SECTION 26.24.13.

10 LOW VOLTAGE SWITCHBOARD

PART 1 GENERAL
1.01 SECTION INCLUDES

A. Low Voltage Switchboard – Furnish and install switchboard(s) as specified herein and where shown
on the associated [schedules] [drawings].

1.02 REFERENCES

The switchboard(s) and overcurrent protection device(s) referenced herein are designed and
manufactured according to the latest revision of the following specifications.

A. Switchgear assemblies: CSA C22.2 No.31


B. UL891
C. Panelboards: CSA C22.2 No.29
D. Molded Case Circuit Breakers: CSA C22.2 No. 5
E. UL489
F. Enclosed Switches: CSA C22.2 No. 4

1.03 SUBMITTAL AND RECORD DOCUMENTATION

A. Approval documents shall include drawings. Drawings shall indicate front and side enclosure
elevations with overall dimensions shown; conduit entrance location and requirements, single-line
diagrams, equipment schedule and switchboard instrument details.

1.04 QUALIFICATIONS

A. Company specializing in manufacturing of switchboard products with a minimum of fifty (50) years
documented experience.

B. Switchboards shall be manufactured in accordance with standards listed Article 1.02 –


REFERENCES.

1.05 DELIVERY, STORAGE, AND HANDLING

A. Inspect and report concealed damage to carrier within their required time period.

B. Handle carefully to avoid damage to switchboard internal components, enclosure, and finish.

C. Store in a clean, dry environment. Maintain factory packaging and, if required, provide an additional
heavy canvas or heavy plastic cover to protect enclosure(s) from dirt, water, construction debris, and
traffic.

1.06 OPERATIONS AND MAINTENANCE MATERIALS

A. Manufacturer shall provide installation instructions:


- Instructions for Safe Installation, Operation and Maintenance of Switchboards Rated 600 Volts
or less.

1.07 WARRANTY

A. Manufacturer shall warrant specified equipment free from defects in materials and workmanship for

MasterFormat 2004
Number: 26 24 13
October 2016
the lesser of one (1) year from the date of installation or eighteen (18) months from the date of
purchase.

1.08 RELATED SPECIFICATIONS

A. Section 260526 – Grounding and Bonding


B. Section 261313 – Enclosed Circuit Breakers
C. Section 262313 – Enclosed Switches
D. Section 262416 – Panelboards
E. Section 264300 – Surge Protective Device (SPD)
F. Section 262300 – Low-Voltage Switchgear
G. Section 26091380 – Web Enabled Power Distribution
H. Section 26091310 – Electrical Power Monitoring and Control

PART 2 PRODUCTS
2.01 MANUFACTURERS

A. Shall be Square D Company

B. Substitutions must be submitted in writing three weeks prior to original bid date with supporting
documentation demonstrating that the alternate manufacturer meets all aspects of the specification
herein.

2.02 TERMINATIONS

A. Termination lugs shall be CSA/UL Listed to accept solid or stranded [copper and aluminum
conductors] [copper conductors only]. Termination lugs shall be suitable for cables sized per the 75C
column of the CE Code table. It is permissible for primary cables terminating in a bussed auxiliary
section to be sized to the 90C column of the CE Code.

2.03 ENCLOSURE

A. The switchboard shall be totally enclosed, dead front, freestanding or freestanding wall supported and
rear aligned with front, side or rear access.

B. The switchboard shall be [NEMA Type 1 - General Purpose] [NEMA Type 1 – with drip hood] [NEMA
Type 3R - Rainproof].

C. NEMA Type 1 enclosure shall be [standard] [Sprinkler Protection CEC26-008]

D. NEMA Type 3R enclosure shall be [Standard] [Canadian winter]. [Canadian Winter] Type 3R will
come equipped with bottom closure plates, enclosure heater, and wind barriers mounted atop existing
ventilation on each section. These modifications are intended to provide an extra degree of protection
against wind-blown snow; however, they do not guarantee protection in harsh winter conditions.

E. The framework shall be formed steel and secured together to support all cover plates, bussing and
component devices during shipment and installation. All closure plates are to be single tool, screw
removable. Ventilation shall be provided when required. Each section shall include a single-piece
removable top plate.

F. The switchboard enclosure shall be painted on all exterior surfaces. The paint finish shall be ASA49
grey [unless otherwise specified].
G. Steel base channels shall be bolted to the frame to rigidly support the entire shipping section for
moving on rollers and for floor mounting. An option of a steel base channel shall be made available

2.04 BUSSING

A. The switchboard shall be [silver-plated copper] [tin-plated copper].

B. The through bus shall have a maximum ampacity of [400A] [600A] [800A] [1,000A] [1,200A] [1,600A]
[2,000A] [2500A] [3,000A] [4,000A] [5,000A] [6,000A]. The switchboard bussing shall be of sufficient
cross-sectional area to meet the CSA C22.2 No. 31 standard for temperature rise.

C. The switchboard shall be rated with a minimum short circuit rating of [14,000A] [18,000A] [22,000A]
[25,000A] [30,000A] [35,000A] [42,000A] [50,000A] [65,000A] [100,000A] [200,000A] at [240Vac]
[480Vac] [600Vac].

D. Provisions shall be made for future splicing of additional sections.

E. All bolts used on bus bar joints shall be a minimum of grade 5.

F. The utility metering compartment shall have provisions for [window type] [bar type] current
transformers as supplied by the applicable public utility.

2.05 MAIN DISCONNECT DEVICES

(Select A or B)

A. [Main Circuit Breaker]


(Select 1, 2, or 3)

1. [Electronic trip molded case, full function, circuit breaker]


(Select a. or b.)
[a. Shall be rated for 80% continuous current and be PowerPact P or R style
breaker with MICROLOGIC trip system.]
[b. Shall be rated for 100% continuous current and be PowerPact P or R style
breaker with MICROLOGIC trip system.]
c. Rated ampacity shall be [800A] [1,200A] [1,600A] [2,000A] [2,500A]

2. [Thermal magnetic molded case circuit breaker]


a. Shall be rated for 80% continuous current and be PowerPact M, P or R style breaker
with standard electronic trip system.
b. Rated ampacity shall be [800A] [1,000A] [1,200A] [1,600A][2,000A] [2,500A]

3. [Stored energy electronic trip insulated case circuit breaker]


a. Shall be a MASTERPACT NW, two-step stored energy circuit breaker.
b. Rated ampacity shall be [800A] [1,000A] [1,200A] [1,600A] [2,000A][2,500A] [3,000A]
[4,000A] [5,000A] [6,000A].
c. Circuit breaker(s) shall have [10kA] [14kA] [18kA] [25kA] [35kA] [42kA] [50kA] [65kA]
[85kA] [100kA] [125kA] [200kA] interrupting capacity at [240Vac] [480Vac] [600Vac].
d. Shall be rated for 100% continuous current.
e. Provide a fixed instantaneous (High Level Selective Override) circuit on breaker(s).
The circuit shall have a defeatable instantaneous adjustment to allow the breaker to
remain closed for up to 30 cycles during overcurrents below the rms symmetrical
short time withstand ratings. The circuit shall instantaneously trip when current
levels exceed applicable withstand ratings.
f. Electronic Trip System
i. Circuit breaker trip system shall be a MICROLOGIC electronic trip unit.
ii. All trip units shall be removable to allow for field upgrades.
iii. Trip Units shall incorporate “True RMS Sensing”, and have LED long-time pickup
indications.
iv. MICROLOGIC trip unit functions shall consist of adjustable long-time pickup and delay,
[optional short-time pickup and delay], instantaneous [optional neutral protection and
optional ground-fault pickup and delay].
v. Adjustable long-time pickup (Ir) and delay shall be available in an adjustable rating plug
that is UL Listed as field-replaceable. Adjustable rating plug shall allow for nine long-time
pickup settings from 0.4 to 1 times the sensor plug (In). Other adjustable rating plugs
shall be available for more precise settings to match the application. Long-time delay
settings shall be in nine bands from 0.5–24 seconds at six times Ir.
vi. [Short-time pickup shall allow for nine settings from 1.5 to 10 times Ir. Short-time delay
shall be in nine bands from 0.1–0.4 I 2 t ON and 0–0.4 I 2 t OFF.]
vii. Instantaneous settings on the trip units with LSI protection shall be available in nine
bands from 2 to 15 times In. [The Instantaneous setting shall also have an OFF setting
when short-time pick-up is provided.]
viii. All trip units shall have the capability for the adjustments to be set and read locally by
rotating a switch. [Optional: trip units shall have the capability to electronically adjust the
settings locally and remotely to fine increments below the switch settings. Fine
increments for pickup adjustments are to be one ampere. Fine increments for delay
adjustments are to be one second.]
ix. Trip unit shall provide local trip indication [and capability to indicate local and remote
reason for trip, i.e., overload, short circuit or ground fault.]
x. [Ground-fault protection shall be available for solidly grounded three-phase, three-wire or
three-phase, four-wire systems. Trip unit shall be capable of the following types of
ground-fault protection: residual, source ground return, and modified differential. Ground-
fault sensing systems may be changed in the field.]
xi. [Ground-fault settings for circuit breaker sensor sizes 1200 A or below shall be in nine
bands from 0.2 to 1.0 times In. The ground-fault settings for circuit breakers above 1200
A shall be nine bands from 500 to 1200 A.]
xii. [Neutral current transformers shall be available for four-wire systems.]
xiii. [Trip units shall be capable of communicating on four wire MODBUS ® networks without
software interfaces (black boxes).]
xiv. [Trip units shall be available to provide additional protection by offering adjustable inverse
definite minimum time lag (IDMTL). IDMTL provides optimized coordination by the
adjustment of the slope of the long-time delay protection.]
xv. [Trip units shall be available to provide real time metering. Metering functions include
current, voltage, power and frequency. Metering accuracy shall be 1.5% current, 0.5%
voltage, and 2% power. These accuracies include CT and meter.]
xvi. [Trip units shall be available to provide harmonic analysis and waveform capture.]
xvii. A means to seal the trip unit adjustments in accordance with NEC Section 240-6(b) shall
be provided.
xviii. The following table indicates the standard and optional features of the Trip Units. Select
the appropriate trip unit (s) for the system performance desired.

Micrologic Trip Unit Series


Features Standard A P H
True RMS Sensing X X X X
LI X X X X
LSI o o X X
LSIG/Ground –Fault Trip o o o
Ground Fault Alarm (no trip) X X
Ground Fault Trip and Programming Alarm o o
Adjustable Rating Plugs X X X X
LED - Long-time Pickup X X X X
LED - Trip indication X X X
Digital Ammeter X X X
Phase loading Bar Graph X X X
Zone Selective Interlocking X X X
Communications o X X
LCD Dot Matrix Display X X
Advanced User Interface X X
Protective Relay Functions X X
Thermal Imaging X X
Neutral Protection X X
Electronic Contact Wear Indication X X
Temperature Indication X X
Incremental Fine Tuning of Settings X X
Selectable Long-time Delay Bands X X
Power Measurement X X
Waveform Capture X
Data Logging X
X=Standard o=Option

[B. Main Fusible Switch]


1. Shall be [QMQB type fusible switch 400 through 1,200A] [BOLT-LOC fixed mounted bolted pressure
switch 1,600 through 3,000A].

2. Bolted pressure contacts shall be made by providing an additional pressure or clamping action at
both ends of the switchblade when the blades are fully closed.

3. Manual operated switches shall have quick-make, quick-break front operating mechanisms.

4. Accessories shall be supplied as follows:


[Capacitor trip power supply]
[Blown main fuse indication]
[Phase failure relay with capacitor trip power supply]
[Key interlock]
5. [Equipment ground fault protection]
a. Provide a zero sequence type ground fault system including current sensor and appropriate
relaying equipment. The current sensor shall enclose all phase (and neutral, if present)
conductors to be monitored. The current sensor frame shall be so constructed that one leg can be
opened to allow the removal of the sensor without disturbing the cables or requiring drop-links in
the bussing. A test winding shall be provided to simulate the flow of ground fault current through
the current sensor for testing.
b. The ground fault relay shall be of solid state construction and have adjustable pick-up for ground
fault currents from 100 amperes to 1200 amperes.

2.06 SWITCHBOARD - AUTOMATIC THROW-OVER SYSTEM


[Select A or B or C]
A. Main-Main Automatic Throwover System
( Bold designates standard time-delays or percentages)
1. Main-Main standard functions shall include the following:
a. Automatic Transfer to Alternate Source, Manual Return to Normal Source for Main-Main
b. Open Transition with control program interlocking to prevent paralleling
c. Bypass of Retransfer delay if alternate source fails
d. Electrically Interlocked
e. Manual Circuit Breaker Close Buttons Inhibited
f. Time Delay On Transfer [ 5 seconds ] [ seconds]
g. [[ 2] [ ] Second Time Delay On Retransfer, Open Transition]] [ 2 Second Time Delay On
Retransfer, Closed Transition]]
h. Source Stabilization Before Retransfer [[ 10] [ ]seconds]
i. Undervoltage sensing on Both Sources(27 Device) , [ 10% ] [14%] [17%] [20%] differential,
strap adjustable with local LED indication
j. Phase Sequence( reverse phase) Sensing on Both Sources(47 Device) , 2 cycles with local
LED indication
k. Phase Loss(47 Device), 68% of nominal with local LED indication
l. Phase Imbalance(47 Device) [ 2% ] [ 3% ] [ 3.5% ] [ 4% ] Strap Adjustable with local LED
indication
m. Auto / Manual Switch with Removable Key and light indication
n. 1. White Light for Auto
o. 2. Blue Light for Manual
p. Control Power Transfer Between Sources
q. Full Automatic Mode with Drawout Breakers in the Test Position
r. Open(Green)/Close(Red) Lighted Push Buttons for Manual Operation of the Circuit
Breakers
s. Test Switch for Simulating Loss of either Source
t. Circuit Breaker Electrical Trip Lockout with Amber Light indication
u. Uninterruptible Power Supply for 120Vac Control Power
v. UPS Bypass relay
w. White Lights for Sources Available
x. Operator Interface Panel
y. Wire Labels for Control Wiring
z. Fused Control Circuits With Individual Blown Fuse Indication
1. Optional Functions shall include the following:
a. Automatic Return from Alternate Source for Main-Main
b. Remote Alarm Contact ( System Inoperative), 5A @ 120Vac
c. Closed Transition on Retransfer
d. Sync Check(25), 2 seconds maximum paralleling when sources synchronized, Voltage [ 30
% ] [ %] adjustable(10-30%), phase relationship is 6 to 20 and frequency is 0.15 Hz to 0.5
Hz
e. Preferred Source Selector
f. Pilot Lights Test Switch
2. Documentation shall include the following:
a. Wiring diagram of each assembly in system.
b. System schematic diagram.
c. Input/Output listing.
d. Sequence of operation.
e. Test procedures.
3. The manufacturer shall provide a qualified service representative for one day to initialize the
automatic throwover system.
B. Main-Generator
(Bold designates standard time-delays or percentages)
1. Standard functions shall include the following:
a. Automatic Transfer to Alternate Source, Automatic Re-transfer to Normal Source for Main-
Generator
b. Open Transition with control program interlocking to prevent paralleling
c. Bypass of Retransfer delay if alternate source fails
d. Electrically Interlocked
e. Manual Circuit Breaker Close Buttons Inhibited
f. Time Delay On Transfer [5 seconds] [ seconds]
g. [[ 2] [ ] Second Time Delay On Retransfer, Open Transition]] [ 2 Second Time Delay On
Retransfer, Closed Transition]]
h. Source Stabilization Before Retransfer [[ 10] [ ]seconds]
i. Undervoltage sensing on Both Sources(27 Device) , [ 10% ] [14%] [17%] [20%] differential,
strap adjustable with local LED indication
j. Phase Sequence( reverse phase) Sensing on Both Sources(47 Device) , 2 cycles with local
LED indication
k. Phase Loss(47 Device), 68% of nominal with local LED indication
l. Phase Imbalance(47 Device) [ 2% ] [ 3% ] [ 3.5% ] [ 4% ] Strap Adjustable with local LED
indication
m. Auto / Manual Switch with Removable Key and light indication
n. 1. White Light for Auto
o. 2. Blue Light for Manual
p. Control Power Transfer Between Sources
q. Full Automatic Mode with Drawout Breakers in the Test Position
r. Open(Green)/Close(Red) Lighted Push Buttons for Manual Operation of the Circuit
Breakers
s. Test Switch for Simulating Loss of either Source
t. Circuit Breaker Electrical Trip Lockout with Amber Light indication
u. Uninterruptible Power Supply for 120Vac Control Power
v. UPS Bypass relay
w. White Lights for Sources Available
x. Operator Interface Panel
y. Wire Labels for Control Wiring
z. Fused Control Circuits With Individual Blown Fuse Indication
aa. Overvoltage sensing on Generator (59 Relay), [ 125 % ] [ % ] of nominal( 100-125%), [ 15%
] [ % ]differential(1-15%), adjustable for Main -Generator]
bb. Frequency Sensing on Generator (81 Relay), 60 Hz, [ 3 Hz ] [ ] differential( 0.1-3 Hz),
adjustable for Main-Generator
cc. Engine Start Contacts, 5A @ 120Vac for Main-Generator

2. Optional functions shall include the following:


a. Remote Alarm Contact (System Inoperative), 5A @ 120Vac
b. Closed Transition on Retransfer
c. Sync Check (25), 2 seconds maximum paralleling when sources synchronized, Voltage [30
%] [ %] adjustable (10-30%), phase relationship is 6 to 20 and frequency is 0.15 Hz to 0.5
Hz
d. Pilot Lights Test Switch
e. Time Delay for Engine Cool down, [15 minutes] [ minutes] unloaded
f. Engine Generator Exercising [Loaded] [Unloaded], [30 minutes] [ minutes] once per week
3. Documentation shall include the following:
a. Wiring diagram of each assembly in system.
b. System schematic diagram.
c. Input/Output listing.
d. Sequence of operation.
e. Test procedures.
4. The manufacturer shall provide a qualified service representative for one day to initialize the
automatic throwover system.
C. Main-Tie-Main
(Bold designates standard time-delays or percentages)
1. Standard functions shall include the following:
a. Automatic Transfer to Alternate Source, Automatic Re-transfer to Normal Source for Main-
Tie-Main
b. Open Transition with control program interlocking to prevent paralleling
c. Bypass of Retransfer delay if alternate source fails
d. Electrically Interlocked
e. Manual Circuit Breaker Close Buttons Inhibited
f. Time Delay On Transfer [ 5 seconds] [ seconds]
g. [[ 2] [ ] Second Time Delay On Retransfer, Open Transition]] [ 2 Second Time Delay On
Retransfer, Closed Transition]]
h. Source Stabilization Before Retransfer [[ 10] [ ]seconds]
i. Undervoltage sensing on Both Sources (27 Device) , [ 10% ] [14%] [17%] [20%] differential,
strap adjustable with local LED indication
j. Phase Sequence (reverse phase) Sensing on Both Sources(47 Device) , 2 cycles with local
LED indication
k. Phase Loss (47 Device), 68% of nominal with local LED indication
l. Phase Imbalance (47 Device) [ 2% ] [ 3% ] [ 3.5% ] [ 4% ] Strap Adjustable with local LED
indication
m. Auto / Manual Switch with Removable Key and light indication
n. 1. White Light for Auto
o. 2. Blue Light for Manual
p. Control Power Transfer Between Sources
q. Full Automatic Mode with Drawout Breakers in the Test Position
r. Open(Green)/Close(Red) Lighted Push Buttons for Manual Operation of the Circuit Breakers
s. Test Switch for Simulating Loss of either Source
t. Circuit Breaker Electrical Trip Lockout with Amber Light indication
u. Uninterruptible Power Supply for 120Vac Control Power
v. UPS Bypass relay
w. White Lights for Sources Available
x. Operator Interface Panel
y. Wire Labels for Control Wiring
z. Fused Control Circuits with Individual Blown Fuse Indication
2. Optional Functions shall include the following:
a. Manual Retransfer to Normal Switch for Main-tie-Main
b. Remote Alarm Contact (System Inoperative), 5A @ 120Vac
c. Closed Transition on Retransfer
d. Sync Check (25), 2 seconds maximum paralleling when sources synchronized, Voltage [30
%] [ %] adjustable(10-30%), phase relationship is 6 to 20 and frequency is 0.15 Hz to 0.5
Hz
e. Preferred Source Selector
f. Pilot Lights Test Switch
3. Documentation shall include the following:
a. Wiring diagram of each assembly in system.
b. System schematic diagram.
c. Input/Output listing.
d. Sequence of operation.
e. Test procedures.
The manufacturer shall provide a qualified service representative for one day to initialize the
automatic throwover system

2.07 Metering and Accessories

A. [Main Metering]

1. Metering requirements that exceed the capabilities of the circuit breaker trip units shall use the
Schneider Electric [Powerlogic Circuit Monitor 4000T] [Powerlogic PM8244] [Powerlogic PM5563]
[Powerlogic ION7550] [Powerlogic ION7650] [Powerlogic ION8650]
2. CT’s shall be appropriately sized for use on the main

3. Separate HMI displays shall be mounted on [Main breaker door] [Instrument compartment door]

4. Meter integrated communication available via [Serial port] [Ethernet port] depending on meter
type.

B. [Communications]

1. Equipment can be selected with communications from among the following options [select 1]

a. [Modbus RS48, without device Web pages]

b. [Modbus RS48, with device Web pages]

c. [Modbus RS485 to Ethernet Modbus TCP]

d. [Direct Ethernet Modbus/TCP]

C. [Energy Reduction Maintenance Setting Switch (ERMS)]

1. For each [Main] [Tie] [or Feeder] circuit breaker, provide a Maintenance OFF ON selector switch
on the compartment door to switch the circuit breaker instantaneous tripping characteristics to an
alternate setting temporarily during maintenance activity.

2. Provide a lock feature for the ERMS switch so that it may be locked in either the OFF or ON
maintenance mode position.

3. Provide a blue LED indicating light to indicate trip unit is in the ERMS mode.

4. Wire contacts on all ERMS switches to a common alarm input to plant control system.

2.08 GROUND FAULT PROTECTION


Optional: [Modified differential ground fault protection (MDGF) should be specified on 3PH, 4W systems
when switchboard equipment is connected and grounded to multiple sources, including transformer and
generator sources. This is common on Main-Tie-Main, Main-Tie-Main-Tie-Main, Main-Tie-Generator-Tie-
Main, etc., systems.
Without MDGF circulating currents on the neutral buses can cause nuisance tripping on the tie or main
breakers when systems have multiple grounding points. To obtain a properly operating GF system
equipment manufacturers are required to add additional current transformers (CT’s), ground fault relays
and secondary CT wiring so that the equipment will sense “differential” circulating currents and trip the
proper breakers. Lead times on the equipment may be extended due to additional components, wiring
and testing that are required in the manufacturer’s process. The addition of MDGF assures the
equipment that is shipped has a properly operating GF system.]
A. 3-phase 4-wire, connected equipment having multiple sources shall have a modified differential
ground fault system (MDGF). The manufacturer shall complete the MDGF design prior to building
equipment to insure that the proper main or tie breaker (s) operate properly during the following
occurrences on the main bus.
1. Insure the system will trip with the occurrence of a ground fault at any location in the switchgear.
2. Insure system will not trip without ground fault and with normal current flow.
3. Insure system will not trip due to large single-phase currents.
4. Insure system will trip with combination of normal current flow and ground fault current flowing
together.
5. Insure system will not trip with circulating currents through the neutral due to multiple grounds and
sources external to the immediate low voltage power sources.

B. The manufacturer shall be required to include additional CT’s, ground fault relays, interlocks, wiring,
components etc. to insure the ground fault systems operates without nuisance tripping on the main
bus of the switchgear.
C. The manufacturer shall include a wiring diagram of the MDGF system along with a test procedure
using high current injection equipment.

2.09 DISTRIBUTION SECTION DEVICES

A. Group mounted circuit breakers through 1200A


1. Breakers and all components shall be designed, manufactured and tested in accordance
with applicable UL and CSA standards.

2. Circuit breaker(s) shall be rated for 80% continuous current.

3. Circuit breakers(s) shall have [10kA] [14 kA] [18 kA] [25 kA] [35 kA] [42 kA] [50 kA] [65 kA]
[100 kA] [125 kA] [200 kA] interrupting capacity at [240Vac] [480Vac] [600Vac]. Two tier
CSA or UL listed series ratings are acceptable. When series ratings are applied with integral
or remote upstream devices, a label or manual shall be provided showing the CSA or UL
approved series ratings including:
- Voltage
- Size and type of upstream fuses or breakers
- Size and type of branch devices that can be used

4. Circuit breaker(s) shall be group mounted plug-on with mechanical restraint on a common
pan or rail assembly.

5. The interior shall have three flat bus bars stacked and aligned vertically with glass reinforced
polyester insulators laminated between phases. The molded polyester insulators shall
support and provide phase isolation to the entire length of bus.

6. Circuit breakers equipped with line terminal jaws shall not require additional external
mounting hardware. Circuit breakers shall be held in mounted position by a self-contained
bracket secured to the mounting pan by fasteners. Circuit breakers of different frame sizes
shall be capable of being mounted across from each other.

7. Line-side circuit breaker connections are to be jaw type.

8. All unused spaces provided, unless otherwise specified, shall be fully equipped for future
devices, including all appropriate connectors and mounting hardware.
(Select Electronic trip 100%, Electronic trip 80% or Thermal Magnetic)
a. [Electronic trip molded case full function 100% rated circuit breakers]

(i) All electronic circuit breakers shall have the following time/current response
adjustments: Long Time Pickup, Long Time Delay, [Short Time Pickup], [Short Time
Delay], [Ground Fault Pickup] [Ground Fault Delay] and Instantaneous settings.
Each adjustment shall have discrete settings (fully adjustable) and shall be
independent of all other adjustments.

(ii) Circuit breaker trip system shall be a microprocessor-based true RMS sensing
designed with sensing accuracy through the thirteenth (13th) harmonic. Sensor
ampere ratings shall be as indicated on the associated [schedule] [drawing].
(iii) Local visual trip indication for overload, short circuit and ground fault trip occurrences.

(iv) Long Time Pickup indication to signal when loading approaches or exceeds the
adjustable ampere rating of the circuit breaker shall be provided.

(v) Communications capabilities for remote monitoring of circuit breaker trip system, to
include phase and ground fault currents, pre-trip alarm indication, switch settings,
and trip history information shall be provided.

(vi) Circuit breaker shall be provided with Zone Selective Interlocking (ZSI)
communications capabilities on the short-time and ground fault functions compatible
with all other electronic trip circuit breakers and external ground fault sensing
systems as noted on [schedules] [drawings].

(vii) Furnish thermal magnetic molded case circuit breakers for 250A frames and below.

b. [Electronic trip molded case standard function 80% rated circuit breakers]

(i) All electronic circuit breakers shall have the following time/current response
adjustments: Long Time Pickup, Long Time Delay, [Short Time Pickup], [Short Time
Delay], [Ground Fault Pickup] [Ground Fault Delay] and Instantaneous settings.
Each adjustment shall have discrete settings (fully adjustable) and shall be
independent of all other adjustments.

(ii) Circuit breaker trip system shall be a microprocessor-based true RMS sensing
designed with sensing accuracy through the thirteenth (13th) harmonic. Sensor
ampere ratings shall be as indicated on the associated [schedule] [drawing].

(iii) Local visual trip indication for overload, short circuit and ground fault trip occurrences.

(iv) Long Time Pickup indication to signal when loading approaches or exceeds the
adjustable ampere rating of the circuit breaker shall be provided.

(v) Furnish thermal magnetic molded case circuit breakers for 250A frames and below.

c. [Thermal magnetic molded case circuit breakers]

(i) Molded case circuit breakers shall have integral thermal and instantaneous magnetic
trip in each pole.

(ii) Circuit protective devices shall be Square D molded case circuit breakers. Circuit
breakers shall have [10kA] [14kA] [18kA] [25kA] [35kA] [50kA] [65kA] [100kA] [125kA]
[200kA] [True current limiting*] interrupting capacity at [240Vac] [480Vac] [600Vac].
Ampere ratings shall be as shown on the drawings.
* Manufacturer shall submit one set of published Ip and I²t let-through curves (as
required by CSA or UL) to the owner.

PART 3 EXECUTION
3.01 INSTALLATION

A. Install switchboards in accordance with manufacturer's written instructions, and applicable standards
and safety codes.

3.02 FIELD QUALITY CONTROL


A. Inspect complete installation for physical damage, proper alignment, anchorage, and grounding.

B. Measure steady state load currents at each switchboard feeder; rearrange circuits in the switchboard
to balance the phase loads within 20% of each other. Maintain proper phasing for multi-wire branch
circuits.

C. Check tightness of bolted connections and circuit breaker connections using calibrated torque
wrench or torque screwdriver per manufacturer's written specifications.

END OF SECTION

Note: This specification was previously listed under Division 16, but has been updated to Division 26 as per
MasterFormatTM November 2004 Edition.
Revision Table
Date Author Description
October 6th 2016 Matei Anghel - Added Revision Table
- Added section 2.02 Terminations
Nov 2nd 2016 Matei Anghel - Updated metering and accessories section (2.07)
- Update section 2.03
May 12 2016 Matei Anghel Update 2.03 D: type 3R enclosure with ‘Canadian Winter’ option