Documente Academic
Documente Profesional
Documente Cultură
INTRODUCTION
Parallel Chords, Underslung
Longspan and Deep Longspan Steel Joists are relatively
lightweight shop-fabricated steel trusses. Longspan Steel
Joists are used for the direct support of floor or roof slabs
or decks between walls, beams, and main structural mem- Parallel Chords, Square Ends
bers. Deep Longspan Steel Joists are used for the direct
support of roof slabs or decks between walls, beams and
main structural members.
The LH- and DLH-Series have been designed for the pur- Top Chord Pitched One Way, Underslung
pose of extending the use of joists to spans in excess of
those covered by Open Web Joists.
Longspan Series Joists have been standardized in depths
from 18" (457 mm) through 48" (1219 mm), for clear spans Top Chord Pitched One Way, Square Ends
through 96 feet (29260 mm).
Deep Longspan Series Joists have been standardized in
depths from 52" (1321 mm) through 72" (1829 mm), for
clear spans up through 144 feet (43891 mm). Top Chord Pitched Two Ways, Underslung
STANDARD TYPES
Top Chord Pitched Two Ways, Square Ends
Longspan and Deep Longspan Steel Joists can be
The illustrations above indicate Longspan and Deep
furnished with either underslung or square ends, with par-
Longspan Steel Joists with modified WARREN type web
allel chords or with single or double pitched top chords to
systems. However, the web systems may be any type,
provide sufficient slope for roof drainage. Square end joists
whichever is standard with the manufacturer furnishing the
are primarily intended for bottom chord bearing.
product.
Sloped parallel-chord joists shall use span as defined by
the length along the slope. The joist designation is deter-
mined by its nominal depth at the center of the span and by ACCESSORIES
the chord size designation.
The depth of the bearing seat at the ends of underslung
LH- DLH- Longspan Joists has been established at 5" (127
mm) for chord sizes #2 through #17. A bearing seat depth
of 7¹⁄₂ inches (191 mm) has been established for the DLH-
Series chord sizes #18 and #19. CEILING
EXTENSION
LONGSPAN AND DEEP
All Longspan and Deep Longspan Steel Joists are fabricat- LONGSPAN JOISTS FOR ROOF
CONSTRUCTION ON
ed with standardized camber as listed in paragraph 103.6. STRUCTURAL STEEL COLUMNS
41
STANDARD SPECIFICATIONS
FOR LONGSPAN STEEL JOISTS, LH-SERIES AND
DEEP LONGSPAN STEEL JOISTS, DLH-SERIES
ANSI Designation: SJI-LH/DLH-1.0
Adopted by the Steel Joist Institute February 15, 1978
Revised to May 1, 2000 – Effective August 1, 2002
42
LONGSPAN AND DEEP LONGSPAN STEEL JOISTS, LH- AND DLH-SERIES
mechanical properties which conform to the requirements a specified minimum yield strength of 36 ksi (250
of one of the listed specifications, test specimens and pro- MPa), and the other having a specified minimum yield
cedure shall conform to those of such specifications and to strength greater than 36 ksi (250 MPa).
ASTM A370. AWS A5.1, E60XX
In the case of material, the mechanical properties which do AWS A5.17, FXX-EXXX flux electrode combination
not conform to the requirements of one of the listed speci- AWS A5.20, E60T-X
fications, the test specimens and procedures shall conform or any of those listed in Section 102.3(a).
to the applicable requirements of ASTM A370, and the
Other welding methods, providing equivalent strength as
specimens shall exhibit a yield strength equal to or exceed-
demonstrated by tests, may be used.
ing the design yield strength and an elongation of not less
than (a) 20 percent in 2 inches (51 mm) for sheet and strip, 102.4 PAINT
or (b) 18 percent in 8 inches (203 mm) for plates, shapes
and bars with adjustments for thickness for plates, shapes The standard shop paint is intended to protect the steel for
and bars as prescribed in ASTM A36/A36M, A242/A242M, only a short period of exposure in ordinary atmospheric
A529/A529M, A572/A572M, A588/A588M, whichever conditions and shall be considered an impermanent and
specification is applicable on the basis of design yield provisional coating.
strength. When specified, the standard shop paint shall conform to
The number of tests shall be as prescribed in ASTM one of the following:
A6/A6M for plates, shapes, and bars; and ASTM (a) Steel Structures Painting Council Specification, SSPC
A570/A570M, A606, A607, and A611 for sheet and strip. No. 15
If as-formed strength is utilized, the test reports shall show (b) Or, shall be a shop paint which meets the minimum
the results of tests performed on full section specimens in performance requirements of the above listed specifi-
accordance with the provisions of the AISI Specifications cation.
for the Design of Cold formed Steel Structural Members
and shall indicate compliance with these provisions and SECTION 103.
with the following additional requirements: DESIGN AND
(a) The yield strength measured in the tests shall equal or
exceed the design yield strength.
MANUFACTURE
(b) Where tension tests are made for acceptance and con- 103.1 METHOD
trol purposes, the tensile strength shall be at least 6 Joists shall be designed in accordance with these specifi-
percent greater than the yield strength of the section. cations as simply supported, uniformly loaded trusses sup-
(c) Where compression tests are used for acceptance and porting a floor or roof deck so constructed as to brace the
control purposes, the specimen shall withstand a gross top chord of the joists against lateral buckling. Where any
shortening of 2 percent of its original length without applicable design feature is not specifically covered herein,
cracking. The length of the specimen shall be not the design shall be in accordance with the following speci-
greater than 20 times its least radius of gyration. fications.
(d) If any test specimen fails to pass the requirements of (a) American Institute of Steel Construction Specification
subparagraphs a, b, and c above, as applicable, two for Design, Fabrication and Erection of Structural Steel
retests shall be made of specimens from the same lot. for Buildings (Allowable Stress Design), where the
Failure of one of the retest specimens to meet such material used consists of plates, shapes or bars.
requirements shall be the cause for rejection of the lot (b) American Iron and Steel Institute Specification for the
represented by the specimens. Design of Cold-Formed Steel Structural Members, for
members which are formed from sheet or strip materi-
102.3 WELDING ELECTRODES
al.
The following electrodes shall be used for arc welding:
(a) For connected members both having a specified mini- 103.2 UNIT STRESSES
mum yield strength greater than 36 ksi (250 MPa). Joists shall have their components so proportioned that the
AWS A5.1 or A5.5, E70XX unit stresses in kips per square inch (Mega Pascals) shall
AWS A5.17, F7XX -EXXX flux electrode combination not exceed the following, where Fy is the yield strength
AWS A5.18, E70S-X or E7OU-1 defined in Section 102.2:
AWS A5.20, E7OT-X (a) Tension:
(b) For connected members both having a specified mini- All members.......................................Ft = 0.6Fy
mum yield strength of 36 ksi (250 MPa) or one having
43
LONGSPAN AND DEEP LONGSPAN STEEL JOISTS, LH- AND DLH-SERIES
Fa 12π 2E
=
23(K ! r )
2
44
LONGSPAN AND DEEP LONGSPAN STEEL JOISTS, LH- AND DLH-SERIES
ls = maximum length center-to-center between panel ry = member radius of gyration out of the plane of the joist.
point and filler (tie), or between adjacent fillers (ties). rz = least radius of gyration of a member component.
rx = member radius of gyration in the plane of the joist.
TABLE 103.3.1
MAXIMUM AND EFFECTIVE SLENDERNESS RATIOS
I TOP CHORD INTERIOR PANEL
A. The slenderness ratios, 1.0l/r and 1.0ls/r, of members as a whole or any component part shall not exceed 90.
45
LONGSPAN AND DEEP LONGSPAN STEEL JOISTS, LH- AND DLH-SERIES
46
LONGSPAN AND DEEP LONGSPAN STEEL JOISTS, LH- AND DLH-SERIES
47
LONGSPAN AND DEEP LONGSPAN STEEL JOISTS, LH- AND DLH-SERIES
48
LONGSPAN AND DEEP LONGSPAN STEEL JOISTS, LH- AND DLH-SERIES
The ends of all bridging lines terminating at walls or beams (e) Attachments
shall be anchored to resist the force shown in Table The spacing of attachments along the top chord shall
104.5.1. not exceed 36 inches (914 mm). Such attachments of
104.7 END ANCHORAGE the slab or deck to the top chords of joists shall be
capable of resisting the following forces:
(a) Masonry and Concrete
Ends of LH- and DLH-Series Joists resting on steel TABLE 104.9.1
bearing plates on masonry or structural concrete shall
be attached thereto with a minimum of two ¹⁄₄ inch (6 *Section Equivalent
mm) fillet welds 2 inches (51mm) long, or with two ³⁄₄ Number Force Required
inch (19mm) bolts or the equivalent. 02 to 04 incl. 120 lbs./ft. (1.75 kN/m)
(b) Steel 05 to 09 incl. 150 lbs./ft. (2.19 kN/m)
10 to 17 incl. 200 lbs./ft. (2.92 kN/m)
Ends of LH and DLH-Series Joists resting on steel 18 and 19 250 lbs./ft. (3.65 kN/m)
supports shall be attached thereto with a minimum of
two ¹⁄₄ inch (6mm) fillet welds 2 inches (51mm) or with * Last two digits of joist designation shown in Load Table.
two ³⁄₄ inch (19mm) bolts or the equivalent. In steel
frames, where columns are not framed in at least two (f) Wood Nailers
directions with structural steel members, bearing seats Where wood nailers are used, such nailers in conjunc-
for joists at column lines shall be fabricated to allow for tion with deck or slab shall be firmly attached to the top
field bolting. chords of the joists in conformance with Section
(c) Uplift 104.9(e).
Where uplift forces are a design consideration, roof (g) Joist With Standing Seam Roofing
joists shall be anchored to resist such forces. The stiffness and strength of standing-seam roof clips
104.8 JOIST SPACING varies from one manufacturer to another. Therefore,
some roof systems cannot be counted on to provide
Joists shall be spaced so that the loading on each joist lateral stability to the joists which support the roof.
does not exceed the allowable load given for the particular Sufficient stability must be provided to brace the joists
designation and clear span in the Load Table. laterally under the full design load. The compression
104.9 FLOOR AND ROOF DECKS chord must resist the chord axial design force in the
plane of the joist (i.e., x-x axis buckling) and out of the
(a) Material plane of the joist (i.e., y-y axis buckling). Out of plane
Floor and roof decks may consist of cast-in-place or strength may be achieved by adjusting the bridging
pre-cast concrete or gypsum, formed steel, wood, or spacing and/or increasing the compression chord
other suitable material capable of supporting the area, the joist depth, and the y-axis radius of gyration.
required load at the specified joist spacing. The effective slenderness ratio in the y-direction
(b) Thickness equals 0.94 L/ry; where L is the bridging spacing. The
maximum bridging spacing may not exceed that spec-
Cast-in-place slabs shall be not less than 2 inches (51
ified in Section 104.5d.
mm) thick.
Horizontal bridging members attached to the compres-
(c) Centering
sion chords and their anchorages must be designed
Centering for structural slabs may be ribbed metal lath, for a compressive axial force of 0.0025nP, where n is
corrugated steel sheets, paper-backed welded wire the number of joists between end anchors and P is the
fabric, removable centering or any other suitable mate- chord design force. The attachment force between the
rial capable of supporting the slab at the designated horizontal bridging member and the compression
joist spacing. Centering shall not cause lateral dis- chord is 0.005P. Horizontal bridging attached to the
placement or damage to the top chord of joists during tension chords shall be proportioned so that the slen-
installation or removal of the centering or placing of the derness ratio between attachments does not exceed
concrete. 300. Diagonal bridging shall be proportioned so that
(d) Bearing the slenderness ratio between attachments does not
Slabs or decks shall bear uniformly along the top exceed 200.
chords of the joists.
49
LONGSPAN AND DEEP LONGSPAN STEEL JOISTS, LH- AND DLH-SERIES
50
LONGSPAN AND DEEP LONGSPAN STEEL JOISTS, LH- AND DLH-SERIES
51
STANDARD LOAD TABLE
LONGSPAN STEEL JOISTS, LH-SERIES
Based on a Maximum Allowable Tensile Stress of 30 ksi
Adopted by the Steel Joist Institute May 25, 1983;
Revised to May 1, 2000 – Effective August 1, 2002
The black figures in the following table give the TOTAL safe Where the joist span is in the RED SHADED area of the
uniformly distributed load-carrying capacities, in pounds load table, the row of bridging nearest the midspan shall be
per linear foot, of LH-Series Steel Joists. The weight of diagonal bridging with bolted connections at chords and
DEAD loads, including the joists, must in all cases be intersection. Hoisting cables shall not be released until this
deducted to determine the LIVE load-carrying capacities of row of bolted diagonal bridging is completely installed.
the joists. The approximate DEAD load of the joists may be Where the joist span is in the BLUE SHADED area of the
determined from the weights per linear foot shown in the load table, all rows of bridging shall be diagonal bridging
tables. with bolted connections at chords and intersection. Hoisting
The RED figures in this load table are the LIVE loads per cables shall not be released until the two rows of bridging
linear foot of joist which will produce an approximate deflec- nearest the third points are completely installed.
tion of ¹⁄₃₆₀ of the span. LIVE loads which will produce a The approximate moment of inertia of the joist, in inches4 is;
deflection of ¹⁄₂₄₀ of the span may be obtained by multiply-
I j = 26.767(WLL)(L3)(10-6), where WLL = RED figure in the
ing the RED figures by 1.5. In no case shall the TOTAL load
Load Table, and L = (clear span + .67) in feet.
capacity of the joists be exceeded.
When holes are required in top or bottom chords, the car-
This load table applies to joists with either parallel chords or
rying capacities must be reduced in proportion to the reduc-
standard pitched top chords. When top chords are pitched,
tion of chord areas.
the carrying capacities are determined by the nominal
depth of the joists at the center of the span. Standard top The top chords are considered as being stayed laterally by
chord pitch is ¹⁄₈ inch per foot. If pitch exceeds this standard, floor slab or roof deck.
the load table does not apply. Sloped parallel-chord joists The approximate joist weights per linear foot shown in
shall use span as defined by the length along the slope. these tables do not include accessories.
52
STANDARD LOAD TABLE/LONG SPAN STEEL JOISTS, LH-SERIES
Based on a Maximum Allowable Tensile Stress of 30 ksi
53
STANDARD LOAD TABLE/LONG SPAN STEEL JOISTS, LH-SERIES
Based on a Maximum Allowable Tensile Stress of 30 ksi
* The safe uniform load for the clear spans shown in the minimum clear span listed in the Safe Load Column.
Safe Load Column is equal to (Safe Load)/(Clear span + * To solve for live loads for clear spans shown in the Safe
0.67). (The added 0.67 feet (8 inches) is required to Load Column (or lesser clear spans), multiply the live load
obtain the proper length on which the Load Tables were of the shortest clear span shown in the Load Table by the
developed). (the shortest clear span shown in the Load Table + 0.67
* In no case shall the safe uniform load, for clear spans less feet)2 and divide by (the actual clear span + 0.67 feet)2.
than the minimum clear span shown in the Safe Load The live load shall not exceed the safe uniform load.
Column, exceed the uniform load calculated for the
54
STANDARD LOAD TABLE
DEEP LONGSPAN STEEL JOISTS, DLH-SERIES
Based on a Maximum Allowable Tensile Stress of 30 ksi
Adopted by the Steel Joist Institute May 25, 1983;
Revised to May 1, 2000 – Effective August 1, 2002
The black figures in the following table give the TOTAL safe All rows of bridging shall be diagonal bridging with bolted
uniformly distributed load-carrying capacities, in pounds connections at the chords and intersections.
per linear foot, of DLH-Series Steel Joists. The weight of Where the joist span is in the BLUE SHADED area of the
DEAD loads, including the joists, must in all cases be load table hoisting cables shall not be released until the two
deducted to determine the LIVE load-carrying capacities of rows of bridging nearest the third points are completely
the joists. The approximate DEAD load of the joists may be installed.
determined from the weights per linear foot shown in the
Where the joist span is in the GRAY SHADED area of the
tables. All loads shown are for roof construction only.
load table hoisting cables shall not be released until all rows
The RED figures in this load table are the LIVE loads per of bridging are completely installed.
linear foot of joist which will produce an approximate deflec- 4
The approximate moment of inertia of the joist, in inches is;
tion of ¹⁄₃₆₀ of the span. LIVE loads which will produce a
deflection of ¹⁄₂₄₀ of the span may be obtained by multiply- I j = 26.767(WLL)(L3)(10-6), where WLL = RED figure in the
ing the RED figures by 1.5. In no case shall the TOTAL load Load Table, and L = (clear span + .67) in feet.
capacity of the joists be exceeded. When holes are required in top or bottom chords, the car-
This load table applies to joists with either parallel chords or rying capacities must be reduced in proportion to the reduc-
standard pitched top chords. When top chords are pitched, tion of chord areas.
the carrying capacities are determined by the nominal The top chords are considered as being stayed laterally by
depth of the joists at the center of the span. Standard top floor slab or roof deck.
chord pitch is ¹⁄₈ inch per foot. If pitch exceeds this standard, The approximate joist weights per linear foot shown in
the load table does not apply. Sloped parallel-chord joists these tables do not include accessories.
shall use span as defined by the length along the slope.
55
STANDARD LOAD TABLE/DEEP LONGSPAN STEEL JOISTS, DLH-SERIES
Based on a Maximum Allowable Tensile Stress of 30 ksi
* The safe uniform load for the clear spans shown in the minimum clear span listed in the Safe Load Column.
Safe Load Column is equal to (Safe Load)/(Clear span + * To solve for live loads for clear spans shown in the Safe
0.67). (The added 0.67 feet (8 inches) is required to Load Column (or lesser clear spans), multiply the live load
obtain the proper length on which the Load Tables were of the shortest clear span shown in the Load Table by (the
developed). shortest clear span shown in the Load Table + 0.67 feet)2
* In no case shall the safe uniform load, for clear spans less and divide by (the actual clear span + 0.67 feet)2 . The live
than the minimum clear span shown in the Safe Load load shall not exceed the safe uniform load.
Column, exceed the uniform load calculated for the
56
METRIC LOAD TABLE
LONGSPAN STEEL JOISTS, LH-SERIES
Based on a Maximum Allowable Tensile Stress of 207 MPa
Adopted by the Steel Joist Institute May 2, 1994;
Revised to May 1, 2000 – Effective August 1, 2002
The black figures in the following table give the TOTAL safe Where the joist span is in the RED SHADED area of the
uniformly distributed load-carrying capacities, in load table, the row of bridging nearest the mid span shall be
kiloNewtons per meter (kN/m) of LH-Series Steel Joists. diagonal bridging with bolted connections at chords and
The weight (kN/m) of the DEAD loads, including the joists, intersection. Hoisting cables shall not be released until this
must in all cases be deducted to determine the LIVE row of bolted diagonal bridging is completely installed.
load-carrying capacities of the joists. The approximate Where the joist span is in the BLUE SHADED area of the
DEAD load of the joist may be determined from the weights load table, all rows of bridging shall be diagonal bridging
shown in the tables. with bolted connections at chords and intersection. Hoisting
The RED figures this load table are the LIVE loads cables shall not be released until the two rows of bridging
(kiloNewtons per meter) of joist which will produce an nearest the third points are completely installed.
approximate deflection of ¹⁄₃₆₀ of the span. LIVE loads which When holes are required in top or bottom chords, the car-
produce a deflection of ¹⁄₂₄₀ of the span may be obtained by rying capacities must be reduced in proportion to the reduc-
multiplying the red figures by 1.5. In no case shall the tion of chord areas.
TOTAL load capacity of the joists be exceeded.
The top chords are considered as being stayed laterally by
This load table applies to joists with either parallel chords or floor slab or roof deck.
standard pitched top chords. When top chords are pitched,
The approximate joist weights (kg/m) and mass (kN/m)
the carrying capacities are determined by the nominal
shown in these tables do not include accessories.
depth of the joist at center of the span. Standard top chord
pitch is 1:96. If pitch exceeds this standard, the load table The approximate moment of inertia of the joist, in mm4 is:
does not apply. Sloped parallel-chord joists shall use span I j = 2.6953(WLL)(L3)(10-5), where WLL = RED figure in the
as defined by the length along the slope. Load Table: L = (span + 204) in millimeters.
57
STANDARD LOAD TABLE IN METRIC UNITS/LONGSPAN STEEL JOISTS, LH-SERIES
Safe Uniformly Distributed Load In Kilonewtons/Meter
58
STANDARD LOAD TABLE IN METRIC UNITS/LONGSPAN STEEL JOISTS, LH-SERIES
Safe Uniformly Distributed Load In Kilonewtons/Meter
* The safe uniform load for the clear spans shown in the * To solve for live loads for clear spans shown in the Safe
Safe Load Column is equal to (Safe Load)/(Clear span + Load Column (or lesser clear spans), multiply the live load
204). (The added 204 millimeters is required to obtain the of the shortest clear span shown in the Load Table by the
proper length on which the Load Tables were developed). (the shortest clear span shown in the Load Table + 204
* In no case shall the safe uniform load, for clear spans less mm)2 and divide by (the actual clear span + 204 mm)2.
than the minimum clear span shown in the Safe Load The live load shall not exceed the safe uniform load.
Column, exceed the uniform load calculated for the mini-
mum clear span listed in the Safe Load Column.
59
METRIC LOAD TABLE
DEEP LONGSPAN STEEL JOISTS, DLH-SERIES
Based on a Maximum Allowable Tensile Stress of 207 MPa
Adopted by the Steel Joist Institute May 2, 1994;
Revised to May 1, 2000 – Effective August 1, 2002
The black figures in the following table give the TOTAL safe All rows of bridging shall be diagonal bridging with bolted
uniformly distributed load-carrying capacities, in connections at the chords and intersections.
kiloNewtons per meter (kN/m) of DLH-Series Steel Joists. Where the joist span is in the BLUE SHADED area of the
The weight (kN/m) of the DEAD loads, including the joists, load table hoisting cables shall not be released until the two
must in all cases be deducted to determine the LIVE rows of bridging nearest the third points are completely
load-carrying capacities of the joists. The approximate installed.
DEAD load of the joist may be determined from the weights
Where the joist span is in the GRAY SHADED area of
shown in the tables. All loads shown are for roof construc-
the load table hoisting cables shall not be released until all
tion only.
rows of bridging are completely installed.
The RED figures this load table are the LIVE loads
When holes are required in top or bottom chords, the car-
(kiloNewtons per meter) of joist which will produce an
rying capacities must be reduced in proportion to the reduc-
approximate deflection of ¹⁄₃₆₀ of the span. LIVE loads which
tion of chord areas.
produce a deflection of ¹⁄₂₄₀ of the span may be obtained by
multiplying the RED figures by 1.5. In no case shall the The top chords are considered as being stayed laterally by
TOTAL load capacity of the joists be exceeded. the roof deck.
This load table applies to joists with either parallel chords or The approximate joist weights (kN/m) and mass (kg/m)
standard pitched top chords. When top chords are pitched, shown in these tables do not include accessories.
the carrying capacities are determined by the nominal The approximate moment of inertia of the joist, in mm4 is:
depth of the joist at center of the span. Standard top chord I j = 2.6953(WLL)(L3)10-5), where WLL = RED figure in the
pitch is 1:96. If pitch exceeds this standard, the load table Load Table; L = (span + 204) in millimeters.
does not apply. Sloped parallel-chord joists shall use span
as defined by the length along the slope.
60
STANDARD LOAD TABLE IN METRIC UNITS/LONGSPAN STEEL JOISTS, DLH-SERIES
Safe Uniformly Distributed Load In Kilonewtons/Meter
* The safe uniform load for the clear spans shown in the * To solve for live loads for clear spans shown in the Safe
Safe Load Column is equal to (Safe Load)/(Clear span + Load Column (or lesser clear spans), multiply the live load
204). (The added 204 millimeters is required to obtain the of the shortest clear span shown in the Load Table by the
proper length on which the Load Tables were developed). (the shortest clear span shown in the Load Table + 204
* In no case shall the safe uniform load, for clear spans less mm)2 and divide by (the actual clear span + 204 mm)2 .
than the minimum clear span shown in the Safe Load The live load shall not exceed the safe uniform load.
Column, exceed the uniform load calculated for the mini-
mum clear span listed in the Safe Load Column.
61