On-Site Test

ABS Protocols for Gommissioning

Voltage drop
Measuring instrument type--___-.-..-..: tr RMO500A.Micro Ohmmeter. DV Power

catculation formuta.................-......: u (mv ) - l(A\xR!Y9hm\


1000
(adjusted cunent range: 200 A DC)

Note The procedures associated with the measurement of the voltage drop and the related
default values for the individual components are listed in the product manual in chapter
"Commissioning" in document "Tests Prior to Commissioning".

A. Phasing checked acc, to primary drawings----- __-------V


B. Values of voltage drop measured (see table 1).-----. ----_--.-._-.---.-- El

Table {: Measurement of voltage drop

Designation of measuring point in Actualvalue (measurcd)


accordance with the circuit Phase Remarks
diagram mV pOhm

c20/c20t ec203e c200e c2020 R 27,46 137,3 max. 159 uOhm

c22tc2281 Y 27,15 135,8 max. 159 uOhm

B 26,92 136,6 max. 159 uOhm

c20tc201 e c203 0 c200+ c204+ R 28,23 '141,2 m€x. 159 pOhm

c12tc126l Y 27,17 135,8 max. 159 pOhm

B 28,10 140,5 max. 159 pOhm

c22t c2261 a C226+ C220 + C224 R 29,08 145,4 max. 173 pOhm

c2241 Y 28,94 144,7 max. 173 pOhm

B 28,U 143,4 max. 173 uOhm

c1 a cI 261 +C{ 26+C{ 20 + C124 R 35,93 179,7 max. 206 uOhm

cl241 Y u,70 173,5 max. 206 pOhm

B 36,33 181,6 max. 206 pOhm

Date, Customer,NCC

1HDG 518 680 N en