” 18”
12” 20” ENGINEER:
NOTE: The length of the sleeve should not extend over 6”
beyond the wall, except on the actuator side, where the CONTRACTOR:
sleeve may extend to a maximum 16” beyond the wall. PO NUMBER:
Arrow United Industries
DATE:
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853 Additional Information
Ph: (570) 746-1888 Fax: (570) 746-9286 on reverse side
www.arrowunited.com MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

NOTES
1. Underwriters Laboratories approved for dual direction air flow and dynamic applications.
2. Approved for vertical and horizontal installations.
3. Underwriters Laboratories classified for use in fire resistance ratings of less than 3 hours, in accordance with UL
Standard 555, 6th Edition.
4. Damper will be fabricated 1/4” undersized.
5. Optional auxiliary blade position indication switches are rated at 11A, 1/3HP, 125VAC. These snap action
switches are intended to make or break a circuit and will not provide variable or proportional resistance.

PERFORMANCE
Single Panel Multiple Panel
Maximum Velocity 4000 fpm 2000 fpm
Maximum Pressure 4 in. wg. 4 in. wg.

PRESSURE DROP
1.0
Pressure Drop (in. wg.)

24 x 24
0.1
36 x 36

0.01
500 1000 2000
FACE VELOCITY IN FEET PER MINUTE
TYPICAL PERFORMANCE CURVE
TESTED PER AMCA STANDARD 500-D; FIGURE 5.3 (IN-DUCT MOUNT)
(SMALLER SIZES WILL HAVE HIGHER PRESSURE DROPS)

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com

MEMBER OF AMCA

IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIED RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA SD-SMD37-
04.11

MODEL MD37 MODEL MD37


NON-MOTORIZED VERTICAL & HORIZONTAL MOUNT
3 HR. DYNAMICALLY RATED,
Classified by Underwriters Laboratories as a 3 hour fire protection rated
UL CLASSIFIED FIRE DAMPER Fire Damper, FOR USE IN DYNAMIC SYSTEMS, in accordance with
VERTICAL AND HORIZONTAL INSTALLATION Standards UL-555 and NFPA-90A, for the protection of openings in fire
partitions having a resistance rating of 3 hours or more.
“A” WIDE
A UNDERWRITERS LABORATORIES, INC.®
CLASSIFIED
FIRE DAMPERS
FIRE RESISTANCE RATING 3 HR.
IN ACCORDANCE WITH UL-555
SEE U.L. FIRE RESISTANCE DIRECTORY

California State Fire Marshal


Listing No. 3225-1328:115
“B” HIGH

DIMENSIONAL DATA
RECTANGULAR DAMPERS
MINIMUM SIZE: 4”W x 4”H
Dampers can be furnished with a duct size minimum of 4”W
x 4”H using a Type B or C enclosure in a factory furnished
sleeve. The overall frame is 8”W x 8”H.
MAXIMUM SIZE:
VERTICAL HORIZONTAL
A 11-3/8” Single Panel: 36”W x 48”H Single Panel: 30”W x 48”H
or 36”W x 30”H
STANDARD MATERIALS AND CONSTRUCTION Multiple Panel: 126”W x 48”H Multiple Panel: 60”W x 48”H
FRAME: 5-1/2” x 7/8” x 16GA galvanized steel hat channel.
BLADES: 16GA Galvanized steel, 6” nominal width, parallel ROUND AND OVAL DAMPERS
action (Type C Housing, Duct Dimensions)
AXLES: Square, plated solid steel stub. MINIMUM SIZE: 6” Diameter
BEARINGS: Oil Impregnated Bronze MAXIMUM SIZE:
LINKAGE: Plated steel angle and crank plates with stainless steel VERTICAL HORIZONTAL
pivots, in-jamb type. Single Panel:Round: 34” Dia. Single Panel: Round: 28” Dia.
STOPS: 18GA galvanized steel at head and sill. Oval: 34”W x 46”H Oval:28”W x 46”H or
JAMB SEALS: Stainless steel. 34”W x 28”H
FINISH: Mill on galvanized steel. Multiple Panel:Round: 46” Dia. Multiple Panel: Round: 46” Dia.
ACTUATOR: Non-motorized spring closure mechanism with 165ºF Oval: 124”W x 46”H Oval: 58”W x 46”H
fusible link.

NOTES: AVAILABLE OPTIONS:


(Must Be Specified)
1. Underwriters Laboratories approved for dual direction air flow and dynamic
applications. 1. Minimum 16” deep 20 GA sleeve. Longer sleeves
2. Approved for vertical and horizontal installations. and sleeves as thick as 10 GA also available.
2. Type C housing for round and oval ductwork.
3. Underwriters Laboratories classified for use in fire resistance ratings of 3 hours or
3. 212ºF fusible link.
more, in accordance with UL Standard 555, 6th Edition. 4. Dual position indication package. (See note 5.)
4. Damper will be fabricated 1/4” undersized.
5. Optional auxiliary blade position indication switches are rated at 11A, 1/3HP,
125VAC. These snap action circuits are intended to make or break a circuit and
will not provide variable or proportional resistance. PROJECT:

Wall Recommended LOCATION:


Thickness Sleeve Length
ARCHITECT:
4”, 6” 16”
8” 18” ENGINEER:
12” 20”
NOTE: The length of the sleeve should not extend CONTRACTOR:
over 6” beyond the wall, except on the actuator side,
PO NUMBER:
where the sleeve may extend to a maximum 16”
Arrow United Industries DATE:
A Division of Mestek, Inc.
Additional Information
314 Riverside Drive . Wyalusing, PA 18853
on reverse side
Ph: (570) 746-1888 Fax: (570) 746-9286 MEMBER OF AMCA
www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA

PERFORMANCE
Single Panel Double Panel
Maximum Velocity 4000 fpm 2000 fpm
Maximum Pressure 4 in. wg. 4 in. wg.

PRESSURE DROP

1.0
PRESSURE DROP (in. wg.)

0.1 24 x 24
36 x 36

0.01
500 1000 2000

FACE VELOCITY IN FEET PER MINUTE


TYPICAL PERFORMANCE CURVE
TESTED PER AMCA STANDARD 500-D; FIGURE 5.3 (IN-DUCT MOUNT)
(SMALLER SIZES WILL HAVE HIGHER PRESSURE DROPS)

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
MEMBER OF AMCA

IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
Ceiling Radiation Dampers

A89 2 hour rated horiz no extension non insulated


A91 2 hour rated horiz no extension insulated
A93 2 hour rated horiz no extension insulated
A95 2 hour rated horiz round no extension non insulated
A97 2 hour rated horiz round no extension insulated
Thermal Blanket
Installation
ASD-A89-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA

UL-CLASSIFIED
MODEL A89
CEILING DAMPER RECTANGULAR
For 2-Hr. Designs TWO-BLADE/UN-INSULATED

MATERIALS AND CONSTRUCTION UNDERWRITERS LABORATORIES INC.®


FRAME: One-Piece, roll-formed 22-Ga. CLASSIFIED
galvanized steel. (221/32” standard CEILING DAMPERS
depth). FIRE RESISTANCE CLASSIFICATION
BLADES: 22-Ga. galvanized steel. DESIGN NO’S. — SEE PRODUCT CATEGORY
IN UL FIRE RESISTANCE DIRECTORY
FUSIBLE LINK: 165°F Standard (212°F Optional).
SPRING: Extension type. ARROW UNITED INDUSTRIED
FINISH: Mill. A Mestek Company

OPTIONAL THERMAL BLANKET for lay-in diffuser/


grille installations: 1/4” thick ceramic fiber, (8 lbs./cu. California State Fire Marshal Listing No.:
ft. density). 3225-1328:105
HEIGHT 1-hr. Combustible Ceiling Assemblies
1-hr. & 2-hr. Non-Combustible Ceiling Assemblies
DIMENSIONAL DATA
Maximum Size: 100 sq. in.
FUSIBLE Width: 33/4” Minimum; 18” Maximum
A LINK Height: 33/4” Minimum; 10” Maximum
A
WIDTH

The larger dimension is always the width, and is parallel to the blades.
OPTIONAL FRAME EXTENSIONS
To facilitate various installations, a damper frame extension can be
provided for the top of the frame, the bottom of the frame, or both the
top and bottom of the frame, and will result in the following total frame
depth:
CLOSED
POSITION Top Extension: 61/8”
Bottom Extension: 61/4”
Top and Bottom Extension: 91/4”

TOP FRAME CEILING DAMPERS - FUNCTION AND APPLICATION


BLADE EXTENSION This ceiling damper is used to provide the required fire and heat
radiation protection of HVAC penetrations of Floor-
EXTENSION
OPEN Ceiling and Roof-Ceiling Assemblies having a Restrained or Unre-
SPRING
POSITION strained Assembly Fire Resistance Rating of 2 hours or less, in
accordance with UL-263. Standard Fire Dampers (11/2 hr. & 3-hr.)
STD.
do not provide the necessary heat radiation protection. Ceiling
221/32 FRAME
Dampers are also called Ceiling Fire Dampers, Radiation Damp-
DEPTH
ers, and Radiation Shields. See ARROW’s UL-approved In-
stallation Instructions for various installation requirements and
procedures. Approved Ceiling Designs are illustrated by De-
sign Number in UL’s Fire Resistance Directory.
BOTTOM FRAME
SECTION A-A EXTENSION

PROJECT: CONTRACTOR:
LOCATION: PO NUMBER:
ARCHITECT: DATE:
ENGINEER:

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED
www.arrowunited.com
MEMBER OF AMCA INDUSTRIESRESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-A91-04.11

UL-CLASSIFIED
MODEL A91
CEILING DAMPER RECTANGULAR
For 2-Hr. Designs TWO-BLADE/INSULATED

UNDERWRITERS LABORATORIES INC.®


MATERIALS AND CONSTRUCTION CLASSIFIED
FRAME: One-Piece, roll-formed 22-Ga. CEILING DAMPERS
galvanized steel. (221/32” standard FIRE RESISTANCE CLASSIFICATION
depth). DESIGN NO’S. — SEE PRODUCT CATEGORY
BLADES: 22-Ga. galvanized steel. IN UL FIRE RESISTANCE DIRECTORY
1
INSULATION: /2” thick gypsum. Arrow United
FUSIBLE LINK: 165°F Standard (212°F Optional). Industries
SPRING: Extension type.
FINISH: Mill. California State Fire Marshal Listing No.:
OPTIONAL THERMAL BLANKET for lay-in diffuser/
grille installations: 1/4” thick ceramic fiber, (8 lbs./cu. 3225-1328:105
ft. density). 1-hr. Combustible Ceiling Assemblies
1-hr. & 2-hr. Non-Combustible Ceiling Assemblies
HEIGHT
DIMENSIONAL DATA
Maximum Size: 324 Sq. in.
Width: 103/4” Minimum; 18” Maximum
Height: 53/4” Minimum; 18” Maximum
FUSIBLE The larger dimension is always the width, and is parallel to the blades.
A LINK A
WIDTH

OPTIONAL FRAME EXTENSIONS


To facilitate various installations, a damper frame extension can be
provided for the top of the frame, the bottom of the frame, or both the
top and bottom of the frame, and, depending on the HEIGHT of the
damper, will result in the following total frame depths:
Heights: Heights: Heights:
53/4”-10” 101/2”-14” 14 1/2”-18”
CLOSED
POSITION Top Extension: 91/4” 91/4” 103/4”
Bottom Extension: 61/8” 61/8” 61/8”
Top and Bottom Extension: 91/4” 103/4” 123/4”
CEILING DAMPERS - FUNCTION AND APPLICATION
BLADE TOP FRAME This ceiling damper is used to provide the required fire and heat radia-
INSULATION
EXTENSION tion protection of HVAC penetrations of Floor-
OPEN EXTENSION Ceiling and Roof-Ceiling Assemblies having a Restrained or Unrestrained
POSITION SPRING
Assembly Fire Resistance Rating of 2 hours or less, in accordance with
STD. UL-263. Standard Fire Dampers (11/2-hr. & 3-hr.) do not provide the
221/32 FRAME necessary heat radiation protection. Ceiling Dampers are also called
DEPTH Ceiling Fire Dampers, Radiation Dampers, and Radiation Shields.
See Arrow’s UL-approved Installation Instructions for various in-
stallation requirements and procedures. Approved Ceiling Designs
BOTTOM FRAME are illustrated by Design Number in UL’s Fire Resistance Directory.
EXTENSION
SECTION A-A

PROJECT:
LOCATION: CONTRACTOR:
ARCHITECT: PO NUMBER:
ENGINEER: DATE:
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED
MEMBER OF AMCA INDUSTRIESRESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
ASD-A93-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA

UL-CLASSIFIED
MODEL A93
CEILING DAMPER RECTANGULAR
For 2-Hr. Designs FOUR-BLADE/INSULATED

UNDERWRITERS LABORATORIES INC.®


MATERIALS AND CONSTRUCTION CLASSIFIED
FRAME: One-Piece, roll-formed 22-Ga. CEILING DAMPERS
galvanized steel. (221/32” standard FIRE RESISTANCE CLASSIFICATION
depth). DESIGN NO’S. — SEE PRODUCT CATEGORY
BLADES: 22-Ga. galvanized steel. IN UL FIRE RESISTANCE DIRECTORY
1
INSULATION: /2” thick gypsum. Arrow United Industries
FUSIBLE LINK: 165°F Standard (212°F Optional). A Mestek Company
SPRING: Extension type.
FINISH: Mill. California State Fire Marshal Listing No.:
OPTIONAL THERMAL BLANKET for lay-in diffuser/ 3225-1328:105
grille installations: 1/4” thick ceramic fiber, (8 lbs./cu. 1-hr. Combustible Ceiling Assemblies
ft. density). 1-hr. & 2-hr. Non-Combustible Ceiling Assemblies

DIMENSIONAL DATA
HEIGHT Maximum Size: 576 Sq. in.
Width: 33/4” Minimum; 24” Maximum
Height: 183/4” Minimum; 24” Maximum
The smaller dimension is always the width, and is parallel to the
blades.
FUSIBLE
A A
LINK OPTIONAL FRAME EXTENSIONS
WIDTH

To facilitate various installations, a damper frame extension can


be provided for the top of the frame, the bottom of the frame, or
both the top and bottom of the frame, and, depending on the
HEIGHT of the damper, will result in the following total frame
depths:
CLOSED
POSITION Heights: Heights:
183/4”-20” 201/2”-24”
Top Extension: 91/4” 91/4”
TOP FRAME Bottom Extension: 61/8” 61/8”
EXTENSION Top and Bottom Extension: 91/4” 103/4”
BLADE INSULATION
OPEN
BLADE EXTENSION CEILING DAMPERS - FUNCTION AND APPLICATION
POSITION SEPARATOR SPRING This ceiling damper is used to provide the required fire and heat
STD. radiation protection of HVAC penetrations of Floor-
21
2 /32 FRAME
Ceiling and Roof-Ceiling Assemblies having a Restrained or Unre-
DEPTH
strained Assembly Fire Resistance Rating of 2 hours or less, in
accordance with UL-263. Standard Fire Dampers (11/2-hr. & 3-hr.)
BOTTOM FRAME do not provide the necessary heat radiation protection. Ceiling
EXTENSION Dampers are also called Ceiling Fire Dampers, Radiation Dampers,
and Radiation Shields. See Arrow’s UL-approved Installation In-
structions for various installation requirements and procedures.
Approved Ceiling Designs are illustrated by Design Number in UL’s
PROJECT: Fire Resistance Directory.
LOCATION:
CONTRACTOR:
ARCHITECT:
PO NUMBER:
ENGINEER:
DATE:
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES
RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
MEMBER OF AMCA
ASD-A95-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA

UL-CLASSIFIED
MODEL A95
CEILING DAMPER ROUND
For 2-Hr. Designs TWO-BLADE/UN-INSULATED

UNDERWRITERS LABORATORIES INC.®


MATERIALS AND CONSTRUCTION CLASSIFIED
FRAME: One-Piece, roll-formed 22-Ga. CEILING DAMPERS
galvanized steel. (327/32” standard FIRE RESISTANCE CLASSIFICATION
depth). DESIGN NO’S. — SEE PRODUCT CATEGORY
IN UL FIRE RESISTANCE DIRECTORY
BLADES: 22-Ga. galvanized steel. ISSUE NO.
FUSIBLE LINK: 165°F Standard (212°F Optional). Arrow United Industries
SPRING: Extension type. A Mestek Company
FINISH: Mill.
OPTIONAL THERMAL BLANKET for lay-in diffuser/
California State Fire Marshal Listing No.:
grille installations: 1/4” thick ceramic fiber, (8 lbs./cu.
ft. density). 3225-1328:105
1-hr. Combustible Ceiling Assemblies
1-hr. & 2-hr. Non-Combustible Ceiling Assemblies
CLOSED
POSITION
DIMENSIONAL DATA
Maximum Size: 95 Sq. in.
FUSIBLE
A LINK A Minimum Diameter: 53/4” Minimum
Maximum Diameter: 11”

33/4 THRU 11”


DIAMETERS
OPTIONAL FRAME EXTENSIONS
To facilitate various installations, a damper frame extension can be
provided for the top of the frame, the bottom of the frame, or both the
top and bottom of the frame, and will result in the following total frame
depths:

Top Extension: 71/2”


Bottom Extension: 51/2”
Top and Bottom Extension: 97/8”
BLADE TOP FRAME
EXTENSION
EXTENSION CEILING DAMPERS - FUNCTION AND APPLICATION
SPRING
This ceiling damper is used to provide the required fire and heat
radiation protection of HVAC penetrations of Floor-
STD. Ceiling and Roof-Ceiling Assemblies having a Restrained or Unre-
OPEN POSITION 27/8 FRAME strained Assembly Fire Resistance Rating of 2 hours or less, in
DEPTH
accordance with UL-263. Standard Fire Dampers (11/2-hr. & 3-hr.)
do not provide the necessary heat radiation protection. Ceiling
Dampers are also called Ceiling Fire Dampers, Radiation Damp-
ers, and Radiation Shields. See Arrow’s UL-approved Installa-
BOTTOM FRAME tion Instructions for various installation requirements and pro-
EXTENSION cedures. Approved Ceiling Designs are illustrated by Design
Number in UL’s Fire Resistance Directory.
PROJECT:
LOCATION: CONTRACTOR:
ARCHITECT: PO NUMBER:
ENGINEER: DATE:

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED
MEMBER OF AMCA INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-A97-04.11

UL-CLASSIFIED
MODEL A97
CEILING DAMPER ROUND
For 2-Hr. Designs TWO-BLADE/INSULATED

UNDERWRITERS LABORATORIES INC.®


MATERIALS AND CONSTRUCTION CLASSIFIED
FRAME: One-Piece, roll-formed 22-Ga. CEILING DAMPERS
galvanized steel. (327/32” standard FIRE RESISTANCE CLASSIFICATION
depth). DESIGN NO’S. — SEE PRODUCT CATEGORY
BLADES: 22-Ga. galvanized steel. IN UL FIRE RESISTANCE DIRECTORY
INSULATION: 1/2” thick gypsum. Arrow United Industries
FUSIBLE LINK: 165°F Standard (212°F Optional). A Mestek Company
SPRING: Extension type.
FINISH: Mill. California State Fire Marshal Listing No.:
OPTIONAL THERMAL BLANKET for lay-in dif-
fuser/grille installations: 1/4” thick ceramic fiber, (8 3225-1328:105
lbs./cu. ft. density). 1-hr. Combustible Ceiling Assemblies
1-hr. & 2-hr. Non-Combustible Ceiling Assemblies

CLOSED DIMENSIONAL DATA


POSITION
Maximum Size: 314 Sq. in.
Minimum Diameter: 113/4”.
FUSIBLE Maximum Diameter: 20”.
A LINK
A

113/4 THRU 20” OPTIONAL FRAME EXTENSIONS


DIAMETERS To facilitate various installations, a damper frame extension can be
provided for the top of the frame, the bottom of the frame, or both the
top and bottom of the frame, and will result in the following total frame
depths:
Diameters: Diameters:
113/4”-16” 163/4”-20”
Top Extension: 101/2” 121/2”
Bottom Extension: 51/2” 51/8”
Top and Bottom Extension: 127/8” 147/8”
BLADE TOP FRAME
INSULATION
EXTENSION
EXTENSION CEILING DAMPERS - FUNCTION AND APPLICATION
SPRING This ceiling damper is used to provide the required fire and heat
radiation protection of HVAC penetrations of Floor-
OPEN
STD. Ceiling and Roof-Ceiling Assemblies having a Restrained or Unre-
POSITION
27/8 FRAME strained Assembly Fire Resistance Rating of 2 hours or less, in ac-
DEPTH cordance with UL-263. Standard Fire Dampers (11/2-hr. & 3-hr.) do
not provide the necessary heat radiation protection. Ceiling Dampers
are also called Ceiling Fire Dampers, Radiation Dampers, and Radia-
tion Shields. See Arrow’s UL-approved Installation Instructions
BOTTOM FRAME
for various installation requirements and procedures. Approved
EXTENSION Ceiling Designs are illustrated by Design Number in UL’s Fire Re-
SECTION A - A sistance Directory.
PROJECT:
CONTRACTOR:
LOCATION:
PO NUMBER:
ARCHITECT:
DATE:
ENGINEER:
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED
INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
MEMBER OF AMCA
ASD-ATB-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA

THERMAL BLANKET
For Lay-In Diffuser/Grille Installations Of
ARROW'S UL-CLASSIFIED CEILING DAMPERS

UTILIZES CEILING REFER TO CEILING


DAMPER MODEL NO.: DAMPER SUBMITTAL NO.:
A89 ASD-A89
A91 ASD-A91
A93 ASD-A93
A95 ASD-A95
A97 ASD-A97

See Reverse Side for INFORMATIONAL DATA.

PROJECT:
LOCATION: CONTRACTOR:
ARCHITECT: P. O. NUMBER:
ENGINEER: DATE:
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com

MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

THERMAL BLANKET
For Lay-In Diffuser/Grille Installations Of
ARROW'S'S UL-CLASSIFIED CEILING DAMPERS
INFORMATIONAL DATA

1) A Thermal Blanket is required for ceiling dampers supported by a lay-in diffuser/grille.

2) The area below the plane of the ceiling damper blade down to the topside of the diffuser/grille must be insulated.
Two methods of insulating this area may be employed when the topside of the diffuser/grille is flat and is raised
no more than 1¦2" from the face of the ceiling:

a) The first and most convenient method is to use a Thermal Blanket. Cut the desired hole, and lay the Thermal
Blanket over the diffuser/grille. Next, take an extension piece of the blanket and wrap it around the damper/
diffuser overlap connection. Secure it in place with the use of hanger wire. The Thermal Blanket should extend
out to the tee grid on all four sides.

b) An alternative method is to use the same ceiling tile material as is used for the remainder of the ceiling. Although
the tile must be cut to allow for the damper/diffuser overlap connection to pass through, the clearance between
the tile and the tee grid and between the damper and the tile should not be greater than 1/4" total.

EXCEPTION: When the topside of the lay-in diffuser/grille is pitched or contains an obstruction of greater than
1/2" from the ceiling surface, the Thermal Blanket MUST be used.

3) When a opposed blade damper (OBD) is installed between the ceiling damper and the ceiling surface, be sure
that the insulation covers the area below the plane of the damper blade down to the topside of the diffuser/grill.

4) When a sloped or tapered surface-mount diffuser/grille is used, the diffuser/grille MUST be insulated with a
Thermal Blanket. The Thermal Blanket should provide insulation from the plane of the ceiling damper blade down
to the top of the ceiling surface.

5) Arrow's Thermal Blanket is a 1/4" thick non-asbestos ceramic fiber, with 8 lbs./cu. ft. density. The blanket offers
highly efficient insulation and possesses high tensile strength and resiliency to withstand vibration and physical
abuse. It will not separate, sag, or settle. It is characterized by extreme resistance to thermal shock, and its
thermal and physical properties are unaffected by oil or water after drying.

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com

MEMBER OF AMCA

IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
CEILING RADIATION DAMPERS II-ACRD-04.11

INSTALLATION INSTRUCTIONS

Models A80/A90 Series ceiling dampers approved for installations which LAY-IN INSTALLATION
provide appropriate protection of duct outlets in ceiling/floor or ceiling/ The ceiling dampers in these applications are supported directly by the
roof assemblies that are fire rated at two hours or less. These ceiling ceiling grid. When lay-in diffusers/grilles are to be utilized, the ceiling
dampers when installed as described herein are used in lieu of hinged- damper is mounted directly to the diffuser/grille and the diffuser/grille is
blade sheet metal dampers in steel ducts as specified in Underwriters supported directly by the grid.
Laboratories Inc.’s Fire Resistance Directory (FRD). The models above A.Lay-in Ceiling Dampers, ductless or ducted, (Models A93, A91). See
are installed in two basic methods: Figure 1. The ceiling damper shall completely fill the opening of a grid
1. Lay-in, in which the damper is supported by the ceiling grid. module and rest directly on the tee bar grid, (main runners and/or cross
2. Surface Mounted, in which the damper is supported from struc- tees on four sides). The four corners of the grid module into which the
tural members above the ceiling surface. damper is installed shall have a hanger wire support. Openings of 24 x
24, 24 x 18, 24 x 12 and 24 x 6 are the only sizes available for this
NOTE: Grilles, diffusers or lay-in diffusers mentioned in the fol- installation method. When dampers installed in this manner are to be
lowing instructions are an accessory item and not included with connected to a round or flexible duct, the damper must have an ex-
the damper. tended upper frame with a square to round adapter.
GENERAL REQUIREMENTS FOR SURFACE MOUNTED AND LAY-IN B. Lay-in Diffuser Ceiling Dampers, ductless or ducted. (Models A90,A292,
INSTALLATIONS A95, A97. See Figure 2. In this application, lay-in diffuser or lay-in
grille fills a full 24 x 24 grid module and the damper mounts on the
The following are requirements for all models and installation methods:
reduced neck of the device. The following are requirements for instal-
1. Grilles, Diffusers or Lay-in Diffusers shall be made of steel. lation:
2. Flexible air ducts shall be Class O or Class 1 and bear the UL Listing
1. The 233/4” x 233/4” lay-in diffuser shall have a topside surface of 24
Mark. A steel strap or 16 SWG hanger wire shall be used to connect the
MSG steel and have a maximum 20” diameter or 18” square collar.
flexible air duct to the damper assembly.
3. A maximum of 1/8” (1/4” total) clearance may exist between the ceiling 2. The four corners of the grid module into which the lay-in diffuser is
damper and a diffuser or grille. A maximum of 1/8” (1/4” total) clearance installed shall have a hanger wire support.
may exist between a damper and tee bars of a grid supported installa-
tion. A maximum of 1/8” (1/4” total) clearance may exist between the 3. If flexible duct is used, the round damper shall have an extended
ceiling damper and the duct drop. Note: These maximum clearances upper frame. Square dampers with an extended upper frame and
are allowed for fitting purposes. square to round adapter may also be used with flexible duct.

4. Ceiling dampers shall be overlapped by the duct drop, a minimum 9/16” 4. The top surface of the lay-in diffuser and the ceiling damper frame
and fastened with No. 8 sheet metal screws, 3/16” tubular steel rivets or below the blade plane shall be insulated. Two methods of insulating
1
/4” tack welds. Square and rectangular dampers shall have a minimum this area may be employed when the topside of the diffuser/grille is
of one fastener, four total, within one inch from each corner. Round flat and is raised no more than 1/2” from the face of the ceiling: The
ceiling dampers shall have a minimum of three fasteners equally spaced. first method and most convenient is by the use of our thermal
Screws and rivets shall be located a minimum of 3/16” from the edge of blanket. Simply cut the desired hole and lay the blanket over the
the damper frame, duct drop or collars. Note: Do not drive sheet metal diffuser. Next, take an extension piece and wrap it around the
screws into the damper frames so as to prevent the blades from clos- damper/diffuser overlap connection. Secure it in place with the use
ing. We suggest the use of steel pop rivets with the flat head on the of hanger wire. The blanket shall extend out to the tee grid on all
inside of the damper frame. four sides. The second method is to use the same ceiling tile
5. Connections of the grille, diffuser or lay-in diffuser to the duct and/or material as is utilized for the remainder of the ceiling. This should be
damper shall have minimum 9/16” overlap and fastened with the same cut to allow the damper/diffuser connections to pass through, how-
minimum requirements of duct drop to damper fasteners described in ever, clearance between the tile and tee grid and between the
the preceding paragraph. damper and the tile shall not be greater than 1/4” total. Exception:
When the topside of the lay-in diffuser is pitched or contains ob-
6. Hanger wire shall be minimum 12 SWG for all damper/ceiling assembly struction of greater than 1/2” from the ceiling surface, the thermal
supports and shall be vertical and not splayed. blanket must be used.
7. Opposed Blade Dampers (OBD) may be utilized in any ceiling damper
installation. The OBD may be installed into a ceiling damper with an 5. When an Opposed Blade Damper is installed between the ceiling
extended lower frame or directly to the duct drop below the damper, damper and ceiling surface, ensure that the insulation covers the
however, no installation shall exceed the maximum spacings allowed area below the blade plane to the diffuser topside.
between the ceiling surface and blades of the ceiling damper. SURFACE MOUNTED DIFFUSER OR GRILLE INSTALLATION
8. All ceiling dampers are shipped in the closed position. To install the
damper, the blades must be manually held open and the free end of the The ceiling dampers in these applications are supported by duct drop or
fusible link must be attached, in the field, to the adjacent blade. The hanger wire and not by the ceiling surface in which installed. The ceiling
lanced tab, provided on uninsulated blades or the fusible link holder, damper/grille assemblies shall also be located in the field of an acoustical
provided on gypsum insulated blades may be bent with pliers or by hand panel; but where it is necessary to cut a main runner or cross tee, each
to provide an adequate attachment. cut end shall be supported by a vertical 12 SWG hanger wire. A 1/2”
clearance shall be maintained between the duct outlet and each cut end of
9. The clearance between the lower surface of the ceiling and the lower the main runner or cross tee. Each ceiling damper/grille assembly shall be
surface of the damper blades shall not exceed 5” in any type installation. located so that no more than one main runner or cross tee is cut when
10.Installations that require extended upper frames for protection of the penetrating the ceiling membrane. The grille provided shall be of a type
damper blades may be provided with sleeves in the field. These that has a flange at least 1” wide to support the surrounding acoustical
sleeves shall extend from the damper frame to an elevation above the material. The size of the cutout in the acoustical material shall not be larger
blades, when they are in the open position and held by the fusible link. than the flanged grille/diffuser. The cutout shall also not be more than 1/2”
The sleeve shall be attached to the damper frame in the same manner (1” total) larger than the damper/grille frame.
as required for the duct drop to damper frame.
A. Ductless, Surface Mounted Ceiling Dampers (Models A98, A91, A93, B. Main ducts must be supported adjacent to the duct drops with
A95, A97). See Figure 4. In this application, hanger wire supports steel 11/2” deep 16 MSG channels on all round installations. However,
are utilized in lieu of a steel duct drop and the flanged grille or diffuser where square or rectangular duct drops are used, the steel chan-
is attached directly to the damper. Square and rectangular dampers nels may be bolted to opposite sides of the duct drop with 3/16” bolts
shall be supported by a minimum of four each hanger wires, located a minimum of 3/8” in length. Two bolts per side, spaced 6” O.D. are
within 1/2” of each corner. Round dampers shall be supported by a required.
minimum of three each hanger wires, equally spaced. The wires may
be attached in two methods as follows: C. When a sloped or tapered surface mount diffuser or grille is
utilized, the diffuser shall be insulated with our thermal blanket.
1. Dampers with extended upper frames may be supported by The blanket shall insulate the diffuser from the blade plane down
hanger wires looped through 1/4” holes drilled or punched in the to the top of the ceiling surface. See Figure 4.
field. There should be a minimum 3/16” spacing between the holes
and frame edge. 2. When flex duct is to be connected to a surface mounted ceiling
2. Dampers with standard size frames may be supported with damper/diffuser assembly, an extended upper frame must be pro-
hanger straps, one for each hanger wire. See Figure 5 for vided for this type installation. Square and rectangular dampers shall
hanger strap details. be supported by a minimum of four each hanger wires, located within
1
/2” of each corner. Round dampers shall be supported by a minimum
B. Ducted, Surface Mounted Ceiling Dampers (Models A89, A91, A93,
of three each hanger wires, equally spaced. These hanger wires for
A95, A97). See Figure 3.
both the rectangular and round dampers shall support the damper by
1. A. When a steel duct drop supports the ceiling damper, the grille way of hanger straps, one for each hanger wire. See Figure 5 for
may be connected directly to the damper frame or the duct drop hanger strap details.
may extend down to the ceiling line, thus allowing the grille or
diffuser to be connected directly to the duct. All of the Surface Mounted Installations described above are with lay-in
acoustical ceiling panels. The damper may also be utilized with all other
ceiling material types described for two hour or less designs. One addi-
tional general requirement shall be that the hanger wires, which support the
damper assembly, be connected to structural supports above the ceiling in
FIG. 1 accordance with the requirements of the Floor-Ceiling or Roof-Ceiling
Design from UL Fire Resistance Directory specified by the customer.
1. STEEL GRID 7. HANGER STRAPS
2. CEILING PANELS 8. LAY-IN DIFFUSER
3. HANGER WIRE 9. SLOPED OR TAPERED GRILLE
4. CEILING DAMPER 10. GRILLE
5. CERAMIC BLANKET 11. 11/2” DEEP CHANNELS
6. NO. 8 OR NO. 10 SHEET MIN. 16 GA.
METAL SCREWS 12. DUCT DROP
13. RIVET
FIG. 2
FIG. 4

FIG. 3
FIG. 5

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
Fire / Smoke Dampers

AS1 1 1/2 hour rated with sleeve Class I


AS2 1 1/2 hour rated with sleeve Class II
AT1 3 hour rated with sleeve Class I
AT2 3 hour rated with sleeve Class II
UA1 1 1/2 hour rated w/sleeve Class I Airfoil Blade
UA2 1 1/2 hour rated w/sleeve Class II Airfoil Blade
Installation (1-1/2 Hour Rated)
Installation (3 Hour Rated)
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-AS1-04.11

MODEL AS1 UNDERWRITERS LABORATORIES INC.®


LEAKAGE AND TEMPERATURE RATED CLASSIFIED FIRE DAMPER
FIRE RESISTANCE RATING 11/2 HR
COMBINATION FIRE/SMOKE DAMPER . ALSO AS TO LEAKAGE RESISTANCE
CLASS I
LEAKAGE CLASS I • DYNAMICALLY CLASSIFIED FILE #R4708
TEMPERATURE CLASS 250°F OR 350°F This combination fire/smoke damper meets the construction
and performance requirements of:

• Underwriters Laboratories Inc. Standards 555 and 555S


STANDARD MATERIALS AND CONSTRUCTION • National Fire Protection Association Standards 90A, 92A
and 92B
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel. • ICC's International Building Code
BLADES: 16-GA Galvanized steel, 6" nominal width, parallel action. • ICBO's Uniform Building Code
AXLES: Plated solid steel stub. • SBCCI's Standard Building Code
BEARINGS: Oil Impregnated Bronze. • BOCA's National Building Code
LINKAGE: Plated steel angle and crank plates with stainless steel • New York City MEA Listing #111-99-M
pivots, in-jamb type. • California State Fire Marshall Listing #3225-1328:113, 114
STOPS: 18-GA galvanized steel at head and sill.
BLADE EDGE
SEALS: Silicone.
DIMENSIONAL DATA See notes 1 & 2
SIDE JAMB RECTANGULAR DAMPERS
SEALS: Stainless steel. Minimum Size: 16"W x 8"H
SLEEVE: Minimum 20-GA galvanized steel by 20" long is standard on
sizes over 24"W x 12"H. A 20-GA by 17" long integral sleeve Maximum Size: Vertical Horizontal
is standard on sizes 24"W x 12"H and smaller. GALVANIZED STEEL CONSTRUCTION
CAULKING: Hardcast Irongrip 601, or UL-listed equivalent.
Single Panel: 36"W x 48"H 36"W x 48"H
FINISH: Mill on galvanized steel.
or 48"W x 36"H
ACTUATOR: ELECTRIC, with 165°F thermal disc; or PNEUMATIC, with
165°F fusible link and P.E.R.V. Factory-installed for Multiple Panel: 108"W x 48"H 72"W x 48"H
Power-Open/Spring-Return (Fail Close) operation. STAINLESS STEEL CONSTRUCTION (250º only)
Single Panel: 32"W x 32"H 24"W x 24"H
Multiple Panel: N/A N/A
THIS DIMENSION
WILL INCREASE IF
ROUND AND OVAL DAMPERS
SLEEVE LENGTH (Type C Housing, Duct Dimensions)
IS INCREASED Frame Width = Duct Width + 2"
THIS DIMENSION Frame Height = Duct Height + 2"
20" (STD)
WILL INCREASE IF
SLEEVE LENGTH
Minimum Size: Round: 14" Diameter
10½" 5½" 4"
IS INCREASED Oval: 14" x 6"

10" 7"
GALVANIZED STEEL CONSTRUCTION
OPERATOR Maximum Size: Vertical Horizontal
Single Panel Single Panel
Round: 34" Diameter 34" Diameter
Oval: 34"W x 46"H 34"W x 46"H
or 46"W x 34"H
Double Panel Double Panel
Round: 46" Diameter 46" Diameter
Oval: 70"W x 46"H 70"W x 46"H
or 94"W x 34"H
HEAT SENSITIVE INTEGRAL STAINLESS STEEL CONSTRUCTION (250º only)
DEVICE SLEEVE
(Single Panel Only)
Round: 30" Diameter 22" Diameter
Oval: 30"W x 30"H 22"W x 22"H
NOTES:
1. Units up to 24"W x 12"H will have a 20-GA by
17" long integral sleeve as standard with a single blade. PROJECT:
2. Units that are BOTH less than 16"W AND over 12"H are Leakage
Class II. LOCATION:
3. Dampers will be fabricated ¼" undersize (½" width undersizing ARCHITECT:
when two panels wide).
ENGINEER:
4. Approved for vertical and horizontal installation.
5. Stainless steel construction not available in integral sleeve design. CONTRACTOR:
Arrow United Industries PO NUMBER:
A Division of Mestek, Inc.
DATE:
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA
AVAILABLE OPTIONS: (Must Be Specified)
1. 304 S.S. or 316 S.S. Construction. (Sleeve and in- A = Nominal Duct Width
airstream parts only.) Actuator must be externally B = Nominal Duct Height
mounted. 17" STANDARD
FOR INTEGRAL
2. Sleeve thicknesses heavier than the standard 20-GA
SLEEVE
and longer than the standard 20" length (17" on
integral sleeve.)
20" STANDARD
3. Type C Housing for round and oval ductwork. FOR
4. 212ºF thermal disc (electric models) or fusible link MULTI-BLADE
(pneumatic models.)
5. "Sens-O-Therm" Thermally Reopenable Tempera-
ture Sensing System is available with 165ºF (Stan-
dard) or 212ºF settings. This system includes con-
tacts for connection to open and closed position OPERATOR
indicator lamps. It also includes a second thermal
disc to re-close the damper when the rated degrada-
"B" + 2"
tion temperature is reached.
6. Dual position indication package. These optional
auxiliary blade position indication switches are in-
tended to make or break a circuit and will not provide
variable or proportional resistance.
7. Smoke detetctor (minimum 20" sleeve required,
damper height must be 10" minimum.)

Recommended Sleeve Length "A" + 2"


Wall
Thickness W/Integral W/Non-Integral
TYPE "C" HOUSING
Sleeve Sleeve
4", 6" 17" 20"
8" 19" 22"
Types of Heat Activated Closure
12" 23" 26" Mechanisms:
Note: The length of the sleeve should not extend The standard damper blade closing mechanism
provides for a gradual (non-slamming) blade clo-
over 6" beyond the wall, except on the actuator
sure. Upon activation of the factory mounted heat
side, where the sleeve may extend to a maximum
response device, the actuator return spring closes
16" beyond the wall.
the damper at a gradual speed. The heat response
device is either a bi-metallic thermal disc when an
GENERAL NOTES electric actuator is provided or a three way fuse link
1. Underwriters Laboratories Inc. approved for dual activated air valve (P.E.R.V.) when a pneumatic
direction air flow and dynamic applications. actuator is supplied. Standard temperature rating of
the heat response device is 165ºF (212ºF optional).
2. Normally, actuators will be mounted externally on
the right side of the sleeve as viewed from the When the optional Sens-O-Therm reopenable fea-
jackshaft side of the damper. Certain actuators may ture is specified, a "low temperature" 165ºF (std.) or
be mounted on the left side, if specified on the order. 212ºF (opt.) bi-metallic thermal disc is employed
with either an electric or pneumatic actuator. Upon
3. Underwriters Laboratories Inc. Classified for use in
activation of this heat response device, the actuator's
fire resistance ratings of less than 3 hours, in
return spring closes the damper at a gradual rate.
accordance with UL Standard 555.
Upon closure, the position indication switch pack-
4. Underwriters Laboratories Inc. Classified smoke age will indicate "closed" to the control center or
damper for use in smoke control systems designed panel (field supplied). The Fire Commander will
for Leakage Class I, and Temperature Class 250°F have the option to remotely re-open the damper for
or 350°F in accordance with UL Standard 555S. smoke control purposes. NFPA and UL require that
the re-opened damper automatically re-close if duct
5. Installation must comply with the requirements of temperatures exceed the damper's "high-tempera-
NFPA-90A & -92A. Actuators must be arranged to ture" thermal disc rating (250º or 350ºF). Upon re-
operate automatically, must fail-close upon loss of closing, the damper cannot be remotely re-opened
power, and must be controlled by a smoke detec- and must remain closed to protect the integrity of
tion system. the fire barrier.
ARROW UNITED INDUSTRIES SUBMITTAL DATA
Actuators:
A variety of electric or pneumatic actuators are available. When required, optional internal (based on minimum size
In all cases, the selected actuator must be factory restrictions) or left hand external actuator locations are
mounted. Standard mounting location is on the outside available. All actuators are set up for Power-Open/Spring
of the damper sleeve (external) and on the right hand Return (Fail Closed) operation. Actuator must be externally
side (viewed from the jackshaft face). mounted when stainless steel construction.
Underwriters Laboratories requires that all UL rated dampers be accompanied with their matching UL-approved factory-
mounted actuators. The factors for proper actuator selection are actuator type (electric or pneumatic), voltage require-
ment, temperature rating, and damper size. ABI must factory install actuators for all combination fire/smoke dampers.

ELECTRIC (For Internal or External Mount Unless Noted)


Maximum Single Panel Size Minimum Size
HONEYWELL Voltage @250ºF @350ºF For Internal Mount
ML4202/4302 120VAC 1 sq. ft.
1 sq. ft.
ML8202/8302 24VAC (External Mount Only) 12" x 12"
(Sens-O-Therm N/A)
ML4115 120VAC 24" x 24"
24" x 24"
ML8115 24VAC (External Mount Only) 12" x 12"
(Sens-O-Therm N/A)
MS4209/4309 120VAC 36" x 36" or 48" x 24" 24" x 24" 12" x 12"
MS8209/8309 24VAC
36" x 48" or 48" x 36"
MS4120 120VAC
(Up to 36" x 36" rated to 36" x 48" 12" x 20"
MS8120 24VAC
3000 fpm, 4 in. wg.)

SIEMENS
GGD221 120VAC
GGD121 24VAC 36" x 48" N/A 12" x 20"
GGD321 230VAC

BELIMO
FSNF120 120VAC
36" x 36" or 48" x 24" 36" x 36" 12" x 20"
FSNF24 24VAC

PNEUMATIC (For Internal or External Mount Unless Noted)


Maximum Single Panel Size Minimum Size
SIEMENS @250ºF @350ºF For Internal Mount
24" x 12"@20psi
331-4830 24" x 24" @ 25 psi 12" x 12"
(Ext Mt Only)
24" x 24" @ 25 psi
331-2977 36" x 36" @ 20 psi 12" x 20"
(Sens-O-Therm N/A)
36" x 48" @ 22 psi 36" x 48" @ 22 psi
331-2996 16" x 24"
(Sens-O-Therm N/A) (Sens-O-Therm N/A)

* Consult Factory for Multiple Panel Applications


AMP DRAW
ML4202/4302(120VAC) Running: .18 Holding: .11
NOTE: When the optional "Sens-O-Therm" ML8202/8302 (24VAC) Running: .70 Holding: .35
Thermally Reopenable Temperature Sensing ML4115 (120VAC) Running: .18 Holding: .11
System is supplied, the pneumatic actuator's air ML8115 (24 VAC) Running: .70 Holding: .35
supply is controlled by a factory-supplied 120VAC MS4209/4309 (120VAC) Running: .25 Holding: .13
(Std.) Electric/Pneumatic Valve. Optional valves MS8209/8309 (24VAC) Running: 1.0 Holding: .13
are available for 120VDC, 24VAC, 24VDC, or MS4120 (120VAC) Running: .35 Holding: .15
12VDC. Contact Customer Service for pricing and MS8120 (24VAC) Running: 1.8 Holding: .42
availability. GGD121 (24VAC) Running: 6.25 Holding: .42
GGD221 (120VAC) Running: 1.3 Holding: .10
GGD321 (230VAC) Running: .65 Holding: .04
FSNF120 (120VAC) Running: .23 Holding: .09
FSNF24 (24VAC) Running: .23 Holding: .09
ARROW UNITED INDUSTRIES SUBMITTAL DATA

PERFORMANCE LEAKAGE
MAXIMUM DIFFERENTIAL Definition: UL 555S Class I:
PRESSURE: 4 in. wg Leakage Not Greater Than:
MAXIMUM VELOCITY: 4 CFM per sq. ft. @ 1 in. wg
2000/3000 FPM Based on Actuator Model 8 CFM per sq. ft @ 4 in. wg

FULL OPEN PRESSURE DROP DATA


Differential pressure across a damper is the loss of The pressure drop data shown below is based
systems pressure to move air at a particular velocity on actual tests conducted per AMCA Standard
from one side to the other side of the damper. This 500-D, Test Device Setup Figure 5.3. This test
loss in pressure is a result of two factors: the turbu- setup is the standard test method used to
lence created as the air passes over and around the compare damper pressure drop performance.
damper components and more significantly the This setup does not take into account elbows or
reduction in free area resulting from the frame, other duct fittings that are part of every actual
blades, etc. being in the air stream. duct system. The configuration of the actual
duct system immediately upstream and down-
stream of the damper often contributes more
pressure loss than the damper itself.

PRESSURE DROP: TYPICAL PERFORMANCE CURVE


1.0

24 x 24
Pressure Drop (in. wg.)

36 x 36

TESTED PER AMCA


0.1 STANDARD 500-D
FIGURE 5.3: (IN-DUCT MOUNT)
(SMALLER SIZES WILL HAVE
HIGHER PRESSURE DROPS)

0.01
500 1000 2000
FACE VELOCITY IN FEET PER MINUTE
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853 IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUS-
Ph: (570) 746-1888 Fax: (570) 746-9286 TRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
www.arrowunited.com
MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA SD-AS2-04.11

MODEL AS2 UNDERWRITERS LABORATORIES INC.®


CLASSIFIED FIRE DAMPER
LEAKAGE AND TEMPERATURE RATED FIRE RESISTANCE RATING 11/2 HR
COMBINATION FIRE/SMOKE DAMPER . ALSO AS TO LEAKAGE RESISTANCE
CLASS II
arrow united
FILE #R4708
LEAKAGE CLASS II • DYNAMICALLY CLASSIFIED industries
TEMPERATURE CLASS 250°F OR 350° This combination fire/smoke damper meets the construction
and performance requirements of:

STANDARD MATERIALS AND CONSTRUCTION • Underwriters Laboratories Inc. Standards 555 and 555S
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel. • National FIre Protection Association Standards 90A, 92A,
BLADES: 16-GA Galvanized steel, 6" nominal width, parallel action. and 92B
AXLES: Plated solid steel stub. • ICC's International Building Code
BEARINGS: Oil Impregnated Bronze. • ICBO's Uniform Building Code
LINKAGE: Plated steel angle and crank plates with stainless steel • SBCCI's Standard Building Code
pivots; in-jamb type. • BOCA's National Building Code
STOPS: 18-GA galvanized steel at head and sill. • New York City MEA Listing #111-99-M
BLADE EDGE • California State Fire Marshall Listing #3225-1328:113, 114
SEALS: Silicone.
SIDE JAMB
SEALS: Stainless steel. DIMENSIONAL DATA See note 1
SLEEVE: Minimum 20-GA galvanized steel by 20" long is standard on RECTANGULAR DAMPERS
sizes over 24"W x 12"H. A 20-GA by 17" long integral sleeve Minimum Size: 8"W x 8"H
is standard on sizes 24"W x 12"H and smaller.
NOTE: Dampers can be furnished with a duct size minimum of
CAULKING: Hardcast Irongrip 601, or UL-listed equivalent.
4"W x 4"H using a type B or C enclosure in a factory furnished
FINISH: Mill on galvanized steel.
sleeve. The overall frame is 8"W x 8"H.
ACTUATOR: ELECTRIC, with 165°F thermal disc; or PNEUMATIC, with
165°F fusible link and P.E.R.V. Factory-installed for Maximum Size: Vertical Horizontal
Power-Open/Spring-Return (Fail Close) operation. GALVANIZED STEEL CONSTRUCTION
Single Panel: 36"W x 48"H 36"W x 48"H
THIS DIMENSION or 48"W x 36"H
WILL INCREASE IF Multiple Panel: 108"W x 48"H 72"W x 48"H
SLEEVE LENGTH
IS INCREASED
STAINLESS STEEL CONSTRUCTION (250º only)
THIS DIMENSION Single Panel: 32"W x 32"H 24"W x 24"H
20" (STD) Multiple Panel: N/A N/A
WILL INCREASE IF
SLEEVE LENGTH 10½" 5½" 4"
IS INCREASED ROUND AND OVAL DAMPERS
(Type C Housing, Duct Dimensions)
10" 7" Frame Width = Duct Width + 2"
OPERATOR Frame Height = Duct Height + 2"
Minimum Size: 6" Diameter
GALVANIZED STEEL CONSTRUCTION
Maximum Size: Vertical Horizontal
Single Panel Single Panel
Round: 34" Diameter 34" Diameter
Oval: 34"W x 46"H 34"W x 46"H
or 46"W x 34"H
Double Panel Double Panel
INTEGRAL
Round: 46" Diameter 46" Diameter
HEAT SENSITIVE
DEVICE SLEEVE Oval: 70"W x 46"H 70"W x 46"H
or 94"W x 34"H
STAINLESS STEEL CONSTRUCTION (250º only)
NOTES: (Single Panel Only)
1. Units up to 24"W x 12"H will have a 20-GA by Round: 30" Diameter 22" Diameter
17" long integral sleeve as standard with a Oval: 30"W x 30"H 22"W x 22"H
single blade.
2. Dampers will be fabricated 1/4" undersize PROJECT:
(1/2" width undersizing when two panels wide). LOCATION:
3. Approved for vertical and horizontal installation. ARCHITECT:
4. Stainless steel construction not available in ENGINEER:
integral sleeve design. CONTRACTOR:
PO NUMBER:
Arrow United Industries
A Division of Mestek, Inc. DATE:
314 Riverside Drive . Wyalusing, PA 18853
Additional Information
Ph: (570) 746-1888 Fax: (570) 746-9286
on reverse side
ARROW UNITED INDUSTRIES SUBMITTAL DATA
AVAILABLE OPTIONS: (Must Be Specified)
1. 304 S.S. & 316 S.S. construction. (Sleeve and 16" (Std.)
airstream parts only.) Actuator must be externally
mounted. Round or Oval duct
requires type "C" B+2
2. Sleeve thicknesses heavier than the standard 20- transition
GA and longer than the standard 20" length (17" on
integral sleeve.)
3. Type C Housing for round and oval ductwork. A+2
4. 212ºF thermal disc (electric models) or fusible link
(pneumatic models.)
16" (Std.)
5. "Sens-O-Therm" Thermally Reopenable Tempera-
ture Sensing System is available with 165ºF (Stan- < 6" high rectangular
dard) or 212ºF settings. This system includes duct requires type
"B" transition B (4" min.)
contacts for connection to open and closed posi-
tion indicator lamps. It also includes a second
thermal disc to re-close the damper when the rated A (8" min.)
degradation temperature is reached.
6. Dual position indication package. These optional
auxiliary blade position indication switches are 16" (Std.)
intended to make or break a circuit and will not
provide variable or proportional resistance. < 8" high rectangular
duct requires type
7. Smoke detetctor (minimum 20" sleeve required, "C" transition B (4" min.)
damper height must be 10" minimum.)

Wall Recommended Sleeve Length A (4" min.)


Thickness W/Integral W/Non-Integral TYPE "C" HOUSING
Sleeve Sleeve
4", 6" 17" 20" Types of Heat Activated Closure
8" 19" 22" Mechanisms:
12" 23" 26"
The standard damper blade closing mechanism
Note: The length of the sleeve should not extend provides for a gradual (non-slamming) blade clo-
over 6" beyond the wall, except on the actuator sure. Upon activation of the factory mounted heat
side, where the sleeve may extend to a maximum response device, the actuator return spring closes
16" beyond the wall. the damper at a gradual speed. The heat response
device is either a bi-metallic thermal disc when an
GENERAL NOTES electric actuator is provided or a three way fuse link
1. Underwriters Laboratories Inc. approved for dual activated air valve (P.E.R.V.) when a pneumatic
direction air flow and dynamic applications. actuator is supplied. Standard temperature rating of
the heat response device is 165ºF (212ºF optional).
2. Normally, actuators will be mounted externally on
the right side of the sleeve as viewed from the When the optional Sens-O-Therm reopenable fea-
jackshaft side of the damper. Certain actuators may ture is specified, a "low temperature" 165ºF (std.) or
be mounted on the left side, if specified on the order. 212ºF (opt.) bi-metallic thermal disc is employed
with either an electric or pneumatic actuator. Upon
3. Underwriters Laboratories Inc. Classified for use in
activation of this heat response device, the actuator's
fire resistance ratings of less than 3 hours, in
return spring closes the damper at a gradual rate.
accordance with UL Standard 555.
Upon closure, the position indication switch pack-
4. Underwriters Laboratories Inc. Classified smoke age will indicate "closed" to the control center or
damper for use in smoke control systems designed panel (field supplied). The Fire Commander will
for Leakage Class II, and Temperature Class 250°F have the option to remotely re-open the damper for
or 350°F in accordance with UL Standard 555S. smoke control purposes. NFPA and UL require that
the re-opened damper automatically re-close if duct
5. Installation must comply with the requirements of temperatures exceed the damper's "high-tempera-
NFPA-90A & -92A. Actuators must be arranged to ture" thermal disc rating (250º or 350ºF). Upon re-
operate automatically, must fail-close upon loss of closing, the damper cannot be remotely re-opened
power, and must be controlled by a smoke detec- and must remain closed to protect the integrity of
tion system. the fire barrier.
ARROW UNITED INDUSTRIES SUBMITTAL DATA
Actuators:
A variety of electric or pneumatic actuators are available. When required, optional internal (based on minimum size
In all cases, the selected actuator must be factory restrictions) or left hand external actuator locations are
mounted. Standard mounting location is on the outside available. All actuators are set up for Power-Open/Spring
of the damper sleeve (external) and on the right hand Return (Fail Closed) operation. Actuator must be externally
side (viewed from the jackshaft face). mounted when stainless steel construction.
Underwriters Laboratories requires that all UL rated dampers be accompanied with their matching UL-approved factory-
mounted actuators. The factors for proper actuator selection are actuator type (electric or pneumatic), voltage require-
ment, temperature rating, and damper size. ARROW must factory install actuators for all combination fire/smoke
dampers.
ELECTRIC (For Internal or External Mount Unless Noted)
Maximum Single Panel Size Minimum Size
HONEYWELL Voltage @250ºF @350ºF For Internal Mount
ML4202/4302 120VAC 1 sq. ft.
ML8202/8302 24VAC 1 sq. ft. (External Mount Only) 12" x 12"
(Sens-O-Therm N/A)
ML4115 120VAC 4 sq. ft. 24" x 24"
ML8115 24VAC Width/Height not to (External Mount Only) 12" x 12"
exceed 36" (Sens-O-Therm N/A)
MS4209/4309 120VAC 36" x 36" or 48" x 24"
MS8209/8309 24VAC (Up to 24" x 24" rated to 48" x 24" 12" x 12"
3000 fpm, 4 in. wg.)
36" x 48" or 48" x 36"
MS4120 120VAC
(Up to 36" x 36" rated to 36" x 48" 12" x 20"
MS8120 24VAC
3000 fpm, 4 in. wg.)
SIEMENS
GGD221 120VAC
GGD121 24VAC 36" x 48" N/A 12" x 20"
GGD321 230VAC

BELIMO
FSNF120 120VAC
36" x 36" or 48" x 24" 36" x 36" 12" x 20"
FSNF24 24VAC

PNEUMATIC (For Internal or External Mount Unless Noted)


Maximum Single Panel Size Minimum Size
SIEMENS @250ºF @350ºF For Internal Mount
24" x 12"@20psi
331-4830 24" x 24" @ 25 psi 12" x 12"
(Ext Mt Only)
24" x 24" @ 25 psi
331-2977 36" x 36" @ 20 psi 12" x 20"
(Sens-O-Therm N/A)
36" x 48" @ 22 psi 36" x 48" @ 22 psi
331-2996 16" x 24"
(Sens-O-Therm N/A) (Sens-O-Therm N/A)

* Consult Factory for Multiple Panel Applications


AMP DRAW
ML4202/4302(120VAC) Running: .18 Holding: .11
ML8202/8302 (24VAC) Running: .70 Holding: .35
NOTE: When the optional "Sens-O-Therm" ML4115 (120VAC) Running: .18 Holding: .11
Thermally Reopenable Temperature Sensing ML8115 (24 VAC) Running: .70 Holding: .35
System is supplied, the pneumatic actuator's air MS4209/4309 (120VAC) Running: .25 Holding: .13
supply is controlled by a factory-supplied 120VAC MS8209/8309 (24VAC) Running: 1.0 Holding: .13
(Std.) Electric/Pneumatic Valve. Optional valves MS4120 (120VAC) Running: .35 Holding: .15
are available for 120VDC, 24VAC, 24VDC, or
MS8120 (24VAC) Running: 1.8 Holding: .42
12VDC. Contact Customer Service for pricing and
GGD121 (24VAC) Running: 6.25 Holding: .42
availability.
GGD221 (120VAC) Running: 1.3 Holding: .10
GGD321 (230VAC) Running: .65 Holding: .04
FSNF120 (120VAC) Running: .23 Holding: .09
FSNF24 (24VAC) Running: .23 Holding: .09
ARROW UNITED INDUSTRIES SUBMITTAL DATA

PERFORMANCE LEAKAGE
MAXIMUM DIFFERENTIAL Definition: UL 555S Class II:
PRESSURE: 4 in. wg Leakage Not Greater Than:
MAXIMUM VELOCITY: 10 CFM per sq. ft. @ 1 in. wg
2000/3000 FPM Based on Actuator Model 20 CFM per sq. ft @ 4 in. wg

FULL OPEN PRESSURE DROP DATA


The pressure drop data shown below is based
Differential pressure across a damper is the loss of
on actual tests conducted per AMCA Standard
systems pressure to move air at a particular velocity
500-D, Test Device Setup Figure 5.3. This test
from one side to the other side of the damper. This
setup is the standard test method used to
loss in pressure is a result of two factors: the turbu-
compare damper pressure drop performance.
lence created as the air passes over and around the
This setup does not take into account elbows or
damper components and more significantly the
other duct fittings that are part of every actual
reduction in free area resulting from the frame,
duct system. The configuration of the actual
blades, etc. being in the air stream.
duct system immediately upstream and down-
stream of the damper often contribute more
pressure loss than the damper itself.

PRESSURE DROP: TYPICAL PERFORMANCE CURVE


1.0

24 x 24
Pressure Drop (in. wg.)

36 x 36

TESTED PER AMCA


0.1 STANDARD 500-D
FIGURE 5.3: (IN-DUCT MOUNT)
(SMALLER SIZES WILL HAVE
HIGHER PRESSURE DROPS)

0.01
500 1000 2000
FACE VELOCITY IN FEET PER MINUTE

IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-AT1-04.11

MODEL AT1 • 3 HR. RATED UNDERWRITERS LABORATORIES INC.®


CLASSIFIED FIRE DAMPER
LEAKAGE AND TEMPERATURE RATED FIRE RESISTANCE RATING 3 HR
COMBINATION FIRE/SMOKE DAMPER ALSO AS TO LEAKAGE RESISTANCE
CLASS I
Arrow United Industries
LEAKAGE CLASS I • DYNAMICALLY CLASSIFIED
TEMPERATURE CLASS 250°F OR 350°F
This combination fire/smoke damper meets the construction
and performance requirements of:

• Underwriters Laboratories Inc. Stds. 555 & 555S


• NFPA Stds. 90A, 92A, & 92B
STANDARD MATERIALS AND CONSTRUCTION • ICC's International Building Code
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel. • ICBO's Uniform Building Code
BLADES: 16-GA Galvanized steel, 6" nominal width, parallel action. • SBCCI's Standard Building Code
AXLES: Plated solid steel stub. • BOCA's National Building Code
BEARINGS: Oil Impregnated Bronze. • New York City MEA Listing #111-99-M
LINKAGE: Plated steel angle and crank plates with stainless steel • California State Fire Marshall Listing #3225-1328:113,114
pivots, in-jamb type.
STOPS: 18-GA galvanized steel at head and sill. DIMENSIONAL DATA See notes 1 & 2
BLADE EDGE RECTANGULAR DAMPERS
SEALS: Silicone material.
Minimum Size: 16"W x 8"H (See note #1)
SIDE JAMB
SEALS: Stainless steel. NOTE: Dampers can be furnished with a duct size
SLEEVE: Minimum 20-GA galvanized steel by 20" long is standard. minimum of 16"W x 6"H using a type B enclosure
18-GA for sizes over 84" wide. in a factory furnished sleeve. The overall frame is
CAULKING: Hardcast Irongrip 601, or UL-listed equivalent. 16"W x 8"H.
FINISH: Mill on galvanized steel.
ACTUATOR: ELECTRIC, with 165°F thermal disc; or PNEUMATIC, with Maximum Size: Vertical Horizontal
165°F fusible link and P.E.R.V. Factory-installed for Single Panel: 36"W x 48"H or 30"W x 48"H or
Power-Open/Spring-Return (Fail Close) operation.
42"W x 36"H 36"W x 30"H
Multi Panel: 108"W x 48"H 60"W x 48"H

THIS DIMENSION WILL ROUND AND OVAL DAMPERS


INCREASE IF SLEEVE
LENGTH IS INCREASED
(Type C Housing, Duct Dimensions)
20" (STD) Frame Width = Duct Width + 2"
Frame Height = Duct Height + 2"
10½" 5½" 4"

Minimum Size:
Round: 14" Diameter
Oval: 14"W x 6"H

Maximum Size: Vertical Horizontal


Single Panel Single Panel
Round: 34" Diameter 28" Diameter
Oval: 34"W x 46"H 34"W x 28"H
Multi Panel Multi Panel
Oval: 106"W x 46"H 58"W x 46"H

NOTES:
1. Units that are less than 16"W are Leakage Class II. PROJECT:
2. Dampers will be fabricated 1/4" undersize (1/2" width LOCATION:
undersizing when two panels wide). ARCHITECT:
3. Approved for vertical and horizontal installation. ENGINEER:
4. Optional auxiliary blade position indication switches CONTRACTOR:
are rated at 11A, 1/3HP, 125VAC. These snap action PO NUMBER:
switches are intended to make or break a circuit and DATE:
will not provide variable or proportional resistance.
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Additional Information
Ph: (570) 746-1888 Fax: (570) 746-9286
MEMBER OF AMCA
on reverse side
www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA A=Nominal Duct Width
B=Nominal Duct Height

AVAILABLE OPTIONS: (Must Be Specified)


1. Sleeve thicknesses heavier than the standard 20-
GA and longer than the standard 20" length. 20" STANDARD
FOR
2. Type C Housing for round and oval ductwork. MULTI-BLADE
3. 212ºF thermal disc (electric models) or fusible link
(pneumatic models.)

4. "Sens-O-Therm" Thermally Reopenable Tempera-


ture Sensing System is available with 165ºF (Stan-
dard) or 212ºF settings. This system includes OPERATOR
contacts for connection to open and closed posi-
tion indicator lamps. It also includes a second
"B" + 2"
thermal disc to re-close the damper when the
rated degradation temperature is reached.

5. Dual position indication package. These optional


auxiliary blade position indication switches are
intended to make or break a circuit and will not
provide variable or proportional resistance.

6. Smoke detector (minimum 20" sleeve required,


damper height must be 10" minimum.) "A" + 2"

Wall Recommended Sleeve Length


Thickness W/Integral W/Non-Integral TYPE "C" HOUSING
Sleeve Sleeve
4", 6" 17" 20"
8" 19" 22"
Types of Heat Activated Closure
12" 23" 26" Mechanisms:
Note: The length of the sleeve should not extend The standard damper blade closing mechanism
provides for a gradual (non-slamming) blade clo-
over 6" beyond the wall, except on the actuator
sure. Upon activation of the factory mounted heat
side, where the sleeve may extend to a maximum
response device, the actuator return spring closes
16" beyond the wall.
the damper at a gradual speed. The heat response
device is either a bi-metallic thermal disc when an
GENERAL NOTES electric actuator is provided or a three way fuse link
1. Underwriters Laboratories Inc. approved for dual activated air valve (P.E.R.V.) when a pneumatic
direction air flow and dynamic applications. actuator is supplied. Standard temperature rating of
the heat response device is 165ºF (212ºF optional).
2. Normally, actuators will be mounted externally on
the right side of the sleeve as viewed from the When the optional Sens-O-Therm reopenable fea-
jackshaft side of the damper. Certain actuators may ture is specified, a "low temperature" 165ºF (std.) or
be mounted on the left side, if specified on the order. 212ºF (opt.) bi-metallic thermal disc is employed
with either an electric or pneumatic actuator. Upon
3. Underwriters Laboratories Inc. Classified for use in
activation of this heat response device, the actuator's
fire resistance ratings 3 hours and longer, in accor-
return spring closes the damper at a gradual rate.
dance with UL Standard 555.
Upon closure, the position indication switch pack-
4. Underwriters Laboratories Inc. Classified smoke age will indicate "closed" to the control center or
damper for use in smoke control systems designed panel (field supplied). The Fire Commander will
for Leakage Class II, and Temperature Class 250°F have the option to remotely re-open the damper for
or 350°F in accordance with UL Standard 555S. smoke control purposes. NFPA and UL require that
the re-opened damper automatically re-close if duct
5. Installation must comply with the requirements of temperatures exceed the damper's "high-tempera-
NFPA-90A & -92A. Actuators must be arranged to ture" thermal disc rating (250º or 350ºF). Upon re-
operate automatically, must fail-close upon loss of closing, the damper cannot be remotely re-opened
power, and must be controlled by a smoke detec- and must remain closed to protect the integrity of
tion system. the fire barrier.
ARROW UNITED INDUSTRIES SUBMITTAL DATA
Actuators:
A variety of electric or pneumatic actuators are available. When required, optional internal (based on minimum size
In all cases, the selected actuator must be factory restrictions) or left hand external actuator locations are
mounted. Standard mounting location is on the outside available. All actuators are set up for Power-Open/Spring
of the damper sleeve (external) and on the right hand Return (Fail Closed) operation.
side (viewed from the jackshaft face).
Underwriters Laboratories requires that all UL rated dampers be accompanied with their matching UL-approved factory-
mounted actuators. The factors for proper actuator selection are actuator type (electric or pneumatic), voltage require-
ment, temperature rating, and damper size. ARROW must factory install actuators for all combination fire/smoke
dampers.
ELECTRIC (For Internal or External Mount Unless Noted)
Maximum Single Panel Size Minimum Size
HONEYWELL Voltage @250ºF @350ºF For Internal Mount
1 sq. ft.
ML4202/4302 120VAC 1 sq. ft. (External Mount Only) 12" x 12"
ML8202/8302 24VAC (Sens-O-Therm N/A)
ML4115 120VAC 4 sq. ft. 24" x 24"
ML8115 24VAC Width/Height not to (External Mount Only) 12" x 12"
exceed 36" (Sens-O-Therm N/A)

MS4209/4309 120VAC
36" x 36" or 42" x 24" 42" x 24" 12" x 12"
MS8209/8309 24VAC

36" x 48" or 42" x 36"


MS4120 120VAC
(Up to 36" x 36" rated to 36" x 48" 12" x 20"
MS8120 24VAC
3000 fpm, 4 in. wg.)
SIEMENS
GGD221 120VAC
GGD121 24VAC 36" x 48" N/A 12" x 20"
GGD321 230VAC

BELIMO
FSNF120 120VAC
36" x 36" or 42" x 24" 36" x 36" 12" x 20"
FSNF24 24VAC

PNEUMATIC (For Internal or External Mount Unless Noted)


Maximum Single Panel Size Minimum Size
SIEMENS @250ºF @350ºF For Internal Mount
331-4830 24" x 24" @ 25 psi N/A 12" x 12"

24" x 24" @ 25 psi


331-2977 36" x 36" @ 20 psi 12" x 20"
(Sens-O-Therm N/A)
36" x 48" @ 22 psi 36" x 48" @ 22 psi
331-2996 16" x 24"
(Sens-O-Therm N/A) (Sens-O-Therm N/A)

* Consult Factory for Multiple Panel Applications


AMP DRAW
ML4202/4302(120VAC) Running: .18 Holding: .11
ML8202/8302 (24VAC) Running: .70 Holding: .35
NOTE: When the optional "Sens-O-Therm" ML4115 (120VAC) Running: .18 Holding: .11
Thermally Reopenable Temperature Sensing ML8115 (24 VAC) Running: .70 Holding: .35
System is supplied, the pneumatic actuator's air MS4209/4309 (120VAC) Running: .25 Holding: .13
supply is controlled by a factory-supplied 120VAC MS8209/8309 (24VAC) Running: 1.0 Holding: .13
(Std.) Electric/Pneumatic Valve. Optional valves MS4120 (120VAC) Running: .35 Holding: .15
are available for 120VDC, 24VAC, 24VDC, or
MS8120 (24VAC) Running: 1.8 Holding: .42
12VDC. Contact Customer Service for pricing and
GGD121 (24VAC) Running: 6.25 Holding: .42
availability.
GGD221 (120VAC) Running: 1.3 Holding: .10
GGD321 (230VAC) Running: .65 Holding: .04
FSNF120 (120VAC) Running: .23 Holding: .09
FSNF24 (24VAC) Running: .23 Holding: .09
ARROW UNITED INDUSTRIES SUBMITTAL DATA

PERFORMANCE LEAKAGE
MAXIMUM DIFFERENTIAL Definition: UL 555S Class I:
PRESSURE: 4 in. wg Leakage Not Greater Than:
MAXIMUM VELOCITY: 4 CFM per sq. ft. @ 1 in. wg
2000/3000 FPM Based on Actuator Model 8 CFM per sq. ft @ 4 in. wg

FULL OPEN PRESSURE DROP DATA


The pressure drop data shown below is based
Differential pressure across a damper is the loss of
on actual tests conducted per AMCA Standard
systems pressure to move air at a particular velocity
500-D, Test Device Setup Figure 5.3. This test
from one side to the other side of the damper. This
setup is the standard test method used to
loss in pressure is a result of two factors: the turbu-
compare damper pressure drop performance.
lence created as the air passes over and around the
This setup does not take into account elbows or
damper components and more significantly the
other duct fittings that are part of every actual
reduction in free area resulting from the frame,
duct system. The configuration of the actual
blades, etc. being in the air stream.
duct system immediately upstream and down-
stream of the damper often contribute more
pressure loss than the damper itself.

PRESSURE DROP: TYPICAL PERFORMANCE CURVE


1.0

24 x 24
Pressure Drop (in. wg.)

36 x 36

TESTED PER AMCA


0.1 STANDARD 500-D
FIGURE 5.3: (IN-DUCT MOUNT)
(SMALLER SIZES WILL HAVE
HIGHER PRESSURE DROPS)

0.01
500 1000 2000
FACE VELOCITY IN FEET PER MINUTE
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 MEMBER OF AMCA
www.arrowunited.com

IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES RESERVES THE LEFT TO MAKE CHANGES WITHOUT NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-AT2-04.11

MODEL AT2 • 3 HR. RATED UNDERWRITERS LABORATORIES INC.®


CLASSIFIED FIRE DAMPER
FIRE RESISTANCE RATING 3 HR
LEAKAGE AND TEMPERATURE RATED ALSO AS TO LEAKAGE RESISTANCE

COMBINATION FIRE/SMOKE DAMPER CLASS II


Arrow United Industries

LEAKAGE CLASS II • DYNAMICALLY CLASSIFIED


TEMPERATURE CLASS 250°F OR 350°F This combination fire/smoke damper meets the construction
and performance requirements of:

• Underwriters Laboratories Inc. Stds 555 and 555S


• National Fire Protection Association Stds 90A, 92A, and 92B
STANDARD MATERIALS AND CONSTRUCTION • ICC's International Building Code
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel. • ICBO's Uniform Building Code
BLADES: 16-GA Galvanized steel, 6" nominal width, parallel action. • SBCCI's Standard Building Code
AXLES: Plated solid steel stub. • BOCA's National Building Code
BEARINGS: Oil Impregnated Bronze. • New York City MEA Listing #111-99-M
LINKAGE: Plated steel angle and crank plates with stainless steel • California State Fire Marshall Listing #3225-1328:113, 114
pivots, in-jamb type.
STOPS: 18-GA galvanized steel at head and sill.
BLADE EDGE
SEALS: Silicone material.
SIDE JAMB
SEALS: Stainless steel.
SLEEVE: Minimum 20-GA galvanized steel by 20" long is standard. DIMENSIONAL DATA See note 1
18-GA for sizes over 84" wide. RECTANGULAR DAMPERS
CAULKING: Hardcast Irongrip 601, or UL-listed equivalent.
FINISH: Mill on galvanized steel. Minimum Size: 8"W x 8"H
ACTUATOR: ELECTRIC, with 165°F thermal disc; or PNEUMATIC, with Dampers can be furnished with a duct size mini-
165°F fusible link and P.E.R.V. Factory-installed for mum of 4"W x 4"H using a type B enclosure pan or
Power-Open/Spring-Return (Fail Close) operation.
transitions in a factory furnished sleeve. The over-
all frame is 8"W x 8"H.
This dimension will Maximum Size: Vertical Horizontal
change when sleeve
length is increased.
Single Panel: 36"W x 48"H or30"W x 48"H or
42"W x 36"H 36"W x 30"H
20" (STD)
Multi Panel: 108"W x 48"H 60"W x 48"H
10½" 5½" 4"

ROUND AND OVAL DAMPERS


(Type C Housing, Duct Dimensions)
Frame Width = Duct Width + 2"
Frame Height = Duct Height + 2"
Minimum Size:
Round: 6" Diameter
Maximum Size: Vertical Horizontal
Single Panel Single Panel
Round: 34" Diameter 28" Diameter
Oval: 34"W x 46"H 34"W x 28"H or
28"W x 36"H
Multi Panel Multi Panel
Oval: 106"W x 46"H 58"W x 46"H

NOTES:
1. Dampers will be fabricated ¼" undersize (½" width PROJECT: __________________________
undersizing when 2 panels wide.) LOCATION: _________________________
2. Approved for vertical and horizontal installation.
ARCHITECT: ________________________
3. Optional auxiliary blade position indication switches
ENGINEER: __________________________
are rated at 11A, 1/3HP, 125VAC. These snap action
switches are intended to make or break a circuit and CONTRACTOR: ______________________
will not provide variable or proportional resistance. PO NUMBER: ________________________
DATE: ______________________________
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 Additional Information
www.arrowunited.com on reverse side
MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA
A=Nominal Duct Width
B=Nominal Duct Height
AVAILABLE OPTIONS: (Must Be Specified) 20" STANDARD
1. Sleeve thicknesses heavier than the standard 20- FOR
GA and longer than the standard 20" length. MULTI-BLADE

2. Type C Housing for round and oval ductwork.

3. 212ºF thermal disc (electric models) or fusible link


(pneumatic models.)

4. "Sens-O-Therm" Thermally Reopenable Tempera-


ture Sensing System is available with 165ºF (Stan- OPERATOR
dard) or 212ºF settings. This system includes
contacts for connection to open and closed posi-
tion indicator lamps. It also includes a second
"B" + 2"
thermal disc to re-close the damper when the
rated degradation temperature is reached.

5. Dual position indication package. These optional


auxiliary blade position indication switches are
intended to make or break a circuit and will not
provide variable or proportional resistance.

6. Smoke detector (minimum 20" sleeve required,


damper height must be 10" minimum.)
"A" + 2"

Wall Recommended Sleeve Length


Thickness W/Integral W/Non-Integral TYPE "C" HOUSING
Sleeve Sleeve
4", 6" 17" 20"
8" 19" 22"
Types of Heat Activated Closure
12" 23" 26" Mechanisms:
Note: The length of the sleeve should not extend The standard damper blade closing mechanism
provides for a gradual (non-slamming) blade clo-
over 6" beyond the wall, except on the actuator
sure. Upon activation of the factory mounted heat
side, where the sleeve may extend to a maximum
response device, the actuator return spring closes
16" beyond the wall.
the damper at a gradual speed. The heat response
device is either a bi-metallic thermal disc when an
GENERAL NOTES electric actuator is provided or a three way fuse link
1. Underwriters Laboratories Inc. approved for dual activated air valve (P.E.R.V.) when a pneumatic
direction air flow and dynamic applications. actuator is supplied. Standard temperature rating of
the heat response device is 165ºF (212ºF optional).
2. Normally, actuators will be mounted externally on
the right side of the sleeve as viewed from the When the optional Sens-O-Therm reopenable fea-
jackshaft side of the damper. Certain actuators may ture is specified, a "low temperature" 165ºF (std.) or
be mounted on the left side, if specified on the order. 212ºF (opt.) bi-metallic thermal disc is employed
with either an electric or pneumatic actuator. Upon
3. Underwriters Laboratories Inc. Classified for use in
activation of this heat response device, the actuator's
fire resistance ratings 3 hours and longer, in accor-
return spring closes the damper at a gradual rate.
dance with UL Standard 555.
Upon closure, the position indication switch pack-
4. Underwriters Laboratories Inc. Classified smoke age will indicate "closed" to the control center or
damper for use in smoke control systems designed panel (field supplied). The Fire Commander will
for Leakage Class II, and Temperature Class 250°F have the option to remotely re-open the damper for
or 350°F in accordance with UL Standard 555S. smoke control purposes. NFPA and UL require that
the re-opened damper automatically re-close if duct
5. Installation must comply with the requirements of temperatures exceed the damper's "high-tempera-
NFPA-90A & -92A. Actuators must be arranged to ture" thermal disc rating (250º or 350ºF). Upon re-
operate automatically, must fail-close upon loss of closing, the damper cannot be remotely re-opened
power, and must be controlled by a smoke detec- and must remain closed to protect the integrity of
tion system. the fire barrier.
ARROW UNITED INDUSTRIES SUBMITTAL DATA
Actuators:
A variety of electric or pneumatic actuators are available. When required, optional internal (based on minimum size
In all cases, the selected actuator must be factory restrictions) or left hand external actuator locations are
mounted. Standard mounting location is on the outside available. All actuators are set up for Power-Open/Spring
of the damper sleeve (external) and on the right hand Return (Fail Closed) operation.
side (viewed from the jackshaft face).
Underwriters Laboratories requires that all UL rated dampers be accompanied with their matching UL-approved factory-
mounted actuators. The factors for proper actuator selection are actuator type (electric or pneumatic), voltage require-
ment, temperature rating, and damper size. ARROW must factory install actuators for all combination fire/smoke
dampers.
ELECTRIC (For Internal or External Mount Unless Noted)
Maximum Single Panel Size Minimum Size
HONEYWELL Voltage @250ºF @350ºF For Internal Mount
ML4202/4302 120VAC 1 sq. ft.
ML8202/8302 24VAC 1 sq. ft. (External Mount Only) 12" x 12"
(Sens-O-Therm N/A)
ML4115 120VAC 4 sq. ft. 24" x 24"
ML8115 24VAC Width/Height not to (External Mount Only) 12" x 12"
exceed 36" (Sens-O-Therm N/A)
MS4209/4309 120VAC 36" x 36" or 42" x 24"
MS8209/8309 24VAC (Up to 24" x 24" rated to 42" x 24" 12" x 12"
3000 fpm, 4 in. wg.)
36" x 48" or 42" x 36"
MS4120 120VAC
(Up to 36" x 36" rated to 36" x 48" 12" x 20"
MS8120 24VAC
3000 fpm, 4 in. wg.)
SIEMENS
GGD221 120VAC
GGD121 24VAC 36" x 48" N/A 12" x 20"
GGD321 230VAC

BELIMO
FSNF120 120VAC
36" x 36" or 42" x 24" 36" x 36" 12" x 20"
FSNF24 24VAC

PNEUMATIC (For Internal or External Mount Unless Noted)


Maximum Single Panel Size Minimum Size
SIEMENS @250ºF @350ºF For Internal Mount
331-4830 24" x 24" @ 25 psi N/A 12" x 12"

24" x 24" @ 25 psi


331-2977 36" x 36" @ 20 psi 12" x 20"
(Sens-O-Therm N/A)
36" x 48" @ 22 psi 36" x 48" @ 22 psi
331-2996 16" x 24"
(Sens-O-Therm N/A) (Sens-O-Therm N/A)

* Consult Factory for Multiple Panel Applications


AMP DRAW
ML4202/4302(120VAC) Running: .18 Holding: .11
ML8202/8302 (24VAC) Running: .70 Holding: .35
NOTE: When the optional "Sens-O-Therm" ML4115 (120VAC) Running: .18 Holding: .11
Thermally Reopenable Temperature Sensing ML8115 (24 VAC) Running: .70 Holding: .35
System is supplied, the pneumatic actuator's air MS4209/4309 (120VAC) Running: .25 Holding: .13
supply is controlled by a factory-supplied 120VAC MS8209/8309 (24VAC) Running: 1.0 Holding: .13
(Std.) Electric/Pneumatic Valve. Optional valves MS4120 (120VAC) Running: .35 Holding: .15
are available for 120VDC, 24VAC, 24VDC, or
MS8120 (24VAC) Running: 1.8 Holding: .42
12VDC. Contact Customer Service for pricing and
GGD121 (24VAC) Running: 6.25 Holding: .42
availability.
GGD221 (120VAC) Running: 1.3 Holding: .10
GGD321 (230VAC) Running: .65 Holding: .04
FSNF120 (120VAC) Running: .23 Holding: .09
FSNF24 (24VAC) Running: .23 Holding: .09
ARROW UNITED INDUSTRIES SUBMITTAL DATA

PERFORMANCE LEAKAGE
MAXIMUM DIFFERENTIAL Definition: UL 555S Class II:
PRESSURE: 4 in. wg Leakage Not Greater Than:
MAXIMUM VELOCITY: 10 CFM per sq. ft. @ 1 in. wg
2000/3000 FPM Based on Actuator Model 20 CFM per sq. ft @ 4 in. wg

FULL OPEN PRESSURE DROP DATA


The pressure drop data shown below is based
Differential pressure across a damper is the loss of
on actual tests conducted per AMCA Standard
systems pressure to move air at a particular velocity
500-D, Test Device Setup Figure 5.3. This test
from one side to the other side of the damper. This
setup is the standard test method used to
loss in pressure is a result of two factors: the turbu-
compare damper pressure drop performance.
lence created as the air passes over and around the
This setup does not take into account elbows or
damper components and more significantly the
other duct fittings that are part of every actual
reduction in free area resulting from the frame,
duct system. The configuration of the actual
blades, etc. being in the air stream.
duct system immediately upstream and down-
stream of the damper often contribute more
pressure loss than the damper itself.

PRESSURE DROP: TYPICAL PERFORMANCE CURVE


1.0

24 x 24
Pressure Drop (in. wg.)

36 x 36

TESTED PER AMCA


0.1 STANDARD 500-D
FIGURE 5.3: (IN-DUCT MOUNT)
(SMALLER SIZES WILL HAVE
HIGHER PRESSURE DROPS)

0.01
500 1000 2000
FACE VELOCITY IN FEET PER MINUTE
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA

IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-UA1-04.12

MODEL UA1 1-1/2 HR. RATED


UNDERWRITERS LABORATORIES INC.®
MODEL UA1 250 • MODEL UA1 350 Classified

FIRE DAMPERS
LEAKAGE AND TEMPERATURE RATED FIRE RESISTANCE RATING 11/2 Hr.
ALSO CLASSIFIED AS TO LEAKAGE RESISTANCE
COMBINATION FIRE/SMOKE DAMPER CLASS I-250°F
R-4708
LEAKAGE CLASS 1 • DYNAMICALLY CLASSIFIED
TEMPERATURE CLASS 250°F or 350°F UNDERWRITERS LABORATORIES INC.®
Classified

FIRE DAMPERS
FIRE RESISTANCE RATING 11/2 Hr.
STANDARD MATERIALS AND CONSTRUCTION ALSO CLASSIFIED AS TO LEAKAGE RESISTANCE
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel. CLASS I-350°F
R-4708
BLADES: 20-GA Double skinned Galvanized Steel. (Equal to 14-GA),
parallel action
SEALS: Silicone blade edge and stainless steel compression jamb. Recommended
Wall Sleeve
AXLES: Square plated steel.
Thickness Length
BEARINGS: Oil Impregnated Bronze.
4", 6" 20"
LINKAGE: Concealed In-Jamb, Plated Steel Tie Bar, Stainless Steel Pivots 8" 22"
STOPS: 18-GA Galvanized steel at head and sill 12" 26"
NOTE: The length of the sleeve should not extend
SLEEVE: Minimum 20-GA galvanized steel by 20" long is standard for
over 6" beyond the wall, except on the actuator side,
sizes up to 84" wide; and 18-GA is standard for sizes over where the sleeve may extend to a maximum 16" beyond
84" wide. the wall.
CAULKING: UL approved.
FINISH: Mill on galvanized steel. California State Fire Marshal
Listing No.:3225-1328:110
ACTUATOR: ELECTRIC, with 165° thermal disc; or PNEUMATIC, with 165°F
fusible link and P.E.R.V. Factory-installed for Power-Open/
Spring-Return (fail close) operation. See Reverse Side.
DIMENSIONAL DATA
RECTANGULAR DAMPERS
Minimum Size: 8"W x 8"H
8"W x 6"H *
(with B Pan) *
20" (STD.)
Maximum Size:
Single Section: 32"W x 48"H
THIS DIMENSION WILL Multiple Section: Vert: 128"W x 96"H
CHANGE WHEN SLEEVE
LENGTH IS INCREASED Horiz: 96"W x 96"H
"A" WIDE ROUND AND OVAL DAMPERS
10.5" 5.5" 4" (Type C Housing)
A
Minimum Size:
Round: 6" Diameter
Maximum Size:
Round:
Single Panel
30" Diameter *
Oval: 30"W x 46"H
2x2 Multiple Panel Assembly
Round: 62" Diameter
"B" HIGH

Oval: 62"W x 94"H

NOTE: Dampers 13" high and less have a single blade.


ACTUATOR
(OPTIONAL
LOCATION)

PROJECT:
A
LOCATION:
ACTUATOR SLEEVE
ARCHITECT:
SECTION A-A
ENGINEER:
CONTRACTOR:
PO NUMBER:
* UNITS UNDER 12 INCHES IN WIDTH ARE LEAKAGE CLASS II. DATE:
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 Additional Information
www.arrowunited.com on reverse side
MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA
ACTUATOR SELECTION
Underwriters Laboratories requires that all UL-555S rated dampers be accompanied with their matching UL-approved factory supplied actuators. The
factors for proper actuator selection are actuator type (electric or pneumatic), voltage requirement, temperature rating, and damper size. ARROW
will factory install actuators for all combination fire/smoke dampers.
ELECTRIC
Honeywell Honeywell Honeywell

ML4115 (120 VAC) MS 4209 (120 VAC) MS 4120 (120 VAC)


ML8115 (24 VAC) MS 8209 (24 VAC) MS 8120 (24 VAC)
Max Panel
Size at 250º 24" x 16" 32" x 24" 32" x 48"

Max Panel
Size at 350º Not Available 24" x 24" 32" x 48"

Min. size for


Internal mount: 12" x 12" 12" x 12" 12" x 21"

PNEUMATIC
Siemens Siemens AMP DRAW
331-2997 331-2996 ML 4115—run .18 hold .11
Max Panel ML 8115—run .70 hold .35
Size at 250º 24" x 24" (@20 PSI) 32" x 48" (@20PSI) MS 4209—run .25 hold .13
MS 8209—run 1.0 hold .13
Max Panel 32" x 48" (@20PSI) MS 4120—run .35 hold .15
Size at 350º 24" x 24" (@25 PSI) (Not available with MS 8120—run 1.8 hold .42
Sens-O-Therm)
Min. size for
Internal Mount: 12" x 20" 16" x 24"

AVAILABLE OPTIONS: (Must Be Specified)


1. Normally, actuators are externally mounted on the left side of the sleeve, as viewed from the jackshaft side of the damper. Actuators
may be mounted on the right side at no additional charge, if specified on the order, except where two actuators are used on multiple
panel assemblies.
2. Sleeve thicknesses heavier than 20 gauge are available.
3. Sleeve lengths longer than the standard 20" are available.
4. 212°F thermal disc (electric models); PERV with 212°F fusible link (pneumatic models).
5. "Sens-O-Therm" Thermally Reopenable Temperature Sensing System is available with 165°F (Standard) or 212°F low temperature settings.
This system includes open and closed position indicator switches. It also includes a second thermal disc to re-close the damper when the
rated degradation temperature is reached.
6. Dual position indication package. Optional auxiliary blade position indication switches are rated at 11A, 1/3HP, 125VAC. These snap action
switches are intended to make or break a circuit and will not provide variable or proportional resistance.
7. Smoke detector (damper height must be 10" minimum).
GENERAL NOTES
1. Underwriters Laboratories Inc. classified leakage damper for use in smoke control systems designed for Leakage Class I and Temperature Class
250°F or 350°F, in accordance with UL Standard 555S.

2. Underwriters Laboratories Inc. classified for use for fire resistance ratings of less than 3 hours, in accordance with UL Standard 555.

3. Refer to UL-approved Installation Instructions for detailed operational information.

PERFORMANCE

LEAKAGE
Definition: UL 555S Class I:
Leakage Not Greater Than:
4 CFM per sq. ft. @ 1 in. wg
8 CFM per sq. ft. @ 4 in. wg

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853 Size Tested: 32x36
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
MEMBER OF AMCA

INTHEINTERESTOFPRODUCTDEVELOPMENT,ARROWUNITEDINDUSTRIESRESERVESTHERIGHTTOMAKECHANGESWITHOUTNOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-UA2-04.12

MODEL UA2 1-1/2 HR. RATED UNDERWRITERS LABORATORIES INC.®


Classified
MODEL UA2 250 • MODEL UA2 350 FIRE DAMPERS
FIRE RESISTANCE RATING 11/2 Hr.
LEAKAGE AND TEMPERATURE RATED ALSO CLASSIFIED AS TO LEAKAGE RESISTANCE
CLASS II-250°F
COMBINATION FIRE/SMOKE DAMPER R-4708

LEAKAGE CLASS 2 • DYNAMICALLY CLASSIFIED UNDERWRITERS LABORATORIES INC.®


TEMPERATURE CLASS 250°F or 350°F Classified

FIRE DAMPERS
FIRE RESISTANCE RATING 11/2 Hr.
STANDARD MATERIALS AND CONSTRUCTION ALSO CLASSIFIED AS TO LEAKAGE RESISTANCE
CLASS II-350°F
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel.
R-4708
BLADES: 20-GA Double skinned Galvanized Steel. (Equal to 14-GA),
parallel action
SEALS: Silicone blade edge and stainless steel compression jamb. Recommended
Wall Sleeve
AXLES: Square plated steel. Thickness Length
BEARINGS: Oil Impregnated Bronze.
4", 6" 20"
LINKAGE: Concealed In-Jamb, Plated Steel Tie Bar, Stainless Steel Pivots 8" 22"
STOPS: 18-GA galvanized steel at head and sill. 12" 26"

SLEEVE: Minimum 20-GA galvanized steel by 20" long is standard for NOTE: The length of the sleeve should not extend
over 6" beyond the wall, except on the actuator side,
sizes up to 84" wide; and 18-GA is standard for sizes over
where the sleeve may extend to a maximum 16" beyond
84" wide. the wall.
CAULKING: UL approved.
FINISH: Mill on galvanized steel. California State Fire Marshal
Listing No.:3225-1328:110
ACTUATOR: ELECTRIC, with 165° thermal disc; or PNEUMATIC, with 165°F
fusible link and P.E.R.V. Factory-installed for Power-Open/
Spring-Return (fail close) operation. See Reverse Side.
DIMENSIONAL DATA
RECTANGULAR DAMPERS
Minimum Size: 8"W x 8"H
8"W x 6"H
(with B Pan)
Maximum Size:
20" (STD.)
Single Section: 32"W x 48"H
THIS DIMENSION WILL Multiple Section: Vert: 128"W x 96"H
CHANGE WHEN SLEEVE
LENGTH IS INCREASED Horiz: 96"W x 96"H
"A" WIDE ROUND AND OVAL DAMPERS
10.5" 5.5" 4" (Type C Housing)
A
Minimum Size:
Round: 6" Diameter
Maximum Size: Single Panel
Round: 30" Diameter
Oval: 30"W x 46"H
2x2 Multiple Panel Assembly
Round: 62" Diameter
"B" HIGH

Oval: 62"W x 94"H

NOTE: Dampers 13" high and less have a single blade.


ACTUATOR
(OPTIONAL
LOCATION)

PROJECT: _____________________________
A LOCATION: ____________________________
ACTUATOR SLEEVE

SECTION A-A
ARCHITECT: ___________________________
ENGINEER: ____________________________
CONTRACTOR: _________________________
PO NUMBER: __________________________
Arrow United Industries
A Division of Mestek, Inc. DATE: ________________________________
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 Additional Information
www.arrowunited.com on reverse side
MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA
ACTUATOR SELECTION
Underwriters Laboratories requires that all UL-555S rated dampers be accompanied with their matching UL-approved factory supplied
actuators. The factors for proper actuator selection are actuator type (electric or pneumatic), voltage requirement, temperature rating, and
damper size. ARROW will factory install actuators for all combination fire/smoke dampers.

ELECTRIC
Honeywell Honeywell Honeywell

ML4115 (120 VAC) MS 4209 (120 VAC) MS 4120 (120 VAC)


ML8115 (24 VAC) MS 8209 (24 VAC) MS 8120 (24 VAC)
Max Panel
Size at 250º 24" x 16" 32" x 24" 32" x 48"
(Sizes to 24" x 24" rated
up to 3000FPM, 4" wg.)
Max Panel Not Available 24" x 24" 32" x 48"
Size at 350º

Min. size for


Internal mount: 12" x 12" 12" x 12" 12" x 21"

PNEUMATIC
Siemens Siemens
331-2997 331-2996 AMP DRAW
Max Panel ML 4115—run .18 hold .11
Size at 250º 24" x 24" (@20 PSI) 32" x 48" (@20PSI) ML 8115—run .70 hold .35
MS 4209—run .25 hold .13
Max Panel 32" x 48" (@20PSI) MS 8209—run 1.0 hold .13
Size at 350º 24" x 24" (@25 PSI) (Not available with MS 4120—run .35 hold .15
Sens-O-Therm) MS 8120—run 1.8 hold .42
Min. size for
Internal Mount: 12" x 20" 16" x 24"

AVAILABLE OPTIONS: (Must Be Specified)


1. Normally, actuators are externally mounted on the left side of the sleeve, as viewed from the jackshaft side of the damper. Actuators
may be mounted on the right side at no additional charge, if specified on the order, except where two actuators are used on multiple
panel assemblies.
2. Sleeve thicknesses heavier than 20 gauge are available.
3. Sleeve lengths longer than the standard 20" are available.
4. 212°F thermal disc (electric models); PERV with 212°F fusible link (pneumatic models).
5. "Sens-O-Therm" Thermally Reopenable Temperature Sensing System is available with 165°F (Standard) or 212°F low temperature settings.
This system includes open and closed position indicator switches. It also includes a second thermal disc to re-close the damper when the
rated degradation temperature is reached.
6. Dual position indication package. Optional auxiliary position indication switches are rated 11A, 1/3HP, 125VAC. These snap action switches
are intended to make or break a circuit and will not provide variable or proportional resistance.
7. Smoke detector (damper height must be 10" minimum).
GENERAL NOTES
1. Underwriters Laboratories Inc. classified leakage damper for use in smoke control systems designed for Leakage Class II and Temperature
Class 250°F or 350°F, in accordance with UL Standard 555S.
2. Underwriters Laboratories Inc. classified for use for fire resistance ratings of less than 3 hours, in accordance with UL Standard 555.
3. Refer to UL-approved Installation Instructions for detailed operational information.

PERFORMANCE

LEAKAGE
Definition: UL 555S Class II:
Leakage Not Greater Than:
10 CFM per sq. ft. @ 1 in. wg
20 CFM per sq. ft. @ 4 in. wg

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com Size Tested: 32x36

MEMBER OF AMCA

IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
II-FS CDLG-04.11
INSTALLATION INSTRUCTIONS
FIRE/LEAKAGE RATED DAMPER
MULTI-BLADE FIRE RATED DAMPERS, SINGLE THICKNESS AND
AIRFOIL BLADE DESIGN 1½ HR. RATED FIRE SMOKE DAMPERS

TYPICAL WALL INSTALLATION


These dynamically rated fire/smoke and fire dampers are factory
sealed into the provided sleeve and must be positioned so that it
is within the fire rated masonry, block or gypsum wallboard barrier,
when the damper is intended to be used as a fire rated damper.
When the damper is to be used as a leakage rated damper only, it
is to be installed within 24" of the smoke barrier and be upstream
of any duct outlets.

This damper may be mounted in the vertical or horizontal position


with the damper blades running horizontal. These dampers may
be mounted right side up or upside down.

Dampers are supplied with factory mounted actuators (except


Multi-Blade Fire Dampers) and are intended to close automatically
when sensing heat or upon loss of electrical power or release of
air pressure. When this damper is used as a leakage rated
damper only, it shall be arranged to operate automatically and is to
be controlled by a smoke detector. See additional instructions,
which detail damper actuator sequence of operations.

A duct access door is to be located on the jackshaft side of each


damper.

MOUNTING:
1. The installation of the damper and all duct connections to the
damper sleeve shall conform to NFPA-90A and the SMACNA
Fire, Smoke and Radiation Damper Installation Guide. All duct
connections shall also conform to UL555 when the damper is
intended to be used as a fire damper.
2. Sleeves shall be the same gauge or heavier as the duct to
which it is attached. Gauges shall conform to SMACNA or
ASHRAE duct standards.
3. The damper is normally supplied with a factory attached sleeve
(see Note 11 when field supplied sleeve). Duct connections
to the sleeve will be either of the breakaway or rigid types that
are listed below. The following determines if the connections
are to be rigid or breakaway. For rigid type duct connections,
sleeve shall be a minimum of 16 GA on dampers not exceed-
ing 36" wide or 24" high or 24" diameter and 14 GA on larger
units. Maximum sleeve thickness will not exceed 10 GA
galvanized steel. Dampers supplied with thinner sleeves will
require a breakaway connection of the types listed in Note 5.
The standard factory supplied sleeve is 20 GA galvanized steel
(18 GA on dampers wider than 84") and assumes that a
breakaway type duct connection will be employed.
4. Duct connections not listed as breakaways (See Note 5) shall
be considered rigid. Breakaway joints shall have no more than
two No. 10 sheet metal screws on each side and on the
bottom. The screws shall penetrate both sides of the slip
pocket. When a breakaway joint is used along the top and
bottom duct connection, a flat drive slip no longer than 20
inches is permitted on the two sides.

Commercial Damper / Louver Group


MOUNTING (cont.)
5. The following breakaway duct-to-sleeve connections may be used: Plain “S” Slip, Double “S” Slip, Inside Slip,
Hemmed “S” Slip, Standing “S” Slip, Standing “S” Slip (Bar Reinforced), Standing “S” Slip (Angle Reinforced) and
Standing “S” Slip (Alternate Bar).
6. All connecting ducts shall not be continuous but shall terminate at the fire damper sleeve. Connecting ducts are at-
tached to the damper sleeve as instructed by Notes 3, 4 and 5.
7. The opening in the wall for the fire/leakage rated damper shall be sized so as to provide expansion clearance between
the sleeve and the opening of a minimum of 1/8" per foot of overall damper/sleeve width and height. The maximum
opening size shall not exceed 1/8" per foot plus 1"; minimum total clearance shall be at least 1/4" larger than the overall
assembly. Perimeter mounting angles shall increase in size, proportionately, so there will be a minimum of 1" of overlap
on the wall, including at the corners, and the angles shall be flush against the wall.
8. Fasten the perimeter mounting angles on all four sides and on both faces of the damper to the sleeve only, with 1/4"
diameter steel or stainless steel nuts and bolts or by tack welding with beads 1/2" ± 1/4" in length or with #10 steel or
stainless steel sheet metal screws or 3/16" steel or stainless steel pop rivets. All connections shall be spaced a maxi-
mum of 6" on center and shall have a connection not more than 3" from each corner, (1" on the alternate assembly).
Perimeter mounting angles shall be a minimum of 1-1/2" x 7/8" 16 gauge steel. Corners of angles are not welded together
for dampers whose width or height exceeds 24". For dampers 24" x 24" or smaller, the corners of the perimeter mount-
ing angles can be welded. Some local codes may not allow welded corners. Perimeter angles and their mounting
fasteners are not normally supplied with the damper. Attachment of these angles must not restrict operation of the
damper.
9. Caulking is allowed between the mounting angles and the damper sleeve, and between the mounting angles and the
floor or wall construction. Caulk shall be one of the following: Dow Corning RTV732, General Electric IS808 or Novagard
RTV300. Caulking is not allowed between the damper sleeve and the wall or floor inside the opening.
10. Dampers shall be maintained in intervals as stated in NFPA 90A and 92A unless local codes require more frequent
inspections.
11. Single panel dampers with factory mounted internal actuators can be supplied without sleeves. See Note 2 for required
sleeve gauge thickness. Field supplied sleeve is attached to damper frame with 3/16" diameter steel rivets, ¼" diameter
steel bolts, #10 steel sheet metal screws or ½" long welds. Fasteners to be staggered on each side of the damper
frame at 6"maximum centers and 3-½" maximum from each corner.

INSTALLATION INSTRUCTIONS FOR ELECTRIC OR PNEUMATIC REOPENABLE (SENS-O-THERM) FIRE/LEAKAGE


RATED DAMPERS WITH POSITION INDICATOR SWITCHES. DAMPER IS SUPPLIED WITH ONE HIGH LIMIT AND
ONE LOW LIMIT THERMAL DISC. ALL DAMPERS REQUIRE A MASTER CONTROL SWITCH FOR REOPENABLE
OPERATION. SEE PAGE 5 FOR WIRING SCHEMATIC.
CUSTOMER WIRING
a. Connect input power L1 from the normal position lead of the
(MCS) switch to damper lead L1.
CIRCUIT TEST
NOTE:
1. Place (MCS) switch in center closed position.
If a smoke detector or other sensing device is to be employed, its N.C.
2. Apply power.
contact set should be wired in series between the (MCS) position
RESULT: The closed indicator light (if used) should now be on
switch normal wire and Lead L1.
and the damper blades closed.
b. Connect incoming L2 to damper L2 3. Transfer (MCS) switch to reopen position.
c. Connect the reopen switch lead from (MCS) to orange damper lead. RESULT: The damper blades should open; the closed indicator
d. Connect the incoming ground to the wiring enclosure. light (if used) should go off and the open indicator light (if used)
e. Replace enclosure cover. should go on.
4. Transfer (MCS) switch to the normal position.
EMERGENCY OPERATION (SMOKE MANAGEMENT): RESULT: The damper blades should remain open and the open
1. MCS closed position--Damper will close regardless of whether the indicator light (if used) should remain on.
thermal switch device has activated or not and regardless of the 5. Transfer the (MCS) switch to the closed position.
command from the smoke system. RESULT: The damper blades should close; the open indicator
2. MCS reopen position--If the damper has not been exposed to an light (if used) should go off and the closed indicator light (if
elevated temp. higher than its rating, the damper will open. Also, the used) should come on.
damper will open regardless of whether the low limit thermal switch
either (165º F or 212ºF) has activated or not and regardless of a
command from additional sensing devices such as a smoke detector.
NOTE: If the master control switch (MCS) is in the reopen position and the
high temperature thermodisc has not been tripped, the damper will
remain open regardless of whether the low temperature thermodisc
and/or other sensing devices have tripped or not. If the damper has
been exposed to an elevated temperature higher than its temperature
degradation rating or if the electrical or pneumatic supply has been
disconnected, the damper will close and remain closed regardless of
any (MCS) position.

2
MULTIPLE PANEL SIZE LIMITATIONS
AIRFOIL FIRE SMOKE DAMPER - Vertical Mount
MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS
MS4209, 4309 32" x 24" 128" x 24" 4
MS8209, 8309
331-2996 32" x 48" 128" x 48" 4
MS4120, 8120 32" x 48" 128" x 96"** (4x2) 8 Acts.

AIRFOIL FIRE SMOKE DAMPER- Horizontal Mount


MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS
MS4209, 4309 32" x 24" 96" x 24" 3
MS8209, 8309
331-2996 32" x 48" 96" x 48" 3
MS4120, 8120 32" x 48" 96" x 96"** (3x2) 6 Acts.

SINGLE THICKNESS FIRE DAMPER- Vertical Mount


MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS
Spring / Fuse Link 36" x 48" 126" x 48" 4
Spring / Fuse Link 36" x 48" 72" x 60"** 4

SINGLE THICKNESS FIRE DAMPER - Horizontal Mount


MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS
Spring / Fuse Link 36" x 48" 72" x 48"* 2
AIRFOIL FIRE DAMPER - Vertical or Horizontal Mount
MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS
Spring / Fuse Link 32" x 48" Single Panel Only 1

SINGLE THICKNESS FIRE SMOKE DAMPER - Vertical Mount


MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS

MS4209, 4309 36" x 36" 108" x 36" 3


MS8209, 8309 48" x 24" 96" x 24" 2
FSNF120, 24

MS4120, 8120 36" x 48" 108" x 48" 3


48" x 36" 96" x 36" 2

GGD121, 221, 321 36" x 48" 108" x 48" 3


331-2996

331-2977 36" x 36" 108" x 36" 3

SINGLE THICKESS FIRE SMOKE DAMPER - Horizontal Mount


MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS

MS4209, 4309
MS8209, 8309
36" x 36" 72" x 36" 2
FSNF120, 24 *
331-2977

MS4120, 8120
GGD121, 221, 321 36" x 48" 72" x 48"* 2
331-2996

* See Page 8 for Mullion Stiffener Detail


** See Page 7 for Mullion Stiffener Detail
3
EXPANSION CLEARANCE OF
1" MINIMUM
1
/8" PER FOOT OF DAMPER
SEE NOTE ON DUCT OVERLAP WIDTH AND HEIGHT, 1/4"
CONNECTION METAL STUD MINIMUM. MAXIMUM
CONSTRUCTION CLEARANCE OF 1/8" PER
FOOT PLUS 1".

SEE NOTE #8 FOR


ATTACHMENT METHOD

NOTE: SEE SUPPLEMENTAL


INSTALLATION INSTRUCTIONS
A33129 FOR ONE-SIDE MOUNTING
WITH RETAINING ANGLE UNDER
THE GYPSUM WALLBOARD

1- 1/ 2" x 7/ 8 " x 16 GA.


(MINIMUM SIZE) STEEL
RETAINING ANGLES,
CLOSED CORNERS

16" MAXIMUM ON SIDE


WITH FACTORY INSTALLED
ACTUATOR OR FACTORY 6" MAXIMUM ON NON-
INSTALLED ACCESS DOOR WOOD STUD MOTOR FACE OR NON-
CONSTRUCTION ACCESS-DOOR SIDE

WALL / PARTITION CONSTRUCTION


VARIES, PER TESTED DESIGN

ONE SIDE MOUNTING, ANGLES


OUTSIDE GYPSUM WALLBOARD
APPLICATION
These instructions illustrate alternate mounting of Classified 4. Steel retaining angles must be attached to both the damper
fire and fire/smoke dampers to a rated wall or partition from sleeve and to the partition framing on all four sides of this one
one side only. The steel retaining angles are on the outside face mounting method.
face of the gypsum board and on the outside of the ma- A. Damper sleeve to retaining angles attached 6" maximum
sonry or concrete wall or partition. on-centers, 3" maximum from each corner, minimum of two
1. This installation is limited to the following: fasteners per side by the following means:
A. Two hour or less rated wall or partition. 1. 3/16" diameter steel bolts and nuts,
B. Vertically mounted damper. 2. Welding, 1/2" long beads,
C. Wood stud/metal stud gypsum board construction as 3. #10 steel sheet metal screws,
well as masonry/concrete construction. 4. 3/16" diameter steel rivets.
D. Maximum size damper of 48" wide x 36" high or 36" B. Retaining angles to gypsum board wall framing attached
wide x 48" high. using drywall screws 6" maximum on-centers, 3" maximum
2. See page 6 for opening framing details. from each corner, minimum of two fasteners per side.
3. Closed plane of damper blades must be within the plane C. Retaining angles to concrete or masonry attached using
of the rated wall or partition.
3
/16" steel masonry fasteners 6" maximum on-centers, 3"
maximum from each corner, minimum of two fasteners per
side.
4
ELECTRIC WIRING SCHEMATICS

This schematic is used for dampers This schematic is used for dampers supplied
supplied with a single thermal switch. with the Sens-O-Therm, reopenable feature
(two thermal switches).

NOTES:
1. All wiring to be in accordance with N.E.C. (NFPA-70).
2. Refer to actuator label for appropriate voltage.
3. Connect incoming ground to the actuator assembly.
4. If the actuator is electrically energized yet the damper
remains in the closed position, check that the reset button
on the heat response device is depressed.
5. Optional auxiliary blade position indication switches are
rated at 1A, 1/3HP, 125VAC. These snap action switches
are intended to make or break a circuit and will not provide
variable or proportional resistance.

This schematic is used to wire auxiliary blade


position indication switches.

5
INSTALLATION INSTRUCTIONS FOR 1-1/2 HOUR
UL CLASSIFIED FIRE DAMPERS INSTALLED INTO
METAL OR WOOD FRAMED 1 HOUR AND 2 HOUR RATED DRYWALL PARTITIONS

NOTES:
1. These illustrated partition designs have
successfully been tested in conjunction with
1-1/2 hour classified fire dampers, for
additional designs, reference Underwriters
Laboratories, Inc. Fire Resistance Directory.
Specific framing requirements of openings
may vary with the Local Authority that has
jurisdiction. Specific framing requirements
should be provided in the architectural and
structural drawings.

2. Reference the damper's installation


instructions regarding the approved method
of attaching the damper to the sleeve,
attaching the retaining angles to the sleeve,
required expansion clearances, sleeve
gauge, etc. Type of framing does not affect
the stated required expansion clearance.

3. Gypsum panels surrounding the opening are


to be fastened to all stud and runner
flanges, 12" o.c. maximum.

4. When wooden studs are used, filler pieces


must be installed around the entire opening.
Filler pieces are optional when metal studs
are used (consult local codes to determine if
filler pieces are required). Filler pieces are
to be double screwed (or nailed to wooden
studs) on 12" max. centers to the web of
runners and studs.

5. Double jamb studding shown and required


when opening width or length exceeds 36".
Single jamb studding acceptable for
openings 36" x 36" and smaller.

6
FABRICATION AND INSTALLATION INSTRUCTIONS FOR
TWO PANEL HIGH MULLION STIFFENER

Purpose When Required


This factory or field fabricated This 12 GA steel flat plate is sandwiched
plate reinforces the damper's between the damper's vertical frame
vertical mullion to prevent members at its vertical mullion. This
excessive mullion deflection. stiffener is required whenever the
damper assembly is both multiple panels
wide and multiple panels high.

1
2
1 One piece full height 6" by
12 GA steel plate.

2 1/4" Steel bolts and nuts on 12"


max. centers, staggered on both
faces. First fastener 6" maximum
from each end. Ends of plate do
not need to be attached to top and
bottom of sleeve.

3 Vertical damper Mullion

Notes
1. When assembly is ordered with a factory supplied sleeve, this mullion stiffener
will be factory furnished and installed.
2. When assembly is ordered without a factory supplied sleeve, this mullion stiff-
ener is to be field fabricated and field installed.

INSTALLATION OF MULTIPLE SHIP SECTION DAMPER ASSEMBLIES


Large damper openings may require multiple factory assembled modules to fill the opening. After
placing the modules into the opening, the individual modules are fastened together using ¼”
diameter steel bolts, lockwashers, and nuts. Fasteners are to be on 6” maximum centers and on
both faces of the sleeve.

7
FABRICATION AND INSTALLATION INSTRUCTIONS
FOR MULLION ANGLE WHEN HORIZONTALLY MOUNTED

PURPOSE: WHEN REQUIRED:


This factory or field fabricated angle/strap assembly This angle/strap assembly is centered above the
reinforces the damper mullion to prevent excessive damper mullion (located where two damper panels
mullion deflection during exposure to a fire. butt together) when the damper is mounted horizon-
tally. This reinforcement is required only on multiple
panel assemblies when the damper height (dimension
perpendicular to blade span) exceeds 26 inches.

1 4" x 1" x 16GA (minimum required size) galvanized steel angle, length of angle same as inside sleeve height.

2 16 GA (minimum thickness) tab (stitch welded) or angle (stitch welded or mechanically attached with two fasten-
ers -- see below) to each end of angle which permits angle assembly to be stitch welded or mechanically attached
to the sleeve. Fasteners to be steel, No. 10 S.M.S., 3/16" dia. rivets, or No. 10 bolts; two at each tab.

3 8" x 3/4" x 20GA (minimum required size) galvanized steel strap attached to damper mullion with one fastener,
attached to angle with two fasteners (see note 2 for type of fastener). Number of straps required:
A. All single panel and multiple panel assemblies not exceeding 26" in height do not require a mullion angle.
B. Multiple panel assemblies exceeding 26" but not exceeding 36" in height require one strap centered along the
damper height.
C. Multiple panel assemblies exceeding 36" in height require two straps, 6" to each side of the damper mid-height.

8
INSTALLATION INSTRUCTIONS AII-AT-04.11
THREE HOUR FIRE RATED DAMPERS
MODEL: AT - FIRE and LEAKAGE RATED
MD39 - FIRE RATED

INTRODUCTION
The Model AT-Series damper is dynamically rated
and Underwriters Laboratories Classified for Three
Hour Fire Resistance (per Standard 555) and Classi-
fied as a Leakage Rated Damper (per Standard 555S).
(Model MD37 is not leakage rated.)
When motorized, this damper is sealed into a factory
provided sleeve. When provided as a nonmotorized,
spring closure assembly, the sleeve can be field sup-
plied, mounted and sealed to the damper. The sleeved
damper assembly must be mounted such that the
closed plane of the damper blades are within the fire
rated wall.
This damper may be mounted in the vertical or horizon-
tal position, with the blades running horizontally. The
vertical damper may be mounted right side up or up-
side down.
This damper will close automatically upon sensing el-
evated temperature or upon loss of electrical power or
release of air pressure (Model AT). A duct access
door is to be located on the jackshaft side of each
damper to allow for inspection and maintenance.

MINIMUM
MOUNTING DAMPER SLEEVE
WIDTH THICKNESS
1. The installation of the damper and all duct connec-
tions to the damper sleeve shall conform to these
(in.) (in.) (Ga.)
instructions as well as to NFPA-90A and the 12 or less .018 26
SMACNA Fire, Smoke and Radiation Damper Instal-
lation Guide. 13 - 30 .024 24
2. Sleeves shall be steel of the same gauge or heavier 31 - 54 .030 22
as the duct to which it is attached. Gauges shall 55 - 84 .036 20
conform to SMACNA or ASHRAE duct standards
(See Table 1.) 85 or more .047 18

Damper sleeves can be no thicker than 10 ga. steel. TABLE 1


The sleeve is to be attached to the damper by means
of 3/16” steel rivets, 1/4” steel bolts, #10 steel sheet
metal screws or 1/2” long welds. Fasteners to be 10”
maximum on centers, staggered on both faces, 31/2”
maximum from each end.

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com

MEMBER OF AMCA
MOUNTING, Continued
3. Duct connections to the sleeve will be either of the 8. The perimeter mounting angles shall be fastened to
breakaway or rigid types that are listed below. The the damper sleeve on all four (4) sides and both
following determines if the connections are to be rigid faces. Do not fasten mounting angles to the wall.
or breakaway. For rigid type duct connections, Acceptable methods of attachment are 1/4” diam-
sleeve shall be a minimum of 16 ga. on dampers not eter steel or stainless steel nuts and bolts, tackweld
exceeding 36” wide or 24” high or 24” diameter and beads 1/2” long ± 1/4”, #10 steel or stainless steel
14 ga. on larger units. Dampers supplied with thin- sheet metal screws or 3/16” steel or stainless steel
ner sleeves will require a breakaway connection of pop rivets. Connections shall be spaced a maxi-
the types listed in Note 5. The standard factory sup- mum of 6” on center and shall have a connection no
plied sleeve is 20 ga. galvanized steel (18 ga. on greater than 11/2” from each corner.
dampers wider than 84”) and assumes that a
breakaway type duct connection will be employed. Perimeter mounting angles shall be a minimum 7/8”
x 11/2” x 16 ga. steel. Note the larger leg shall be
4. Duct connections not listed as breakaways (See against the wall opening. Corners may be tabbed
Note 5) shall be considered rigid. Breakaway joints or loose.
shall have no more than two No. 10 sheet metal
screws on each side and on the bottom. The screws Perimeter mounting angles are an option that can
shall penetrate both sides of the slip pocket. When be supplied by the factory. However, fasteners are
a breakaway joint is used along the top and bottom always a field supplied item. Attachment of these
duct connection, a flat drive slip no longer than 20 angles must not restrict the operation of the damp-
inches is permitted on the two sides. ers.

5. The following breakaway duct-to-sleeve connections 9. To maintain the leakage rating of the model AT, field
may be used: Plain “S” Slip, Double “S” Slip, Inside supplied sleeves must be caulked to the damper
Slip, Hemmed “S” Slip, Standing “S” Slip, Standing frame. Caulking is allowed between the mounting
“S” Slip (Bar Reinforced), Standing “S” Slip (Angle angles and the floor or wall construction. Caulk
Reinforced) and Standing “S” Slip (Alternate Bar). shall be one of the following: Dow Corning RTV732,
General Electric IS808 or Novagard RTV300. Caulk-
6. All connecting ducts shall not be continuous but shall ing is not allowed between the damper sleeve and
terminate at the fire damper sleeve. Connecting ducts the wall or floor inside the opening (annular space).
are attached to the damper sleeve as instructed by
Notes 3, 4 and 5. 10. Damper shall be maintained in intervals as stated
in NFPA 90A and 92A unless local codes require
7. The opening in the wall or floor for fire rated damp- more frequent inspections.
ers shall be 1/8” per foot (1/4” minimum) to a maxi-
mum of 1” greater than the overall damper sleeve
width and height to allow for expansion. This sizing
dimension covers all dampers up to 96”W x 48”H.
Damper widths above 96” shall require the opening
width to be a minimum of 11/4” and a maximum of 2”
greater than the overall width. Perimeter mounting
angles must be sized to allow a minimum of 1/2” over-
lap of the wall opening regardless of damper shift in
the opening.

2
ACTUATOR
1. If the actuator is electrically energized yet the damper remains in the closed position, check that the reset button on the heat response
device is depressed.
2. See Page 4 for electric wiring instructions for electric actuators and position indication switches.
3. Check actuator label for proper supply voltage and current draw or minimum and maximum air supply pressure.
4. All wiring to be in accordance with N.E.C. (NFPA-70).
5. Operation of optional reopenable (Sens-O-Therm) feature:
A.Master Control Switch in closed position—
Damper will close regardless of whether the thermo switch device has activated or not and regardless of the command from the
smoke system.
B. Master Control Switch in reopen position—
If the damper has not been exposed to an elevated temp. higher than its rating the damper will open. Also, the damper will open
regardless of whether the low limit switch either (165°F or 212°F) has actuated or not. If the damper has been exposed to an
elevated temperature higher than its temperature degradation rating or if the electrical or pneumatic supply has been disconnected,
the damper will close and remain closed regardless of any (MCS) position.
6. Horizontally mounted, two panel wide assemblies greater than 26” high require a mullion stiffener. Reference page 8 ofAII-AS.

VERTICALLY MOUNTED

MAX. W x H MAX. W x H MAX. PANELS


DAMPER ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
MODEL TYPE SECTION (in.) ASSEMBLY (in.) OF ACTUATORS
MS4209, 4309
MS8209, 8309
FT 36 x 36 108 x 36 3
FSNF120, 24
331-2961, 2995
MS4120, 8120
GGD121, 221
FT 36 x 48 108 x 48 3
GGD321
331-2792

SPRING/
MD39 36 x 48 126 x 48 4
FUSE LINK

TABLE 2

HORIZONTALLY MOUNTED

MAX. W x H MAX. W x H MAX. PANELS


DAMPER ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
MODEL TYPE SECTION (in.) ASSEMBLY (in.) OF ACTUATORS
MS4209, 4309
MS8209, 8309
FT 30 x 36 60 x 36 2
FSNF120, 24
331-2961, 2995
MS4120, 8120
GGD121, 221
FT 30 x 48 60 x 48 2
GGD321
331-2792
SPRING/
MD39 30 x 48 60 x 48 2
FUSE LINK

SPRING/
MD39 FUSE LINK 36 x 30 --- 1

TABLE 3
3
ELECTRIC WIRING SCHEMATICS

This schematic is used for dampers This schematic is used for dampers supplied
supplied with a single thermal switch. with the Sens-O-Therm, reopenable feature
(two thermal switches).

NOTES:
1. All wiring to be in accordance with N.E.C. (NFPA-70).
2. Refer to actuator label for appropriate voltage.
3. Connect incoming ground to the actuator assembly.
4. If the actuator is electrically energized yet the damper
remains in the closed position, check that the reset button
on the heat response device is depressed.
5. Optional auxiliary blade position indication switches are
rated at 11A, 1/3HP, 125VAC. These snap action switches
are intended to make or break a circuit and will not provide
variable or proportional resistance.

This schematic is used to wire auxiliary blade


position indication switches.

4
Corridor Fire / Smoke Dampers

AS2C 1 hour rated horiz with sleeve Class II


AS1G/F 1 1/2 hour rated vert with sleeve Class I
AS2G/F 1 1/2 hour rated vert with sleeve Class II
Installation (Front Access)
Installation (Detectors)
Installation (1-1/2 Hour Rated)
Installation (Corridor)
ASD-AS2C-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA

UNDERWRITERS LABORATORIES INC.®


MODEL AS2C CLASSIFIED CORRIDOR DAMPER
Fire Resistance Rating 1Hr.
LEAKAGE CLASS II Also As To Leakage Resistance
TEMPERATURE CLASS 250°F, CLASS II - 250°F
R4708
ONE HOUR FIRE RATED DAMPER FOR TUNNEL
CORRIDOR CEILING APPLICATIONS California State Fire Marshal Listing
3225-1328:113

STANDARD MATERIALS & CONSTRUCTION DIMENSIONAL DATA:


FRAME: 5-1/2" x 7/8" x 20-GA galvanized steel hat channel. Outside Sleeve (See note below):
BLADES: 20-GA galvanized steel, 6" nominal width; parallel
Minimum Size: 8"W x 8"H
action.
AXLES: Square, plated solid steel stub. Maximum Size: 24"W x 24"H
BEARINGS: Oil Impregnated Bronze. Round Duct Transition:
LINKAGE: In-jamb type, located outside of the airstream; Minimum Size: 6" Diameter
plated steel tie bar and crankplates, with stainless
steel pivots. Maximum Size: 22" Diameter
STOPS: 20-GA galvanized steel at head and sill.
Overall sleeve width and sleeve height will be
BLADE EDGE SEALS: Silicone (350°F).
2" greater than ordered round duct size.
SIDE JAMB SEALS: Stainless steel.
SLEEVE: 16" deep by 20 GA, unflanged. Outside sleeve dimensions are available on
CAULKING: UL approved. one inch increments. Outside sleeve dimen-
FINISH: Mill on galvanized steel. sions are not undersized.
ACTUATOR: 120 VAC electric with 165°F thermal disc, factory
installed for power-open/fail-close operation. AVAILABLE OPTIONS (Must Be Specified)
Actuator internally mounted (8"-12" high dampers 1. 212°F thermal disc.
are externally mounted), damper closure time of 2. Round/rectangular duct transitions, top side
less than 15 seconds. only on flanged sleeves, top and/or bottom
AIRFLOW: Rated for both up and down flow; 2000fpm, 4 in. wg. side on unflanged sleeves.
3. 13/4" grille clearance and 3/4" flanged sleeve.
OUTSIDE SLEEVE 4. 3" grille clearance and 3/4" flanged sleeve.
WxH 5. Perimeter mounting angles, one or two sets
THERMAL DISC per damper.
6. Smoke detector (*).
7. Externally mtd. actuator. (Std. 8"-12" high)
6-15/16"*

14-3/4" DEEP * (16" WHEN


3" GRILLE CLEARANCE)*

8. “Sens-O-Therm” Thermally Reopenable Tem-


ACTUATOR
perature Sensing System. This system in-
cludes contacts for connection to open and
closed position indicator lamps. It also in-
UNFLANGED)
16 (WHEN *

cludes a second thermal disc to re-close the


damper when the rated degradation tempera-
ture is reached.
3-9/16"

(3" AVAILABLE)

3/4" FLANGE
1-3/4" GRILLE
CLEARANCE

PROJECT:
LOCATION:
ARCHITECT:
ENGINEER:
* Sleeve Length — 1-1/2" Greater on actuator side when CONTRACTOR:
factory mounted smoke detector. PO NUMBER:
Arrow United Industries DATE:
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA

PERFORMANCE LEAKAGE
MAXIMUM DIFFERENTIAL Definition: UL 555S Class II:
PRESSURE: 4 in. wg Leakage Not Greater Than:
MAXIMUM VELOCITY: 10 CFM per sq. ft. @ 1 in. wg
2000 FPM 20 CFM per sq. ft @ 4 in. wg

FULL OPEN PRESSURE DROP DATA


Differential pressure across a damper is the loss of Test Device Setup Figure 5.3. This test setup is
systems pressure to move air at a particular velocity the standard test method used to compare
from one side to the other side of the damper. This damper pressure drop performance. This setup
loss in pressure is a result of two factors: the turbu- does not take into account elbows or other duct
lence created as the air passes over and around the fittings that are part of every actual duct system.
damper components and more significantly the The configuration of the actual duct system
reduction in free area resulting from the frame, immediately upstream and downstream of the
blades, etc. being in the air stream. damper often contribute more pressure loss
The pressure drop data shown below is based on than the damper itself.
actual tests conducted per AMCA Standard 500-D,
ACTUATOR SELECTION
ELECTRIC (For Internal or External Mount Unless Noted)
Minimum Size
HONEYWELL Voltage Amp Draw Maximum Panel Size For Internal Mount
ML4202/4302 120VAC Run: .18 - Hold: .11
1 sq. ft. External Mount Only
ML8202/8302 24VAC Run: .70 - Hold: .35

ML4115 120VAC Run: .18 - Hold: .11


ML8115 24VAC Run: .70 - Hold: .35 24" x 24" 12" x 13"

PNEUMATIC (For Internal or External Mount Unless Noted)


Minimum Size
SIEMENS Pressure Maximum Panel Size For Internal Mount
331-4830 25PSI 24" x 24" 12" x 13"
Actuator Note: Internally mounted actuators are not accessible from the grille side of the damper.

Pressure Drop: TYPICAL PERFORMANCE CURVE


1.0
Pressure Drop (in. wg.)

TESTED PER AMCA


STANDARD 500-D
FIGURE 5.3: (IN-DUCT MOUNT)
(SMALLER SIZES WILL HAVE
0.1 HIGHER PRESSURE DROPS)

24 x 24

0.01
500 1000 2000

Arrow United Industries


FACE VELOCITY IN FEET PER MINUTE A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
MEMBER OF AMCA
www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-AS1G-04.11.17

MODEL AS1G/F (Leakage Class I) UNDERWRITERS LABORATORIES INC.®


CLASSIFIED FIRE DAMPER
• FRONT ACCESS DAMPERS FOR GRILLE FIRE RESISTANCE RATING 11/2 HR
INSTALLATIONS (VERTICAL & HORIZONTAL) ALSO AS TO LEAKAGE RESISTANCE
CLASS I
• LEAKAGE AND TEMPERATURE RATED ARROW UNITED INDUSTRIES
COMBINATION FIRE/SMOKE DAMPERS
This combination fire/smoke damper meets the construction
• TEMPERATURE CLASS 250°F/350°F and performance requirements of:
• Underwriters Laboratories Inc. Standards 555 and 555S
STANDARD MATERIALS AND CONSTRUCTION • National Fire Protection Association Standards 90A, 92A
and 92B
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel.
• ICC's International Building Code
BLADES: 16-GA galvanized steel, single thickness, parallel • ICBO's Uniform Building Code
action. • SBCCI's Standard Building Code
AXLES: Square, plated solid steel stub. • BOCA's National Building Code
BEARINGS: Oil Impregnated Bronze. • New York City MEA Listing #111-99-M
LINKAGE: In-jamb type, located out of the airstream; • California State Fire Marshall Listing #3225-1328:113, 114
galvanized steel angle interconnect, with stain-
less steel pivots.
DIMENSIONAL DATA
STOPS: 20-GA galvanized steel at head and sill. Minimum Size: *12"W x 12"H
BLADE EDGE Maximum Size: 36"W x 42"H
SEALS: Silicone. ROUND DUCT TRANSITION:
JAMB SEALS: Stainless steel. Minimum Size: 10" Diameter
SLEEVE: 20-GA galvanized steel by 15" long (11/2" grille Maximum Size: 34" Diameter
clearance) or 17" long (31/2" grille clearance) with *Units under 16" in width are leakage Class II.
13
/16" front flange. Overall sleeve width and sleeve height will be 2" greater than
ordered round duct size.
FINISH: Mill on galvanized steel.
Opening Size - No expansion clearance is required but
ACTUATOR: 120 VAC electric with 165°F thermal disc, factory- sufficient clearance between the damper and the opening is
installed for Power-Open/Spring-Return (fail required for the insulation and for mounting. The minimum
close) operation. Actuator is internally mounted width shall be 3/8" larger than the nominal size. The minimum
and accessible from grille side. opening height shall be 1/4" larger than the nominal size when
NOTE: Maximum Velocity of 2000 fpm and 4 in. wg static vertically mounted. When horizontally mounted, the opening
pressure. height shall be 3/8" larger than the nominal size. The maximum
sizes shall be no more than 1/4" greater than the minimum sizes.
Example: An 18" wide by 24" high nominal size damper
when mounted vertically, will require a minimum opening
FIRE RATED width of 183/8" and a minimum opening height of 241/4".
PARTITION
FACTORY INSTALLED INSULATION,
3 SIDES WHEN WALL MOUNTED, AVAILABLE OPTIONS: (Must Be Specified)
4 SIDES WHEN FLOOR MOUNTED 1. 212°F thermal disc.
2. Dual position indication package. These
optional auxiliary blade position indication
switches are intended to make or break a
circuit and will not provide variable or
proportional resistance.
3. Tab-Lock Retaining Angles.
4. Round duct transition, one or two sides.
5. “Sens-O-Therm” Thermally Reopenable Tem-
perature Sensing System is available with
165°F (Standard) or 212°F settings. This
system includes open and closed position
indicator switches. It also includes a second
thermal disc to re-close the damper when the
GRILLE, rated degradation temperature (250ºF or
OPENING SIZE, 350ºF) is reached.
BY OTHERS SEE DIMENSIONAL
DATA
PROJECT:
17" DEEP WHEN 3½"
CLEARANCE LOCATION:
15" DEEP WHEN 1½"
CLEARANCE ARCHITECT:
ENGINEER:
Arrow United Industries CONTRACTOR:
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853 PO NUMBER:
Ph: (570) 746-1888 Fax: (570) 746-9286 DATE: Additional information
www.arrowunited.com MEMBER OF AMCA on reverse side
ARROW UNITED INDUSTRIES SUBMITTAL DATA

PERFORMANCE LEAKAGE
MAXIMUM DIFFERENTIAL Definition: UL 555S Class I:
PRESSURE: 4 in. wg Leakage Not Greater Than:
MAXIMUM VELOCITY: 4 CFM per sq. ft. @ 1 in. wg
2000/3000 FPM Based on Actuator Model 8 CFM per sq. ft @ 4 in. wg

ELECTRIC
Maximum Single Panel Size
HONEYWELL Voltage @250ºF @350ºF Minimum Size
ML4202/4302 120VAC
ML8202/8302 24VAC 1 Sq. Ft. N/A 12" x 12"

ML4115 120VAC
24" x 24" N/A 12" x 12"
ML8115 24VAC

MS4209/4309 120VAC
36" x 36" 24" x 24" 12" x 12"
MS8209/8309 24VAC
36" x 42"
MS4120 120VAC
(Up to 36" x 36" rated to 36" x 42" 12" x 20"
MS8120 24VAC 3000 fpm, 4 in. wg.)

SIEMENS
GGD221 120VAC
GGD121 24VAC 36" x 42" N/A 12" x 20"
GGD321 230VAC
BELIMO
FSNF120 120VAC
FSNF24 24VAC 36" x 36" 36" x 36" 12" x 20"

PNEUMATIC
Maximum Single Panel Size
SIEMENS @250ºF @350ºF Minimum Size
331-4830 24" x 24" @ 25 psi N/A 12" x 16"
24" x 24" @ 25 psi
331-2977 36" x 36" @ 20 psi 12" x 20"
(Sens-O-Therm N/A)

GENERAL NOTES
1. Underwriters Laboratories Inc. approved for dual direction flow and dynamic applications.
2. Underwriters Laboratories Inc. Classified for use in fire resistance ratings of less than 3 hours, in accordance with
UL Standard 555.
3. Underwriters Laboratories Inc. Classified leakage rated damper for use in smoke control systems designed for
Leakage Class I, and Temperature Class 250ºF of 350ºF in accordance with UL Standard 555S.
4. Installation must comply with the requirements of NFPA-90A & -92A. Actuators must be arranged to operate
automatically, must fail close upon loss of power, and must be controlled by a smoke detection system.

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com

In the interest of product development, Arrow United


MEMBER OF AMCA Industries reserves the right to make changes without notice.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-AS2G-04.11.17

UNDERWRITERS LABORATORIES INC.®


MODEL AS2G/F (Leakage Class II) CLASSIFIED FIRE DAMPER
FIRE RESISTANCE RATING 11/2 HR
• FRONT ACCESS DAMPERS FOR GRILLE ALSO AS TO LEAKAGE RESISTANCE
CLASS II
INSTALLATIONS (VERTICAL & HORIZONTAL) Arrow United Industries
• LEAKAGE AND TEMPERATURE RATED
This combination fire/smoke damper meets the construction
COMBINATION FIRE/SMOKE DAMPERS and performance requirements of:
• TEMPERATURE CLASS 250°F/350°F
• Underwriters Laboratories Inc. Standards 555 and 555S
• National Fire Protection Association Standards 90A, 92A
and 92B
STANDARD MATERIALS AND CONSTRUCTION • ICC's International Building Code
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel. • ICBO's Uniform Building Code
BLADES: 16-GA galvanized steel, single thickness, parallel • SBCCI's Standard Building Code
action. • BOCA's National Building Code
AXLES: Square, plated solid steel stub. • New York City MEA Listing #111-99-M
BEARINGS: Oil Impregnated Bronze. • California State Fire Marshall Listing #3225-1328:113, 114
LINKAGE: In-jamb type, located out of the airstream;
galvanized steel angle interconnect, with stain- DIMENSIONAL DATA
less steel pivots. Minimum Size: 12"W x 12"H
STOPS: 20-GA galvanized steel at head and sill. Maximum Size: 36"W x 42"H
BLADE EDGE ROUND DUCT TRANSITION:
SEALS: Silicone. Minimum Size: 10" Diameter
JAMB SEALS: Stainless steel. Maximum Size: 34" Diameter
SLEEVE: 20-GA galvanized steel by 15" long (11/2" grille Overall sleeve width and sleeve height will be 2" greater than
clearance) or 17" long (31/2" grille clearance) with ordered round duct size.
13
/16" front flange. Opening Size - No expansion clearance is required but
FINISH: Mill on galvanized steel. sufficient clearance between the damper and the opening is
ACTUATOR: 120 VAC electric with 165°F thermal disc, factory- required for the insulation and for mounting. The minimum
installed for Power-Open/Spring-Return (fail width shall be 3/8" larger than the nominal size. The minimum
opening height shall be 1/4" larger than the nominal size when
close) operation. Actuator is internally mounted
vertically mounted. When horizontally mounted, the opening
and accessible from grille side. height shall be 3/8" larger than the nominal size. The maximum
NOTE: Maximum Velocity of 2000 fpm and 4 in. wg static sizes shall be no more than 1/4" greater than the minimum sizes.
pressure.
Example: An 18" wide by 24" high nominal size damper
FIRE RATED when mounted vertically will require a minimum opening width
PARTITION of 183/8" and a minimum opening height of 241/4".
FACTORY INSTALLED INSULATION,
3 SIDES WHEN WALL MOUNTED, AVAILABLE OPTIONS: (Must Be Specified)
4 SIDES WHEN FLOOR MOUNTED
1. 212°F thermal disc.
2. Dual position indication package. These
optional auxiliary blade position indication
switches are intended to make or break a
circuit and will not provide variable or propor-
tional resistance.
3. Tab-Lock Retaining Angles.
4. Round duct transition, one or two sides.
5. “Sens-O-Therm” Thermally Reopenable Tem-
perature Sensing System is available with 165°F
(Standard) or 212°F settings. This system in-
cludes open and closed position indicator
switches. It also includes a second thermal
disc to re-close the damper when the rated
GRILLE, degradation temperature (250º or 350ºF) is
OPENING SIZE, reached.
BY OTHERS SEE DIMENSIONAL
DATA
PROJECT:
17" DEEP WHEN 3½"
CLEARANCE LOCATION:
15" DEEP WHEN 1½"
CLEARANCE ARCHITECT:
ENGINEER:
Arrow United Industries
A Division of Mestek, Inc. CONTRACTOR:
314 Riverside Drive . Wyalusing, PA 18853 PO NUMBER:
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com DATE: Additional information
MEMBER OF AMCA on reverse side
ARROW UNITED INDUSTRIES SUBMITTAL DATA

PERFORMANCE LEAKAGE
MAXIMUM DIFFERENTIAL Definition: UL 555S Class II:
PRESSURE: 4 in. wg Leakage Not Greater Than:
MAXIMUM VELOCITY: 10 CFM per sq. ft. @ 1 in. wg
2000/3000 FPM Based on Actuator Model 20 CFM per sq. ft @ 4 in. wg

ELECTRIC
Maximum Single Panel Size
HONEYWELL Voltage @250ºF @350ºF Minimum Size
ML4202/4302 120VAC
ML8202/8302 24VAC 1 Sq. Ft. N/A 12" x 12"

ML4115 120VAC
24" x 24" N/A 12" x 12"
ML8115 24VAC

MS4209/4309 120VAC
36" x 36" 36" x 24" 12" x 12"
MS8209/8309 24VAC
36" x 42"
MS4120 120VAC
(Up to 36" x 36" rated to 36" x 42" 12" x 20"
MS8120 24VAC 3000 fpm, 4 in. wg.)

SIEMENS
GGD221 120VAC
GGD121 24VAC 36" x 42" N/A 12" x 20"
GGD321 230VAC
BELIMO
FSNF120 120VAC
FSNF24 24VAC 36" x 36" 36" x 36" 12" x 20"

PNEUMATIC
Maximum Single Panel Size
SIEMENS @250ºF @350ºF Minimum Size
331-4830 24" x 24" @ 25 psi N/A 12" x 16"
24" x 24" @ 25 psi 12" x 20"
331-2977 36" x 36" @ 20 psi (Sens-O-Therm N/A)

GENERAL NOTES
1. Underwriters Laboratories Inc. approved for dual direction flow and dynamic applications.
2. Underwriters Laboratories Inc. Classified for use in fire resistance ratings of less than 3 hours, in accordance with
UL Standard 555.
3. Underwriters Laboratories Inc. Classified leakage rated damper for use in smoke control systems designed for
Leakage Class II, and Temperature Class 250ºF of 350ºF in accordance with UL Standard 555S.
4. Installation must comply with the requirements of NFPA-90A & -92A. Actuators must be arranged to operate
automatically, must fail close upon loss of power, and must be controlled by a smoke detection system.

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
MEMBER OF AMCA In the interest of product development, Arrow United Industries
reserves the right to make changes without notice.
INSTALLATION INSTRUCTIONS AII-FRONT ACCESS-04.11
FIRE/SMOKE RATED FRONT ACCESS
(GRILLE MOUNT) DAMPERS
MODELS AS_G or AS_F (Single Thickness)
MODELS AA_G or AA_F (Airfoil)
APPLICATION INSTALLATION - General Requirements
This UL Classified (see complete marking on product) This damper is approved for vertical and horizontal instal-
combination fire/smoke damper has been tested with the lation. This damper can also be mounted into wood stud
damper out of the plane of the fire barrier. This arrangement construction walls, See Figure 3. Blades must run
allows for grille and grille/OBD assemblies to be flush horizontal when vertically mounted. When vertically
mounted to the face of the fire barrier. Upon removal of the mounted, this damper is required to be insulated on the
grille; the damper, damper actuator, and resetting of the heat top and two sides (the bottom is not insulated). This
responsive device are accessible. damper cannot be mounted up-side-down, reference “Top
This damper is intended to close automatically when of Damper” label. When horizontally mounted, the exte-
sensing elevated temperature or upon loss of electrical rior of the sleeve is insulated on all four sides. Pinching,
power. If closed due to loss of electrical power, the damper racking and other causes of frame distortion can result in
will reopen when electrical power is restored. reduced leakage resistance or incomplete closure.
• 11/2 Hour Fire Rated, UL File R4708 Electrical wiring is to be in compliance with local codes
• For use in Dynamic or Static Systems and the National Electric Code (NEC). Reference wiring
• Available in UL Leakage Class I or II diagram on damper, ensure that supply voltage matches
• Factory Mounted Sleeve and Actuator actuator requirements. Damper and actuator must be
• 15 second (maximum) opening time, tested prior to system start-up to ensure proper operation.
Actuator Regulated Closure.
1. If the actuator is electrically energized yet the damper
remains in the closed position, check that the reset
button on the heat response device is depressed
(disconnect power before resetting).

0.20" THICK
17" DEEP WHEN 3½" 2. Insulation - The exterior of the damper sleeve is factory
GRILLE CLEARANCE
INSULATION ON TOP 15" DEEP WHEN 1½" insulated. Care should be taken during installation to
AND BOTH SIDES GRILLE CLEARANCE
(BASED ON 4½" WALL) 1.00" prevent ripping or other damage to the insulation.
.75"
INTEGRAL SLEEVE &
13/16" FLANGE 3. Opening Size - No expansion clearance is required but
(OPEN CORNER)
sufficient clearance between the damper and the open-
7/8" DIA. HOLE IN ing is required for the insulation and for mounting. The
SLEEVE ON
ACTUATOR SIDE
minimum opening width shall be 3/8" larger than the
FOR WIRING ENTRY. nominal width. The minimum opening height shall be
1
HEAT RESPONSE /4" larger than the nominal height when vertically
DEVICE INSIDE
SLEEVE mounted. When horizontally mounted, the opening
NOMINAL height shall be 3/8" larger than the nominal height. The
WIDTH OR
HEIGHT maximum opening size shall be no more than 1/4"
MINUS ¼"
greater than the minimum opening size.
Example: An 18" wide by 24" high nominal size damper,
GRILLE
CLEARANCE
when mounted vertically, will require a minimum opening
OF 1½"OR 3½" width of 18 3/8" and a minimum opening height of 241/4".
Note, the preceding example is based on the standard
13/16"
20 GA. (MIN.)
20 ga. sleeve.
14 GA. (MAX.)
SLEEVE 4. Duct Mounting - When duct work is connected to the
non-flange end of the damper sleeve, the following
Figure 1 applies:
Sleeves shall be steel of the same gauge or heavier
Vertical (Wall) Mount as the duct to which it is attached. Sleeve gauge
Arrow United Industries
to be 20 ga. (min.), 14 ga. (max.). Connecting
A Division of Mestek, Inc. ducts shall not be continuous, but terminate at
314 Riverside Drive . Wyalusing, PA 18853 damper sleeve.
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
MEMBER OF AMCA
Duct Mounting - (continued) Metal Stud or Masonry Wall Construction
Duct connections to the sleeve will be either of the
breakaway or rigid types. The following determines if the In addition to the previously stated General Requirements,
connections are rigid or breakaway: For rigid type duct the following instructions pertain to block, masonry or
connections, sleeve shall be a minimum of 16 ga. on metal stud construction, See Figure 2.
dampers not exceeding 36" wide or 24" high and 14 ga. on 7. Grille — A minimum 26 ga. steel frame is required,
larger units. The standard factory supplied sleeve is 20 core of grille can be aluminum or nonmetallic. If a
ga. galvanized steel and requires that a breakaway type thinner or non-steel grille frame is used, then open
duct connection will be employed. The following breakaway corners of flanged sleeve must be closed off with 20
duct-to-sleeve connections may be used: Plain “S” Slip, ga. (minimum) corner tabs (by others) riveted to
Double “S” Slip, Inside Slip, Hemmed “S” Slip, Standing flanges. When the flanges are not continuous but
“S” Slip (Bar or Angle Reinforced), Standing “S” Slip formed by a series of flange clips, grille flange must be
(Alternate Bar). Various flanged connection systems are steel of a minimum thickness of 26 ga., See Figure 4.
also approved as breakaway connections. Consult 8. Mounting Damper to Opening - Unlike traditional
manufacturer's instructions for specific details. fire damper installations, this damper requires no
5. Sens-O-Therm Reopenable Feature - This feature perimeter retaining angles. To mount the damper,
allows the damper to be reopened from a remote switch (by insert the damper into the opening until the flange
others) after the low temperature heat responsive device contacts the wall face, See Note 3 for proper open-
has been activated. ing sizing. Through the grille clearance area of the
Operation of optional reopenable (Sens-O-Therm) sleeve, secure the damper to the steel wall stud
feature: framing using #10 steel S.M.S. 12" O.C. (maximum),
A. Master Control Switch in closed position - the damper 6" (maximum) from each corner, minimum of one
will close regardless of whether the thermal switch device fastener per each side, bottom and top. For masonry
has activated or not and regardless of the command from construction, use #10 x 1-1/4 (minimum) steel con-
the smoke detector. crete screws or anchors (same spacing as for steel
B. Master Control Switch in reopen position - if the stud construction). Follow masonry anchor
damper has not been exposed to an elevated temperature manufacturer's recommendations for minimum dis-
higher than its rating, the damper will open. Also, the tance from edge.
damper will open regardless of whether the low limit
switch (either 165°F or 212°F) has actuated or not. If the
damper has been exposed to an elevated temperature
higher than its temperature degradation rating or if the
electrical or pneumatic supply has been disconnected,
the damper will close and remain closed regardless of a
Master Control Switch position.
6. Maintenance - Damper shall be maintained in intervals
as stated in NFPA 90A and 92A unless local codes require
more frequent inspections.

Figure 2
(See Figure 5 for Horizontal Mounting)

Page 2
Wood Stud Wall Construction Flange Clip Mounting
In addition to the previously stated General Requirements,
the following instructions pertain to wood stud construc-
tion walls, See Figure 3.
9. Grille — A minimum 26 ga. steel frame is required,
core of grille can be aluminum or nonmetallic. If a
thinner or non-steel grille frame is used, then open
corners of flanged sleeve must be closed off with 20
ga. (minimum) corner tabs (by others) riveted to
flanges. Grille is attached to either the sleeve flange
or to the wood framing with steel screws 10" maxi-
mum on center.
10. Mounting - The damper is retained in the opening by
Figure 4
the front sleeve flange and rear retaining angles. Rear
perimeter retaining angles to be a minimum size of 11/2"
x 11/2" x 16 Ga. steel or ARROW supplied 11/2" x 7/8" x 16
Ga. steel "Tab-Lock" retaining angles. Angles are
attached to the damper sleeve using #10 steel sheet
metal screws or 3/16" steel rivets at 6" maximum on- For use on damp-
center. ers with one heat
response device
(non-reopenable).

For use on damp-


ers with two heat
response devices
(reopenable).

Figure 3

(See Figure 5 for Horizontal Mounting)

Wiring Schematic

Page 3
Figure 5 -- Horizontal (Floor) Mount

UN-FLANGED SLEEVE,
DAMPER ABOVE FLOOR PLANE

NOTE: WHEN MOUNTED HORIZONTALLY,


FLOOR MUST BE OF MASONRY

8" MAX.

OPENING SIZE
SEE NOTE 3
FACTORY INSULATED
SLEEVE, 4 SIDES
SEE NOTE 10
(SIMILAR)

MASONRY MASONRY
FLOOR FLOOR
FASTENER
SEE NOTE 8

OPENING SIZE FLANGED


SEE NOTE 3 SLEEVE

8" MAX. SEE NOTE 7 FOR


PROPER CLOSING
OF FLANGED
SLEEVE CORNER

FLANGED SLEEVE,
DAMPER BELOW FLOOR PLANE

IF DUCT
CONNECTION,
SEE NOTE 4

Page 4
II-DETECTOR-CDLG-04.12
INSTALLATION INSTRUCTIONS FOR
DUCT SMOKE DETECTORS MOUNTED
ON COMBINATION FIRE/SMOKE
OR SMOKE DAMPERS

Please reference smoke detector manufacturer’s documen- To avoid stratification, detector placement should be such
tation supplied with the damper for additional information. that there is a uniform airflow through the duct. Per NFPA
72, detectors should be at least six duct widths down-
ASSEMBLY APPROVAL stream from any duct openings, sharp bends or branch
connectors.
Underwriters Laboratories Inc. does not have a separate Prod-
uct Category for factory mounted damper/smoke detector as- DAMPERS AVAILABLE
semblies. Individually the smoke detector and the damper
have been evaluated by their applicable UL Standards. It is The smoke detector models listed below can be provided
the responsibility of the Local Authority Having Jurisdiction to with any of the following combination fire/smoke damp-
determine the appropriateness of the smoke detector/damper ers or smoke dampers:
assembly taking into consideration design velocities during
an incident condition and obstructions/duct fittings in prox- Single Thickness & Airfoil Bladed, 1½ & 3 Hr. Rated
imity of the smoke detector. Fire/Smoke, Corridor Fire/Smoke, and Airfoil &
Single Thickness Smoke Only Models.
PURPOSE OF DUCT SMOKE DETECTION
The detector can be provided one of two different ways.
National and local safety standards and codes recognize the The detector can be factory mounted to the sleeve of the
ability of air duct systems to transfer smoke, toxic gases, damper and factory wired to the damper actuator. When
and flame from area to area. Sometimes smoke can be of factory wired, the damper will travel to the “fail” position
such quantity as to be a serious hazard to life safety unless when the detector senses smoke (electrical power dis-
blowers are shut down and dampers are actuated. The pri- connected). The detector can also be factory mounted
mary purpose of duct smoke detection, then, is to prevent to the sleeve of the damper but not wired to the damper
injury, panic, and property damage by reducing the spread actuator. NOTE: Model 2151 must be factory wired.
(recirculation) of smoke. Duct smoke detection can also
serve to protect the air conditioning system itself from fire DUCT DETECTORS AVAILABLE
and smoke damage. Consult NFPA 90A, NFPA 72 and Local
Codes to determine where smoke detectors are required. Two models of detectors are offered, each with specific
application requirements.

TABLE ONE
DAMPER MINIMUM
MODEL SLEEVE DEPTH
Single Thickness &
Airfoil Fire/Smoke
20”
Dampers
Corridor 15½” with flange and 1¾” grille clearance
Fire/Smoke 16¾” with flange and 3” grille clearance
18¾” without a flange

Smoke Only 18”


Note: Additional sleeve length added to actuator
(detector) side.

Commercial Damper / Louver Group


EXTERNAL DUCT MOUNTED — MODEL SM-501-P

This photoelectronic detector mounts externally to the duct


with intake and exhaust sampling tubes penetrating into the
duct. This detector is recommended for ducts, 6 inches and
wider with duct velocities within the 500 fpm to 4000 fpm
range. Since this smoke detector is not rated for use at
velocities below 500 fpm, local code may require an alternate
means of damper closure such as zone detection or auto-
mated damper closure when the system fan is shut down.
The Local Authority Having Jurisdiction should be consulted
EXTERIOR MOUNTED DUCT
prior to the installation of the damper and smoke detector. DETECTOR AND WIRING
For proper air sampling, duct pressure should be a minimum ENCLOSURE (HOUSING EXTENDS
of 0.01 inches of water. Standard location when factory BEYOND FRAME ON SHORT
HEIGHT DAMPERS
mounted will be on the side opposite the damper actuator.
The inlet sampling tube is to be located between blades to
avoid blockage of the airflow past the tube. If the detector is
to be mounted on the actuator side then a longer damper 8” MINIMUM
DAMPER WIDTH
sleeve must be specified at time of order. Note: the damper
2 ¾”
sleeve can extend no more than 16” beyond the face of the
fire barrier. Inlet sampling tube length and orientation are INLET
SAMPLING
critical for proper functioning. The inlet holes in the sampling 10” MIN. TUBE
DAMPER
tube must face into the airflow. The orientation of the inlet HEIGHT
9½”

tube can be easily site rotated for proper airflow orientation.

Inlet sampling tube length requirements: INLET SAMPLING TUBE LOCATED


BETWEEN OPENED BLADES
DAMPER FRAME/SLEEVE
A. The inlet sampling tube must span the duct width. Duct EXTERNAL ACTUATOR
widths must be known at time of order to insure that the
MODEL SM-501-P
proper length of inlet sampling tube will be provided. See
Table Two for appropriate sampling tube part number.
B. Insure that the red end cap is installed in the end of the
inlet sampling tube.
C. For tubes longer than the width of the duct, the tube should
extend out of the opposite side of the duct. Trim the tube
so two inches maximum extend outside of the duct with
the extended end plugged and tape close any holes in the
protruding section of the tube.

GENERAL DESCRIPTION/SPECIFICATIONS TABLE TWO


DUCT INLET SAMPLING
Type: Photoelectronic SM-501-P WIDTH TUBE MODEL
Velocity Range: 500-4,000 fpm
6” to 12” STS-1.0
Operating Temperature Range: 32°F to 100°F.
12” to 30” STS-2.5
Operating Humidity Range: 10% to 85% R.H.
Nominal Voltage: 30” to 60” STS-5.0
230VAC 50-60 Hz., 115 VAC 50-60 Hz., 60” to 120” STS-10.0
24VDC 50-60 Hz., 24 VAC 50-60 Hz.
Contact Ratings:
Alarm: 2 sets of Form “C” rated @10 Amps @ 115VAC
Trouble: 1 set of Form “C” rated @10 Amps @ 115VAC
Agency Listings:
UL 268A; UROX.S2839
MEA Listed: 73-92-EX; Vol. 20
CSFM 3240-1004:108

ADDITIONAL INFORMATION

Reference smoke detector manufacturer’s instructions


packaged with each detector for specific wiring instruc-
tions, maintenance and testing information. The model
SM-501-P detector housing cover must be securely fas-
tened to complete the air-tight enclosure for proper air
sampling.
INTERNAL DUCT MOUNTED — MODEL 2151 ADDITIONAL INSTALLATION REQUIREMENTS
This photoelectronic detector mounts internally within ducts
up to 18 inches in width. Since this detector is mounted These devices will not operate without electrical power. The
within the duct, NFPA requires that means must be pro- Model SM-501-P detector housing is not weather proof and
vided to monitor and test this detector from outside of the if specified, requires the WP-1 NEMA 3R weatherproof en-
duct. To accomplish this requirement, a remote test sta- closure. Location of the detector must not interfere with the
tion (Model RTS451) and a remote test coil kit (Model movement of the damper blades or the damper linkage. All
RTC100) are provided, reference separate instructions and wiring must be installed in compliance with the National
the wiring schematic contained within this booklet. Duct Electrical Code and the local codes having jurisdiction. For
velocity can range from 0 to 3000 fpm. For ducts wider signal wiring (the wiring between detectors or from detec-
than 18 inches with velocities less than 500 fpm, it is rec- tors to auxiliary devices), it is usually recommended that
ommended that multiple detectors 18 inches maximum on single-conductor wire be no smaller than 18 AWG. The
center be installed. Standard location when factory mounted detector terminals accommodate wire sizes up to 14 AWG.
will be the top inside of the damper sleeve. When a smoke detector is controlling a damper driven with
a pneumatic actuator, the pneumatic actuator must be con-
GENERAL DESCRIPTION/SPECIFICATIONS trolled by an E/P valve (solenoid).
Type: Photoelectronic
Velocity Range: 0-3,000 fpm
Operating Temperature Range: 32°F to 120°F.
Operating Humidity Range: 10% to 93% R.H.
Nominal Voltage: MAINTENANCE AND SERVICE OF DUCT DETECTORS
120VAC (Requires Base No. B114LP)
Remote testing: Requires remote test station Smoke detectors are designed to be as maintenance free
RTS451 and remote test coil kit RTC100 for each as possible. However, dust, dirt, and other foreign matter
Model 2151 detector. can accumulate inside a detector and change its sensitiv-
Contact Ratings: See information provided with each ity; this is especially true with duct type smoke detectors.
detector. They can become more sensitive, which may cause un-
wanted alarms, or less sensitive, which may reduce the level
Agency Listings of protection. Both are undesirable. Therefore, detectors
UL 268A, File S911 (N) (Requires remote test coil) should be tested periodically and maintained at regular in-
RR 8281 (City of Los Angeles) tervals. Refer to Section 4-4 and Appendix B of NFPA-90A,
CSFM 7272-1209:159 Chapter 7 of NFPA 72E.

Additional Information: TYPICAL MAINTENANCE PRACTICES

Reference smoke detector manufacturers’ instructions Each installation location must be assessed on its own mer-
packaged with each detector for specific wiring instruc- its. If the protected area is of a very dirty nature, then the
tions, maintenance and testing information. duct units will have to be checked and cleaned on a quar-
TESTING AND MAINTENANCE: terly basis or when cleaning is required. As a guideline, the
detector head should be cleaned every six months or as
Reference smoke detector manufacturers’ instructions on required. Notify the proper authorities that the smoke de-
field testing and recommended/required maintenance. tector system is undergoing maintenance, and therefore the
system will be temporarily out of service. CAUTION: Dis-
able the zone or system undergoing maintenance to prevent
8” MINIMUM unwanted alarms and possible dispatch of the fire depart-
DAMPER WIDTH 4 x 4 STEEL
WIRING ENCLOSURE
ment. The methods of cleaning are to vacuum the detector
CONDUIT
FITTING head thoroughly or to blow the detector head out using com-
pressed air. Do not use chemicals to clean the detector
INTERNAL MOUNTED
DUCT DETECTOR head as this could contaminate the detector head and dam-
10” MIN. age the casing. Sampling tubes must be inspected and
DAMPER
HEIGHT
cleaned in accordance with the schedule as determined
above, to allow the free flow of air through the sensing tube.
Reference instructions packaged with each detector for spe-
cific maintenance and testing information.
EXTERNAL
ACTUATOR
DAMPER FRAME
AND SLEEVE

MODEL 2151
TYPICAL
ELECTRIC
ACTUATOR

MODEL SM-501-P
SMOKE DETECTOR
WIRING SHOWN FOR 115VAC
OPERATION

1 2 3 4 5 6 7 8

H N R G

OPTIONAL
FACTORY WIRING OPTIONAL
REOPENABLE
G N H SITE WIRING
FEATURE

MODEL 2151 2” X 4” WIRING ENCLOSURE WITH


COVER - FACTORY MOUNTED SINGLE GANG BOX TO BE
TO SIDE OF DAMPER REMOTELY MOUNTED MIN. 2½”
4” SQUARE OR OCTAGONAL DEEP (FIELD SUPPLIED)
JUNCTION BOX-MOUNTED
TO TOP INSIDE OF
DAMPER SLEEVE, APPROX. RTS451 REMOTE
MODEL 2151 PHOTOELECTRIC
CENTERED ON WIDTH TEST STATION
SMOKE DETECTOR WITH MODEL SHIPPED LOOSE
B114LP BASE (120 VAC) (BY FACTORY)
B114LP BASE INCLUDES RTC100
TEST COIL

BLACK

BLACK

120 VAC
TEST
ACTUATOR PURPLE COIL

WHITE

HOT COMMON

INCOMING SUPPLY WIRING


BY CUSTOMER (120VAC)

LEAD 1 (HOT)
LEAD 2 (COMMON)
OVERRIDE WIRE WHEN (2) THERMAL GROUND NOTES:
DISCS ARE PROVIDED;
SEE MOTOR SCHEMATIC FOR 1) SMOKE DETECTOR SUPPLY VOLTAGE MUST BE 120 VAC.
SPECIFIC INSTRUCTIONS
2) WIRING SHOWN REQUIRES THAT THE SMOKE DETECTOR
SYSTEM AND THE DAMPER ACTUATOR ARE POWERED
WIRING ENCLOSURE BY A 120 VAC SUPPLY. CONSULT SMOKE DETECTOR
LITERATURE WHEN ACTUATOR REQUIRES 24 VAC
SUPPLY.

OPTIONAL 3) WIRE IDENTIFICATION FOR REFERENCE ONLY.


THERMAL DISC FACTORY SITE
(1 OR 2) WIRING WIRING
AI-AS CDLG-04.11
INSTALLATION INSTRUCTIONS
FIRE/LEAKAGE RATED DAMPER
MULTI-BLADE FIRE RATED DAMPERS, SINGLE THICKNESS AND
AIRFOIL BLADE DESIGN 1½ HR. RATED FIRE SMOKE DAMPERS

TYPICAL WALL INSTALLATION


These dynamically rated fire/smoke and fire dampers are factory
sealed into the provided sleeve and must be positioned so that it
is within the fire rated masonry, block or gypsum wallboard barrier,
when the damper is intended to be used as a fire rated damper.
When the damper is to be used as a leakage rated damper only, it
is to be installed within 24" of the smoke barrier and be upstream
of any duct outlets.

This damper may be mounted in the vertical or horizontal position


with the damper blades running horizontal. These dampers may
be mounted right side up or upside down.

Dampers are supplied with factory mounted actuators (except


Multi-Blade Fire Dampers) and are intended to close automatically
when sensing heat or upon loss of electrical power or release of
air pressure. When this damper is used as a leakage rated
damper only, it shall be arranged to operate automatically and is to
be controlled by a smoke detector. See additional instructions,
which detail damper actuator sequence of operations.

A duct access door is to be located on the jackshaft side of each


damper.

MOUNTING:
1. The installation of the damper and all duct connections to the
damper sleeve shall conform to NFPA-90A and the SMACNA
Fire, Smoke and Radiation Damper Installation Guide. All duct
connections shall also conform to UL555 when the damper is
intended to be used as a fire damper.
2. Sleeves shall be the same gauge or heavier as the duct to
which it is attached. Gauges shall conform to SMACNA or
ASHRAE duct standards.
3. The damper is normally supplied with a factory attached sleeve
(see Note 11 when field supplied sleeve). Duct connections
to the sleeve will be either of the breakaway or rigid types that
are listed below. The following determines if the connections
are to be rigid or breakaway. For rigid type duct connections,
sleeve shall be a minimum of 16 GA on dampers not exceed-
ing 36" wide or 24" high or 24" diameter and 14 GA on larger
units. Maximum sleeve thickness will not exceed 10 GA
galvanized steel. Dampers supplied with thinner sleeves will
require a breakaway connection of the types listed in Note 5.
The standard factory supplied sleeve is 20 GA galvanized steel
(18 GA on dampers wider than 84") and assumes that a
breakaway type duct connection will be employed.
4. Duct connections not listed as breakaways (See Note 5) shall
be considered rigid. Breakaway joints shall have no more than
two No. 10 sheet metal screws on each side and on the
bottom. The screws shall penetrate both sides of the slip
pocket. When a breakaway joint is used along the top and
bottom duct connection, a flat drive slip no longer than 20
inches is permitted on the two sides.

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
MEMBER OF AMCA www.arrowunited.com
MOUNTING (cont.)
5. The following breakaway duct-to-sleeve connections may be used: Plain “S” Slip, Double “S” Slip, Inside Slip,
Hemmed “S” Slip, Standing “S” Slip, Standing “S” Slip (Bar Reinforced), Standing “S” Slip (Angle Reinforced) and
Standing “S” Slip (Alternate Bar).
6. All connecting ducts shall not be continuous but shall terminate at the fire damper sleeve. Connecting ducts are at-
tached to the damper sleeve as instructed by Notes 3, 4 and 5.
7. The opening in the wall for the fire/leakage rated damper shall be sized so as to provide expansion clearance between
the sleeve and the opening of a minimum of 1/8" per foot of overall damper/sleeve width and height. The maximum
opening size shall not exceed 1/8" per foot plus 1"; minimum total clearance shall be at least 1/4" larger than the overall
assembly. Perimeter mounting angles shall increase in size, proportionately, so there will be a minimum of 1" of overlap
on the wall, including at the corners, and the angles shall be flush against the wall.
8. Fasten the perimeter mounting angles on all four sides and on both faces of the damper to the sleeve only, with 1/4"
diameter steel or stainless steel nuts and bolts or by tack welding with beads 1/2" ± 1/4" in length or with #10 steel or
stainless steel sheet metal screws or 3/16" steel or stainless steel pop rivets. All connections shall be spaced a maxi-
mum of 6" on center and shall have a connection not more than 3" from each corner, (1" on the alternate assembly).
Perimeter mounting angles shall be a minimum of 1-1/2" x 7/8" 16 gauge steel. Corners of angles are not welded together
for dampers whose width or height exceeds 24". For dampers 24" x 24" or smaller, the corners of the perimeter mount-
ing angles can be welded. Some local codes may not allow welded corners. Perimeter angles and their mounting
fasteners are not normally supplied with the damper. Attachment of these angles must not restrict operation of the
damper.
9. Caulking is allowed between the mounting angles and the damper sleeve, and between the mounting angles and the
floor or wall construction. Caulk shall be one of the following: Dow Corning RTV732, General Electric IS808 or Novagard
RTV300. Caulking is not allowed between the damper sleeve and the wall or floor inside the opening.
10. Dampers shall be maintained in intervals as stated in NFPA 90A and 92A unless local codes require more frequent
inspections.
11. Single panel dampers with factory mounted internal actuators can be supplied without sleeves. See Note 2 for required
sleeve gauge thickness. Field supplied sleeve is attached to damper frame with 3/16" diameter steel rivets, ¼" diameter
steel bolts, #10 steel sheet metal screws or ½" long welds. Fasteners to be staggered on each side of the damper
frame at 6"maximum centers and 3-½" maximum from each corner.

INSTALLATION INSTRUCTIONS FOR ELECTRIC OR PNEUMATIC REOPENABLE (SENS-O-THERM) FIRE/LEAKAGE


RATED DAMPERS WITH POSITION INDICATOR SWITCHES. DAMPER IS SUPPLIED WITH ONE HIGH LIMIT AND
ONE LOW LIMIT THERMAL DISC. ALL DAMPERS REQUIRE A MASTER CONTROL SWITCH FOR REOPENABLE
OPERATION. SEE PAGE 5 FOR WIRING SCHEMATIC.
CUSTOMER WIRING
a. Connect input power L1 from the normal position lead of the
(MCS) switch to damper lead L1.
CIRCUIT TEST
NOTE:
1. Place (MCS) switch in center closed position.
If a smoke detector or other sensing device is to be employed, its N.C.
2. Apply power.
contact set should be wired in series between the (MCS) position
RESULT: The closed indicator light (if used) should now be on
switch normal wire and Lead L1.
and the damper blades closed.
b. Connect incoming L2 to damper L2 3. Transfer (MCS) switch to reopen position.
c. Connect the reopen switch lead from (MCS) to orange damper lead. RESULT: The damper blades should open; the closed indicator
d. Connect the incoming ground to the wiring enclosure. light (if used) should go off and the open indicator light (if used)
e. Replace enclosure cover. should go on.
4. Transfer (MCS) switch to the normal position.
EMERGENCY OPERATION (SMOKE MANAGEMENT): RESULT: The damper blades should remain open and the open
1. MCS closed position--Damper will close regardless of whether the indicator light (if used) should remain on.
thermal switch device has activated or not and regardless of the 5. Transfer the (MCS) switch to the closed position.
command from the smoke system. RESULT: The damper blades should close; the open indicator
2. MCS reopen position--If the damper has not been exposed to an light (if used) should go off and the closed indicator light (if
elevated temp. higher than its rating, the damper will open. Also, the used) should come on.
damper will open regardless of whether the low limit thermal switch
either (165º F or 212ºF) has activated or not and regardless of a
command from additional sensing devices such as a smoke detector.
NOTE: If the master control switch (MCS) is in the reopen position and the
high temperature thermodisc has not been tripped, the damper will
remain open regardless of whether the low temperature thermodisc
and/or other sensing devices have tripped or not. If the damper has
been exposed to an elevated temperature higher than its temperature
degradation rating or if the electrical or pneumatic supply has been
disconnected, the damper will close and remain closed regardless of
any (MCS) position.

2
MULTIPLE PANEL SIZE LIMITATIONS
AIRFOIL FIRE SMOKE DAMPER - Vertical Mount (UA)
MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS
MS4209, 4309 32" x 24" 128" x 24" 4
MS8209, 8309
331-2996 32" x 48" 128" x 48" 4
MS4120, 8120 32" x 48" 128" x 96"** (4x2) 8 Acts.

AIRFOIL FIRE SMOKE DAMPER- Horizontal Mount (UA)


MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS
MS4209, 4309 32" x 24" 96" x 24" 3
MS8209, 8309
331-2996 32" x 48" 96" x 48" 3
MS4120, 8120 32" x 48" 96" x 96"** (3x2) 6 Acts.

SINGLE THICKNESS FIRE DAMPER- Vertical Mount (MD)


MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS
Spring / Fuse Link 36" x 48" 126" x 48" 4
Spring / Fuse Link 36" x 48" 72" x 60"** 4

SINGLE THICKNESS FIRE DAMPER - Horizontal Mount (MD)


MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS
Spring / Fuse Link 36" x 48" 72" x 48"* 2
AIRFOIL FIRE DAMPER - Vertical or Horizontal Mount (MA)
MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS
Spring / Fuse Link 32" x 48" Single Panel Only 1

SINGLE THICKNESS FIRE SMOKE DAMPER - Vertical Mount (AS)


MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS

MS4209, 4309 36" x 36" 108" x 36" 3


MS8209, 8309 48" x 24" 96" x 24" 2
FSNF120, 24

MS4120, 8120 36" x 48" 108" x 48" 3


48" x 36" 96" x 36" 2

GGD121, 221, 321 36" x 48" 108" x 48" 3


331-2996

331-2977 36" x 36" 108" x 36" 3

SINGLE THICKESS FIRE SMOKE DAMPER - Horizontal Mount (AS)


MAX. W x H MAX. W x H MAX. PANELS
ACTUATOR SINGLE MULTIPLE PANEL WIDE & QTY.
TYPE SECTION (in.) ASSEMBLY(in.) OF ACTUATORS

MS4209, 4309
MS8209, 8309
36" x 36" 72" x 36" 2
FSNF120, 24 *
331-2977

MS4120, 8120
GGD121, 221, 321 36" x 48" 72" x 48"* 2
331-2996

* See Page 8 for Mullion Stiffener Detail


** See Page 7 for Mullion Stiffener Detail
3
EXPANSION CLEARANCE OF
1
1" MINIMUM /8" PER FOOT OF DAMPER
SEE NOTE ON DUCT OVERLAP WIDTH AND HEIGHT, 1/4"
CONNECTION METAL STUD MINIMUM. MAXIMUM
CONSTRUCTION CLEARANCE OF 1/8" PER
FOOT PLUS 1".

SEE NOTE #8 FOR


ATTACHMENT METHOD

NOTE: SEE SUPPLEMENTAL


INSTALLATION INSTRUCTIONS
A33129 FOR ONE-SIDE MOUNTING
WITH RETAINING ANGLE UNDER
THE GYPSUM WALLBOARD

1- 1/ 2" x 7/ 8 " x 16 GA.


(MINIMUM SIZE) STEEL
RETAINING ANGLES,
CLOSED CORNERS

16" MAXIMUM ON SIDE


WITH FACTORY INSTALLED
ACTUATOR OR FACTORY 6" MAXIMUM ON NON-
INSTALLED ACCESS DOOR WOOD STUD MOTOR FACE OR NON-
CONSTRUCTION ACCESS-DOOR SIDE

WALL / PARTITION CONSTRUCTION


VARIES, PER TESTED DESIGN

ONE SIDE MOUNTING, ANGLES


OUTSIDE GYPSUM WALLBOARD
APPLICATION
These instructions illustrate alternate mounting of Classified 4. Steel retaining angles must be attached to both the damper
fire and fire/smoke dampers to a rated wall or partition from sleeve and to the partition framing on all four sides of this one
one side only. The steel retaining angles are on the outside face mounting method.
face of the gypsum board and on the outside of the ma- A. Damper sleeve to retaining angles attached 6" maximum
sonry or concrete wall or partition. on-centers, 3" maximum from each corner, minimum of two
1. This installation is limited to the following: fasteners per side by the following means:
A. Two hour or less rated wall or partition. 1. 3/16" diameter steel bolts and nuts,
B. Vertically mounted damper. 2. Welding, 1/2" long beads,
C. Wood stud/metal stud gypsum board construction as 3. #10 steel sheet metal screws,
well as masonry/concrete construction. 4. 3/16" diameter steel rivets.
D. Maximum size damper of 48" wide x 36" high or 36" B. Retaining angles to gypsum board wall framing attached
wide x 48" high. using drywall screws 6" maximum on-centers, 3" maximum
2. See page 6 for opening framing details. from each corner, minimum of two fasteners per side.
3. Closed plane of damper blades must be within the plane C. Retaining angles to concrete or masonry attached using
3
of the rated wall or partition. /16" steel masonry fasteners 6" maximum on-centers, 3"
maximum from each corner, minimum of two fasteners per
side.
4
ELECTRIC WIRING SCHEMATICS

This schematic is used for dampers This schematic is used for dampers supplied
supplied with a single thermal switch. with the Sens-O-Therm, reopenable feature
(two thermal switches).

NOTES:
1. All wiring to be in accordance with N.E.C. (NFPA-70).
2. Refer to actuator label for appropriate voltage.
3. Connect incoming ground to the actuator assembly.
4. If the actuator is electrically energized yet the damper
remains in the closed position, check that the reset button
on the heat response device is depressed.
5. Optional auxiliary blade position indication switches are
rated at 1A, 1/3HP, 125VAC. These snap action switches
are intended to make or break a circuit and will not provide
variable or proportional resistance.

This schematic is used to wire auxiliary blade


position indication switches.

5
INSTALLATION INSTRUCTIONS FOR 1-1/2 HOUR
UL CLASSIFIED FIRE DAMPERS INSTALLED INTO
METAL OR WOOD FRAMED 1 HOUR AND 2 HOUR RATED DRYWALL PARTITIONS

NOTES:
1. These illustrated partition designs have
successfully been tested in conjunction with
1-1/2 hour classified fire dampers, for
additional designs, reference Underwriters
Laboratories, Inc. Fire Resistance Directory.
Specific framing requirements of openings
may vary with the Local Authority that has
jurisdiction. Specific framing requirements
should be provided in the architectural and
structural drawings.

2. Reference the damper's installation


instructions regarding the approved method
of attaching the damper to the sleeve,
attaching the retaining angles to the sleeve,
required expansion clearances, sleeve
gauge, etc. Type of framing does not affect
the stated required expansion clearance.

3. Gypsum panels surrounding the opening are


to be fastened to all stud and runner
flanges, 12" o.c. maximum.

4. When wooden studs are used, filler pieces


must be installed around the entire opening.
Filler pieces are optional when metal studs
are used (consult local codes to determine if
filler pieces are required). Filler pieces are
to be double screwed (or nailed to wooden
studs) on 12" max. centers to the web of
runners and studs.

5. Double jamb studding shown and required


when opening width or length exceeds 36".
Single jamb studding acceptable for
openings 36" x 36" and smaller.

6
FABRICATION AND INSTALLATION INSTRUCTIONS FOR
TWO PANEL HIGH MULLION STIFFENER

Purpose When Required


This factory or field fabricated This 12 GA steel flat plate is sandwiched
plate reinforces the damper's between the damper's vertical frame
vertical mullion to prevent members at its vertical mullion. This
excessive mullion deflection. stiffener is required whenever the
damper assembly is both multiple panels
wide and multiple panels high.

1
2
1 One piece full height 6" by
12 GA steel plate.

2 1/4" Steel bolts and nuts on 12"


max. centers, staggered on both
faces. First fastener 6" maximum
from each end. Ends of plate do
not need to be attached to top and
bottom of sleeve.

3 Vertical damper Mullion

Notes
1. When assembly is ordered with a factory supplied sleeve, this mullion stiffener
will be factory furnished and installed.
2. When assembly is ordered without a factory supplied sleeve, this mullion stiff-
ener is to be field fabricated and field installed.

INSTALLATION OF MULTIPLE SHIP SECTION DAMPER ASSEMBLIES


Large damper openings may require multiple factory assembled modules to fill the opening. After
placing the modules into the opening, the individual modules are fastened together using ¼”
diameter steel bolts, lockwashers, and nuts. Fasteners are to be on 6” maximum centers and on
both faces of the sleeve.

7
FABRICATION AND INSTALLATION INSTRUCTIONS
FOR MULLION ANGLE WHEN HORIZONTALLY MOUNTED

PURPOSE: WHEN REQUIRED:


This factory or field fabricated angle/strap assembly This angle/strap assembly is centered above the
reinforces the damper mullion to prevent excessive damper mullion (located where two damper panels
mullion deflection during exposure to a fire. butt together) when the damper is mounted horizon-
tally. This reinforcement is required only on multiple
panel assemblies when the damper height (dimension
perpendicular to blade span) exceeds 26 inches.

1 4" x 1" x 16GA (minimum required size) galvanized steel angle, length of angle same as inside sleeve height.

2 16 GA (minimum thickness) tab (stitch welded) or angle (stitch welded or mechanically attached with two fasten-
ers -- see below) to each end of angle which permits angle assembly to be stitch welded or mechanically attached
to the sleeve. Fasteners to be steel, No. 10 S.M.S., 3/16" dia. rivets, or No. 10 bolts; two at each tab.

3 8" x 3/4" x 20GA (minimum required size) galvanized steel strap attached to damper mullion with one fastener,
attached to angle with two fasteners (see note 2 for type of fastener). Number of straps required:
A. All single panel and multiple panel assemblies not exceeding 26" in height do not require a mullion angle.
B. Multiple panel assemblies exceeding 26" but not exceeding 36" in height require one strap centered along the
damper height.
C. Multiple panel assemblies exceeding 36" in height require two straps, 6" to each side of the damper mid-height.

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com

MEMBER OF AMCA

8
AII-AS2C CDLG-04.8
INSTALLATION INSTRUCTIONS
FIRE/LEAKAGE RATED CORRIDOR DAMPERS

APPLICATION INSTALLATION
This Corridor Damper is Classified by Underwrit- Several methods of installing this damper are il-
ers Laboratories for One Hour Fire Resistance and lustrated in this booklet. Depending on method
as a Class II 250°F Leakage Rated Damper to UL chosen, expansion clearance and perimeter
Standard 555S. This damper is to be mounted hori- mounting angles may not be required. Regard-
zontally into ceilings of fire rated corridors where less of installation method used, the damper frame
permitted by the Authority Having Jurisdiction. Mini- is to be square and not distorted. Frame distor-
mum ceiling construction requirements are illus- tion can result in reduced leakage resistance or
trated later in this booklet. This damper is supplied incomplete closure.
with a factory mounted actuator and is intended to
close automatically when sensing elevated tem- 1. The installation of the damper and all duct con-
perature or upon loss of electrical power. Damper nections to the damper sleeve shall conform to
will close within 15 seconds. If closed due to loss NFPA-90A and the SMACNA Fire, Smoke and
of electrical power, the damper will reopen when Radiation Damper Installation Guide. All duct
electrical power is restored. An aluminum or steel connections shall also conform to UL555.
grille can be installed below the damper as long as
the grille does not interfere with the closure of the 2. Sleeves shall be the same gauge or heavier as
damper. the duct to which it is attached. Gauges shall
conform to SMACNA duct standards.
Wiring Diagram
3. The damper is supplied with a factory attached
sleeve. Duct connections to the sleeve will
be either of the breakaway or rigid types that
are listed below. The following determines if
the connections are to be rigid or breakaway.
For rigid type duct connections, sleeve shall
be a minimum of 16 GA. Maximum sleeve
thickness will not exceed 10 GA. galvanized
steel. Dampers supplied with thinner sleeves
will require a breakaway connection of the
types listed in Note 5. The standard factory
supplied sleeve is 20 GA. galvanized steel and
assumes that a breakaway type duct connec-
tion will be employed.

4. Duct connections not listed as breakaways


(See Note 5) shall be considered rigid.
Breakaway joints shall have no more than two
No. 10 sheet metal screws on each side and
on the bottom. The screws shall penetrate both
sides of the slip pocket. When a breakaway
joint is used along the top and bottom duct con-
nection, a flat drive slip no longer than 20 inches
is permitted on the two sides.

Arrow United Industries


These Installation Instructions comply A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
with Underwriters Laboratories Inc. Ph: (570) 746-1888 Fax: (570) 746-9286
Safety Standard 555 and 555S. MEMBER OF AMCA www.arrowunited.com
Installations (Con’t.)
5. The following breakaway duct-to-sleeve connec- 7. Ducts connected to round or flat oval transitions
tions may be used: Plain “S” Slip, Double “S” are connected either with a four inch wide draw
Slip, Inside Slip Joint, Hemmed “S” Slip, Stand- band or by attaching the duct to the factory sup-
ing “S” Slip (Bar Reinforced), Standing “S” slip plied transition collar with a maximum of three
(Angle Reinforced) and Standing “S” Slip (Alter- equally spaced No. 10 sheet metal screws.
nate Bar).
8. Various brands of manufactured flanged connec-
6. All connecting ducts shall not be continuous but tions can be used as breakaway connections
shall terminate at the fire damper sleeve. Con- as long as they are installed as shown by Figure
necting ducts are attached to the damper sleeve 5-2 of the 5th Edition of SMACNA’s Fire, Smoke
as instructed by Notes 3, 4 and 5. and Radiation Damper Installation Guide.

ELECTRICAL CONNECTIONS
Electrical Connections and sequence of operations for fire/leakage rated Corridor Damper.
Damper supplied with one manually resettable thermal device.
Read Before Installation
1. Make sure that the electrical thermal device has 6. Circuit test:
been set. Simply push the red button located by A. Caution-when operating damper, keep fingers
the motor. and clothing away from damper blades.
B. Make sure that the proper electrical power
2. All wiring to be in accordance with N.E.C.
source has been supplied; 24VAC or 120VAC.
(NFPA-70).
C. Apply power, the damper blades should open.
3. Indentify actuator model number, check its op- D. Disconnect power; the damper blades should
erating voltage and current requirements. This close.
information is shown on a label on or near the
E. To check the electric resettable thermo device;
actuator.
1. Apply electrical power (damper blades
4. Electrical supply is connected to terminals L1 opened).
and L2, reference wiring schematic. Connect 2. Hold a lit match or lighter near the face of
the incoming ground to the wiring enclosure. the thermal device. A faint click should be
heard and the damper blades should close.
5. If a smoke detector or other sensing device is to
be employed, it should be wired in series with 3. After the thermal disc has cooled, push the
L1 and the damper. red reset button and the damper blades
should reopen.

ACTUATOR ACTUATOR VOLTAGE MAX. VEL. MAX. TEMP. MAX. DAMPER


LOCATION MODEL NO. (FPM) RATING SIZE W X H
Internal or External ML8115 24VAC 2000 250°F 24 x 24

Internal or External ML4115 120VAC 2000 250°F 24 x 24

Internal or External ML8202/8302 24VAC 2000 250ºF 1.0 sq. ft.

Internal or External ML4202/4302 120VAC 2000 250ºF 1.0 sq. ft.

2
24” C/C (2) 16d NAILS (TYP)
MAX.
UL CLASSIFIED 5/8” THICK GYP-
SUM WALLBOARD APPLIED TO
EACH SIDE OF WOOD FRAMING
ATTACHED WITH 6d NAILS 7” O.C.
OR WITH 1-5/8” LONG DRYWALL 2x4
SCREWS 12” O.C. WOOD STUD

REF. UL DESIGNS
U309, U314
SINGLE LAYER OF 5/8” THICK (GA FILE WP3510)
UL CLASSIFIED WALLBOARD FOR ADDITIONAL
LINING OPENING DETAILS

SINGLE STUDDING

WOOD FRAMING CONSTRUCTION


(MIN. REQUIREMENTS)
WEB BENT OVER AND
ATTACHED WITH (2) 1/2”
24” C/C LONG STEEL SCREWS
MAX. OR BY WELDING
UL CLASSIFIED 5/8” THICK
GYPSUM WALLBOARD APPLIED
TO EACH SIDE OF STEEL
FRAMING ATTACHED WITH 1”
DRYWALL SCREWS 12” O.C. 3-1/2” DEEP
STEEL STUD

REF. UL DESIGN
U425 (GA FILE WP 1206)
SINGLE
FOR ADDITIONAL DETAILS.
STUDDING
ALSO, REFERENCE UL
DESIGN U469 FOR AN
2 ADDITIONAL APPROVED
8 METAL STUD CONSTRUCTION.
2
SEE SHEET A10-27502
WHEN DESIGN U469 IS USED.
RUNNER CUT AND
BENT DOWN, ATTACH
TO STUD WITH (4) 1/2”
LONG STEEL SCREWS

STEEL FRAMING CONSTRUCTION


(MIN. REQUIREMENTS)

NOTE: If ceiling construction varies from details shown above,


consult local Authority Having Jurisdiction (AHJ) or project
Architect / Engineer for ceiling acceptance. 3
DUCT CONNECTION TO
DAMPER SLEEVE TO BE A
BREAKAWAY TYPE CONNECTION

STANDARD
MAXIMUM

ZERO TO 1/2”

6-15/16”
CLEARANCE
16”

STANDARD
(REF.)

SEE NOTE 1

16”

STANDARD
MAXIMUM

SEE SEPARATE

3-9/16”
DETAIL FOR CEILING
6”

CONSTRUCTION

FASTEN THE PERIMETER MOUNTING ANGLES ON ALL FOUR SIDES NOTES:


OF THE DAMPER TO THE SLEEVE ONLY, WITH 1/4” DIAMETER STEEL 1. CLOSED PLANE OF DAMPER BLADES MUST BE
OR STAINLESS STEEL NUTS AND BOLTS OR BY TACK WELDING WITHIN THE CEILING OR NO MORE THAN 1-1/2”
WITH BEADS 1/2” +/- 1/4” IN LENGTH OR WITH #10 STEEL OR STAIN- AWAY FROM THE FACE OF THE CEILING.
LESS STEEL SHEET METAL SCREWS OR 3/16” STEEL OR STAINLESS 2. SHOWN INSTALLED IN WOOD FRAMING.
STEEL POP RIVETS. ALL CONNECTIONS SHALL BE SPACED A INSTALLATION IN STEEL FRAMING IS SIMILAR.
MAXIMUM OF 8” ON CENTER AND SHALL HAVE A CONNECTION
NOT MORE THAN 3” FROM EACH CORNER. PERIMETER MOUNT-
ING ANGLES SHALL BE A MINIMUM OF 7/8 x 1 x 16 GA. STEEL AND
LAP THE CEILING BY A MINIMUM OF 1”. THE CORNERS OF THE
PERIMETER MOUNTING ANGLES CAN BE WELDED. SOME LOCAL
CODES MAY NOT ALLOW WELDED CORNERS. PERIMETER MOUNT-
ING ANGLES AND THEIR MOUNTING FASTENERS ARE NOT NOR-
MALLY SUPPLIED WITH THE DAMPER. ATTACHMENT OF THESE
ANGLES MUST NOT RESTRICT OPERATION OF THE DAMPER.

NON-FLANGED SLEEVE

4
DUCT CONNECTION TO
DAMPER SLEEVE TO BE A
BREAKAWAY TYPE CONNECTION

MAXIMUM
ZERO TO 3/16”

16”
CLEARANCE
STANDARD SLEEVE

16”
DEPTH WITH 3”
GRILLE CLEARANCE

9-1/16”
(REF.)

3”
SEE SEPARATE DETAIL ¾ GRILLE CLEARANCE
FOR CEILING CONSTRUCTION
10d STEEL NAILS OR #12 x 2” 1g STEEL
NOTE: SCREWS 6” MAXIMUM O.C., 3” MAXIMUM FROM
SHOWN INSTALLED IN WOOD FRAMING. INSTALLATION CORNERS. NAILS TO BE SET AS SO AS NOT TO
IN STEEL FRAMING IS SIMILAR. WHEN STEEL FRAMING, DISTORT DAMPER SLEEVE. FRAME DISTORTION
OPENING NEED NOT BE LINED WITH GYPSUM BOARD. CAN RESULT IN REDUCED LEAKAGE RESISTANCE
WHEN STEEL FRAMING AND NO OPENING LINING, OR INCOMPLETE CLOSURE. WHEN THE 3/4” FLANGES
#12 x 1” LONG (MINIMUM) STEEL SHEET METAL ARE SHIPPED LOOSE, USE THE SAME FASTENERS TO
SCREWS 6” MAXIMUM O.C., 3” MAXIMUM FROM ATTACH THE FLANGES THAT ATTACH THE
CORNERS. WHEN STEEL FRAMING AND OPENING DAMPER TO THE FRAMING.
LINING, SCREWS TO BE 1-1/2” MINIMUM LENGTH.

FLANGE EXPOSED, NO PERIMETER MOUNTING


ANGLES, 3” GRILLE CLEARANCE
Not Approved for the City of Los Angeles

DUCT CONNECTION TO
DAMPER SLEEVE TO BE A
BREAKAWAY TYPE CONNECTION
MAXIMUM

ZERO TO 3/16”
16”

CLEARANCE

STANDARD SLEEVE
14¾” DEPTH WITH 3”
GRILLE CLEARANCE
13
7- /16”
(REF.)

1¾”

¾ GRILLE CLEARANCE
SEE SEPARATE DETAIL
FOR CEILING CONSTRUCTION
10d STEEL NAILS OR #12 x 2” 1g STEEL
NOTE:
SCREWS 6” MAXIMUM O.C., 3” MAXIMUM FROM
SHOWN INSTALLED IN WOOD FRAMING. INSTALLATION
CORNERS. NAILS TO BE SET AS SO AS NOT TO
IN STEEL FRAMING IS SIMILAR. WHEN STEEL FRAMING,
DISTORT DAMPER SLEEVE. FRAME DISTORTION
OPENING NEED NOT BE LINED WITH GYPSUM BOARD.
CAN RESULT IN REDUCED LEAKAGE RESISTANCE
WHEN STEEL FRAMING AND NO OPENING LINING,
OR INCOMPLETE CLOSURE. WHEN THE 3/4” FLANGES
#12 x 1” LONG (MINIMUM) STEEL SHEET METAL
ARE SHIPPED LOOSE, USE THE SAME FASTENERS TO
SCREWS 6” MAXIMUM O.C., 3” MAXIMUM FROM
ATTACH THE FLANGES THAT ATTACH THE
CORNERS. WHEN STEEL FRAMING AND OPENING
DAMPER TO THE FRAMING.
LINING, SCREWS TO BE 1-1/2” MINIMUM LENGTH.

FLANGE EXPOSED, NO PERIMETER MOUNTING


ANGLES, 1¾” GRILLE CLEARANCE
Not Approved for the City of Los Angeles
5
DUCT CONNECTION TO
DAMPER SLEEVE TO BE A
BREAKAWAY TYPE CONNECTION

ZERO TO 3/16”

MAXIMUM
CLEARANCE

16”
STANDARD SLEEVE

16”
DEPTH WITH 3”
GRILLE CLEARANCE
9-1/16”

(REF.)

3”
GRILLE CLEARANCE
SEE SEPARATE DETAIL
FOR CEILING CONSTRUCTION #12 x 1” LONG STEEL SHEET METAL SCREWS
6” MAXIMUM O.C., 3” MAXIMUM FROM
NOTE: CORNERS. SCREWS TO BE SET SO AS NOT
STEEL FRAMING ONLY, OPENING NEED TO DISTORT DAMPER SLEEVE. DAMPER
NOT BE LINED WITH GYPSUM BOARD. SLEEVE FRAME CAN RESULT IN REDUCED
WHEN STEEL FRAMING AND LINING, LEAKAGE RESISTANCE OR INCOMPLETE
DAMPER ATTACHED TO FRAMING WITH CLOSURE. WHEN THE 3/4” FLANGES ARE
#12 x 1-1/2” LONG STEEL SHEET SHIPPED LOOSE, USE THE SAME FASTENERS
METAL SCREWS 6” MAXIMUM O.C., TO ATTACH THE FLANGES THAT ATTACH THE
3” MAXIMUM FROM CORNERS. DAMPER TO THE FRAMING.

FLANGE CONCEALED, NO PERIMETER MOUNTING


ANGLES, 3” GRILLE CLEARANCE
Not Approved for the City of Los Angeles

DUCT CONNECTION TO
DAMPER SLEEVE TO BE A
BREAKAWAY TYPE CONNECTION
MAXIMUM

ZERO TO 3/16”
CLEARANCE
16”

STANDARD SLEEVE
14¾ DEPTH WITH 3”
GRILLE CLEARANCE
7-13/16”
(REF.)

1¾”

GRILLE CLEARANCE

SEE SEPARATE DETAIL #12 x 1” LONG STEEL SHEET METAL SCREWS


FOR CEILING CONSTRUCTION 6” MAXIMUM O.C., 3” MAXIMUM FROM
CORNERS. SCREWS TO BE SET SO AS NOT
NOTE: TO DISTORT DAMPER SLEEVE. DAMPER
STEEL FRAMING ONLY, OPENING NEED SLEEVE FRAME CAN RESULT IN REDUCED
NOT BE LINED WITH GYPSUM BOARD. LEAKAGE RESISTANCE OR INCOMPLETE
WHEN STEEL FRAMING AND LINING, CLOSURE. WHEN THE 3/4” FLANGES ARE
DAMPER ATTACHED TO FRAMING WITH SHIPPED LOOSE, USE THE SAME FASTENERS
#12 x 1-1/2” LONG STEEL SHEET TO ATTACH THE FLANGES THAT ATTACH THE
METAL SCREWS 6” MAXIMUM O.C., DAMPER TO THE FRAMING.
3” MAXIMUM FROM CORNERS.

FLANGE CONCEALED, NO PERIMETER MOUNTING


ANGLES, 1¾” GRILLE CLEARANCE
Not Approved for the City of Los Angeles
6
DUCT CONNECTION TO
DAMPER SLEEVE TO BE A
BREAKAWAY TYPE CONNECTION

ZERO TO 1/4”
TOTAL CLEARANCE

MAXIMUM
16”
STANDARD SLEEVE

16”
DEPTH WITH 3”
GRILLE CLEARANCE
9-1/16”
(REF.)

3”

SEE SEPARATE DETAIL ¾ GRILLE CLEARANCE


FOR CEILING CONSTRUCTION
FASTEN THE PERIMETER MOUNTING ANGLES ON ALL FOUR SIDES OF
THE DAMPER TO THE SLEEVE ONLY, WITH 1/4” DIAMETER STEEL OR
NOTE: STAINLESS STEEL NUTS AND BOLTS OR BY TACK WELDING WITH
SHOWN INSTALLED IN WOOD BEADS 1/2” + 1/4” IN LENGTH OR WITH #10 STEEL OR STAINLESS STEEL
FRAMING. INSTALLATION IN SHEET METAL SCREWS OR 3/16” STEEL OR STAINLESS STEEL POP
STEEL FRAMING IS SIMILAR. RIVETS. ALL CONNECTIONS SHALL BE SPACED A MAXIMUM OF 8” ON
CENTER AND SHALL HAVE A CONNECTION OF NOT MORE THAN 3” FROM
EACH CORNER. PERIMETER MOUNTING ANGLES SHALL BE A MINIMUM
OF 7/8” x 1 x 16 GA. STEEL AND LAP THE CEILING BY A MINIMUM OF 1”.
THE CORNERS OF THE PERIMETER MOUNTING ANGLES CAN BE WELDED.
PERIMETER ANGLES AND THEIR MOUNTING FASTENERS ARE NOT
NORMALLY SUPPLIED WITH THE DAMPER. ATTACHMENT OF THESE
ANGLES MUST NOT RESTRICT OPERATION OF THE DAMPER.

FLANGE EXPOSED, PERIMETER MOUNTING


ANGLES, 3” GRILLE CLEARANCE

DUCT CONNECTION TO
DAMPER SLEEVE TO BE A
BREAKAWAY TYPE CONNECTION

ZERO TO 1/4”
TOTAL CLEARANCE
MAXIMUM
16”

STANDARD SLEEVE
14¾” DEPTH WITH 1-3/4”
GRILLE CLEARANCE
7-13/16”
(REF.)

1¾”

¾ GRILLE CLEARANCE
SEE SEPARATE DETAIL
FOR CEILING CONSTRUCTION
FASTEN THE PERIMETER MOUNTING ANGLES ON ALL FOUR SIDES OF
NOTE: THE DAMPER TO THE SLEEVE ONLY, WITH 1/4” DIAMETER STEEL OR
SHOWN INSTALLED IN WOOD STAINLESS STEEL NUTS AND BOLTS OR BY TACK WELDING WITH
FRAMING. INSTALLATION IN BEADS 1/2” + 1/4” IN LENGTH OR WITH #10 STEEL OR STAINLESS STEEL
STEEL FRAMING IS SIMILAR. SHEET METAL SCREWS OR 3/16” STEEL OR STAINLESS STEEL POP
RIVETS. ALL CONNECTIONS SHALL BE SPACED A MAXIMUM OF 8” ON
CENTER AND SHALL HAVE A CONNECTION OF NOT MORE THAN 3” FROM
EACH CORNER. PERIMETER MOUNTING ANGLES SHALL BE A MINIMUM
OF 7/8” x 1 x 16 GA. STEEL AND LAP THE CEILING BY A MINIMUM OF 1”.
THE CORNERS OF THE PERIMETER MOUNTING ANGLES CAN BE WELDED.
PERIMETER ANGLES AND THEIR MOUNTING FASTENERS ARE NOT
NORMALLY SUPPLIED WITH THE DAMPER. ATTACHMENT OF THESE
ANGLES MUST NOT RESTRICT OPERATION OF THE DAMPER.

FLANGE EXPOSED, PERIMETER MOUNTING


ANGLES, 1¾” GRILLE CLEARANCE
7
DUCT CONNECTION TO
DAMPER SLEEVE TO BE A
BREAKAWAY TYPE CONNECTION

ZERO TO 1/4”
TOTAL CLEARANCE

MAXIMUM
16”
STANDARD SLEEVE

16”
DEPTH WITH 3”
GRILLE CLEARANCE
9-1/16”
(REF.)

3”

GRILLE CLEARANCE
¾
SEE SEPARATE DETAIL
FASTEN THE PERIMETER MOUNTING ANGLES ON ALL FOUR SIDES OF
FOR CEILING CONSTRUCTION
THE DAMPER TO THE SLEEVE ONLY, WITH 1/4” DIAMETER STEEL OR
STAINLESS STEEL NUTS AND BOLTS OR BY TACK WELDING WITH
NOTE: BEADS 1/2” + 1/4” IN LENGTH OR WITH #10 STEEL OR STAINLESS STEEL
STEEL FRAMING ONLY, SHEET METAL SCREWS OR 3/16” STEEL OR STAINLESS STEEL POP
OPENING NEED NOT BE LINED RIVETS. ALL CONNECTIONS SHALL BE SPACED A MAXIMUM OF 8” ON
WITH GYPSUM BOARD CENTER AND SHALL HAVE A CONNECTION OF NOT MORE THAN 3” FROM
EACH CORNER. PERIMETER MOUNTING ANGLES SHALL BE A MINIMUM
OF 7/8” x 1 x 16 GA. STEEL AND LAP THE CEILING BY A MINIMUM OF 1”.
THE CORNERS OF THE PERIMETER MOUNTING ANGLES CAN BE WELDED.
PERIMETER ANGLES AND THEIR MOUNTING FASTENERS ARE NOT
NORMALLY SUPPLIED WITH THE DAMPER. ATTACHMENT OF THESE
ANGLES MUST NOT RESTRICT OPERATION OF THE DAMPER.

FLANGE CONCEALED, PERIMETER MOUNTING


ANGLES, 3” GRILLE CLEARANCE
DUCT CONNECTION TO
DAMPER SLEEVE TO BE A
BREAKAWAY TYPE CONNECTION

ZERO TO 1/4”
MAXIMUM

TOTAL CLEARANCE
16”

STANDARD SLEEVE
14¾”
DEPTH WITH 1¾”
GRILLE CLEARANCE
7-13/16”
(REF.)

1¾”
GRILLE CLEARANCE
SEE SEPARATE DETAIL FASTEN THE PERIMETER MOUNTING ANGLES ON ALL FOUR SIDES OF
FOR CEILING CONSTRUCTION THE DAMPER TO THE SLEEVE ONLY, WITH 1/4” DIAMETER STEEL OR
STAINLESS STEEL NUTS AND BOLTS OR BY TACK WELDING WITH
BEADS 1/2” + 1/4” IN LENGTH OR WITH #10 STEEL OR STAINLESS STEEL
SHEET METAL SCREWS OR 3/16” STEEL OR STAINLESS STEEL POP
NOTE: RIVETS. ALL CONNECTIONS SHALL BE SPACED A MAXIMUM OF 8” ON
STEEL FRAMING ONLY, CENTER AND SHALL HAVE A CONNECTION OF NOT MORE THAN 3” FROM
OPENING NEED NOT BE LINED EACH CORNER. PERIMETER MOUNTING ANGLES SHALL BE A MINIMUM
WITH GYPSUM BOARD OF 7/8” x 1 x 16 GA. STEEL AND LAP THE CEILING BY A MINIMUM OF 1”.
THE CORNERS OF THE PERIMETER MOUNTING ANGLES CAN BE WELDED.
PERIMETER ANGLES AND THEIR MOUNTING FASTENERS ARE NOT
NORMALLY SUPPLIED WITH THE DAMPER. ATTACHMENT OF THESE
ANGLES MUST NOT RESTRICT OPERATION OF THE DAMPER.
FLANGE CONCEALED, PERIMETER MOUNTING
ANGLES, 1¾” GRILLE CLEARANCE
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA
8
Smoke Dampers

A1 With sleeve Class I


A2 With sleeve Class II
AA1 With sleeve Class I AirFoil Blade
AA2 With sleeve Class II AirFoil Blade
Installation (A1, A2)
Installation (Airfoil)
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-A1-04.9

MODEL A1 Damper Classified By


UNDERWRITERS LABORATORIES INC.®
As To Leakage Resistance
LEAKAGE AND TEMPERATURE RATED CLASS I
SMOKE DAMPER Arrow United FILE #R4708
Industries
LEAKAGE CLASS I This Smoke Damper meets the construction and
performance requirements of:
TEMPERATURE CLASS 250°F OR 350°F
• Underwriter's Laboratories Inc. Standard 555S
• National Fire Protection Association Standards 90A,
STANDARD MATERIALS AND CONSTRUCTION 92A, and 92B
• ICC'S International Building Code
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel. • ICBO's Uniform Building Code
For maximum free area, a flat head and sill are • SBCCI's Standard Building Code
used for sizes less than 14" high. • BOCA's National Building Code
BLADES: 16-GA galvanized steel, 6" nominal width; parallel action. • New York City MEA Listing #112-99-M
AXLES: Plated solid steel stub. • California State Fire Marshall Listing #3230-1328:106
BEARINGS: Oil Impregnated Bronze. 18"
LINKAGE: Plated steel angle and crank plates with stainless steel STD THIS DIMENSION WILL
pivots, in-jamb type. 10½ 5½ 2 CHANGE WHEN SLEEVE
STOPS: 18-GA galvanized steel at head and sill. LENGTH IS INCREASED
BLADE
EDGE SEALS: Silicone.
SIDE
JAMB SEALS: Stainless steel.
SLEEVE: Minimum 20 Ga. galvanized steel by 18" long.
CAULKING: Hardcast Irongrip 601, or UL-listed equivalent.
FINISH: Mill on galvanized steel.
ACTUATOR: Factory mounted, actuator based on damper size.

DIMENSIONAL DATA • GALVANIZED STEEL (Horizontal or Vertical) SLEEVE

RECTANGULAR DAMPERS A1 (250ºF) A1 (350ºF)


Minimum Size: 16"W x 8"H (Dampers can be furnished with a duct size minimum of 16"W x 6"H using
a type B enclosure in a factory furnished sleeve. The overall frame is 16"W x 8"H).
Maximum Size:
Single Panel: 36"W x 48"H or 48"W x 36"H 36"W x 48"H
Multiple Panel: 108"W x 48"H 108"W x 48"H

ROUND AND OVAL DAMPERS Frame Width = Duct Width + 2"


(Type C Housing, Duct Dimensions): Frame Height = Duct Height + 2"
Minimum Size: Round: 14" Diameter 14" Diameter
Oval: 14"W x 6"H 14"W x 6"H
Maximum Size: Single Panel Multiple Panel Single Panel Multiple Panel
Round: 34" Diameter 46" Diameter 34" Diameter 46" Diameter
Oval: 34"W x 46"H 106"Wx46"H 34"W x 46"H 106"W x 46"H
or 46"W x 34"H
DIMENSIONAL DATA • TYPE 304 and 316 STAINLESS STEEL (Horizontal or Vertical)
RECTANGULAR DAMPERS S1 (250ºF rated only)
Minimum Size: 16"W x 8"H (Dampers can be furnished with
a duct size minimum of 16"W x 6"H using a
type B enclosure in a factory furnished
PROJECT:
sleeve. The overall frame is 16"W x 8"H).
Maximum Size: LOCATION:
Single Panel: 36"W x 36"H ARCHITECT:
Multiple Panel: N/A
ENGINEER:
ROUND AND OVAL DAMPERS Frame Width = Duct Width + 2" CONTRACTOR:
(Type C Housing, Duct Dimensions): Frame Height = Duct Height + 2"
Minimum Size: Round: 14" Diameter PO NUMBER:
Oval: 14"W x 6"H DATE:
Maximum Size:
Single Panel Arrow United Industries
Round: 34" Diameter A Division of Mestek, Inc.
Oval: 34"W x 34"H 314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
MEMBER OF AMCA www.arrowunited.com
ARROW UNITED INDUSTRIES SUBMITTAL DATA

AVAILABLE OPTIONS: (Must Be Specified)


1. 304 S.S. & 316 S.S. Construction Available. (Sleeve and
in-airstream parts only.) Actuator must be externally
mounted.

2. Sleeves: 20 GA galvanized steel (18 GA for widths greater


than 84") x 18" (minimum length) is standard. Sleeves of
longer lengths and heavier gauges are available.

3. Type C Housing for round and oval ductwork.

4. Dual position indication package. Optional auxiliary blade


position indication switches are rated at 11A, 1/3HP,
125VAC. These snap-action switches are intended to
make or break a circuit and will not provide variable or
proportional resistance.

5. Smoke detector (damper height must be 10" minimum.)

6. Side plate in lieu of sleeve on single panels only when A = Nominal Duct Width
actuators are mounted externally. A single panel damper B = Nominal Duct Height
with an internal actuator can be provided without a sleeve
or side plate.
18" STANDARD

OPERATOR

"B" + 2"

"A" + 2"

TYPE "C" HOUSING


GENERAL NOTES
1. Flow may be from either direction.
2. Installation must comply with the requirements of NFPA-90A & -92A.
Actuators must be arranged to operate automatically, and must be
controlled by a smoke detection system.
3. Smoke dampers must be installed within 24" of a smoke barrier.
Local codes may require that the damper be mounted within
the smoke barrier.
4. Dampers will be fabricated ¼" undersize (½" width undersizing when
two panels wide.)
5. Units less than 16"W are Leakage Class II.
ARROW UNITED INDUSTRIES SUBMITTAL DATA
ACTUATOR SELECTION (Single Panel Only)
Underwriters Laboratories requires that all rated dampers be accompanied with their matching UL-approved factory-
mounted actuators. The factors for proper actuator selection are actuator type (electric or pneumatic), voltage requirement,
temperature rating, and damper size. ARROW will factory install actuators for smoke dampers. When stainless steel
construction, actuator must be externally mounted.

ELECTRIC (For Internal or External Mount Unless Noted)


Maximum Single Panel Size Minimum Size
HONEYWELL Voltage @250ºF @350ºF For Internal Mount
ML4202/4302 120VAC 1 sq. ft.
1 sq. ft. 12" x 12"
ML8202/8302 24VAC (External Mount Only)
ML4115 120VAC 24" x 24"
24" x 24" 12" x 12"
ML8115 24VAC (External Mount Only)
36" x 36" or 48" x 24"
MS4209/4309 120VAC
Sizes up to 36"W x 24"H 24" X 24" 12" x 12"
MS8209/8309 24VAC
rated for PC/SO operation
36" x 48" or 48" x 36"
Up to 36" x 36" rated to
MS4120 120VAC 3000 fpm, 4 in. wg. OR 36" x 48" 12" x 20"
MS8120 24VAC PC/SO operation at
2000 fpm / 4 in. wg.

SIEMENS
GGD221 120VAC
GGD121 24VAC 36" x 48" N/A 12" x 20"
GGD321 230VAC

BELIMO
FSNF120 120VAC
36" x 36" or 48" x 24" 36" x 36" 12" x 20"
FSNF24 24VAC

PNEUMATIC (For Internal or External Mount Unless Noted)


Maximum Single Panel Size Minimum Size
SIEMENS @250ºF @350ºF For Internal Mount
331-4830 24" x 24" @ 25 psi N/A 12" x 12"

331-2977 36" x 36" @ 20 psi 24" x 24" @ 25 psi 12" x 20"

331-2996 36" x 48" @ 22 psi 36" x 48" @ 22 psi 16" x 24"

* Consult Factory for multiple panel applications.

AMP DRAW
ML4202/4302(120VAC) Running: .18 Holding: .11
ML8202/8302 (24VAC) Running: .70 Holding: .35
ML4115 (120VAC) Running: .18 Holding: .11
ML8115 (24 VAC) Running: .70 Holding: .35
MS4209/4309 (120VAC) Running: .25 Holding: .13
MS8209/8309 (24VAC) Running: 1.0 Holding: .13
MS4120 (120VAC) Running: .35 Holding: .15
MS8120 (24VAC) Running: 1.8 Holding: .42
GGD121 (24VAC) Running: 6.25 Holding: .42
GGD221 (120VAC) Running: 1.3 Holding: .10
GGD321 (230VAC) Running: .65 Holding: .04
FSNF120 (120VAC) Running: .23 Holding: .09
FSNF24 (24VAC) Running: .23 Holding: .09
ARROW UNITED INDUSTRIESE SUBMITTAL DATA

PERFORMANCE LEAKAGE

MAXIMUM DIFFERENTIAL Definition: UL 555S Class I:


PRESSURE: 4 in. wg Leakage Not Greater Than:
MAXIMUM VELOCITY: 4 CFM per sq. ft. @ 1 in. wg
2000 / 3000 fpm based on actuator model 8 CFM per sq. ft @ 4 in. wg

FULL OPEN PRESSURE DROP DATA


Differential pressure across a damper is the loss of The pressure drop data shown below is based
systems pressure to move air at a particular velocity on actual tests conducted per AMCA Standard
from one side to the other side of the damper. This 500-D, Test Device Setup Figure 5.3. This test
loss in pressure is a result of two factors: the turbu- setup is the standard test method used to
lence created as the air passes over and around the compare damper pressure drop performance.
damper components and more significantly the This setup does not take into account elbows or
reduction in free area resulting from the frame, other duct fittings that are part of every actual
blades, etc. being in the air stream. duct system. The configuration of the actual
duct system immediately upstream and down-
stream of the damper often contributes more
pressure loss than the damper itself.

PRESSURE DROP: TYPICAL PERFORMANCE CURVE


1.0

24 x 24
Pressure Drop (in. wg.)

36 x 36

TESTED PER AMCA


0.1 STANDARD 500-D
FIGURE 5.3: (IN-DUCT MOUNT)
(SMALLER SIZES WILL HAVE
HIGHER PRESSURE DROPS)

0.01
500 1000 2000
FACE VELOCITY IN FEET PER MINUTE
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 MEMBER OF AMCA
www.arrowunited.com
IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROU UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-A2-04.9

MODEL A2 Damper Classified By


UNDERWRITERS LABORATORIES INC.®
LEAKAGE AND TEMPERATURE RATED As To Leakage Resistance
CLASS II
SMOKE DAMPER Arrow United
Industries FILE #R4708
LEAKAGE CLASS II This Smoke Damper meets the construction and
TEMPERATURE CLASS 250°F OR 350°F performance requirements of:
• Underwriter's Laboratories Inc. Standard 555S
STANDARD MATERIALS AND CONSTRUCTION • National Fire Protection Association Standards 90A,
92A, and 92B
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel. • ICC'S International Building Code
For maximum free area, a flat head and sill are • ICBO's Uniform Building Code
used for sizes less than 14" high. • SBCCI's Standard Building Code
BLADES: 16-GA galvanized steel, 6" nominal width; parallel action. • BOCA's National Building Code
AXLES: Plated solid steel stub. • New York City MEA Listing #112-99-M
BEARINGS: Oil Impregnated Bronze. • California State Fire Marshall Listing #3230-1328:106
LINKAGE: Plated steel angle and crank plates with stainless steel 18"
pivots, in-jamb type. STD
THIS DIMENSION WILL
STOPS: 18-GA galvanized steel at head and sill. 10½ 5½ 2 CHANGE WHEN SLEEVE
BLADE LENGTH IS INCREASED
EDGE SEALS: Silicone.
SIDE
JAMB SEALS: Stainless steel.
SLEEVE: Minimum 20 Ga. galvanized steel by 18" long.
CAULKING: Hardcast Irongrip 601, or UL-listed equivalent.
FINISH: Mill on galvanized steel.
ACTUATOR: Factory mounted, actuator based on damper size.

SLEEVE
DIMENSIONAL DATA • GALVANIZED STEEL (Horizontal or Vertical)
RECTANGULAR DAMPERS A2 (250ºF) A2 (350ºF)
Minimum Size: 8"W x 8"H (Dampers can be furnished with a duct size minimum of 4"W x 4"H using
a type B or C enclosure in a factory furnished sleeve. The overall frame is 8"W x 8"H).
Maximum Size:
Single Panel: 36"W x 48"H or 48"W x 36"H 36"W x 48"H or 48"W x 24"H
Multiple Panel: 108"W x 48"H 108"W x 48"H

ROUND AND OVAL DAMPERS Frame Width = Duct Width + 2"


(Type C Housing, Duct Dimensions): Frame Height = Duct Height + 2"
Minimum Size: Round: 6" Diameter 6" Diameter
Maximum Size: Single Panel Multiple Panel Single Panel Multiple Panel
Round: 34" Diameter 46" Diameter 34" Diameter 46" Diameter
Oval: 34"W x 46"H or 106"Wx46"H 34"W x 46"H or 106"W x 46"H
46"W x 34"H 46"W x 22"H
DIMENSIONAL DATA • TYPE 304 and 316 STAINLESS STEEL (Horizontal or Vertical)
RECTANGULAR DAMPERS S2 (250ºF or 350ºF)
Minimum Size: 8"W x 8"H (Dampers can be furnished with a
duct size minimum of 4"W x 4"H using a type B
or C enclosure in a factory furnished sleeve.
The overall frame is 8"W x 8"H).
Maximum Size:
Single Panel: 36"W x 36"H
Multiple Panel: N/A
PROJECT:
ROUND AND OVAL DAMPERS Frame Width = Duct Width + 2" LOCATION:
(Type C Housing, Duct Dimensions): Frame Height = Duct Height + 2"
Minimum Size: Round: 6" Diameter ARCHITECT:
ENGINEER:
Maximum Size: Single Panel
Round: 34" Diameter CONTRACTOR:
Oval: 34"W x 34"H PO NUMBER:
Arrow United Industries
A Division of Mestek, Inc. DATE:
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com AMCA MEMBER
ARROW UNITED INDUSTRIES SUBMITTAL DATA

AVAILABLE OPTIONS: (Must Be Specified)


1. 304 S.S. & 316 S.S. construction available. (Sleeve and in-
airstream parts only.) Actuator must be externally mounted.

2. Sleeves: 20 GA galvanized steel (18 GA for widths greater


than 84") x 18" (minimum length is standard). Sleeves of
longer lengths and heavier gauges are available.

3. Type C Housing for round and oval ductwork.

4. Dual position indication package. Optional auxiliary blade


position indication switches are rated at 11A, 1/3HP,
125VAC. These snap-action switches are intended to
make or break a circuit and will not provide variable or
proportional resistance.
A = Nominal Duct Width
5. Smoke detector (damper height must be 10" minimum.)
B = Nominal Duct Height
6. Side plate in lieu of sleeve on single panels only when
actuators are mounted externally. A single panel damper
with an internal actuator can be provided without a sleeve 18" STANDARD
or side plate.

OPERATOR

"B" + 2"

"A" + 2"

GENERAL NOTES TYPE "C" HOUSING


1. Flow may be from either direction.
2. Installation must comply with the requirements of NFPA-90A & -92A.
Actuators must be arranged to operate automatically, and must be
controlled by a smoke detection system.
3. Smoke dampers must be installed within 24" of a smoke barrier.
Local codes may require that the damper be mounted within
the smoke barrier.
4. Dampers will be fabricated ¼" undersize (½" width undersizing when
two panels wide.)
ARROW UNITED INDUSTRIES SUBMITTAL DATA
ACTUATOR SELECTION (Single Panel Only)
Underwriters Laboratories requires that all rated dampers be accompanied with their matching UL-approved factory-
mounted actuators. The factors for proper actuator selection are actuator type (electric or pneumatic), voltage requirement,
temperature rating, and damper size. ARROW will factory install actuators for smoke dampers. When stainless steel
construction, actuator must be externally mounted.
ELECTRIC (For Internal or External Mount Unless Noted)
Maximum Single Panel Size Minimum Size
HONEYWELL Voltage @250ºF @350ºF For Internal Mount
ML4202/4302 120VAC 1 sq. ft.
1 sq. ft. 12" x 12"
ML8202/8302 24VAC (External Mount Only)
ML4115 120VAC 4 sq. ft.--Width or Height 24" x 24"
ML8115 24VAC not to exceed 36" (External Mount Only) 12" x 12"

36" x 36" or 48" x 24"


Sizes up to 36"W x 24"H
MS4209/4309 120VAC rated for PC/SO operation 48" x 24" 12" x 12"
MS8209/8309 24VAC at 2000fpm, 4 in. wg.
(Up to 24" x 24" rated
for 3000 fpm, 4 in. wg.)
36" x 48" or 48" x 36"
Sizes up to 36" x 36"
MS4120 120VAC rated for PC/SO operation
36" x 48" 12" x 20"
MS8120 24VAC at 2000 fpm, 4 in. wg.
(Up to 36" x 36" rated to
3000 fpm, 4 in. wg.)
SIEMENS
GGD221 120VAC
GGD121 24VAC 36" x 48" N/A 12" x 20"
GGD321 230VAC

BELIMO
FSNF120 120VAC
36" x 36" or 48" x 24" 36" x 36" 12" x 20"
FSNF24 24VAC

PNEUMATIC (For Internal or External Mount Unless Noted)


Maximum Single Panel Size Minimum Size
SIEMENS @250ºF @350ºF For Internal Mount
331-4830 24" x 24" @ 25 psi N/A 12" x 12"

331-2977 36" x 36" @ 20 psi 24" x 24" @ 25 psi 12" x 20"

331-2996 36" x 48" @ 22 psi 36" x 48" @ 22 psi 16" x 24"

* Consult Factory for Multiple Panel Applications

AMP DRAW
ML4202/4302(120VAC) Running: .18 Holding: .11
ML8202/8302 (24VAC) Running: .70 Holding: .35
ML4115 (120VAC) Running: .18 Holding: .11
ML8115 (24 VAC) Running: .70 Holding: .35
MS4209/4309 (120VAC) Running: .25 Holding: .13
MS8209/8309 (24VAC) Running: 1.0 Holding: .13
MS4120 (120VAC) Running: .35 Holding: .15
MS8120 (24VAC) Running: 1.8 Holding: .42
GGD121 (24VAC) Running: 6.25 Holding: .42
GGD221 (120VAC) Running: 1.3 Holding: .10
GGD321 (230VAC) Running: .65 Holding: .04
FSNF120 (120VAC) Running: .23 Holding: .09
FSNF24 (24VAC) Running: .23 Holding: .09
ARROW UNITED INDUSTRIES SUBMITTAL DATA

PERFORMANCE LEAKAGE

MAXIMUM DIFFERENTIAL Definition: UL 555S Class II:


PRESSURE: 4 in. wg Leakage Not Greater Than:
MAXIMUM VELOCITY: 10 CFM per sq. ft. @ 1 in. wg
2000 / 3000 fpm based on actuator model 20 CFM per sq. ft @ 4 in. wg

FULL OPEN PRESSURE DROP DATA


Differential pressure across a damper is the loss of The pressure drop data shown below is based
systems pressure to move air at a particular velocity on actual tests conducted per AMCA Standard
from one side to the other side of the damper. This 500-D, Test Device Setup Figure 5.3. This test
loss in pressure is a result of two factors: the turbu- setup is the standard test method used to
lence created as the air passes over and around the compare damper pressure drop performance.
damper components and more significantly the This setup does not take into account elbows or
reduction in free area resulting from the frame, other duct fittings that are part of every actual
blades, etc. being in the air stream. duct system. The configuration of the actual
duct system immediately upstream and down-
stream of the damper often contributes more
pressure loss than the damper itself.

PRESSURE DROP: TYPICAL PERFORMANCE CURVE


1.0

24 x 24
Pressure Drop (in. wg.)

36 x 36

TESTED PER AMCA


0.1 STANDARD 500-D
FIGURE 5.3: (IN-DUCT MOUNT)
(SMALLER SIZES WILL HAVE
HIGHER PRESSURE DROPS)

0.01
500 1000 2000
FACE VELOCITY IN FEET PER MINUTE
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA

IN THE INTEREST OF PRODUCT DEVELOPMENT, ARROW UNITED INDUSTRIES RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
ARROW UNITED INDUSTRIES SUBMITTAL DATA ASD-AA1-04.11

MODEL AA1
Damper Classified By
UNDERWRITERS LABORATORIES INC.®
MODEL AA1 250 • MODEL AA1 350 AS TO LEAKAGE RESISTANCE
CLASS I
LEAKAGE AND TEMPERATURE RATED R4708
Arrow United Industries
AIRFOIL BLADE SMOKE DAMPER
LEAKAGE CLASS I* This smoke damper meets the construction and
performance requirements of:
TEMPERATURE CLASS 250°F or 350°F
• Underwriters Laboratories Inc. Standard 555S
U.L. Approved for Dual Directional Air Flow • National Fire Protection Association Standards 90A,
92A, 92B
• ICC's International Building Code
STANDARD MATERIALS AND CONSTRUCTION • ICBO's Uniform Building Code
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel. • SBCCI's Standard Building Code
BLADES: 20-GA Double-skinned galvanized steel. (Equal to 14-GA), • BOCA's National Building Code
parallel action. • New York City MEA Listing #112-99-M
• California State Fire Marshall Listing #3230-1328:111
STOPS: 18-GA galvanized steel at head and sill.
SEALS: Silicone blade edges, and stainless steel compression type DIMENSIONAL DATA
at jambs.
AXLES: Square plated steel. RECTANGULAR DAMPERS
BEARINGS: Oil Impregnated Bronze. Minimum Size:8"W x 8"H (See Note #3)
LINKAGE: Concealed in-jamb, plated steel tie bar, stainless steel pivots NOTE: Dampers can be furnished with a duct
size minimum of 4"W x 4"H using a type B or C
SLEEVE: Minimum 20-GA galvanized steel by 20" long. 18-GA is enclosure in a factory furnished sleeve. The
standard for sizes over 84" wide. overall frame is 8"W x 8"H.
CAULKING: Hardcast Irongrip 601, or UL-listed equivalent. Maximum Size:
FINISH: Mill on galvanized steel. Single Section: 36"W x 48"H
Multiple Section: 144"W x 96"H
*UNITS UNDER 12 INCHES IN WIDTH ARE LEAKAGE CLASS II.
ROUND AND OVAL DAMPERS
(Type C Housing, Duct Dimensions)
Frame Width = Duct Width + 2"
20" MINIMUM
Frame Height = Duct Height + 2"
THIS DIMENSION WILL (For small sizes, see NOTE above)
INCREASE WHEN SLEEVE
LENGTH IS INCREASED
Minimum Size:
"A" WIDE
10-1/2" 5-1/2" 4" Round: 4" Diameter
A
Maximum Size: Single Panel
Round: 34" Diameter
Oval: 34"W x 46"H
2x2 Multiple Panel Assembly
Round: 70" Diameter
Oval: 70"W x 94"H
"B" HIGH

NOTE: Dampers 13" high and less have a single blade.

ACTUATOR
(OPTIONAL
LOCATION)

PROJECT:
A
ACTUATOR SLEEVE
LOCATION:
ARCHITECT:
NOTES: ENGINEER:
1. Approved for vertical and horizontal installation. CONTRACTOR:
2. Outside of damper frame (inside of sleeve) will be
PO NUMBER
fabricated 1/4" undersize.
*Dampers narrower than 12" wide will be Leakage Class II DATE:

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286 MEMBER OF AMCA Additional Information
www.arrowunited.com on reverse side
ARROW UNITED INDUSTRIES SUBMITTAL DATA
ACTUATOR SELECTION
Underwriters Laboratories requires that all UL-555S rated dampers be accompanied with their matching UL-approved factory supplied actuators.
The factors for proper actuator selection are actuator type (electric or pneumatic), voltage requirement, temperature rating, and damper size.
ARROW will factory install actuators for all combination fire/smoke dampers.

ELECTRIC
Honeywell Honeywell Honeywell

ML4115 (120VAC) MS 4209 (120 VAC) MS 4120 (120 VAC)


ML8115 (24VAC) MS 8209 (24 VAC) MS 8120 (24 VAC)
Max Panel 36" x 24"
Size at 250º 24" x 16" (Sizes up to 24" x 24" rated 36" x 48"
up to 3000 FPM, 4 in. wg.)
Max Panel
Size at 350º Not Available 24" x 24" 36" x 48"

Min. size for


Internal mount: 12" x 12" 12" x 12" 12" x 21"

PNEUMATIC
Siemens Siemens AMP DRAW
331-2997 331-2996 ML4115—run .18 hold .11
Max Panel ML8115—run .70 hold .35
Size at 250º 24" x 24" (@20 PSI) 36" x 48" (@20PSI) MS 4209—run .25 hold .13
MS 8209—run 1.0 hold .13
Max Panel MS 4120—run .35 hold .15
Size at 350º 24" x 24" (@25 PSI) 36" x 48" (@20PSI) MS 8120—run 1.8 hold .42

Min. size for


Internal Mount: 12" x 20" 16" x 24"

AVAILABLE OPTIONS: (Must Be Specified)


1. Normally, actuators are externally mounted on the left side of the sleeve, as viewed from the jackshaft side of the damper. Actuators
may be mounted on the right side at no additional charge, if specified on the order, except where two actuators are used on multiple
panel assemblies.
2. Sleeve thicknesses heavier than 20 gauge are available.
3. Sleeve lengths longer than the standard 20" are available.
4. Dual position indication package. Optional auxiliary blade position indication switches are rated at 11A, 1/3HP, 125VAC. These snap
action switches are intended to make or break a circuit and will not provide variable or proportional resistance.
5. Smoke detector (damper height must be 10" minimum).

GENERAL NOTES
1. Underwriters Laboratories Inc. classified leakage damper for use in smoke control systems designed for Leakage Class I and Temperature
Class 250°F or 350°F, in accordance with UL Standard 555S.
2. Refer to UL-approved Installation Instructions for detailed operational information.
3. Smoke dampers must be installed within 24" of a smoke barrier. Some codes require that the smoke damper be installed within the
smoke barrier.

PERFORMANCE

LEAKAGE
Definition: UL 555S Class I:
Leakage Not Greater Than:
4 CFM per sq. ft. @ 1 in. wg
8 CFM per sq. ft. @ 4 in. wg

MAXIMUM DIFFERENTIAL
PRESSURE: 4 in. wg.
MAXIMUM VELOCITY:
2000 / 3000 FPM Based on Actuator Model
FACE VELOCITY IN FEET PER MINUTE
Arrow United Industries TYPICAL PERFORMANCE CURVE
TESTED PER AMCA STANDARD 500-D; FIGURE 5.3:
A Division of Mestek, Inc. (IN-DUCT MOUNT)
314 Riverside Drive . Wyalusing, PA 18853 SMALLER SIZES WILL HAVE HIGHER PRESSURE DROPS
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA

INTHEINTERESTOFPRODUCTDEVELOPMENT,ARROWUNITEDINDUSTRIESRESERVESTHERIGHTTOMAKECHANGESWITHOUTNOTICE.
ASD-AA2-04.11
ARROW UNITED INDUSTRIES SUBMITTAL DATA

MODEL AA2
Damper Classified By
UNDERWRITERS LABORATORIES INC.®
MODEL AA2 250 • MODEL AA2 350 AS TO LEAKAGE RESISTANCE
CLASS II
LEAKAGE AND TEMPERATURE RATED
R4708
AIRFOIL BLADE SMOKE DAMPER Arrow United Industries

This smoke damper meets the construction and


LEAKAGE CLASS II performance requirements of:
TEMPERATURE CLASS 250°F or 350°F
• Underwriters Laboratories Inc. Standard 555S
U.L. Approved for Dual Directional Air Flow • National Fire Protection Association Standards 90A,
92A, 92B
• ICC's International Building Code
STANDARD MATERIALS AND CONSTRUCTION • ICBO's Uniform Building Code
FRAME: 51/2" x 7/8" x 16-GA galvanized steel hat channel. • SBCCI's Standard Building Code
• BOCA's National Building Code
BLADES: 20-GA Double-skinned galvanized steel. (Equal to 14-GA),
• New York City MEA Listing #112-99-M
parallel action.
• California State Fire Marshall Listing #3230-1328:111
STOPS: 18-GA galvanized steel at head and sill.
SEALS: Silicone blade edges, and stainless steel compression type at
jambs.
DIMENSIONAL DATA
AXLES: Square plated steel. RECTANGULAR DAMPERS
BEARINGS: Oil Impregnated Bronze. Minimum Size:8"W x 8"H
LINKAGE: Concealed in-jamb, plated steel tie bar, stainless steel pivots NOTE: Dampers can be furnished with a duct
SLEEVE: Minimum 20-GA galvanized steel by 20" long. 18-GA is size minimum of 4"W x 4"H using a type B or C
enclosure in a factory furnished sleeve. The
standard for sizes over 84" wide.
overall frame is 8"W x 8"H.
CAULKING: Hardcast Irongrip 601, or UL-listed equivalent.
Maximum Size:
FINISH: Mill on galvanized steel. Single Section: 36"W x 48"H
Multiple Section: 144"W x 96"H

ROUND AND OVAL DAMPERS


(Type C Housing, Duct Dimensions)
Frame Width = Duct Width + 2"
20" MINIMUM
Frame Height = Duct Height + 2"
(For small sizes, see NOTE above)
THIS DIMENSION WILL
INCREASE WHEN SLEEVE
LENGTH IS INCREASED Minimum Size:
Round: 4" Diameter
"A" WIDE
A
10-1/2" 5-1/2" 4" Maximum Size: Single Panel
Round: 34" Diameter
Oval: 34"W x 46"H
2x2 Multiple Panel Assembly
Round: 70" Diameter
Oval: 70"W x 94"H
NOTE: Dampers 13" high and less have a single blade.
"B" HIGH

ACTUATOR
(OPTIONAL
LOCATION)
PROJECT:
LOCATION:
A ARCHITECT:
ACTUATOR SLEEVE
ENGINEER:
NOTES:
1. Approved for vertical and horizontal installation. CONTRACTOR:
2. Outside of damper frame (inside of sleeve) will be PO NUMBER:
fabricated 1/4" undersize. DATE:
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
Additional Information
www.arrowunited.com
on reverse side
MEMBER OF AMCA
ARROW UNITED INDUSTRIES SUBMITTAL DATA
ACTUATOR SELECTION
Underwriters Laboratories requires that all UL-555S rated dampers be accompanied with their matching UL-approved factory supplied actuators.
The factors for proper actuator selection are actuator type (electric or pneumatic), voltage requirement, temperature rating, and damper size.
ARROW will factory install actuators for all combination fire/smoke dampers.

ELECTRIC
Honeywell Honeywell Honeywell
ML4115 (120VAC) MS 4209 (120 VAC) MS 4120 (120 VAC)
ML8115 (24VAC) MS 8209 (24 VAC) MS 8120 (24 VAC)
Max Panel 36" x 24"
Size at 250º 24" x 16" (Sizes up to 24" x 24" rated 36" x 48"
up to 3000 FPM, 4 in. wg.)
Max Panel
Size at 350º Not Available 24" x 24" 36" x 48"

Min. size for


Internal mount: 12" x 12" 12" x 12" 12" x 21"

PNEUMATIC
Siemens Siemens AMP DRAW
331-2997 331-2996 ML4115—run .18 hold .11
ML8115—run .70 hold .35
Max Panel
Size at 250º 24" x 24" (@20 PSI) 36" x 48" (@20PSI) MS 4209—run .25 hold .13
MS 8209—run 1.0 hold .13
Max Panel MS 4120—run .35 hold .15
24" x 24" (@25 PSI) 36" x 48" (@20PSI) MS 8120—run 1.8 hold .42
Size at 350º
Min. size for
Internal Mount: 12" x 20" 16" x 24"

AVAILABLE OPTIONS: (Must Be Specified)


1. Normally, actuators are externally mounted on the left side of the sleeve, as viewed from the jackshaft side of the damper. Actuators
may be mounted on the right side at no additional charge, if specified on the order, except where two actuators are used on multiple
panel assemblies.
2. Sleeve thicknesses heavier than 20 gauge are available.
3. Sleeve lengths longer than the standard 20" are available.
4. Dual position indication package. Optional auxiliary blade position indication switches are rated at 11A, 1/3HP, 125VAC. These snap
action switches are intended to make or break a circuit and will not provide variable or proportional resistance.
5. Smoke detector (damper height must be 10" minimum).

GENERAL NOTES

1. Underwriters Laboratories Inc. classified leakage damper for use in smoke control systems designed for Leakage Class II and Temperature
Class 250°F or 350°F, in accordance with UL Standard 555S.
2. Refer to UL-approved Installation Instructions for detailed operational information.
3. Smoke dampers must be installed within 24" of a smoke barrier. Some codes require that the smoke damper be installed within the
smoke barrier.
PERFORMANCE

LEAKAGE
Definition: UL 555S Class II:
Leakage Not Greater Than:
10 CFM per sq. ft. @ 1 in. wg
20 CFM per sq. ft. @ 4 in. wg

MAXIMUM DIFFERENTIAL
PRESSURE: 4 in. wg.
MAXIMUM VELOCITY:
2000 / 3000 FPM Based on Actuator Model

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com MEMBER OF AMCA

INTHEINTERESTOFPRODUCTDEVELOPMENT,ARROWUNITEDINDUSTRIESRESERVESTHERIGHTTOMAKECHANGESWITHOUTNOTICE.
AII-SSD-04.3
INSTALLATION INSTRUCTIONS
MODELS: A1, A2
(STAINLESS STEEL CONSTRUCTION)
SMOKE DAMPERS AND OPERATORS

1.0 GENERAL INFORMATION dampers can be positioned so that they are within
the rated masonry, block, or gypsum wallboard
1.1 These dampers are supplied with external factory mounted smoke barrier (See detail below).
actuators and are intended to close automatically upon loss
2.2 Dampers can be vertically or horizontally mounted
of electrical power or release of air pressure.
with horizontal blades. Flow may be from either
1.2 The standard factory supplied sleeve is 20 GA stainless
direction.
steel.
1.3 Maximum panel size of 36” x 36”, single panel only. 2.3 The damper frame must be installed square. For
dampers supplied without sleeves, use metal shims,
2.0 DAMPER INSTALLATION if required, between the damper frame and duct/
sleeve to prevent distortion. Damper is to be
2.1 Dampers shall be installed not more than 24 inches from a
anchored at both frame flanges. Check the damper
smoke barrier and before the first duct inlet or outlet.
for free operation. Excessive drag or binding could
Installation shall be in accordance with NFPA-90A. These
cause damage to the damper and/or actuator.

TYPICAL WALL INSTALLATIONS


(FLOOR INSTALLATIONS SIMILAR)
SMOKE SMOKE
DAMPER DAMPER

SEALANT

AIR AIR
FLOW FLOW

24”
DUCT INLET
MAX. OR OUTLET
DAMPER FRAME
3½ MAX. 3½ MAX.

SLEEVE OR DUCT

3/16 x 1/4 LG. (MIN.) STAINLESS STEEL SELF-PIERCING OR POP


RIVET OR 1/4 X 1/2 LG. (MIN.) BOLTS WITH NUTS OR #10 x 1/2 LG.
(MIN.) STAINLESS STEEL SHEET METAL SCREWS OR 1/2 LG. FILLET
WELDS. DAMPER FRAME TO SLEEVE FASTENING TO BE 3-1/2
MAX. FROM ENDS AND STAGGERED NO MORE THAN 10” ON
CENTER.
Arrow United Industries
A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
MEMBER OF AMCA Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
SEALANT

Sealants are used to prevent leakage through cracks that are formed where two parts meet. The amount of sealant
requred is therefore dependent on the leakage class rating required.

1. Field applied sealant around damper perimeter on both upstream and downstream side to cover gap between
frame and sleeve - Class I rated dampers.
2. Field applied sealant around damper perimeter on upstream or downstream side to cover gap between frame
and sleeve - Class II rated dampers.

One of the following UL Classified caulking/sealants must be used:


-Hardcast 601
-Dow Corning RTV732
-General Electric IS808
-Novagard RTV300
-3M Firedam

WIRING SCHEMATICS
1. All wiring installations must comply with the requirements of N.E.C. (NFPA-70), and the National Electric Code.
2. Damper with actuator must be arranged to operate automatically and must be controlled by a smoke detector.
3. Refer to actuator label for appropriate voltage.
4. Connect incoming ground to the actuator assembly.
5. Optional auxiliary blade position indication switches are rated at 11A, 1/3HP, 125VAC. These snap action switches are
intended to make or break a circuit and will not provide variable or proportional resistance.
VIOLET OR BLACK

MOTOR MOTOR
VIOLET OR BLACK

MOTOR MOTOR

OPEN CLOSED
WHITE

INDICATION INDICATION
WHITE

SWITCH SWITCH
MS-1 MS-2
NC C NC C
YELLOW
BLUE

GRAY
RED

SMOKE SMOKE
DETECTOR DETECTOR
MS1 IS CLOSED WHEN DAMPER
IS OPEN NC
MS2 IS CLOSED WHEN DAMPER
IS CLOSED
NC
SEE ACTUATOR
FOR PROPER VOLTAGE
SEE ACTUATOR
FOR PROPER VOLTAGE
L1 CUSTOMER WIRING L2
L1 CUSTOMER WIRING L2

WIRING SCHEMATIC WHEN INTEGRAL WIRING SCHEMATIC WHEN NO


AUXILIARY SWITCH PACKAGE INTEGRAL AUXILIARY SWITCH
PACKAGE

2
AII-SD CDLG-04.11
INSTALLATION INSTRUCTIONS
SINGLE THICKNESS AND AIRFOIL
SMOKE DAMPERS AND OPERATORS

1.0 GENERAL INFORMATION dampers can be positioned so that they are within
the rated masonry, block, or gypsum wallboard
1.1 See table on page 2 for specific damper specifications. smoke barrier (See detail on page 2).
1.2 These dampers are supplied with factory mounted actua-
2.2 Dampers can be vertically or horizontally mounted
tors and are intended to close automatically upon loss of
with horizontal blades. Flow may be from either
electrical power or release of air pressure.
direction.
1.3 The standard factory supplied sleeve is 20 GA galvanized
steel (18GA on dampers wider than 84”). 2.3 The damper frame must be installed square. For
dampers supplied without sleeves, use metal shims,
2.0 DAMPER INSTALLATION if required, between the damper frame and duct/
sleeve to prevent distortion. Damper is to be
2.1 Dampers shall be installed not more than 24 inches from a
anchored at both frame flanges. Check the damper
smoke barrier and before the first duct inlet or outlet.
for free operation. Excessive drag or binding could
Installation shall be in accordance with NFPA-90A. These
cause damage to the damper and/or actuator.

SMOKE BARRIER

SEALANT

AIR
FLOW

24” MAX.
DUCT INLET
OR OUTLET

DAMPER FRAME
3½ MAX. 3½ MAX.

SLEEVE OR DUCT

3/16 x 1/4 LG. (MIN.) STAINLESS STEEL SELF-PIERCING OR POP


RIVET OR 1/4 X 1/2 LG. (MIN.) BOLTS WITH NUTS OR #10 x 1/2 LG.
(MIN.) STAINLESS STEEL SHEET METAL SCREWS OR 1/2 LG. FILLET
WELDS. DAMPER FRAME TO SLEEVE FASTENING TO BE 3-1/2
MAX. FROM ENDS AND STAGGERED NO MORE THAN 10” ON
CENTER.

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
MEMBER OF AMCA
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com
TYPICAL WALL INSTALLATIONS
(FLOOR INSTALLATIONS SIMILAR)

SMOKE SMOKE
DAMPER DAMPER

SEALANT

AIR AIR
FLOW FLOW

24”
DUCT INLET
MAX. OR OUTLET

In-Wall Installation Out of Wall Installation

TYPICAL WALL INSTALLATIONS


(FLOOR INSTALLATIONS SIMILAR)

AIRFOIL MODELS - VERTICAL OR HORIZONTAL MOUNT


ACTUATOR MAXIMUM MAXIMUM MAX. PANELS
TYPE SINGLE PANEL MULTIPLE PANEL WIDE & QUANTITY
(W x H) (W x H) OF ACTUATORS
MS4209, 4309
36 x 24 144 x 24 4
MS8209, 8309
331-2996 36 x 48 144 x 48 4
MS4120, 8120 36 x 48 144 x 96* (4x2) 8 Acts.
SINGLE THICKNESS MODELS - VERTICAL OR HORIZONTAL MOUNT
ACTUATOR MAXIMUM MAXIMUM MAX. PANEL
TYPE SINGLE PANEL MULTIPLE PANEL WIDE & QUANTITY
(W x H) (W x H) OF ACTUATORS
MS4209, 4309
MS8209, 8309 36 x 36 OR 108 x 36 OR 3
FSNF120, 24 48 x 24 96 x 24 2

MS4120, 8120 36 x 48 OR 108 x 48 OR 3


48 x 36 96 x 36 2

GGD121,221,321
331-2996 36 x 48 108 x 48 3

331-2977 36 x 36 108 x 36 3

*See Page 4 for Mullion Stiffener Detail

2
SEALANT

Sealants are used to prevent leakage through cracks that are formed where two parts meet. The amount of sealant
requred is therefore dependent on the leakage class rating required.

1. Field applied sealant around damper perimeter on both upstream and downstream side to cover gap between
frame and sleeve - Class I rated dampers.
2. Field applied sealant around damper perimeter on upstream or downstream side to cover gap between frame
and sleeve - Class II rated dampers.

One of the following UL Classified caulking/sealants must be used:


-Hardcast 601
-Dow Corning RTV732
-General Electric IS808
-Novagard RTV300
-3M Firedam

WIRING SCHEMATICS
1. All wiring installations must comply with the requirements of N.E.C. (NFPA-70), and the National Electric Code.
2. Damper with actuator must be arranged to operate automatically and must be controlled by a smoke detector.
3. Refer to actuator label for appropriate voltage.
4. Connect incoming ground to the actuator assembly.
5. Optional auxiliary blade position indication switches are rated at 11A, 1/3HP, 125VAC. These snap action switches are
intended to make or break a circuit and will not provide variable or proportional resistance.
VIOLET OR BLACK

MOTOR MOTOR
VIOLET OR BLACK

MOTOR MOTOR

OPEN CLOSED
WHITE

INDICATION INDICATION
SWITCH SWITCH
WHITE
MS-1 MS-2
NC C NC C
YELLOW
BLUE

GRAY
RED

SMOKE SMOKE
DETECTOR DETECTOR
MS1 IS CLOSED WHEN DAMPER
IS OPEN NC
MS2 IS CLOSED WHEN DAMPER
IS CLOSED
NC
SEE ACTUATOR
FOR PROPER VOLTAGE
SEE ACTUATOR
FOR PROPER VOLTAGE
L1 CUSTOMER WIRING L2
L1 CUSTOMER WIRING L2

WIRING SCHEMATIC WHEN INTEGRAL WIRING SCHEMATIC WHEN NO


AUXILIARY SWITCH PACKAGE INTEGRAL AUXILIARY SWITCH
PACKAGE

3
FABRICATION AND INSTALLATION INSTRUCTIONS FOR
TWO PANEL HIGH MULLION STIFFENER

Purpose When Required


This factory or field fabricated This 12 GA steel flat plate is sandwiched
plate reinforces the damper's between the damper's vertical frame
vertical mullion to prevent members at its vertical mullion. This
excessive mullion deflection. stiffener is required whenever the damper
assembly is both multiple panels wide
and multiple panels high.

1
2
1 One piece full height 6"
by 12 GA steel plate.

2 1/4" Steel bolts and nuts on 12"


max. centers, staggered on both
faces. First fastener 6" maximum
from each end. Ends of plate do
not need to be attached to top
and bottom of sleeve.

3 Vertical damper Mullion

Notes
1. When assembly is ordered with a factory supplied sleeve, this mullion stiffener will
be factory furnished and installed.
2. When assembly is ordered without a factory supplied sleeve, this mullion stiffener
is to be field fabricated and field installed.

INSTALLATION OF MULTIPLE SHIP SECTION DAMPER ASSEMBLIES


Large damper openings may require multiple factory assembled modules to fill the opening.
After placing the modules into the opening, the individual modules are fastened together
using ¼” diameter steel bolts, lockwashers, and nuts. Fasteners are to be on 6” maximum
centers and on both faces of the sleeve.

Arrow United Industries


A Division of Mestek, Inc.
314 Riverside Drive . Wyalusing, PA 18853
Ph: (570) 746-1888 Fax: (570) 746-9286
www.arrowunited.com

MEMBER OF AMCA

4
Duct Access Doors

1035 ADD
1036 ADG

S-ar putea să vă placă și