45021F
GS DRIVER PARAMETERS
Supply voltage to driver 18 to 32 Vdc
Maximum transient supply current 25.0 A for 0.20 seconds
Normal steady state input current <4.0 A
Via terminal blocks on driver assembly, stud for external ground
Electrical connection
Maximum separation of valve & driver 100 m
Valve position command signal 4 to 20 mA current signal into 249 impedance
Valve indicated position signal 4 to 20 mA current signal into <500 impedance
Shutdown/reset command Close contact to run, open to close valve
System fault indication signal 1 Form C dry contact output
Ambient temperature capability –5 to +130 °F (–20 to +55 °C)
GS driver dimensions 9.0 x 10.0 x 3.0 inches (229 x 254 x 76 mm)
Open or short circuit conditions within the valve assembly or wiring connections
Fault detection capabilities Input signal in excess of 20 mA
Position loop error in excess of 5% of full scale for more than 0.250 seconds
EMC Directive:
Declared to 89/336/EEC COUNCIL DIRECTIVE of 03 May 1989 on the
approximation of the laws of the Member States relating to electromagnetic
compatibility.
European compliance for CE Mark
ATEX Directive:
Declared to 94/9/EEC COUNCIL DIRECTIVE of 23 March 1994 on the
approximation of the laws of the Member States concerning equipment and
protective systems intended for use in potentially explosive atmospheres.
Hazardous locations certifications See table on the back page
GS VALVE PARAMETERS GS3 GS10
1
Gas flow range 10 to 5000 pph 25 to 15 000 pph
Gas supply pressure range 100 to 750 psig (690 to 5170 kPa)
Minimum pressure differential 20 psid (138 kPa) minimum recommended for accurate flow characteristics
Gas filtration requirements 25 µm or better
Metering ports available 0.1 in², 0.2 in², 0.3 in², 0.39 in² 0.5 in², 1.0 in²
(maximum area) (65 mm², 129 mm², 194 mm², 252 mm²) (323 mm², 645 mm²)
Gas inlet & ambient temperature2 –20 to +217 °F (–29 to +103 °C) –20 to +250 °F (-29 to +121 °C)
Accuracy (% of port area) ±5.0% of actual or ±0.5% of maximum (greater of)
Metering valve leakage <1.0% of rated maximum flow with gas at specified conditions when closed
Flow shut-off valve leakage N/A N/A
Flow shut-off valve response N/A N/A
Full travel slew time
<100 ms <150 ms
(closed loop position control)
Shut down slew time (@ 24 Vdc to driver) <50 ms <75 ms
Position loop bandwidth3 35 radians/second (typical)
2.00 in. RF flange per ANSI B16.5
Gas connections Straight threaded port per SAE J514-16 Class 600 face to face dim. per
ANSI S75.03
Overboard gas vent connection Straight threaded port per SAE J514-4 Straight threaded port per SAE
J514-4
DIV 2—Actuator motor 0.500 NPT conduit connection, 3 leads 72 in. (1.8 m)
long minimum.
Position sensor connection, MS3102R-16S-1P multi-pin circular connector
Electrical connectors
(GS3 only)
DIV 1—Wiring cavity with terminal blocks and two 0.5 inch NPT conduit
connections
DIV 1—Steel, 45 lbs (20 kg)
Assembly weight 70 lbs (32 kg)
DIV 2—Aluminum, 20 lbs (9.1 kg)
15 g vibration at 20 to 500 Hz per MIL-STD-810C Curve G in any plane,
Vibration and shock
20 g maximum shock per MIL-STD-810C Method 516.2 Procedure 1
Hazardous locations certifications See table on the back page
Notes:
1
Valve flow capacities are dependent on the gas properties, pressures, and temperatures available.
Please consult Woodward for sizing software or assistance in selecting the correct valve for each application or if an
application exceeds these published limits.
2
Dry gas required for temperatures below 0 °C (32 °F).
3
The system dynamics are approximately second order. Bandwidth is determined by magnitude response at –6 dB, 24
Vdc to GS Driver.
Woodward
Industrial Controls
GS VALVE AND DRIVER HAZARDOUS LOCATION LISTING
PO Box 1519
Fort Collins CO, USA GS3 GS10
80522-1519
1000 East Drake Road Driver: CSA Listed for Class I, Division 2, Driver: CSA Listed for Class I, Division 2,
Fort Collins CO 80525 Groups A, B, C, & D and Zone 2, Group IIC, Groups A, B, C, & D and Zone 2, Group IIC,
Ph: +1 (970) 482-5811 T4 for North America. T4 for North America.
Fax: +1 (970) 498-3058
LCIE Listed for Class I, Zone 2, Group IIC, LCIE Listed for Class I, Zone 2, Group IIC,
T4 for Europe, when installed in an IP-54 T4 for Europe, when installed in an IP-54
Distributors & Service
minimum enclosure (per EN50021). minimum enclosure (per EN50021).
Woodward has an
international network of Low Carbon Steel Valve: CSA Listed for Low Carbon Steel Valve: CSA Listed for
distributors and service Class I, Division 1, Groups C, D and Division Class I, Division 1, Groups C, D and
facilities. For your nearest 2, Groups A, B, C, D/Zone 2, Group IIC, T3 Division 2, Groups A, B, C, D/ Zone 2,
representative, call the for North America. Group IIC, T3 for North America.
Fort Collins plant or see
the Worldwide Directory LCIE Listed for Class I, Zone 1, Group IIB, LCIE Listed for Class I, Zone 1, Group IIB,
on our website. T3 for Europe. T3 for Europe.
Aluminum Alloy Valve: CSA Listed for
Class I, Division 2, Groups A, B, C, D and
Corporate Headquarters
Zone 2, Group IIC, T3 for North America.
Rockford IL, USA
Ph: +1 (815) 877-7441
www.woodward.com
© Woodward Governor
Company, 1995
All Rights Reserved