Documente Academic
Documente Profesional
Documente Cultură
Document Version
Submitted manuscript
Published in:
CSEE Journal of Power and Energy Systems
General rights
Copyright and moral rights for the publications made accessible in the Research Explorer are retained by the
authors and/or other copyright owners and it is a condition of accessing publications that users recognise and
abide by the legal requirements associated with these rights.
Takedown policy
If you believe that this document breaches copyright please refer to the University of Manchester’s Takedown
Procedures [http://man.ac.uk/04Y6Bo] or contact uml.scholarlycommunications@manchester.ac.uk providing
relevant details, so we can investigate your claim.
2 2 *
is ,abc Pac , Q iabc Rarm Larm vdc - 1
Pac* +
Pc 3 3 Pdc K dr
PCC + K dr -
icon idc
Rs Ls Rc Lc vdc + Pac +
Pc Cdc Pac* +
K P (s) id* *
vdc
-
K v (s) id*
vabc veq vdc - +
vs ,abc Cf eabc veq vdc
Pac
(a)Type 1: V-Pac droop A (b) Type 2: V-Pac droop B
v , vac
ac iq* Control (e) Type 5: V-id droop s
AV/RP Control
Q* , Q Fig. 3. Five types of dc voltage droop control implementations.
Fig. 2. VSC-HVDC control structure.
*
vdc K dv -
+
K (s) id*
A. Converter System Modeling + f vP* -
Pac* , Pdc* , idc
* K dP
The converter system model employed in this paper is
primarily based on the average-value model (AVM) developed - f vP
vdc K dv
in [16] and [17] for modular multilevel converters (MMC). As +
depicted in Fig. 1, the converter AC terminal is modeled by a Pac , Pdc , idc K dP
controlled voltage source interfacing with the point of common
coupling (PCC) through a lumped impedance representing both Fig. 4. Generalized droop control structure.
transformer and arm impedances. The AC system strength is TABLE I
quantified by the short-circuit ratio (SCR) which is directly DROOP CONTROLLER PARAMETERS OF TYPES 1-5
linked to the system impedance. The converter DC side is
Para
modeled by a controlled DC current source based on the power met Type 1 Type 2 Type 3 Type 4 Type 5
balance principle. An equivalent DC capacitance Cdc is ers
computed based on the derivations presented in [18]. The arm Kdv 1/Kdr 1 1 1 1
inductor is also modeled on the DC side, since one third of the KdP 1 Kdr Kdr Kdr 0
DC current flows through the arm inductor in each phase [16]. KP 1 Ts 1
K pP i Kiv Kiv Kiv
As shown in Fig. 2, a cascaded control system for VSC- K(s) s K pv K pv K pv
s s s K dr Ts 1
HVDC is typically implemented in a dq synchronous frame,
where the transformation angle is provided by a phase-locked
loop (PLL). The active current reference is provided by a DC In Type 3 and Type 4, DC power or DC current imported by
voltage (DV) controller or an active power (AP) controller. the converter is used to produce the supplementary signal for
The AC voltage or reactive power is controlled by the DV controller adjustment to obtain V-Pdc or V-Idc droop
manipulating the reactive current. respectively [1], [4], [13]. These two types are of particular
B. Candidate Droop Controllers interest if system operators are more concerned with DC rather
than ac power flow.
According to existing literature [3-6, 13, 19], dynamic
Type 5 is derived based on the frequency droop concept that
implementations of the DC voltage droop controller can be
droop control can be obtained by adding a proportional
classified into five types that are depicted in Fig. 3. These
feedback loop around the main controller [20]. This
designs aim to achieve similar or identical steady-state voltage
implementation is very similar to the standard design for
droop characteristics. The droop constant Kdr, which is
generator governors and STATCOM controls; however it has
interpreted here as the ratio between the steady-state deviation
rarely been discussed for MTDC applications. One possible
of DC voltage to change in ac or DC power, is likely to be
drawback of this design is that specified V-P droop
selected primarily based on power flow requirements in terms
characteristics cannot be perfectly achieved by Type 5 due to
of power sharing and DC voltage deviation [3], [4], [6], [13].
the mismatch between the active power and d-axis active
The Type 1 model has been widely used in [2], [5], [19],
current.
where the V-Pac droop characteristic is realized by modifying
the active power reference in proportion to the DC voltage C. Generalized Droop Controller Modeling
error. The Type 1 droop control effectively acts as the outer The droop implementations and typical AP or DV
control of the active power control. Alternatively, as shown in controllers described in Section II B can all be represented in
Type 2, V-Pac droop can be achieved by modifying the standard the generalized form shown in Fig. 4. A new droop variable fvP,
DV controller using a supplementary signal in proportion to which is defined as the sum of the DC voltage multiplied by
the active power error [3].
3
PI sections with i j1 R1 L1 PI sections with gain in the AP controller KP(s), since at low frequencies the AP
RL branches RL branches plant model is dominated by a large steady-state gain whereas
vin1 RCB LCB v0 v j 1 i j 2 R2 L2
vj vn RCB LCB vin 2 the DV plant model is dominated by an integrator.
iout1 iout 2 Type 5 controllers can be shown in the generalized droop
i jn Rn Ln control structure with K(s) represented as a lag compensator:
G C G
C
C G G 1 Ts 1 Kv 1
, where T pv , 1 v
C
2 2 2 2 K ( s) . (3)
Kdr Ts 1 Ki K p K dr
Fig. 5. Cable model with parallel RL branches.
D. Cable Modeling
The cascaded π-section cable (CPIC) model is commonly
adopted for mathematical modeling of VSC-HVDC systems
[5], [8], [22]. However, as identified in [11], relying on the
CPIC may give false judgement of DC system stability since
the resistance of the CPIC model can be much lower than that
of a frequency-dependent (FD) cable model [23]. Therefore, a
modified π-section cable (MPIC) model proposed in [11] is
utilized here for state-space modeling of DC lines to give a
more accurate representation of DC system dynamics. In the
MPIC model shown in Fig. 5, each π section is comprised of
multiple parallel RL branches to provide a degree of
frequency-dependency. For a symmetrical monopole system,
Fig. 6. State-space VSC model for DV/AP control studies. based upon the FD cable model in PSCAD/EMTDC, frequency
scan results of the series impedance of both positive and
DV droop gain Kdv and AC/DC current/power multiplied by negative poles are employed to account for the mutual
AP droop gain KdP, is considered as the new output signal to be impedance. Vector fitting is utilized for the parameterization
controlled in order to have a zero steady-state error. As shown process [24].
in Table I, the DV and AP droop gains Kdv and KdP are related A DC inductor LCB, which is required by DC circuit
to the slope Kdr as: Kdr=KdP/Kdv. The main controller K(s) is breakers for fault current limiting, is included at both ends of
normally a PI controller for typical droop schemes but a more each cable as shown in Fig. 5. A state-space model of a cable
complex controller can be easily incorporated in this model that consists of n parallel branches and m π sections has
generalized droop structure. (mn+m+3) state variables.
This generalized droop control structure shown in Fig. 4
enables various types of DV/AP controllers to be evaluated E. Open-Loop and Closed-Loop Models
under a common framework. A similar control structure is also This section briefly describes the open-loop and closed-loop
applicable to the general representation of a constant ac voltage formulations of a generalized small-signal MTDC model.
control, reactive power control and droop AC voltage control. All the differential equations which describe the dynamics of
Furthermore, functionality and flexibility of the mathematical ac and DC systems, converters and controllers need to be
modeling of MTDC systems are also greatly improved by identified and linearized around a specified operating point,
utilizing this control topology. which is provided by a power flow calculation. Detailed
The DV controller Kv(s) and AP controller KP(s) presented derivations of these linearized equations are provided in [19],
in Fig. 3 are typically PI controllers. The superscripts ‘v’ and [22]. The open-loop VSC system model used to assess DV/AP
‘P’ denote whether the related PI controllers are designed control structures is formulated by interconnecting multiple
based upon the DC voltage plant or the active power plant sub-systems, as illustrated in Fig. 6, where xQ and xvac represent
respectively. Please note that per unit representation is used the states of the RP and AV controllers respectively; the states
throughout this paper. of the PI current controllers are denoted by xid and xiq; the state
The PI AP controller KP(s) can be tuned using the Skogestad of the PLL loop filter is denoted by xpll; θ is the output angle of
internal model control (SIMC) method [21]: the PLL; and the notation of the states related to converter ac
1 and DC plants are shown in Fig. 1 and Fig. 2. In Fig. 6, w1 and
K pP id , KiP (1)
des des w2 represent exogenous input vectors, whereas z1 and z2 are
exogenous output vectors.
where τid is the time constant of the d-axis current loop and τdes
In a MTDC system, a general state space model for the jth
is the desired time constant of the AP control loop.
VSC system can be written as (4), where xj and uj are the state
SIMC can also be applied for the tuning of the PI DV
variables and the input vector of the jth converter respectively.
controller and the resulting parameters are:
The DC current injected into the jth converter idc(j) and the
Cdc Cdc
K pv , Kiv (2) converter DC voltage udc(j) are treated separately from other
des id 4( des id )2 inputs/outputs, since converter models and the DC network
where Cdc is the equivalent DC link capacitance and τdes is the models are integrated together through the exchange of DC
desired time constant of the DV control loop. For similar voltages and currents.
closed-loop bandwidth, the proportional gain in the DV
controller Kv(s) is usually much larger than the proportional
4
VSC1
MIMO Plant for DC Voltage Control Pac1
TABLE II Pac P P
. CONVERTER PCC POWERS IN THE TWO POWER FLOW SCENARIOS. icon icon ac aco 2
vdc (9)
vdc vdco vdco
Scenario VSC1(p.u.) VSC2(p.u.) VSC3(p.u.) VSC4(p.u.)
where the subscript ‘o’ denotes the operating point. A DC link
PF1 -0.750 -0.600 0.759 0.580
model shown in Fig. 11 is used to represent a simplified
PF2 0.750 0.600 -0.781 -0.580
system and conceptually illustrate the impact of the DC
inductor. An inverter in constant power mode behaves as a
Bus 1 Bus 2
icon1 negative resistance in parallel with a DC current sink. The
RL LL icon 2 negative resistance will impose negative damping and reduce
2
vdco Pac
vdc1 vdc 2 relative stability of the system. A similar effect has been
Cdc Paco vdco
Cdc analyzed in [26], [27] for DC links of low-power inverter
drive systems.
Constant Power Sink
For the generic DC link shown in Fig. 11, if the voltage vdc1
Fig. 11. Simplified dc link model with linearized DC power sink. is to be controlled by varying the DC current icon1, the
1500 1500 numerator of the transfer function relating icon1(s) to vdc1(s) is:
R P 1 RL Paco
s 2 L aco2 s 1 2 . (10)
1000 1000 LL Cdc vdco LLCdc vdco
Imag Axis
Imag Axis
Fig. 12. Trajectories of selected closed-loop eigenvalues for scenarios PF1 and
DC inductance or the inverting power of the power sink
PF2 as the dc inductor varies from 0 to 150 mH (Type 2 droop, Kdr=5%). increases the possibilities of RHP zeros and degrades the
controllability of the DC link. The effect of DC inductors on
0 0
32.5 Hz MTDC stability is highly dependent on the DC power flow,
Magnitude (dB)
Magnitude (dB)
59 Hz 175 Hz
-20 229 Hz -20
particularly the VSCs in constant power control mode.
-40 -40
With the DC inductor size varying from 0 to 150 mH,
-60
10 10
0
10
-60
1
10 10
2
10
trajectories
0 of selected closed-loop eigenvalues of the four-
1 2
90 90
terminal model under two power flow conditions are shown in
0 0 Fig. 12. The increase of LCB reduces the oscillating frequencies
Phase (deg)
Phase (deg)
-90 -90
-180 -180
and damping of the poles associated with the DC network.
-270
PF1
PF2
-270
PF1
PF2
Using a larger LCB has a more significant destabilizing impact
-360
10 10
0
10
-360
1
10 10 2
10 on the PF2 scenario than the PF1 scenario. A low-frequency
0 1 2
Frequency
Frequency
(a) System with L =0 mH (b) System with L =100 mH
CB
dominant mode migrates into the RHP and renders the closed-
CB
Fig. 13. Frequency responses of the open-loop transfer function vdc4(s)/ id 4 (s), * loop system unstable for the PF2 case, where both converters
operate as inverters in constant power control mode and
for systems with and without dc breaking inductor.
impose virtual negative admittances.
Under scenarios PF1 and PF2, frequency responses of the
presented in Section II-E. A more accurate model using a FD open-loop plant model with respect to VSC4 operating in
cable model is built in PSCAD for time-domain simulations. droop control are presented in Fig. 13, for the four-terminal
Two power flow scenarios, which are parameterized in models with and without DC breaking inductors of 100 mH
Table II as PF1 and PF2, are used for all test cases. Inverter [25]. The scenario PF2 always has a larger phase lag than PF1
orientation (P>0 for inverters) and per unit values are used in above 4 Hz due to the RHP zeros caused by the power flow
this paper. VSC3 and VSC4 employ voltage droop control direction. This implies that, with identical control settings, the
whereas active power control is applied to VSC1 and VSC2. system with fewer inverters in constant AP control mode is
The nominal value of the droop constant Kdr is 5%, for both likely to have better stability margins especially phase margins,
VSC3 and VSC4. The nominal bandwidths of the DV and AP and be more robust to unmodeled high-frequency dynamics.
controllers are selected to be 18 Hz. The introduction of the 100 mH inductor into the system
A. DC Inductor and DC Power Flow significantly amplifies the frequency-domain peaks. The loop
transfer function L(s) in this case is therefore more likely to
DC circuit breakers rely on large DC inductors to limit the cross 0 dB at these frequency peaks and this could severely
rise of the DC fault current. The DC inductor may however degrade the phase margin and may cause instability, especially
degrade the stability and transient performance of MTDC when relatively high-gain controllers are employed. The DV
systems [22], [25]. The detrimental effect caused by this controller gain should be sufficiently low around these
component requires further in-depth analysis. resonant frequencies to allow acceptable stability margins.
From the DC grid perspective, an inverter in constant power
control can be approximated as a DC power sink. The DC
current imported by this power sink can be linearized as:
6
Imag Axis
Imag Axis
300
Imag Axis
Imag Axis
4000
200 200 200
3000
Magnitude (dB)
Magnitude (dB)
-20 -20 -20
MPIC
-40 CPIC -40 -40
0 -60 0 -60 0
Phase (deg)
1 2 1 2
10 10 10 10 10 10
-90
90 90
-180
0 0
Phase (deg)
Phase (deg)
0 1 2
10 10 10 -90 -90
Frequency (Hz) Type2
Frequency (Hz) -180 -180 Type3
Fig. 15. Closed-loop eigenvalues of the four-terminals models based upon -270 -270 Type4
MPIC and CPIC models (PF1, Type 3 droop, Kdr=5%). -360 0 -360 0
Type5
1 2 1 2
10 10 10 10 10 10
Frequency
Frequency(Hz) Frequency (Hz)
Frequency
(a) System with LCB=0 mH (b) System with LCB=100 mH
Fig. 17. Frequency responses of the plant models fvP4(s)/ i*d4(s), for Types 2 to
B. DC Cable Modeling 5 regarding droop control using VSC4, for systems with/without LCB (PF2,
The impact of DC cable modeling on MTDC stability has Kdr=5%).
been neglected in a majority of previous literature. The
(dB)
20 20
(dB)
13 dB
Magnitude
Magnitude
eigenvalues of the MPIC-based and the CPIC-based test 10 10 70 Hz
Magnitude
Magnitude
0 0
system models are shown in Fig. 14. The high-frequency DC -10 -10
network modes resulting from the CPIC-based model are
S(s)S(s)
S(s)
-20 -20
S(s)
located quite close to the imaginary axis, whereas the DC -30 0
10 10
1
10
2
-30 0
10 10
1
10
2
Magnitude(dB)
20 20
11.3 dB
damping. The dominant poles in Fig. 14 show that, with
T(s)Magnitude
Magnitude
70 Hz
0 0
identical controllers, the closed-loop model based on the CPIC Type1
Type2
-20 -20
model may have much poorer stability than the MPIC based T(s)
Type3
T(s)
T(s)
Type5
model. The CPIC-based model also exhibits more and sharper -40 0
10 10
1
10
2
-40 0
10 10
1
10
2
(dB)
Magnitude
Magnitude
-40 -20
A more realistic MPIC model should therefore be
Magnitude
Magnitude
considered since the CPIC model will exaggerate stability -60 -40
Type1
problems. Type2
-80 -60
Type3
C. Short-circuit Ratio Type5
-100 0 -80 0 1 2
1 2
10 10 10
For a VSC system connected to a weak ac system, the PCC 10 10
Frequency
Frequency(Hz)
10
Frequency
Frequency (Hz)
voltage could be sensitive to the active and reactive current (a ) u Pref 1 , Pref 2 , y vdc1 , vdc 2 , vdc 3 , vdc 4 (b) u Pref 1 , Pref 2 , y Pac 3 , Pac 4
variations of the converter system, and this leads to a more Fig. 19. Maximum singular value of the closed-loop disturbance models y/d
nonlinear relationship between the active power and d-axis with disturbances d and outputs y (PF2, Kdr=3.3%, LCB=100mH).
current. Such nonlinearities can cause RHP zeros in the plant
models of both the active power and DC voltage control for severely affected by the SCR variation. Conversely, the system
converters in rectifier operation [19]. The RHP zeros will based upon the Type 3 controller becomes unstable for
locate closer to the origin for a system with a lower SCR and SCR1.9 due to the poles at 75 Hz. In this case, the RHP zeros
larger rectifying power. As the SCR of the droop-controlled caused by lower SCRs are more likely to be excited for a Type
VSCs of the test system varies from 5 to 1.7, the trajectories of 3 droop due to the plant model having higher resonant gains
the dominant closed-loop eigenvalues are shown in Fig. 16. than that for the Type 2 droop. This demonstrates a key
The stability of the system using a Type 2 controller is not
7
advantage of the Type 2 control over Type 3 control in terms droop has better low-frequency disturbance rejection
of robustness. capability. However, it may be more vulnerable to RHP zeros
and unmodeled dynamics due to its high bandwidth. The
IV. DROOP CONTROLLER COMPARISONS comparison between sensitivity peaks suggests that Types 2
Most of the stability limitations addressed in Section III are and 5 tend to provide better stability than Types 1 and 3. Type
generally applicable to all five types of DC voltage controls. 5 droop has slightly lower bandwidths than Types 2 and 3.
The following comparative study investigates key stability However the complementary sensitivity T(s) for Type 2 droop
features of the five droop implementations considered in this may not roll off sufficiently fast at high frequencies and may
paper. need additional low-pass filters to improve noise attenuation.
As shown in Fig. 18(b) when considering droop control
A. Selection of Output Signal implemented on VSC4, frequency-domain peaks of S(s) and
Control Types 2 to 4 have identical controller structure and T(s) at 70 Hz for Type 3 control are significantly higher than
are essentially differentiated by the selection of output signals, the others. This indicates that a closed-loop system utilizing the
namely, AC power, DC power and DC current. Type 3 control structure gives a much poorer stability and
Frequency responses of the plant models for Types 2 to 5 are robustness under this condition. The large gain of the plant L(s)
compared in Fig. 17, with respect to droop control at 55 Hz for Type 3 results in a high cross-over frequency
implemented on VSC4. The differences of Type 3 V-PDC droop which then seriously worsens the stability margins. This
and Type 4 V-IDC droop is negligible in the frequency domain, clearly shows a key weakness of using DC power rather than
since the converter DC current and DC power contain almost ac power as the feedback signal for droop control.
identical dynamic information. Hence only Type 3 will be B. Droop Parameterization
considered out of these two controller types for further study. This section is focused on analyzing the robustness of the
Within low frequencies below 24 Hz, there is little difference candidate controllers with respect to droop parameterization.
between the plant models for Type 2 V-Pac droop and Type 3
The maximum singular value (G(j )), which represents
V-PDC droop. However, the plant model for Type 3 tends to
have a larger phase drop than the model for Type 2 as the maximum gain of a multivariable system G(j ) as a
frequency increases. Consequently, with identical controller function of frequency, is a very effective frequency domain
parameters, the closed-loop system for Type 3 will have a measure for MIMO performance and robustness [21].
worse phase margin than Type 2, if the cross-over frequency is In a MTDC system, the converters operating in AP control
higher than 24 Hz. Moreover, the plant model for Type 3 also mode act as disturbances to the converters regulating DC
has a larger resonant peak at 53 Hz than that for Type 2. This voltage. The maximum singular value plots are shown in Fig.
together with the phase lag effect implies that V-PDC droop is 19(a) and (b) respectively for the closed-loop model between
likely to be more prone to high-gain instability than V-Pac the disturbances [P*1 P*2] and DC voltages, and the model
droop. between [P*1 P*2] and the powers of VSCs in droop control.
Adding 100mH DC inductors does not impact the low- As shown in Fig. 19, the DC voltages are less perturbed by
frequency response of the plant models for Type 2 and Type 3, the disturbances at low frequencies for Type 1. However, this
as shown in Fig. 17(b). However, the plant model for Type 3 comes at a cost of more excessive usage of the active powers
contains more and sharper resonant peaks above 100 Hz than associated with VSC3 and VSC4. The Type 1 controller
that for Type 2, since the signal PDC is significantly affected by struggles to maintain system stability as the unacceptably high
the overall DC network dynamics. Type 3 control is thus much gain at 37.5 Hz implies very poor damping. Type 1 and Type 2
more likely to be affected by modeling of the DC components controls share identical output signals and are differentiated by
such as DC cable and DC inductor. the parameterization of K(s), as the Type 1 control can be
DC voltage control using droop control can be decomposed written in the form of Type 2 but with K(s)=KP(s)/Kdr instead
into multiple SISO closed-loop systems. The SISO sensitivity of K(s)=Kv(s). This implies that utilization of a relatively small
and complementary sensitivity transfer functions S(s) and T(s) droop Kdr will result in a high-bandwidth DV control loop if
resulting from Types 1, 2, 3 and 5 are compared in Fig. 18(a) Type 1 is employed.
and (b), for droop control implemented on VSC3 and VSC4 The singular value plots suggest that Types 2 and 5 have
respectively. The bandwidth of Type 1 control is much higher very similar frequency-domain characteristics. Slightly worse
than the other droop types because the equivalent integral gain disturbance rejection performance is provided by Type 3 in the
of Type 1 is much larger than the others, as the PI controller of frequency range of 35 to 100 Hz.
Type 1 is identical to the AP controller. Therefore, Type 1
8
800 800 the DV control bandwidth and the overall system becomes
more vulnerable to the constraints discussed in Section III. As
600 600
shown in Fig. 20(c) for Type 3 control, the closed-loop system
Imag Axis
Imag Axis
400
Kdr increasing
400
modes located above 35 Hz migrate towards the right-half s-
plane as Kdr increases, since increasing of the weight of the DC
200 200 power/current in fvP creates larger resonant peaks in the plant.
As shown in Fig. 20(b) and (d), the high-frequency modes for
0 0
-60 -40 -20 0 20 -60 -40 -20 0 20 Types 2 and 5 are much more robust to droop variation than
Real Axis Real Axis
(a) Type 1 droop (b) Type 2 droop
those for the other controllers, which is a clear advantage of
800 800
using ac power or current for droop control.
When large droop constants Kdr are used, using DC power
600 600 or current for droop control may result in high-frequency peaks
Imag Axis
Imag Axis
in the plant and cause poor stability. For better stability, a low-
400 400
pass filter (LPF) with an appropriately designed bandwidth is
200 200
recommended to filter the measured DC power/current before
feeding to Type 3 and 4 controllers.
0
-60 -40 -20 0 20
0
-60 -40 -20 0 20
The critically-damped dominant modes for Types 2, 3 and 5
Real Axis Real Axis migrate towards the origin as Kdr decreases. The application of
(c) Type 3 droop (d) Type 5 droop
very small droop constants can result in very slow modes and
Fig. 20. Trajectories of closed-loop eigenvalues as Kdr varies from 1% to 20%
(PF2, LCB=100 mH). long settling time for Types 2, 3 and 5, as the interactions
between the integrators of droop controllers become stronger.
500 500
Furthermore, the steady-state power sharing between droop-
400
K(s) gain increasing
400 controlled terminals will be more dependent on DC system
impedance for the use of a very small Kdr [12].
Imag Axis
Imag Axis
300 300
200 200
As the desired time constant τdes that is used for AP or DV
controller design varies from 40ms to 4ms, the eigenvalue
100 100
trajectories of the systems employing Type 1 and Type 2
0
-60 -40 -20 0 20
0
-60 -40 -20 0 20
control are shown in Fig. 21. For the configuration of Type 1
Real Axis
(a) Kdr=5%, Type 1 control
Real Axis droop with Kdr=5%, increasing the gains of the AP controller
(b) Kdr=2.5%, Type 1 control
250 250
KP(s) enhances both the damping and response speed of the
system. Contrarily, as shown in Fig. 21(b) for the case with
200 200
Kdr=2.5%, increasing the gains of KP(s) could easily cause
Imag Axis
Imag Axis
150 150 instability of the system. This effect implies that the controller
100 100 parameters of Type 1 have to be retuned upon the variation of
19
the droop constant. In contrast, for the Type 2 control, the
Imag Axis
18
50 50 17
16
15
eigenvalue trajectories for variations of tuning parameters of
-27 -26 -25 -24 -23
0
-60 -40 -20 0
0
-60
Real Axis
-40 -20 0 Kv(s) are much less dependent on the selection of Kdr, as shown
Real Axis Real Axis
(c) Kdr=5%, Type 2 control (d) Kdr=2.5%, Type 2 control
in Fig. 21(c) and (d). This shows another advantage of Type 2
Fig. 21. Eigenvalue trajectories as the desired bandwidth varies from 4 Hz to over Type 1 that the parameterization of the main droop
40 Hz for the design of AP or DV controller parameters (PF2, LCB=100 mH). controller K(s) is much more robust.
The key stability and robustness features of the five types of
Fig. 20 shows the sensitivity of the closed-loop eigenvalues droop controller are summarized Table III.
as the droop Kdr varies from 1% to 20%. As shown in Fig.
20(a) for Type 1 control, reducing the droop constant increases
TABLE III
COMPARISON OF THE KEY STABILITY FEATURES BETWEEN THE FIVE TYPES OF DROOP CONTROLLERS
Assessment Item Type 1 Type 2 Type 3 Type 4 Type 5
Closed-loop bandwidth High Moderate Moderate Moderate Moderate
Usage of converter power High Moderate Moderate Moderate Moderate
Low-frequency disturbance rejection Fast Moderate Moderate Moderate Moderate
Robustness to DC network resonances Moderate/Poor Moderate Poor Poor Moderate
Robustness to droop gain variation Poor Good Moderate/Poor Moderate/Poor Good
Robustness to DV PI gain variations Poor Good Moderate Moderate Good
9
s vdco + Pac* +
vdc K v (s) id*
V. ACTIVE STABILIZING CONTROL s v +
-
Ka Pref Pac
As the combined effect of DC power flow and DC P Po
P Ks
impedance resonance could pose severe constraints on MTDC s P + +
stability, there is a poorly damped mode at 17.8 Hz, as shown
Fig. 22. Active stabilizing controller.
in Fig. 20 and Fig. 21, irrespective of the droop
implementation. Such an oscillating mode is caused by the 10
0.86 dB
10
Magnitude (dB)
-12.1 dB
Magnitude (dB)
-10 -14.3 dB -10
modified form of active damping control for inverter drive -16 dB
systems [26, 27], is proposed in this paper for MTDC systems -20 -20
PF1,no ASC
to mitigate the negative admittance effect and inherently -30 2.3 Hz 25 Hz
PF2,no ASC
-30
improve controllability and robustness of the DC voltage PF1,ASC
PF2,ASC
control. The key purpose of the ASC is to increase the dynamic -40 0
10 10
1
10
2
-40 0
10 10
1
10
2
damping by forming an additional feedback around the Frequency (Hz) Frequency (Hz)
constant power control loop. According to Fig. 22, the active ( a ) d Pref 1 , Pref 2 , y vdc1 , vdc 2 , vdc 3 , vdc 4 (b) d Pref 1 , Pref 2 , y Pac 3 , Pac 4
power reference Pac* is modified by the ASC as: Fig. 23. Maximum singular value of the closed-loop disturbance models y/d
with disturbances d and outputs y (PF2, Kdr=5%, Ks=3, Type 2, LCB=100mH).
P* Pref Ka vdc vdco P* Pref Ka vdc (11) -3 -3
x 10 x 10
4
where Ka is the stabilizing gain, vdco is the filtered DC voltage PF1, no ASC
6
and Pref is the steady-state power reference. By simplifying the 3 PF2, no ASC
VSC2 (pu)
VSC3 (pu)
PF1, ASC
closed-loop active power control to a first-order plant with a 4 2 PF2, ASC
bandwidth of ωP, the active power output of a converter in the
2 1
ASC control mode can be represented as: Vdc
Vdc
P P P 0
P P* Pref Ka vdc . (12) 0
s P s P s P 2 2.2 2.4 2.6
-1
2 2.2 2.4 2.6
Time (s) Time (s)
Subsequently, the small-signal representation of the DC
Fig. 24. Responses of the dc voltage deviations of VSC2 and VSC3 to a 50
current source of the AVM can be linearized as: MW step decrease of Pref1 (PF2, Kdr=5%, Ks=3, Type 2, LCB=100mH).
P Po
icon 2 vdc
vdco vdco
. (13) The four-terminal model is also built in PSCAD based on
P 1 P Ka Po
Pref 2 vdc the AVM converter model and FD cable model to verify the
s P vdco s P vdco vdco analytical results using time-domain simulations. Responses of
As shown in Fig. 22, the stabilizing gain Ka is given as: the deviations of vDC2 and vDC3 to a 0.05 pu step change of Pref1
p are shown in Fig. 24, which agree very well with the frequency
Ka P K s Po K s (14) domain results shown in Fig. 23. The impact of ASC on the
s p robustness improvement is evident, as the simulations for the
where Po is the converter power operating point, the filtering two cases with ASC are both stable and well damped.
parameter αp shall be sufficiently large, and Ks is named as When large droop constants are used, utilizing DC power or
virtual admittance gain. The equivalent input admittance of the current for droop control may result in high-frequency peaks in
converter with ASC can then be derived as: the plant and cause poor stability. For better stability, a low-
P K P P Po K s Po pass filter (LPF) HF(s) with an appropriately designed
Yeq a 2o 2 . (15) bandwidth is recommended here for the power measurement of
s P vdco vdco s P vdco vdco the Type 3 and 4 control, as shown in Fig. 25.
Natural admittance of 0 can be roughly achieved within the AP The impact of this additional LPF for Type 3 droop on the
bandwidth by selecting Ks=0. However, Ks slightly larger than frequency responses of the closed-loop disturbance models is
0 is recommended since ωP may not be sufficiently high to shown in Fig. 26. The corresponding eigenvalues of interest
cover the resonant frequency of interest (i.e. 17.8 Hz in this are shown in Table III. A second-order LPF with a bandwidth
case). of 15 Hz is employed. Using the Type 3 droop with Kdr=20%
The impact of applying the ASC control instead of the causes a series of singular value peaks, which implies poor
constant power control to VSC1 and VSC2 is demonstrated in damping and instability at the associated resonant frequencies.
terms of closed-loop responses in Fig. 23, where the maximum The LPF used for DC power filtering is effective in terms of
singular values of the disturbance models of interest are shown. stabilizing the oscillatory modes at 52 Hz and 124 Hz.
For the original system without the ASC, stability and However the LPF is not able to improve the poorly damped
disturbance rejection performance of the system for the PF2 low-frequency modes caused by the negative admittance effect.
scenario is significantly worse than that for the PF1 scenario. This issue is much more effectively dealt with by employing
Replacing the typical AP control with the ASC enhances the the ASC control for VSC1 and VSC2, as shown in Fig. 26.
stability of the system for the PF2 scenario, and significantly With the system stabilized by the Type 3 controllers with
improves the robustness of the DC voltage control to power LPF, responses of VSC1 and VSC3 to an ac fault at PCC2 are
flow variations. shown in Fig. 27, for three ASC control scenarios. The fault
10
occurring at 2s caused 30% voltage sag at PCC2 and was Pac* , Pdc* , idc
* +
K dr
cleared after 0.1s. A larger ASC is more effective in damping -
improvement but requires more usage of the converter power. Pac , Pdc , idc
H F (s) +
DC voltages of the inverters in constant power control can be *
vdc
-
K v (s) id*
+
significantly more oscillatory than those converters in droop vdc
control, although this may not be a severe issue for systems
Fig. 25. Modified droop controller with additional filtering function.
without breaking inductors.
10 20
17.8 Hz
VI. CONCLUSION 0
124 Hz 0
52.2 Hz
-10
In this paper, a general framework for the analysis of
Magnitude (dB)
Magnitude (dB)
-20 -20
various droop control configurations employed for MTDC
-30
systems has been proposed. This framework is then used to -40
-40
compare leading droop configurations in terms of their impact -60
Original
-50 LPF
on controllability, closed-loop stability, robustness and ASC+LPF
dynamic performance of the overall MTDC system. -60 0
10 10
1
10
2
-80 0
10
1
10
2
10
The following stability limitations have been identified for Frequency (Hz) Frequency (Hz)
( a ) d Pref 1 , Pref 2 , y vdc1 , vdc 2 , vdc 3 , vdc 4 (b) d Pref 1 , Pref 2 , y Pac 3 , Pac 4
the DC voltage control:
1) The negative admittance effect caused by inverters Fig. 26. Maximum singular value of the closed-loop disturbance models y/d
with disturbances d and outputs y (PF2, Kdr=20%, Ks=4, Type 3, LCB=100 mH).
operating in constant power mode limits DC voltage
control bandwidth and degrades both robustness and TABLE IV
stability of the DC system.
2) The use of large DC inductors can severely deteriorate the SELECTED EIGENVALUES CORRESPONDING TO THE CASE SHOWN
controllability of the DC network and cause critical low- IN FIG. 26
frequency resonances for any of the droop configurations. Mode Original LPF ASC+LPF
3) Weak ac system connection can pose different bandwidth 1 0.252±j781 11.1±j782 11.1±j782
limitations on different types of droop controllers. 2 28.3±j643 13.1±630 13.1±630
The analysis in this paper leads to the following design 3 5.43±j327 23.4±j222 23.6±j224
recommendations for DC voltage droop control: 4 2.55±j112 2.55±j112 18.4±126
1) All the five droop types can be applied with care.
However, under severe plant constraints, Type 2 and 1 1.01
-0.8
oscillatory modes, the DC power or DC current is
Vdc VSC3 (pu)
0.76
grids,” Electric Power Systems Research, vol. 103, pp. 137– [23] A. Semlyen and A. Deri, “Time domain modelling of
144, Oct. 2013. frequency dependent three-phase transmission line
[7] L. D. Zhang, L. Harnefors, and H. P. Nee, “Interconnection of impedance,” IEEE Transactions on Power Apparatus and
two very weak AC systems by VSC-HVDC links using power- Systems, vol. PAS-104, no. 6, pp. 1549–1555, Jun. 1985.
synchronization control,” IEEE Transactions on Power [24] B. Gustavsen and A. Semlyen, “Rational approximation of
Systems, vol. 26, no. 1, pp. 344–355, Feb. 2011. frequency domain responses by vector fitting,” IEEE
[8] G. Pinares and M. Bongiorno, “Modeling and analysis of VSC- Transactions on Power Delivery, vol. 14, no. 3, pp. 1052–
based HVDC systems for DC network stability studies,” IEEE 1061, Jul. 1999.
Transactions on Power Delivery, vol. 31, no. 2, pp. 848–856, [25] J. Häfner and B. Jacobson, “Proactive hybrid HVDC breakers-
Apr. 2016. a key innovation for reliable HVDC grid,” in Proceedings of
[9] L. Harnefors, M. Bongiorno, and S. Lundberg, “Input- the Electric Power System of the Future-Integrating
admittance calculation and shaping for controlled voltage- Supergrids and Microgrids International Symposium,Bologna,
source converters,” IEEE Transactions on Industrial Italy, 2011, pp. B4–B110.
Electronics, vol. 54, no. 6, pp. 3323–3334, Dec. 2007. [26] S. D. Sudhoff, K. A. Corzine, S. F. Glover, H. J. Hegner, and
[10] J. Z. Zhou, H. Ding, S. T. Fan, Y. Zhang, and A. M. Gole, H. N. Robey, “DC link stabilized field oriented control of
“Impact of short-circuit ratio and phase-locked-loop electric propulsion systems,” IEEE Transactions on Energy
parameters on the small-signal behavior of a VSC-HVDC Conversion, vol. 13, no. 1, pp. 27–33, Mar. 1998.
converter,” IEEE Transactions on Power Delivery, vol. 29, no. [27] K. Pietilainen, L. Harnefors, A. Petersson, and H. P. Nee, “DC-
5, pp. 2287–2296, Oct. 2014. link stabilization and voltage sag ride-through of inverter
[11] J. Beerten, S. D'Arco, and J. A. Suul, “Cable model order drives,” IEEE Transactions on Industrial Electronics, vol. 53,
reduction for HVDC systems interoperability analysis,” in no. 4, pp. 1261–1268, Jun. 2006.
Proceedings of the 11th IET International Conference on AC
and DC Power Transmission, 2015, pp. 1–10.
[12] J. Beerten and R. Belmans, “Analysis of power sharing and
voltage deviations in droop-controlled DC grids,” IEEE Wenyuan Wang received B.Eng. and Ph.D.
Transactions on Power Systems, vol. 28, no. 4, pp. 4588–4597, degrees in electrical and electronic engineering from
Nov. 2013. the University of Manchester, U.K. in 2011 and 2015
respectively, where he was also a research associate.
[13] L. Xu and L. Yao, “DC voltage control and power dispatch of
His research interests include operation, stability and
a multi-terminal HVDC system for integrating large offshore control of multi-terminal VSC-HVDC systems. He is
wind farms,” IET Renewable Power Generation, vol. 5, no. 3, currently working at General Electric Grid Solutions,
pp. 223–233, May 2011. Stafford, U.K.
[14] F. Thams, J. A. Suul, S. D’Arco, M. Molinas, and F. W. Fuchs,
“Stability of DC voltage droop controllers in VSC HVDC
systems,” in Proceedings of 2015 IEEE Eindhoven PowerTech,
2015, pp. 1–7.
[15] G. O. Kalcon, G. P. Adam, O. Anaya-Lara, S. Lo, and K. Mike Barnes (M’96–SM’07) received B.Eng. and
Uhlen, “Small-signal stability analysis of multi-terminal VSC- Ph.D. degrees from the University of Warwick,
based DC transmission systems,” IEEE Transactions on Power Coventry, U.K. In 1997, he was a Lecturer with the
Systems, vol. 27, no. 4, pp. 1818–1830, Nov. 2012. University of Manchester Institute of Science and
Technology (UMIST, now merged with The
[16] H. Saad, S. Dennetiere, J. Mahseredjian, P. Delarue, X.
University of Manchester), Manchester, U.K., where
Guillaud, J. Peralta, and S. Nguefeu, “Modular multilevel he is currently a professor. His research interests
converter models for electromagnetic transients,” IEEE cover the field of power-electronics-enabled power
Transactions on Power Delivery, vol. 29, no. 3, pp. 1481– systems.
1489, Jun. 2014.
[17] A. Beddard, C. E. Sheridan, M. Barnes, and T. C. Green,
“Improved accuracy average value models of modular
Ognjen Marjanovic (M’08) received a First Class
multilevel converters,” IEEE Transactions on Power Delivery, honors degree from the Department of Electrical and
vol. 31, no. 5, pp. 2260–2269, Oct. 2016. Electronic Engineering, Victoria University of
[18] L. Harnefors, A. Antonopoulos, S. Norrga, L. Angquist, and H. Manchester, Manchester, U.K., and a Ph.D. degree
P. Nee, “Dynamic analysis of modular multilevel converters,” from the School of Engineering, Victoria University of
IEEE Transactions on Industrial Electronics, vol. 60, no. 7, pp. Manchester. Currently he is a Senior Lecturer in the
2526–2537, Jul. 2013. School of Electrical and Electronic Engineering at the
[19] W. Wang, M. Barnes, and O. Marjanovic, “Frequency- University of Manchester, UK. His main research
response analysis and compensator enhancement of droop focus is to employ valuable control theory and
concepts in order to solve operational issues of challenging real-world systems
control for VSC-HVDC,” in Proceedings of the 11th IET and processes.
International Conference on AC and DC Power Transmission,
Birmingham, UK, 2015, pp. 1–8.
[20] P. Kundur, Power System Stability and Control. New York:
McGraw-Hill, 1994.
[21] S. Skogestad and I. Postlethwaite, Multivariable Feedback
Control: Analysis and Design, 2nd ed. Chichester: Wiley,
2005.
[22] W. Y. Wang, M. Barnes, O. Marjanovic, and O. Cwikowski,
“Impact of DC breaker systems on multiterminal VSC-HVDC
stability,” IEEE Transactions on Power Delivery, vol. 31, no. 2,
pp. 769–779, Apr. 2016.