Documente Academic
Documente Profesional
Documente Cultură
Doctorate of Philosophy
Submitted by
Soumitri Jena
Enrol. No. 15914014
Dr.Bhavesh Bhalja
January, 2016
Abstract
The busbar is one of the most critical parts of the power system, where many trans-
mission lines converge. Busbar faults are seldom but the occurrence of it can lead
to extensive damage and large-scale blackout. The consequences of unprotected bus
fault are found to be very extreme. Reliable operation during bus fault is essential for
generator stability. Unwanted tripping, which may lead to longer supply interruptions
should be avoided. Busbars mainly lie in the second zone protection in distance pro-
tection schemes, so a busbar fault clearance is relatively slow. Time graded distance
protection is not an ideal choice for the purpose. System protections may not be ad-
equate and a dedicated busbar protection scheme is required. It is true that risk of a
fault occurring on a busbar is low, but it can not be ignored completely.
1 Introduction 1
1.1 Busbar Faults and Protection Requirements . . . . . . . . . . . . . . . 1
1.2 Busbar Protection Schemes . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2.1 Directional Comparison . . . . . . . . . . . . . . . . . . . . . . 2
1.2.1.1 Series Trip Scheme: . . . . . . . . . . . . . . . . . . . . 2
1.2.1.2 Directional Blocking Scheme: . . . . . . . . . . . . . . 3
1.2.1.3 Directional Comparison Scheme: . . . . . . . . . . . . 3
1.2.2 Differential Protection technique . . . . . . . . . . . . . . . . . 3
1.2.2.1 Circulating Current Differential Protection: . . . . . . 4
1.2.2.2 Biased Percentage Differential Protection: . . . . . . . 4
1.2.2.3 High Impedance voltage Scheme: . . . . . . . . . . . . 5
1.2.2.4 Protection using linear couplers: . . . . . . . . . . . . 6
1.3 Techniques Used in Commercial Relays . . . . . . . . . . . . . . . . . . 7
1.3.1 Microprocessor based protection . . . . . . . . . . . . . . . . . . 7
1.3.2 Digital Differential Protection . . . . . . . . . . . . . . . . . . . 8
1.3.2.1 Distributed Busbar Protection . . . . . . . . . . . . . . 8
1.3.2.2 Centralized Busbar Protection . . . . . . . . . . . . . . 8
1.3.3 Busbar protection during CT saturation . . . . . . . . . . . . . 9
1.3.4 Neural Network based Busbar Protection . . . . . . . . . . . . . 9
1.3.5 Travelling-Wave Based Busbar Protection . . . . . . . . . . . . 10
1.3.6 Wavelet Transform Based Busbar Protection Scheme . . . . . . 10
1.4 Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
i
List of Figures
ii
Chapter 1
Introduction
Though a critical point in the complex power system, busbar protection is often over-
looked. A fault on the busbar may result in tripping of all the lines connected to it,
resulting a widespread system failure. Thus, quick and reliable operation of breakers
is required from the busbar protection schemes. This chapter presents a bibliographic
and comprehensive review of different relaying schemes in the field of busbar protection.
In the event of an internal fault on busbar, tripping of all the connected lines is
required. Also unwanted tripping is avoided because they may lead to large scale sys-
tem interruptions. Busbar faults are found to be very rare (8%) when compared to
line faults which are about (60%) of the total faults. It has been observed that among
busbar faults single line to ground faults are 67%, 15% are double line to ground faults
and 18% are triple line to ground faults [3].
1
Faults on the busbar are mainly because of:
• Insulation failure.
External Internal
2
fault, contacts R1 and R2 close simultaneously and energizes the auxiliary relay and
trip both the circuit breakers.
3
culating current differential protection, biased percentage differential protection, high
impedance voltage scheme and protection using linear couplers.
The restraining current is fed to the unidirectional restraining coils. The current
through the operating coil is the vector sum of currents whereas the current through
the restraining coil is the scalar sum of currents.
4
Figure 1.6: Percentage bias characteristics
During normal operating conditions the operating current is close to zero and the
restraining current is a finite value in proportion to the load current. During internal
bus fault conditions there is an increase in both operating and restraining current. So
IOP /IRT point moves from restraining region to operating region. This causes the relay
to trip. The relay characteristics are adjustable owing to mismatch of CTs. However,
this scheme avoids substantial CT saturation errors and may maloperate for close-in
external faults.
The full wave rectifier circuit adds considerable resistance to the circuit. The bridge
circuit is tuned to 50 Hz fundamental frequency, So the circuit is immune to DC
offset values. IEEE standards [4] are the guidelines for selecting the relay operation.
The disadvantage with this scheme is that it slows the relaying processes, but this is
countered somewhat by the addition of a high speed overcurrent(OC) unit in series with
a voltage limiting metal oxide resistor, which is connected in the circuit to limit very
high magnitude fault currents across the bridge terminal. Thus, the overcurrent unit
trips for high magnitude internal bus faults.The relative magnitudes of the voltages
across the differential junction classifies the fault as internal or external one and a
minimum pickup current distinguishes between internal and external fault.
5
Figure 1.7: High Impedance differential protection
For an internal bus fault, all the line currents are directed to the faulted busbar and
secondary voltages of the linear couplers add together and impressed across the relay
unit. This provides very high-speed protection which is free from CT saturation er-
rors. However, installation of dedicated linear couplers only for bus protections creates
economical constraints.
6
1.3 Techniques Used in Commercial Relays
Digital relays are most economical and effective means for busbar protection. These
relays are most economical in terms of maintenance cost and fewer hardware alterations
for new system changes [5]. The first commissioned digital busbar system has taken a
lot of alterations. Now more than 500 types of systems are used world wide for different
type of bus configurations. The commercialization of these relays has encouraged
innovative designs to provide security, speed and sensitivity. The fast fault clearing
time has also ensured greater generator stability [6]. However selectivity is a major
issue still now. The last two decades have seen remarkable success in microprocessor
based relaying scheme. Combination of microprocessor, microcontroller, digital signal
processors and artificial intelligence techniques have taken the level a way higher.
Digital output system contains a digital to analog converter. Storage unit contains
Random Access Memory(RAM), Read Only Memory(ROM) and hard disc storage for
temporary and permanent storage of data. Microprocessor unit takes the trip decision
according to the relay logic.
Substation Busbar
RAM
Microcontroller
Relay
Digital output system contains a digital to analog converter. Storage unit contains
Random Access Memory(RAM), Read Only Memory(ROM) and hard disc storage for
7
temporary and permanent storage of data. Microprocessor unit takes the trip decision
according to the relay logic.
8
1.3.3 Busbar protection during CT saturation
Because of iron cores are used in CTs for protection of busbar, most of the CTs are
prone to saturation errors. The main function of a protective CT is to faithfully amplify
the CT secondary current in case of normal as well as faulty conditions. The magnitude
of CT saturation depends on the level of fault current, residual flux, magnitude of DC
component and CT secondary burden [14].
Stability during saturation is one of the main requirements for busbar protection.
Different researchers have proposed different methods for this purpose. Sachdev et
al. [15] proposed a technique based on positive and negative sequence impedance for
deciding internal and external fault. Their method is also stable during CT saturation,
but it requires voltage information, which is not available always. Eissa [16] proposed
a scheme based on phase comparison. It gives improved results than previously used
magnitude comparison schemes, but delays relay operation. Kang et al. [17] proposed
an algorithm by compensating current to distorted CT secondary currents. However,
this method is not suitable for severe CT saturation cases.
Current signals from the CT units are given to ADC through Signal conditioning
(SC) and Anti Aliasing Filter (AAF) block. AAF is a low pass filter and removes high
frequency signals. These current signals are then given as input to ANN input neurons.
The structure of neurons is decided based on the relay logics. The output of neurons
is given to a decision logic block, which decides the tripping signal.
9
AAF
Power System Network CTs SC ANN Decision Logic
ADC
Recently the number of ANN based algorithms reported for busbar protection are
increasing. Feser et al.[18] proposed an ANN based busbar protection scheme by pro-
cessing large no of data signals. However, the scheme maloperates due to CT saturation
errors. Zadeh et al. [19] proposed a classification algorithm based on Neuro-Fuzzy clas-
sifier to decide the fault zone for busbar faults. However large training sets, tedious
training process and large number of neurons make these schemes ineffective.
Wang et al.[20] were the first to purpose a busbar zone identification scheme based
on polarities of transient current waves. Jiang et al. [21] then proposed a transient
based protection technique which depends on the energy spectrum of fault transients.
Eissa [2] proposed a directional busbar protection scheme by extracting features from
pre fault and post fault voltage and current signals. However, faults with inception an-
gle close to zero degree do not produce sufficient travelling waves. Close-in faults which
generate very high frequency travelling waves falls outside the boundary of conventional
CVTs. Thus limiting the applicability of these schemes.
10
The wavelet packet then decomposes the differential current signal into detail ap-
proximate coefficients. Then the relay logic block takes the trip decision.
1.4 Conclusion
An attempt to review different busbar protection techniques and existing schemes is
made in this chapter. A bibliographic survey of relevant research work and history
of busbar protection are presented in this chapter. A comparative summary and an
attempt to find out the optimum technique is also made. Though very sophisticated
busbar techniques are available, there also exists a wide scope of improvement.
11
Chapter 2
12
NN1
Va , I a
NN2
Int.
NN1 Output Neuron
Vb , I b
Ext.
NN2 Output Neuron
NN1
Vc, Ic
NN2
The magnitude of three phase voltages (Va , Vb , Vc ) and currents (Ia , Ib , Ic ) are mea-
sured from CTs and PTs. These signals are then sampled and digitalized using analog
to digital converters. The data are sent to the ANN pattern recogniser. The recogniser
verifies the data and confirms the fault, if exists and then issues a trip signal. The
advantage of ANN based relays is that they can learn different aspects related to fault
type and fault conditions.
13
In general the neural network architecture consists of several layers i.e an input
layer, an output layer and possibly number of hidden layers. The number of hidden
layers are most probably limited to two in most of the cases to improve the execution
time.
Each node receives a set of weighted inputs and processes to give an ouput depend-
ing on the activation function. Different sigmoidal functions are used very frequently.
1
f (x) = (2.1)
1 + e−x
The node output then travels to the next node and then so on. In a feed forward
network the outputs travel in forward direction only.
The activation function and the number of layers are decided prior to the training
process. The relationship between the input and output neurons can be completely
represented by adjusting the weights in the training process.
Where tmi is the desired output and omi is actual output from the output of the neurons.
The error E is the summation of all the individual neurons.
X
E= Em (2.3)
m
This error is minimised by adjusting the weights in the negative direction of gradient.
∂E
∆Wij = −η (2.4)
∂Wij
This processes of calculation the error and updating the weights is processed from
the output to input neurons i.e in the backward direction. The weights are updated
14
until the error exceed a predefined threshold.
Neural networks have the inherent benefit to adjusts their weights to the changes
in the surrounding environment. A neural network trained to work in a particular
environment may work efficiently to smaller changes in the environment. The adaptive
architecture of neural networks makes it suitable for pattern classification and decision
making.
However, the application of ANN based modules to real world problem is a major
issue. The real time data consists of thousands of inputs. The training is non-linear
and requires a huge amount of dataset. There exist no analytic methods to validate
the ANN outputs, only extensive training can validate the performance. The lack of
transparency puts ANN based schemes in backtrack.
When a fault occurs on the busbar the direction of initial travelling waves on
all the lines connected to the busbar is considered to be positive. When a fault
occurs in one of the lines the direction of initial travelling waves in all of the lines
are found positive, whereas initial travelling waves in the faulty line are found to
be negative [23].
L2
R2
L1
R1
L3
R3
A simple busbar arrangement is shown in the figure. R1, R2 and R3 are corresponding
relays of line L1, L2 and L3. When a fault occurs on the line L1 travelling waves
are generated in both the directions from the fault point. Reflection and refraction
coefficients appear along the line where impedances are discontinuous i.e busbar and
15
other lines. Considering R1 as a zero reference point, then along the positive direction
at a point x the transient voltage and current waveforms can be represented by
x x
∆v = v + (t − ) + v − (t + ) (2.5)
v v
1 + x x
∆i = [v (t − ) + u− (t + )] (2.6)
zc v v
q
1
Where v = √LC and zc = CL represents the velocity and current of the travelling
wave. u+ is the positive travelling wave and u− is the negative travelling wave. The
voltage of positive and negative travelling wave can be obtained by solving (2.1) and
(2.2).
∆v + zc ∆i
v+ = (2.7)
2
∆v − zc ∆i
v− = (2.8)
2
2. When the busbar experiences a fault on itself, all the relays experience a positive
initial travelling wave and negative direction travelling wave does not appear.
3. For an internal fault, initial travelling waves are experienced at the relay locations
at the same time whereas for an external fault the relays experience travelling
waves at different point of time.
The Wavelet Transforms (WT) of a time dependent signal f (t) is the set of coeffi-
cients W Ta,b . These coefficients depend on the similarity between the signal f (t) and
set of functions ψa,b (t), these functions are derived from the mother wavelet ψ(t) as
follows !
1 t−b
ψa,b (t) = 1/2 ψ (2.9)
|a| a
Where a and b are scaling and time-shift constants. The coefficient of WT can be
defined as Z ∞
W Ta,b = hψa,b (t), f (t)i = f (t).ψa,b (t)dt (2.10)
−∞
16
In busbar protection, the fault signals are decomposed into different frequency band
in time domain. These decomposed signals are used to generate precise information
about the fault. The fault signals are decomposed into successive approximate and
detailed signals. The information lost between two successive approximate signals is
obtained from the detailed signal. In the next step, two new signals are generated from
each of the approximate and detailed signals. Thus, a complete binary tree is formed.
The approximate signals are result of output of the Low-pass filter (LPF) and the
detailed signals are the output obtained from the High-pass filter (HPF). In the next
level, these signals are again given to LPF and HPF. The decomposition is proceeded
till the desired level of decomposition is not achieved [24].
Fault Signal
A (0)
A (1) D (1)
AAA (3) DAA (3) ADA (3) DDA (3) AAD (3) DAD (3) ADD (3) DDD (3)
Figure 2.4 shows decomposition of a fault signal obtained after the CT secondary. A
sampling frequency f (s) is decided for the wavelet packet. In each level the signal is di-
vided into two frequency intervals [0,f (s)/2] and [f (s)/2, f (s)]. So the end of level 3 the
signal is decomposed into the band of [0,f (s)/8],[f (s)/8,2f (s)/8]. . . . . . ,[7f (s)/8, f (s)].
The average value of the decomposed current signal gives the energy level in each fre-
quency band.
The features extracted from the energy spectrum from different samples of internal
and external faults are used to develop the relay logic. As the trip logic is based
on frequency changes rather than magnitude changes, these relays deliver satisfactory
performance in case of CT saturation errors.
17
Figure 2.6: Wavelet Decomposition of a Fault signal [1]
Several algorithms have been proposed in the literature for CT saturation detec-
tion. These techniques can be roughly classified into two groups depending on the input
current i.e 1) The CT secondary current 2) The differential current. Algorithms used
in the group (1) detect CT saturation based on the unusual CT secondary waveforms
that differ from the CT secondary waveforms during normal operating conditions. The
algorithms used in the group (2) detect CT saturation by the fact that, during the
inception of a fault, there is a low magnitude of differential current which is followed
18
by a large differential current because one of the CTs has saturated.
One of the earlier reported methods [25] depend on the calculation of the core flux
in the case of saturated CTs and compensate it using compensating currents.With the
help of magnetising curve, this method successfully determines the secondary current
required, even when the CT is saturated.
Some of the methods, assume the fact that if CT secondary waveform is perfectly
sinusoidal then the mean should be zero, which is not the case when the CT has sat-
urated its core. The summation of instantaneous currents over cycle and the second
order derivatives are zero for a perfectly sinusoidal curve, which is not true for a satu-
rated CT secondary waveform.
A number of techniques based on Artificial Intelligence [27] [28] have been reported
in the literature to detect CT saturation. The basic idea is to train a network with a
large number of discrete saturated CT secondary waveforms and test with a large num-
ber of samples. However, because of non-transparency and tedious training processes,
these methods are not being practically implemented.
19
Figure 2.8: Secondary saturated waveforms for a 400:1 CT and zero crossing instants
In steady state operation of the power system synchronism between nominal fre-
quency and nominal voltage between the sending and receiving ends keep the balance
between generated and consumed active or reactive power. However, because of the
above listed methods if there is a sudden change in electrical power whereas the me-
chanical input to the generator remains constant. The electrical power output from a
generator (Pg ) is given by the equation
Eg El
Pg = sinδ (2.11)
X
Where:
20
Eg = Internal voltage generated by the generator.
El = Voltage at the receiving end load.
X= Reactance between the generator and load.
δ=The angle by which Eg leads load voltage.
Accelerating power in a generator can be given by the formula
Pa = Pm − Pg (2.12)
Where:
Pm = Mechanical power given to the generator unit.
Pg = Electrical power generated by the generator unit.
The mechanical input given to the generator unit must be equal to the average
electrical power output, in order to maintain equilibrium. In the case of a disturbance
in the system, one of the above parameters changes. In the case of faults the reactance
(X) between the source and the load or the load voltage (El ) or any combination
of both changes. When a generator trips or in the case of opening of a breaker the
reactance (X) changes. In these cases, the mechanical power input to the generator is
no longer equal to the electrical power output. This causes severe oscillations in the
rotor unit. Which leads to power swings.
G1 CB G2
Severe Fault
Relay
Power swings can cause the load impedance seen by the relay to fall within the
operating region of the relay. Hence unwanted tripping may lead to cascading outages
and complete blackout.
21
Pm
Pe
A Power Swing Block (PSB) is present in modern day relays. The main idea of
the PSB is to differentiate between Power swing and fault conditions. An Out of Step
Trip (OST) block is also present which differentiate between stable power swing and
unstable power swing. Corrective measures are taken after detection of the type of
power swing.
2.4 Conclusion
The busbar is a point of interconnection in the power system where different apparatus
are connected. Busbar is a vital element in view of stability and interconnectivity.
Faults can be on the busbar itself or be on different equipment connected. Though
faults on a busbar are rare, but the consequences are very severe. Therefore, a dedi-
cated busbar protection scheme should be employed for busbar protection. Faults on
the busbar must be clearly identified and cleared with minimum possible time. So It
is highly desirable to develop a fast and reliable busbar protection scheme. The pro-
22
tection should also be sustainable for CT saturation conditions. CT saturation should
not lead to misclassification of faults. CT saturation should be detected effectively.
An efficient busbar protection scheme should also discriminate between power swing
condition and fault conditions.
23
References
24
[14] B. Bhalja, R. Maheshwari, and N. G. Chothani, Protection and switchgear. Oxford
University Press, 2011.
[17] Y. Kang, U. Lim, and S. Kang, “Compensating algorithm suitable for use
with measurement-type current transformers for protection,” IEE Proceedings-
Generation, Transmission and Distribution, vol. 152, no. 6, pp. 880–890, 2005.
[19] H. Zadeh, “Fuzzy neuro approach to busbar protection,” in IEEE Power Engi-
neering Society General Meeting, pp. 1089–1093 Vol. 2, June 2005.
[20] G. Wang, H. Li, and X. Li, “A new numerical distributed busbar protection,” in
Eighth IEE International Conference on Developments in Power System Protec-
tion, vol. 1, pp. 387–390 Vol.1, April 2004.
[24] U. Parikh, B. Das, and R. Maheshwari, “Combined wavelet-svm technique for fault
zone detection in a series compensated transmission line,” IEEE Transactions on
Power Delivery, vol. 23, pp. 1789–1794, Oct 2008.
[25] Y. Kang, J. Park, S. Kang, A. Johns, and R. Aggarwal, “An algorithm for compen-
sating secondary currents of current transformers,” IEEE Transactions on Power
Delivery, vol. 12, pp. 116–124, Jan 1997.
25
[27] Y.-Y. Hong and P.-C. Chang-Chian, “Detection and correction of distorted cur-
rent transformer current using wavelet transform and artificial intelligence,” IET-
Generation, Transmission Distribution, vol. 2, pp. 566–575, July 2008.
[30] B. Su, X. Dong, Z. Bo, Y.-Z. Sun, B. Caunce, D. Tholomier, and A. Apostolov,
“Fast detector of symmetrical fault during power swing for distance relay,” in
IEEE Power Engineering Society General Meeting,, pp. 1836–1841 Vol. 2, June
2005.
26