Documente Academic
Documente Profesional
Documente Cultură
SECTION 089100
LOUVERS
1 - GENERAL
1.2 SUMMARY
A. Contractor shall provide all labour, Materials, Contractor’s Equipment and Plant to fully
execute the requirements to furnish, deliver, and install the Works as expressly described in
the Drawings and Specification, or implied therefrom, and in accordance with the Contract.
It is the intent of this Specification section that the work performed pursuant hereto be
complete and acceptable in every respect for its intended purpose. It is further required that
the provisions of this Specification section shall be complementary to, and shall be
correlated with, the requirements of the Contract. Nothing in this Specification section shall
limit the scope of work as required by the Contract.
B. Section Includes:
1. Fixed, extruded-aluminum louvers.
a. (ref LRV-01 is not used)
b. Sand louvers (ref LRV-02): Sand trap louvers
c. Internal louvers (ref LRV-06).
d. Architectural louvers and doors (ref LRV-07).
2. Fixed stainless-steel louvers.
a. Architectural louvers (ref LRV-09).
1.3 DEFINITIONS
A. Louver Terminology: Definitions of terms for metal louvers contained in AMCA 501 apply
to this Section unless otherwise defined in this Section or in referenced standards.
B. Horizontal Louver: Louver with horizontal blades; i.e., the axes of the blades are horizontal.
C. Drainable-Blade Louver: Louver with blades having gutters that collect water and drain it
to channels in jambs and mullions, which carry it to bottom of unit and away from opening.
D. Sand Trap Louvers: Louvers specifically designed to separate sand and dust from the air.
1) The mean hourly wind speed for this area is 23.3 meters per second.
2) Calculate wind loads in accordance with SEI/ASCE 7 or BS 6399 Pt 2.
b. When tested at both positive and negative applications of design wind loads,
multiplied by a factor of 1.5, there shall be no permanent damage to louvers,
framing, or anchors. Framing members shall not be buckled.
2. Seismic Loads: Withstand the effects of earthquake motions in accordance with 1997
UBC Division IV-Earthquake Design. The following factors shall be used:
1.5 SUBMITTALS
A. Product Data: For each type of product indicated.
1. For louvers specified to bear AMCA seal, include printed catalog pages showing
specified models with appropriate AMCA Certified Ratings Seals.
B. Visual Mockup Shop Drawings: Showing fabrication and installation details for visual
mockups.
C. Shop Drawings: For louvers and accessories. Include plans, elevations, sections, details,
and attachments to other work. Show frame profiles and blade profiles, angles, and spacing.
1. Indicate locations, dimensions, tolerances, and details of steel framing and support
required for support of louvers.
2. Show weep paths, gaskets, flashing, sealant, and other means of preventing water
intrusion.
3. Show mullion profiles and locations.
D. Samples for Verification: For each type of metal finish required.
E. Certification: Signed and sealed by Contractor, certifying that products and systems to be
provided comply with performance requirements in the Contract Documents. Include
calculations and structural analysis including comprehensive engineering analysis (limited
to the extent of the defined Performance Requirements in this Section) signed and sealed by
the qualified professional engineer responsible for their preparation.
B. Visual Mockups: After approval of samples, build visual mockups for louvers, complete
with framing, anchors, and connections, to comply with the following requirements, using
materials indicated in the Contract Documents for the completed Work:
1. Provide components for mockups as indicated on the A12 Series Drawings and as
specified in Division 01 Section “Mock-Ups, Mock-Up Area & Facility and Other
Requirements.” Build visual mockups of size and extent indicated on Drawings, in
location as directed by Engineer.
2. Purpose of visual mockups is to verify selections made under sample submittals and
to demonstrate aesthetic effects and set quality standards for materials and execution.
3. Obtain Engineer’s approval of visual mockups before starting work, fabrication, or
construction.
4. Maintain visual mockups during construction in an undisturbed condition as a
standard for judging the completed Work.
5. Demolish and remove visual mockups when directed by Engineer.
C. SMACNA Standard: Comply with recommendations in SMACNA's "Architectural Sheet
Metal Manual" for fabrication, construction details, and installation procedures.
1.7 REFERENCES
A. Product manufacture, testing and installation shall comply with the following references
unless otherwise stated in the specification or otherwise approved by the Engineer.
E. ASTM International
1. ASTM B 26/B 26M-03: Specification for Aluminum-Alloy Sand Castings
2. ASTM B 209M-04: Specification for Aluminum and Aluminum-Alloy Sheet and
Plate [Metric]
3. ASTM B 221M-04: Specification for Aluminum and Aluminum-Alloy Extruded
Bars, Rods, Wire, Profiles and Tubes [Metric]
4. ASTM E 488-96 (Reapproved 2003): Test Methods for Strength of Anchors in
Concrete and Masonry Elements
F. International Code Council
1. Uniform Building Code (UBC) 1997
G. National Association of Architectural Metal Manufacturers
1. Metal Finishes Manual for Architectural and Metal Products. 1988.
H. Sheet Metal and Air Conditioning Contractors' National Association
1. Architectural Sheet Metal Manual. 2003.
1.9 WARRANTY
A. Special Finish Warranty: Manufacturer's standard form in which manufacturer agrees to
repair or replace components on which finishes do not comply with requirements or that fail
in materials or workmanship within specified warranty period. Warranty does not include
normal weathering.
1. Warranty Periods: See Division 01 Section “Warranties” for commencement date of
warranty period.
2 - PRODUCTS
2.1 MATERIALS
A. Aluminum Extrusions: ASTM B 221M, Alloy 6063-T5, T-52, or T6.
B. Aluminum Sheet: ASTM B 209M, Alloy 3003 or 5005 with temper as required for
forming, or as otherwise recommended by metal producer for required finish.
D. Stainless-Steel Sheet: ASTM A 240/A 240M, Type 304, No. 4 finish, with grain running
parallel to length of blades and frame members.
E. Fasteners: Use types and sizes to suit unit installation conditions.
1. Use Phillips flat-head tamper-resistant screws for exposed fasteners unless otherwise
indicated on Drawings.
2. For fastening aluminum, use aluminum or 300 series stainless-steel fasteners.
B. Vertical Assemblies: Where height of louver units exceeds fabrication and handling
limitations, fabricate units to permit field-bolted assembly with close-fitting joints in jambs
and mullions, reinforced with splice plates.
1. Horizontal Mullions: Provide horizontal mullions at joints unless continuous vertical
assemblies are indicated on Drawings.
C. Maintain equal louver blade spacing to produce uniform appearance.
D. Fabricate frames, including integral sills, to fit in openings of sizes indicated, with
allowances made for fabrication and installation tolerances, adjoining material tolerances,
and perimeter sealant joints.
1. Frame Type: Interior flange unless otherwise indicated on Drawings.
E. Include supports, anchorages, and accessories required for complete assembly.
F. Provide vertical mullions of type and at spacings indicated on Drawings, but not more than
recommended by manufacturer, or 1800 mm o.c., whichever is less.
1. Fully Recessed Mullions – Interior Louvers: Where indicated, provide mullions fully
recessed behind louver blades. Where length of louver exceeds fabrication and
handling limitations, fabricate with close-fitting blade splices designed to permit
expansion and contraction.
2. Exposed Mullions – Exterior Louvers: Where indicated, provide units with exposed
mullions of same width and depth as louver frame. Where length of louver exceeds
fabrication and handling limitations, provide interlocking split mullions designed to
permit expansion and contraction.
G. Provide subsills made of same material as louvers for recessed louvers.
H. Join frame members to each other and to fixed louver blades with fillet welds, threaded
fasteners, or both, as standard with louver manufacturer, or size of louver assembly makes
bolted connections between frame members necessary.
2. Interior Louvers:
C. Louver Screen Frames: Fabricate with mitered corners to louver sizes indicated.
1. Metal: Same kind and form of metal as specified for louver to which screens are
attached. Reinforce extruded-aluminum screen frames at corners with clips.
2. Finish: Same finish as louver frames to which louver screens are attached.
3. Type:
a. For use with insect screen: Rewirable frames with a driven spline or insert.
b. For use with bird screen: Non-rewirable, U-shaped frames.
D. Bird Screening (ref LRV-04): Stainless steel, Type 316L; 13-mm- square mesh, 1.19-mm
wire.
E. Insect Screening (ref LRV-05): Stainless steel, type 316L; 1.4-by-1.4-mm mesh, 0.23-mm
wire.
C. Provide insulated, blank-off panels for louvers for portions of louvers not connected to
ducts.
3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and openings, with Installer present, for compliance with requirements
for installation tolerances and other conditions affecting performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Coordinate setting drawings, diagrams, templates, instructions, and directions for
installation of anchorages that are to be embedded in concrete or masonry construction.
Coordinate delivery of such items to Project site.
3.3 INSTALLATION
A. Locate and place louvers and vents level, plumb, and at indicated alignment with adjacent
work.
1. Refer to Division 05 Section “Structural Steel Framing” for limitations on sizes and
locations of site-drilled holes in structural steel.
B. Install doors within architectural louvers such that louver blades on door align with louver
blades on adjoining wall to provide continuous appearance. Adjust hardware for hinged
louvers for proper operation. Coordinate with Division 08 Section "Door Hardware".
C. Use concealed anchorages where possible. Provide brass or lead washers fitted to screws
where required to protect metal surfaces and to make a weathertight connection.
D. Form closely fitted joints with exposed connections accurately located and secured.
E. Provide perimeter reveals and openings of uniform width for sealants and joint fillers, as
specified or as indicated on Drawings.
F. Repair finishes damaged by cutting, welding, soldering, and grinding. Restore finishes so
no evidence remains of corrective work. Return items that cannot be refinished in the field
to the factory, make required alterations, and refinish entire unit or provide new units.
G. Protect unpainted nonferrous-metal surfaces that will be in contact with concrete, masonry,
or dissimilar metals from corrosion and galvanic action by separating surfaces with
waterproof gaskets or nonmetallic flashing.
H. Install concealed gaskets, flashings, joint fillers, and insulation as louver installation
progresses, where weathertight louver joints are required. Comply with Division 07 Section
"Joint Sealants" for sealants applied during louver installation.
B. Before final inspection, clean exposed surfaces with water and a mild soap or detergent not
harmful to finishes. Thoroughly rinse surfaces and dry.
C. Restore louvers and vents damaged during installation and construction so no evidence
remains of corrective work. If results of restoration are unsuccessful, as determined by
Engineer, remove damaged units and replace with new units.
1. Touch up minor abrasions in finishes with air-dried coating that matches color and
gloss of, and is compatible with, factory-applied finish coating.
END OF SECTION