Date/Time Milli seconds Source Event Text

02‐09‐19 10:59 117      Waveform Captured


02‐09‐19 10:59 270 WSOS Capture Now On
02‐09‐19 10:49 627      Waveform Captured
02‐09‐19 10:49 782 WSOS Capture Now On
02‐09‐19 10:47 268 OCP  Operator control panel door opened
02‐09‐19 10:34 165 OCP  Operator control panel door closed
02‐09‐19 10:34 191      Waveform Captured
02‐09‐19 10:34 492      Under Voltage Pickup Reset
02‐09‐19 10:34 492      Phase A Minimum Voltage 0.79 pu
02‐09‐19 10:34 400      Phase A Voltage Normal
02‐09‐19 10:34 400      Phase C Voltage Normal
02‐09‐19 10:34 345      Phase C Voltage Abnormally High
02‐09‐19 10:34 345      Under Voltage Pickup
02‐09‐19 10:34 335      Phase A Voltage Abnormally Low
02‐09‐19 10:32 420      Waveform Captured
02‐09‐19 10:32 573 WSOS Capture Now On
02‐09‐19 10:27 414 OCP  Operator control panel door opened
02‐09‐19 9:53 828      Waveform Captured
02‐09‐19 9:53 129      Under Voltage Pickup Reset
02‐09‐19 9:53 129      Phase A Minimum Voltage 0.78 pu
02‐09‐19 9:53 37      Phase A Voltage Normal
02‐09‐19 9:53 32      Phase C Voltage Normal
02‐09‐19 9:53 983      Phase C Voltage Abnormally High
02‐09‐19 9:53 979      Under Voltage Pickup
02‐09‐19 9:53 969      Phase A Voltage Abnormally Low
02‐09‐19 9:53 807      Waveform Captured
02‐09‐19 9:53 105      Under Voltage Pickup Reset
02‐09‐19 9:53 105      Phase A Minimum Voltage 0.78 pu
02‐09‐19 9:53 13      Phase A Voltage Normal
02‐09‐19 9:53 10      Phase C Voltage Normal
02‐09‐19 9:52 958      Under Voltage Pickup
02‐09‐19 9:52 955      Phase C Voltage Abnormally High
02‐09‐19 9:52 947      Phase A Voltage Abnormally Low
02‐09‐19 4:33 875      Waveform Captured
02‐09‐19 4:33 139      Under Voltage Pickup Reset
02‐09‐19 4:33 139      Phase C Minimum Voltage 0.83 pu
02‐09‐19 4:33 49      Phase C Voltage Normal
02‐09‐19 4:33 44      Phase A Voltage Normal
02‐09‐19 4:33 27      Under Voltage Pickup
02‐09‐19 4:33 19      Phase A Voltage Abnormally High
02‐09‐19 4:33 16      Phase C Voltage Abnormally Low
01‐09‐19 21:49 187      Phase A Voltage Normal
01‐09‐19 21:49 179      Phase A Voltage Abnormally Low
01‐09‐19 21:49 945      Waveform Captured
01‐09‐19 21:49 243      Under Voltage Pickup Reset
01‐09‐19 21:49 243      Phase A Minimum Voltage 0.79 pu
01‐09‐19 21:49 150      Phase A Voltage Normal
01‐09‐19 21:49 148      Phase C Voltage Normal
01‐09‐19 21:49 140      Phase B Voltage Normal
01‐09‐19 21:49 95      Phase C Voltage Abnormally High
01‐09‐19 21:49 95      Phase B Voltage Abnormally High
01‐09‐19 21:49 95      Under Voltage Pickup
01‐09‐19 21:49 88      Phase A Voltage Abnormally Low
01‐09‐19 21:47 446      Phase B Voltage Normal
01‐09‐19 21:47 406      Phase A Voltage Normal
01‐09‐19 21:47 404      Phase A Voltage Abnormally Low
01‐09‐19 21:47 398      Phase B Voltage Abnormally Low
01‐09‐19 21:47 163      Waveform Captured
01‐09‐19 21:47 462      Under Voltage Pickup Reset
01‐09‐19 21:47 462      Phase A Minimum Voltage 0.78 pu
01‐09‐19 21:47 370      Phase A Voltage Normal
01‐09‐19 21:47 367      Phase C Voltage Normal
01‐09‐19 21:47 357      Phase B Voltage Normal
01‐09‐19 21:47 320      Phase B Voltage Abnormally High
01‐09‐19 21:47 315      Phase C Voltage Abnormally High
01‐09‐19 21:47 314      Under Voltage Pickup
01‐09‐19 21:47 307      Phase A Voltage Abnormally Low
01‐09‐19 17:06 573 OCP  Operator control panel door closed
01‐09‐19 17:01 214      Last Good Value Trapped is     0 A
01‐09‐19 16:54 457 PTCL DNP3 Standard ACR 2
01‐09‐19 16:52 295      Waveform Captured
01‐09‐19 16:52 448 WSOS Capture Now On
01‐09‐19 16:52 226 WSOS Waveform Capture On
01‐09‐19 16:52 573 WSOS Waveform Capture Pickup On
01‐09‐19 16:52 495 WSOS Waveform Capture Harmonics On
01‐09‐19 16:52 204 WSOS Waveform Capture Auto Close On
01‐09‐19 16:52 153 WSOS Waveform Capture Manual Close On
01‐09‐19 16:52 136 WSOS Waveform Capture Manual Trip On
01‐09‐19 16:52 550 WSOS Waveform Capture Protection Trip On
01‐09‐19 16:52 649 WSOS Waveform Capture Ratio 20/80
01‐09‐19 16:51 43 WSOS Over Voltage Protection (A) Phase logic OR
01‐09‐19 16:51 910 WSOS Over Voltage Protection (A) Alarm Mode On

01‐09‐19 16:51 260 WSOS Over Voltage Protection (A) Over Voltage Protection ON


01‐09‐19 16:51 779 WSOS Under Voltage Protection (A) Alarm Mode On
01‐09‐19 16:49 452 PTCL DNP3 Standard ACR 2
01‐09‐19 16:48 87 PTCL DNP3 Standard ACR 2
01‐09‐19 16:47 855 PTCL DNP3 Standard ACR 2
Under Voltage Protection (A) Under Voltage Protection 
01‐09‐19 16:36 854 WSOS ON
01‐09‐19 16:35 135 WSOS Under/Over Voltage (A) Fault Reset Time 100 ms
Under Voltage Protection (A) Definite Time 3.00 
01‐09‐19 16:35 617 WSOS seconds
Under Voltage Protection (A) Definite Time 2.00 
01‐09‐19 16:35 329 WSOS seconds

01‐09‐19 16:35 870 WSOS Over Voltage Protection (A) Definite Time 2.00 seconds


01‐09‐19 16:34 355 WSOS Over Voltage Protection (A) Pickup set to 1.15 pu
01‐09‐19 16:34 718 WSOS Under Voltage Protection (A) Phase logic OR
Under Voltage Protection (A) Definite Time 1.15 
01‐09‐19 16:34 529 WSOS seconds
01‐09‐19 16:33 619 WSOS Under Voltage Protection (A) Pickup set to 0.85 pu
01‐09‐19 16:32 990 WSOS Nominal Phase‐Ground 12.710 kV
01‐09‐19 16:31 43      Over Frequency Reset
01‐09‐19 16:31 43      Under Frequency Reset
01‐09‐19 16:31 43 WSOS Under / Over Frequency Not Available
01‐09‐19 16:31 170 WSOS Under / Over Voltage Protection Available
01‐09‐19 16:30 547 WSOS Under / Over Frequency Available
01‐09‐19 16:30 355 WSOS Harmonics Available

01‐09‐19 16:30 244 WSOS Sag / Swell Voltage Monitoring Monitoring Available


01‐09‐19 16:29 111 WSOS Waveform Capture Available
01‐09‐19 16:25 769 OCP  Operator control panel door opened
01‐09‐19 11:32 759 OCP  Operator control panel door closed
01‐09‐19 11:23 618 OCP  Operator control panel door opened
01‐09‐19 11:12 545 OCP  Operator control panel door closed
01‐09‐19 11:02 419 OCP  Operator control panel door opened
31‐08‐19 16:57 990      Last Good Value Trapped is     3 A
31‐08‐19 16:08 886      Last Good Value Trapped is     2 A
30‐08‐19 16:39 139      Last Good Value Trapped is     2 A
30‐08‐19 15:06 916      Last Good Value Trapped is     3 A
30‐08‐19 10:34 254      Last Good Value Trapped is     2 A
30‐08‐19 9:47 135      Last Good Value Trapped is     2 A
30‐08‐19 8:54 499      Last Good Value Trapped is     2 A
29‐08‐19 17:49 208      Last Good Value Trapped is     2 A
29‐08‐19 12:14 442      Last Good Value Trapped is     3 A
29‐08‐19 8:23 395      Last Good Value Trapped is     3 A
28‐08‐19 17:01 709      Last Good Value Trapped is     3 A
28‐08‐19 0:00 474      Battery Test Off
28‐08‐19 0:00 474      Battery Test Capacity OK
28‐08‐19 0:00 472      Battery Test End Voltage 25.18 V
28‐08‐19 0:00 472      Battery Test Middle Voltage 24.29 V
28‐08‐19 0:00 472      Battery Test Beginning Voltage 25.89 V
28‐08‐19 0:00 356      Battery Test Performing Test...
28‐08‐19 0:00 354      Battery Test Start
27‐08‐19 19:11 407      Last Good Value Trapped is     3 A
27‐08‐19 12:03 91      Last Good Value Trapped is     3 A
27‐08‐19 11:44 55      Last Good Value Trapped is     3 A
27‐08‐19 8:50 174      Last Good Value Trapped is     2 A
26‐08‐19 14:14 538      Last Good Value Trapped is     3 A
26‐08‐19 11:37 727      Last Good Value Trapped is     3 A
26‐08‐19 9:39 966      Last Good Value Trapped is     3 A
26‐08‐19 8:33 306      Last Good Value Trapped is     3 A
23‐08‐19 16:55 225      Last Good Value Trapped is     3 A
23‐08‐19 6:18 464      Last Good Value Trapped is     2 A
23‐08‐19 5:17 809      Last Good Value Trapped is     2 A
23‐08‐19 1:32 742      Last Good Value Trapped is     2 A
23‐08‐19 0:47 129      Last Good Value Trapped is     2 A
22‐08‐19 22:33 793      Last Good Value Trapped is     2 A
22‐08‐19 21:04 577      Last Good Value Trapped is     2 A
22‐08‐19 20:42 524      Last Good Value Trapped is     2 A
22‐08‐19 19:11 319      Last Good Value Trapped is     3 A
22‐08‐19 6:54 912      Last Good Value Trapped is     2 A
22‐08‐19 0:00 468      Battery Test Off
22‐08‐19 0:00 468      Battery Test Capacity OK
22‐08‐19 0:00 468      Battery Test End Voltage 25.19 V
22‐08‐19 0:00 468      Battery Test Middle Voltage 24.29 V
22‐08‐19 0:00 468      Battery Test Beginning Voltage 25.85 V
21‐08‐19 23:59 354      Battery Test Performing Test...
21‐08‐19 23:59 352      Battery Test Start
21‐08‐19 23:15 308      Last Good Value Trapped is     2 A
21‐08‐19 22:19 173      Last Good Value Trapped is     2 A
21‐08‐19 20:34 426      Last Good Value Trapped is     2 A
21‐08‐19 19:47 318      Last Good Value Trapped is     2 A
21‐08‐19 19:14 243      Last Good Value Trapped is     2 A
21‐08‐19 18:16 119      Last Good Value Trapped is     2 A
21‐08‐19 17:14 991      Last Good Value Trapped is     3 A
20‐08‐19 19:15 964      Last Good Value Trapped is     2 A
20‐08‐19 15:51 628 OCP  Operator control panel door closed
20‐08‐19 15:25 319 OCP  Operator control panel door opened
20‐08‐19 0:15 466      Last Good Value Trapped is     2 A
19‐08‐19 22:05 165      Last Good Value Trapped is     2 A
19‐08‐19 20:38 974      Last Good Value Trapped is     2 A
19‐08‐19 19:31 337      Last Good Value Trapped is     2 A
Current at maximum Phase C ‐ Maximum Current of 54 
19‐08‐19 15:41 280      A during fault
Current at maximum Phase B ‐ Maximum Current of 31 
19‐08‐19 15:41 280      A during fault
Current at maximum Phase A ‐ Maximum Current of 70 
19‐08‐19 15:41 280      A during fault
19‐08‐19 15:41 280      Protection Disk Reset
19‐08‐19 15:41 230      All protection elements resetting
19‐08‐19 15:41 170      Protection Group A Active
19‐08‐19 15:41 170      Pickup Phase A
19‐08‐19 15:41 170      Pickup
19‐08‐19 12:54 22 OCP  Operator control panel door closed
19‐08‐19 12:47 0 WSOS 19‐08‐19 12:47
19‐08‐19 12:43 621      Last Good Value Trapped is     0 A
19‐08‐19 12:39 510 OCP  Operator control panel door opened
19‐08‐19 12:27 786      Inrush current timer expired
Current at maximum Phase C ‐ Maximum Current of 78 
19‐08‐19 12:27 898      A during fault
Current at maximum Phase B ‐ Maximum Current of 77 
19‐08‐19 12:27 898      A during fault
Current at maximum Phase A ‐ Maximum Current of 27 
19‐08‐19 12:27 898      A during fault
19‐08‐19 12:27 898      Protection Disk Reset
19‐08‐19 12:27 843      All protection elements resetting
19‐08‐19 12:27 781      Pickup Phase C
19‐08‐19 12:27 781      Pickup Phase B
19‐08‐19 12:27 781      Pickup
19‐08‐19 12:27 788      Inrush current timing has started
19‐08‐19 12:27 593      Last Good Value Trapped is     3 A
19‐08‐19 12:27 708      Inrush current timer ready
18‐08‐19 21:11 890      Inrush current timer expired
18‐08‐19 21:11 927      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 74 
18‐08‐19 21:11 55      A during fault
Current at maximum Phase B ‐ Maximum Current of 71 
18‐08‐19 21:11 55      A during fault
Current at maximum Phase A ‐ Maximum Current of 121 
18‐08‐19 21:11 55      A during fault
18‐08‐19 21:11 55      Protection Disk Reset
18‐08‐19 21:11 990      All protection elements resetting
18‐08‐19 21:11 990      Protection element timing
18‐08‐19 21:11 988      All protection elements resetting
18‐08‐19 21:11 988      Protection element timing
18‐08‐19 21:11 985      All protection elements resetting
18‐08‐19 21:11 985      Protection element timing
18‐08‐19 21:11 983      All protection elements resetting
18‐08‐19 21:11 982      Protection element timing
18‐08‐19 21:11 980      All protection elements resetting
18‐08‐19 21:11 980      Protection element timing
18‐08‐19 21:11 978      All protection elements resetting
18‐08‐19 21:11 978      Protection element timing
18‐08‐19 21:11 975      All protection elements resetting
18‐08‐19 21:11 975      Protection element timing
18‐08‐19 21:11 973      All protection elements resetting
18‐08‐19 21:11 973      Protection element timing
18‐08‐19 21:11 970      All protection elements resetting
18‐08‐19 21:11 970      Protection element timing
18‐08‐19 21:11 968      All protection elements resetting
18‐08‐19 21:11 968      Protection element timing
18‐08‐19 21:11 966      All protection elements resetting
18‐08‐19 21:11 966      Protection element timing
18‐08‐19 21:11 963      All protection elements resetting
18‐08‐19 21:11 963      Protection element timing
18‐08‐19 21:11 960      All protection elements resetting
18‐08‐19 21:11 960      Protection element timing
18‐08‐19 21:11 958      All protection elements resetting
18‐08‐19 21:11 958      Protection element timing
18‐08‐19 21:11 955      All protection elements resetting
18‐08‐19 21:11 955      Protection element timing
18‐08‐19 21:11 952      All protection elements resetting
18‐08‐19 21:11 952      Protection element timing
18‐08‐19 21:11 951      All protection elements resetting
18‐08‐19 21:11 951      Protection element timing
18‐08‐19 21:11 948      All protection elements resetting
18‐08‐19 21:11 948      Protection element timing
18‐08‐19 21:11 945      All protection elements resetting
18‐08‐19 21:11 945      Protection element timing
18‐08‐19 21:11 942      All protection elements resetting
18‐08‐19 21:11 910      Pickup Phase B
18‐08‐19 21:11 906      Pickup Phase C
18‐08‐19 21:11 882      Pickup Phase A
18‐08‐19 21:11 882      Pickup
18‐08‐19 21:11 900      Measuring Frequency On Bushing Ai
18‐08‐19 21:11 892      Inrush current timing has started
18‐08‐19 21:11 987      Source Supply Off
18‐08‐19 21:10 939      Measuring Frequency On Bushing Bi
18‐08‐19 21:10 917      Inrush current timer ready
18‐08‐19 19:41 181      Inrush current timer expired
18‐08‐19 19:41 238      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 41 
18‐08‐19 19:41 323      A during fault
Current at maximum Phase B ‐ Maximum Current of 99 
18‐08‐19 19:41 323      A during fault
Current at maximum Phase A ‐ Maximum Current of 79 
18‐08‐19 19:41 323      A during fault
18‐08‐19 19:41 323      Protection Disk Reset
18‐08‐19 19:41 258      All protection elements resetting
18‐08‐19 19:41 258      Protection element timing
18‐08‐19 19:41 256      All protection elements resetting
18‐08‐19 19:41 256      Protection element timing
18‐08‐19 19:41 254      All protection elements resetting
18‐08‐19 19:41 254      Protection element timing
18‐08‐19 19:41 251      All protection elements resetting
18‐08‐19 19:41 251      Protection element timing
18‐08‐19 19:41 248      All protection elements resetting
18‐08‐19 19:41 248      Protection element timing
18‐08‐19 19:41 246      All protection elements resetting
18‐08‐19 19:41 246      Protection element timing
18‐08‐19 19:41 243      All protection elements resetting
18‐08‐19 19:41 173      Pickup Phase B
18‐08‐19 19:41 173      Pickup Phase A
18‐08‐19 19:41 173      Pickup
18‐08‐19 19:41 183      Inrush current timing has started
18‐08‐19 19:41 298      Source Supply Off
18‐08‐19 19:41 188      Inrush current timer ready
18‐08‐19 19:35 275      Last Good Value Trapped is     2 A
18‐08‐19 18:07 612      Last Good Value Trapped is     2 A
18‐08‐19 16:06 433      Last Good Value Trapped is     2 A
18‐08‐19 13:33 205      Last Good Value Trapped is     2 A
18‐08‐19 9:44 315      Last Good Value Trapped is     2 A
18‐08‐19 8:58 230      Last Good Value Trapped is     2 A
18‐08‐19 6:00 328      Last Good Value Trapped is     2 A
18‐08‐19 1:30 651      Last Good Value Trapped is     2 A
18‐08‐19 0:01 928      Last Good Value Trapped is     2 A
17‐08‐19 16:40 872      Last Good Value Trapped is     3 A
17‐08‐19 14:57 134      Last Good Value Trapped is     3 A
17‐08‐19 14:15 540      Last Good Value Trapped is     3 A
17‐08‐19 12:30 547      Inrush current timer expired
17‐08‐19 12:30 695      Auxiliary Supply Normal
17‐08‐19 12:30 599      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 66 
17‐08‐19 12:30 659      A during fault
Current at maximum Phase B ‐ Maximum Current of 24 
17‐08‐19 12:30 659      A during fault
Current at maximum Phase A ‐ Maximum Current of 58 
17‐08‐19 12:30 659      A during fault
17‐08‐19 12:30 659      Protection Disk Reset
17‐08‐19 12:30 609      All protection elements resetting
17‐08‐19 12:30 544      Pickup Phase C
17‐08‐19 12:30 544      Pickup
17‐08‐19 12:30 549      Inrush current timing has started
17‐08‐19 12:30 312      Auxiliary Supply Failure
17‐08‐19 12:30 939      Source Supply Off
17‐08‐19 12:30 346      Last Good Value Trapped is     3 A
17‐08‐19 12:30 886      Inrush current timer ready
17‐08‐19 1:42 940      Last Good Value Trapped is     2 A
17‐08‐19 1:10 863      Last Good Value Trapped is     2 A
16‐08‐19 23:36 643      Last Good Value Trapped is     2 A
16‐08‐19 23:03 566      Last Good Value Trapped is     2 A
16‐08‐19 20:51 767      Last Good Value Trapped is     2 A
16‐08‐19 20:06 667      Last Good Value Trapped is     2 A
16‐08‐19 19:18 566      Last Good Value Trapped is     2 A
16‐08‐19 18:59 527      Last Good Value Trapped is     3 A
15‐08‐19 23:59 419      Battery Test Off
15‐08‐19 23:59 419      Battery Test Capacity OK
15‐08‐19 23:59 415      Battery Test End Voltage 25.16 V
15‐08‐19 23:59 415      Battery Test Middle Voltage 24.29 V
15‐08‐19 23:59 415      Battery Test Beginning Voltage 25.82 V
15‐08‐19 23:59 293      Battery Test Performing Test...
15‐08‐19 23:59 291      Battery Test Start
15‐08‐19 19:31 254      Inrush current timer expired
15‐08‐19 19:31 394      Auxiliary Supply Normal
15‐08‐19 19:31 291      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 82 
15‐08‐19 19:31 371      A during fault
Current at maximum Phase B ‐ Maximum Current of 32 
15‐08‐19 19:31 371      A during fault
Current at maximum Phase A ‐ Maximum Current of 63 
15‐08‐19 19:31 371      A during fault
15‐08‐19 19:31 371      Protection Disk Reset
15‐08‐19 19:31 306      All protection elements resetting
15‐08‐19 19:31 306      Protection element timing
15‐08‐19 19:31 304      All protection elements resetting
15‐08‐19 19:31 304      Protection element timing
15‐08‐19 19:31 301      All protection elements resetting
15‐08‐19 19:31 301      Protection element timing
15‐08‐19 19:31 300      All protection elements resetting
15‐08‐19 19:31 300      Protection element timing
15‐08‐19 19:31 297      All protection elements resetting
15‐08‐19 19:31 297      Protection element timing
15‐08‐19 19:31 294      All protection elements resetting
15‐08‐19 19:31 294      Protection element timing
15‐08‐19 19:31 291      All protection elements resetting
15‐08‐19 19:31 274      Pickup Phase A
15‐08‐19 19:31 246      Pickup Phase C
15‐08‐19 19:31 246      Pickup
15‐08‐19 19:31 256      Inrush current timing has started
15‐08‐19 19:29 994      Auxiliary Supply Failure
15‐08‐19 19:29 805      Source Supply Off
15‐08‐19 19:29 767      Inrush current timer ready
15‐08‐19 19:12 76      Last Good Value Trapped is     3 A
15‐08‐19 8:35 668 OCP  Operator control panel door closed
15‐08‐19 8:28 996 OCP  Operator control panel door opened
15‐08‐19 1:19 515      Inrush current timer expired
15‐08‐19 1:19 564      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 84 
15‐08‐19 1:19 654      A during fault
Current at maximum Phase B ‐ Maximum Current of 97 
15‐08‐19 1:19 654      A during fault
Current at maximum Phase A ‐ Maximum Current of 38 
15‐08‐19 1:19 654      A during fault
15‐08‐19 1:19 654      Protection Disk Reset
15‐08‐19 1:19 590      All protection elements resetting
15‐08‐19 1:19 590      Protection element timing
15‐08‐19 1:19 587      All protection elements resetting
15‐08‐19 1:19 530      Pickup Phase C
15‐08‐19 1:19 507      Pickup Phase B
15‐08‐19 1:19 507      Pickup
15‐08‐19 1:19 517      Inrush current timing has started
15‐08‐19 1:19 852      Source Supply Off
15‐08‐19 1:19 549      Inrush current timer ready
15‐08‐19 0:01 200      Last Good Value Trapped is     2 A
14‐08‐19 22:23 218      Inrush current timer expired
14‐08‐19 22:23 275      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 98 
14‐08‐19 22:23 357      A during fault
Current at maximum Phase B ‐ Maximum Current of 39 
14‐08‐19 22:23 357      A during fault
Current at maximum Phase A ‐ Maximum Current of 79 
14‐08‐19 22:23 357      A during fault
14‐08‐19 22:23 357      Protection Disk Reset
14‐08‐19 22:23 293      All protection elements resetting
14‐08‐19 22:23 293      Protection element timing
14‐08‐19 22:23 290      All protection elements resetting
14‐08‐19 22:23 290      Protection element timing
14‐08‐19 22:23 288      All protection elements resetting
14‐08‐19 22:23 288      Protection element timing
14‐08‐19 22:23 285      All protection elements resetting
14‐08‐19 22:23 233      Pickup Phase A
14‐08‐19 22:23 210      Pickup Phase C
14‐08‐19 22:23 210      Pickup
14‐08‐19 22:23 220      Inrush current timing has started
14‐08‐19 22:23 335      Source Supply Off
14‐08‐19 22:23 470      Last Good Value Trapped is     2 A
14‐08‐19 22:23 242      Inrush current timer ready
14‐08‐19 21:30 350      Last Good Value Trapped is     2 A
14‐08‐19 20:03 654      Last Good Value Trapped is     2 A
14‐08‐19 19:10 42      Last Good Value Trapped is     3 A
13‐08‐19 17:41 843 OCP  Operator control panel door closed
13‐08‐19 17:36 415 OCP  Operator control panel door opened
13‐08‐19 17:31 378 OCP  Operator control panel door closed
13‐08‐19 17:29 44      Inrush current timer expired
Current at maximum Phase C ‐ Maximum Current of 40 
13‐08‐19 17:29 187      A during fault
Current at maximum Phase B ‐ Maximum Current of 96 
13‐08‐19 17:29 187      A during fault
Current at maximum Phase A ‐ Maximum Current of 74 
13‐08‐19 17:29 187      A during fault
13‐08‐19 17:29 187      Protection Disk Reset
13‐08‐19 17:29 122      All protection elements resetting
13‐08‐19 17:29 122      Protection element timing
13‐08‐19 17:29 119      All protection elements resetting
13‐08‐19 17:29 119      Protection element timing
13‐08‐19 17:29 117      All protection elements resetting
13‐08‐19 17:29 117      Protection element timing
13‐08‐19 17:29 114      All protection elements resetting
13‐08‐19 17:29 114      Protection element timing
13‐08‐19 17:29 112      All protection elements resetting
13‐08‐19 17:29 112      Protection element timing
13‐08‐19 17:29 109      All protection elements resetting
13‐08‐19 17:29 109      Protection element timing
13‐08‐19 17:29 106      All protection elements resetting
13‐08‐19 17:29 106      Protection element timing
13‐08‐19 17:29 105      All protection elements resetting
13‐08‐19 17:29 105      Protection element timing
13‐08‐19 17:29 101      All protection elements resetting
13‐08‐19 17:29 62      Pickup Phase A
13‐08‐19 17:29 39      Pickup Phase B
13‐08‐19 17:29 39      Pickup
13‐08‐19 17:29 46      Inrush current timing has started
13‐08‐19 17:29 2 OCP  Panel Close Request
13‐08‐19 17:29 202      Auxiliary Supply Normal
13‐08‐19 17:29 106      Source Supply On
13‐08‐19 17:29 511      Auxiliary Supply Failure
13‐08‐19 17:29 240      Source Supply Off
13‐08‐19 17:28 328      Inrush current timer ready
13‐08‐19 17:28 306      Lockout
13‐08‐19 17:28 279 OCP  Panel Trip Request
13‐08‐19 17:27 70 OCP  Operator control panel door opened
13‐08‐19 16:39 714 OCP  Operator control panel door closed
13‐08‐19 16:38 636 OCP  Operator control panel door opened
13‐08‐19 16:21 325      Inrush current timer expired
13‐08‐19 16:21 479      Auxiliary Supply Normal
13‐08‐19 16:21 375      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 133 
13‐08‐19 16:21 498      A during fault
Current at maximum Phase B ‐ Maximum Current of 71 
13‐08‐19 16:21 498      A during fault
Current at maximum Phase A ‐ Maximum Current of 86 
13‐08‐19 16:21 498      A during fault
13‐08‐19 16:21 498      Protection Disk Reset
13‐08‐19 16:21 433      All protection elements resetting
13‐08‐19 16:21 433      Protection element timing
13‐08‐19 16:21 430      All protection elements resetting
13‐08‐19 16:21 430      Protection element timing
13‐08‐19 16:21 428      All protection elements resetting
13‐08‐19 16:21 428      Protection element timing
13‐08‐19 16:21 426      All protection elements resetting
13‐08‐19 16:21 426      Protection element timing
13‐08‐19 16:21 423      All protection elements resetting
13‐08‐19 16:21 423      Protection element timing
13‐08‐19 16:21 420      All protection elements resetting
13‐08‐19 16:21 420      Protection element timing
13‐08‐19 16:21 418      All protection elements resetting
13‐08‐19 16:21 418      Protection element timing
13‐08‐19 16:21 416      All protection elements resetting
13‐08‐19 16:21 416      Protection element timing
13‐08‐19 16:21 413      All protection elements resetting
13‐08‐19 16:21 413      Protection element timing
13‐08‐19 16:21 411      All protection elements resetting
13‐08‐19 16:21 411      Protection element timing
13‐08‐19 16:21 408      All protection elements resetting
13‐08‐19 16:21 408      Protection element timing
13‐08‐19 16:21 406      All protection elements resetting
13‐08‐19 16:21 406      Protection element timing
13‐08‐19 16:21 403      All protection elements resetting
13‐08‐19 16:21 403      Protection element timing
13‐08‐19 16:21 401      All protection elements resetting
13‐08‐19 16:21 401      Protection element timing
13‐08‐19 16:21 398      All protection elements resetting
13‐08‐19 16:21 398      Protection element timing
13‐08‐19 16:21 395      All protection elements resetting
13‐08‐19 16:21 395      Protection element timing
13‐08‐19 16:21 393      All protection elements resetting
13‐08‐19 16:21 393      Protection element timing
13‐08‐19 16:21 391      All protection elements resetting
13‐08‐19 16:21 390      Protection element timing
13‐08‐19 16:21 388      All protection elements resetting
13‐08‐19 16:21 388      Protection element timing
13‐08‐19 16:21 385      All protection elements resetting
13‐08‐19 16:21 385      Protection element timing
13‐08‐19 16:21 383      All protection elements resetting
13‐08‐19 16:21 383      Protection element timing
13‐08‐19 16:21 381      All protection elements resetting
13‐08‐19 16:21 381      Protection element timing
13‐08‐19 16:21 378      All protection elements resetting
13‐08‐19 16:21 378      Protection element timing
13‐08‐19 16:21 375      All protection elements resetting
13‐08‐19 16:21 375      Protection element timing
13‐08‐19 16:21 373      All protection elements resetting
13‐08‐19 16:21 373      Protection element timing
13‐08‐19 16:21 371      All protection elements resetting
13‐08‐19 16:21 361      Measuring Frequency On Bushing Ai
13‐08‐19 16:21 340      Pickup Phase B
13‐08‐19 16:21 340      Pickup Phase A
13‐08‐19 16:21 316      Pickup Phase C
13‐08‐19 16:21 316      Pickup
13‐08‐19 16:21 327      Inrush current timing has started
13‐08‐19 16:18 676      Auxiliary Supply Failure
13‐08‐19 16:18 621      Source Supply Off
13‐08‐19 16:18 573      Measuring Frequency On Bushing Bi
13‐08‐19 16:18 321      Inrush current timer ready
13‐08‐19 15:55 321 OCP  Operator control panel door closed
13‐08‐19 15:51 770 OCP  Operator control panel door opened
13‐08‐19 15:29 620 OCP  Operator control panel door closed
13‐08‐19 15:29 432 OCP  Operator control panel door opened
13‐08‐19 15:28 428 OCP  Operator control panel door closed
13‐08‐19 15:27 541      Inrush current timer expired
Current at maximum Phase C ‐ Maximum Current of 48 
13‐08‐19 15:27 689      A during fault
Current at maximum Phase B ‐ Maximum Current of 102 
13‐08‐19 15:27 689      A during fault
Current at maximum Phase A ‐ Maximum Current of 74 
13‐08‐19 15:27 689      A during fault
13‐08‐19 15:27 689      Protection Disk Reset
13‐08‐19 15:27 624      All protection elements resetting
13‐08‐19 15:27 624      Protection element timing
13‐08‐19 15:27 621      All protection elements resetting
13‐08‐19 15:27 621      Protection element timing
13‐08‐19 15:27 619      All protection elements resetting
13‐08‐19 15:27 619      Protection element timing
13‐08‐19 15:27 616      All protection elements resetting
13‐08‐19 15:27 616      Protection element timing
13‐08‐19 15:27 614      All protection elements resetting
13‐08‐19 15:27 614      Protection element timing
13‐08‐19 15:27 611      All protection elements resetting
13‐08‐19 15:27 611      Protection element timing
13‐08‐19 15:27 609      All protection elements resetting
13‐08‐19 15:27 609      Protection element timing
13‐08‐19 15:27 606      All protection elements resetting
13‐08‐19 15:27 606      Protection element timing
13‐08‐19 15:27 604      All protection elements resetting
13‐08‐19 15:27 604      Protection element timing
13‐08‐19 15:27 601      All protection elements resetting
13‐08‐19 15:27 601      Protection element timing
13‐08‐19 15:27 599      All protection elements resetting
13‐08‐19 15:27 561      Pickup Phase A
13‐08‐19 15:27 534      Pickup Phase B
13‐08‐19 15:27 534      Pickup
13‐08‐19 15:27 544      Inrush current timing has started
13‐08‐19 15:27 501 OCP  Panel Close Request
13‐08‐19 15:27 423      Close Coil Connect
13‐08‐19 15:27 407      Trip Coil Connected
13‐08‐19 15:27 666 OCP  Trip Coil Disconnected
13‐08‐19 15:27 661 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:27 563 OCP  Trip Coil Disconnected
13‐08‐19 15:27 558 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:27 666 OCP  Trip Coil Disconnected
13‐08‐19 15:27 661 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:27 485 OCP  Trip Coil Disconnected
13‐08‐19 15:27 480 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:27 347 OCP  Trip Coil Disconnected
13‐08‐19 15:27 341 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:27 794 OCP  Trip Coil Disconnected
13‐08‐19 15:27 787 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:27 173 OCP  Trip Coil Disconnected
13‐08‐19 15:27 168 OCP  Panel Trip Request ‐ Denied
13‐08‐19 15:27 439 OCP  Trip Coil Disconnected
13‐08‐19 15:27 432 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:26 377      Close Coil Disconnected
13‐08‐19 15:26 361      Trip Coil Disconnected
13‐08‐19 15:26 315 OCP  Close Coil Disconnected
13‐08‐19 15:26 311 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:26 898      Close Coil Connect
13‐08‐19 15:26 850      Trip Coil Connected
13‐08‐19 15:26 655 OCP  Trip Coil Disconnected
13‐08‐19 15:26 650 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:26 3 OCP  Trip Coil Disconnected
13‐08‐19 15:26 996 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:26 392 OCP  Trip Coil Disconnected
13‐08‐19 15:26 387 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:26 230 OCP  Trip Coil Disconnected
13‐08‐19 15:26 225 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:26 503 OCP  Trip Coil Disconnected
13‐08‐19 15:26 498 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:26 274      Close Coil Disconnected
13‐08‐19 15:26 274      Trip Coil Disconnected
13‐08‐19 15:26 732 OCP  Close Coil Disconnected
13‐08‐19 15:26 727 OCP  Panel Close Request ‐ Denied
13‐08‐19 15:26 153 OCP  Operator control panel door opened
13‐08‐19 15:24 760      Auxiliary Supply Normal
13‐08‐19 15:24 666      Source Supply On
13‐08‐19 15:24 78      Auxiliary Supply Failure
13‐08‐19 15:24 136 OCP  Operator control panel door closed
13‐08‐19 15:24 868      Source Supply Off
13‐08‐19 15:23 527      Close Coil Connect
13‐08‐19 15:23 527      Trip Coil Connected
13‐08‐19 15:23 713      Close Coil Disconnected
13‐08‐19 15:23 441      Trip Coil Disconnected
13‐08‐19 15:23 749      Last Good Value Trapped is     3 A
13‐08‐19 15:23 819      Inrush current timer ready
13‐08‐19 15:23 792      Lockout
13‐08‐19 15:23 761 OCP  Panel Trip Request
13‐08‐19 15:23 15 OCP  Operator control panel door opened
12‐08‐19 18:03 661 OCP  Operator control panel door closed
12‐08‐19 18:00 0 WSOS 12‐08‐19 18:00
12‐08‐19 17:59 383      Load Supply Off
12‐08‐19 17:59 383      Source Supply On
12‐08‐19 17:59 362 WSOS Source I, Load X
12‐08‐19 17:58 938      Source Supply Off
12‐08‐19 17:58 938      Load Supply On
12‐08‐19 17:58 910 WSOS Source X, Load I
12‐08‐19 17:58 397 WSOS Power Unsigned
12‐08‐19 17:58 507 WSOS Power Signed
12‐08‐19 17:58 899 WSOS Power Unsigned
12‐08‐19 17:54 963 OCP  Operator control panel door opened
12‐08‐19 17:41 123      Inrush current timer expired
12‐08‐19 17:41 301      Auxiliary Supply Normal
12‐08‐19 17:41 182      Source Supply On
12‐08‐19 17:41 125      Inrush current timing has started
12‐08‐19 17:31 872      Auxiliary Supply Failure
12‐08‐19 17:30 863      Source Supply Off
12‐08‐19 17:30 765      Inrush current timer ready
12‐08‐19 17:02 33      Last Good Value Trapped is     2 A
12‐08‐19 8:43 213 OCP  Operator control panel door closed
12‐08‐19 8:41 771 OCP  Operator control panel door opened
12‐08‐19 8:38 757 OCP  Operator control panel door closed
12‐08‐19 8:37 321 OCP  Operator control panel door opened
12‐08‐19 7:42 2      Inrush current timer expired
12‐08‐19 7:42 153      Auxiliary Supply Normal
12‐08‐19 7:42 41      Source Supply On
12‐08‐19 7:42 4      Inrush current timing has started
12‐08‐19 7:42 322      Auxiliary Supply Failure
12‐08‐19 7:42 411      Source Supply Off
12‐08‐19 7:42 338      Inrush current timer ready
12‐08‐19 7:17 736 OCP  Operator control panel door closed
12‐08‐19 7:16 570 OCP  Operator control panel door opened
12‐08‐19 6:45 717      Inrush current timer expired
12‐08‐19 6:45 865      Auxiliary Supply Normal
12‐08‐19 6:45 769      Source Supply On
12‐08‐19 6:45 744      Measuring Frequency On Bushing Ai
12‐08‐19 6:45 719      Inrush current timing has started
12‐08‐19 6:45 470      Auxiliary Supply Failure
12‐08‐19 6:44 238      Source Supply Off
12‐08‐19 6:44 183      Measuring Frequency On Bushing Ci
12‐08‐19 6:44 153      Inrush current timer ready
12‐08‐19 6:01 526      Inrush current timer expired
12‐08‐19 6:01 675      Auxiliary Supply Normal
12‐08‐19 6:01 591      Source Supply On
12‐08‐19 6:01 534      Measuring Frequency On Bushing Ai
12‐08‐19 6:01 528      Inrush current timing has started
12‐08‐19 6:00 817      Auxiliary Supply Failure
12‐08‐19 6:00 560      Source Supply Off
12‐08‐19 6:00 512      Measuring Frequency On Bushing Bi
12‐08‐19 6:00 482      Inrush current timer ready
11‐08‐19 15:23 479 OCP  Operator control panel door closed
11‐08‐19 15:22 646      Inrush current timer expired
Current at maximum Phase C ‐ Maximum Current of 62 
11‐08‐19 15:22 723      A during fault
Current at maximum Phase B ‐ Maximum Current of 48 
11‐08‐19 15:22 723      A during fault
Current at maximum Phase A ‐ Maximum Current of 26 
11‐08‐19 15:22 723      A during fault
11‐08‐19 15:22 723      Protection Disk Reset
11‐08‐19 15:22 674      All protection elements resetting
11‐08‐19 15:22 643      Pickup Phase C
11‐08‐19 15:22 643      Pickup
11‐08‐19 15:22 648      Inrush current timing has started
11‐08‐19 15:22 601 OCP  Panel Close Request
11‐08‐19 15:21 943      Close Coil Connect
11‐08‐19 15:21 927      Trip Coil Connected
11‐08‐19 15:21 110 OCP  Operator control panel door opened
11‐08‐19 11:34 39      Normal Power Mode
11‐08‐19 11:29 843      Battery Normal
11‐08‐19 11:29 565      Auxiliary Supply Normal
11‐08‐19 11:29 241      Source Supply On
11‐08‐19 11:29 221      Measuring Frequency On Bushing Ai
11‐08‐19 11:19 142      Low Power Mode
11‐08‐19 10:24 195      Maintenance Required
11‐08‐19 10:24 195      Battery Low
11‐08‐19 8:42 293 OCP  Operator control panel door closed
11‐08‐19 8:41 252      Trip Coil Disconnected
11‐08‐19 8:41 220      Close Coil Disconnected
11‐08‐19 8:41 139      Lockout
11‐08‐19 8:41 108 OCP  Panel Trip Request
11‐08‐19 8:41 247 OCP  Operator control panel door opened
11‐08‐19 8:37 233      Auxiliary Supply Failure
11‐08‐19 8:37 190      Source Supply Off
11‐08‐19 8:37 137      Measuring Frequency On Bushing Ci
11‐08‐19 8:37 800      Inrush current timer ready
10‐08‐19 11:26 683      Last Good Value Trapped is     2 A
10‐08‐19 9:31 172 OCP  Operator control panel door closed
10‐08‐19 9:24 961 OCP  Operator control panel door opened
10‐08‐19 0:06 546      Last Good Value Trapped is     2 A
09‐08‐19 23:22 942      Last Good Value Trapped is     2 A
09‐08‐19 18:21 782      Last Good Value Trapped is     2 A
09‐08‐19 0:00 704      Battery Test Off
09‐08‐19 0:00 704      Battery Test Capacity OK
09‐08‐19 0:00 700      Battery Test End Voltage 25.20 V
09‐08‐19 0:00 700      Battery Test Middle Voltage 24.35 V
09‐08‐19 0:00 700      Battery Test Beginning Voltage 25.90 V
09‐08‐19 0:00 586      Battery Test Performing Test...
09‐08‐19 0:00 583      Battery Test Start
08‐08‐19 20:33 20      Inrush current timer expired
Current at maximum Phase C ‐ Maximum Current of 136 
08‐08‐19 20:33 186      A during fault
Current at maximum Phase B ‐ Maximum Current of 75 
08‐08‐19 20:33 186      A during fault
Current at maximum Phase A ‐ Maximum Current of 87 
08‐08‐19 20:33 186      A during fault
08‐08‐19 20:33 186      Protection Disk Reset
08‐08‐19 20:33 123      All protection elements resetting
08‐08‐19 20:33 123      Protection element timing
08‐08‐19 20:33 121      All protection elements resetting
08‐08‐19 20:33 121      Protection element timing
08‐08‐19 20:33 118      All protection elements resetting
08‐08‐19 20:33 118      Protection element timing
08‐08‐19 20:33 115      All protection elements resetting
08‐08‐19 20:33 115      Protection element timing
08‐08‐19 20:33 114      All protection elements resetting
08‐08‐19 20:33 113      Protection element timing
08‐08‐19 20:33 110      All protection elements resetting
08‐08‐19 20:33 110      Protection element timing
08‐08‐19 20:33 108      All protection elements resetting
08‐08‐19 20:33 108      Protection element timing
08‐08‐19 20:33 105      All protection elements resetting
08‐08‐19 20:33 105      Protection element timing
08‐08‐19 20:33 103      All protection elements resetting
08‐08‐19 20:33 103      Protection element timing
08‐08‐19 20:33 100      All protection elements resetting
08‐08‐19 20:33 100      Protection element timing
08‐08‐19 20:33 98      All protection elements resetting
08‐08‐19 20:33 98      Protection element timing
08‐08‐19 20:33 95      All protection elements resetting
08‐08‐19 20:33 95      Protection element timing
08‐08‐19 20:33 93      All protection elements resetting
08‐08‐19 20:33 93      Protection element timing
08‐08‐19 20:33 91      All protection elements resetting
08‐08‐19 20:33 91      Protection element timing
08‐08‐19 20:33 88      All protection elements resetting
08‐08‐19 20:33 88      Protection element timing
08‐08‐19 20:33 86      All protection elements resetting
08‐08‐19 20:33 86      Protection element timing
08‐08‐19 20:33 83      All protection elements resetting
08‐08‐19 20:33 83      Protection element timing
08‐08‐19 20:33 80      All protection elements resetting
08‐08‐19 20:33 80      Protection element timing
08‐08‐19 20:33 78      All protection elements resetting
08‐08‐19 20:33 78      Protection element timing
08‐08‐19 20:33 76      All protection elements resetting
08‐08‐19 20:33 76      Protection element timing
08‐08‐19 20:33 73      All protection elements resetting
08‐08‐19 20:33 73      Protection element timing
08‐08‐19 20:33 71      All protection elements resetting
08‐08‐19 20:33 71      Protection element timing
08‐08‐19 20:33 68      All protection elements resetting
08‐08‐19 20:33 36      Pickup Phase A
08‐08‐19 20:33 33      Pickup Phase B
08‐08‐19 20:33 10      Pickup Phase C
08‐08‐19 20:33 10      Pickup
08‐08‐19 20:33 23      Inrush current timing has started
08‐08‐19 20:23 676 OCP  Operator control panel door closed
08‐08‐19 20:23 503 OCP  Panel Close Request
08‐08‐19 20:23 650 OCP  Operator control panel door opened
08‐08‐19 20:23 650 OCP  Operator control panel door closed
08‐08‐19 20:11 593 OCP  Operator control panel door opened
08‐08‐19 19:46 417 OCP  Operator control panel door closed
08‐08‐19 19:46 473      Inrush current timer ready
08‐08‐19 19:46 463      Lockout
08‐08‐19 19:46 434 OCP  Panel Trip Request
08‐08‐19 19:46 416 OCP  Operator control panel door opened
08‐08‐19 19:30 757      Last Good Value Trapped is     2 A
08‐08‐19 7:02 226      Last Good Value Trapped is     2 A
08‐08‐19 0:36 771      Last Good Value Trapped is     2 A
07‐08‐19 22:05 915      Last Good Value Trapped is     2 A
07‐08‐19 21:42 862      Last Good Value Trapped is     2 A
07‐08‐19 18:13 897      Last Good Value Trapped is     2 A
07‐08‐19 6:47 943      Last Good Value Trapped is     2 A
06‐08‐19 23:59 915      Last Good Value Trapped is     2 A
06‐08‐19 22:55 756      Last Good Value Trapped is     2 A
06‐08‐19 22:16 162      Last Good Value Trapped is     2 A
06‐08‐19 21:13 510      Last Good Value Trapped is     2 A
06‐08‐19 20:09 360      Last Good Value Trapped is     2 A
06‐08‐19 9:44 129      Last Good Value Trapped is     3 A
05‐08‐19 23:05 581      Inrush current timer expired
05‐08‐19 23:05 704      Auxiliary Supply Normal
05‐08‐19 23:05 639      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 99 
05‐08‐19 23:05 769      A during fault
Current at maximum Phase B ‐ Maximum Current of 155 
05‐08‐19 23:05 769      A during fault
Current at maximum Phase A ‐ Maximum Current of 84 
05‐08‐19 23:05 769      A during fault
05‐08‐19 23:05 769      Protection Disk Reset
05‐08‐19 23:05 704      All protection elements resetting
05‐08‐19 23:05 704      Protection element timing
05‐08‐19 23:05 701      All protection elements resetting
05‐08‐19 23:05 701      Protection element timing
05‐08‐19 23:05 699      All protection elements resetting
05‐08‐19 23:05 699      Protection element timing
05‐08‐19 23:05 696      All protection elements resetting
05‐08‐19 23:05 696      Protection element timing
05‐08‐19 23:05 694      All protection elements resetting
05‐08‐19 23:05 694      Protection element timing
05‐08‐19 23:05 691      All protection elements resetting
05‐08‐19 23:05 691      Protection element timing
05‐08‐19 23:05 689      All protection elements resetting
05‐08‐19 23:05 689      Protection element timing
05‐08‐19 23:05 687      All protection elements resetting
05‐08‐19 23:05 687      Protection element timing
05‐08‐19 23:05 684      All protection elements resetting
05‐08‐19 23:05 684      Protection element timing
05‐08‐19 23:05 682      All protection elements resetting
05‐08‐19 23:05 682      Protection element timing
05‐08‐19 23:05 679      All protection elements resetting
05‐08‐19 23:05 679      Protection element timing
05‐08‐19 23:05 676      All protection elements resetting
05‐08‐19 23:05 676      Protection element timing
05‐08‐19 23:05 674      All protection elements resetting
05‐08‐19 23:05 674      Protection element timing
05‐08‐19 23:05 671      All protection elements resetting
05‐08‐19 23:05 671      Protection element timing
05‐08‐19 23:05 669      All protection elements resetting
05‐08‐19 23:05 669      Protection element timing
05‐08‐19 23:05 666      All protection elements resetting
05‐08‐19 23:05 666      Protection element timing
05‐08‐19 23:05 664      All protection elements resetting
05‐08‐19 23:05 664      Protection element timing
05‐08‐19 23:05 662      All protection elements resetting
05‐08‐19 23:05 662      Protection element timing
05‐08‐19 23:05 659      All protection elements resetting
05‐08‐19 23:05 659      Protection element timing
05‐08‐19 23:05 657      All protection elements resetting
05‐08‐19 23:05 656      Protection element timing
05‐08‐19 23:05 654      All protection elements resetting
05‐08‐19 23:05 654      Protection element timing
05‐08‐19 23:05 651      All protection elements resetting
05‐08‐19 23:05 651      Protection element timing
05‐08‐19 23:05 649      All protection elements resetting
05‐08‐19 23:05 649      Protection element timing
05‐08‐19 23:05 646      All protection elements resetting
05‐08‐19 23:05 596      Pickup Phase C
05‐08‐19 23:05 596      Pickup Phase A
05‐08‐19 23:05 571      Pickup Phase B
05‐08‐19 23:05 571      Pickup
05‐08‐19 23:05 583      Inrush current timing has started
05‐08‐19 23:03 230      Auxiliary Supply Failure
05‐08‐19 23:03 896      Source Supply Off
05‐08‐19 23:03 855      Inrush current timer ready
05‐08‐19 19:27 37      Last Good Value Trapped is     3 A
05‐08‐19 18:18 393      Last Good Value Trapped is     3 A
05‐08‐19 17:37 316      Last Good Value Trapped is     3 A
05‐08‐19 16:43 216      Last Good Value Trapped is     3 A
05‐08‐19 10:04 846 OCP  Operator control panel door closed
05‐08‐19 10:01 928      Last Good Value Trapped is     0 A
05‐08‐19 9:54 907 OCP  Operator control panel door opened
05‐08‐19 6:45 967      Last Good Value Trapped is     2 A
05‐08‐19 2:24 814      Last Good Value Trapped is     2 A
05‐08‐19 0:05 475      Last Good Value Trapped is     2 A
04‐08‐19 23:29 388      Last Good Value Trapped is     2 A
04‐08‐19 21:09 556      Last Good Value Trapped is     2 A
04‐08‐19 19:41 355      Last Good Value Trapped is     2 A
04‐08‐19 18:57 256      Last Good Value Trapped is     2 A
04‐08‐19 16:32 448      Last Good Value Trapped is     2 A
04‐08‐19 15:53 866      Last Good Value Trapped is     2 A
04‐08‐19 15:21 802      Last Good Value Trapped is     2 A
04‐08‐19 13:51 628      Last Good Value Trapped is     2 A
04‐08‐19 11:54 404      Last Good Value Trapped is     3 A
04‐08‐19 10:35 741      Last Good Value Trapped is     3 A
04‐08‐19 5:42 545      Last Good Value Trapped is     2 A
04‐08‐19 1:48 963      Last Good Value Trapped is     2 A
04‐08‐19 1:00 348      Last Good Value Trapped is     2 A
04‐08‐19 0:38 794      Last Good Value Trapped is     2 A
03‐08‐19 21:15 812      Last Good Value Trapped is     2 A
03‐08‐19 17:03 262      Last Good Value Trapped is     3 A
03‐08‐19 16:08 654      Last Good Value Trapped is     3 A
03‐08‐19 15:25 69      Last Good Value Trapped is     3 A
03‐08‐19 7:30 557      Last Good Value Trapped is     2 A
03‐08‐19 5:23 241      Last Good Value Trapped is     2 A
03‐08‐19 4:23 90      Last Good Value Trapped is     2 A
03‐08‐19 0:30 516      Last Good Value Trapped is     2 A
02‐08‐19 23:58 704      Battery Test Off
02‐08‐19 23:58 704      Battery Test Capacity OK
02‐08‐19 23:58 695      Battery Test End Voltage 24.97 V
02‐08‐19 23:58 695      Battery Test Middle Voltage 24.14 V
02‐08‐19 23:58 695      Battery Test Beginning Voltage 25.53 V
02‐08‐19 23:58 584      Battery Test Performing Test...
02‐08‐19 23:58 580      Battery Test Start
02‐08‐19 22:22 208      Last Good Value Trapped is     2 A
02‐08‐19 21:49 129      Last Good Value Trapped is     2 A
02‐08‐19 19:18 787      Last Good Value Trapped is     3 A
01‐08‐19 18:13 686      Last Good Value Trapped is     3 A
01‐08‐19 12:26 649      Inrush current timer expired
01‐08‐19 12:26 788      Auxiliary Supply Normal
01‐08‐19 12:26 694      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 80 
01‐08‐19 12:26 792      A during fault
Current at maximum Phase B ‐ Maximum Current of 99 
01‐08‐19 12:26 792      A during fault
Current at maximum Phase A ‐ Maximum Current of 37 
01‐08‐19 12:26 792      A during fault
01‐08‐19 12:26 792      Protection Disk Reset
01‐08‐19 12:26 724      All protection elements resetting
01‐08‐19 12:26 724      Protection element timing
01‐08‐19 12:26 722      All protection elements resetting
01‐08‐19 12:26 722      Protection element timing
01‐08‐19 12:26 719      All protection elements resetting
01‐08‐19 12:26 667      Pickup Phase C
01‐08‐19 12:26 644      Pickup Phase B
01‐08‐19 12:26 644      Pickup
01‐08‐19 12:26 652      Inrush current timing has started
01‐08‐19 12:23 41      Auxiliary Supply Failure
01‐08‐19 12:23 699      Source Supply Off
01‐08‐19 12:23 327      Last Good Value Trapped is     3 A
01‐08‐19 12:23 622      Inrush current timer ready
01‐08‐19 10:31 651 OCP  Operator control panel door closed
01‐08‐19 10:27 513 OCP  Operator control panel door opened
01‐08‐19 10:21 412      Inrush current timer expired
01‐08‐19 10:21 578      Auxiliary Supply Normal
01‐08‐19 10:21 474      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 166 
01‐08‐19 10:21 610      A during fault
Current at maximum Phase B ‐ Maximum Current of 183 
01‐08‐19 10:21 610      A during fault
Current at maximum Phase A ‐ Maximum Current of 75 
01‐08‐19 10:21 610      A during fault
01‐08‐19 10:21 610      Protection Disk Reset
01‐08‐19 10:21 552      All protection elements resetting
01‐08‐19 10:21 519      Protection element timing
01‐08‐19 10:21 517      All protection elements resetting
01‐08‐19 10:21 517      Protection element timing
01‐08‐19 10:21 515      All protection elements resetting
01‐08‐19 10:21 515      Protection element timing
01‐08‐19 10:21 512      All protection elements resetting
01‐08‐19 10:21 512      Protection element timing
01‐08‐19 10:21 509      All protection elements resetting
01‐08‐19 10:21 509      Protection element timing
01‐08‐19 10:21 507      All protection elements resetting
01‐08‐19 10:21 507      Protection element timing
01‐08‐19 10:21 505      All protection elements resetting
01‐08‐19 10:21 505      Protection element timing
01‐08‐19 10:21 502      All protection elements resetting
01‐08‐19 10:21 502      Protection element timing
01‐08‐19 10:21 499      All protection elements resetting
01‐08‐19 10:21 499      Protection element timing
01‐08‐19 10:21 497      All protection elements resetting
01‐08‐19 10:21 497      Protection element timing
01‐08‐19 10:21 494      All protection elements resetting
01‐08‐19 10:21 494      Protection element timing
01‐08‐19 10:21 492      All protection elements resetting
01‐08‐19 10:21 492      Protection element timing
01‐08‐19 10:21 490      All protection elements resetting
01‐08‐19 10:21 490      Protection element timing
01‐08‐19 10:21 487      All protection elements resetting
01‐08‐19 10:21 487      Protection element timing
01‐08‐19 10:21 484      All protection elements resetting
01‐08‐19 10:21 484      Protection element timing
01‐08‐19 10:21 482      All protection elements resetting
01‐08‐19 10:21 482      Protection element timing
01‐08‐19 10:21 479      All protection elements resetting
01‐08‐19 10:21 479      Protection element timing
01‐08‐19 10:21 477      All protection elements resetting
01‐08‐19 10:21 477      Protection element timing
01‐08‐19 10:21 474      All protection elements resetting
01‐08‐19 10:21 474      Protection element timing
01‐08‐19 10:21 472      All protection elements resetting
01‐08‐19 10:21 472      Protection element timing
01‐08‐19 10:21 469      All protection elements resetting
01‐08‐19 10:21 462      Measuring Frequency On Bushing Ai
01‐08‐19 10:21 430      Pickup Phase A
01‐08‐19 10:21 424      Pickup Phase C
01‐08‐19 10:21 402      Pickup Phase B
01‐08‐19 10:21 402      Pickup
01‐08‐19 10:21 414      Inrush current timing has started
01‐08‐19 9:13 661      Auxiliary Supply Failure
01‐08‐19 9:13 382      Source Supply Off
01‐08‐19 9:13 334      Measuring Frequency On Bushing Ci
01‐08‐19 9:13 312      Inrush current timer ready
01‐08‐19 9:13 395      Last Good Value Trapped is     3 A
01‐08‐19 9:13 117      Inrush current timing has started
01‐08‐19 9:13 404      Inrush current timer ready
01‐08‐19 9:00 861 OCP  Operator control panel door closed
01‐08‐19 8:54 285 OCP  Operator control panel door opened
01‐08‐19 5:53 894      Last Good Value Trapped is     2 A
01‐08‐19 5:11 785      Last Good Value Trapped is     2 A
01‐08‐19 4:34 190      Last Good Value Trapped is     2 A
01‐08‐19 3:50 78      Last Good Value Trapped is     2 A
01‐08‐19 2:35 887      Last Good Value Trapped is     2 A
01‐08‐19 1:45 761      Last Good Value Trapped is     2 A
31‐07‐19 22:12 746      Last Good Value Trapped is     3 A
31‐07‐19 21:03 91      Last Good Value Trapped is     2 A
31‐07‐19 15:58 811 OCP  Operator control panel door closed
31‐07‐19 15:51 411      Battery Test Off
31‐07‐19 15:51 410      Battery Test Capacity OK
31‐07‐19 15:51 410      Battery Test End Voltage 25.23 V
31‐07‐19 15:51 410      Battery Test Middle Voltage 24.24 V
31‐07‐19 15:51 410      Battery Test Beginning Voltage 25.59 V
31‐07‐19 15:51 296      Battery Test Performing Test...
31‐07‐19 15:51 287 WSOS Battery Test Start
31‐07‐19 15:50 0 WSOS 31‐07‐19 15:50
31‐07‐19 15:40 51 OCP  Operator control panel door opened
31‐07‐19 9:00 426      Last Good Value Trapped is     3 A
31‐07‐19 6:01 487      Last Good Value Trapped is     2 A
31‐07‐19 5:32 913      Last Good Value Trapped is     2 A
31‐07‐19 5:00 333      Last Good Value Trapped is     2 A
31‐07‐19 3:47 650      Last Good Value Trapped is     2 A
31‐07‐19 3:04 44      Last Good Value Trapped is     2 A
31‐07‐19 0:58 739      Last Good Value Trapped is     2 A
30‐07‐19 22:46 427      Last Good Value Trapped is     2 A
30‐07‐19 21:13 219      Last Good Value Trapped is     3 A
30‐07‐19 19:24 984      Last Good Value Trapped is     3 A
30‐07‐19 6:40 1      Last Good Value Trapped is     2 A
30‐07‐19 5:06 765      Last Good Value Trapped is     2 A
30‐07‐19 4:16 642      Last Good Value Trapped is     2 A
30‐07‐19 1:30 234      Last Good Value Trapped is     2 A
30‐07‐19 0:08 537      Last Good Value Trapped is     3 A
29‐07‐19 19:12 345      Last Good Value Trapped is     3 A
29‐07‐19 6:45 387      Last Good Value Trapped is     2 A
28‐07‐19 20:03 397      Last Good Value Trapped is     3 A
28‐07‐19 19:00 272      Last Good Value Trapped is     3 A
28‐07‐19 17:05 573      Last Good Value Trapped is     3 A
27‐07‐19 20:24 438      Last Good Value Trapped is     3 A
27‐07‐19 19:43 354      Last Good Value Trapped is     2 A
27‐07‐19 17:22 429 OCP  Operator control panel door closed
27‐07‐19 17:19 492      Inrush current timer expired
Current at maximum Phase C ‐ Maximum Current of 65 
27‐07‐19 17:19 657      A during fault
Current at maximum Phase B ‐ Maximum Current of 126 
27‐07‐19 17:19 657      A during fault
Current at maximum Phase A ‐ Maximum Current of 82 
27‐07‐19 17:19 657      A during fault
27‐07‐19 17:19 657      Protection Disk Reset
27‐07‐19 17:19 592      All protection elements resetting
27‐07‐19 17:19 592      Protection element timing
27‐07‐19 17:19 589      All protection elements resetting
27‐07‐19 17:19 589      Protection element timing
27‐07‐19 17:19 587      All protection elements resetting
27‐07‐19 17:19 587      Protection element timing
27‐07‐19 17:19 584      All protection elements resetting
27‐07‐19 17:19 584      Protection element timing
27‐07‐19 17:19 582      All protection elements resetting
27‐07‐19 17:19 582      Protection element timing
27‐07‐19 17:19 579      All protection elements resetting
27‐07‐19 17:19 579      Protection element timing
27‐07‐19 17:19 577      All protection elements resetting
27‐07‐19 17:19 577      Protection element timing
27‐07‐19 17:19 574      All protection elements resetting
27‐07‐19 17:19 574      Protection element timing
27‐07‐19 17:19 572      All protection elements resetting
27‐07‐19 17:19 572      Protection element timing
27‐07‐19 17:19 569      All protection elements resetting
27‐07‐19 17:19 569      Protection element timing
27‐07‐19 17:19 567      All protection elements resetting
27‐07‐19 17:19 567      Protection element timing
27‐07‐19 17:19 564      All protection elements resetting
27‐07‐19 17:19 564      Protection element timing
27‐07‐19 17:19 562      All protection elements resetting
27‐07‐19 17:19 562      Protection element timing
27‐07‐19 17:19 560      All protection elements resetting
27‐07‐19 17:19 560      Protection element timing
27‐07‐19 17:19 557      All protection elements resetting
27‐07‐19 17:19 557      Protection element timing
27‐07‐19 17:19 555      All protection elements resetting
27‐07‐19 17:19 555      Protection element timing
27‐07‐19 17:19 552      All protection elements resetting
27‐07‐19 17:19 552      Protection element timing
27‐07‐19 17:19 550      All protection elements resetting
27‐07‐19 17:19 549      Protection element timing
27‐07‐19 17:19 547      All protection elements resetting
27‐07‐19 17:19 547      Protection element timing
27‐07‐19 17:19 544      All protection elements resetting
27‐07‐19 17:19 544      Protection element timing
27‐07‐19 17:19 542      All protection elements resetting
27‐07‐19 17:19 542      Protection element timing
27‐07‐19 17:19 540      All protection elements resetting
27‐07‐19 17:19 539      Protection element timing
27‐07‐19 17:19 537      All protection elements resetting
27‐07‐19 17:19 537      Protection element timing
27‐07‐19 17:19 534      All protection elements resetting
27‐07‐19 17:19 514      Pickup Phase C
27‐07‐19 17:19 509      Pickup Phase A
27‐07‐19 17:19 484      Pickup Phase B
27‐07‐19 17:19 484      Pickup
27‐07‐19 17:19 494      Inrush current timing has started
27‐07‐19 17:09 151 OCP  Panel Close Request
27‐07‐19 17:08 655      Close Coil Connect
27‐07‐19 17:08 639      Trip Coil Connected
27‐07‐19 16:50 886 OCP  Operator control panel door opened
27‐07‐19 16:49 71      Close Coil Disconnected
27‐07‐19 16:49 71      Trip Coil Disconnected
27‐07‐19 16:49 379      Switchgear Serial Number 700612
27‐07‐19 16:49 378      U Series Switch
27‐07‐19 16:49 778      Static IP 10.1.1.2 is active
27‐07‐19 16:49 72      Source Supply On
27‐07‐19 16:49 615      Cubicle Serial Number 851445
Protection and Communications Module Serial Number 
27‐07‐19 16:49 614      4596
27‐07‐19 16:49 614      U‐Boot Version 2013.01.01r25766
27‐07‐19 16:49 614      DSP00‐08.03r29405
27‐07‐19 16:49 614      Application Version A50‐05.04r29672
27‐07‐19 16:49 325      Switch Disconnected
27‐07‐19 16:49 318      Protection Group A Active
27‐07‐19 16:49 920      Maintenance Required
27‐07‐19 16:49 622      SCEM Type SCEM11
27‐07‐19 16:49 622      Battery Normal
27‐07‐19 16:49 620      SCEM Type Unknown
27‐07‐19 16:49 618      Auxiliary Supply Normal
27‐07‐19 16:49 617      Battery Low
27‐07‐19 16:49 617      Switch Open
27‐07‐19 16:49 615      Battery Normal
27‐07‐19 16:49 615      Radio Supply Off
27‐07‐19 16:49 613      Normal Power Mode
27‐07‐19 16:49 610      Power Up
27‐07‐19 15:08 89      Power Down
27‐07‐19 8:55 444      Maintenance Required
27‐07‐19 8:55 444      Battery Low
27‐07‐19 7:32 50      Source Supply Off
27‐07‐19 7:31 352      Auxiliary Supply Failure
27‐07‐19 7:21 106 OCP  Operator control panel door closed
27‐07‐19 7:21 913      Close Coil Disconnected
27‐07‐19 7:21 913      Trip Coil Disconnected
27‐07‐19 7:20 581      Inrush current timer ready
27‐07‐19 7:20 561      Lockout
27‐07‐19 7:20 532 OCP  Panel Trip Request
27‐07‐19 7:20 104 OCP  Operator control panel door opened
27‐07‐19 5:04 680      Last Good Value Trapped is     2 A
27‐07‐19 3:48 988      Last Good Value Trapped is     2 A
27‐07‐19 3:29 941      Last Good Value Trapped is     2 A
27‐07‐19 2:33 802      Last Good Value Trapped is     2 A
27‐07‐19 1:03 582      Last Good Value Trapped is     2 A
26‐07‐19 23:54 414      Last Good Value Trapped is     2 A
26‐07‐19 17:01 515      Last Good Value Trapped is     3 A
26‐07‐19 8:31 579      Last Good Value Trapped is     3 A
26‐07‐19 6:17 247      Last Good Value Trapped is     2 A
26‐07‐19 1:20 985      Last Good Value Trapped is     2 A
25‐07‐19 23:26 196      Last Good Value Trapped is     2 A
25‐07‐19 22:33 61      Last Good Value Trapped is     2 A
25‐07‐19 22:07 495      Last Good Value Trapped is     2 A
25‐07‐19 20:44 787      Last Good Value Trapped is     2 A
25‐07‐19 18:15 422      Last Good Value Trapped is     3 A
25‐07‐19 16:32 675      Last Good Value Trapped is     3 A
25‐07‐19 16:06 114      Last Good Value Trapped is     3 A
25‐07‐19 13:36 789      Last Good Value Trapped is     3 A
25‐07‐19 11:50 602      Last Good Value Trapped is     3 A
25‐07‐19 8:34 713      Last Good Value Trapped is     3 A
25‐07‐19 5:05 187      Last Good Value Trapped is     2 A
25‐07‐19 0:00 896      Battery Test Off
25‐07‐19 0:00 896      Battery Test Capacity OK
25‐07‐19 0:00 888      Battery Test End Voltage 25.27 V
25‐07‐19 0:00 888      Battery Test Middle Voltage 24.24 V
25‐07‐19 0:00 888      Battery Test Beginning Voltage 26.0 V
25‐07‐19 0:00 774      Battery Test Performing Test...
25‐07‐19 0:00 772      Battery Test Start
24‐07‐19 19:08 186      Last Good Value Trapped is     2 A
24‐07‐19 17:37 980      Last Good Value Trapped is     2 A
24‐07‐19 16:42 860      Last Good Value Trapped is     3 A
24‐07‐19 6:46 638      Last Good Value Trapped is     2 A
24‐07‐19 6:07 42      Last Good Value Trapped is     2 A
24‐07‐19 0:02 149      Last Good Value Trapped is     2 A
23‐07‐19 23:13 34      Last Good Value Trapped is     2 A
23‐07‐19 22:16 905      Last Good Value Trapped is     2 A
23‐07‐19 21:59 367      Last Good Value Trapped is     2 A
23‐07‐19 21:09 254      Last Good Value Trapped is     2 A
23‐07‐19 20:32 172      Last Good Value Trapped is     2 A
23‐07‐19 19:59 104      Last Good Value Trapped is     2 A
23‐07‐19 19:13 511      Last Good Value Trapped is     3 A
23‐07‐19 18:25 919      Last Good Value Trapped is     3 A
23‐07‐19 17:27 313      Last Good Value Trapped is     3 A
23‐07‐19 14:14 60 OCP  Operator control panel door closed
23‐07‐19 14:09 503 OCP  Operator control panel door opened
23‐07‐19 8:45 374      Last Good Value Trapped is     3 A
23‐07‐19 6:45 87      Last Good Value Trapped is     2 A
23‐07‐19 5:15 363      Last Good Value Trapped is     2 A
23‐07‐19 0:31 660      Last Good Value Trapped is     2 A
23‐07‐19 0:06 599      Last Good Value Trapped is     2 A
22‐07‐19 23:16 475      Last Good Value Trapped is     2 A
22‐07‐19 19:03 388      Last Good Value Trapped is     3 A
22‐07‐19 18:31 319      Last Good Value Trapped is     3 A
22‐07‐19 17:50 238      Last Good Value Trapped is     3 A
22‐07‐19 6:52 914      Last Good Value Trapped is     2 A
22‐07‐19 5:45 744      Last Good Value Trapped is     2 A
22‐07‐19 5:23 189      Last Good Value Trapped is     2 A
21‐07‐19 21:45 78      Last Good Value Trapped is     2 A
21‐07‐19 20:30 406      Last Good Value Trapped is     2 A
21‐07‐19 19:48 815      Last Good Value Trapped is     2 A
21‐07‐19 17:16 524      Last Good Value Trapped is     2 A
21‐07‐19 15:21 320      Last Good Value Trapped is     2 A
21‐07‐19 13:31 624      Last Good Value Trapped is     2 A
21‐07‐19 13:04 576      Last Good Value Trapped is     2 A
21‐07‐19 12:35 24      Last Good Value Trapped is     2 A
21‐07‐19 11:40 425      Last Good Value Trapped is     2 A
21‐07‐19 10:34 804      Last Good Value Trapped is     2 A
21‐07‐19 8:27 538      Last Good Value Trapped is     2 A
21‐07‐19 7:31 407      Last Good Value Trapped is     2 A
21‐07‐19 6:28 253      Last Good Value Trapped is     2 A
20‐07‐19 4:17 227      Last Good Value Trapped is     2 A
20‐07‐19 3:15 69      Last Good Value Trapped is     2 A
20‐07‐19 2:46 495      Last Good Value Trapped is     2 A
20‐07‐19 2:04 889      Last Good Value Trapped is     2 A
20‐07‐19 1:16 267      Last Good Value Trapped is     2 A
19‐07‐19 22:16 25      Inrush current timer expired
19‐07‐19 22:16 193      Auxiliary Supply Normal
19‐07‐19 22:16 92      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 45 
19‐07‐19 22:16 165      A during fault
Current at maximum Phase B ‐ Maximum Current of 97 
19‐07‐19 22:16 165      A during fault
Current at maximum Phase A ‐ Maximum Current of 68 
19‐07‐19 22:16 165      A during fault
19‐07‐19 22:16 165      Protection Disk Reset
19‐07‐19 22:16 100      All protection elements resetting
19‐07‐19 22:16 100      Protection element timing
19‐07‐19 22:16 98      All protection elements resetting
19‐07‐19 22:16 98      Protection element timing
19‐07‐19 22:16 95      All protection elements resetting
19‐07‐19 22:16 95      Protection element timing
19‐07‐19 22:16 93      All protection elements resetting
19‐07‐19 22:16 93      Protection element timing
19‐07‐19 22:16 90      All protection elements resetting
19‐07‐19 22:16 90      Protection element timing
19‐07‐19 22:16 88      All protection elements resetting
19‐07‐19 22:16 88      Protection element timing
19‐07‐19 22:16 85      All protection elements resetting
19‐07‐19 22:16 85      Protection element timing
19‐07‐19 22:16 83      All protection elements resetting
19‐07‐19 22:16 82      Protection element timing
19‐07‐19 22:16 80      All protection elements resetting
19‐07‐19 22:16 80      Protection element timing
19‐07‐19 22:16 77      All protection elements resetting
19‐07‐19 22:16 77      Protection element timing
19‐07‐19 22:16 75      All protection elements resetting
19‐07‐19 22:16 75      Protection element timing
19‐07‐19 22:16 73      All protection elements resetting
19‐07‐19 22:16 43      Pickup Phase A
19‐07‐19 22:16 40      Measuring Frequency On Bushing Bi
19‐07‐19 22:16 18      Pickup Phase B
19‐07‐19 22:16 18      Pickup
19‐07‐19 22:16 27      Inrush current timing has started
19‐07‐19 22:04 605      Auxiliary Supply Failure
19‐07‐19 22:04 87      Source Supply Off
19‐07‐19 22:04 293      Last Good Value Trapped is     3 A
19‐07‐19 22:04 35      Inrush current timer ready
19‐07‐19 5:48 918      Last Good Value Trapped is     2 A
18‐07‐19 6:49 125      Last Good Value Trapped is     2 A
18‐07‐19 6:19 51      Last Good Value Trapped is     2 A
18‐07‐19 0:00 892      Battery Test Off
18‐07‐19 0:00 892      Battery Test Capacity OK
18‐07‐19 0:00 891      Battery Test End Voltage 25.19 V
18‐07‐19 0:00 891      Battery Test Middle Voltage 24.32 V
18‐07‐19 0:00 891      Battery Test Beginning Voltage 25.96 V
18‐07‐19 0:00 772      Battery Test Performing Test...
18‐07‐19 0:00 768      Battery Test Start
17‐07‐19 6:12 509      Last Good Value Trapped is     2 A
16‐07‐19 7:15 749      Last Good Value Trapped is     2 A
16‐07‐19 6:45 174      Last Good Value Trapped is     2 A
16‐07‐19 5:52 38      Last Good Value Trapped is     2 A
15‐07‐19 16:55 97 OCP  Operator control panel door closed
15‐07‐19 16:55 815 OCP  Operator control panel door opened
15‐07‐19 9:00 591 OCP  Operator control panel door closed
15‐07‐19 8:58 234 OCP  Operator control panel door opened
15‐07‐19 7:41 803      Last Good Value Trapped is     2 A
15‐07‐19 7:11 232      Last Good Value Trapped is     2 A
15‐07‐19 5:26 968      Last Good Value Trapped is     2 A
15‐07‐19 4:51 882      Last Good Value Trapped is     2 A
15‐07‐19 2:45 68      Last Good Value Trapped is     2 A
15‐07‐19 1:38 903      Last Good Value Trapped is     2 A
15‐07‐19 0:59 809      Last Good Value Trapped is     2 A
14‐07‐19 18:40 472      Last Good Value Trapped is     2 A
14‐07‐19 15:11 610      Last Good Value Trapped is     2 A
14‐07‐19 9:42 23      Last Good Value Trapped is     2 A
14‐07‐19 8:52 919      Last Good Value Trapped is     2 A
14‐07‐19 8:09 824      Last Good Value Trapped is     2 A
14‐07‐19 5:35 949      Last Good Value Trapped is     2 A
14‐07‐19 2:49 37      Last Good Value Trapped is     2 A
14‐07‐19 1:24 831      Last Good Value Trapped is     2 A
13‐07‐19 15:11 632      Last Good Value Trapped is     2 A
13‐07‐19 9:24 517      Last Good Value Trapped is     2 A
13‐07‐19 8:19 882      Last Good Value Trapped is     2 A
13‐07‐19 7:02 704      Last Good Value Trapped is     2 A
13‐07‐19 5:16 436      Last Good Value Trapped is     2 A
13‐07‐19 4:50 871      Last Good Value Trapped is     2 A
13‐07‐19 4:29 817      Last Good Value Trapped is     2 A
13‐07‐19 3:57 738      Last Good Value Trapped is     2 A
13‐07‐19 3:24 653      Last Good Value Trapped is     2 A
13‐07‐19 1:36 385      Last Good Value Trapped is     2 A
13‐07‐19 0:46 763      Last Good Value Trapped is     2 A
12‐07‐19 23:49 626      Last Good Value Trapped is     2 A
12‐07‐19 23:28 576      Last Good Value Trapped is     2 A
12‐07‐19 7:46 307      Last Good Value Trapped is     3 A
12‐07‐19 7:12 725      Last Good Value Trapped is     2 A
12‐07‐19 5:45 2      Last Good Value Trapped is     2 A
12‐07‐19 5:17 431      Last Good Value Trapped is     2 A
12‐07‐19 4:55 874      Last Good Value Trapped is     2 A
12‐07‐19 2:44 36      Last Good Value Trapped is     2 A
12‐07‐19 0:32 207      Last Good Value Trapped is     2 A
11‐07‐19 23:27 550      Last Good Value Trapped is     2 A
11‐07‐19 22:43 947      Last Good Value Trapped is     2 A
11‐07‐19 22:07 364      Last Good Value Trapped is     2 A
11‐07‐19 21:30 280      Last Good Value Trapped is     2 A
11‐07‐19 19:10 988      Last Good Value Trapped is     2 A
11‐07‐19 8:02 783      Last Good Value Trapped is     3 A
11‐07‐19 5:53 961      Last Good Value Trapped is     2 A
11‐07‐19 4:25 238      Last Good Value Trapped is     2 A
11‐07‐19 2:57 516      Last Good Value Trapped is     2 A
11‐07‐19 1:32 305      Last Good Value Trapped is     2 A
11‐07‐19 0:00 896      Battery Test Off
11‐07‐19 0:00 896      Battery Test Capacity OK
11‐07‐19 0:00 888      Battery Test End Voltage 25.22 V
11‐07‐19 0:00 888      Battery Test Middle Voltage 24.34 V
11‐07‐19 0:00 888      Battery Test Beginning Voltage 25.93 V
11‐07‐19 0:00 768      Battery Test Performing Test...
11‐07‐19 0:00 766      Battery Test Start
10‐07‐19 23:51 563      Last Good Value Trapped is     2 A
10‐07‐19 21:48 774      Last Good Value Trapped is     2 A
10‐07‐19 20:21 576      Last Good Value Trapped is     2 A
10‐07‐19 3:43 476      Last Good Value Trapped is     2 A
10‐07‐19 2:05 728      Last Good Value Trapped is     2 A
10‐07‐19 1:03 71      Last Good Value Trapped is     2 A
09‐07‐19 22:18 162      Last Good Value Trapped is     2 A
09‐07‐19 20:06 346      Last Good Value Trapped is     2 A
09‐07‐19 5:45 620      Last Good Value Trapped is     2 A
09‐07‐19 5:03 510      Last Good Value Trapped is     2 A
09‐07‐19 4:18 395      Last Good Value Trapped is     2 A
09‐07‐19 3:58 844      Last Good Value Trapped is     2 A
09‐07‐19 2:53 680      Last Good Value Trapped is     2 A
08‐07‐19 20:30 249      Last Good Value Trapped is     2 A
08‐07‐19 19:48 152      Last Good Value Trapped is     2 A
08‐07‐19 19:13 572      Last Good Value Trapped is     3 A
08‐07‐19 18:20 953      Last Good Value Trapped is     3 A
08‐07‐19 17:17 316      Last Good Value Trapped is     3 A
08‐07‐19 4:15 231      Last Good Value Trapped is     2 A
08‐07‐19 1:00 250      Last Good Value Trapped is     2 A
07‐07‐19 23:16 1      Last Good Value Trapped is     2 A
07‐07‐19 17:50 269      Last Good Value Trapped is     2 A
07‐07‐19 16:34 619      Last Good Value Trapped is     2 A
07‐07‐19 15:32 505      Last Good Value Trapped is     2 A
07‐07‐19 14:49 929      Last Good Value Trapped is     2 A
07‐07‐19 14:11 363      Last Good Value Trapped is     2 A
07‐07‐19 12:21 666      Last Good Value Trapped is     2 A
07‐07‐19 11:04 286 OCP  Operator control panel door closed
07‐07‐19 10:52 274 OCP  Operator control panel door opened
07‐07‐19 0:07 587      Inrush current timer expired
Current at maximum Phase C ‐ Maximum Current of 41 
07‐07‐19 0:07 717      A during fault
Current at maximum Phase B ‐ Maximum Current of 62 
07‐07‐19 0:07 717      A during fault
Current at maximum Phase A ‐ Maximum Current of 87 
07‐07‐19 0:07 717      A during fault
07‐07‐19 0:07 717      Protection Disk Reset
07‐07‐19 0:07 653      All protection elements resetting
07‐07‐19 0:07 653      Protection element timing
07‐07‐19 0:07 650      All protection elements resetting
07‐07‐19 0:07 650      Protection element timing
07‐07‐19 0:07 648      All protection elements resetting
07‐07‐19 0:07 648      Protection element timing
07‐07‐19 0:07 645      All protection elements resetting
07‐07‐19 0:07 645      Protection element timing
07‐07‐19 0:07 643      All protection elements resetting
07‐07‐19 0:07 643      Protection element timing
07‐07‐19 0:07 640      All protection elements resetting
07‐07‐19 0:07 640      Protection element timing
07‐07‐19 0:07 638      All protection elements resetting
07‐07‐19 0:07 638      Protection element timing
07‐07‐19 0:07 635      All protection elements resetting
07‐07‐19 0:07 635      Protection element timing
07‐07‐19 0:07 632      All protection elements resetting
07‐07‐19 0:07 632      Protection element timing
07‐07‐19 0:07 630      All protection elements resetting
07‐07‐19 0:07 630      Protection element timing
07‐07‐19 0:07 627      All protection elements resetting
07‐07‐19 0:07 610      Pickup Phase B
07‐07‐19 0:07 582      Pickup Phase A
07‐07‐19 0:07 582      Pickup
07‐07‐19 0:07 589      Inrush current timing has started
06‐07‐19 23:43 247 OCP  Operator control panel door closed
06‐07‐19 23:42 57 OCP  Operator control panel door opened
06‐07‐19 23:38 411      Auxiliary Supply Normal
06‐07‐19 23:38 295      Source Supply On
06‐07‐19 23:22 904 OCP  Operator control panel door closed
06‐07‐19 23:22 887 OCP  Operator control panel door opened
06‐07‐19 22:04 513      Auxiliary Supply Failure
06‐07‐19 22:04 128      Source Supply Off
06‐07‐19 16:21 817      Last Good Value Trapped is     3 A
06‐07‐19 8:33 918      Last Good Value Trapped is     3 A
05‐07‐19 12:01 376      Last Good Value Trapped is     3 A
04‐07‐19 16:30 951      Last Good Value Trapped is     3 A
04‐07‐19 12:37 477      Last Good Value Trapped is     3 A
04‐07‐19 11:41 358      Last Good Value Trapped is     3 A
04‐07‐19 10:41 726      Last Good Value Trapped is     2 A
04‐07‐19 9:35 571      Last Good Value Trapped is     3 A
04‐07‐19 0:00 886      Battery Test Off
04‐07‐19 0:00 886      Battery Test Capacity OK
04‐07‐19 0:00 879      Battery Test End Voltage 25.24 V
04‐07‐19 0:00 879      Battery Test Middle Voltage 24.34 V
04‐07‐19 0:00 879      Battery Test Beginning Voltage 25.99 V
04‐07‐19 0:00 766      Battery Test Performing Test...
04‐07‐19 0:00 763      Battery Test Start
03‐07‐19 16:41 401      Last Good Value Trapped is     3 A
03‐07‐19 15:00 160      Last Good Value Trapped is     3 A
03‐07‐19 12:05 260      Last Good Value Trapped is     2 A
02‐07‐19 17:33 370      Last Good Value Trapped is     3 A
02‐07‐19 17:10 321      Last Good Value Trapped is     3 A
02‐07‐19 9:48 691 OCP  Operator control panel door closed
02‐07‐19 9:36 447 OCP  Operator control panel door opened
01‐07‐19 17:02 469      Last Good Value Trapped is     3 A
01‐07‐19 16:53 876 OCP  Operator control panel door closed
01‐07‐19 16:31 654 OCP  Operator control panel door opened
01‐07‐19 8:46 432 OCP  Operator control panel door closed
01‐07‐19 8:44 987 OCP  Operator control panel door opened
29‐06‐19 17:01 76      Last Good Value Trapped is     3 A
28‐06‐19 17:00 757      Last Good Value Trapped is     3 A
28‐06‐19 16:17 156      Last Good Value Trapped is     3 A
27‐06‐19 23:51 882      Battery Test Off
27‐06‐19 23:51 882      Battery Test Capacity OK
27‐06‐19 23:51 880      Battery Test End Voltage 25.24 V
27‐06‐19 23:51 880      Battery Test Middle Voltage 24.34 V
27‐06‐19 23:51 880      Battery Test Beginning Voltage 25.82 V
27‐06‐19 23:51 764      Battery Test Performing Test...
27‐06‐19 23:51 760      Battery Test Start
27‐06‐19 19:10 177      Last Good Value Trapped is     3 A
27‐06‐19 18:34 603      Last Good Value Trapped is     2 A
27‐06‐19 17:42 498      Last Good Value Trapped is     3 A
27‐06‐19 17:07 430      Last Good Value Trapped is     3 A
26‐06‐19 17:13 808      Last Good Value Trapped is     4 A
25‐06‐19 20:25 190      Last Good Value Trapped is     3 A
24‐06‐19 18:41 378      Last Good Value Trapped is     3 A
23‐06‐19 15:05 57 OCP  Operator control panel door closed
23‐06‐19 14:54 0 WSOS 23‐06‐19 14:54
23‐06‐19 15:02 908 WSOS Protection Group (A) Maximum Time Off

23‐06‐19 15:02 461 WSOS Protection Group (A) Sequence Reset Time 10 seconds


23‐06‐19 15:00 90 WSOS Protection Group (A) Loss Of Phase Protection On
23‐06‐19 15:00 619 WSOS Protection Group (A) Inrush Restraint On
Protection Group (A) Inrush Restraint Multiplier 10.0 
23‐06‐19 15:00 505 WSOS times
Protection Group (A) Inrush Restraint Time 10.00 
23‐06‐19 15:00 513 WSOS seconds
23‐06‐19 15:00 361 WSOS Protection Group (A) Phase Setting Current 60 A
23‐06‐19 14:44 191 OCP  Operator control panel door opened
22‐06‐19 17:14 460      Last Good Value Trapped is     4 A
21‐06‐19 19:27 845      Last Good Value Trapped is     4 A
21‐06‐19 6:33 459      Last Good Value Trapped is     3 A
21‐06‐19 2:32 370      Last Good Value Trapped is     3 A
21‐06‐19 0:00 16      Battery Test Off
21‐06‐19 0:00 16      Battery Test Capacity OK
21‐06‐19 0:00 16      Battery Test End Voltage 25.5 V
21‐06‐19 0:00 16      Battery Test Middle Voltage 24.29 V
21‐06‐19 0:00 16      Battery Test Beginning Voltage 25.74 V
21‐06‐19 0:00 891      Battery Test Performing Test...
21‐06‐19 0:00 889      Battery Test Start
20‐06‐19 23:24 932      Last Good Value Trapped is     3 A
20‐06‐19 21:46 716      Last Good Value Trapped is     3 A
20‐06‐19 21:18 658      Last Good Value Trapped is     3 A
20‐06‐19 20:53 605      Last Good Value Trapped is     3 A
20‐06‐19 20:22 542      Last Good Value Trapped is     3 A
20‐06‐19 10:05 985 OCP  Operator control panel door closed
20‐06‐19 10:03 387      Trip Coil Connected
20‐06‐19 10:03 371      Close Coil Connect
20‐06‐19 10:03 611      Close Coil Disconnected
20‐06‐19 10:03 595      Trip Coil Disconnected
20‐06‐19 9:36 106 OCP  Operator control panel door opened
19‐06‐19 17:10 679      Last Good Value Trapped is     3 A
19‐06‐19 9:43 901      Last Good Value Trapped is     3 A
18‐06‐19 18:22 249      Last Good Value Trapped is     3 A
18‐06‐19 17:16 103      Last Good Value Trapped is     3 A
18‐06‐19 12:14 437 OCP  Operator control panel door closed
18‐06‐19 12:12 733 OCP  Operator control panel door opened
Current at maximum Phase C ‐ Maximum Current of 78 
16‐06‐19 17:01 363      A during fault
Current at maximum Phase B ‐ Maximum Current of 64 
16‐06‐19 17:01 363      A during fault
Current at maximum Phase A ‐ Maximum Current of 121 
16‐06‐19 17:01 363      A during fault
16‐06‐19 17:01 363      Protection Disk Reset
16‐06‐19 17:01 313      All protection elements resetting
16‐06‐19 17:01 108      Pickup Phase B
16‐06‐19 17:01 84      Pickup Phase C
16‐06‐19 17:01 84      Protection Group A Active
16‐06‐19 17:01 84      Pickup Phase A
16‐06‐19 17:01 84      Pickup
16‐06‐19 16:37 408 OCP  Operator control panel door closed
16‐06‐19 16:30 968 OCP  Panel Close Request
16‐06‐19 16:30 294      Trip Coil Connected
16‐06‐19 16:30 262      Close Coil Connect
16‐06‐19 16:29 73 OCP  Operator control panel door opened
16‐06‐19 11:52 758      Auxiliary Supply Normal
16‐06‐19 11:51 848      Battery Normal
16‐06‐19 11:51 124      Auxiliary Supply Failure
16‐06‐19 11:51 719      Auxiliary Supply Normal
16‐06‐19 11:51 967      Source Supply On
16‐06‐19 10:10 562      Maintenance Required
16‐06‐19 10:10 561      Battery Low
16‐06‐19 8:45 284 OCP  Operator control panel door closed
16‐06‐19 8:38 830      Trip Coil Disconnected
16‐06‐19 8:38 814      Close Coil Disconnected
16‐06‐19 8:00 540      Auxiliary Supply Failure
16‐06‐19 8:00 292      Source Supply Off
16‐06‐19 7:54 933      Lockout
16‐06‐19 7:54 904 OCP  Panel Trip Request
16‐06‐19 7:54 998 OCP  Operator control panel door opened
15‐06‐19 17:16 973      Last Good Value Trapped is     3 A
14‐06‐19 20:02 316      Last Good Value Trapped is     3 A
14‐06‐19 19:23 233      Last Good Value Trapped is     4 A
14‐06‐19 0:00 14      Battery Test Off
14‐06‐19 0:00 14      Battery Test Capacity OK
14‐06‐19 0:00 13      Battery Test End Voltage 25.22 V
14‐06‐19 0:00 13      Battery Test Middle Voltage 24.38 V
14‐06‐19 0:00 13      Battery Test Beginning Voltage 25.93 V
14‐06‐19 0:00 889      Battery Test Performing Test...
14‐06‐19 0:00 886      Battery Test Start
13‐06‐19 18:56 698      Last Good Value Trapped is     3 A
13‐06‐19 18:17 620      Last Good Value Trapped is     3 A
12‐06‐19 17:20 458      Last Good Value Trapped is     3 A
12‐06‐19 8:48 508      Last Good Value Trapped is     3 A
11‐06‐19 17:33 235      Last Good Value Trapped is     3 A
11‐06‐19 16:31 590      Last Good Value Trapped is     3 A
11‐06‐19 8:31 173      Last Good Value Trapped is     3 A
10‐06‐19 19:03 744      Last Good Value Trapped is     3 A
10‐06‐19 18:04 604      Last Good Value Trapped is     3 A
10‐06‐19 17:20 499      Last Good Value Trapped is     3 A
10‐06‐19 15:34 254      Last Good Value Trapped is     3 A
10‐06‐19 15:07 190      Last Good Value Trapped is     3 A
10‐06‐19 14:42 136      Last Good Value Trapped is     3 A
10‐06‐19 10:26 614 OCP  Operator control panel door closed
10‐06‐19 10:23 765      Close Coil Connect
10‐06‐19 10:23 765      Trip Coil Connected
10‐06‐19 10:15 636      Close Coil Disconnected
10‐06‐19 10:15 588      Trip Coil Disconnected
10‐06‐19 10:15 290 OCP  Operator control panel door opened
10‐06‐19 9:13 542      Last Good Value Trapped is     3 A
08‐06‐19 16:27 443      Last Good Value Trapped is     3 A
07‐06‐19 19:20 748      Last Good Value Trapped is     3 A
07‐06‐19 18:14 124      Last Good Value Trapped is     3 A
07‐06‐19 17:19 25      Last Good Value Trapped is     3 A
07‐06‐19 16:26 590 OCP  Operator control panel door closed
07‐06‐19 16:25 272 OCP  Operator control panel door opened
07‐06‐19 16:25 271 OCP  Operator control panel door closed
07‐06‐19 16:06 377      Last Good Value Trapped is     3 A
07‐06‐19 15:52 902 OCP  Operator control panel door opened
07‐06‐19 12:15 435      Last Good Value Trapped is     3 A
07‐06‐19 11:14 817      Last Good Value Trapped is     3 A
07‐06‐19 8:20 454      Last Good Value Trapped is     3 A
07‐06‐19 0:00 1      Battery Test Off
07‐06‐19 0:00 1      Battery Test Capacity OK
07‐06‐19 0:00 0      Battery Test End Voltage 25.24 V
07‐06‐19 0:00 0      Battery Test Middle Voltage 24.36 V
07‐06‐19 0:00 0      Battery Test Beginning Voltage 25.93 V
07‐06‐19 0:00 886      Battery Test Performing Test...
07‐06‐19 0:00 883      Battery Test Start
06‐06‐19 9:05 508      Last Good Value Trapped is     3 A
05‐06‐19 17:14 204      Last Good Value Trapped is     3 A
04‐06‐19 18:03 130      Last Good Value Trapped is     2 A
04‐06‐19 16:38 425 OCP  Operator control panel door closed
04‐06‐19 16:22 39 OCP  Operator control panel door opened
04‐06‐19 12:14 485 OCP  Operator control panel door closed
04‐06‐19 12:13 330 OCP  Operator control panel door opened
04‐06‐19 12:11 321 OCP  Operator control panel door closed
Current at maximum Phase C ‐ Maximum Current of 149 
04‐06‐19 12:07 946      A during fault
Current at maximum Phase B ‐ Maximum Current of 80 
04‐06‐19 12:07 946      A during fault
Current at maximum Phase A ‐ Maximum Current of 176 
04‐06‐19 12:07 946      A during fault
04‐06‐19 12:07 946      Protection Disk Reset
04‐06‐19 12:07 878      All protection elements resetting
04‐06‐19 12:07 656      Pickup Phase B
04‐06‐19 12:07 632      Pickup Phase C
04‐06‐19 12:07 632      Protection Group A Active
04‐06‐19 12:07 632      Pickup Phase A
04‐06‐19 12:07 632      Pickup
04‐06‐19 12:07 600 OCP  Panel Close Request
04‐06‐19 12:01 416      Auxiliary Supply Normal
04‐06‐19 11:48 736      Source Supply On
04‐06‐19 11:24 763      Source Supply Off
04‐06‐19 10:31 498      Source Supply On
04‐06‐19 10:31 438      Measuring Frequency On Bushing Ai
04‐06‐19 10:30 956      Measuring Frequency On Bushing Ci
04‐06‐19 10:30 595      Measuring Frequency On Bushing Ai
04‐06‐19 10:30 655      Measuring Frequency On Bushing Ci
04‐06‐19 10:30 455      Measuring Frequency On Bushing Bi
04‐06‐19 10:30 95      Measuring Frequency On Bushing Ai
04‐06‐19 10:09 891      Lockout
04‐06‐19 10:09 865 OCP  Panel Trip Request
04‐06‐19 10:06 502 OCP  Operator control panel door opened
04‐06‐19 8:44 600      Auxiliary Supply Failure
04‐06‐19 8:44 258      Source Supply Off
04‐06‐19 8:44 741      Last Good Value Trapped is     3 A
03‐06‐19 18:25 863      Last Good Value Trapped is     3 A
03‐06‐19 9:27 703      Last Good Value Trapped is     3 A
03‐06‐19 8:06 544      Last Good Value Trapped is     3 A
31‐05‐19 0:00 996      Battery Test Off
31‐05‐19 0:00 996      Battery Test Capacity OK
31‐05‐19 0:00 995      Battery Test End Voltage 25.24 V
31‐05‐19 0:00 995      Battery Test Middle Voltage 24.39 V
31‐05‐19 0:00 995      Battery Test Beginning Voltage 25.92 V
31‐05‐19 0:00 883      Battery Test Performing Test...
31‐05‐19 0:00 881      Battery Test Start
30‐05‐19 15:13 574      Last Good Value Trapped is     3 A
30‐05‐19 13:40 433      Last Good Value Trapped is     3 A
30‐05‐19 11:30 228      Last Good Value Trapped is     3 A
29‐05‐19 13:57 535      Last Good Value Trapped is     3 A
29‐05‐19 11:43 343      Last Good Value Trapped is     3 A
28‐05‐19 11:50 660      Last Good Value Trapped is     3 A
28‐05‐19 9:52 965      Last Good Value Trapped is     3 A
28‐05‐19 8:48 834      Last Good Value Trapped is     3 A
27‐05‐19 14:47 16      Last Good Value Trapped is     3 A
27‐05‐19 11:18 669      Last Good Value Trapped is     3 A
27‐05‐19 11:10 395 OCP  Operator control panel door closed
27‐05‐19 10:48 748 OCP  Operator control panel door opened
27‐05‐19 10:28 586      Last Good Value Trapped is     3 A
27‐05‐19 9:20 969      Last Good Value Trapped is     3 A
24‐05‐19 0:00 998      Battery Test Off
24‐05‐19 0:00 998      Battery Test Capacity OK
24‐05‐19 0:00 994      Battery Test End Voltage 25.30 V
24‐05‐19 0:00 994      Battery Test Middle Voltage 24.42 V
24‐05‐19 0:00 994      Battery Test Beginning Voltage 25.89 V
24‐05‐19 0:00 881      Battery Test Performing Test...
24‐05‐19 0:00 878      Battery Test Start
23‐05‐19 13:02 607      Last Good Value Trapped is     3 A
23‐05‐19 11:54 510      Last Good Value Trapped is     3 A
23‐05‐19 11:34 277 OCP  Operator control panel door closed
23‐05‐19 11:28 724 OCP  Operator control panel door opened
23‐05‐19 11:24 698 OCP  Operator control panel door closed
23‐05‐19 11:22 133 OCP  Operator control panel door opened
Current at maximum Phase C ‐ Maximum Current of 50 
23‐05‐19 10:19 380      A during fault
Current at maximum Phase B ‐ Maximum Current of 34 
23‐05‐19 10:19 380      A during fault
Current at maximum Phase A ‐ Maximum Current of 25 
23‐05‐19 10:19 380      A during fault
23‐05‐19 10:19 380      Protection Disk Reset
23‐05‐19 10:19 330      All protection elements resetting
23‐05‐19 10:19 226      Pickup Phase B
23‐05‐19 10:19 200      Protection Group A Active
23‐05‐19 10:19 200      Pickup Phase C
23‐05‐19 10:19 200      Pickup
23‐05‐19 9:05 247      Last Good Value Trapped is     3 A
22‐05‐19 15:36 360      Last Good Value Trapped is     3 A
22‐05‐19 14:00 749      Last Good Value Trapped is     3 A
22‐05‐19 12:17 623      Last Good Value Trapped is     3 A
22‐05‐19 10:17 457      Last Good Value Trapped is     3 A
21‐05‐19 19:05 488      Last Good Value Trapped is     3 A
21‐05‐19 18:17 405      Last Good Value Trapped is     3 A
20‐05‐19 17:21 473      Last Good Value Trapped is     4 A
19‐05‐19 17:02 691      Last Good Value Trapped is     2 A
19‐05‐19 11:04 710      Last Good Value Trapped is     2 A
18‐05‐19 17:17 968      Last Good Value Trapped is     3 A
17‐05‐19 15:47 948      Last Good Value Trapped is     2 A
17‐05‐19 0:00 998      Battery Test Off
17‐05‐19 0:00 998      Battery Test Capacity OK
17‐05‐19 0:00 996      Battery Test End Voltage 25.24 V
17‐05‐19 0:00 996      Battery Test Middle Voltage 24.39 V
17‐05‐19 0:00 996      Battery Test Beginning Voltage 25.85 V
17‐05‐19 0:00 878      Battery Test Performing Test...
17‐05‐19 0:00 875      Battery Test Start
15‐05‐19 10:24 601      Last Good Value Trapped is     3 A
Current at maximum Phase C ‐ Maximum Current of 32 
13‐05‐19 17:47 11      A during fault
Current at maximum Phase B ‐ Maximum Current of 81 
13‐05‐19 17:47 11      A during fault
Current at maximum Phase A ‐ Maximum Current of 84 
13‐05‐19 17:47 11      A during fault
13‐05‐19 17:47 11      Protection Disk Reset
13‐05‐19 17:47 961      All protection elements resetting
13‐05‐19 17:47 809      Pickup Phase C
13‐05‐19 17:47 801      Pickup Phase B
13‐05‐19 17:47 778      Protection Group A Active
13‐05‐19 17:47 778      Pickup Phase A
13‐05‐19 17:47 778      Pickup
13‐05‐19 17:31 668 OCP  Operator control panel door closed
13‐05‐19 17:29 120 OCP  Panel Close Request
13‐05‐19 17:29 882      Close Coil Connect
13‐05‐19 17:29 882      Trip Coil Connected
13‐05‐19 17:27 304 OCP  Operator control panel door opened
13‐05‐19 17:26 621      Battery Normal
13‐05‐19 17:26 727      Auxiliary Supply Normal
13‐05‐19 17:23 744      Source Supply On
13‐05‐19 17:23 701      Measuring Frequency On Bushing Ci
13‐05‐19 10:22 588      Maintenance Required
13‐05‐19 10:22 587      Battery Low
13‐05‐19 7:45 124      Source Supply Off
13‐05‐19 7:45 555      Auxiliary Supply Failure
13‐05‐19 7:08 325 OCP  Operator control panel door closed
13‐05‐19 7:08 263 OCP  Operator control panel door opened
13‐05‐19 7:08 263 OCP  Operator control panel door closed
13‐05‐19 7:07 825      Trip Coil Disconnected
13‐05‐19 7:07 793      Close Coil Disconnected
13‐05‐19 7:07 735      Lockout
13‐05‐19 7:07 705 OCP  Panel Trip Request
13‐05‐19 7:07 182 OCP  Operator control panel door opened
10‐05‐19 0:00 987      Battery Test Off
10‐05‐19 0:00 987      Battery Test Capacity OK
10‐05‐19 0:00 986      Battery Test End Voltage 25.16 V
10‐05‐19 0:00 986      Battery Test Middle Voltage 24.28 V
10‐05‐19 0:00 986      Battery Test Beginning Voltage 25.90 V
10‐05‐19 0:00 875      Battery Test Performing Test...
10‐05‐19 0:00 873      Battery Test Start
03‐05‐19 0:00 988      Battery Test Off
03‐05‐19 0:00 988      Battery Test Capacity OK
03‐05‐19 0:00 986      Battery Test End Voltage 25.15 V
03‐05‐19 0:00 986      Battery Test Middle Voltage 24.32 V
03‐05‐19 0:00 986      Battery Test Beginning Voltage 25.81 V
03‐05‐19 0:00 873      Battery Test Performing Test...
03‐05‐19 0:00 871      Battery Test Start
02‐05‐19 8:46 394      Last Good Value Trapped is     4 A
Current at maximum Phase C ‐ Maximum Current of 37 
27‐04‐19 20:59 633      A during fault
Current at maximum Phase B ‐ Maximum Current of 41 
27‐04‐19 20:59 633      A during fault
Current at maximum Phase A ‐ Maximum Current of 16 
27‐04‐19 20:59 633      A during fault
27‐04‐19 20:59 633      Protection Disk Reset
27‐04‐19 20:59 565      All protection elements resetting
27‐04‐19 20:59 511      Pickup Phase C
27‐04‐19 20:59 485      Protection Group A Active
27‐04‐19 20:59 485      Pickup Phase B
27‐04‐19 20:59 485      Pickup
27‐04‐19 20:21 352      Auxiliary Supply Normal
27‐04‐19 20:21 230      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 90 
27‐04‐19 20:21 437      A during fault
Current at maximum Phase B ‐ Maximum Current of 64 
27‐04‐19 20:21 437      A during fault
Current at maximum Phase A ‐ Maximum Current of 43 
27‐04‐19 20:21 437      A during fault
27‐04‐19 20:21 437      Protection Disk Reset
27‐04‐19 20:21 369      All protection elements resetting
27‐04‐19 20:21 220      Measuring Frequency On Bushing Ai
27‐04‐19 20:21 209      Pickup Phase A
27‐04‐19 20:21 183      Pickup Phase C
27‐04‐19 20:21 183      Protection Group A Active
27‐04‐19 20:21 183      Pickup Phase B
27‐04‐19 20:21 183      Pickup
27‐04‐19 19:43 141      Auxiliary Supply Failure
27‐04‐19 19:43 380      Source Supply Off
26‐04‐19 0:00 997      Battery Test Off
26‐04‐19 0:00 997      Battery Test Capacity OK
26‐04‐19 0:00 990      Battery Test End Voltage 25.9 V
26‐04‐19 0:00 990      Battery Test Middle Voltage 24.35 V
26‐04‐19 0:00 990      Battery Test Beginning Voltage 25.81 V
26‐04‐19 0:00 871      Battery Test Performing Test...
26‐04‐19 0:00 870      Battery Test Start
24‐04‐19 23:33 472 OCP  Operator control panel door closed
24‐04‐19 23:32 156 OCP  Operator control panel door opened
24‐04‐19 23:18 59 OCP  Operator control panel door closed
Current at maximum Phase C ‐ Maximum Current of 69 
24‐04‐19 23:18 217      A during fault
Current at maximum Phase B ‐ Maximum Current of 54 
24‐04‐19 23:18 217      A during fault
Current at maximum Phase A ‐ Maximum Current of 29 
24‐04‐19 23:18 217      A during fault
24‐04‐19 23:18 217      Protection Disk Reset
24‐04‐19 23:18 150      All protection elements resetting
24‐04‐19 23:18 3      Pickup Phase C
24‐04‐19 23:18 3      Protection Group A Active
24‐04‐19 23:18 3      Pickup Phase B
24‐04‐19 23:18 3      Pickup
24‐04‐19 23:18 966 OCP  Panel Close Request
24‐04‐19 23:18 34 OCP  Operator control panel door opened
24‐04‐19 23:16 15      Auxiliary Supply Normal
24‐04‐19 23:14 905      Auxiliary Supply Failure
24‐04‐19 23:14 111      Auxiliary Supply Normal
24‐04‐19 23:08 748      Source Supply On
24‐04‐19 23:08 482      Measuring Frequency On Bushing Ci
24‐04‐19 18:18 170      Source Supply Off
24‐04‐19 18:16 351      Auxiliary Supply Failure
24‐04‐19 17:20 808      Auxiliary Supply Normal
24‐04‐19 17:20 718      Source Supply On
24‐04‐19 17:12 663      Auxiliary Supply Failure
24‐04‐19 17:12 160      Source Supply Off
24‐04‐19 10:57 969      Auxiliary Supply Normal
24‐04‐19 10:57 852      Source Supply On
24‐04‐19 8:15 321 OCP  Operator control panel door closed
24‐04‐19 8:15 584      Lockout
24‐04‐19 8:15 557 OCP  Panel Trip Request
24‐04‐19 8:15 267 OCP  Operator control panel door opened
24‐04‐19 5:42 391      Auxiliary Supply Failure
24‐04‐19 5:42 126      Source Supply Off
21‐04‐19 14:57 601 OCP  Operator control panel door closed
21‐04‐19 14:55 341 OCP  Operator control panel door opened
19‐04‐19 0:00 984      Battery Test Off
19‐04‐19 0:00 983      Battery Test Capacity OK
19‐04‐19 0:00 982      Battery Test End Voltage 25.19 V
19‐04‐19 0:00 982      Battery Test Middle Voltage 24.31 V
19‐04‐19 0:00 982      Battery Test Beginning Voltage 25.89 V
19‐04‐19 0:00 870      Battery Test Performing Test...
19‐04‐19 0:00 867      Battery Test Start
Current at maximum Phase C ‐ Maximum Current of 107 
15‐04‐19 7:25 775      A during fault
Current at maximum Phase B ‐ Maximum Current of 48 
15‐04‐19 7:25 775      A during fault
Current at maximum Phase A ‐ Maximum Current of 84 
15‐04‐19 7:25 775      A during fault
15‐04‐19 7:25 775      Protection Disk Reset
15‐04‐19 7:25 693      All protection elements resetting
15‐04‐19 7:25 449      Pickup Phase B
15‐04‐19 7:25 449      Pickup Phase A
15‐04‐19 7:25 423      Protection Group A Active
15‐04‐19 7:25 423      Pickup Phase C
15‐04‐19 7:25 423      Pickup
12‐04‐19 0:00 990      Battery Test Off
12‐04‐19 0:00 990      Battery Test Capacity OK
12‐04‐19 0:00 989      Battery Test End Voltage 25.13 V
12‐04‐19 0:00 989      Battery Test Middle Voltage 24.32 V
12‐04‐19 0:00 989      Battery Test Beginning Voltage 25.55 V
12‐04‐19 0:00 867      Battery Test Performing Test...
12‐04‐19 0:00 865      Battery Test Start
Current at maximum Phase C ‐ Maximum Current of 64 
11‐04‐19 14:08 48      A during fault
Current at maximum Phase B ‐ Maximum Current of 43 
11‐04‐19 14:08 48      A during fault
Current at maximum Phase A ‐ Maximum Current of 31 
11‐04‐19 14:08 48      A during fault
11‐04‐19 14:08 48      Protection Disk Reset
11‐04‐19 14:08 978      All protection elements resetting
11‐04‐19 14:08 863      Pickup Phase A
11‐04‐19 14:08 856      Pickup Phase B
11‐04‐19 14:08 833      Protection Group A Active
11‐04‐19 14:08 833      Pickup Phase C
11‐04‐19 14:08 833      Pickup
Current at maximum Phase C ‐ Maximum Current of 34 
11‐04‐19 5:44 825      A during fault
Current at maximum Phase B ‐ Maximum Current of 64 
11‐04‐19 5:44 825      A during fault
Current at maximum Phase A ‐ Maximum Current of 78 
11‐04‐19 5:44 825      A during fault
11‐04‐19 5:44 825      Protection Disk Reset
11‐04‐19 5:44 753      All protection elements resetting
11‐04‐19 5:44 598      Pickup Phase C
11‐04‐19 5:44 596      Pickup Phase B
11‐04‐19 5:44 573      Protection Group A Active
11‐04‐19 5:44 573      Pickup Phase A
11‐04‐19 5:44 573      Pickup
10‐04‐19 23:24 184      Auxiliary Supply Normal
10‐04‐19 23:23 26      Source Supply On
10‐04‐19 23:15 601      Auxiliary Supply Failure
10‐04‐19 23:15 197      Source Supply Off
10‐04‐19 23:04 219      Normal Power Mode
10‐04‐19 23:04 213      Battery Normal
10‐04‐19 23:04 645      Auxiliary Supply Normal
10‐04‐19 23:04 397      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 25 
10‐04‐19 23:04 545      A during fault
Current at maximum Phase B ‐ Maximum Current of 55 
10‐04‐19 23:04 545      A during fault
Current at maximum Phase A ‐ Maximum Current of 58 
10‐04‐19 23:04 545      A during fault
10‐04‐19 23:04 545      Protection Disk Reset
10‐04‐19 23:04 490      All protection elements resetting
10‐04‐19 23:04 375      Pickup Phase B
10‐04‐19 23:04 352      Protection Group A Active
10‐04‐19 23:04 352      Pickup Phase A
10‐04‐19 23:04 352      Pickup
10‐04‐19 20:37 376      Low Power Mode
10‐04‐19 20:10 339      Maintenance Required
10‐04‐19 20:10 339      Battery Low
10‐04‐19 15:25 426      Auxiliary Supply Failure
10‐04‐19 15:25 250      Source Supply Off
Current at maximum Phase C ‐ Maximum Current of 45 
10‐04‐19 13:52 712      A during fault
Current at maximum Phase B ‐ Maximum Current of 96 
10‐04‐19 13:52 712      A during fault
Current at maximum Phase A ‐ Maximum Current of 101 
10‐04‐19 13:52 712      A during fault
10‐04‐19 13:52 712      Protection Disk Reset
10‐04‐19 13:52 662      All protection elements resetting
10‐04‐19 13:52 424      Pickup Phase C
10‐04‐19 13:52 422      Pickup Phase B
10‐04‐19 13:52 399      Protection Group A Active
10‐04‐19 13:52 399      Pickup Phase A
10‐04‐19 13:52 399      Pickup
Current at maximum Phase C ‐ Maximum Current of 25 
10‐04‐19 12:10 761      A during fault
Current at maximum Phase B ‐ Maximum Current of 28 
10‐04‐19 12:10 761      A during fault
Current at maximum Phase A ‐ Maximum Current of 45 
10‐04‐19 12:10 761      A during fault
10‐04‐19 12:10 761      Protection Disk Reset
10‐04‐19 12:10 711      All protection elements resetting
10‐04‐19 12:10 603      Protection Group A Active
10‐04‐19 12:10 603      Pickup Phase A
10‐04‐19 12:10 603      Pickup
09‐04‐19 16:40 368      Last Good Value Trapped is     3 A
09‐04‐19 11:49 487      Last Good Value Trapped is     4 A
07‐04‐19 16:21 552      Last Good Value Trapped is     3 A
07‐04‐19 14:08 868      Last Good Value Trapped is     3 A
Current at maximum Phase C ‐ Maximum Current of 83 
06‐04‐19 19:15 764      A during fault
Current at maximum Phase B ‐ Maximum Current of 37 
06‐04‐19 19:15 764      A during fault
Current at maximum Phase A ‐ Maximum Current of 78 
06‐04‐19 19:15 764      A during fault
06‐04‐19 19:15 764      Protection Disk Reset
06‐04‐19 19:15 704      All protection elements resetting
06‐04‐19 19:15 522      Pickup Phase B
06‐04‐19 19:15 517      Pickup Phase A
06‐04‐19 19:15 494      Protection Group A Active
06‐04‐19 19:15 494      Pickup Phase C
06‐04‐19 19:15 494      Pickup
05‐04‐19 0:00 998      Battery Test Off
05‐04‐19 0:00 998      Battery Test Capacity OK
05‐04‐19 0:00 988      Battery Test End Voltage 25.30 V
05‐04‐19 0:00 988      Battery Test Middle Voltage 24.46 V
05‐04‐19 0:00 988      Battery Test Beginning Voltage 25.92 V
05‐04‐19 0:00 865      Battery Test Performing Test...
05‐04‐19 0:00 862      Battery Test Start
Current at maximum Phase C ‐ Maximum Current of 49 
03‐04‐19 15:24 334      A during fault
Current at maximum Phase B ‐ Maximum Current of 39 
03‐04‐19 15:24 334      A during fault
Current at maximum Phase A ‐ Maximum Current of 75 
03‐04‐19 15:24 334      A during fault
03‐04‐19 15:24 334      Protection Disk Reset
03‐04‐19 15:24 284      All protection elements resetting
03‐04‐19 15:24 100      Pickup Phase B
03‐04‐19 15:24 69      Pickup Phase C
03‐04‐19 15:24 69      Protection Group A Active
03‐04‐19 15:24 69      Pickup Phase A
03‐04‐19 15:24 69      Pickup
Current at maximum Phase C ‐ Maximum Current of 26 
02‐04‐19 19:34 586      A during fault
Current at maximum Phase B ‐ Maximum Current of 40 
02‐04‐19 19:34 586      A during fault
Current at maximum Phase A ‐ Maximum Current of 56 
02‐04‐19 19:34 586      A during fault
02‐04‐19 19:34 586      Protection Disk Reset
02‐04‐19 19:34 519      All protection elements resetting
02‐04‐19 19:34 422      Pickup Phase B
02‐04‐19 19:34 396      Protection Group A Active
02‐04‐19 19:34 396      Pickup Phase A
02‐04‐19 19:34 396      Pickup
02‐04‐19 19:33 507      Battery Normal
02‐04‐19 19:33 528      Auxiliary Supply Normal
02‐04‐19 19:33 300      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 47 
02‐04‐19 19:33 442      A during fault
Current at maximum Phase B ‐ Maximum Current of 58 
02‐04‐19 19:33 442      A during fault
Current at maximum Phase A ‐ Maximum Current of 23 
02‐04‐19 19:33 442      A during fault
02‐04‐19 19:33 442      Protection Disk Reset
02‐04‐19 19:33 375      All protection elements resetting
02‐04‐19 19:33 291      Measuring Frequency On Bushing Ai
02‐04‐19 19:33 270      Pickup Phase C
02‐04‐19 19:33 247      Protection Group A Active
02‐04‐19 19:33 247      Pickup Phase B
02‐04‐19 19:33 247      Pickup
02‐04‐19 18:40 694      Measuring Frequency On Bushing Bi
02‐04‐19 12:41 213      Maintenance Required
02‐04‐19 12:41 212      Battery Low
02‐04‐19 5:14 867      Auxiliary Supply Failure
02‐04‐19 5:14 424      Source Supply Off
30‐03‐19 17:17 38      Last Good Value Trapped is     4 A
29‐03‐19 17:49 854      Last Good Value Trapped is     3 A
29‐03‐19 0:00 977      Battery Test Off
29‐03‐19 0:00 977      Battery Test Capacity OK
29‐03‐19 0:00 975      Battery Test End Voltage 25.8 V
29‐03‐19 0:00 975      Battery Test Middle Voltage 24.32 V
29‐03‐19 0:00 975      Battery Test Beginning Voltage 25.95 V
29‐03‐19 0:00 862      Battery Test Performing Test...
29‐03‐19 0:00 860      Battery Test Start
28‐03‐19 16:24 332      Last Good Value Trapped is     3 A
28‐03‐19 9:15 664      Last Good Value Trapped is     3 A
27‐03‐19 17:35 89      Last Good Value Trapped is     4 A
26‐03‐19 19:43 53      Last Good Value Trapped is     3 A
26‐03‐19 18:16 906      Last Good Value Trapped is     2 A
26‐03‐19 17:41 355      Last Good Value Trapped is     4 A
26‐03‐19 16:47 280      Last Good Value Trapped is     4 A
Current at maximum Ground Maximum Current Of 361 
25‐03‐19 9:16 906      A during fault
Current at maximum Phase C ‐ Maximum Current of 
25‐03‐19 9:16 906      1008 A during fault
Current at maximum Phase A ‐ Maximum Current of 
25‐03‐19 9:16 906      1134 A during fault
25‐03‐19 9:16 906      Protection Disk Reset
25‐03‐19 9:16 856      All protection elements resetting
25‐03‐19 9:16 816      Protection element timing
25‐03‐19 9:16 794      All protection elements resetting
25‐03‐19 9:16 786      Protection element timing
25‐03‐19 9:16 759      All protection elements resetting
25‐03‐19 9:16 712      Pickup Ground
25‐03‐19 9:16 712      Pickup SGF
25‐03‐19 9:16 709      Pickup Phase C
25‐03‐19 9:16 686      Protection Group A Active
25‐03‐19 9:16 686      Pickup Phase A
25‐03‐19 9:16 686      Pickup
23‐03‐19 15:08 452      Last Good Value Trapped is     3 A
23‐03‐19 12:02 757      Last Good Value Trapped is     3 A
23‐03‐19 9:07 970      Last Good Value Trapped is     4 A
22‐03‐19 20:05 743      Last Good Value Trapped is     3 A
22‐03‐19 14:25 349      Last Good Value Trapped is     3 A
22‐03‐19 12:34 953      Auxiliary Supply Normal
22‐03‐19 12:34 796      Source Supply On
Current at maximum Ground Maximum Current Of 1 A 
22‐03‐19 12:34 991      during fault
Current at maximum Phase C ‐ Maximum Current of 98 
22‐03‐19 12:34 991      A during fault
Current at maximum Phase B ‐ Maximum Current of 67 
22‐03‐19 12:34 991      A during fault
Current at maximum Phase A ‐ Maximum Current of 51 
22‐03‐19 12:34 991      A during fault
22‐03‐19 12:34 991      Protection Disk Reset
22‐03‐19 12:34 923      All protection elements resetting
22‐03‐19 12:34 771      Pickup Phase A
22‐03‐19 12:34 746      Pickup Phase C
22‐03‐19 12:34 746      Protection Group A Active
22‐03‐19 12:34 746      Pickup Phase B
22‐03‐19 12:34 746      Pickup
22‐03‐19 5:54 843      Auxiliary Supply Failure
22‐03‐19 5:54 416      Source Supply Off
22‐03‐19 0:00 980      Battery Test Off
22‐03‐19 0:00 980      Battery Test Capacity OK
22‐03‐19 0:00 979      Battery Test End Voltage 25.8 V
22‐03‐19 0:00 979      Battery Test Middle Voltage 24.27 V
22‐03‐19 0:00 979      Battery Test Beginning Voltage 25.99 V
22‐03‐19 0:00 860      Battery Test Performing Test...
22‐03‐19 0:00 858      Battery Test Start
21‐03‐19 17:33 327      Last Good Value Trapped is     2 A
Current at maximum Phase C ‐ Maximum Current of 40 
21‐03‐19 16:53 885      A during fault
Current at maximum Phase B ‐ Maximum Current of 54 
21‐03‐19 16:53 885      A during fault
Current at maximum Phase A ‐ Maximum Current of 22 
21‐03‐19 16:53 885      A during fault
21‐03‐19 16:53 885      Protection Disk Reset
21‐03‐19 16:53 820      All protection elements resetting
21‐03‐19 16:53 740      Pickup Phase C
21‐03‐19 16:53 715      Protection Group A Active
21‐03‐19 16:53 715      Pickup Phase B
21‐03‐19 16:53 715      Pickup
15‐03‐19 0:00 967      Battery Test Off
15‐03‐19 0:00 967      Battery Test Capacity OK
15‐03‐19 0:00 966      Battery Test End Voltage 25.0 V
15‐03‐19 0:00 966      Battery Test Middle Voltage 24.20 V
15‐03‐19 0:00 966      Battery Test Beginning Voltage 25.84 V
15‐03‐19 0:00 858      Battery Test Performing Test...
15‐03‐19 0:00 853      Battery Test Start
Current at maximum Phase C ‐ Maximum Current of 34 
14‐03‐19 11:15 98      A during fault
Current at maximum Phase B ‐ Maximum Current of 33 
14‐03‐19 11:15 98      A during fault
14‐03‐19 11:15 98      Protection Disk Reset
14‐03‐19 11:15 46      All protection elements resetting
14‐03‐19 11:15 28      Pickup Phase B
14‐03‐19 11:15 5      Protection Group A Active
14‐03‐19 11:15 5      Pickup Phase C
14‐03‐19 11:15 5      Pickup
Current at maximum Phase C ‐ Maximum Current of 41 
13‐03‐19 17:38 157      A during fault
Current at maximum Phase B ‐ Maximum Current of 66 
13‐03‐19 17:38 157      A during fault
Current at maximum Phase A ‐ Maximum Current of 34 
13‐03‐19 17:38 157      A during fault
13‐03‐19 17:38 157      Protection Disk Reset
13‐03‐19 17:38 107      All protection elements resetting
13‐03‐19 17:38 985      Pickup Phase C
13‐03‐19 17:38 985      Pickup Phase A
13‐03‐19 17:38 959      Protection Group A Active
13‐03‐19 17:38 959      Pickup Phase B
13‐03‐19 17:38 959      Pickup
12‐03‐19 14:55 706      Last Good Value Trapped is     4 A
12‐03‐19 11:05 893      Last Good Value Trapped is     4 A
12‐03‐19 8:33 91      Last Good Value Trapped is     5 A
10‐03‐19 14:52 202      Last Good Value Trapped is     4 A
08‐03‐19 0:00 970      Battery Test Off
08‐03‐19 0:00 970      Battery Test Capacity OK
08‐03‐19 0:00 968      Battery Test End Voltage 25.9 V
08‐03‐19 0:00 968      Battery Test Middle Voltage 24.28 V
08‐03‐19 0:00 968      Battery Test Beginning Voltage 25.96 V
08‐03‐19 0:00 853      Battery Test Performing Test...
08‐03‐19 0:00 851      Battery Test Start
Current at maximum Phase C ‐ Maximum Current of 43 
07‐03‐19 18:09 799      A during fault
Current at maximum Phase B ‐ Maximum Current of 53 
07‐03‐19 18:09 799      A during fault
Current at maximum Phase A ‐ Maximum Current of 20 
07‐03‐19 18:09 799      A during fault
07‐03‐19 18:09 799      Protection Disk Reset
07‐03‐19 18:09 734      All protection elements resetting
07‐03‐19 18:09 654      Pickup Phase C
07‐03‐19 18:09 631      Protection Group A Active
07‐03‐19 18:09 631      Pickup Phase B
07‐03‐19 18:09 631      Pickup
Current at maximum Phase C ‐ Maximum Current of 34 
07‐03‐19 16:55 30      A during fault
Current at maximum Phase B ‐ Maximum Current of 63 
07‐03‐19 16:55 30      A during fault
Current at maximum Phase A ‐ Maximum Current of 71 
07‐03‐19 16:55 30      A during fault
07‐03‐19 16:55 30      Protection Disk Reset
07‐03‐19 16:55 972      All protection elements resetting
07‐03‐19 16:55 853      Pickup Phase C
07‐03‐19 16:55 848      Pickup Phase B
07‐03‐19 16:55 825      Protection Group A Active
07‐03‐19 16:55 825      Pickup Phase A
07‐03‐19 16:55 825      Pickup
07‐03‐19 16:50 513      Auxiliary Supply Normal
07‐03‐19 16:50 392      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 41 
07‐03‐19 16:50 457      A during fault
Current at maximum Phase B ‐ Maximum Current of 25 
07‐03‐19 16:50 457      A during fault
Current at maximum Phase A ‐ Maximum Current of 25 
07‐03‐19 16:50 457      A during fault
07‐03‐19 16:50 457      Protection Disk Reset
07‐03‐19 16:50 407      All protection elements resetting
07‐03‐19 16:50 342      Protection Group A Active
07‐03‐19 16:50 342      Pickup Phase C
07‐03‐19 16:50 342      Pickup
07‐03‐19 16:48 639      Auxiliary Supply Failure
07‐03‐19 16:48 707      Source Supply Off
Current at maximum Phase C ‐ Maximum Current of 43 
07‐03‐19 8:21 406      A during fault
Current at maximum Phase B ‐ Maximum Current of 28 
07‐03‐19 8:21 406      A during fault
Current at maximum Phase A ‐ Maximum Current of 60 
07‐03‐19 8:21 406      A during fault
07‐03‐19 8:21 406      Protection Disk Reset
07‐03‐19 8:21 339      All protection elements resetting
07‐03‐19 8:21 239      Pickup Phase C
07‐03‐19 8:21 216      Protection Group A Active
07‐03‐19 8:21 216      Pickup Phase A
07‐03‐19 8:21 216      Pickup
03‐03‐19 17:37 127 OCP  Operator control panel door closed
Current at maximum Phase C ‐ Maximum Current of 61 
03‐03‐19 17:36 26      A during fault
Current at maximum Phase B ‐ Maximum Current of 109 
03‐03‐19 17:36 26      A during fault
Current at maximum Phase A ‐ Maximum Current of 130 
03‐03‐19 17:36 26      A during fault
03‐03‐19 17:36 26      Protection Disk Reset
03‐03‐19 17:36 961      All protection elements resetting
03‐03‐19 17:36 775      Pickup Phase C
03‐03‐19 17:36 775      Pickup Phase B
03‐03‐19 17:36 752      Protection Group A Active
03‐03‐19 17:36 752      Pickup Phase A
03‐03‐19 17:36 752      Pickup
03‐03‐19 17:36 723 OCP  Panel Close Request
03‐03‐19 17:18 578      Lockout
03‐03‐19 17:18 551 OCP  Panel Trip Request
03‐03‐19 17:15 280 OCP  Operator control panel door opened
Current at maximum Phase C ‐ Maximum Current of 26 
02‐03‐19 18:59 199      A during fault
Current at maximum Phase B ‐ Maximum Current of 27 
02‐03‐19 18:59 199      A during fault
Current at maximum Phase A ‐ Maximum Current of 45 
02‐03‐19 18:59 199      A during fault
02‐03‐19 18:59 199      Protection Disk Reset
02‐03‐19 18:59 149      All protection elements resetting
02‐03‐19 18:59 49      Protection Group A Active
02‐03‐19 18:59 49      Pickup Phase A
02‐03‐19 18:59 49      Pickup
Current at maximum Phase B ‐ Maximum Current of 43 
01‐03‐19 14:30 980      A during fault
Current at maximum Phase A ‐ Maximum Current of 42 
01‐03‐19 14:30 980      A during fault
01‐03‐19 14:30 980      Protection Disk Reset
01‐03‐19 14:30 925      All protection elements resetting
01‐03‐19 14:30 850      Pickup Phase A
01‐03‐19 14:30 827      Protection Group A Active
01‐03‐19 14:30 827      Pickup Phase B
01‐03‐19 14:30 827      Pickup
01‐03‐19 0:00 963      Battery Test Off
01‐03‐19 0:00 963      Battery Test Capacity OK
01‐03‐19 0:00 962      Battery Test End Voltage 25.16 V
01‐03‐19 0:00 962      Battery Test Middle Voltage 24.29 V
01‐03‐19 0:00 962      Battery Test Beginning Voltage 25.97 V
01‐03‐19 0:00 851      Battery Test Performing Test...
01‐03‐19 0:00 849      Battery Test Start
28‐02‐19 8:07 246      Last Good Value Trapped is     3 A
28‐02‐19 6:46 44      Last Good Value Trapped is     3 A
28‐02‐19 5:29 849      Last Good Value Trapped is     3 A
28‐02‐19 4:37 718      Last Good Value Trapped is     3 A
28‐02‐19 4:07 645      Last Good Value Trapped is     3 A
28‐02‐19 3:19 28      Last Good Value Trapped is     3 A
28‐02‐19 2:45 444      Last Good Value Trapped is     3 A
28‐02‐19 1:31 767      Last Good Value Trapped is     3 A
28‐02‐19 1:07 713      Last Good Value Trapped is     3 A
27‐02‐19 22:47 397      Last Good Value Trapped is     3 A
27‐02‐19 9:20 681      Last Good Value Trapped is     3 A
27‐02‐19 6:33 774      Last Good Value Trapped is     3 A
27‐02‐19 1:40 536      Last Good Value Trapped is     3 A
26‐02‐19 23:11 688      Last Good Value Trapped is     4 A
26‐02‐19 22:36 611      Last Good Value Trapped is     4 A
26‐02‐19 21:51 514      Last Good Value Trapped is     4 A
26‐02‐19 14:07 822 OCP  Operator control panel door closed
26‐02‐19 14:06 334 OCP  Operator control panel door opened
Current at maximum Phase C ‐ Maximum Current of 25 
26‐02‐19 7:14 175      A during fault
Current at maximum Phase B ‐ Maximum Current of 12 
26‐02‐19 7:14 175      A during fault
Current at maximum Phase A ‐ Maximum Current of 31 
26‐02‐19 7:14 175      A during fault
26‐02‐19 7:14 175      Protection Disk Reset
26‐02‐19 7:14 126      All protection elements resetting
26‐02‐19 7:14 80      Protection Group A Active
26‐02‐19 7:14 80      Pickup Phase A
26‐02‐19 7:14 80      Pickup
25‐02‐19 16:19 984      Last Good Value Trapped is     4 A
25‐02‐19 15:23 407      Last Good Value Trapped is     6 A
25‐02‐19 14:22 828      Last Good Value Trapped is     3 A
25‐02‐19 13:00 228      Last Good Value Trapped is     2 A
25‐02‐19 10:32 514      Last Good Value Trapped is     4 A
24‐02‐19 20:33 266      Auxiliary Supply Normal
24‐02‐19 20:33 160      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 110 
24‐02‐19 20:33 377      A during fault
Current at maximum Phase B ‐ Maximum Current of 85 
24‐02‐19 20:33 377      A during fault
Current at maximum Phase A ‐ Maximum Current of 159 
24‐02‐19 20:33 377      A during fault
24‐02‐19 20:33 377      Protection Disk Reset
24‐02‐19 20:33 312      All protection elements resetting
24‐02‐19 20:33 110      Pickup Phase B
24‐02‐19 20:33 85      Pickup Phase C
24‐02‐19 20:33 85      Protection Group A Active
24‐02‐19 20:33 85      Pickup Phase A
24‐02‐19 20:33 85      Pickup
24‐02‐19 19:19 973      Auxiliary Supply Failure
24‐02‐19 19:19 920      Source Supply Off
24‐02‐19 16:12 632      Last Good Value Trapped is     5 A
24‐02‐19 11:37 789      Last Good Value Trapped is     3 A
24‐02‐19 9:52 605      Last Good Value Trapped is     3 A
24‐02‐19 9:19 36      Last Good Value Trapped is     3 A
Current at maximum Phase C ‐ Maximum Current of 45 
24‐02‐19 7:58 381      A during fault
Current at maximum Phase B ‐ Maximum Current of 61 
24‐02‐19 7:58 381      A during fault
Current at maximum Phase A ‐ Maximum Current of 29 
24‐02‐19 7:58 381      A during fault
24‐02‐19 7:58 381      Protection Disk Reset
24‐02‐19 7:58 331      All protection elements resetting
24‐02‐19 7:58 179      Pickup Phase C
24‐02‐19 7:58 153      Protection Group A Active
24‐02‐19 7:58 153      Pickup Phase B
24‐02‐19 7:58 153      Pickup
24‐02‐19 5:19 514      Auxiliary Supply Normal
24‐02‐19 5:19 388      Source Supply On
Current at maximum Phase C ‐ Maximum Current of 25 
24‐02‐19 5:19 418      A during fault
Current at maximum Phase B ‐ Maximum Current of 23 
24‐02‐19 5:19 418      A during fault
Current at maximum Phase A ‐ Maximum Current of 37 
24‐02‐19 5:19 418      A during fault
24‐02‐19 5:19 418      Protection Disk Reset
24‐02‐19 5:19 368      All protection elements resetting
24‐02‐19 5:19 323      Protection Group A Active
24‐02‐19 5:19 323      Pickup Phase A
24‐02‐19 5:19 323      Pickup
24‐02‐19 5:17 668      Auxiliary Supply Failure
24‐02‐19 5:17 634      Source Supply Off
24‐02‐19 5:16 16      Auxiliary Supply Normal
24‐02‐19 5:16 854      Source Supply On
24‐02‐19 5:10 258      Auxiliary Supply Failure
24‐02‐19 5:10 997      Source Supply Off
23‐02‐19 17:00 963      Last Good Value Trapped is     3 A
Current at maximum Phase C ‐ Maximum Current of 27 
22‐02‐19 17:34 602      A during fault
Current at maximum Phase B ‐ Maximum Current of 37 
22‐02‐19 17:34 602      A during fault
Current at maximum Phase A ‐ Maximum Current of 16 
22‐02‐19 17:34 602      A during fault
22‐02‐19 17:34 602      Protection Disk Reset
22‐02‐19 17:34 552      All protection elements resetting
22‐02‐19 17:34 501      Protection Group A Active
22‐02‐19 17:34 501      Pickup Phase B
22‐02‐19 17:34 501      Pickup
22‐02‐19 16:37 200      Last Good Value Trapped is     5 A
22‐02‐19 14:05 556      Last Good Value Trapped is     4 A
22‐02‐19 12:25 938      Last Good Value Trapped is     3 A
22‐02‐19 0:00 965      Battery Test Off
22‐02‐19 0:00 965      Battery Test Capacity OK
22‐02‐19 0:00 963      Battery Test End Voltage 25.16 V
22‐02‐19 0:00 963      Battery Test Middle Voltage 24.34 V
22‐02‐19 0:00 963      Battery Test Beginning Voltage 25.99 V
22‐02‐19 0:00 849      Battery Test Performing Test...
22‐02‐19 0:00 843      Battery Test Start
Current at maximum Phase C ‐ Maximum Current of 14 
21‐02‐19 18:08 271      A during fault
Current at maximum Phase B ‐ Maximum Current of 34 
21‐02‐19 18:08 271      A during fault
Current at maximum Phase A ‐ Maximum Current of 33 
21‐02‐19 18:08 271      A during fault
21‐02‐19 18:08 271      Protection Disk Reset
21‐02‐19 18:08 214      All protection elements resetting
21‐02‐19 18:08 199      Pickup Phase B
21‐02‐19 18:08 176      Protection Group A Active
21‐02‐19 18:08 176      Pickup Phase A
21‐02‐19 18:08 176      Pickup
21‐02‐19 16:50 65      Last Good Value Trapped is     5 A
21‐02‐19 9:28 16      Last Good Value Trapped is     4 A
20‐02‐19 17:39 442      Last Good Value Trapped is     4 A
20‐02‐19 14:57 767      Last Good Value Trapped is     3 A
Current at maximum Phase C ‐ Maximum Current of 46 
19‐02‐19 12:46 220      A during fault
Current at maximum Phase B ‐ Maximum Current of 57 
19‐02‐19 12:46 220      A during fault
Current at maximum Phase A ‐ Maximum Current of 24 
19‐02‐19 12:46 220      A during fault
19‐02‐19 12:46 220      Protection Disk Reset
19‐02‐19 12:46 135      All protection elements resetting
19‐02‐19 12:46 31      Pickup Phase C
19‐02‐19 12:46 8      Protection Group A Active
19‐02‐19 12:46 8      Pickup Phase B
19‐02‐19 12:46 8      Pickup
19‐02‐19 9:24 965      Auxiliary Supply Normal
19‐02‐19 9:24 854      Source Supply On
19‐02‐19 9:24 844      Measuring Frequency On Bushing Ai
19‐02‐19 9:24 590      Auxiliary Supply Failure
19‐02‐19 9:24 324      Source Supply Off
19‐02‐19 9:24 264      Measuring Frequency On Bushing Bi
Current at maximum Phase C ‐ Maximum Current of 33 
18‐02‐19 19:22 101      A during fault
Current at maximum Phase B ‐ Maximum Current of 74 
18‐02‐19 19:22 101      A during fault
Current at maximum Phase A ‐ Maximum Current of 64 
18‐02‐19 19:22 101      A during fault
18‐02‐19 19:22 101      Protection Disk Reset
18‐02‐19 19:22 46      All protection elements resetting
18‐02‐19 19:22 999      Pickup Phase C
18‐02‐19 19:22 989      Pickup Phase B
18‐02‐19 19:22 966      Protection Group A Active
18‐02‐19 19:22 966      Pickup Phase A
18‐02‐19 19:22 966      Pickup
Current at maximum Phase C ‐ Maximum Current of 25 
18‐02‐19 16:56 289      A during fault
Current at maximum Phase B ‐ Maximum Current of 24 
18‐02‐19 16:56 289      A during fault
Current at maximum Phase A ‐ Maximum Current of 41 
18‐02‐19 16:56 289      A during fault
18‐02‐19 16:56 289      Protection Disk Reset
18‐02‐19 16:56 239      All protection elements resetting
18‐02‐19 16:56 177      Protection Group A Active
18‐02‐19 16:56 177      Pickup Phase A
18‐02‐19 16:56 177      Pickup
17‐02‐19 18:11 963 OCP  Operator control panel door closed
Current at maximum Phase C ‐ Maximum Current of 37 
17‐02‐19 18:04 15      A during fault
Current at maximum Phase B ‐ Maximum Current of 22 
17‐02‐19 18:04 15      A during fault
Current at maximum Phase A ‐ Maximum Current of 48 
17‐02‐19 18:04 15      A during fault
17‐02‐19 18:04 15      Protection Disk Reset
17‐02‐19 18:04 961      All protection elements resetting
17‐02‐19 18:04 923      Pickup Phase C
17‐02‐19 18:04 900      Protection Group A Active
17‐02‐19 18:04 900      Pickup Phase A
17‐02‐19 18:04 900      Pickup
17‐02‐19 18:04 862 OCP  Panel Close Request
17‐02‐19 18:04 28      Trip Coil Connected
17‐02‐19 18:04 980      Close Coil Connect
17‐02‐19 18:03 867 OCP  Operator control panel door opened
17‐02‐19 17:01 508 OCP  Operator control panel door closed
17‐02‐19 17:01 189      Close Coil Disconnected
17‐02‐19 17:01 173      Trip Coil Disconnected
17‐02‐19 17:01 232      Lockout
17‐02‐19 17:01 203 OCP  Panel Trip Request
17‐02‐19 17:00 393 OCP  Operator control panel door opened
17‐02‐19 16:19 116 OCP  Operator control panel door closed
17‐02‐19 16:07 40 OCP  Operator control panel door opened
16‐02‐19 20:25 291      Auxiliary Supply Normal
16‐02‐19 20:25 181      Source Supply On
16‐02‐19 20:17 729      Auxiliary Supply Failure
16‐02‐19 20:17 468      Source Supply Off
Current at maximum Phase C ‐ Maximum Current of 31 
16‐02‐19 18:36 883      A during fault
Current at maximum Phase B ‐ Maximum Current of 31 
16‐02‐19 18:36 883      A during fault
Current at maximum Phase A ‐ Maximum Current of 13 
16‐02‐19 18:36 883      A during fault
16‐02‐19 18:36 883      Protection Disk Reset
16‐02‐19 18:36 834      All protection elements resetting
16‐02‐19 18:36 824      Pickup Phase C
16‐02‐19 18:36 801      Protection Group A Active
16‐02‐19 18:36 801      Pickup Phase B
16‐02‐19 18:36 801      Pickup
16‐02‐19 6:53 609      Auxiliary Supply Normal
16‐02‐19 6:53 474      Source Supply On
16‐02‐19 6:53 448      Measuring Frequency On Bushing Ai
16‐02‐19 6:35 35      Auxiliary Supply Failure
16‐02‐19 6:35 765      Source Supply Off
16‐02‐19 6:35 722      Measuring Frequency On Bushing Bi
15‐02‐19 10:31 902      Auxiliary Supply Normal
15‐02‐19 10:31 791      Source Supply On
15‐02‐19 10:31 781      Measuring Frequency On Bushing Ai
15‐02‐19 10:31 601      Auxiliary Supply Failure
15‐02‐19 10:31 293      Source Supply Off
15‐02‐19 10:31 241      Measuring Frequency On Bushing Bi
15‐02‐19 0:00 961      Battery Test Off
15‐02‐19 0:00 961      Battery Test Capacity OK
15‐02‐19 0:00 960      Battery Test End Voltage 25.19 V
15‐02‐19 0:00 960      Battery Test Middle Voltage 24.36 V
15‐02‐19 0:00 960      Battery Test Beginning Voltage 26.3 V
15‐02‐19 0:00 843      Battery Test Performing Test...
15‐02‐19 0:00 840      Battery Test Start
14‐02‐19 7:20 829      Auxiliary Supply Normal
14‐02‐19 7:20 723      Source Supply On
14‐02‐19 7:20 350      Auxiliary Supply Failure
14‐02‐19 7:20 192      Source Supply Off
Current at maximum Phase C ‐ Maximum Current of 41 
12‐02‐19 17:20 120      A during fault
Current at maximum Phase B ‐ Maximum Current of 20 
12‐02‐19 17:20 120      A during fault
Current at maximum Phase A ‐ Maximum Current of 48 
12‐02‐19 17:20 120      A during fault
12‐02‐19 17:20 120      Protection Disk Reset
12‐02‐19 17:20 66      All protection elements resetting
12‐02‐19 17:20 8      Pickup Phase C
12‐02‐19 17:20 8      Protection Group A Active
12‐02‐19 17:20 8      Pickup Phase A
12‐02‐19 17:20 8      Pickup
09‐02‐19 21:41 598      Auxiliary Supply Normal
09‐02‐19 21:41 524      Source Supply On
09‐02‐19 21:40 167      Auxiliary Supply Failure
09‐02‐19 21:40 979      Source Supply Off
09‐02‐19 21:24 717      Auxiliary Supply Normal
09‐02‐19 21:24 621      Source Supply On
09‐02‐19 21:24 611      Measuring Frequency On Bushing Ai
09‐02‐19 19:54 298      Measuring Frequency On Bushing Ci
09‐02‐19 19:11 208      Measuring Frequency On Bushing Ai
09‐02‐19 19:10 228      Measuring Frequency On Bushing Ci
09‐02‐19 19:10 538      Auxiliary Supply Failure
09‐02‐19 19:10 190      Source Supply Off
09‐02‐19 17:15 729      Auxiliary Supply Normal
09‐02‐19 17:15 667      Source Supply On
09‐02‐19 17:15 655      Measuring Frequency On Bushing Ai
09‐02‐19 17:14 625      Auxiliary Supply Failure
09‐02‐19 17:14 204      Source Supply Off
09‐02‐19 17:14 154      Measuring Frequency On Bushing Ci
08‐02‐19 0:00 963      Battery Test Off
08‐02‐19 0:00 963      Battery Test Capacity OK
08‐02‐19 0:00 962      Battery Test End Voltage 25.20 V
08‐02‐19 0:00 962      Battery Test Middle Voltage 24.38 V
08‐02‐19 0:00 962      Battery Test Beginning Voltage 25.99 V
08‐02‐19 0:00 840      Battery Test Performing Test...
08‐02‐19 0:00 838      Battery Test Start
01‐02‐19 0:00 952      Battery Test Off
01‐02‐19 0:00 952      Battery Test Capacity OK
01‐02‐19 0:00 952      Battery Test End Voltage 25.29 V
01‐02‐19 0:00 952      Battery Test Middle Voltage 24.42 V
01‐02‐19 0:00 951      Battery Test Beginning Voltage 26.4 V
01‐02‐19 0:00 838      Battery Test Performing Test...
01‐02‐19 0:00 835      Battery Test Start
25‐01‐19 17:03 79      Battery Normal
25‐01‐19 17:03 937      Auxiliary Supply Normal
25‐01‐19 17:03 780      Source Supply On
25‐01‐19 17:03 768      Measuring Frequency On Bushing Ai
25‐01‐19 16:29 783      Maintenance Required
25‐01‐19 16:29 783      Battery Low
25‐01‐19 8:59 489      Auxiliary Supply Failure
25‐01‐19 8:59 211      Source Supply Off
25‐01‐19 8:59 155      Measuring Frequency On Bushing Ci
25‐01‐19 0:00 952      Battery Test Off
25‐01‐19 0:00 952      Battery Test Capacity OK
25‐01‐19 0:00 952      Battery Test End Voltage 25.23 V
25‐01‐19 0:00 952      Battery Test Middle Voltage 24.32 V
25‐01‐19 0:00 952      Battery Test Beginning Voltage 26.1 V
25‐01‐19 0:00 835      Battery Test Performing Test...
25‐01‐19 0:00 834      Battery Test Start
23‐01‐19 18:32 398      Auxiliary Supply Normal
23‐01‐19 18:32 311      Source Supply On
23‐01‐19 18:20 317      Auxiliary Supply Failure
23‐01‐19 18:20 964      Source Supply Off
23‐01‐19 5:32 313      Auxiliary Supply Normal
23‐01‐19 5:32 202      Source Supply On
23‐01‐19 5:24 581      Auxiliary Supply Failure
23‐01‐19 5:24 314      Source Supply Off
18‐01‐19 0:00 967      Battery Test Off
18‐01‐19 0:00 967      Battery Test Capacity OK
18‐01‐19 0:00 958      Battery Test End Voltage 25.11 V
18‐01‐19 0:00 958      Battery Test Middle Voltage 24.34 V
18‐01‐19 0:00 958      Battery Test Beginning Voltage 26.4 V
18‐01‐19 0:00 834      Battery Test Performing Test...
18‐01‐19 0:00 832      Battery Test Start
16‐01‐19 11:32 444      Auxiliary Supply Normal
16‐01‐19 11:32 346      Source Supply On
16‐01‐19 11:30 101      Auxiliary Supply Failure
16‐01‐19 11:30 736      Source Supply Off
15‐01‐19 17:55 763 OCP  Operator control panel door closed
15‐01‐19 17:53 467 OCP  Operator control panel door opened
14‐01‐19 20:03 631      Auxiliary Supply Normal
14‐01‐19 20:03 532      Source Supply On
14‐01‐19 20:03 507      Measuring Frequency On Bushing Ai
14‐01‐19 19:50 88      Auxiliary Supply Failure
14‐01‐19 19:50 815      Source Supply Off
12‐01‐19 16:25 184      Auxiliary Supply Normal
12‐01‐19 16:25 103      Source Supply On
12‐01‐19 16:25 51      Measuring Frequency On Bushing Ci
12‐01‐19 16:10 798      Auxiliary Supply Failure
12‐01‐19 16:09 489      Source Supply Off
11‐01‐19 0:00 950      Battery Test Off
11‐01‐19 0:00 950      Battery Test Capacity OK
11‐01‐19 0:00 949      Battery Test End Voltage 25.29 V
11‐01‐19 0:00 949      Battery Test Middle Voltage 24.35 V
11‐01‐19 0:00 949      Battery Test Beginning Voltage 26.6 V
11‐01‐19 0:00 832      Battery Test Performing Test...
11‐01‐19 0:00 830      Battery Test Start
09‐01‐19 3:10 729      Auxiliary Supply Normal
09‐01‐19 3:10 624      Source Supply On
09‐01‐19 0:41 399      Auxiliary Supply Failure
09‐01‐19 0:41 194      Source Supply Off
04‐01‐19 0:00 950      Battery Test Off
04‐01‐19 0:00 950      Battery Test Capacity OK
04‐01‐19 0:00 949      Battery Test End Voltage 25.23 V
04‐01‐19 0:00 949      Battery Test Middle Voltage 24.36 V
04‐01‐19 0:00 949      Battery Test Beginning Voltage 26.8 V
04‐01‐19 0:00 830      Battery Test Performing Test...
04‐01‐19 0:00 828      Battery Test Start
28‐12‐18 0:00 957      Battery Test Off
28‐12‐18 0:00 957      Battery Test Capacity OK
28‐12‐18 0:00 946      Battery Test End Voltage 25.27 V
28‐12‐18 0:00 946      Battery Test Middle Voltage 24.39 V
28‐12‐18 0:00 946      Battery Test Beginning Voltage 25.99 V
28‐12‐18 0:00 828      Battery Test Performing Test...
28‐12‐18 0:00 826      Battery Test Start
24‐12‐18 18:45 183      Auxiliary Supply Normal
24‐12‐18 18:45 86      Source Supply On
24‐12‐18 18:20 245      Auxiliary Supply Failure
24‐12‐18 18:20 975      Source Supply Off
24‐12‐18 16:15 37      Auxiliary Supply Normal
24‐12‐18 16:15 918      Source Supply On
24‐12‐18 16:15 905      Measuring Frequency On Bushing Ai
24‐12‐18 16:09 946      Auxiliary Supply Failure
24‐12‐18 16:09 615      Source Supply Off
24‐12‐18 16:09 557      Measuring Frequency On Bushing Bi
21‐12‐18 0:00 939      Battery Test Off
21‐12‐18 0:00 939      Battery Test Capacity OK
21‐12‐18 0:00 938      Battery Test End Voltage 25.22 V
21‐12‐18 0:00 938      Battery Test Middle Voltage 24.42 V
21‐12‐18 0:00 938      Battery Test Beginning Voltage 26.4 V
21‐12‐18 0:00 826      Battery Test Performing Test...
21‐12‐18 0:00 824      Battery Test Start
20‐12‐18 2:06 147      Auxiliary Supply Normal
20‐12‐18 2:06 57      Source Supply On
20‐12‐18 1:55 244      Auxiliary Supply Failure
20‐12‐18 1:55 935      Source Supply Off
18‐12‐18 10:53 175      Auxiliary Supply Normal
18‐12‐18 10:53 37      Source Supply On
18‐12‐18 10:53 995      Normal Power Mode
18‐12‐18 9:25 817 OCP  Operator control panel door closed
18‐12‐18 9:19 836      Maintenance Required
18‐12‐18 9:19 835      Low Power Mode
18‐12‐18 9:19 594 OCP  Panel Close Request
18‐12‐18 9:18 924 OCP  Operator control panel door opened
18‐12‐18 9:04 651      Measuring Frequency On Bushing Ai
18‐12‐18 9:01 796 OCP  Operator control panel door closed
18‐12‐18 9:00 21      Lockout
18‐12‐18 9:00 990 OCP  Panel Trip Request
18‐12‐18 9:00 633 OCP  Operator control panel door opened
18‐12‐18 8:17 785      Auxiliary Supply Failure
18‐12‐18 8:17 644      Source Supply Off
18‐12‐18 8:17 587      Measuring Frequency On Bushing Bi
18‐12‐18 8:00 31      Auxiliary Supply Normal
18‐12‐18 8:00 922      Source Supply On
18‐12‐18 7:59 877      Measuring Frequency On Bushing Ci
18‐12‐18 3:55 342      Measuring Frequency On Bushing Ai
18‐12‐18 3:43 189      Measuring Frequency On Bushing Bi
18‐12‐18 3:41 723      Measuring Frequency On Bushing Ai
18‐12‐18 3:22 306      Auxiliary Supply Failure
18‐12‐18 3:22 29      Source Supply Off
14‐12‐18 0:00 945      Battery Test Off
14‐12‐18 0:00 945      Battery Test Capacity OK
14‐12‐18 0:00 943      Battery Test End Voltage 25.20 V
14‐12‐18 0:00 943      Battery Test Middle Voltage 24.27 V
14‐12‐18 0:00 943      Battery Test Beginning Voltage 26.7 V
14‐12‐18 0:00 824      Battery Test Performing Test...
14‐12‐18 0:00 823      Battery Test Start
09‐12‐18 19:12 196      Auxiliary Supply Normal
09‐12‐18 19:12 92      Source Supply On
09‐12‐18 19:12 39      Measuring Frequency On Bushing Ci
09‐12‐18 19:05 156      Auxiliary Supply Failure
09‐12‐18 19:05 597      Source Supply Off
09‐12‐18 5:28 45      Auxiliary Supply Normal
09‐12‐18 5:28 944      Source Supply On
09‐12‐18 5:20 359      Auxiliary Supply Failure
09‐12‐18 5:20 47      Source Supply Off
07‐12‐18 0:00 944      Battery Test Off
07‐12‐18 0:00 944      Battery Test Capacity OK
07‐12‐18 0:00 943      Battery Test End Voltage 24.95 V
07‐12‐18 0:00 943      Battery Test Middle Voltage 24.10 V
07‐12‐18 0:00 943      Battery Test Beginning Voltage 25.75 V
07‐12‐18 0:00 823      Battery Test Performing Test...
07‐12‐18 0:00 821      Battery Test Start
30‐11‐18 0:00 943      Battery Test Off
30‐11‐18 0:00 943      Battery Test Capacity OK
30‐11‐18 0:00 943      Battery Test End Voltage 25.22 V
30‐11‐18 0:00 943      Battery Test Middle Voltage 24.32 V
30‐11‐18 0:00 943      Battery Test Beginning Voltage 25.92 V
30‐11‐18 0:00 821      Battery Test Performing Test...
30‐11‐18 0:00 819      Battery Test Start
25‐11‐18 21:17 418      Auxiliary Supply Normal
25‐11‐18 21:17 318      Source Supply On
25‐11‐18 18:26 780      Auxiliary Supply Failure
25‐11‐18 18:26 516      Source Supply Off
23‐11‐18 0:00 937      Battery Test Off
23‐11‐18 0:00 937      Battery Test Capacity OK
23‐11‐18 0:00 931      Battery Test End Voltage 25.5 V
23‐11‐18 0:00 931      Battery Test Middle Voltage 24.20 V
23‐11‐18 0:00 931      Battery Test Beginning Voltage 25.90 V
23‐11‐18 0:00 819      Battery Test Performing Test...
23‐11‐18 0:00 817      Battery Test Start
19‐11‐18 17:37 648      Auxiliary Supply Normal
19‐11‐18 17:37 542      Source Supply On
19‐11‐18 17:26 296      Auxiliary Supply Failure
19‐11‐18 17:26 791      Source Supply Off
19‐11‐18 5:24 141      Auxiliary Supply Normal
19‐11‐18 5:24 40      Source Supply On
19‐11‐18 5:13 111      Auxiliary Supply Failure
19‐11‐18 5:13 933      Source Supply Off
19‐11‐18 5:12 715      Auxiliary Supply Normal
19‐11‐18 5:12 619      Source Supply On
19‐11‐18 5:09 135      Auxiliary Supply Failure
19‐11‐18 5:09 748      Source Supply Off
16‐11‐18 0:00 935      Battery Test Off
16‐11‐18 0:00 935      Battery Test Capacity OK
16‐11‐18 0:00 935      Battery Test End Voltage 25.1 V
16‐11‐18 0:00 935      Battery Test Middle Voltage 24.13 V
16‐11‐18 0:00 935      Battery Test Beginning Voltage 25.73 V
16‐11‐18 0:00 817      Battery Test Performing Test...
16‐11‐18 0:00 814      Battery Test Start
09‐11‐18 0:00 928      Battery Test Off
09‐11‐18 0:00 928      Battery Test Capacity OK
09‐11‐18 0:00 927      Battery Test End Voltage 25.0 V
09‐11‐18 0:00 927      Battery Test Middle Voltage 24.11 V
09‐11‐18 0:00 927      Battery Test Beginning Voltage 25.63 V
09‐11‐18 0:00 814      Battery Test Performing Test...
09‐11‐18 0:00 811      Battery Test Start
02‐11‐18 12:55 300      Auxiliary Supply Normal
02‐11‐18 12:55 216      Source Supply On
02‐11‐18 12:54 911      Auxiliary Supply Failure
02‐11‐18 12:54 543      Source Supply Off
02‐11‐18 12:00 42 OCP  Operator control panel door closed
02‐11‐18 12:00 830 OCP  Panel Close Request
02‐11‐18 11:59 927 OCP  Operator control panel door opened
02‐11‐18 11:18 662 OCP  Operator control panel door closed
02‐11‐18 11:18 97      Trip Coil Connected
02‐11‐18 11:18 65      Close Coil Connect
02‐11‐18 11:18 640 OCP  Trip Coil Disconnected
02‐11‐18 11:18 634 OCP  Panel Close Request ‐ Denied
02‐11‐18 11:18 656 OCP  Operator control panel door opened
02‐11‐18 9:55 314 OCP  Operator control panel door closed
02‐11‐18 9:55 314 OCP  Operator control panel door opened
02‐11‐18 9:55 313 OCP  Operator control panel door closed
02‐11‐18 9:54 272 OCP  Operator control panel door opened
02‐11‐18 9:00 267      Auxiliary Supply Normal
02‐11‐18 9:00 150      Source Supply On
02‐11‐18 7:07 509 OCP  Operator control panel door closed
02‐11‐18 7:07 759      Close Coil Disconnected
02‐11‐18 7:07 759      Trip Coil Disconnected
02‐11‐18 7:07 409      Lockout
02‐11‐18 7:07 379 OCP  Panel Trip Request
02‐11‐18 7:07 443 OCP  Operator control panel door opened
02‐11‐18 7:01 104      Auxiliary Supply Failure
02‐11‐18 7:01 724      Source Supply Off
02‐11‐18 0:00 937      Battery Test Off
02‐11‐18 0:00 937      Battery Test Capacity OK
02‐11‐18 0:00 932      Battery Test End Voltage 24.84 V
02‐11‐18 0:00 932      Battery Test Middle Voltage 24.2 V
02‐11‐18 0:00 932      Battery Test Beginning Voltage 25.52 V
02‐11‐18 0:00 812      Battery Test Performing Test...
02‐11‐18 0:00 808      Battery Test Start
31‐10‐18 5:10 193      Auxiliary Supply Normal
31‐10‐18 5:10 88      Source Supply On
31‐10‐18 5:02 7      Auxiliary Supply Failure
31‐10‐18 5:02 671      Source Supply Off
28‐10‐18 0:29 512      Auxiliary Supply Normal
28‐10‐18 0:29 410      Source Supply On
27‐10‐18 23:30 694      Auxiliary Supply Failure
27‐10‐18 23:30 385      Source Supply Off
26‐10‐18 6:00 388      Auxiliary Supply Normal
26‐10‐18 6:00 275      Source Supply On
26‐10‐18 4:59 141      Auxiliary Supply Failure
26‐10‐18 4:59 713      Source Supply Off
26‐10‐18 0:00 922      Battery Test Off
26‐10‐18 0:00 922      Battery Test Capacity OK
26‐10‐18 0:00 921      Battery Test End Voltage 25.6 V
26‐10‐18 0:00 921      Battery Test Middle Voltage 24.11 V
26‐10‐18 0:00 921      Battery Test Beginning Voltage 25.51 V
26‐10‐18 0:00 808      Battery Test Performing Test...
26‐10‐18 0:00 801      Battery Test Start
25‐10‐18 22:12 550      Auxiliary Supply Normal
25‐10‐18 22:12 425      Source Supply On
25‐10‐18 22:04 685      Auxiliary Supply Failure
25‐10‐18 22:04 392      Source Supply Off
19‐10‐18 11:00 668 OCP  Operator control panel door closed
19‐10‐18 10:57 355 OCP  Operator control panel door opened
19‐10‐18 10:56 352 OCP  Operator control panel door closed
19‐10‐18 10:54 70      Trip Coil Connected
19‐10‐18 10:54 155 OCP  Trip Coil Disconnected
19‐10‐18 10:54 149 OCP  Panel Trip Request ‐ Denied
19‐10‐18 10:54 926      Trip Coil Disconnected
19‐10‐18 10:54 643 OCP  Capacitor Disconnected
19‐10‐18 10:54 637 OCP  Panel Trip Request ‐ Denied
19‐10‐18 10:54 730 OCP  Panel Close Request
19‐10‐18 10:54 406      Close Coil Connect
19‐10‐18 10:54 215 OCP  Close Coil Disconnected
19‐10‐18 10:54 209 OCP  Panel Close Request ‐ Denied
19‐10‐18 10:54 760 OCP  Close Coil Disconnected
19‐10‐18 10:54 755 OCP  Panel Close Request ‐ Denied
19‐10‐18 10:54 508 OCP  Close Coil Disconnected
19‐10‐18 10:54 501 OCP  Panel Close Request ‐ Denied
19‐10‐18 10:54 991      Close Coil Disconnected
19‐10‐18 10:54 121      Lockout
19‐10‐18 10:54 91 OCP  Panel Trip Request
19‐10‐18 10:52 888      Switchgear Serial Number 700612
19‐10‐18 10:52 887      U Series Switch
19‐10‐18 10:52 764      Static IP 10.1.1.2 is active
19‐10‐18 10:52 60      Source Supply On
19‐10‐18 10:52 838 OCP  Operator control panel door opened
19‐10‐18 10:52 595      Cubicle Serial Number 851445
Protection and Communications Module Serial Number 
19‐10‐18 10:52 595      4596
19‐10‐18 10:52 595      U‐Boot Version 2013.01.01r25766
19‐10‐18 10:52 594      DSP00‐08.03r29405
19‐10‐18 10:52 594      Application Version A50‐05.04r29672
19‐10‐18 10:52 171      Switch Disconnected
19‐10‐18 10:52 168      Protection Group A Active
19‐10‐18 10:52 860      Maintenance Required
19‐10‐18 10:52 604      SCEM Type SCEM11
19‐10‐18 10:52 602      SCEM Type Unknown
19‐10‐18 10:52 600      Auxiliary Supply Normal
19‐10‐18 10:52 598      Switch Closed
19‐10‐18 10:52 596      Battery Normal
19‐10‐18 10:52 596      Radio Supply Off
19‐10‐18 10:52 594      Normal Power Mode
19‐10‐18 10:52 590      Power Up
19‐10‐18 10:41 124      Power Down
19‐10‐18 10:41 542      Trip Coil Disconnected
19‐10‐18 10:41 526      Close Coil Disconnected
19‐10‐18 10:39 815      Close Coil Connect
19‐10‐18 10:39 815      Trip Coil Connected
19‐10‐18 10:39 737      Trip Coil Disconnected
19‐10‐18 10:39 721      Close Coil Disconnected
19‐10‐18 10:35 839 WSOS WSOS Close Request
19‐10‐18 10:35 854      Lockout
19‐10‐18 10:35 822 WSOS WSOS Trip Request
19‐10‐18 10:32 202 WSOS Sync Check (J) Close Retry Off
19‐10‐18 10:32 202 WSOS Sync Check (J) Close Retry Period 300 seconds
19‐10‐18 10:32 196 WSOS Phase Fault Trip Mode On ‐ Denied
19‐10‐18 10:32 177 WSOS Normal Voltage Close Off ‐ Denied
19‐10‐18 10:32 117 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 112 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 809 WSOS Sync Check (I) Close Retry Off
19‐10‐18 10:32 809 WSOS Sync Check (I) Close Retry Period 300 seconds
19‐10‐18 10:32 791 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 791 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 779 WSOS Normal Voltage Close Off ‐ Denied
19‐10‐18 10:32 698 WSOS Phase Fault Trip Mode On ‐ Denied
19‐10‐18 10:32 436 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 430 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 184 WSOS Phase Fault Trip Mode On ‐ Denied
19‐10‐18 10:32 144 WSOS Normal Voltage Close Off ‐ Denied
19‐10‐18 10:32 88 WSOS Sync Check (H) Close Retry Period 300 seconds
19‐10‐18 10:32 76 WSOS Sync Check (H) Close Retry Off
19‐10‐18 10:32 68 WSOS Sync Check (G) Close Retry Period 300 seconds
19‐10‐18 10:32 63 WSOS Sync Check (G) Close Retry Off
19‐10‐18 10:32 23 WSOS Phase Fault Trip Mode On ‐ Denied
19‐10‐18 10:32 906 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 900 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 871 WSOS Normal Voltage Close Off ‐ Denied
19‐10‐18 10:32 585 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 572 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 310 WSOS Normal Voltage Close Off ‐ Denied
19‐10‐18 10:32 305 WSOS Sync Check (F) Close Retry Off
19‐10‐18 10:32 299 WSOS Sync Check (F) Close Retry Period 300 seconds
19‐10‐18 10:32 242 WSOS Phase Fault Trip Mode On ‐ Denied
19‐10‐18 10:32 209 WSOS Sync Check (E) Close Retry Off
19‐10‐18 10:32 131 WSOS Sync Check (E) Close Retry Period 300 seconds
19‐10‐18 10:32 131 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 122 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 90 WSOS Phase Fault Trip Mode On ‐ Denied
19‐10‐18 10:32 961 WSOS Normal Voltage Close Off ‐ Denied
19‐10‐18 10:32 701 WSOS Sync Check (D) Close Retry Period 300 seconds
19‐10‐18 10:32 701 WSOS Sync Check (D) Close Retry Off
19‐10‐18 10:32 695 WSOS Normal Voltage Close Off ‐ Denied
19‐10‐18 10:32 614 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 601 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 396 WSOS Phase Fault Trip Mode On ‐ Denied
19‐10‐18 10:32 109 WSOS Phase Fault Trip Mode On ‐ Denied
19‐10‐18 10:32 109 WSOS Sync Check (C) Close Retry Period 300 seconds
19‐10‐18 10:32 103 WSOS Sync Check (C) Close Retry Off
19‐10‐18 10:32 702 WSOS Normal Voltage Close Off ‐ Denied
19‐10‐18 10:32 595 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 589 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 506 WSOS Sync Check (B) Close Retry Off
19‐10‐18 10:32 500 WSOS Sync Check (B) Close Retry Period 300 seconds
19‐10‐18 10:32 390 WSOS Normal Voltage Close Off ‐ Denied
19‐10‐18 10:32 366 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 358 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 199 WSOS Phase Fault Trip Mode On ‐ Denied
Protection Group (A) Sensitive Ground Fault Trips to 
19‐10‐18 10:32 144 WSOS Lockout 3
Negative Phase Sequence Trip 3 (A) Reclose Time 2.00 
19‐10‐18 10:32 64 WSOS seconds
19‐10‐18 10:32 34 WSOS SGF Trip 3 (A) Reclose Time 2.00 seconds
19‐10‐18 10:32 29 WSOS Ground Trip 3 (A) Minimum Time 0.19 seconds

19‐10‐18 10:32 26 WSOS Ground Trip 3 (A) Instantaneous Multiplier 4.0 times


19‐10‐18 10:32 23 WSOS Ground Trip 3 (A) Very Inverse IEC255 Curve
19‐10‐18 10:32 21 WSOS Ground Trip 3 (A) Additional Time 0.05 seconds
19‐10‐18 10:32 15 WSOS Ground Trip 3 (A) Time Multiplier 0.50 times
19‐10‐18 10:32 14 WSOS High Voltage Check Time 20 seconds ‐ Denied

19‐10‐18 10:32 12 WSOS Auto‐Changeover High Voltage Dead Time 10 seconds

19‐10‐18 10:32 11 WSOS Auto‐Changeover High Voltage Live Time 10 seconds


19‐10‐18 10:32 991 WSOS This Device SLAVE ‐ Denied
19‐10‐18 10:32 989 WSOS Ground Trip 1 (A) Very Inverse IEC255 Curve
19‐10‐18 10:32 987 WSOS Ground Trip 1 (A) Additional Time 0.05 seconds

19‐10‐18 10:32 984 WSOS Ground Trip 1 (A) Instantaneous Multiplier 4.0 times


19‐10‐18 10:32 981 WSOS Ground Trip 1 (A) Minimum Time 0.19 seconds
19‐10‐18 10:32 974 WSOS Ground Trip 1 (A) Time Multiplier 0.50 times
19‐10‐18 10:32 962 WSOS One Way ‐ Denied
19‐10‐18 10:32 886 WSOS Phase Trip 1 (A) Time Multiplier 0.12 times
19‐10‐18 10:32 883 WSOS Phase Trip 1 (A) Additional Time 0.04 seconds
19‐10‐18 10:32 882 WSOS Phase Trip 1 (A) Extremely Inverse IEC255 Curve

19‐10‐18 10:32 879 WSOS Phase Trip 1 (A) Instantaneous Multiplier 5.0 times


19‐10‐18 10:32 873 WSOS Phase Trip 1 (A) Minimum Time 0.11 seconds
19‐10‐18 10:32 873 WSOS Sync Check (A) Close Retry Period 300 seconds
19‐10‐18 10:32 869 WSOS Sync Check (A) Close Retry Off
19‐10‐18 10:32 806 WSOS Protection Group (A) Phase Setting Current 30 A
19‐10‐18 10:32 792 WSOS Phase Trip 2 (A) Time Multiplier 0.12 times

19‐10‐18 10:32 788 WSOS Phase Trip 2 (A) Instantaneous Multiplier 5.0 times


19‐10‐18 10:32 785 WSOS Phase Trip 2 (A) Minimum Time 0.11 seconds
19‐10‐18 10:32 782 WSOS Phase Trip 2 (A) Additional Time 0.04 seconds
19‐10‐18 10:32 778 WSOS Phase Trip 2 (A) Extremely Inverse IEC255 Curve
19‐10‐18 10:32 774 WSOS Phase Trip 3 (A) Reclose Time 2.00 seconds
19‐10‐18 10:32 772 WSOS Protection Group (A) Ground Setting Current 10 A

19‐10‐18 10:32 758 WSOS Auto‐Changeover Operation Warning Time 10 seconds

19‐10‐18 10:32 734 WSOS Ground Trip 2 (A) Instantaneous Multiplier 4.0 times


19‐10‐18 10:32 734 WSOS Ground Trip 2 (A) Minimum Time 0.19 seconds
19‐10‐18 10:32 706 WSOS Ground Trip 2 (A) Very Inverse IEC255 Curve
19‐10‐18 10:32 704 WSOS Ground Trip 2 (A) Additional Time 0.05 seconds
19‐10‐18 10:32 704 WSOS Tie ‐ Denied
19‐10‐18 10:32 696 WSOS Ground Trip 2 (A) Time Multiplier 0.50 times
Negative Phase Sequence Trip 2 (A) Reclose Time 2.00 
19‐10‐18 10:32 657 WSOS seconds
19‐10‐18 10:32 648 WSOS Phase Trip 3 (A) Additional Time 0.04 seconds
19‐10‐18 10:32 648 WSOS Phase Trip 3 (A) Extremely Inverse IEC255 Curve

19‐10‐18 10:32 643 WSOS Phase Trip 3 (A) Instantaneous Multiplier 5.0 times


19‐10‐18 10:32 643 WSOS Auto‐Restore Off ‐ Denied
19‐10‐18 10:32 641 WSOS Phase Trip 3 (A) Minimum Time 0.11 seconds
19‐10‐18 10:32 636 WSOS Phase Trip 3 (A) Time Multiplier 0.12 times
19‐10‐18 10:32 630 WSOS Protection Group (A) Maximum Time 2.0 seconds
19‐10‐18 10:32 488 WSOS SGF Trip 2 (A) Reclose Time 2.00 seconds
19‐10‐18 10:32 482 WSOS Phase Trip 2 (A) Reclose Time 2.00 seconds
19‐10‐18 10:32 451 WSOS Normal Voltage Close Off ‐ Denied
19‐10‐18 10:32 439 WSOS Phase Fault Trip Mode On ‐ Denied
19‐10‐18 10:32 419 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 413 WSOS Trip Mode On ‐ Denied
19‐10‐18 10:32 402 WSOS Phase Trip 1 (A) Reclose Time 2.00 seconds
19‐10‐18 10:18 400 WSOS Protection Group (A) Trips to Lockout 3
19‐10‐18 10:17 64      Battery Test Off
19‐10‐18 10:17 64      Battery Test Capacity OK
19‐10‐18 10:17 64      Battery Test End Voltage 25.23 V
19‐10‐18 10:17 64      Battery Test Middle Voltage 24.39 V
19‐10‐18 10:17 64      Battery Test Beginning Voltage 26.6 V
19‐10‐18 10:16 948      Battery Test Performing Test...
19‐10‐18 10:16 943 WSOS Battery Test Start
19‐10‐18 10:16 671 WSOS Battery Test Automatic Test Status On
19‐10‐18 10:15 0 WSOS 19‐10‐18 10:15
17‐10‐18 12:29 867 WSOS Sensitive Ground Fault Protection Alarm Off
17‐10‐18 12:29 589 WSOS Sensitive Ground Fault Protection Alarm On
17‐10‐18 12:29 258 WSOS Sensitive Ground Fault Protection On
17‐10‐18 12:29 203 WSOS Ground Protection On
17‐10‐18 12:29 241 WSOS Automatic Reclose On
17‐10‐18 12:28 184 WSOS WSOS Close Request
17‐10‐18 12:28 148      Lockout
17‐10‐18 12:28 119 WSOS WSOS Trip Request
17‐10‐18 12:27 160      Close Coil Connect
17‐10‐18 12:27 160      Trip Coil Connected
17‐10‐18 12:20 138      Close Coil Disconnected
17‐10‐18 12:20 138      Trip Coil Disconnected
17‐10‐18 12:20 491      U Series Switch
17‐10‐18 12:20 89      SCEM Type SCEM11
17‐10‐18 12:20 721      SCEM Type Unknown
17‐10‐18 12:20 37      Source Supply On
17‐10‐18 12:20 92      Switch Closed
17‐10‐18 12:19 251      Source Supply Off
17‐10‐18 12:19 606      Close Coil Connect
17‐10‐18 12:19 606      Trip Coil Connected
17‐10‐18 12:19 600      Maintenance Required
17‐10‐18 12:19 599      Switch Disconnected
17‐10‐18 12:12 467      Close Coil Disconnected
17‐10‐18 12:12 467      Trip Coil Disconnected
17‐10‐18 12:12 440      Switchgear Serial Number 700612
17‐10‐18 12:12 437      U Series Switch
17‐10‐18 12:12 763      Static IP 10.1.1.2 is active
17‐10‐18 12:12 70      Source Supply On
17‐10‐18 12:12 797 OCP  Operator control panel door opened
17‐10‐18 12:12 608      Cubicle Serial Number 851445
Protection and Communications Module Serial Number 
17‐10‐18 12:12 607      4596
17‐10‐18 12:12 607      U‐Boot Version 2013.01.01r25766
17‐10‐18 12:12 607      DSP00‐08.03r29405
17‐10‐18 12:12 607      Application Version A50‐05.04r29672
17‐10‐18 12:12 174      Switch Disconnected
17‐10‐18 12:12 174      Protection Group A Active
17‐10‐18 12:12 869      Maintenance Required
17‐10‐18 12:12 615      SCEM Type SCEM11
17‐10‐18 12:12 615      SCEM Type Unknown
17‐10‐18 12:12 612      Auxiliary Supply Normal
17‐10‐18 12:12 610      Switch Closed
17‐10‐18 12:12 609      Radio Supply Off
17‐10‐18 12:12 605      Normal Power Mode
17‐10‐18 12:12 604      Battery Normal
17‐10‐18 12:12 602      Power Up
16‐10‐18 22:14 901      Power Down
16‐10‐18 22:13 154      Close Coil Disconnected
16‐10‐18 22:13 154      Trip Coil Disconnected
16‐10‐18 22:13 391      Switchgear Serial Number 700612
16‐10‐18 22:13 388      U Series Switch
16‐10‐18 22:13 751      Static IP 10.1.1.2 is active
16‐10‐18 22:13 60      Source Supply On
16‐10‐18 22:13 749 OCP  Operator control panel door opened
16‐10‐18 22:13 614      Cubicle Serial Number 851445
Protection and Communications Module Serial Number 
16‐10‐18 22:13 613      4596
16‐10‐18 22:13 613      U‐Boot Version 2013.01.01r25766
16‐10‐18 22:13 613      DSP00‐08.03r29405
16‐10‐18 22:13 613      Application Version A50‐05.04r29672
16‐10‐18 22:13 171      Switch Disconnected
16‐10‐18 22:13 171      Protection Group A Active
16‐10‐18 22:13 860      Maintenance Required
16‐10‐18 22:13 620      SCEM Type SCEM11
16‐10‐18 22:13 619      SCEM Type Unknown
16‐10‐18 22:13 618      Auxiliary Supply Failure
16‐10‐18 22:13 617      Switch Closed
16‐10‐18 22:13 615      Battery Normal
16‐10‐18 22:13 615      Radio Supply Off
16‐10‐18 22:13 611      Normal Power Mode
16‐10‐18 22:13 609      Power Up
03‐10‐18 21:25 765      Power Down
03‐10‐18 21:23 907 WSOS New SCEM Data
03‐10‐18 21:22 156 WSOS Display Phase To Phase Voltage
03‐10‐18 21:22 813      Source Supply Off
03‐10‐18 21:22 813      Ci Dead
03‐10‐18 21:22 948      Bi Dead
03‐10‐18 21:22 930      Measuring Frequency On Bushing Ci
03‐10‐18 21:22 357      Ai Dead
03‐10‐18 21:22 330      Measuring Frequency On Bushing Bi
03‐10‐18 21:22 314 WSOS Display Phase To Ground Voltage
03‐10‐18 21:22 69      Source Supply On
03‐10‐18 21:21 857      Switchgear Serial Number 182850
03‐10‐18 21:21 854      U Series Switch
03‐10‐18 21:21 738      Static IP 10.1.1.2 is active
03‐10‐18 21:21 819 OCP  Operator control panel door opened
03‐10‐18 21:21 621      Cubicle Serial Number 851445
Protection and Communications Module Serial Number 
03‐10‐18 21:21 620      4596
03‐10‐18 21:21 620      U‐Boot Version 2013.01.01r25766
03‐10‐18 21:21 620      DSP00‐08.03r29405
03‐10‐18 21:21 620      Application Version A50‐05.04r29672
03‐10‐18 21:21 180      Switch Disconnected
03‐10‐18 21:21 180      Protection Group A Active
03‐10‐18 21:21 869      Maintenance Required
03‐10‐18 21:21 626      SCEM Type SCEM11
03‐10‐18 21:21 626      SCEM Type Unknown
03‐10‐18 21:21 625      Auxiliary Supply Failure
03‐10‐18 21:21 623      Switch Closed
03‐10‐18 21:21 622      Battery Normal
03‐10‐18 21:21 622      Radio Supply Off
03‐10‐18 21:21 618      Normal Power Mode
03‐10‐18 21:21 615      Power Up
03‐10‐18 21:17 250      Power Down
03‐10‐18 21:17 402      Maintenance Required
03‐10‐18 21:17 401      Switch Disconnected
03‐10‐18 21:15 50 WSOS Cubicle Serial Number 851445
03‐10‐18 21:15 0 WSOS 03‐10‐18 21:15
03‐10‐18 21:14 110      Normal Power Mode
03‐10‐18 21:14 290      Static IP 10.1.1.2 is active
03‐10‐18 21:14 132      Battery Normal
03‐10‐18 21:14 131      Switchgear Serial Number 182850
03‐10‐18 21:14 131      U Series Switch
03‐10‐18 21:14 131      Auxiliary Supply Normal
03‐10‐18 21:14 131      SCEM Type SCEM11
03‐10‐18 21:14 131      Switch Closed
03‐10‐18 21:14 111      Cubicle Serial Number 0
Protection and Communications Module Serial Number 
03‐10‐18 21:14 111      4596
03‐10‐18 21:14 111      U‐Boot Version 2013.01.01r25766
03‐10‐18 21:14 111      DSP00‐08.03r29405
03‐10‐18 21:14 111      Application Version A50‐05.04r29672
03‐10‐18 21:14 318 OCP  Operator control panel door opened
03‐10‐18 21:14 302      Switch Disconnected
03‐10‐18 21:14 291      Protection Group A Active
03‐10‐18 21:14 248 PTCL DNP3 Standard ACR 2
03‐10‐18 21:14 200      Maintenance Required
03‐10‐18 21:14 106      Power Up