Sunteți pe pagina 1din 4

I/A Series

••

TAC MicroNet Sensors


TM

The TAC I/A Series MicroNet Sensors (MN-Sxxx series) are a family of digital wall
temperature and humidity sensors for use with TAC I/A Series MicroNet controllers.
These sensors feature a Sensor Link (S-Link) communication protocol which provides a
simple two-wire interface for power and exchange of sensor and subbase information.
Subbase information includes selecting occupancy override, fan speed, operating mode,
or emergency heat. Available in twelve models, MN-Sxxx series sensors provide an
integral analog-to-digital conversion for elimination of sensor-to-controller noise effects
and wire resistance offset.

Using the digital wall sensor, the operator can monitor performance and edit
operational settings. MN-Sxxx series sensors are suitable for direct-wall, 2 x 4 electrical
box, 1/4 DIN electrical box, or surface box mounting.
• Contemporary, low-profile packaging.
• Digital zone temperature indication
The MN-Sxxx series sensor measures room conditions and transmits the information
(selectable for 0.1 or 1 degree display
to the controller via the S-Link. A single sensor is connected directly to an application
resolution of °F or °C).
specific TAC I/A Series MicroNet controller via low-cost, unshielded, twisted-pair cable.
The connection between the sensor and controller is not polarity-sensitive.
• Self-compensating temperature conversions
remove the need to calibrate over time. A convenient connection to either a MicroNet LONWORKS® or MicroNet BACnet network
• Digital zone humidity indication (selectable is provided as an option with each sensor in the series. If the LONWORKS network wiring
for 0.1 or 1% RH display resolution). is connected to the sensor, a PC running WorkPlace Tech Tool or a third party Network
Management Tool can be connected to the network at the sensor. This feature allows
• Long-life humidity sensing element with
convenient access to the MicroNet LONWORKS network.
excellent resistance to contamination and
Table-1 Model Chart.
condensation.
• Pushbutton override capabilities allow
Model
occupants to switch to timed occupied mode
for after hours operation.
Temperature Description Keypad Display
Temperature
and Humidity
• Displays selected system values such as Sensor
Sensor
setpoints, outdoor air temperature, and
operating mode. MN-S1 MN-S1HT Sensor only None None
• Provides the ability to change operating
modes. One LED Override Status
MN-S2 MN-S2HT Sensor with override
button Indication
• Directly connects to selected TAC I/A a
Series MicroNet controllers via low-cost, Sensor with setpoint Digital LCD and
b b Three
unshielded, twisted-pair cable, which MN-S3 MN-S3HT adjustment and LED Override Status
button
provides both power and communication. override Indication
c
Sensor with setpoint, Digital LCD and
• Separate wiring subbase and electronics. b b Six-
MN-S4 MN-S4HT override, and controller LED Override Status
• LonWorks network jack for convenient button
mode functions Indication
network access. Sensor with setpoint, c
b MN-S4HT- Six Digital LCD and LED
• S-Link jack for Pocket TAC I/A access to the MN-S4-FCS b On/Off and Fan speed
FCS button Fan Status Indication
connected controller. functions
Sensor with setpoint, c
Digital LCD and
override, controller
b b Seven LED Override and
MN-S5 MN-S5HT mode functions, and
button Emergency Heat
emergency heat key/
Indication
indication
a
LCD displays value and setpoint.
b
Allows viewing of alarms and diagnostics.
c
LCD displays values, setpoints, and controller mode functions.
SOFTWARE SPECIFICATIONS
Digital Display (MN-S3xx, MN-S4xx and MN-S5xx Models only)

Custom field-configurable sensor displays.

Auto-ranging of displayed values.

Occupant command capabilities.

Adjustable minimum/maximum limit setpoint values.

Controller driven, automatically configured, customized display/command values


(Table-2).

Table-2 Typical MN-S3xx, -S4xx, or -S5xx Display/Change Values.


Model Family Value Display Change

S3xx, S4xx, S5xx Zone Temperature Yes No

S4xx, S5xx Outdoor Air Temperature Yes No

S4xx, S5xx Percent Humidity Yes No


a a
S3xx , S4xx , S5xx Heating Setpoint, Cooling Yes Yes
Setpoint, Unoccupied Heat,
Unoccupied Cool
b
S4xx, S5xx Mode Heating/Cooling/ Yes Yes
Auto/Off

S4xx, S5xx Fan (On/Speed (Low/ Yes Yes


Medium/High), Auto
a
S3xx and S4xx-FCS models have a single setpoint.
b
S4xx-FCS models do not allow mode changes.

Communications
S-Link
Sensor Link (S-Link) communications wiring provides power and communication
interface to the TAC I/A Series MicroNet sensor (MN-Sxxx series). It uses two-wire,
unshielded cable and is not polarity sensitive. From some sensor models, the user can
view and adjust application parameters. Maximum wire length allowed between a
controller and the TAC I/A Series MicroNet sensor is 200 ft. (61 m).

BACnet or LONWORKS Network


The BACnet or LONWORKS network wiring can be connected to the second set of
terminals in the sensor base. This optional connection allows convenient access to the
LONWORKS network at the sensor.

2
SPECIFICATIONS
TEMPERATURE SENSOR AGENC Y LISTINGS Units
Type FCC °F, °C, or %.
Precision thermistor. Class B.
Command Options (S4xx and S5xx
Range UL Listed Models)
32 to 122 °F (0 to 50 °C). UL-916 (File # E71385 Category PAZX). Varies with the controller application.

HUMIDITY SENSOR UL Listed to Canadian Safety Standards System Mode


Element (CAN/CSA C22.2). Heat/Cool/Off/Auto (except MN-S4xx-
Type Thermoset polymer capacitive FCS).
sensor. European Community – EMC Directive
89/336/EEC Fan Mode
Accuracy ±2% RH at 77 °F (25 °C). Emissions and Immunity EN61326 Off/On/Speed (Low, Medium, High)/
Auto.
Range
5 to 95%, non-condensing. AMBIENT LIMITS Override
Operating Temperature Occupied/Unoccupied (except MN-
Hysteresis 32 to 122 °F (0 to 50 °C). S4xx-FCS).
±1.2% RH maximum.
Shipping and Storage Temperature Emergency Heat
Immersion -40 to 160 °F Enable/Disable (MN-S5xx models only).
Extended exposure to equal to or
greater than 90% RH causes a revers- Humidity
ible 3% shift. Sensor will recover from 5 to 95% RH, non-condensing.
short term exposure to liquid water or
condensation. Repeated exposure will
degrade the performance of the sensor. Wiring Terminals
Four (4) screw terminals. AWG #18 to
Dimensions #24 (0.823 mm2 maximum) wire.
4-21/32 H x 3 W x 1 D in
(118.5 x 76.2 x 24 mm). Display
Setpoints, input spans, and units vary
Enclosure with the controller application.
Conforms to NEMA-1 requirements.
Range
Surge Immunity Compliance -99 to 999 or -9.9 to 99.9.
IEEE C62.41 (IEEE-587, Category A & B).

3
PDA
TAC MicroNet Sensor
(MN-S5 Shown) 5
Desktop PC or Notebook PC
4 MNL-V3RVx UNC Controller
with WorkPlace Tech Tool Software MN 110 or MN 130
Controller or MN 50
1 2 Controller
3

Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material brouilleur du Canada
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
interference that may cause undesired operation.
device may not cause harmful interference, and (2) This device must accept any interference received, including
This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This

D E C O N N E C T E R AVA N T E N T R E T E N .
D I S C O N N E C T P O W E R B E F O R E S E RV I C I N G .
I N T E R C O N N E C T S E PA R AT E C L A S S 2 C I R C U I T S .
RISK OF ELECTRICAL SHOCK OR FIRE. DO NOT

C5
DO5

DO5: 250VAC, 3A Max, COS f = 0.4.


DO1-DO4: 24VAC, 0.4A Max Total Load.
S-LK: 16VDC Max, Class 2.
CAUTION

UI: 5VDC Max, Class 2.


Ambient Temp: -40°C to +60°C

Power: 24VAC, 50/60Hz, Class 2,


Regulating Equipment
N2223

Temperature indicating and

DO4
8.5VA + DO1-DO4 loads.

24VAC
DO3
DO2
24VAC
DO1
SW

E9429
24H

934G
SW 3
24H
SW 2
24H

T
MNL-CIM

I
M
X
24H 1

V
C
E
R
C
V

SRVC
24G

R
S

LON
J1
GN

LON
AO

S-LK
D

S-LK

COM 0V

COM 0V
UI1
UI

MNL-11RF2
I/A Series
S-L

UI2
K/C DI

24VAC
OM

UI3
S-L

GND
K

0V
TAC MicroNet Controller
LON
LON

Interface Module

LONWORKS Router 6
Network (if required) I/A
MN
Se
rie
80
0

MN 100, MN 150, or MNL-V1RVx 4


MN 200 Controller or MNL-V2RVx MN 800 TAC MicroNet Sensor
Controller Controller (MN-S3 Shown)

1 A PC can be connected to the LONWORKS TP/FT-10 Network, either directly or through the LONWORKS® network jack of a LONWORKS
controller or MN-Sxxx Wall Sensor. The PC must have an Echelon® LONTALK® adapter card.
2 Programming any of the TAC I/A Series controllers, or the TAC I/A Series MN 800 controller, requires WorkPlace Tech Tool.
3 This controller is not suitable for exposed mounting on a wall or panel, or in any other easily accessible place due to the possibility of
personal contact with the high-voltage terminals. It must be mounted inside a suitable grounded metal enclosure.
4 MicroNet Sensors can be connected to any MN controller.
5 A PDA running the Pocket TAC I/A interface software may be used to communicate with TAC MicroNet I/A Series controllers.
6 When routers are used, WorkPlace Tech is able to communicate through them to any of the TAC I/A Series devices on the network.

PC Workstation with WorkPlace


Tech Tool Suite and:
Ethernet TCP/IP and BACnet/IP • Enterprise Server (used with UNC)
or
• Enterprise Network Server (used with ENC)

UNC Universal
Network Controller
or
ENC Enterprise S-Link S-Link S-Link S-Link S-Link
Network Controller Sensor Sensor Sensor Sensor Sensor

BACnet MS/TP Communications Bus


TAC MicroNet BACnet TAC MicroNet BACnet TAC MicroNet BACnet TAC MicroNet BACnet TAC MicroNet BACnet
MNB-1000 MNB-300 MNB-70 MNB-V1 MNB-V2
Plant Controller Unitary Controller Zone Controller Cooling Controller Deluxe Controller

© Copyright 2008, TAC


All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within
this document is subject to change without notice. Distributed, manufactured, and sold by TAC. I/A Series trademarks are owned by
Invensys Systems, Inc. and are used on this product under master license from Invensys. Invensys does not manufacture this product
or provide any product warranty or support. For service, support, and warranty information, contact TAC at 1-888-444-1311.

F-26290-9 TAC
August 2008 1354 Clifford Avenue
PO Box 2940
Loves Park, IL 61132-2940

www.tac.com

S-ar putea să vă placă și