Sunteți pe pagina 1din 9

Regulators and Final Control

Elements
7

7.1 Electric Motors 1377


DAMPERS AND LOUVERS 1362 Motor Drivers 1378
Introduction 1362 Controllers 1378
Damper Designs 1363 Sensors for Feedback 1378
Parallel-Blade Dampers and Louvers 1364 Communication Protocols 1380
Rotating Disc Dampers 1365 Conclusions 1380
Multiple-Disc Dampers 1365 References 1380
Fan Suction Dampers 1366 Bibliography 1381
Variable-Orifice Dampers 1366
Conclusions 1367 7.4
Bibliography 1367 PUMPS AS CONTROL ELEMENTS 1382
Rotodynamic or Centrifugal Pumps 1384
7.2
Radial-Flow 1384
EELECTRIC ENERGY MODULATION 1368
Axial- and Mixed-Flow 1385
Introduction 1368 Peripheral or Regenerative Turbine 1385
On/Off Power Control 1369 Positive-Displacement Pumps 1386
Throttling Power Controllers 1369 Rotary Pumps 1386
Saturable Core Reactors 1369 Gear Pumps 1387
SCR Power Controllers 1370 Reciprocating Pumps 1387
Zero-Voltage-Fired SCR Controllers 1371 Air Pumps and Air Lifts 1388
Controlling Infrared Tungsten Heaters 1372 Condensate Pumps 1388
Common SCR Limitations 1372 Air Lifts 1388
Ignitron Tube 1373 Design of Pumping Systems 1388
Power Amplifier 1374 Head Requirements 1388
References 1374 NPSH Calculation 1389
Bibliography 1374 Specific Speed 1390
Horsepower 1390
7.3 Installation Considerations for Wastewater
LINEAR AND ANGULAR Pumping Stations 1390
POSITIONING OF MACHINERY 1375 Metering Pumps 1391
Open- and Closed-Loop Positioning 1376 Plunger Pumps 1391
Positioning System Components 1376 Diaphragm Pumps 1392
Motors and Actuators 1377 Pneumatic Metering Pumps 1393

1359

© 2006 by Béla Lipták


1360 Regulators and Final Control Elements

Installation Considerations 1393 Stability 1422


NPSH and Pulsation Dampening 1395 Safety 1423
Opposed Centrifugal Pumps 1395 Installation 1423
Bibliography 1396 Bibliography 1423
ISA Specification Form (Table 7.7s) 1425
Instructions for ISA Form S20.51 1425
7.5
REGULATORS—FLOW 1397
7.8
Introduction 1398 REGULATORS—TEMPERATURE 1426
Purge Flow Regulators 1398
Introduction 1427
Flow Regulators for Chromatographs 1399
Variable-Orifice Flow Regulators 1399 Control Quality 1427
HVAC Balancing Flow Regulators 1399 Types of Temperature Regulators 1428
Oil Flow Regulator 1401 Direct- and Pilot-Actuated 1428
Industrial Flow Regulators 1401 Remote or Internal Element 1428
Thermal Mass Flowmeters 1402 Accessories and Special Features 1429
Bibliography 1403 Thermal Systems 1430
Bulbs, Wells, Fittings 1430
Vapor-Filled System 1431
7.6 Liquid-Filled System 1434
REGULATORS—LEVEL 1405 Hot Chamber System 1435
Fusion-Type System (Wax-Filled) 1435
Introduction 1405 The Regulator Valve 1436
Float-Type Level Regulators 1405 Single- and Double-Seated Valves 1436
The Phenomenon of Offset 1406 Three-Way Valves 1436
Span, Dead Band, and Hysteresis 1406 Valve Features 1438
Power Generated by the Float 1406
Conclusions 1438
Specific Gravity and Temperature Effects 1407
Bibliography 1438
Stuffing Boxes 1408
Installation 1408
Conclusions 1409 7.9
Diverter Valves 1409 THERMOSTATS AND HUMIDISTATS 1440
Altitude Valves 1410 Introduction 1441
Bibliography 1411 Accuracy of Thermostats and Humidistats 1441
Conventional 1441
Advanced 1441
7.7 Thermostats 1441
REGULATORS— PRESSURE 1412 ElectroMechanical Designs 1442
Introduction 1413 Electrical/Electronic Design Features 1442
Regulators vs. Control Valves 1414 Microprocessor-Based Units 1443
Control Valves 1414 Control by Phone 1443
Regulator Applications 1414 The Proportional-Only Controller 1443
Gas Industry Applications 1415 Thermostat Action and Spring Range 1445
Liquid Pressure Regulation 1415 Thermostat Design Variations 1445
Gas Station Safety Regulators 1416 Special-Purpose Thermostats 1446
Pressure Surge Relief Valves 1416 Humidistats 1450
Pressure Regulator Designs 1416 Relative Humidity Sensors 1450
Weight-Loaded Regulators 1418 Humidistat Design Features 1452
Spring-Loaded Regulators 1418 Bibliography 1453
Pilot-Operated Regulators 1418
Regulator Characteristics and Sizing 1419
Seating and Sensitivity 1419 7.10
Droop or Offset 1420 VARIABLE-SPEED DRIVES 1454
Noise 1421 Introduction 1455
Cavitation 1422 Transportation Efficiency 1455
Sizing and Rangeability 1422 Characteristics of Variable-Speed Drives 1455

© 2006 by Béla Lipták


Contents of Chapter 7 1361

Electromechanical Drives 1456 Thyristor DC Drives 1464


Mechanical Variable-Speed Drives 1456 Variable-Frequency Drives 1465
Hydraulic Variable-Speed Drives 1458 Comparison of Solid-State Drives 1468
Magnetic Variable-Speed Drives 1459 Efficiency of Solid-State Drives 1469
Variable Voltage 1461 Recent VFD Developments 1469
Pole-Changing AC Motors 1461 Efficiency of Variable-Speed Drives
Solid-State Variable-Speed Drives 1461 and Pumps 1469
Underlying Semiconductor Technology 1461 Evaluation of VSD Efficiencies 1470
Drive Circuit Topologies 1462 Conclusions 1471
Variable-Speed DC Motors 1462 Bibliography 1471

© 2006 by Béla Lipták


7.1 Dampers and Louvers
A. BRODGESELL (1970) B. G. LIPTÁK (1985, 1995, 2005)

Flow sheet symbol

Types of Designs: A. Multiple blade or louver


B. Rotating disc, including multiple disc
C. Radial vanes
D. Iris-type variable orifice
(Note: Some butterfly valves and guillotine-type slide gate valves are similar in
their functions to dampers. They are discussed in Chapter 6.)
Design Pressure: Type A designs can usually handle up to 10 in. H2O (2.5 kPa) shut-off differen-
tials; type D units can handle up to 15 psid (103 kPa)
Materials of Construction: Steel, galvanized steel, aluminum, and fiberglass; stainless steel is used in special
cases
Sizes: Type A dampers are available up to 6 ft × 8 ft (1.8 m × 2.4 m) for HVAC
applications and in even larger sizes for boilers and other industrial applications
Flow Characteristics: See Figure 7.1b
2
Leakage through Each ft At 3 in. H2O (0.75 kPa) shut-off pressure differential: the leakage of standard type
2 2 2
(0.092 m ) of Damper Area: A units is 50 SCFM (250 l/s/m ); special low-leakage type A, 5 SCFM (25 l/s/m );
2
positive-steel type B, 0.5 SCFM (2.5 l/s/m )
Costs: Type A costs range from $100 to $250 per square foot of area ($1000 to $2500
per square meter) as a function of size, features, and accessories
Partial List of Suppliers: Air Clean Damper Co. (www.aircleandamper.com)
Arrow United Industries (www.arrowunited.com)
Babcock & Wilcox Co. (www.babcock.com)
Bachmann Industries (www.bachmannusa.com)
Belimo Air Controls (www.belimo.org)
Damper Design Inc.(www.damperdesign.com)
Flextech Industries (www.flextech-ind.com)
FMC Corp. (www.fmc.com)
Honeywell Sensing and Controls (www.honeywell.com/sensing)
Johnson Controls (www.jci.com)
Louvers & Dampers Inc. (www.louvers-dampers.com)
Miracle Vent Inc. (www.miraclevent.com)
Polymil Products Inc. (www.polymil.com)
Ruskin Air & Sound Control (www.ruskin.com)
Safe-Air/Dowco (www.safeair-dowco.com)
Vent Products Co. (www.ventprod.com)
Young Regulator Co. (www.youngregulator.com)

INTRODUCTION such as heating, ventilation, and air conditioning (HVAC),


while the process control-quality units can handle higher
Dampers and louvers are used to control the flow of gases and pressures, higher temperatures, and corrosive vapors. The
vapors. These streams usually flow in large ducts at relatively process control-quality units also can provide superior leak-
low static pressures. There are both “commercial” and “pro- age and control characteristics.
cess control” quality dampers on the market. Commercial- Dampers are also used to control the flow of solids or to
quality units are used for the less-demanding applications, throttle the capacity of fans and compressors. There is no

1362

© 2006 by Béla Lipták


7.1 Dampers and Louvers 1363

Top 1.0

0.8

0.6
Joint unsupported
by vertical 0.5
edge stop
0.4
Air flow
Joint supported Vertical edge stop 0.3
by vertical
edge stop
0.2
Joint unsupported
Top and bottom by vertical
leaf edges 0.15
edge stop
deflect toward

Damper pressure drop (in. w.g.)


horizontal

io
edge stop under 0.1

rat
pressure 0.09

a
are
0.08
Parallel Bottom

0
0.5
e
0.07

0.7 0
Fre

0.6
damper Opposed blade proportioning

0
0.06

5
(uni-rotational damper

0.7
0.05

0
0.8
louvre) (counter-rotational louvre)
0.04
FIG. 7.1a
The designs of the parallel-blade and opposed-blade dampers, 0.03
which are also referred to as uni-rotational and counter-rotational
louver designs. 0.02

0.015

1.0
0.01
90° louvre
(parallel)
0.8 0.008
Fraction of maximum flow

0.007
0.006
0.6 0.005

0.004
0.4 Butterfly 500 700 1000 1500 3000 5000
(150) (210) (300) (450) (900) (1500)
800 2000 4000
0.2 (240) (600) (1200)
Approach velocity ft/m (m/m)

0 FIG. 7.1c
0 0.2 0.4 0.6 0.8 1.0
Fraction of maximum rotation Pressure drop through wide-open dampers. The free-area ratio of
100 Percent of total
an open damper is the total open area between the blades, divided
A-1
B-2 system drop by the nominal area.
Linear C-5 through the
80 D-8 damper in the
E - 22 wide open
Percent maximum flow

F - 50 position
clear distinction between butterfly valves and butterfly damp-
60
C G - Inherent character- ers or between slide-gate valves and guillotine dampers. The
A B E F G
D istic of an opposed design features of these dampers are quite similar to their
blade damper with
40 equal percentage control valve counterparts, which are discussed in Chapter 6.
linkage at a constant
pressure drop
Dampers in general are large in size, and their operating
20 and shut-off pressures are limited to lower values. The diam-
eters of the largest dampers can exceed 20 ft (6 m).
0
0 20 40 60 80 100
Percent linkage movement
DAMPER DESIGNS
FIG. 7.1b
The flow characteristics of a parallel-blade damper are similar to
those of a conventional butterfly valve (see top part of this figure). Dampers and louvers can be grouped according to their
The flow characteristics of an opposed-blade damper approach equal- shapes into parallel-blade, disc and multiple-disc, radial vane,
percentage characteristics when the total system pressure drop is and variable-orifice designs. Within each design category,
through it and it shifts its characteristics toward quick opening, as there can be subdivisions according to leakage rates, materi-
the damper receives less and less of the total pressure differential. als of construction, actuator designs, or accessories provided.

© 2006 by Béla Lipták


1364 Regulators and Final Control Elements

3−1/2 in.
90 mm

FIG. 7.1d
2 2
Standard commercial damper frame sizes and areas, ft /m . (Courtesy of Ruskin, previously Johnson Controls.)

Parallel-Blade Dampers and Louvers positioned manually, pneumatically, or electrically. In the


uni-rotational louver (parallel damper) design, the vanes
Multiblade dampers consist of two or more rectangular remain parallel at all rotational positions. In a counter-
vanes mounted on shafts that are one above the other, which rotational louver (opposed blade), alternate vanes rotate
are interconnected so they rotate together (Figure 7.1a). in opposite directions. Both designs are illustrated in
The vanes are operated by an external lever, which can be Figure 7.1a.

© 2006 by Béla Lipták


7.1 Dampers and Louvers 1365

Flow guides are sometimes installed between adjacent Sealed, low-leakage damper
vanes in order to improve the effectiveness of throttling. In
4
the top of Figure 7.1b, the blade-angle vs. flow characteristics
(1.00)
of a parallel-blade damper and a butterfly valve are shown.
The sensitivity of this design is very high at mid-flow while

Pressure differential, inches of H2O (kPa)


the last 30° of rotation is relatively ineffective. The flow
3
characteristics of butterfly valves are similar though some- (0.75)
what superior to those of louvers.
The lower portion of Figure 7.1b shows an opposed-blade
damper with equal percentage linkage. As less and less of 2
the total system pressure drop is assigned to the damper, the (0.50)
characteristics of this damper shift toward quick opening.
Figure 7.1c gives the pressure drop across wide-open
dampers. Ideally the wide-open pressure drop should be 1
between 4 and 8% of the pressure difference across the closed (0.25)
damper. If the damper is sized so that closed pressure differ-
ence is between 12 and 25 times the pressure drop, when the
damper is open, its apparent characteristic will be nearly 0
0 1 2 3 4 5 6 7 8
linear (see curves C and D in Figure 7.1b). (0.3) (0.6) (0.9) (1.2) (1.5) (1.8) (2.1) (2.4)
Figure 7.1d provides some dimensional data for standard Leakage, cfm/ft2 [(m3/min)/m2]
commercial damper frames, including their areas. Static across damper, inches of H2O (kPa)

Low-Leakage Designs The parallel-blade damper cannot Standard unsealed damper


provide tight shut-off because of the long length of unsealed 4
(1.00)
seating surfaces. The leakage characteristics of unsealed stan-
dard dampers are given in the lower portion of Figure 7.1e. In 3
low-leakage damper designs, blade seals are installed along the (0.75)
seating surfaces of the blades, resulting in the reduced leakage 2
characteristic shown in the upper portion of Figure 7.1e. (0.50)
There are a number of variations in the blade-edge seal 1
designs. Some of these designs are illustrated in Figure 7.1f. (0.25)

0
Corrosion Resistant Designs For corrosive services, both 0 10 20 30 40 50 60 70 80 90
(3) (6) (9) (12) (15) (18) (21) (24) (27)
the parallel- and the opposed-blade designs are available in
sizes from 12 by 24 in. up to 60 by 120 in. These units are Leakage, cfm/ft2 [(m3/min)/m2]
made of fiberglass-reinforced polymer with 304 stainless steel FIG. 7.1e
hardware. Some design variations are shown in Figure 7.1g. The leakage rates through sealed, low-leakage dampers are shown
in the top, while the leakage rates of unsealed dampers are given
Actuators and Accessories Damper actuators can be man- in the bottom portion of the figure. (Courtesy of Honeywell and
ual, electric, hydraulic, or pneumatic. Standard pneumatic actu- Ruskin, formerly Johnson Controls.)
2
ators vary their effective diaphragm areas from 2 to 24 in. (13
2
to 155 cm ), while their stroke lengths range from 2 to 6 in. (51
Rotating Disc Dampers
to 152 mm). The amount of force they produce ranges from
about 10 to 300 lbf (4.5 to 136 kgf). The standard spring ranges The rotating disc damper designs are very similar to the but-
for dampers include the spans of 3–7, 5–10, and 8–13 PSIG terfly valve designs, which were discussed in detail in
(0.2–0.48, 0.34–0.68, and 0.54–0.88 bars). Electronic actuators Section 6.17. These dampers are usually installed in circular
can be operated by 4 to 20 mA DC analog or by digital signals. ducts and can be operated both manually or automatically. A
For more accurate throttling, the actuators can also be corrosion-resistant version of this design is made of fiberglass-
provided with positioners. If remote indication of damper reinforced plastics materials and is illustrated in Figure 7.1h.
status is desired, limit switches can be installed to detect the
blade angle. These can be pneumatic sensors of nozzle back- Multiple-Disc Dampers
pressure or mechanically actuated position sensors. The
damper position switch can be furnished with an adjustable A unique variation of the butterfly design is the multiple
mounting flange, which allows the unit to be mounted rotating disc damper. In this design several disc elements are
through a duct wall with the trip lever positioned so that it distributed over an area (Figure 7.1i). One advantage of this
is actuated by the damper blade itself. configuration is improved flow control characteristics,

© 2006 by Béla Lipták


1366 Regulators and Final Control Elements

Model ABK6 Model ABF6 Model ABFA


“K” style “F” style “FA” style

Enlarged view of
blade seal
Pressure
effects
seal

High pressure Low pressure


side side

FIG. 7.1f
Low-leakage damper designs tend to increase the efficiency of 45° Adjustable 90° Adjustable Combination
HVAC systems. In this figure, two blade-edge seal designs are stationary &
adjustable
illustrated. (Courtesy of Honeywell and Ruskin, formerly Johnson
Controls.)
FIG. 7.1g
Corrosion-resistant fiberglass-reinforced polymer damper designs
for both adjustable and stationary applications. (Courtesy of
because each disc can have its own unique spring range and Polymil Products Inc.)
failure position.
Another major advantage is the substantial reduction in Variable-Orifice Dampers
leakage compared to the parallel-blade design. At a static pres-
sure of 3 in. H2O (0.75 kPa) the leakage can be estimated as Variable-orifice dampers use the same principle as the iris
0.01% of full damper capacity, which corresponds to about 0.5 diaphragm of a camera. In order to achieve control action,
2 2 2
SCFM (2.5 l/s/m ) leakage per ft (0.092 m ) of damper area. the closure element moves within an annular ring in the
damper body and produces a circular flow orifice of variable
Fan Suction Dampers

On blowers and fans, when throughputs must be controlled,


radial vane dampers can be utilized. The damper consists of
a number of radial vanes arranged to rotate about their radial
axis (Figure 7.1j).
The radial vane dampers do not provide high-quality
control, and their closed position leakage rates are also high.
Their control applications include furnace draft control.
Usually a positioner is furnished with these units, which
provides a linear relationship between the control signal and
the blade pitch angle. In certain packages the positioner is
factory set in the reverse acting mode, meaning that an increas-
ing control air signal will reduce the air flow by decreasing
the blade pitch. In such packages, one has to install a reversing FIG. 7.1h
relay between the positioner and the actuator, if direct action Corrosion-resistant single-disc damper (Courtesy of Polymil Prod-
is desired. ucts Inc.)

© 2006 by Béla Lipták


7.1 Dampers and Louvers 1367

D-2 D-1 D-1 D-1 D-1 D-2


Actuator
D-3 D-3 D-3

D-4 D-4 Wafer


valve
body
Adjustable
Section A-A orifice
A
FIG. 7.1k
FIG. 7.1i Variable-orifice or iris damper. The sleeve can be made of nylon
Multiple-disc dampers provide better sealing and control or of other materials and is provided with a built-in retaining ring
characteristics. at each end. When the upper end is fixed and the lower end is
rotated, this gradually reduces the orifice opening. At 180° of
diameter (Figure 7.1k). The flow characteristics are similar rotation the orifice is completely closed. If the sleeve is first turned
to those of a linear valve. back on itself, partly “inside out,” the effect of rotation is exactly
However, tight shut-off is not possible, and leakage rates the same, but operates in a much more compact form, as a pleated
are comparable to or greater than those of a butterfly valve duplex diaphragm.
of equal size. Maximum pressure differential is limited to
approximately 15 psid (104 kPa). Dual valve units can be
provided with a common discharge port for applications CONCLUSIONS
involving the blending of two streams.
For solids service, the variable-orifice valve can be used Dampers are suitable for control of large flows at low pressures
for throttling, if the valve is installed in a vertical line. In where high control accuracy is not a requirement. Typical
horizontal lines, the shutter mechanism of the valve forms a applications of these units include air conditioning systems
dam, which makes the valve unsuitable for solids service. and furnace draft control. Variable-orifice or iris dampers are
Standard sizes range from 4 to 12 in. (100 to 300 mm). smaller than other dampers, offer better control quality, and
can also be used to control vertical solid flows.

Bibliography

Ball, K. E., “Final Elements, Final Frontier,” InTech, November 1986.


Brown, E. J., “Air Diffusing Equipment,” in ASHRAE Handbook, Equipment
Volume, Chapter 2, 1979.
“Catalog of U.S. & Canadian Valves & Actuators,” Washington, D.C.: Valve
Manufacturers Association of America, 2003.
Dickey, P. S., “A Study of Damper Characteristics,” Reprint No. A-8, Bailey
Meter Co.
Daryanani, S., et al., “Variable Air Volume Systems,” Air Conditioning,
Heating and Ventilating, March 1966.
“Evaluation Finding for Oiles Multiple Viscous Shear Dampers,” Cerf.
Report: Hitec 99-04, American Society of Civil Engineers, 1999.
Lipták, B. G., “Reducing the Operating Costs of Buildings by Use of Com-
FIG. 7.1j
puters,” ASHRAE Transactions, Vol. 83, Part 1, 1977.
Radial vane dampers are used to throttle the flow on the suction Lipták, B. G., “Optimization of Semiconductor Manufacturing Plants,”
side of air fans and blowers. Instruments and Controls Systems, October 1982.

© 2006 by Béla Lipták

S-ar putea să vă placă și