Documente Academic
Documente Profesional
Documente Cultură
Contents
Clad Switchgear
VacClad-W Metal-
General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-2
General Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-2
Standard Metal-Clad Switchgear Assembly Ratings . . . . . . . . . . . . . . . . . 5.1-4
Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-5
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-5
Switchgear Meters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-17
Protective Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-17
Instrument Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-17
Dummy Element (Dummy Breaker). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-18
Roll-on-the-Floor Breaker Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-19
Integral Motorized Remote Racking Option (VC-W MR2) . . . . . . . . . . . . . 5.1-20
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-24
System Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1-25
General Description
Eaton’s VacClad-W metal-clad switchgear
withType VCP-W vacuum breakers
provides centralized control and protection
of medium-voltage power equipment and
circuits in industrial, commercial and
utility installations involving generators,
motors, feeder circuits, and transmission
and distribution lines.
VacClad-W offers a total design concept
of cell, breaker and auxiliary equipment,
which can be assembled in various
combinations to satisfy user application
requirements. Two-high breaker arrange
ments are standard up to 15 kV. One-
high arrangements can be furnished
when required.
Ratings
Maximum Voltages:
4.76 kV, 8.25 kV, 15 kV
Interrupting Ratings:
4.76 kV: Up to 63 kA
8.25 kV: Up to 63 kA
15.0 kV: Up to 63 kA
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
General Description 5.1-3
Shorting Bar
(Bolted Fault)
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
General Description 5.1-4
Standard Metal-Clad
Switchgear Assembly Ratings
VacClad-W metal-clad switchgear is
available for application at voltages
up to 38 kV, 50 or 60 Hz. Refer to the
table below for complete list of
available ratings.
Table 5.1-1. Standard VCP-W (Non-Arc-Resistant) Metal-Clad Switchgear Ratings Per IEEE C37.20.2-2015 ab
Rated (Ref.) (Ref.) Insulation Level Rated Main Bus Rated Short-Time Rated Momentary
Maximum Rated Rated Power Lightning Continuous Current cd Short-Circuit Short-Circuit
Voltage Voltage Short- Frequency Impulse Current Withstand Current Withstand
Range Circuit Withstand Withstand (2-Second) (10-Cycle) (167 ms)
Factor Current Voltage, Voltage K*I e 2.7 *K*I f 1.6 *K* I g
K I 60 Hz, [LIWV] (Ref. only)
1 Minute (BIL)
kV rms kA rms kV rms kV Peak Amperes kA rms Sym. kA Crest kA rms Asym.
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-5
Circuit Breakers VCP-W Circuit Breaker Ratings The new 1997 and 2000 editions of ANSI
standard C37.06 still include the earlier
■■ Table 5.1-2 includes 5/15 kV circuit
breakers rated on the basis of K > 1 ratings as Table A1 and A1A. The
VCP-W Circuit Breakers K = 1.0 in accordance with revised change from K > 1.0 to K = 1.0 should
Eaton’s VCP-W medium-voltage circuit ANSI standards be implemented by manufacturers
breakers offer the latest in vacuum as they develop and test new circuit
■■ Table 5.1-3 includes capabilities of breakers designs. The change does
technology, providing superior control traditional 5/15 kV circuit breakers rated
and protection of medium-voltage not require, recommend or suggest
on the basis of K > 1.0. Contact Eaton that manufactures re-rate and re-test
power equipment in utility, industrial, for availability of these
commercial, mining and marine existing breakers to new standard.
circuit breakers
installations. Built in a state-of-the-art And accordingly, Eaton continues to
ISOT 9002 certified facility, they meet and The following discussion provides a brief offer both circuit breakers rated on the
exceed all ANSI and IEC requirements. explanation of rated voltage range factor traditional basis of K > 1.0 just as
Available in drawout configurations, K = 1 and K > 1.0. thousands of those breakers have been
Eaton’s vacuum circuit breakers are a applied for variety of circuit switching
result of our ongoing commitment to applications worldwide, and also as Eaton
research and development, which have Discussion of changes in the develops new breakers, they are rated
resulted in significant breakthrough Rated Voltage Range Factor, and tested to the new K = 1 ratings.
technologies. Each breaker is provided
with its unique Quality Assurance
K, or “K-factor” As a leader in vacuum interruption
Certificate that documents all tests In 1997 and 2000 editions of ANSI C37.06, technology, Eaton continues to provide
and inspections performed. under Table 1, preferred values for the a wide choice of modern vacuum circuit
rated voltage range factor, K, were set to breakers so that the user can select the
VCP-W Standard Features 1.0 for all indoor circuit breaker ratings. most economical circuit breaker that can
This was done because interrupting satisfy their circuit switching application.
■■ Eaton’s maintenance-free vacuum capabilities of today’s vacuum circuit
interrupters with visual contact breakers are better represented by
erosion indicator K = 1.0.
■■ Non-sliding/non-rolling V-Flex™
current transfer system Unlike old air-magnetic and oil circuit
breakers, today’s vacuum breakers
■■ Glass polyester insulation
generally do not require a reduction in
■■ Front-accessible operating interrupting current, as the operating
mechanism voltage is raised to rated maximum
■■ Electrically operated trip-free, voltage, for example from 11.5 kV up to
spring stored energy mechanism 15 kV. The interrupting capability of
vacuum circuit breakers is essentially
■■ Interlocks that prevent moving a
constant over the entire range of
closed circuit breaker into or out operating voltages, up to and including
of the connected position its rated maximum voltage.
■■ Closing springs automatically
discharge before moving the circuit The change was also made as a step
breaker into or out of the enclosure toward harmonizing preferred ANSI
ratings with the preferred ratings of
■■ Provisions for manual charging of
IEC standards. It was further recognized
closing springs that it is much simpler to select and
■■ Manual close and trip pushbuttons apply circuit breakers rated on the
■■ Operations counter basis of K = 1.0.
■■ Closing spring charged/discharged The change in the K value, however,
indicator in no way affects the ratings and
■■ Circuit breaker Open/Closed capabilities of circuit breakers originally
indicator tested and rated on the basis of K > 1
in the earlier editions of C37.06. Existing
■■ Auxiliary switch with 2A/3B for dc
circuit breakers, with ratings based on
and 1A/3B for ac spare contacts K > 1.0, are still perfectly valid, meet the
■■ Spring charging motor, close coil, latest editions of the standards, and
trip coil, latch check switch and should be continued to be applied as
anti-pump relay they have been in the past. The original
K > 1.0 ratings are neither “obsolete”
nor “inferior” to the new K = 1.0 ratings;
they are just different.
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-6
Table 5.1-2. Available 5/15 kV VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K = 1.0)
(Continued on next page)
Identification Rated Values
Drawout Circuit Insulation Level Short-Circuit Ratings (Reference C37.04-1999 and C37.06-2009 Except as Noted a)
Breaker Type Transient Recovery Voltage
Asymmetrical Interrupting
Symmetrical Interrupting
dc Component (% dc) d
Short-Time Withstand
Maximum Voltage (V)
Continuous Current b
Interrupting Time
Voltage (1 min.)
Current (2.6 x I)
(T2 = t3 x 1.137)
RRRV = uc/t3 g
Time to Peak
Current (It) e
Peak Voltage
Current (I) c
Current f
(E2) = (uc)
Units kV rms Hz kV kV A kA rms % kA rms kA rms kV µsec µsec kV/ ms Cycles
rms Peak rms sym asym Peak Peak µsec (60 Hz)
Total
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-7
Table 5.1-2. Available VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K = 1.0) (Continued)
Identification Rated Values
Drawout Capacitance Current Switching Capability Out-of-Phase
Circuit Breaker (Reference C37.04a-2003, C37.06-2009 and C37.09a-2005) Switching
Type Back-to-Back Capacitor Switching
Voltage = 1.44 x V
Inrush Frequency
Current = 0.25 x I
Operating Duty
Inrush Current
Bank Current
Units A Duty No-Load Class A Class A Class A kA kHz kV kA
rms Cycle Operations rms rms rms Peak rms rms
ij
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-8
Table 5.1-3. Available 5/15 kV VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis, Per ANSI Standards (Rated K > 1) abcd
Identification Rated Values Related Required Capabilities
Recovery Voltage g
Rated Continuous
Current at 60 Hz
Voltage (1 min.)
K Times Rated 2.7 K 1.6 K
Rate of Rise of
Short-Circuit Times Times
Current f Rated Rated
Short- Short-
Rated
Circuit Circuit
Current Current
V Ie E2 V/K KI KI 2.7 KI 1.6 KI l m
kV MVA kV K e kV kV f kA kV T2 h Yi j kV kA kA rms S
Class Class rms rms Crest Amp rms Crest µS kV/ Cycles Sec. ms rms kA rms kA rms Crest asym.
µS
50 VCP-WND 4.16 250 4.76 1.24 19 60 1200 29 8.9 50 0.2 5 2 300 3.85 36 36 97 58 1.2
250
50 VCP-W 4.16 250 4.76 1.24 19 60 1200 29 8.9 50 0.2 5 2 300 3.85 36 36 97 58 1.2
250 2000
3000
50 VCP-W 4.16 350 4.76 1.19 19 60 1200 41 8.9 50 0.2 5 2 300 4.0 49 49 132 78 1.2
350 2000
3000
75 VCP-W 7.2 500 8.25 1.25 36 95 1200 33 15.5 60 0.29 5 2 300 6.6 41 41 111 66 1.2
500 2000
3000
150 VCP-W 13.8 500 15 1.30 36 95 1200 18 28 75 0.42 5 2 300 11.5 23 23 62 37 1.2
500 2000
3000
150 VCP-W 13.8 750 15 1.30 36 95 1200 28 28 75 0.42 5 2 300 11.5 36 36 97 58 1.2
750 2000
3000
150 VCP-W 13.8 1000 15 1.30 36 95 1200 37 28 75 0.42 5 2 300 11.5 48 48 130 77 1.2
1000 2000
3000
a For capacitor switching, refer to Table 5.1-2 and Table 5.1-4. h 3-cycle rating available, refer to Table 5.1-2 and Table 5.1-4.
b 5 and 15 kV circuit breakers are UL listed. i Tripping may be delayed beyond the rated permissible tripping delay at
c Circuit breakers shown in this table were tested in accordance with lower values of current in accordance with the following formula:
IEEE standard C37.09-1979.
( )
2
d Contact Eaton for availability of these circuit breakers. (KTimes Rated Short-Circuit Current)
T (seconds) =Y Short-Circuit CurrentThrough Breaker
e For three-phase and line-to-line faults, the symmetrical interrupting
capability at an operating voltage The aggregate tripping delay on all operations within any 30-minute period
must not exceed the time obtained from the above formula.
Isc = V (Rated Short-Circuit Current)
Vo j For reclosing service, there is No derating necessary for Eaton’s
VCP-W family of circuit breakers. R = 100%. Type VCP-W breaker can perform
But not to exceed KI.
the O-C-O per ANSI C37.09; O-0.3s-CO-15s-CO per IEC 56; and some VCP-Ws
Single line-to-ground fault capability at an operating voltage
have performed O-0.3s-CO-15s-CO-15s-CO-15s-CO; all with no derating.
Contact Eaton for special reclosing requirements.
Isc = 1.15 V (Rated Short-Circuit Current)
Vo k For higher close and latch ratings, refer to Table 5.1-4.
But not to exceed KI. l Included for reference only.
The above apply on predominately inductive or resistive three-phase m Asymmetrical interrupting capability = “S” times symmetrical
circuits with normal-frequency line-to-line recovery voltage equal interrupting capability, both at specified operating voltage.
to the operating voltage.
f 4000 A forced cooled rating is available for 5/15 kV. 3000 A forced
cooled rating is available for 38 kV. Contact Eaton for details.
E2
g RRRV = 1.137
T2
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-9
VCP-W Circuit Breaker Operating Times Figure 5.1-2 below shows the sequence
The closing time (initiation of close signal of events in the course of circuit
to contact make) and opening time interruption, along with applicable
(initiation of the trip signal to contact VCP-W circuit breaker timings.
break) are shown in Table 5.1-4.
Table 5.1-4. Closing Time and Opening Time
Rated Breaker Closing Time Opening Time Milliseconds
Control Voltage Rating Milliseconds Standard 5-Cycle Breaker Optional 3-Cycle Breaker
Clearing Time
Interrupting Time
Standard: 83 ms (5 Cycle)
Optional Available: 50 ms (3 Cycle)
ab
Contact Parting Time
Maximum Contact Parting Time = 38 ms (2-1/4 Cycle) Based on Minimum Tripping
Delay Equal to 8 ms (1/2 Cycle)
38 ms 12 ms 47 ms
52-1 Load 52-2 52-1 Opening Time Arcing Dead Time (With Arcing)
Time
7
ms 52 ms
52-2 Closing Time
Source #1 Source #2
52-1 “b”
Contact
+ Makes
59 ms
Transfer 52-1
Dead Bus Time (No Arcing)
Initiate b
Control Standard Approx. 100 ms
Supply ”b“ Contact
Total Transfer Time
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-10
WCP-W Load Current Switching VCP-WC Extra Capabilities Breakers Eaton is a world leader in vacuum
Table 5.1-5 showing number of operations Introducing the VCP-WC extra capability interrupter and vacuum circuit breaker
is a guide to normal maintenance for medium-voltage drawout circuit breaker. technology, offering VCP-WC with
circuit breakers operated under usual Designed to provide all the industry- extra capabilities without sacrificing
service conditions for most repetitive leading features expected of the VCP-W, the proven features already standard
duty applications including isolated plus extra capabilities for those application with other VCP-W circuit breakers.
capacitor bank switching and shunt requirements that go beyond what is Features such as:
reactor switching, but not for arc furnace usually experienced.The performance ■■ Vacuum interrupters with
switching.The numbers in the table are enhancement features of the VCP-WC copper-chrome contacts
equal to or in excess of those required make it an ideal choice for capacitor
■■ V-Flex non-sliding current
by ANSI C37.06. switching duty, high altitude applications,
transfer system
transformer secondary fault protection,
Maintenance shall consist of adjusting, locations with concentrations of rotating ■■ Visible contact erosion indicators
cleaning, lubricating, tightening, etc., machinery or high operating endurance ■■ Visible contact wipe indicators
as recommended by the circuit breaker requirements, just to mention a few.
instruction book. ■■ Front, functionally grouped controls
Consider these capability enhancements:
and indicators
Continuous current switching assumes Definite purpose capacitor switching
■■ ■■ Glass-polyester (5/15 kV), or epoxy
opening and closing rated continuous
■■ Higher close and latch insulation (27/38 kV)
current at rated maximum voltage with
power factor between 80% leading and ■■ Faster rate of rise of recovery voltage ■■ Front, vertically mounted stored energy
80% lagging. mechanism
■■ Higher short-circuit current
■■ Drawout on extension rails
Inrush current switching ensures a ■■ Higher mechanical endurance
closing current equal to 600% of rated ■■ Integrally mounted wheels
■■ Higher insulation level
continuous current at rated maximum ■■ Quality Assurance Certificate
■■ Higher voltage ratings with K=1
voltage with power factor of 30% lagging
or less, and an opening current equal ■■ 3-cycle interrupting time
to rated continuous current at rated ■■ Higher switching life
maximum voltage with power factor
■■ Designed and tested to ANSI
between 80% leading and 80% lagging.
standards and higher
In accordance with ANSI C37.06, if a ■■ WR fixed retrofit configuration
short-circuit operation occurs before available
the completion of the listed switching
operations, maintenance is recommended
and possible functional part replacement
may be necessary, depending on previous
accumulated duty, fault magnitude and
expected future operations.
4.76, 8.25, 15 1200, 2000 33 kA and below 2000 10,000 10,000 750
4.76, 8.25, 15 3000 All 1000 5000 5000 400
4.76, 15 All 37 kA and above 1000 5000 5000 400
27 All All 500 2500 2500 100
38 All All 250 1500 1500 100
a Each operation is comprised of one closing plus one opening.
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-11
Table 5.1-6. Extra Capability Type VCP-WC Ratings (Symmetrical Current Basis), Rated K = 1
Identification Rated Values Mechanical
Circuit Voltage Insulation Current Maximum Rate of Capacitor Switching Ratings Endurance
Breaker Level Short-Circuit Current Permissible Rise of General Definite Purpose
Type Tripping Recovery Purpose
Delay Voltage Back-to-Back
Short-Time Current
Interrupting Time b
Current
Sym. Interrupting
Inrush Frequency
Voltage (1 min.)
for 3 Seconds a
Capacitor Bank
at Voltage (Isc)
Inrush Current
Capability
at 60 Hz
Current
kV K kV kV A kA % kA kA kA ms Seconds kV/µs A rms A rms kA kHz No-Load
rms rms Peak rms rms rms Peak rms Peak Operations
Total
50 VCP-W 25C 5.95 1 24 75 1200 25 50 31 97 25 50 2.0 0.9 400 & 630 400 & 630 20 & 20 6.5 & 5.5 10,000
2000 75 36 0.9 1000 1000 18 2.7 10,000
3000 d 75 36 0.8 250 — — — 5,000
50 VCP-W 40C 5.95 1 24 75 1200 40 75 58 139 40 50 2.0 0.9 630 630 15 3.5 10,000
2000 0.9 1000 1000 18 2.7 10,000
3000 d 0.8 250 — — — 5,000
50 VCP-W 50C 5.95 1 24 75 1200 50 57 64 139 50 50 2.0 0.9 630 630 15 3.5 10,000
2000 57 64 0.9 1000 1000 18 2.7 10,000
3000 d 52 62 0.8 250 — — — 5,000
50 VCP-W 63C 5.95 1 24 75 1200 63 62 83 175 63 50 2.0 1.1 250 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
2000 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
3000 d 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
75 VCP-W 50C 10.3 1 42 95 1200 50 57 64 139 50 50 2.0 0.9 630 630 15 3.5 10,000
2000 57 64 0.9 1000 1000 18 2.7 10,000
3000 d 52 62 0.8 250 — — — 5,000
150 VCP-W 25C 17.5 1 42 95 1200 25 50 31 97 f 25 50 2.0 0.9 400 & 600 g 400 & 600 g 20 & 20 6.5 & 5.5 10,000
2000 75 36 0.9 1000 g 1000 g 18 2.7 10,000
3000 d 75 36 0.8 250 g — — — 5,000
150 VCP-W 40C 17.5 1 42 95 1200 40 75 58 139 40 50 2.0 0.9 630 g 630 g 15 3.5 10,000
2000 0.9 1000 g 1000 g 18 2.7 10,000
3000 d 0.8 250 g — — — 5,000
150 VCP-W 50C 17.5 1 42 95 1200 50 57 64 139 50 50 2.0 0.9 630 g 630 g 15 3.5 10,000
2000 57 64 0.9 1000 g 1000 g 18 2.7 10,000
3000 d 52 62 0.8 250 g — — — 5,000
150 VCP-W 63C 15 1 42 95 1200 63 62 83 175 63 50 2.0 1.1 250 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
2000 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
3000 d 400 & 1600 e 8.8 & 7.7 1.6 & 0.465 10,000
a Except as noted.
b 3 cycles.
c Contact Eaton for higher RRRV or for more information.
d 4000 A FC rating available.
e C37.04.a-2003 Class C2 at 15 kV.
f Close and Latch Current for 1200 A Type 150 VCP-W 25C is proven at 15 kV. For sealed interrupters at high altitudes, switching voltage is not derated.
g Capacitor Switching Ratings are proven at 15 kV. For sealed interrupters at high altitudes, switching voltage is not derated.
h 2.5 seconds.
i 1.6 second.
j 1 second.
k 2000 A FC to 3000 A.
l 2500 A FC to 3000 A.
m Tested at 27 kV, 350 A isolated or back-to-back capacitor bank, inrush current 4.6 kA, inrush frequency 1.2 kHz.
Note: 38 kV, 2500 A and 3000 A WC breakers are not rated for rapid reclosing.
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-12
Type VCP-WG Generator Generator circuits have unique Generator Circuit Configuration
characteristics that require specially The transformer and generator can be
Circuit Breakers designed and tested circuit breakers. in close proximity to the circuit breaker.
The IEEE developed the special industry See Figure 5.1-4. Applications with
standard C37.013 and amendment high continuous current levels require
C37.013a-2007 to address these connections with large conductors of
characteristics. Eaton has dedicated years very low impedance. This construction
of research, design, enhancement and causes unique fault current and voltage
testing to create Eaton’s family of conditions as shown in Figure 5.1-5.
generator breakers.
The VCP-WG (drawout) and VCP-WRG Generator High Voltage
(fixed) circuit breakers meet, and even Circuit Breaker Circuit Breaker
exceed, the rigorous service duty “a” “b”
requirements for generator circuit
applications as defined by IEEE.
~
Generator Step-up
Eaton’s VCP-WG and VCP-WRG generator Transformer
breakers are available in two frame sizes.
The 29.00-inch frame (29.00 inches wide Figure 5.1-4. Generator Circuit Application
with front cover on) has ratings up to
VCP-WG Breaker (Front View) 15 kV, 63 kA and 3000 A (4000 A with High Continuous Current Levels
forced-air cooling). The 31.00-inch frame Generator circuit breakers must be able to
(31.00 inches wide with front cover on) handle high continuous current levels
has ratings up to 15 kV, 75 kA and 4000 A without overheating. VCP-WG drawout
(5000 A with forced-air cooling). The circuit breakers are designed to reliably
31.00-inch frame is also available in a operate up to 4000 A with natural air
fixed version with ratings up to 15 kV, convection cooling, and up to 5000 A with
75 kA and 6000 A (7000 A with forced- suitable enclosure fan cooling during
air cooling). overload conditions. VCP-WRG fixed
Count on Eaton’s innovative technology circuit breakers are designed to reliably
to handle high continuous ac current operate up to 6000 A with natural air
and voltage, then safely switch through convection cooling and up to 7000 A with
extreme out-of-phase voltages and suitable enclosure fan cooling during
high-stress asymmetrical currents overload conditions.
using “clean and green” vacuum
interruption without fail for over
10,000 normal operations.
Eaton’s VCP-WG generator circuit
VCP-WG Breaker (Rear View) breakers meet the strict service duty
requirements set forth by IEEE for
generator circuit applications, including:
Why generator circuit breakers?
■■ Specially rated generator breakers ■■ Generator circuit configuration
typically should be used on generator ■■ High continuous current levels
applications 10,000 kW and above ■■ Unique fault current conditions
■■ A generator circuit breaker, properly
❏❏ Transformer-fed faults
rated and tested to the appropriate
industry standard, can protect the ❏❏ Generator-fed faults
generator from damage, or even ■■ Unique voltage conditions
complete failure, that could occur when ❏❏ Very fast RRRV
feeding a faulted transformer, and also
can protect the transformer, in the event ❏❏ Out-of-phase switching
that a fault should occur in the generator
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-13
Unique Fault Current Conditions The high ratio of inductive reactance to The IEEE standard requires verification
System-source (aka, transformer-fed) resistance (X/R ratio) of the system can that the circuit breaker can interrupt
faults (see Figure 5.1-4, fault location “a”) cause the dc component of the fault under these severe conditions. Eaton’s
can be extremely high. The full energy of current to exceed 100%. The asymmetrical VCP-WG generator circuit breakers have
the power system feeds the fault, and the fault current peak becomes high enough demonstrated their ability to interrupt
low impedance of the fault current path and its decay becomes slow enough three-phase fault current levels up to
does very little to limit the fault current. that the natural current zero is delayed 135% dc content under delayed current
Eaton’s type VCP-WG Generator Circuit for several cycles. The circuit breaker zero conditions.
Breakers are ideal for interrupting such experiences longer arcing time and more
high fault currents because they have electrical, thermal and mechanical stress
demonstrated high interruption ratings during the interruption.
up to 75 kA, with high dc fault content
up to 75%, as proven by high power
laboratory tests. Table 5.1-7. Breaker Operations Information
Generator-source (aka, generator-fed) Circuit Breaker Ratings Maximum Number of Operations a
faults, see Figure 5.1-4, fault location “b”) Rated Rated Rated Between No-Load Rated Inrush
can cause a severe condition called Maximum Continuous Short-Circuit Servicing Mechanical Continuous Current
Voltage Current Current Current Switching
“Delayed Current Zero,” see Figure 5.1-5). kV rms Amperes kA rms, sym. Switching
4.76, 8.25, 15 1200, 2000 33 kA and below 2000 10,000 10,000 750
4.76, 8.25, 15 3000 All 1000 5000 5000 400
4.76, 15 All 37 kA and above 1000 5000 5000 400
27 All All 500 2500 2500 100
38 All All 250 1500 1500 100
a Each operation is comprised of one closing plus one opening.
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-14
Contact Parting
(RRRV) due to the high natural frequency 8
and low impedance and very low stray Current
capacitance. VCP-WG generator circuit pu
breakers are designed to interrupt fault 6
current levels with very fast RRRV in
accordance with IEEE standard C37.013
4
and C37.013a. VCP-WG generator circuit Idc
breakers have a distinct ability to perform
under out-of-phase conditions when 2
the generator and power system voltages
are not in sync. The voltages across the
open contacts can be as high as twice 0
the rated line-to-ground voltage of the
system. The IEEE standard requires
demonstration by test that the generator -2
circuit breaker can switch under specified
out-of-phase conditions.
-4
Versatility in Application
Eaton’s generator vacuum circuit breakers -6
0 20 40 60 80 100 120 140 160
are available in drawout (VCP-WG) or fixed
(VCP-WRG) configurations to provide for
superior performance and versatility. Figure 5.1-5. Generator-Fed Faults Can Experience Delayed Current Zero, Where the High Inductance to
Many industrial and commercial power Resistance Ratio of the System Can Cause the dc Component of the Fault Current to Exceed 100%
systems now include small generators as
a local source of power. New applications
are arising as a result of the de-regulation 10.00 10.00 10.00 10.00
of the utility industry, and the construction (254.0) (254.0) (254.0) (254.0)
of smaller packaged power plants. Eaton’s 29.00 30.00 29.00 26.60
generator breakers interrupt large (736.6) (762.0) (736.6) (675.6)
short-circuit currents in a small three-
pole package.
Typical applications include: 31.40 31.20
(797.6) (792.5)
■■ Electric utilities: fossil, hydro and
wind power
■■ Packaged power plants
■■ Industrial companies using combined 24.60 24.60
(624.8) (624.8)
cycle/combustion turbine plants
■■ Government and military 29-Inch Frame Drawout VCP-WG 29-Inch Frame Fixed VCP-WRG
■■ Commercial institutions
■■ Petrochemical and process industries
10.00 10.00 10.00 10.00
■■ Forestry, pulp and paper (254.0) (254.0) (254.0) (254.0)
30.60 30.00 30.60 26.80*
■■ Mining, exploration and marine
(777.2) (762.0) (777.2) (680.7)
The VCP-WG is the world’s generator
circuit breaker for reliable and robust
power generation protection.
39.60 39.30
(1005.8) (998.2)
Figure 5.1-6. Type VCP-WG (Drawout) and Type VCP-WRG (Fixed) Circuit Breakers
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-15
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-16
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-17
When three VTs are used, they are The minimum number of current
connected line-to-ground, and provide transformers for circuit relaying and
phase-to-phase (Vab, Vbc, Vca), as well instruments is three current transformers,
as phase-to-ground (Va, Vb, Vc) voltages one for each phase or two-phase
for metering and relaying. connected current transformers and
one zero-sequence current transformer.
If metering or relaying application requires Separate sets of current transformers
phase-to-ground voltages, use three VTs, are required for differential relays.
each connected L-G. If not, use of two
VTs connected L-L is sufficient. The minimum pickup of a ground
relay in the residual of three-phase
Protective Relays For ground detection, three VTs connected current transformers is
connected in Line-to-ground/ primarily determined by the current
Eaton can provide a wide range of broken-delta are used. transformer ratio. The relay pickup
protective relays to meet you most
A single VT, when used, can be connected can be reduced by adding one residual
complex protection and system needs.
line-to-line (it will provide line-to-line connected auxiliary current transformer.
output, for example Vab or Vbc or Vca), This connection is very desirable on main
or line-to-ground (it will provide line-to- incoming and tie circuits of low resistance
ground output, for example Va or Vb or grounded circuits.
Vc). Generally, a single VT is used to Standard accuracy current transformers
derive voltage signal for synchronizing are normally more than adequate for most
or Over Voltage/Under Voltage function. standard applications of microprocessor-
based protective relays and meters. See
Table 5.1-11 for CT accuracy information.
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-18
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-19
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-20
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-21
A solid (non-blinking) light indicates that The remote LED lights are not included Technical Data
the breaker/auxiliary has reached and with MR2. If the customer needs to
stopped in the selected position. In case operate the MR2 with the hand-held Control Supply Ratings
normal operation fails, the appropriate pendant, the pendant becomes the ■■ Nominal control voltage—120 Vac,
error code is displayed in a separate master and will override the customer’s 50 or 60 Hz, single-phase
two-character LED display window on the remote control signals.
■■ Control voltage range—100 to 140 Vac,
pendant. A list of various error codes and
their descriptions along with suggested The VC-W MR2 controller is also equipped 50 or 60 Hz
corrective actions are printed on the with terminal blocks to allow the customer ■■ Time to travel from connect to
back side of the pendant. Examples of to interface with the controller via their disconnect, or disconnect to
error states: motor overcurrent, motor SCADA system using a Modbus interface. connect—50 seconds maximum
overtemperature, motor timed out, Please note that only one of the two
■■ Current draw during the travel—
breaker position unknown, open options, discrete I/O interface or Modbus
interface, can be used, but not both. 15 A maximum for about 3 seconds
permissive, communication error and 3.6 A for about 24 seconds
and no breaker/auxiliary. Figure 5.1-8 shows an illustration of a
typical Modbus control example. ■■ Optional dry output contacts when
In addition to pendant, three optional I/O Additional components shown outside included for position indications are
interfaces can be supplied as follows: the MR2 controller in Figure 5.1-8 are not rated for 125 Vac, 2 A
included with the MR2. System-level ■■ External permissive contacts, when
1. I/O interface to allow racking of controls can be optionally supplied by
breaker (connect, test, disconnect) or used, must be rated for 24 Vdc, 50 mA
Eaton’s Engineering Services & Systems.
auxiliary drawer (connect, disconnect) If the customer needs to operate the MR2
by external hardwired dry contacts with the hand-held pendant, the pendant Requirements for External Contacts
and 24 Vdc output for corresponding becomes the master and will override and LEDs when Interfacing with MR2
remote position indicating LEDs. the Modbus interface. Error codes are ■■ External contacts should be rated for
2. I/O board that provided dry contacts displayed on Modbus devices when minimum open circuit voltage of
for remote indication of breaker controlling the MR2 with Modbus and 24 Vdc, and be able to close and
(connect, intermediate, test, on the pendant when controlling with carry 5 mA at 24 Vdc
disconnect)/auxiliary drawer (connect, the pendant. ■■ When remote LEDs are used, use
test) position within its compartment. 24 Vdc rated LEDs, current up to 20 mA
■■ Optional dry output contacts when
3. I/O interface to allow breaker open/
close functions via external hardwired included for position indications are
dry contacts and 24 Vdc output for rated for 125 Vac, 2 A
corresponding remote open/close ■■ External permissive contacts, when
status LEDs. used, must be rated for 24 Vdc, 50 mA
It is the customer’s responsibility to
provide single-phase 120 V, 50 or 60 Hz
nominal supply for the MR2 controller.
It can be derived from within the
switchgear if an appropriate control
power transformer is available within
the switchgear.
Type VC-W MR2 motorized racking
accessory has been endurance tested and
guaranteed for 500 operations as
required by IEEE C37.20.2.
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-22
Figure 5.1-7. VC-W MR2 Controller Interface for a VCB with Distinct Test Position and Open/Close Functions
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-23
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-24
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-25
System Options
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-26
Input
Temp Sensor Terminal InsulGard
Block Relay Optional
Humidity Sensor Modem
120 Vac
Auxiliary
Signals (up to 15 Total) from Power Output
PD Sensors (Coupling Capacitors, Alarm
RFCT Sensor, RTD Input, etc.) Status
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Devices 5.1-27
Radio Frequency Current Sensor (RFCT) Epoxy Bottles with Stress Shield
(5/15 kV Switchgear)
PD Sensors
PD Sensors
PD Sensors are Installed
in Switchgear Cubicle
0
Cub12
Cub13
Cub14
Cub15
Cub16
Cub11
Cub1
Cub2
Cub3
Cub4
Cub5
Cub6
Cub7
Cub8
Cub9
Figure 5-12. How the Process Works—Data Analysis and Report (Sample)
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-28
Standard Height—Layouts
Typical Main-Tie-Main Arrangements (Standard Metal-Clad)
Note: Arrangements shown in Figures 5.1-13–5.1-15 can be provided in 26.00-inch (660.4 mm) wide, 95.00-inch (2413.0 mm) high,
96.25-inch (2444.8 mm) deep structures with 50VCPWND, 1200 A circuit breakers.
Note: R = Multi-function relay, M = Multi-function meter.
Bus 1 Bus 2
52-M1 52-M2
1200 A 1200 or 1200 A 1200 A 1200 or
2000 A 2000 A
R M R M R M R M R M
Figure 5.1-13. Typical Main-Tie-Main Arrangement with Bus and Line VTs and Line CPTs
5 or 15 kV VCP-W Switchgear, 1200 or 2000 A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
Bus 1 Bus 2
52-M1 52-M2
1200 or 1200 A 1200 A 1200 or
2000 A 2000A
R M R M R M R M
Figure 5.1-14. Typical Main-Tie-Main Arrangement with Bus and Line VTs, but without Line CPTs—Preferred Arrangement
5 or 15 kV VCP-W Switchgear, 1200 or 2000 A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-29
Feeder Feeder
Line VTs
CTs
CTs
R M R M
Bus 1 Bus 2
52-M1 52-M2
1200 A 1200 or 1200 or 1200 A
2000 A 2000 A
R M R M R M R M
Figure 5.1-15. Typical Main-Tie-Main Arrangement with Bus and Line VTs, but without Line CPTs—Alternate Arrangement
5 or 15 kV VCP-W Switchgear, 1200 or 2000 A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
Bus 1 Bus 2
R M R M
CTs CTs
Line VTs Line VTs
Source 1 Source 2
Figure 5.1-16. Typical Main-Tie-Main Arrangement with Bus and Line VTs, and Line CPTs
5 or 15 kV VCP-W Switchgear, 3000 A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-30
R R
M M
52-M1 52-M2
3000 A 52-T 3000 A
3000 A
Bus 1 Bus 2
Source 1 Source 2
Figure 5-17. Typical Main-Tie-Main Arrangement with Bus and Line VTs
5 or 15 kV VCP-W Switchgear, 3000 A Mains and Tie, 36.00-Inch (914.4 mm) Wide Structures
a This arrangement can be supplied with cooling fans to allow 4000 A continuous.
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-31
3000 Ampere
Breaker bc
Vent Area
Drawout
Auxiliary
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-32
Standard Height—
Dimensions in Inches (mm)
Note: Dimensions for estimating purposes only.
Typical Units
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-33
3.00 (76.2)
23.00 Rear
1
(584.2) 36.00
3 2.00 32.00 2.00
(914.4)
(50.8) (812.8) (50.8)
3.00
4
(76.2)
5B 5B
23.00
2 (584.2)
28.00
(711.2)
0.88
(4) Knockouts (22.4)
5A 5A 0.88
for Top Secondary (22.4)
Conduit Entry
9.00 6
(228.6)
6.00
(152.4) 96.25
(2444.8) 44.50
7.00 (1130.3)
(177.8) 9 60.88
(1546.4)
0.56 0.56
3.00 3.00
(14.2) (14.2)
(76.2) (76.2)
Front 5A 5A 3.38
(85.9)
3.00 3.00
(76.2) (76.2)
Figure 5.1-27. Top View of Typical Indoor Breaker 16.00 19.00
7
0.25
(406.4) (482.6)
and Auxiliary Structures (6.4)
Front
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-34
7.00 (177.8)
11.50 (292.1)
Upper
2 2 2 7 Hinged
Panel
1-Large Relay
Case
Two Conduits per Breaker 3 3 3 3 3 2-Small Relay
Case
4 3-Instrument
6 5 5 4-Test Switch
4
5-Switch
6-Lock-out
Relay or
3 3 3 3 3
Switch
4 7-Metering
6 5 5 Unit
2 2 2 7 Lower
One Conduit per Breaker Hinged
Panel
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-35
6.00
(152.4)
Attach to the Switchgear 4.00
Channels Using Supplied Hardware (101.6)
1.00 (25.4)
Optional
Rear Door
View “A”
2
36.00 (914.4)
7 GA Steel
2.75 (69.8) Minimum Recommended Clearance
Mounting Clip
Supplied by Eaton X
4.50 (114.3) C 6.00 (152.4)
L
7.00 (177.8)
3.31 (84.1) 4.50 (114.3)
3 7.12 (180.8)
2.00 (50.8)
21.25 (539.8) 4.38 (111.3) 11.50 (292.1)
3 7.12
(180.8)
8.00 (203.2) 1 20.50
(520.7)
90.69 (2303.5)
90.27 (2292.8) 90.27 (2292.8)
101.25 (2571.8)
0.56 (14.2)
3.00 (76.2)
0.56 (14.2)
4
3.00 (76.2)
Channel
Locations
0.25 3.38 (85.9) 2.00 (50.8)
3.88 (98.5)
(6.4)
36 36
10.56 (268.2) 4.50 (114.3)
7.67 (194.8)
0.12 0.12
(3.0) (3.0)
2 X
View X-X
Outdoor Outdoor
End Wall End Wall
Front of Switchgear
Figure 5.1-31. 5/15 kV Switchgear Outdoor Aisleless Base Plan (Typical Details)—Dimensions in Inches (mm)
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-36
6.00
(152.4)
Attach to the Switchgear 4.00
Attach to the Floor at Channels Using Supplied Hardware (101.6)
1.00 (25.4)
One of the Two Hole Locations
Shown Using 5/8" Grade 5 Bolt
or Better Torque to 150 ft-lb 3.00 4.00 (101.6)
6.50 (165.1) (76.2)
1.25
(31.8) 4.00 4.88 (124.0)
4.25
(101.6) 0.75 (19.1)
1 Location for station 3 Power cable entrance (108.0)
ground connection. 2.75 0.63 (16.0)
space. Refer to shop
order base plan drawing (69.8)
5.75 (146.1)
2 5 Attach switchgear to for conduit locations.
foundation using one Conduit projection 6.00 (152.4) 4.50 (114.3)
of the two holes. not to exceed
Use 5/8" Grade 5 or 8.00 inches (203.2 mm). 5.75 (146.1)
3.75
better bolt. Torque
(95.3)
to 150 ft-lb 4 Secondary control wiring Attach to the Floor at
(Total of 4 mounting conduit entrance space. 5 One of the Two Hole Locations
bolts per vertical Conduit stub ups not to Mounting Angle Details Shown Using 5/8" Grade 5 Bolt or
section, one at project more than Better Torque to 150 ft-lb
each corner.) 7.00 inches (177.8 mm). 2
Mounting Clip Details
5 Finished foundation
surface shall be level within
0.06-inch (1.5 mm) 4.50
in 36 inches (914.4 mm) (114.3)
left-to-right, front-to-back, 2.00 (50.8)
5/8" Bolt & HDWE
and diagonally, as measured
Supplied by
by a laser level.
Customer
6.00
(152.4)
2.00 (50.8)
Optional
Rear Door
View “A”
4.50 (114.3)
7.00 (177.8)
3 7.12 (180.8) 2.00
(50.8)
21.25 (539.8) 4.38 (111.3) 11.50 (292.1)
3 7.12
Locations
(180.8)
Channel
20.50
8.00 (203.2) 1
(520.7)
90.69 (2303.5)
90.27
(2292.8)
0.56 (14.2)
3.00 (76.2)
0.56 (14.2)
4
3.00 (76.2) 3.38 (85.9)
0.70
(17.8) 2.00
0.10 0.10 (50.8)
(2.5) (2.5)
Outdoor 4.50
0.12 (3.0) End Wall X (114.3)
2.75 (69.8)
View X-X
4.50 (114.3)
38.00 (965.2) 36.00 (914.4) 36.00 (914.4) 36.00 (914.4) 38.00 (965.2)
Front of Switchgear
Figure 5.1-32. 5/15 kV Switchgear Outdoor Sheltered Aisle Base Plan (Typical Details)—Dimensions in Inches (mm)
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-37
Note: 1 Location for station 2 5 Attach switchgear to 3 Power cable entrance 4 Secondary control wiring conduit
First install both ground connection foundation using one space. Refer to shop entrance space. Conduit stub ups
rows of switchgear typical each end unit. of the two holes. order base plan drawing not to project more than
then install aisle Use 5/8" Grade 5 or for conduit locations. 7.00 inches (177.8 mm).
parts per drawing. (Later) better bolt. Torque Conduit projection
to 150 ft-lb. not to exceed
(Total of 4 mounting 8.00 inches (203.2 mm). Attach to the Floor at
6.00 One of the Two Hole Locations
bolts per vertical (152.4)
6.50 section, one at each Shown Using 5/8" Grade 5 Bolt or
(165.1) corner.) Attach to the Switchgear Better Torque to 150 ft-lb
Channels Using
6 Finished foundation 6.00
5.75 Supplied Hardware
surface shall be level (152.4)
(146.1)
within 0.06-inch
(1.5 mm) in 36.00 inches 4.00 (101.6)
5.75 (146.1) (914.4 mm) left-to-right,
3.75
(95.3) front-to-back, and 4.88 (124.0)
diagonally, as measured
by a laser level. 2
5
Mounting Clip Details
Mounting Angle Details
Optional
Rear Door X
2
7 GA Steel 3.00 Minimum
36.00
Mounting Clip (76.2) Recommended
(914.4) 6.00 (152.4)
Supplied by Eaton Clearance
4.00 CL
(101.6)
4.50 (114.3)
7.00 (177.8)
3 7.12 (180.8) 2.00
21.25 (539.8) 4.38 (111.3) 11.50 (292.1) (50.8)
Locations
3
Channel
8.00 (203.2) 1 20.50
7.12 (180.8) (520.7)
3.00 (76.2)
0.56 (14.2)
4 3.00 (76.2) 3.38 (85.8)
Locations
1.50 (38.1)
Channel
Typical 3.50 (88.9)
1.50
0.75 (38.1)
(19.1) 11.50
Removable 261.50
(292.1)
Covers 11.50 68.96 (6642.1)
(292.1) (1751.6)
Aisle 11.50
(292.1)
0.75 2.00
(19.1) (50.8)
4.00 (101.6)
0.12 0.12
(3.0) (3.0)
Outdoor
4 Outdoor
End Wall
End Wall
38.00 36.00 36.00 36.00 38.00
(965.2) (914.4) (914.4) (914.4) (965.2)
90.27
(2292.8)
Locations
Channel
2.00
0.12 (3.0) (50.8) 4.50 (114.3)
3.00 (76.2) 36.00 Minimum
4.00 (101.6) (914.4) Recommended
Clearance View X-X
Figure 5.1-33. 5/15 kV Switchgear Outdoor Common Aisle Base Plan (Typical Details)—Dimensions in Inches (mm)
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Layouts and Dimensions 5.1-38
Access for
VT Cables
VT Cables
Blank Either/Or
VT or CPT
80.00 Breaker
(2032.0)
CT
CT
36.00
CT
CT
HTR BYZ(1)
SC
86.25 a
Auxiliary Blank Auxiliary
(2190.8)
Figure 5.1-34. 36.00-Inch (660.4 mm) Wide VCP-W Low Profile Indoor Unit
a Other depths possible depending on cable entry direction and VT/CPT Auxiliary
connections. Contact Eaton. VCP-W VCP-W
Breaker Breaker
1200 or 1200, 2000
2000 A or 3000 A
Auxiliary
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Application Data 5.1-39
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Application Data 5.1-40
Standard Height—Weights
B/B 1200 2400 (1090) 3200 (1453) 4200 (1907) 7200 (3269)
2000 2500 (1135) 3300 (1500) 4300 (1952) 7400 (3360)
3000 2600 (1180) 3400 (1545) 4400 (1998) 7600 (3450)
4000 2700 (1226) 3500 (1590) 4500 (2045) 7700 (3500)
B/A 1200 2300 (1044) 2900 (1317) 4100 (1861) 7000 (3178)
or 2000 2400 (1090) 3000 (1362) 4200 (1907) 7200 (3269)
A/B 3000 2500 (1135) 3100 (1407) 4300 (1952) 7400 (3360)
4000 2600 (1180) 3200 (1453) 4400 (1998) 7500 (3409)
A/A 1200 2000 (908) 2600 (1180) 3800 (1725) 6400 (2906)
2000 2100 (953) 2700 (1226) 3900 (1771) 6600 (2996)
3000 2200 (999) 2800 (1271) 4000 (1816) 6800 (3087)
4000 2300 (1046) 2900 (1317) 4100 (1861) 6900 (3136)
50 VCP-W 250, 40C, 25, 40 350 (159) 410 (186) 525 (238)
50 VCP-W 350, 50C, 50 460 (209) 490 (222) 525 (238)
50 VCP-W 500, 63C, 63 575 (261) 575 (261) 575 (261)
75 VCP-W 500, 50C, 50 375 (170) 410 (186) 525 (238)
150 VCP-W 500, 25C, 25 350 (159) 410 (186) 525 (238)
150 VCP-W 750, 40C, 40 350 (159) 410 (186) 525 (238)
150 VCP-W 1000, 50C, 50 460 (209) 490 (222) 525 (238)
150 VCP-W 1500, 63C, 63 575 (261) 575 (261) 575 (261)
a Impact weight = 1.5 times static weight.
Low Profile—Weights
Typical Weights
Table 5.1-17. Assemblies (Less Breakers, See Table 5.1-16 for Breakers)
Vertical Section Main Bus Rating, Indoor Structure
Type Amperes Lb (kg)
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Application Data 5.1-41
Heat Loss
Table 5.1-18. Heat Loss in Watts at Full Rating, at 60 Hz
Type of Switchgear Breaker 1200 A 2000 A 2500 A 3000 A 4000 A
Assembly Rating Fan Cooled
a Line-to-line connection only available. Refer to Eaton for other voltages and kVA ratings.
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Application Data 5.1-42
Typical Schematics
P
(+)
CS CS PR
C T
11
Spring
9UV
WL GL RL
Charged
Indicating
Light
UV
10UV
dc Source
14
TRCO_51N
TRCS_
TCSSLT
LOCATION
12
1 2
9A
4 7 5 6 7 8 9 10 3
3A
3
9
13
61
Y
51
53
55
57
LS1 a
bb a
Y SR
62
ST
52
56
58
54
ST 18 17 16 15 22 2
M b b 1
a
LC a
PS2 LS2 LS2
10A
PS Y
bb 1 bb aa
Not Available when Second 13
14
10
4
24 21 20 19
Trip Coil Option is Chosen
TRCO_51N
TRCS_
TCSSLT
LOCATION
Options
LOCATION
CCBSN CGL
LOCATION LOCATION
TCSSLT
TRCS_
TRCO_51N
N
(-)
1 S-CPU
S-TRU
FUSE
CAC120
LOCATION
S-MRU
CS
C
CS PR
T
11
Spring
9UV
WL GL RL
Charged
Indicating
Light
UV
9UV
10UV
ac Source
14
TRCO_51N
TRCS_
TCSSLT
LOCATION
ac (+) 12 UV
1 2
9A
4 5 9 6 7 8 10 3
10UV
7
Cap Trip Dev
3A
9
3
13
55
61
Y
51
57
53
a a
LS1 ac (–)
bb
Y SR
62
52
58
ST
54
ST 2
M 1
18 17 15 22 For ac UV
b b a
LC
a Trip Only
PS2 LS2 LS2 a
10A
bb PS Y
1 bb aa
Not Available when Second 13
14
56
10
4
2
LOCATION
CCBSN CRL
LOCATION LOCATION
TRCS_
TRSS
TRCO_51N
Options
Figure 5.1-37. Typical 5/15/27 kV VCP-W “dc” and “ac” Control Schematics
Legend: CS = Breaker Control Switch–Close Operation: LS1 = Closed until springs are fully charged.
C = Breaker Control Switch–Close bb = Closed until springs are fully charged.
CS = Breaker Control Switch–Trip LS2 = Open until springs are fully charged.
T = Breaker Control Switch–Trip aa = Open until springs are fully charged.
Y = Anti Pump Relay LS2 = Closed until springs are fully charged.
SR = Spring Release Coil (Coil) bb = Closed until springs are fully charged.
M = Spring Charge Motor LC = Open until mechanism is reset.
ST = Shunt Trip PS1 = Open in all except between “Test” and “Connected” positions.
PR = Protective Relay PS2 = Closed in all except between “Test” and “Connected” positions.
= Secondary Disconnect
>>
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
Application Data 5.1-43
(+)
CS CS PR
C T
11 U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
Spring WL GL RL
Charged
9UV
Indicating
Light U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
UV U24
10UV
dc Source
14
TRCO_51N
TRCS_
TCSSLT
LOCATION
12 OPTIONS
1 2 4 7 5 6 7 8 9 10 3
9A
13
57
3
61
3A
51
53
55
Y
LS1 a
bb a
54
62
Y
52
56
58
SR
ST
ST 18 17 16 15 22 2
b
LOCATION
M 1
b
10A
LC a
PS2 PS Y LS2 LS2 13
bb 1 bb aa TRCO_51N
TRCS_
TCSSLT
LOCATION
14
10
a
4
24 21 20 19
N
LOCATION
TRCS_
TCSSLT
TRCO_51N
CS
C U1 U2 U3 U4 U5 U6 U7 U8 U9 U10
CS PR
T
11
Spring WL GL RL
Charged
9UV
U24 U24 U23 U22 U21 U20 U19 U18 U17 U16 U15
Indicating
Light
Auxiliary Switch #2 Optional
UV
10UV
ac Source
9UV
OPTIONS
TRCO_51N
TRCS_
TCSSLT
LOCATION
14
ac (+) 12 UV
1 2 4 7 5 9 6 7 8 10 3
10UV
9A
9
3A
3
61
55
51
a
53
57
Y
LS1 ac (-) a
bb
62
52
58
54
Y SR
ST
ST
1
18 17 15 22 2
For ac UV
M b a
LOCATION
b
Trip Only
10A
LC
PS2 PS Y LS2 LS2 a 13
bb 1 bb aa TRCO_51N
TRCS_
TCSSLT
LOCATION
14
10
a
56
4
24 21 20 16 19
2
LOCATION
TRCS_
TRSS
TRCO_51N
Legend: CS = Breaker Control Switch–Close Operation: LS1 = Closed until springs are fully charged.
C = Breaker Control Switch–Close bb = Closed until springs are fully charged.
CS = Breaker Control Switch–Trip LS2 = Open until springs are fully charged.
T = Breaker Control Switch–Trip aa = Open until springs are fully charged.
Y = Anti Pump Relay LS2 = Closed until springs are fully charged.
SR = Spring Release Coil (Coil) bb = Closed until springs are fully charged.
M = Spring Charge Motor LC = Open until mechanism is reset.
ST = Shunt Trip PS1 = Open in all except between “Test” and “Connected” positions.
PR = Protective Relay PS2 = Closed in all except between “Test” and “Connected” positions.
= Secondary Disconnect
>>
EATON www.eaton.com
VacClad-W Metal-Clad Switchear Design Guide CA022004EN
5 and 15 kV—36-inch wide Effective November 2018
5.1-44
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2018 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. CA022004EN / Z21326 All other trademarks are property
November 2018 of their respective owners.