Documente Academic
Documente Profesional
Documente Cultură
Dies are used to form the fitting by delivering blows to the fitting while rotating. The Checking the Swage
correct set of dies must be installed in the swager to reach a satisfactory result.
The figure below shows a set of dies installed in the swager. After the swaging process has been fin-
ished, the swage must be within given limits.
Figure 5: Changable Dies used in a Rotary Swager This can be done by using a Go/No-Go
Gauge as shown below, or by using a mi-
crometer.
A properly swaged fitting is shows in
Figure 8.
Figure 8: Sectional View of a swaged Fitting Figure 10: Hydraulical Test Rig
Proof Loading
After installation of the end fittings, the cable must be proof loaded to guarantee a
safe operation. The cable will be installed in a manual test rig as shown in Figure 9
or in a hydraulical operated test rig as in Figure 10. A certain load will then be ap-
plied to the cable.
A broken cable is shown in Figure 11. As you see, a properly swaged end fitting is
always stronger than the cable itself.
Figure 9: Manual Test Rig for Proof Loading
Movable Spring Cable Screw Figure 11: Broken Cable
Anchorage Balance Under Test Jack
Cable Clearances
To prevent cables from chafing/riding conditions certain clearances must be ob-
tained. In general, clearance to structural members such as pipes, ducts and elec-
trical conduit installations etc., shall not be less than the minimum specified in the
applicable manuals.
The permissible clearance of cables from other parts depends on type of cable and
part with categories 1, 2 or 3. (e.g. cat. 1: primary flight control cable)
Critical elements with regard to clearances are:
• Hydraulic lines
• Fuel and oil lines
• Bleed pneumatic ducts
• Electrical conduits and wires
• Instrument and oxygen lines
• High pressure lines
In certain cases engineering approves installation of nylon chafing strips. Limited
contact is acceptable. However, the degree of acceptable rubstrip contact is de-
fined by specification.
Cables routed through fairlead grommets may also have limited contact.
The degree of acceptable contact is defined by applicable specification.
Rubstrips are not acceptable for salvage without engineering approval.
Table 1: Control Cable Tension Chart relating to a given Tensiometer Safety Methods of Tensioning Devices
1/16 3/32 1/8 5/32 3/16 Cable Diameter (inch) Safeting Turnbuckels(Turnbarrels) using Lock Clips
(see “Figure 14: Lock Clip Application” on page 9)
Tensiometer Indication Cable Tension in pounds These days, turnbuckels and also other tensioning devices are usually safetied by
lock clips rather than safety wires. The following procedure explains the installation
12 16 21 12 20 30 pds of lock clips:
19 23 29 17 26 40 pds • Check that the end fittings are not rotated to far out and enough thread is en-
gaged.
25 30 36 22 32 50 pds • Check the turnbarrel and the end fittings groove before assembly for possible
obstructions which may prevent proper installation of locking clip.
31 36 43 26 37 60 pds
• Align slot in barrel with slot in cable end fitting.
36 42 50 30 42 70 pds • Insert straight end of clip into aligned slots and slide into place until hook loop
is over the hole in centre of the turnbarrel.
41 48 57 34 47 80 pds Both lock clips may be inserted in the same barrel hole or may be inserted in
opposite hole!
46 54 63 38 52 90 pds • Verify proper engagement of hook lip in barrel by application of slight pressure
in disengaging direction.
51 60 69 42 56 100 pds
Lock clips are removed by pulling the hook loop out of the turnbarrel hole with a
46 60 110 pds pair of pliers and sliding the straight end out of the slot.
50 64 120 pds Do not reuse lock clips after removal!
Use Riser No. 1 with 1/16, 3/32 and 1/8 inch cable
Figure 14: Lock Clip Application threads visible provided enough room is left on the shank for wrapping lock-
wire.
Straight End • Cut enough lockwire using the correct material and diameter as specified in
Hook Shoulder End Loop the maintenance manual.
• Follow the procedure as shown in the following figure.
• Cut away excessive wire.
Figure 15: Lockwiring Turnbuckles
Hook Loop
Hook Lip
Groove
Turnbuckle Body
Locking Pin
Cleaning
Occasionally, surface protective coating has to be removed from the cable to per- Cable Pulley
form a thorough check. Cable Segment
Remember the following points:
• Do not saturate control cables with cleaning solvent. Solvent penetration to
cable core destroys cable lubrication permitting corrosion and rapid wear.
• Always use an approved cleaning agent as specified in the manual to remove
the protective surface coating. Still, do not saturate the cables core.
• Unfavourable results can occur with misuse of cleaning solvents, Glycol de- Visual inspection should also be preformed to check for wires that may be frac-
tergents and high water pressure during maintenance of aircraft. tured but remain in lay of the cable and are not snagged sponged by the cloth.
• Never use metallic wool or solvent to clean cables. Metallic wools embed dis- A side effect is that cloth are also used to prevent injury to hands while running
similar metal particles which cause further corrosion. along the cable.
Any cable damage shall be individually evaluated!
Wear Tolerances
The following cable wear tolerances can be used as a guide for allowable wear tol-
erance on aircraft in service and at overhaul. There are different limits at mainte-
nance line check and at over haul inspection to use. However limits are given by
the applicable specification and regard to aircraft types in the Maintenance Manual
Chapter 20.
E.g. 7 x 19 cable that has three broken wires or less per inch per strand provided
that not more than six broken wires exist in one inch running length shall be con-
sidered serviceable.
7 x 7 cable that has two broken wires or less per strand per inch provided that no
more that three broken wires exist in one inch running length shall be considered
serviceable. Maximum number of broken wires shall not occur in any consecutive
inch of cable. If maximum number of wires in one inch of cable as noted above are
broken none would be allowed in next consecutive inch.
Critical fatigue area is working length of cable, therefore when broken wire ap-
pears in this area tension should be released and cable checked for defects.
Replace cable which is worn to point that material reduction at any cross section
is in excess of Area of six wires for 7 x 19 cable per inch or three wires for 7 x 7
cable per inch.
Lockclad Cable Damage Protection shall be applied using a clean brush or with a spray as specified in the
applicable manual.
Locklad cables should be replaced when the covering is worn through exposing
wire strands, is broken, or show worn spots which cause the cable to pump when Avoid excessive build up of coating at fairleads grommets pressure seals etc. as
passing over fairlead rollers. this increases cable friction force.
For installed cables the portion of cable to be re coated shall be wiped clean.
Inspection of Installation Check the surface of control cable for lack of protective coating. Clean such areas
Several components are installed along a cable run. Cables should be inspected with a clean cloth moistened with specified cleaning agent.
for broken wires, cable wear and corrosion especially in those sections where they
For nylon coated cables protect compound shall be applied to the area where the
are in contact with pulleys, fairleads, pressure seals or where they are close to toi-
nylon has been stripped.
lets, galleys and areas with water condensation build ups.
To thoroughly inspect the cable move it in full length of travel to expose damaged
areas. The following points should be considered:
• Check security and condition of all pulley brackets.
• Check that all pulley guard pins are in place.
• Check for broken or cracked pulleys and pulley flanges when ever tension is
relieved, check pulley for free rotation.
• Check that all cotter pins are securely installed.
• Examine fairlead grommets and rubstrips replace any that are damaged or
worn.
• Examine all firewall fairlead grommets and check for proper alignment and se-
curity to prevent cable ware.
• Grommet should be rigidly clamped in retainer after some cable tension has
been applied and should not be allowed to swivel or rotate.
• Check that all turnbuckles are properly safetied.
• Check that cable terminal threads meet the visual inspection requirement.
• Check the gap between guard pin/bushing and flange of any pulley,sector or
drum is within the applicable limits.
• Check that cable coated with corrosion preventive compound meet the char-
acteristic stated in the applicable specification.
• Check that cable clearance are in accordance to applicable specifications.
• Check cable for proper alignment (no pull offs).
• Check cable clearances in general. See Title "Cable Clearances" on page 5.
Surface Protection
After cleaning and inspection is completed, corrosion preventive surface coating
must be applied to the cable as specified.
Pulley Discrepancies
Due to different negative influences coming from cable or pulley misalignment,
bearing fault, excessive tension in the cable system, wrong sized pulley can lead
to abnormal cable or pulley wear.
Visually inspect the condition with regards to following discrepancies:
• Evidence of abnormal wear in bottom of grove
• Cracked hub
• Blisters
• Excessive play in bearing or loose bearings
Several pulley faults are shown in the following figure. For limitation and tolerances
consult the applicable manual.
Figure 19: Pulley Wear Indications
The flexible cable is made up of several strands of stainless steel wire. On the
ends are brass nipples which are soldered or swaged on.
The conduit consists of a close coiled wire, covered with a black waterproof coat-
ing. Metal caps are fitted on each end. On long runs metal tubing may be used.
At the transmitting end a hand lever couldm be fitted which engages with the nipple
on the end of the cable. At the receiving end, the cable passes through an adjust-
able stop and the nipple engages the component operating lever.