17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

KEYPLAN PLOT NORTH

A GEOGRAPHIC A
NORTH

11
5 °
IMPZ.SS.06
TRUE
NORTH
5270
B SUPPLY FOR RC FIRE B
WATER TANK (600 GAL)

TRANSFER

ROOM ROOF
SECURITY
PUMP

3030
DOOR CANOPY
DOMESTIC WATER
TANK (1000 GAL)

STAIRCASE-4 2855 4355 2660 4355


6590 2000 3000 1500

2000
1. ALL DIMENSIONS ARE IN MM AND ALL LEVELS ARE IN M UNLESS OTHERWISE SPECIFIED.
2690

C C
2. HEIGHT OF THE BUILDING SHALL BE GOVERNED BY THE REQUIREMENT OF THE EQUIPMENT TO BE HOUSED

DOOR CANOPY
DOOR CANOPY
6980

2900

2900
3365

2000
STAIRCASE NO.1 3. THE WALLS AROUND THE TRANSFORMER/REACTOR SHALL BE FIRE PROOF.

5720
4. THE GROUND WATER TANK & TRANSFER PUMPS WILL BE INDICATED TENTATIVELY SUBJECT TO
1000

MONORAIL CHANGE IN DETAILED DESIGN.


6600

3720
980
5. THE CAPACITY OF FIRE WATER TANK WILL BE INDICATED AFTER THE FINALIZATION OF HYDRAULIC CALCULATIONS.
H&L 6560
DB 6. FOR CIVIL DEATILS, PLEASE REFER RELEVANT CIVIL ARCHITECTURAL DRAWINGS.

2745

2745
FIRE WATER TANK-1
950

FIRE WATER TANK-2


1460 7. GROUND WATER TANK WILL BE LOCATED ON ROOF OF SECURITY ROOM.
IDT-1 ROOM
5500

35/50MVA-132/12kV 8. THE TRANSFORMER ROOF SHALL BE OF STEEL STRUCTURE. PROCEDURE FOR ERECTION AND DISMANTLING

10980
OF ROOF TRUSSES, SHEETING AND LOUVERS FOR TRANSFORMER TO BE SUBMITTED FOR APPROVAL
LVAC ROOM

2000

10980
VOID AREA 9. ALL BLOCK WALLS AND THERMAL INSULATED EXTERNAL WALLS ARE SHOWN WITH
INCLUDING PLASTERING THICKNESS
D D

2745
10. NO OF CABLE DUCTS LOCATION FOR THE INTERNAL CABLING OF THE SUB STATION SHALL BE

2745
MANHOLE
FDP

ACCESS AS PER REQUIREMENTS AND DEWA APPROVAL


1860
TELECOM / DMZ

MUX
LVAC SWITCHGEAR

11. OPEN AREA INSIDE THE COMPOUND SHALL BE PAVED WITH 800mm THICK INTERLOCK PAVING.
13600

CAGE LADDER FOR 12. FIRE BARRIERS SHALL BE DESIGNED / INSTALLED GIVING DUE CONSIDERATION FOR
FUT.

8380
8850

ROOM

ACCESS TO MAINTENANCE EASY OPERATION AND MAINTENANCE OF EQUIPMENTS


A/C & VENT.

F PLATFORM SUMP PIT SUMP PIT

2920

2920
CORRIDOR

DMZ CCTV FUT.

1000x1000 3365 13. COLUMNS ARE SHOWN TENTATIVE ONLY


F HATCH FOR
ACCESSING 14. SCMS PANELS, DMZ PANELS, OPERATOR CONTROL DESKS, SCMS PRINTER & SCMS CUPBOARD
1500 VOID AREA SHALL BE PROVIDED WITH RAISED FLOOR.

9000 FIRE WATER TANK


2000 1647 MAINTENANCE ACCESS

2000
1580

REMOVABLE FIRE WATER TANK PLATFORM


HAND RAIL MAINTENANCE ACCESS CAGE LADDER FOR
E 4500 PLATFORM FIRE WATER TANK E
3700

ROOF ACCESS

1460 2000 1500 4500 5830


2000

HVAC
2500

DUCT IDT-2 ROOM


SHAFT 35/50MVA-132/12kV
ROOM
SIC FACP

6600

4900
ET ROOM-1
4630

FAX
3600

MACHINE
500kVA 11 /0.4 kV
132kV GIS ROOM EARTHING LEGEND
4745

1395 2000 1500 TRANSFORMER


F SYMBOL DESCRIPTION
F
(+R17) (+R18)
DZ-3

11kV BBP

PAVEMENT TILES 80mm THK.


DZ-2

132kV LI BBP

(+R15) (+R14)

4900
(+R16)

110V STATION
DZ-1

CHARGER-1

PAVEMENT TILES 60mm THK.


BATTERY
CHARGER ROOM

ET ROOM-2
FALSE CEILING
CORRIDOR

500kVA 11 /0.4 kV LOCATION FOR STAMP


DCDB-2 DCDB-1
(+R12) (+R13)
DZ-2

110V

EARTHING
132kV HI BBP

F
4818

TRANSFORMER
15000

RAISED FLOOR
IDT-3 ROOM
110V STATION 110V
CZ

35/50MVA-132/12kV
IDT1
+RLA3 +RTA2

F 290mm THK.
(+R11)
DZ-1

CHARGER-2
BATTERY

THERMO BLOCK WALL


KNLG

G 240mm THK. G
132kV PROTECTION PANELS

SOLID BLOCK WALL


IDT2
+RTA4

800

+AVR
1860
CONTROL & PROTECTION ROOM

240mm THK.
RYDA
+RTA5

110V EL.

4900
CHAR.

HOLLOW BLOCK WALL


BATT.

1414

ET ROOM-3
RECORDER PANELS

+RLA7 +RBC6
B/C
DFR3

110V EL 500kVA 11 /0.4 kV REINFORCED CEMENT CONCRETE


DIGITAL FAULT

DCDB
25120

EARTHING

REFERENCE DRAWINGS
SPCB

TRANSFORMER
DFR2

2076 859 1565 470 THK. WALL (300 THK RC WALL + 50 THK
CAVITY WITH APPROVED INSULATION +100 THK
7335
+RTA8

4500
IDT3

F SOLID BLOCK WALL + 20 THK PLASTER )


DFR1

3230

2650

HANDRAIL
SPARE
+RLA9

CAGE LADDER
STAIRCASE NO.2
FUT2

R0 TPD / 132kV / FAY ROAD / SLD / 01 132kV SINGLE LINE DIAGRAM (TENDER DRAWING) --
H FIRE HOSE REEL CABINET (FHC)-CLASS-II
H
FUT1

R0 TPD / 11kV / FAY ROAD / SLD / 01 11kV SINGLE LINE DIAGRAM (TENDER DRAWING) --
SCMS PANELS

SURFACE MOUNTED
1800

CORRIDOR
+SLB3

R0 DEWA/132kV-SS/FAYROAD/001/2017 AL FAY ROAD 132/11kV SUBSTATION (TENDER DRAWING) --


914mmx914mm FIRE ESCAPE
SCMS
REV
+SLB2

PRINTER HATCH WITH LADDER DRAWING NUMBER DRAWING TITLE STATUS


TABLE FB-1 FB-EL FB-2 5645 No.
FUSE BOX FUSE BOX
+SLA3

2000

IDT INTER DISTRIBUTION TRANSFORMER


OPERATOR DESK

3000

ET EARTHING TRANSFORMER
F 1860 BATTERY ROOM-1 2500
+SLA2

BATTERY ROOM-2 SCS SUBSTATION CONTROL SYSTEM


SCMS

1905 2500 NITROGEN ROOM DFR DIGITAL FAULT RECORDER PANELS


+SLB1

REVISIONS
9650

110V DC BATTERY BANK.1 HI-BBP 132kV HIGH IMPEDANCE BUSBAR PROTECTION


LI-BBP 132kV LOW IMPEDANCE BUSBAR PROTECTION
+SLA1

LVAC LOW VOLTAGE ALTERNATING CURRENT SWITCHGEAR


7610

7610

110V DC BATTERY BANK.2


1000

1000

2000

DCDB-1 110V DC DISTRIBUTION BOARD-1


1395 2000 1442
NRV

NRV

I DCDB-2 110V DC DISTRIBUTION BOARD-2 I


FILING RACK

0 FOR DISCUSSION PR 03.11.18 SMK/DK 03.11.18 -


NRV

NRV

DZ BUSBAR PROTECTION - DISCRIMINATING ZONE


EYE WASH

EYE WASH

CABLE
AND SINK

AND SINK
BUILT-IN

CZ 132kV HI - BUSBAR PROTECTION - CHECK ZONE


3000

RISER-2 110V EMERGENCY


REV
NAME DATE NAME DATE
3430

LIGHTING BATTERY AVR AUTOMATIC VOLTAGE REGULATOR PANEL


DETAILS
2720

3680 EL-BATT 110V DC EMERGENCY LIGHTING BATTERY CHARGER No. PREPARED CHECKED STATUS
2480 CHAR.
CLIENT
1465

5540 EL DCDB 110V DC EMERGENCY LIGHTING DISTRIBUTION BOARD


10050 10105 7270 MUX TELECOMMUNICATION PANEL
800 FB BATTERY FUSE BOX
AC & VENT AIR CONDITIONING AND VENTILATION PANEL
FACP FIRE ALARM CONTROL PANEL
FECP FIRE EXTINGUISHING CONTROL PANEL GOVERNMENT OF DUBAI Dubai Electricity & Water Authority
SCP SOLENOID CONTROL PANEL Transmission power Division
VDU VOLTAGE DROP UNIT
P.O.BOX : 564, DUBAI - U.A.E
DMZ CYBER-SECURITY PANEL/DEMILITARIZED ZONE PANEL
SCMS SUBSTATION CONTROL & MONITORING SYS.
TEL : +(971) 4 3072222
CCTV CLOSED CIRCUIT TELEVISION PANEL FAX : +(971) 4 3248111
J SIC SCADA /INTERLOCK CABINET J
ASD ASPIRATION UNIT PROJECT
DACS DIGITAL ACCESS CONTROL SYSTEM
DB DISTRIBUTION BOARD
CP CONTROL PANEL
SCRD SCREED 132/11kV AL FAY ROAD SUBSTATION, DUBAI, UAE.
RCC REINFORCED CEMENT CONCRETE
CL CENTER LINE

FIRST FLOOR PLAN MAIN CONTRACTOR CONTRACT NO.

NATIONAL CONTRACTING CO.LTD


PO-3091800048

SCALE 1 : 125 STANDARD : A1 SUBSTATION NAME


K K
DATE NAME SIGNATURE
132/11kV AL FAY ROAD SUBSTATION
PREPARED 03.11.2018 PR
DRAWING NO.
CHECKED 03.11.2018 SMK
PO/3091800048/FAYROAD/EC/15/479-02
APPROVED 03.11.2018 HAB/KS
CONSULTANT / SUBCONTRACTOR DRAWING TITLE
OVERALL EQUIPMENT LAYOUT
------------------------------------
FIRST FLOOR PLAN L
L
SUB CONTRACTOR REF. CAD REF. REV SHEET LAST SHEET QTY OF SHEET
------------------------------------ XXXXXX
0 2 1 2
17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1