Sunteți pe pagina 1din 3

DOUBLE SKIN AIR HANDLING UNITS (A.H.U.

)
for PHARMACEUTICAL & CLEAN ROOM APPLICATIONS
AIREF ENGINEERS offers efficiently designed and engineered Double Skin Air Handling Units for pharmaceutical
industries, research laboratories, research institutes, hospitals, operation theaters and other clean-room applications.

AIR FLOW RANGE : 600 CFM to 6000 CFM


(Standard Models). Higher capacity units are also
available.

TOTAL STATIC PRESSURE : 40 mm W.G. to


125 mm W.G.

FRAME WORK : Extruded Aluminium profile with TECHNICAL SPECIFICATIONS


nylon reinforced 3D corner joints, used to house all internal MODEL AIR FLOW COOLING DIMENSIONS (inches)
components. Double skin sandwiched panels are fabricated COIL CAP.
from inside with 0.63 mm (24 ga) G.I. sheet and outside with (CFM) (TR) WIDTH HEIGHT
0.63 mm (24 ga) pre-coated G.I. Sheet. The panels include
sandwiched insulation resulting in high rigidity and sound ADSP-06 600 1.0 23 21
attenuation characteristics. The gasket sealed panels
(1’’ thick) are open-able for quick access. ADSP-08 800 1.5 28 21
ADSP-10 1000 2.0 32 21
FAN SECTION : Consists of double-inlet, double-width
(DIDW) centrifugal blowers (indigenous / imported) and ADSP-12 1200 2.5 32 24
pillow block, self aligning bearings. ADSP-16 1600 3.0 35 24
STATIC PRESSURE FAN MAKE ADSP-20 2000 4.0 39 26
40 mm to 65 mm AIRSCANER / NICOTRA ADSP-25 2500 5.0 45 26
100 mm to 125 mm NICOTRA ADSP-30 3000 6.0 43 32
(HEPA filter application) ADSP-35 3500 7.0 49 32
COIL SECTION : Cooling coils (Chilled Water / DX) are ADSP-40 4000 8.0 49 36
made of Copper pipe and Aluminium fins with insulated ADSP-45 4500 9.0 53 38
G.I. Sheet drain pan. Aluminium / S.S. drain pan is optional.
All coils are factory tested at dry air pressure of up to ADSP-50 5000 10.0 53 40
250 pounds under water. ADSP-60 6000 12.0 53 44

PRE FILTER : 50 mm pre-filter is provided (15 microns). Specifications are subject to change without notice.

MICRO-V FINE FILTER : Micro-V filter is provided with CLEAN ROOMS CONCENTRATES
efficiency of 99% for 5 microns.
EYE/EAR DROPS INJECTABLE UNITS
HEPA FILTER : Hepa filter with efficiency of 99.97% for LIQUID SECTION CAPSULE SECTION
0.3 microns is normally installed at duct outlet terminals.
HEPA filters to be provided at site by the client. TABLET SECTION DRY SYRUP SECTION

AIR CURTAINS FRESH AIR UNITS EXHAUST BLOWERS


(AIR WASHERS)
Sizes (Ft.): 2.5, 3, 3.5, 4, 5 & 6 Cap: 500 CFM to 30000 CFM Cap: 500 CFM to 30000 CFM
Motors: Heavy duty (1 & 3 phase) Casing: Double skin / Single skin Casing: Double skin / Single skin
Cap.: 8 m/s to 22 m/s (outlet velocity) Blowers: Aluminium / G.I., Blowers: Aluminium / G.I.,
Types: Low, High & Extra high velocity Indigenous / Imported (NICOTRA) Indigenous / Imported (NICOTRA)
For wider doors, air curtains to be Cooling Media: Cellulose Pad (FILL) Filters: Synthetic, Washable (optional)
installed in multiples. Filters: Synthetic,
Special air curtains for specific sizes Washable
and applications.

AIREF ENGINEERS
Since 1982 TECHNICAL SPECIFICATIONS

DOUBLE SKIN
B
AIR HANDLING UNITS
(FOR PHARMACEUTICAL INDUSTRIES) C
A

STATIC PRESSURE 40-65 mm WG STATIC PRESSURE 100-125 mm WG


(NICOTRA BLOWERS) (NICOTRA BLOWERS)

AIR COIL FOR HEPA FILTER APPLICATIONS


VOLUME AREA
(CFM) (Sq.Ft.) MOTOR A B C MOTOR A B C
POWER (WIDTH) (HEIGHT) (DEPTH) POWER (WIDTH) (HEIGHT) (DEPTH)
(H.P.) (H.P.)

600 1.2 0.75 23 21 66 1.0 23 21 66


800 1.6 0.75 28 21 66 1.5 28 21 66
1000 2.0 1.0 32 21 72 1.5 32 21 72
1200 2.4 1.0 32 24 72 1.5 32 24 72
1600 3.2 1.5 35 24 72 2.0 35 24 72
2000 4.0 1.5 39 26 78 2.0 39 26 78
2500 5.0 2.0 45 26 78 3.0 45 26 78
3000 6.0 2.0 43 32 81 5.0 43 32 81
3500 7.0 3.0 49 32 81 5.0 49 32 81
4000 8.0 3.0 49 36 81 5.0 49 36 81
4500 9.0 3.0 53 38 84 5.0 53 38 84
5000 10.0 5.0 53 40 90 7.5 53 40 90
6000 12.0 5.0 53 44 90 7.5 53 44 90
Specifications are subject to change without notice.

AIREF ENGINEERS
The Air Management Experts....Since 1982

AIR HANDLING UNITS | AIR WASHERS | FAN COIL UNITS


CLEAN ROOM HVAC UNITS | AIR CURTAINS | HEATING UNITS

S-ar putea să vă placă și