PART 1 GENERAL
1.01 SECTION INCLUDES
A. Low Voltage Switchboard – Furnish and install switchboard(s) as specified herein and where shown
on the associated [schedules] [drawings].
1.02 REFERENCES
The switchboard(s) and overcurrent protection device(s) referenced herein are designed and
manufactured according to the latest revision of the following specifications.
A. Approval documents shall include drawings. Drawings shall indicate front and side enclosure
elevations with overall dimensions shown; conduit entrance location and requirements, single-line
diagrams, equipment schedule and switchboard instrument details.
1.04 QUALIFICATIONS
A. Company specializing in manufacturing of switchboard products with a minimum of fifty (50) years
documented experience.
A. Inspect and report concealed damage to carrier within their required time period.
B. Handle carefully to avoid damage to switchboard internal components, enclosure, and finish.
C. Store in a clean, dry environment. Maintain factory packaging and, if required, provide an additional
heavy canvas or heavy plastic cover to protect enclosure(s) from dirt, water, construction debris, and
traffic.
1.07 WARRANTY
A. Manufacturer shall warrant specified equipment free from defects in materials and workmanship for
MasterFormat 2004
Number: 26 24 13
October 2016
the lesser of one (1) year from the date of installation or eighteen (18) months from the date of
purchase.
PART 2 PRODUCTS
2.01 MANUFACTURERS
B. Substitutions must be submitted in writing three weeks prior to original bid date with supporting
documentation demonstrating that the alternate manufacturer meets all aspects of the specification
herein.
2.02 TERMINATIONS
A. Termination lugs shall be CSA/UL Listed to accept solid or stranded [copper and aluminum
conductors] [copper conductors only]. Termination lugs shall be suitable for cables sized per the 75C
column of the CE Code table. It is permissible for primary cables terminating in a bussed auxiliary
section to be sized to the 90C column of the CE Code.
2.03 ENCLOSURE
A. The switchboard shall be totally enclosed, dead front, freestanding or freestanding wall supported and
rear aligned with front, side or rear access.
B. The switchboard shall be [NEMA Type 1 - General Purpose] [NEMA Type 1 – with drip hood] [NEMA
Type 3R - Rainproof].
D. NEMA Type 3R enclosure shall be [Standard] [Canadian winter]. [Canadian Winter] Type 3R will
come equipped with bottom closure plates, enclosure heater, and wind barriers mounted atop existing
ventilation on each section. These modifications are intended to provide an extra degree of protection
against wind-blown snow; however, they do not guarantee protection in harsh winter conditions.
E. The framework shall be formed steel and secured together to support all cover plates, bussing and
component devices during shipment and installation. All closure plates are to be single tool, screw
removable. Ventilation shall be provided when required. Each section shall include a single-piece
removable top plate.
F. The switchboard enclosure shall be painted on all exterior surfaces. The paint finish shall be ASA49
grey [unless otherwise specified].
G. Steel base channels shall be bolted to the frame to rigidly support the entire shipping section for
moving on rollers and for floor mounting. An option of a steel base channel shall be made available
2.04 BUSSING
B. The through bus shall have a maximum ampacity of [400A] [600A] [800A] [1,000A] [1,200A] [1,600A]
[2,000A] [2500A] [3,000A] [4,000A] [5,000A] [6,000A]. The switchboard bussing shall be of sufficient
cross-sectional area to meet the CSA C22.2 No. 31 standard for temperature rise.
C. The switchboard shall be rated with a minimum short circuit rating of [14,000A] [18,000A] [22,000A]
[25,000A] [30,000A] [35,000A] [42,000A] [50,000A] [65,000A] [100,000A] [200,000A] at [240Vac]
[480Vac] [600Vac].
F. The utility metering compartment shall have provisions for [window type] [bar type] current
transformers as supplied by the applicable public utility.
(Select A or B)
2. Bolted pressure contacts shall be made by providing an additional pressure or clamping action at
both ends of the switchblade when the blades are fully closed.
3. Manual operated switches shall have quick-make, quick-break front operating mechanisms.
A. [Main Metering]
1. Metering requirements that exceed the capabilities of the circuit breaker trip units shall use the
Schneider Electric [Powerlogic Circuit Monitor 4000T] [Powerlogic PM8244] [Powerlogic PM5563]
[Powerlogic ION7550] [Powerlogic ION7650] [Powerlogic ION8650]
2. CT’s shall be appropriately sized for use on the main
3. Separate HMI displays shall be mounted on [Main breaker door] [Instrument compartment door]
4. Meter integrated communication available via [Serial port] [Ethernet port] depending on meter
type.
B. [Communications]
1. Equipment can be selected with communications from among the following options [select 1]
1. For each [Main] [Tie] [or Feeder] circuit breaker, provide a Maintenance OFF ON selector switch
on the compartment door to switch the circuit breaker instantaneous tripping characteristics to an
alternate setting temporarily during maintenance activity.
2. Provide a lock feature for the ERMS switch so that it may be locked in either the OFF or ON
maintenance mode position.
3. Provide a blue LED indicating light to indicate trip unit is in the ERMS mode.
4. Wire contacts on all ERMS switches to a common alarm input to plant control system.
B. The manufacturer shall be required to include additional CT’s, ground fault relays, interlocks, wiring,
components etc. to insure the ground fault systems operates without nuisance tripping on the main
bus of the switchgear.
C. The manufacturer shall include a wiring diagram of the MDGF system along with a test procedure
using high current injection equipment.
3. Circuit breakers(s) shall have [10kA] [14 kA] [18 kA] [25 kA] [35 kA] [42 kA] [50 kA] [65 kA]
[100 kA] [125 kA] [200 kA] interrupting capacity at [240Vac] [480Vac] [600Vac]. Two tier
CSA or UL listed series ratings are acceptable. When series ratings are applied with integral
or remote upstream devices, a label or manual shall be provided showing the CSA or UL
approved series ratings including:
- Voltage
- Size and type of upstream fuses or breakers
- Size and type of branch devices that can be used
4. Circuit breaker(s) shall be group mounted plug-on with mechanical restraint on a common
pan or rail assembly.
5. The interior shall have three flat bus bars stacked and aligned vertically with glass reinforced
polyester insulators laminated between phases. The molded polyester insulators shall
support and provide phase isolation to the entire length of bus.
6. Circuit breakers equipped with line terminal jaws shall not require additional external
mounting hardware. Circuit breakers shall be held in mounted position by a self-contained
bracket secured to the mounting pan by fasteners. Circuit breakers of different frame sizes
shall be capable of being mounted across from each other.
8. All unused spaces provided, unless otherwise specified, shall be fully equipped for future
devices, including all appropriate connectors and mounting hardware.
(Select Electronic trip 100%, Electronic trip 80% or Thermal Magnetic)
a. [Electronic trip molded case full function 100% rated circuit breakers]
(i) All electronic circuit breakers shall have the following time/current response
adjustments: Long Time Pickup, Long Time Delay, [Short Time Pickup], [Short Time
Delay], [Ground Fault Pickup] [Ground Fault Delay] and Instantaneous settings.
Each adjustment shall have discrete settings (fully adjustable) and shall be
independent of all other adjustments.
(ii) Circuit breaker trip system shall be a microprocessor-based true RMS sensing
designed with sensing accuracy through the thirteenth (13th) harmonic. Sensor
ampere ratings shall be as indicated on the associated [schedule] [drawing].
(iii) Local visual trip indication for overload, short circuit and ground fault trip occurrences.
(iv) Long Time Pickup indication to signal when loading approaches or exceeds the
adjustable ampere rating of the circuit breaker shall be provided.
(v) Communications capabilities for remote monitoring of circuit breaker trip system, to
include phase and ground fault currents, pre-trip alarm indication, switch settings,
and trip history information shall be provided.
(vi) Circuit breaker shall be provided with Zone Selective Interlocking (ZSI)
communications capabilities on the short-time and ground fault functions compatible
with all other electronic trip circuit breakers and external ground fault sensing
systems as noted on [schedules] [drawings].
(vii) Furnish thermal magnetic molded case circuit breakers for 250A frames and below.
b. [Electronic trip molded case standard function 80% rated circuit breakers]
(i) All electronic circuit breakers shall have the following time/current response
adjustments: Long Time Pickup, Long Time Delay, [Short Time Pickup], [Short Time
Delay], [Ground Fault Pickup] [Ground Fault Delay] and Instantaneous settings.
Each adjustment shall have discrete settings (fully adjustable) and shall be
independent of all other adjustments.
(ii) Circuit breaker trip system shall be a microprocessor-based true RMS sensing
designed with sensing accuracy through the thirteenth (13th) harmonic. Sensor
ampere ratings shall be as indicated on the associated [schedule] [drawing].
(iii) Local visual trip indication for overload, short circuit and ground fault trip occurrences.
(iv) Long Time Pickup indication to signal when loading approaches or exceeds the
adjustable ampere rating of the circuit breaker shall be provided.
(v) Furnish thermal magnetic molded case circuit breakers for 250A frames and below.
(i) Molded case circuit breakers shall have integral thermal and instantaneous magnetic
trip in each pole.
(ii) Circuit protective devices shall be Square D molded case circuit breakers. Circuit
breakers shall have [10kA] [14kA] [18kA] [25kA] [35kA] [50kA] [65kA] [100kA] [125kA]
[200kA] [True current limiting*] interrupting capacity at [240Vac] [480Vac] [600Vac].
Ampere ratings shall be as shown on the drawings.
* Manufacturer shall submit one set of published Ip and I²t let-through curves (as
required by CSA or UL) to the owner.
PART 3 EXECUTION
3.01 INSTALLATION
A. Install switchboards in accordance with manufacturer's written instructions, and applicable standards
and safety codes.
B. Measure steady state load currents at each switchboard feeder; rearrange circuits in the switchboard
to balance the phase loads within 20% of each other. Maintain proper phasing for multi-wire branch
circuits.
C. Check tightness of bolted connections and circuit breaker connections using calibrated torque
wrench or torque screwdriver per manufacturer's written specifications.
END OF SECTION
Note: This specification was previously listed under Division 16, but has been updated to Division 26 as per
MasterFormatTM November 2004 Edition.
Revision Table
Date Author Description
October 6th 2016 Matei Anghel - Added Revision Table
- Added section 2.02 Terminations
Nov 2nd 2016 Matei Anghel - Updated metering and accessories section (2.07)
- Update section 2.03
May 12 2016 Matei Anghel Update 2.03 D: type 3R enclosure with ‘Canadian Winter’ option