'10 • PAC-DB-142
DATA BOOK
V Multi System
(OUTDOOR UNIT) (INDOOR UNIT)
FDC71VN FDC140VN FDT40VD FDEN40VD
100VN 140VS 50VD 50VD
100VS 200VS 60VD 60VD
125VN 250VS 71VD 71VD
125VS 100VD 100VD
125VD 125VD
Ragarding the Service Manual please see the Manual No.’10 • PAC-SM-143.
TABLE OF CONTENTS
- -
CONTENTS
- -
Series code
Inveter type
Product capacity
Model name FDTC : Ceiling cassette-4way compact type
FDT : Ceiling cassette-4way type
FDEN : Ceiling suspended type
FDUM : Duct connected-Low/Middle static
pressure type
SRC : Outdoor unit
Series code
(blank)
: Single type
P : Twin type
T : Triple type
D : Double Twin type
Applicable power source...See the specification
Product capacity
Model name FDTC : Ceiling cassette-4way compact type
FDT : Ceiling cassette-4way type
FDEN : Ceiling suspended type
FDUM : Duct connected-Low/Middle static
pressure type
FDU : Duct connected-High static pressuret type
FDC : Outdoor unit
- -
1.1. SPECIFICATIONS
(1) Ceiling cassette-4way compact type (FDTC)
(a) Single type Adapted to RoHS directive
Model FDTC40ZIXVD
Indoor unit FDTC40VD Outdoor unit SRC40ZIX-S
Item Panel TC-PSA-25W-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 4.0 [ 1.8 (Min.)~4.7 (Max.)] 4.5 [ 2.0 (Min.)~5.4 (Max.)]
Power consumption kW 1.04 1.10
Running current A 4.6 / 4.8 4.9 / 5.2
Power factor % 98 / 99 97
Inrush current A 5 < Max.running current 12 >
Cooling P-Hi : 47 Hi : 42 Me : 36 Lo : 30
Sound Pressure Level dB(A) 47
Heating P-Hi : 47 Hi : 42 Me : 36 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 640 × 800 × 290
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 45 < Direct line start >
Cooling P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 7
Air flow (Standard) CMM 40
Heating P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line: I/Uφ6.35 (1/4") Pipeφ6.35 (1/4") x 0.8 O/Uφ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7 (1/2") x 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- -
Model FDTC50ZIXVD
Indoor unit FDTC50VD Outdoor unit SRC50ZIX-S
Item Panel TC-PSA-25W-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 5.0 [ 2.2 (Min.)~5.6 (Max.)] 5.4 [ 2.5 (Min.)~6.3 (Max.)]
Power consumption kW 1.56 1.45
Running current A 6.9 / 7.2 6.4 / 6.7
Power factor % 99 / 98 99
Inrush current A 5 < Max.running current 14 >
Cooling P-Hi : 47 Hi : 42 Me : 36 Lo : 30
Sound Pressure Level dB(A) 47
Heating P-Hi : 47 Hi : 42 Me : 36 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 640 × 800 × 290
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 45 < Direct line start >
Cooling P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 7
Air flow (Standard) CMM 40
Heating P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line: I/Uφ6.35 (1/4") Pipeφ6.35 (1/4") x 0.8 O/Uφ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7(1/2") x 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- -
Model FDTC60ZIXVD
Indoor unit FDTC60VD Outdoor unit SRC60ZIX-S
Item Panel TC-PSA-25W-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 5.6 [ 2.8(Min.)~6.3(Max.)] 6.7 [ 3.1(Min.)~6.7(Max.)]
Power consumption kW 1.99 2.08
Running current A 8.3 / 8.7 8.7 / 9.1
Power factor % 96 96
Inrush current A 5 < Max.running current 14 >
Cooling P-Hi : 47 Hi : 46 Me : 39 Lo : 30
Sound Pressure Level dB(A) 48
Heating P-Hi : 47 Hi : 46 Me : 39 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 640 × 800 × 290
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 45 < Direct line start >
Cooling P-Hi : 13.5 Hi : 13.5 Me : 10 Lo : 7
Air flow (Standard) CMM 40
Heating P-Hi : 13.5 Hi : 13.5 Me : 10 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") Pipeφ6.35 (1/4") x 0.8 O/Uφ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7(1/2") x 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- -
Model FDTC71VNPVD
Indoor unit FDTC40VD (2 units) Outdoor unit FDC71VN
Item Panel TC-PSA-25W-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 7.1 [ 3.2 (Min.)~8.0 (Max.)] 8.0 [ 3.6 (Min.)~9.0 (Max.)]
Power consumption kW 1.91 2.08
Running current A 8.3 / 8.8 9.0 / 9.6
Power factor % 99 99 / 98
Inrush current A 5 < Max.running current 17 >
Cooling P-Hi : 47 Hi : 42 Me : 36 Lo : 30
Sound Pressure Level dB(A) 48
Heating P-Hi : 47 Hi : 42 Me : 36 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 750 × 968 × 340
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 60
Refrigerant equipment
— 2YC45DXD × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.65 FVC50K
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 86 < Direct line start >
Cooling P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 7
Air flow (Standard) CMM Cooling : 60, Heating : 50
Heating P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") x 0.8 ①φ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") x 0.8 ①φ15.88 (5/8") x 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 2.95kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose —
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-TA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- -
Model FDTC100VNPVD
Indoor unit FDTC50VD (2 units) Outdoor unit FDC100VN
Item Panel TC-PSA-25W-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.84 3.08
Running current A 12.4 / 13.0 13.5 / 14.1
Power factor % 99 99
Inrush current A 5 < Max.running current 24 >
Cooling P-Hi : 47 Hi : 42 Me : 36 Lo : 30
Sound Pressure Level dB(A) 49
Heating P-Hi : 47 HI : 42 Me : 36 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 81
Refrigerant equipment
— RMT5126MDE2×1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 86 < Direct line start >
Cooling P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 7
Air flow (Standard) CMM Cooling : 75, Heating : 73
Heating P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") x 0.8 ①φ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") x 0.8 ①φ15.88 (5/8") x 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) When
wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- -
Model FDTC100VSPVD
Indoor unit FDTC50VD (2 units) Outdoor unit FDC100VS
Item Panel TC-PSA-25W-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.84 3.08
Running current A 4.2 / 4.4 4.5 / 4.8
Power factor % 98 99 / 97
Inrush current A 5 < Max.running current 15 >
Cooling P-Hi : 47 Hi : 42 Me : 36 Lo : 30
Sound Pressure Level dB(A) 49
Heating P-Hi : 47 Hi : 42 Me : 36 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 86 < Direct line start >
Cooling P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 7
Air flow (Standard) CMM Cooling : 75, Heating : 73
Heating P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") x 0.8 ①φ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") x 0.8 ①φ15.88 (5/8") x 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- -
Model FDTC125VNPVD
Indoor unit FDTC60VD (2 units) Outdoor unit FDC125VN
Item Panel TC-PSA-25W-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 5.35 4.62
Running current A 24.0 / 25.1 20.7 / 21.6
Power factor % 97 97
Inrush current A 5 < Max.running current 27 >
Cooling P-Hi : 47 Hi : 46 Me : 39 Lo : 30
Sound Pressure Level dB(A) Cooling : 50 Heating : 51
Heating P-Hi : 47 Hi : 46 Me : 39 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 86 < Direct line start >
Cooling P-Hi : 13.5 Hi : 13.5 Me : 10 Lo : 7
Air flow (Standard) CMM Cooling : 75, Heating : 73
Heating P-Hi : 13.5 Hi : 13.5 Me : 10 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") x 0.8 ①φ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") x 0.8 ①φ15.88 (5/8") x 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- 10 -
Model FDTC125VSPVD
Indoor unit FDTC60VD (2 units) Outdoor unit FDC125VS
Item Panel TC-PSA-25W-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 5.35 4.62
Running current A 8.0 / 8.4 6.9 / 7.2
Power factor % 97 97
Inrush current A 5 < Max.running current 15 >
Cooling P-Hi : 47 Hi : 46 Me : 39 Lo : 30
Sound Pressure Level dB(A) Cooling : 50 Heating : 51
Heating P-Hi : 47 Hi : 46 Me : 39 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 86 < Direct line start >
Cooling P-Hi : 13.5 Hi : 13.5 Me : 10 Lo : 7
Air flow (Standard) CMM Cooling : 75, Heating : 73
Heating P-Hi : 13.5 Hi : 13.5 Me : 10 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") x 0.8 ①φ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") x 0.8 ①φ15.88 (5/8") x 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) When
wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- 11 -
Model FDTC140VNTVD
Indoor unit FDTC50VD (3 units) Outdoor unit FDC140VN
Item Panel TC-PSA-25W-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.64 4.52
Running current A 20.4 / 21.3 20.0 / 20.9
Power factor % 99 98
Inrush current A 5 < Max.running current 24 >
Cooling P-Hi : 47 Hi : 42 Me : 36 Lo : 30
Sound Pressure Level dB(A) 51
Heating P-Hi : 47 Hi : 42 Me : 36 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 86 < Direct line start >
Cooling P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 7
Air flow (Standard) CMM Cooling : 75, Heating : 73
Heating P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") x 0.8 ①φ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") x 0.8 ①φ15.88 (5/8") x 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- 12 -
Model FDTC140VSTVD
Indoor unit FDTC50VD (3 units) Outdoor unit FDC140VS
Item Panel TC-PSA-25W-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.64 4.52
Running current A 6.8 / 7.1 6.6 / 7.0
Power factor % 98 / 99 99 / 98
Inrush current A 5 < Max.running current 15 >
Cooling P-Hi : 47 Hi : 42 Me : 36 Lo : 30
Sound Pressure Level dB(A) 51
Heating P-Hi : 47 Hi : 42 Me : 36 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 86 < Direct line start >
Cooling P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 7
Air flow (Standard) CMM Cooling : 75, Heating : 73
Heating P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") x 0.8 ①φ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") x 0.8 ①φ15.88 (5/8") x 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- 13 -
Model FDTC200VSDVD
Indoor unit FDTC50VD (4 units) Outdoor unit FDC200VS
Item Panel TC-PSA-25W-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 20.0 [ 7.0 (Min.)~22.4 (Max.)] 22.4 [ 7.6 (Min.)~25.0 (Max.)]
Power consumption kW 7.33 6.98
Running current A 10.9 / 11.5 10.4 / 10.9
Power factor % 97 97
Inrush current A 5 < Max.running current 19 >
Cooling P-Hi : 47 Hi : 42 Me : 36 Lo : 30
Sound Pressure Level dB(A) 57
Heating P-Hi : 47 Hi : 42 Me : 36 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 1,300 × 970 × 370
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 122
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 86 x 2 < Direct line start >
Cooling P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 7
Air flow (Standard) CMM Cooling : 150, Heating : 145
Heating P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Oφ6.35 (1/4") ③②φ9.52 (3/8") x 0.8 ①φ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ③φ12.7 x 0.8 ②φ15.88 ①φ22.22 (7/8") x 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 5.4kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is four indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1, "DIS-WA1"×2 (option). Pipe ① : O/U~Branch, ② : Branch~Branch, ③ : Branch~I/U
(7) W hen wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- 14 -
Model FDTC250VSDVD
Indoor unit FDTC60VD (4 units) Outdoor unit FDC250VS
Item Panel TC-PSA-25W-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 25.0 [ 10.0 (Min.)~28.0 (Max.)] 28.0 [ 9.5 (Min.)~31.5 (Max.)]
Power consumption kW 11.28 10.19
Running current A 16.8 / 17.7 15.2 / 16.0
Power factor % 97 97
Inrush current A 5 < Max.running current 22 >
Cooling P-Hi : 47 Hi : 46 Me : 39 Lo : 30
Sound Pressure Level dB(A) Cooling : 57 Heating : 58
Heating P-Hi : 47 Hi : 46 Me : 39 Lo : 32
Exterior dimensions Unit 248 × 570 × 570
mm 1,505 × 970 × 370
Height x Width x Depth Panel 35 × 700 × 700
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 15 PANEL 3.5 140
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 33 < Direct line start > 86 x 2 < Direct line start >
Cooling P-Hi : 13.5 Hi : 13.5 Me : 10 Lo : 7
Air flow (Standard) CMM Cooling : 150, Heating : 145
Heating P-Hi : 13.5 Hi : 13.5 Me : 10 Lo : 8
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-TC-24W-ER (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Oφ6.35 (1/4") ③②φ9.52 (3/8") x 0.8 ①φ12.7 (1/2") x 0.8 O/Uφ12.7 (1/2")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ③φ12.7 x 0.8 ②φ15.88 ①φ22.22 (7/8") x 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 7.2kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is four indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1, "DIS-WA1"×2 (option). Pipe ① : O/U~Branch, ② : Branch~Branch, ③ : Branch~I/U
(7) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJA003Z375 A
- 15 -
Model FDT40ZIXVD
Indoor unit FDT40VD Outdoor unit SRC40ZIX-S
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 4.0 [ 1.8 (Min.)~4.7 (Max.)] 4.5 [ 2.0 (Min.)~5.4 (Max.)]
Power consumption kW 0.93 1.15
Running current A 4.1 / 4.3 5.2 / 5.4
Power factor % 98 97
Inrush current A 5 < Max.running current 12 >
Sound Pressure Level dB(A) P-Hi : 39 Hi : 33 Me : 31 Lo : 30 47
Exterior dimensions Unit 246 × 840 × 840
mm 640 × 800 × 290
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 22 PANEL 5.5 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 45 < Direct line start >
Air flow (Standard) CMM P-Hi : 20 Hi : 18 Me : 16 Lo : 14 40
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") Pipeφ6.35 (1/4") x 0.8 O/Uφ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7 (1/2") x 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 16 -
Model FDT50ZIXVD
Indoor unit FDT50VD Outdoor unit SRC50ZIX-S
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 5.0 [ 2.2 (Min.)~5.6 (Max.)] 5.4 [ 2.5 (Min.)~6.3 (Max.)]
Power consumption kW 1.29 1.29
Running current A 5.7 / 6.0 5.7 / 6.0
Power factor % 98 98
Inrush current A 5 < Max.running current 14 >
Sound Pressure Level dB(A) P-Hi : 39 Hi : 33 Me : 31 Lo : 30 47
Exterior dimensions Unit 246 × 840 × 840
mm 640 × 800 × 290
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 22 PANEL 5.5 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 45 < Direct line start >
Air flow (Standard) CMM P-Hi : 20 Hi : 18 Me : 16 Lo : 14 40
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") Pipeφ6.35 (1/4") x 0.8 O/Uφ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7 (1/2") x 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 17 -
Model FDT60ZIXVD
Indoor unit FDT60VD Outdoor unit SRC60ZIX-S
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 5.6 [ 2.8 (Min.)~6.3 (Max.)] 6.7 [ 3.1 (Min.)~7.1 (Max.)]
Power consumption kW 1.57 1.85
Running current A 7.0 / 7.2 8.2 / 8.7
Power factor % 98 / 99 98 / 97
Inrush current A 5 < Max.running current 14 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 33 Me : 31 Lo : 30 48
Exterior dimensions Unit 246 × 840 × 840
mm 640 × 800 × 290
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 24 PANEL 5.5 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 45 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 18 Me : 16 Lo : 14 40
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") Pipeφ6.35 (1/4") x 0.8 O/Uφ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7 (1/2") x 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 x 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 18 -
Model FDT71VNVD
Indoor unit FDT71VD Outdoor unit FDC71VN
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 7.1 [ 3.2 (Min.)~8.0 (Max.)] 8.0 [ 3.6 (Min.)~9.0 (Max.)]
Power consumption kW 1.90 2.07
Running current A 8.3 / 8.8 9.0 / 9.6
Power factor % 99 / 98 99 / 98
Inrush current A 5 < Max.running current 17 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 35 Me : 33 Lo : 31 48
Exterior dimensions Unit 246 × 840 × 840
mm 750 × 968 × 340
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 24 PANEL 5.5 60
Refrigerant equipment
— 2YC45DXD × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.65 FVC50K
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 21 Me : 19 Lo : 17 Cooling : 60 , Heating : 50
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") x 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 2.95kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose —
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 19 -
Model FDT100VNVD
Indoor unit FDT100VD Outdoor unit FDC100VN
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.76 2.74
Running current A 12.1 / 12.7 12.0 / 12.6
Power factor % 99 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 51 Hi : 40 Me : 37 Lo : 35 49
Exterior dimensions Unit 298 × 840 × 840
mm 845×970×370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 27 PANEL 5.5 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 140 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 37 Hi : 27 Me : 24 Lo : 20 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") x 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 20 -
Model FDT100VSVD
Indoor unit FDT100VD Outdoor unit FDC100VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.76 2.74
Running current A 4.2 / 4.4 4.2 / 4.4
Power factor % 95 / 91 94 / 95
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 51 Hi : 40 Me : 37 Lo : 35 49
Exterior dimensions Unit 298 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 27 PANEL 5.5 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 140 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 37 Hi : 27 Me : 24 Lo : 20 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") x 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 21 -
Model FDT125VNVD
Indoor unit FDT125VD Outdoor unit FDC125VN
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.05 3.77
Running current A 17.7 / 18.6 16.6 / 17.3
Power factor % 99 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 51 Hi : 42 Me : 40 Lo : 37 Cooling : 50 Heating : 51
Exterior dimensions Unit 298 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 27 PANEL 5.5 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 140 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 37 Hi : 30 Me : 27 Lo : 23 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") x 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 22 -
Model FDT125VSVD
Indoor unit FDT125VD Outdoor unit FDC125VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.05 3.77
Running current A 5.9 / 6.3 5.5 / 5.9
Power factor % 99 / 98 99 / 97
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 51 Hi : 42 Me : 40 Lo : 37 Cooling : 50 Heating : 51
Exterior dimensions Unit 298 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 27 PANEL 5.5 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 140 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 37 Hi : 30 Me : 27 Lo : 23 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") x 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 23 -
Model FDT140VNVD
Indoor unit FDT140VD Outdoor unit FDC140VN
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.98 4.57
Running current A 22.0 / 23.0 20.2 / 21.2
Power factor % 98 98
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 51 Hi : 43 Me : 41 Lo : 38 51
Exterior dimensions Unit 298 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 27 PANEL 5.5 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 140 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 37 Hi : 30 Me : 27 Lo : 23 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") x 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 24 -
Model FDT140VSVD
Indoor unit FDT140VD Outdoor unit FDC140VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.98 4.57
Running current A 7.4 / 7.8 6.7 / 7.4
Power factor % 97 98 / 94
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 51 Hi : 43 Me : 41 Lo : 38 51
Exterior dimensions Unit 298 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 27 PANEL 5.5 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 140 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 37 Hi : 30 Me : 27 Lo : 23 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") x 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 25 -
Model FDT71VNPVD
Indoor unit FDT40VD (2 units) Outdoor unit FDC71VN
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 7.1 [ 3.2 (Min.)~8.0 (Max.)] 8.0 [ 3.6 (Min.)~9.0 (Max.)]
Power consumption kW 1.85 1.99
Running current A 8.0 / 8.6 8.7 / 9.1
Power factor % 99 / 98 99
Inrush current A 5 < Max.running current 17 >
Sound Pressure Level dB(A) P-Hi : 39 Hi : 33 Me : 31 Lo : 30 48
Exterior dimensions Unit 246 × 840 × 840
mm 750 × 968 × 340
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 22 PANEL 5.5 60
Refrigerant equipment
— 2YC45DXD × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.65 FVC50K
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 20 Hi : 18 Me : 16 Lo : 14 Cooling : 60, Heating : 50
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") x 0.8 ①φ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") x 0.8 ①φ15.88 (5/8") x 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 2.95kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose —
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 26 -
Model FDT100VNPVD
Indoor unit FDT50VD (2 units) Outdoor unit FDC100VN
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.94 3.09
Running current A 12.9 / 13.7 13.6 / 14.2
Power factor % 99 / 98 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 39 Hi : 33 Me : 31 Lo : 30 49
Exterior dimensions Unit 246 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 22 PANEL 5.5 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 20 Hi : 18 Me : 16 Lo : 14 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1(Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") x 0.8 ①φ9.52 (3/8") x 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") x 0.8 ①φ15.88 (5/8") x 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 27 -
Model FDT100VSPVD
Indoor unit FDT50VD (2 units) Outdoor unit FDC100VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.94 3.09
Running current A 4.3 / 4.6 4.5 / 4.8
Power factor % 99 / 97 99 / 98
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 39 Hi : 33 Me : 31 Lo : 30 49
Exterior dimensions Unit 246 × 840 × 840
mm 845×970×370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 22 PANEL 5.5 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 20 Hi : 18 Me : 16 Lo : 14 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 28 -
Model FDT125VNPVD
Indoor unit FDT60VD (2 units) Outdoor unit FDC125VN
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 3.95 3.70
Running current A 17.7 / 18.5 16.6 / 17.3
Power factor % 97 97
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 33 Me : 31 Lo : 30 Cooling : 50 Heating : 51
Exterior dimensions Unit 246 × 840 × 840
mm 845×970×370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 24 PANEL 5.5 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 18 Me : 16 Lo : 14 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 29 -
Model FDT125VSPVD
Indoor unit FDT60VD (2 units) Outdoor unit FDC125VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 3.95 3.70
Running current A 5.9 / 6.2 5.5 / 5.8
Power factor % 97 97
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 33 Me : 31 Lo : 30 Cooling : 50 Heating : 51
Exterior dimensions Unit 246 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 24 PANEL 5.5 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 18 Me : 16 Lo : 14 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 30 -
Model FDT140VNPVD
Indoor unit FDT71VD (2 units) Outdoor unit FDC140VN
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.51 4.58
Running current A 19.8 / 20.7 20.1 / 21.0
Power factor % 99 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 35 Me : 33 Lo : 31 51
Exterior dimensions Unit 246 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 24 PANEL 5.5 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 21 Me : 19 Lo : 17 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 31 -
Model FDT140VSPVD
Indoor unit FDT71VD (2 units) Outdoor unit FDC140VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.51 4.58
Running current A 6.7 / 7.1 6.7 / 7.1
Power factor % 97 99 / 98
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 35 Me : 33 Lo : 31 51
Exterior dimensions Unit 246 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 24 PANEL 5.5 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 21 Me : 19 Lo : 17 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 32 -
Model FDT200VSPVD
Indoor unit FDT100VD (2 units) Outdoor unit FDC200VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 20.0 [ 7.0 (Min.)~22.4 (Max.)] 22.4 [ 7.6 (Min.)~25.0 (Max.)]
Power consumption kW 6.58 6.02
Running current A 9.9 / 10.6 9.1 / 9.8
Power factor % 96 / 94 95 / 93
Inrush current A 5 < Max.running current 19 >
Sound Pressure Level dB(A) P-Hi : 51 Hi : 40 Me : 37 Lo : 35 57
Exterior dimensions Unit 298 × 840 × 840
mm 1,300 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 27 PANEL 5.5 122
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 140 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 37 Hi : 27 Me : 24 Lo : 20 Cooling : 150, Heating : 145
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 5.4kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 33 -
Model FDT250VSPVD
Indoor unit FDT125VD (2 units) Outdoor unit FDC250VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 25.0 [ 10.0 (Min.)~28.0 (Max.)] 28.0 [ 9.5 (Min.)~31.5 (Max.)]
Power consumption kW 8.30 7.75
Running current A 12.4 / 13.0 11.8 / 12.3
Power factor % 97 95 / 96
Inrush current A 5 < Max.running current 22 >
Sound Pressure Level dB(A) P-Hi : 51 Hi : 42 Me : 40 Lo : 37 Cooling : 57 Heating : 58
Exterior dimensions Unit 298 × 840 × 840
mm 1,505 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 27 PANEL 5.5 140
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 140 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 37 Hi : 30 Me : 27 Lo : 23 Cooling : 150, Heating : 145
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ12.7 (1/2") × 0.8 O/Uφ12.7 (1/2")
mm
Refrigerant piping size Gas line : I/U φ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 7.2kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 34 -
Model FDT140VNTVD
Indoor unit FDT50VD (3 units) Outdoor unit FDC140VN
Item Panel T-PSA-3AW-E
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.65 4.63
Running current A 20.8 / 22.1 20.3 / 21.2
Power factor % 97 / 96 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 39 Hi : 33 Me : 31 Lo : 30 51
Exterior dimensions Unit 246 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 22 PANEL 5.5 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 20 Hi : 18 Me : 16 Lo : 14 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) When
wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 35 -
Model FDT140VSTVD
Indoor unit FDT50VD (3 units) Outdoor unit FDC140VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.65 4.63
Running current A 6.9 / 7.4 6.8 / 7.1
Power factor % 97 / 95 98 / 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 39 Hi : 33 Me : 31 Lo : 30 51
Exterior dimensions Unit 246 × 840 × 840
mm 845 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 22 PANEL 5.5 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 20 Hi : 18 Me : 16 Lo : 14 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 36 -
Model FDT200VSTVD
Indoor unit FDT71VD (3 units) Outdoor unit FDC200VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 20.0 [ 7.0 (Min.)~22.4 (Max.)] 22.4 [ 7.6 (Min.)~25.0 (Max.)]
Power consumption kW 6.49 6.12
Running current A 9.7 / 10.2 9.1 / 9.6
Power factor % 97 97
Inrush current A 5 < Max.running current 19 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 35 Me : 33 Lo : 31 57
Exterior dimensions Unit 246 × 840 × 840
mm 1,300 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 24 PANEL 5.5 122
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 21 Me : 19 Lo : 17 Cooling : 150, Heating : 145
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 5.4kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TB1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 37 -
Model FDT200VSDVD
Indoor unit FDT50VD (4 units) Outdoor unit FDC200VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 20.0 [ 7.0 (Min.)~22.4 (Max.)] 22.4 [ 7.6 (Min.)~25.0 (Max.)]
Power consumption kW 6.58 6.15
Running current A 9.8 / 10.3 9.2 / 9.6
Power factor % 97 97
Inrush current A 5 < Max.running current 19 >
Sound Pressure Level dB(A) P-Hi : 39 Hi : 33 Me : 31 Lo : 30 57
Exterior dimensions Unit 246 × 840 × 840
mm 1,300 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 22 PANEL 5.5 122
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 20 Hi : 18 Me : 16 Lo : 14 Cooling : 150, Heating : 145
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") ③②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ③φ12.7 × 0.8 ②φ15.88 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 5.4kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is four indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1, "DIS-WA1"×2(option). Pipe ① : O/U~Branch, ② : Branch~Branch, ③ : Branch~I/U
(7) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 38 -
Model FDT250VSDVD
Indoor unit FDT60VD (4 units) Outdoor unit FDC250VS
Item Panel T-PSA-3AW-E
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 25.0 [ 10.0 (Min.)~28.0 (Max.)] 28.0 [ 9.5 (Min.)~31.5 (Max.)]
Power consumption kW 8.28 7.70
Running current A 12.3 / 13.0 11.5 / 12.1
Power factor % 97 97
Inrush current A 5 < Max.running current 22 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 33 Me : 31 Lo : 30 Cooling : 57 Heating : 58
Exterior dimensions Unit 246 × 840 × 840
mm 1,505 × 970 × 370
Height x Width x Depth Panel 35 × 950 × 950
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg UNIT 24 PANEL 5.5 140
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Turbo fan × 1 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 50 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 18 Me : 16 Lo : 14 Cooling : 150, Heating : 145
Available static pressure Pa 0 —
Outdoor air intake Possible —
Air filter, Q'ty Pocket plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-T-36W-E (option)
Room temperature control Thermostat by electronics —
Overload protection for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/O φ6.35 (1/4") ③②φ9.52 (3/8") × 0.8 ①φ12.7 (1/2") × 0.8 O/Uφ12.7 (1/2")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ③φ12.7 × 0.8 ②φ15.88 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 7.2kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is four indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1,"DIS-WA1"×2(option). Pipe ① : O/U~Branch, ② : Branch~Branch, ③ : Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJF000Z188 A
- 39 -
Model FDEN40ZIXVD
Indoor unit FDEN40VD Outdoor unit SRC40ZIX-S
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 4.0 [ 1.8 (Min.)~4.7 (Max.)] 4.5 [ 2.0 (Min.)~5.4 (Max.)]
Power consumption kW 1.04 1.13
Running current A 4.7 / 4.8 5.1 / 5.3
Power factor % 97 / 98 97
Inrush current A 5 < Max.running current 12 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 39 Me : 38 Lo : 37 47
Exterior dimensions
mm 210 × 1,070 × 690 640 × 800 × 290
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 28 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 25 < Direct line start > 45 < Direct line start >
Air flow (Standard) CMM P-Hi : 13 Hi : 11 Me : 9 Lo : 7 40
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") Pipe φ6.35 (1/4") × 0.8 O/U φ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7 (1/2") × 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 40 -
Model FDEN50ZIXVD
Indoor unit FDEN50VD Outdoor unit SRC50ZIX-S
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 5.0 [ 2.2 (Min.)~5.6 (Max.)] 5.4 [ 2.5 (Min.)~6.3 (Max.)]
Power consumption kW 1.59 1.58
Running current A 7.1 / 7.5 7.0 / 7.3
Power factor % 97 98
Inrush current A 5 < Max.running current 14 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 39 Me : 38 Lo : 37 47
Exterior dimensions
mm 210 × 1,070 × 690 640 × 800 × 290
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 28 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 25 < Direct line start > 45 < Direct line start >
Air flow (Standard) CMM P-Hi : 13 Hi : 11 Me : 9 Lo : 7 40
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") Pipe φ6.35 (1/4") × 0.8 O/U φ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7 (1/2") × 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 41 -
Model FDEN60ZIXVD
Indoor unit FDEN60VD Outdoor unit SRC60ZIX-S
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 5.6 [ 2.8 (Min.)~6.3 (Max.)] 6.7 [ 3.1 (Min.)~7.1 (Max.)]
Power consumption kW 1.95 2.12
Running current A 8.7 / 9.2 9.4 / 9.8
Power factor % 97 / 96 98
Inrush current A 5 < Max.running current 14 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 41 Me : 39 Lo : 38 48
Exterior dimensions
mm 210 × 1,320 × 690 640 × 800 × 290
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 37 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 20 × 2 < Direct line start > 45 < Direct line start >
Air flow (Standard) CMM P-Hi : 22 Hi : 18 Me : 14 Lo : 12 40
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") Pipe φ6.35 (1/4") × 0.8 O/U φ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7 (1/2") × 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 42 -
Model FDEN71VNVD
Indoor unit FDEN71VD Outdoor unit FDC71VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 7.1 [ 3.2 (Min.)~8.0 (Max.)] 8.0 [ 3.6 (Min.)~9.0 (Max.)]
Power consumption kW 2.01 2.21
Running current A 8.9 / 9.2 9.8 / 10.2
Power factor % 98 / 99 98
Inrush current A 5 < Max.running current 17 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 41 Me : 39 Lo : 38 48
Exterior dimensions
mm 210 × 1,320 × 690 750 × 968 × 340
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 37 60
Refrigerant equipment
— 2YC45DXD × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.65 FVC50K
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 20 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 22 Hi : 18 Me : 14 Lo : 12 Cooling : 60, Heating : 50
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") Pipe φ9.52 (3/8") × 0.8 O/U φ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 2.95kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose —
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 43 -
Model FDEN100VNVD
Indoor unit FDEN100VD Outdoor unit FDC100VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.85 2.97
Running current A 12.5 / 13.1 13.0 / 13.6
Power factor % 99 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 44 Me : 41 Lo : 39 49
Exterior dimensions
mm 250 × 1,620 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 49 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 30 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 26 Me : 23 Lo : 21 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") Pipe φ9.52 (3/8") × 0.8 O/U φ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 44 -
Model FDEN100VSVD
Indoor unit FDEN100VD Outdoor unit FDC100VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.85 2.97
Running current A 4.2 / 4.4 4.3 / 4.6
Power factor % 98 99 / 98
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 44 Me : 41 Lo : 39 49
Exterior dimensions
mm 250 × 1,620 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 49 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 30 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 26 Me : 23 Lo : 21 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") Pipe φ9.52 (3/8") × 0.8 O/U φ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 45 -
Model FDEN125VNVD
Indoor unit FDEN125VD Outdoor unit FDC125VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.45 4.08
Running current A 19.5 / 20.4 17.9 / 18.7
Power factor % 99 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 46 Me : 44 Lo : 43 Cooling : 50 Heating : 51
Exterior dimensions
mm 250 × 1,620 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 49 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 40 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 32 Hi : 29 Me : 26 Lo : 23 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") Pipe φ9.52 (3/8") × 0.8 O/U φ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 46 -
Model FDEN125VSVD
Indoor unit FDEN125VD Outdoor unit FDC125VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.45 4.08
Running current A 6.6 / 6.8 6.0 / 6.3
Power factor % 97 / 99 98 / 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 46 Me : 44 Lo : 43 Cooling : 50 Heating : 51
Exterior dimensions
mm 250 × 1,620 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 49 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 40 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 32 Hi : 29 Me : 26 Lo : 23 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") Pipe φ9.52 (3/8") × 0.8 O/U φ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 47 -
Model FDEN140VNVD
Indoor unit FDEN140VD Outdoor unit FDC140VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 5.80 4.92
Running current A 25.2 / 26.0 21.6 / 22.6
Power factor % 99 99
Inrush current A 5 < Max.running current 26 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 46 Me : 44 Lo : 43 51
Exterior dimensions
mm 250 × 1,620 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 49 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 40 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 32 Hi : 29 Me : 26 Lo : 23 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") Pipe φ9.52 (3/8") × 0.8 O/U φ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 48 -
Model FDEN140VSVD
Indoor unit FDEN140VD Outdoor unit FDC140VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 5.80 4.92
Running current A 8.6 / 9.1 7.2 / 7.6
Power factor % 97 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 46 Me : 44 Lo : 43 51
Exterior dimensions
mm 250 × 1,620 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 49 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 40 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 32 Hi : 29 Me : 26 Lo : 23 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") Pipe φ9.52 (3/8") × 0.8 O/U φ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 49 -
PFA003Z900 A
- 50 -
Model FDEN100VNPVD
Indoor unit FDEN50VD (2 units) Outdoor unit FDC100VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 3.12 3.28
Running current A 13.7 / 14.3 14.4 / 15.1
Power factor % 99 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 39 Me : 38 Lo : 37 49
Exterior dimensions
mm 210 × 1,070 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 28 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 25 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 13 Hi : 11 Me : 9 Lo : 7 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 51 -
Model FDEN100VSPVD
Indoor unit FDEN50VD (2 units) Outdoor unit FDC100VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 3.12 3.28
Running current A 4.6 / 4.8 4.8 / 5.0
Power factor % 98 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 39 Me : 38 Lo : 37 49
Exterior dimensions
mm 210 × 1,070 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 28 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 25 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 13 Hi : 11 Me : 9 Lo : 7 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 52 -
Model FDEN125VNPVD
Indoor unit FDEN60VD (2 units) Outdoor unit FDC125VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.23 3.83
Running current A 18.5 / 19.4 16.8 / 17.6
Power factor % 99 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 41 Me : 39 Lo : 38 Cooling : 50 Heating : 51
Exterior dimensions
mm 210 × 1,320 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 37 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 20 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 22 Hi : 18 Me : 14 Lo : 12 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 53 -
Model FDEN125VSPVD
Indoor unit FDEN60VD (2 units) Outdoor unit FDC125VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.23 3.83
Running current A 6.2 / 6.5 5.6 / 5.9
Power factor % 98 / 99 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 41 Me : 39 Lo : 38 Cooling : 50 Heating : 51
Exterior dimensions
mm 210 × 1,320 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 37 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 20 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 22 Hi : 18 Me : 14 Lo : 12 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 54 -
Model FDEN140VNPVD
Indoor unit FDEN71VD (2 units) Outdoor unit FDC140VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.87 4.59
Running current A 21.6 / 22.6 20.1 / 21.0
Power factor % 98 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 41 Me : 39 Lo : 38 51
Exterior dimensions
mm 210 × 1,320 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 37 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 20 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 22 Hi : 18 Me : 14 Lo : 12 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 55 -
Model FDEN140VSPVD
Indoor unit FDEN71VD (2 units) Outdoor unit FDC140VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.87 4.59
Running current A 7.2 / 7.6 6.7 / 7.1
Power factor % 98 99 / 98
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 41 Me : 39 Lo : 38 51
Exterior dimensions
mm 210 × 1,320 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 37 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 20 × 2 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 22 Hi : 18 Me : 14 Lo : 12 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 φO/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ15.88 (5/8") × 1.0 φO/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 56 -
Model FDEN200VSPVD
Indoor unit FDEN100VD (2 units) Outdoor unit FDC200VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 20.0 [ 7.0 (Min.)~22.4 (Max.)] 22.4 [ 7.6 (Min.)~25.0 (Max.)]
Power consumption kW 6.47 5.97
Running current A 9.7 / 10.1 9.1 / 9.5
Power factor % 96 / 97 95
Inrush current A 5 < Max.running current 19 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 44 Me : 41 Lo : 39 57
Exterior dimensions
mm 250 × 1,620 × 690 1,300 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 49 122
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 30 × 2 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 26 Me : 23 Lo : 21 Cooling : 150, Heating : 145
Available static pressure Pa 0 —
Oudoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 5.4kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 57 -
Model FDEN250VSPVD
Indoor unit FDEN125VD (2 units) Outdoor unit FDC250VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 25.0 [ 10.0 (Min.)~28.0 (Max.)] 28.0 [ 9.5 (Min.)~31.5 (Max.)]
Power consumption kW 9.01 8.05
Running current A 13.5 / 14.1 12.2 / 12.8
Power factor % 96 / 97 95 / 96
Inrush current A 5 < Max.running current 22 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 46 Me : 44 Lo : 43 Cooling : 57 Heating : 58
Exterior dimensions
mm 250 × 1,620 × 690 1,505 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 49 140
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 40 × 2 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 32 Hi : 29 Me : 26 Lo : 23 Cooling : 150, Heating : 145
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ12.7 (1/2") × 0.8 O/Uφ12.7 (1/2")
mm
Refrigerant piping size Gas line : I/Uφ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 7.2kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 58 -
Model FDEN140VNTVD
Indoor unit FDEN50VD (3 units) Outdoor unit FDC140VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.88 4.58
Running current A 21.7 / 22.6 20.2 / 21.1
Power factor % 98 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 39 Me : 38 Lo : 37 51
Exterior dimensions
mm 210 × 1,070 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 28 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 25 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 13 Hi : 11 Me : 9 Lo : 7 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 59 -
Model FDEN140VSTVD
Indoor unit FDEN50VD (3 units) Outdoor unit FDC140VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.88 4.58
Running current A 7.2 / 7.6 6.7 / 7.0
Power factor % 98 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 39 Me : 38 Lo : 37 51
Exterior dimensions
mm 210 × 1,070 × 690 845 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 28 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 25 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 13 Hi : 11 Me : 9 Lo : 7 Cooling : 75, Heating : 73
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 60 -
Model FDEN200VSTVD
Indoor unit FDEN71VD (3 units) Outdoor unit FDC200VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 20.0 [ 7.0 (Min.)~22.4 (Max.)] 22.4 [ 7.6 (Min.)~25.0 (Max.)]
Power consumption kW 6.40 5.90
Running current A 9.6 / 10.0 9.0 / 9.4
Power factor % 96 / 97 95
Inrush current A 5 < Max.running current 19 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 41 Me : 39 Lo : 38 57
Exterior dimensions
mm 210 × 1,320 × 690 1,300 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 37 122
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 20 × 2 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 22 Hi : 18 Me : 14 Lo : 12 Cooling : 150, Heating : 145
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 5.4kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TB1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) W hen wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 61 -
Model FDEN200VSDVD
Indoor unit FDEN50VD (4 units) Outdoor unit FDC200VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 20.0 [ 7.0 (Min.)~22.4 (Max.)] 22.4 [ 7.6 (Min.)~25.0 (Max.)]
Power consumption kW 7.43 7.26
Running current A 11.1 / 11.6 10.8 / 11.4
Power factor % 97 97
Inrush current A 5 < Max.running current 19 >
Sound Pressure Level dB(A) P-Hi : 46 Hi : 39 Me : 38 Lo : 37 57
Exterior dimensions
mm 210 × 1,070 × 690 1,300 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 28 122
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 25 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 13 Hi : 11 Me : 9 Lo : 7 Cooling : 150, Heating : 145
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Oφ6.35 (1/4") ③②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ③φ12.7 × 0.8 ②φ15.88 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 5.4kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is four indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1,"DIS-WA1"×2 (option). Pipe ① : O/U~Branch, ② : Branch~Branch, ③ : Branch~I/U
(7) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 62 -
Model FDEN250VSDVD
Indoor unit FDEN60VD (4 units) Outdoor unit FDC250VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 25.0 [ 10.0 (Min.)~28.0 (Max.)] 28.0 [ 9.5 (Min.)~31.5 (Max.)]
Power consumption kW 9.50 8.69
Running current A 14.1 / 14.9 12.9 / 13.6
Power factor % 97 97
Inrush current A 5 < Max.running current 22 >
Sound Pressure Level dB(A) P-Hi : 50 Hi : 41 Me : 39 Lo : 38 Cooling : 57 Heating : 58
Exterior dimensions
mm 210 × 1,320 × 690 1,505 × 970 × 370
Height x Width x Depth
Exterior appearance Plaster White Stucco White
(Munsell color) (6.8Y8.9/0.2) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 37 140
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 20 × 2 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 22 Hi : 18 Me : 14 Lo : 12 Cooling : 150, Heating : 145
Available static pressure Pa 0 —
Outdoor air intake Not possible —
Air filter, Q'ty Pocket plastic net × 2 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Oφ6.35 (1/4") ③②φ9.52 (3/8") × 0.8 ①φ12.7 (1/2") × 0.8 O/Uφ12.7 (1/2")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ③φ12.7x0.8 ②φ15.88 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 7.2kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is four indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1,"DIS-WA1"×2 (option). Pipe ① : O/U~Branch, ② : Branch~Branch, ③ : Branch~I/U
(7) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 63 -
Model FDUM50ZIXVD
Indoor unit FDUM50VD Outdoor unit SRC50ZIX-S
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 5.0 [ 2.2 (Min.)~5.6 (Max.)] 5.4 [ 2.5 (Min.)~6.3 (Max.)]
Power consumption kW 1.52 1.41
Running current A 6.7 / 7.1 6.3 / 6.5
Power factor % 98 98
Inrush current A 5 < Max.running current 14 >
Sound Pressure Level dB(A) P-Hi : 35 Hi : 34 Me : 31 Lo : 28 47
Exterior dimensions
mm 299 × 750 × 635 640 × 800 × 290
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 34 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 60 < Direct line start > 45 < Direct line start >
Air flow (Standard) CMM P-Hi : 14 Hi : 13 Me : 12 Lo : 11 40
Available static pressure Pa 85 / 90 (at 14 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") Pipeφ6.35 (1/4") × 0.8 O/Uφ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7 (1/2") × 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(6) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 64 -
Model FDUM60ZIXVD
Indoor unit FDUM60VD Outdoor unit SRC60ZIX-S
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 5.6 [ 2.8 (Min.)~6.3 (Max.)] 6.7 [ 3.1 (Min.)~7.1 (Max.)]
Power consumption kW 1.86 1.96
Running current A 8.2 / 8.5 9.0 / 9.4
Power factor % 99 95
Inrush current A 5 < Max.running current 14 >
Sound Pressure Level dB(A) P-Hi : 38 Hi : 34 Me : 31 Lo : 28 48
Exterior dimensions
mm 299 × 950 × 635 640 × 800 × 290
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 40 43
Refrigerant equipment
— 5CS130XG04 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.48 RB68A
Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 100 < Direct line start > 45 < Direct line start >
Air flow (Standard) CMM P-Hi : 18 Hi : 16 Me : 15 Lo : 14 40
Available static pressure Pa 85 / 100 (at 18 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — —
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") Pipeφ6.35 (1/4") × 0.8 O/Uφ6.35 (1/4")
mm
Refrigerant piping size Gas line : φ12.7 (1/2") φ12.7 (1/2") × 0.8 φ12.7 (1/2")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.30m
Vertical height difference between Max.20m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.20m (Outdoor unit is lower)
Refrigerant Quantity R410A 1.4kg in outdoor unit (incl. the amount for the piping of : 15m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 5pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Drain elbow, Drain hole grommet
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(6) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 65 -
Model FDUM71VNVD
Indoor unit FDUM71VD Outdoor unit FDC71VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 7.1 [ 3.2 (Min.)~8.0 (Max.)] 8.0 [ 3.6 (Min.)~9.0 (Max.)]
Power consumption kW 2.08 2.21
Running current A 9.2 / 9.6 10.2 / 10.7
Power factor % 98 94
Inrush current A 5 < Max.running current 17 >
Sound Pressure Level dB(A) P-Hi : 38 Hi : 35 Me : 32 Lo : 29 48
Exterior dimensions
mm 299 × 950 × 635 750 × 968 × 340
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 40 60
Refrigerant equipment
— 2YC45DXD × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.65 FVC50K
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 23 Hi : 20 Me : 18 Lo : 15 Cooling : 60, Heating : 50
Available static pressure Pa 85 / 100 (at 20 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 2.95kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose —
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(6) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 66 -
Model FDUM100VNVD
Indoor unit FDUM100VD Outdoor unit FDC100VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.80 2.77 / 2.80
Running current A 12.5 / 13.1 12.4 / 13.0
Power factor % 97 97 / 98
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 41 Hi : 37 Me : 35 Lo : 32 49
Exterior dimensions
mm 350 × 1,370 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 59 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 3 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 + 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 34 Hi : 28 Me : 25 Lo : 22 Cooling : 75, Heating : 73
Available static pressure Pa 90 / 100 (at 28 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(6) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 67 -
Model FDUM100VSVD
Indoor unit FDUM100VD Outdoor unit FDC100VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.80 2.77 / 2.80
Running current A 4.2 / 4.4 4.1 / 4.3
Power factor % 96 / 97 98 / 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 41 Hi : 37 Me : 35 Lo : 32 49
Exterior dimensions
mm 350 × 1,370 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 59 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 3 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 + 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 34 Hi : 28 Me : 25 Lo : 22 Cooling : 75, Heating : 73
Available static pressure Pa 90 / 100 (at 28 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(6) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 68 -
Model FDUM125VNVD
Indoor unit FDUM125VD Outdoor unit FDC125VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.03 3.80 / 3.85
Running current A 18.3 / 19.1 17.0 / 18.1
Power factor % 96 97
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 41 Hi : 38 Me : 36 Lo : 33 Cooling : 50 Heating : 51
Exterior dimensions
mm 350 × 1,370 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 59 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 3 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 + 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 34 Hi : 28 Me : 25 Lo : 22 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 100 (at 34 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(6) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 69 -
Model FDUM125VSVD
Indoor unit FDUM125VD Outdoor unit FDC125VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.03 3.80 / 3.85
Running current A 6.1 / 6.4 5.7 / 6.0
Power factor % 95 / 96 96 / 97
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 41 Hi : 38 Me : 36 Lo : 33 Cooling : 50 Heating : 51
Exterior dimensions
mm 350 × 1,370 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 59 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 3 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 + 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 34 Hi : 28 Me : 25 Lo : 22 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 100 (at 34 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(6) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 70 -
Model FDUM140VNVD
Indoor unit FDUM140VD Outdoor unit FDC140VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.95 4.89 / 4.91
Running current A 22.3 / 23.3 22.3 / 22.5
Power factor % 97 95 / 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 41 Hi : 38 Me : 36 Lo : 33 51
Exterior dimensions
mm 350 × 1,370 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 59 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 3 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 + 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 34 Hi : 28 Me : 25 Lo : 22 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 100 (at 34 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(6) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 71 -
Model FDUM140VSVD
Indoor unit FDUM140VD Outdoor unit FDC140VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.95 4.89 / 4.91
Running current A 7.4 / 7.7 7.4 / 7.6
Power factor % 97 / 98 95 / 98
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 41 Hi : 38 Me : 36 Lo : 33 51
Exterior dimensions
mm 350 × 1,370 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 59 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 3 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 50 + 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 34 Hi : 28 Me : 25 Lo : 22 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 100 (at 34 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(6) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 72 -
Model FDUM100VNPVD
Indoor unit FDUM50VD (2 units) Outdoor unit FDC100VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 3.12 3.27
Running current A 13.6 / 14.3 14.3 / 15.0
Power factor % 99 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 35 Hi : 34 Me : 31 Lo : 28 49
Exterior dimensions
mm 299 × 750 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 34 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 60 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 14 Hi : 13 Me : 12 Lo : 11 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 90 (at 14 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52(3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7(1/2") × 0.8 ①φ15.88(5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 73 -
Model FDUM100VSPVD
Indoor unit FDUM50VD (2 units) Outdoor unit FDC100VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 3.12 3.27
Running current A 4.6 / 4.8 4.8 / 5.0
Power factor % 98 / 99 98 / 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 35 Hi : 34 Me : 31 Lo : 28 49
Exterior dimensions
mm 299 × 750 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 34 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 60 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 14 Hi : 13 Me : 12 Lo : 11 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 90 (at 14 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7(1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 74 -
Model FDUM125VNPVD
Indoor unit FDUM60VD (2 units) Outdoor unit FDC125VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.47 4.51
Running current A 19.7 / 20.6 19.8 / 20.7
Power factor % 99 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 38 Hi : 34 Me : 31 Lo : 28 Cooling : 50 Heating : 51
Exterior dimensions
mm 299 × 950 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 40 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 18 Hi : 16 Me : 15 Lo : 14 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 100 (at 18 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 75 -
Model FDUM125VSPVD
Indoor unit FDUM60VD (2 units) Outdoor unit FDC125VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.47 4.51
Running current A 6.6 / 6.9 6.6 / 6.9
Power factor % 98 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 38 Hi : 34 Me : 31 Lo : 28 Cooling : 50 Heating : 51
Exterior dimensions
mm 299 × 950 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 40 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 18 Hi : 16 Me : 15 Lo : 14 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 100 (at 18 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 76 -
Model FDUM140VNPVD
Indoor unit FDUM71VD (2 units) Outdoor unit FDC140VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 5.00 4.94 / 4.80
Running current A 22.0 / 23.0 22.4 / 22.1
Power factor % 99 96 / 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 38 Hi : 35 Me : 32 Lo : 29 51
Exterior dimensions
mm 299 × 950 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 40 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 23 Hi : 20 Me : 18 Lo : 15 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 100 (at 20 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/Uφ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 77 -
Model FDUM140VSPVD
Indoor unit FDUM71VD (2 units) Outdoor unit FDC140VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 5.00 4.94 / 4.80
Running current A 7.3 / 7.7 7.4
Power factor % 99 96 / 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 38 Hi : 35 Me : 32 Lo : 29 51
Exterior dimensions
mm 299 × 950 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 40 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 100 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 23 Hi : 20 Me : 18 Lo : 15 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 100 (at 20 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor)
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/U φ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ15.88 (5/8") × 1.0 O/U φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 78 -
Model FDUM200VSPVD
Indoor unit FDUM100VD (2 units) Outdoor unit FDC200VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 20.0 [ 7.0 (Min.)~22.4 (Max.)] 22.4 [ 7.6 (Min.)~25.0 (Max.)]
Power consumption kW 6.86 6.72
Running current A 9.9 / 10.5 9.8 / 10.3
Power factor % 99 99
Inrush current A 5 < Max.running current 19 >
Sound Pressure Level dB(A) P-Hi : 41 Hi : 37 Me : 35 Lo : 32 57
Exterior dimensions
mm 350 × 1,370 × 635 1,300 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 59 122
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 3 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 50 + 100 < Direct line start > 86 x 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 34 Hi : 28 Me : 25 Lo : 22 Cooling : 150, Heating : 145
Available static pressure Pa 90 / 100 (at 28 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/U φ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ22.22 (7/8") × 1.6 O/U φ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 5.4kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 79 -
Model FDUM250VSPVD
Indoor unit FDUM125VD (2 units) Outdoor unit FDC250VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 25.0 [ 10.0 (Min.)~28.0 (Max.)] 28.0 [ 9.5 (Min.)~31.5 (Max.)]
Power consumption kW 9.31 8.35
Running current A 13.6 / 14.3 12.3 / 12.9
Power factor % 99 98
Inrush current A 5 < Max.running current 22 >
Sound Pressure Level dB(A) P-Hi : 41 Hi : 38 Me : 36 Lo : 33 Cooling : 57 Heating : 58
Exterior dimensions
mm 350 × 1,370 × 635 1,505 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 59 140
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 3 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 50 + 100 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 34 Hi : 28 Me : 25 Lo : 22 Cooling : 150, Heating : 145
Available static pressure Pa 85 / 100 (at 34 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ12.7 (1/2") × 0.8 O/U φ12.7 (1/2")
mm
Refrigerant piping size Gas line : I/U φ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ22.22 (7/8") × 1.6 O/U φ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 7.2kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WB1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 80 -
Model FDUM140VNTVD
Indoor unit FDUM50VD (3 units) Outdoor unit FDC140VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 5.09 5.03 / 4.89
Running current A 22.4 / 23.4 22.8 / 22.5
Power factor % 99 96 / 99
Inrush current A 5 < Max.running current 24 >
Sound Pressure Level dB(A) P-Hi : 35 Hi : 34 Me : 31 Lo : 28 51
Exterior dimensions
mm 299 × 750 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 34 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 60 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 14 Hi : 13 Me : 12 Lo : 11 Cooling : 75 , Heating : 73
Available static pressure Pa 85 / 90 (at 14 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 81 -
Model FDUM140VSTVD
Indoor unit FDUM50VD (3 units) Outdoor unit FDC140VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 5.09 5.03 / 4.89
Running current A 7.4 / 7.8 7.6 / 7.5
Power factor % 99 96 / 99
Inrush current A 5 < Max.running current 15 >
Sound Pressure Level dB(A) P-Hi : 35 Hi : 34 Me : 31 Lo : 28 51
Exterior dimensions
mm 299 × 750 × 635 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 34 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 60 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM P-Hi : 14 Hi : 13 Me : 12 Lo : 11 Cooling : 75, Heating : 73
Available static pressure Pa 85 / 90 (at 14 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-TA1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 82 -
Model FDUM200VSTVD
Indoor unit FDUM71VD (3 units) Outdoor unit FDC200VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 20.0 [ 7.0 (Min.)~22.4 (Max.)] 22.4 [ 7.6 (Min.)~25.0 (Max.)]
Power consumption kW 6.88 6.74
Running current A 9.9 / 10.6 9.8 / 10.3
Power factor % 99 99
Inrush current A 5 < Max.running current 19 >
Sound Pressure Level dB(A) P-Hi : 38 Hi : 35 Me : 32 Lo : 29 57
Exterior dimensions
mm 299 × 950 × 635 1,300 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 40 122
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 100 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 23 Hi : 20 Me : 18 Lo : 15 Cooling : 150, Heating : 145
Available static pressure Pa 85 / 100 (at 20 CMM) —
Outdoor air intake Possible —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/U φ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : I/U φ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ22.22 (7/8") × 1.6 O/Uφ22.22 (7/8")
Connecting method Flare piping Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 5.4kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes sizeφ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.
(6) Branching pipe set "DIS-TB1"×1(option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) Initial static pressure values of optional air filter "UM-FL1E" are 5Pa.
(8) When wireless remote controlier is used, fan is 3 speed setting (Hi-Me-Lo) only.
PJR002Z389 a
- 83 -
Model FDU71VNVD
Indoor unit FDU71VD Outdoor unit FDC71VN
Item
Power source 220-240V~50Hz
Operation data Cooling Heating
Nominal capacity kW 7.1 [ 3.2 (Min.)~8.0 (Max.)] 8.0 [ 3.6 (Min.)~9.0 (Max.)]
Power consumption kW 2.08 2.21
Running current A 9.2 10.2
Power factor % 98 94
Inrush current A 5 < Max.running current 17 >
Sound Pressure Level dB(A) Hi : 41 Lo : 37 48
Exterior dimensions
mm 297 × 850 × 650 750 × 968 × 340
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 40 60
Refrigerant equipment
— 2YC45DXD × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.65 FVC50K
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 230 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM Hi : 20 Lo : 17 Cooling : 60, Heating : 50
Available static pressure Pa Standard : 60 Max : 130 —
Outdoor air intake Possible (on return duct) —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 2.95kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose —
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz
(5) Extemal static pressure is changeable to set by remote controller. Standard extemal static pressure is factory setting.
MAX extemal static pressure is "High static pressure" setting.
(6) Values of sound pressure level become 5dB(A) upper at extemal static pressure 130Pa.
PJD001Z301 a
- 84 -
Model FDU100VNVD
Indoor unit FDU100VD Outdoor unit FDC100VN
Item
Power source 220-240V~50Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.88 2.99
Running current A 12.7 13.1
Power factor % 99 99
Inrush current A 5 < Max.running current 25 >
Sound Pressure Level dB(A) Hi : 42 Lo : 37 49
Exterior dimensions
mm 350 × 1,370 × 650 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 63 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 280 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM Hi : 34 Lo : 27 Cooling : 75 , Heating : 73
Available static pressure Pa Standard : 60 Max : 130 —
Outdoor air intake Possible (on return duct) —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz
(5) Extemal static pressure is changeable to set by remote controller. Standard extemal static pressure is factory setting.
MAX extemal static pressure is "High static pressure" setting.
(6) Values of sound pressure level become 5dB(A) upper at extemal static pressure 130Pa.
PJD001Z301 a
- 85 -
Model FDU100VSVD
Indoor unit FDU100VD Outdoor unit FDC100VS
Item
Power source 380-415V 3N~50Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Power consumption kW 2.88 2.99
Running current A 4.3 4.4
Power factor % 97 99
Inrush current A 5 < Max.running current 16 >
Sound Pressure Level dB(A) Hi : 42 Lo : 37 49
Exterior dimensions
mm 350 × 1,370 × 650 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 63 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 280 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM Hi : 34 Lo : 27 Cooling : 75, Heating : 73
Available static pressure Pa Standard : 60 Max : 130 —
Outdoor air intake Possible (on return duct) —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz
(5) Extemal static pressure is changeable to set by remote controller. Standard extemal static pressure is factory setting.
MAX extemal static pressure is "High static pressure" setting.
(6) Values of sound pressure level become 5dB(A) upper at extemal static pressure 130Pa.
PJD001Z301 a
- 86 -
Model FDU125VNVD
Indoor unit FDU125VD Outdoor unit FDC125VN
Item
Power source 220-240V~50Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.04 3.79
Running current A 17.8 16.6
Power factor % 99 99
Inrush current A 5 < Max.running current 27 >
Sound Pressure Level dB(A) Hi : 43 Lo : 38 Cooling : 50 Heating : 51
Exterior dimensions
mm 350 × 1,370 × 650 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 63 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 370 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM Hi : 42 Lo : 33.5 Cooling : 75, Heating : 73
Available static pressure Pa Standard : 60 Max : 130 —
Outdoor air intake Possible (on return duct) —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz
(5) Extemal static pressure is changeable to set by remote controller. Standard extemal static pressure is factory setting.
MAX extemal static pressure is "High static pressure" setting.
(6) Values of sound pressure level become 5dB(A) upper at extemal static pressure 130Pa.
PJD001Z301 a
- 87 -
Model FDU125VSVD
Indoor unit FDU125VD Outdoor unit FDC125VS
Item
Power source 380-415V 3N~50Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Power consumption kW 4.04 3.79
Running current A 6.0 5.6
Power factor % 97 98
Inrush current A 5 < Max.running current 18 >
Sound Pressure Level dB(A) Hi : 43 Lo : 38 Cooling : 50 Heating : 51
Exterior dimensions
mm 350 × 1,370 × 650 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 63 83
Refrigerant equipment
— RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 370 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM Hi : 42 Lo : 33.5 Cooling : 75, Heating : 73
Available static pressure Pa Standard : 60 Max : 130 —
Outdoor air intake Possible (on return duct) —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz
(5) Extemal static pressure is changeable to set by remote controller. Standard extemal static pressure is factory setting.
MAX extemal static pressure is "High static pressure" setting.
(6) Values of sound pressure level become 5dB(A) upper at extemal static pressure 130Pa.
PJD001Z301 a
- 88 -
Model FDU140VNVD
Indoor unit FDU140VD Outdoor unit FDC140VN
Item
Power source 220-240V~50Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Power consumption kW 4.95 4.43
Running current A 21.7 19.5
Power factor % 99 99
Inrush current A 5 < Max.running current 28 >
Sound Pressure Level dB(A) Hi : 43 Lo : 38 51
Exterior dimensions
mm 350 × 1,370 × 650 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 63 81
Refrigerant equipment
— RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 0.9 M-MA68
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 2 Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 370 < Direct line start > 86 < Direct line start >
Air flow (Standard) CMM Hi : 42 Lo : 33.5 Cooling : 75, Heating : 73
Available static pressure Pa Standard : 60 Max : 130 —
Outdoor air intake Possible (on return duct) —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 20 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ9.52 (3/8") Pipeφ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
mm
Refrigerant piping size Gas line : φ15.88 (5/8") φ15.88 (5/8") × 1.0 φ15.88 (5/8")
Connecting method Flare piping Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump Built-in Drain pump —
Drain Hose Connectable with VP20 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Drain hose Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C
60
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz
(5) Extemal static pressure is changeable to set by remote controller. Standard extemal static pressure is factory setting.
MAX extemal static pressure is "High static pressure" setting.
(6) Values of sound pressure level become 5dB(A) upper at extemal static pressure 130Pa.
PJD001Z301 a
- 89 -
PJD001Z301 a
- 90 -
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Values of sound pressure level become 5dB(A) upper at extemal static pressure 200Pa (factory setting).
(6) Values of air flow are based at extemal static pressure 200Pa (factory setting).
PJD001Z301 a
- 91 -
Model FDU250VSVD
Indoor unit FDU250VD Outdoor unit FDC250VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 25.0 [ 10.0 (Min.)~28.0 (Max.)] 28.0 [ 9.5 (Min.)~31.5 (Max.)]
Power consumption kW 9.91 / 10.21 8.50 / 8.22
Running current A 15.7 / 17.0 14.4 / 14.7
Power factor % 91 85
Inrush current A 5 < Max.running current 27 >
Sound Pressure Level dB(A) 52 Cooling : 57 Heating : 58
Exterior dimensions
mm 360 × 1,570 × 830 1,505 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
—
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 92 140
Refrigerant equipment
— GTC5150ND70K × 1
Compressor type & Q'ty
Starting method — Direct line start
Refrigerant oil — 1.45 M-MA32R
Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control — Electronic expansion valve
Air handling equipment
Centrifugal fan × 4 Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 270 × 2 < Direct line start > 86 × 2 < Direct line start >
Air flow (Standard) CMM Hi : 68 / 80 Cooling : 150, Heating : 145
Available static pressure Pa 200 —
Outdoor air intake Possible (on return duct) —
Air filter, Q'ty Procure locally —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W — 33 (Crank case heater)
Remote controller wired : RC-E4 (option) wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Internal thermostat for fan motor Internal thermostat for fan motor
Safety equipment
Frost protection thermostat Abnormal discharge temperature protection.
Installation data Liquid line : I/Uφ12.7 (1/2") Pipeφ12.7 (1/2") × 0.8 O/Uφ12.7 (1/2")
mm
Refrigerant piping size Gas line : φ25.4 (1") φ22.22 (7/8") × 1.6 φ22.22 (7/8")
Connecting method Brazing Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 7.2kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain pump — —
Drain Hose Connectable with VP25 Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories — Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature Extemal static pressure of indoor unit
Operation DB WB DB WB Pa
Cooling 27˚C 19˚C 35˚C 24˚C 100
Heating 20˚C 7˚C 6˚C (With optional fan controller kit:U-FCRA)
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Values of sound pressure level become 5dB(A) upper at extemal static pressure 200Pa (factory setting).
(6) Values of air flow are based at extemal static pressure 200Pa (factory setting).
PJD001Z301 a
- 92 -
G G
326
350
1000 or more
35
Hole
140
100
( Max. Drain lift)
600 or less
248
210
192
□120
132
100 19
88
G
or more
35
45
'10 • PAC-DB-142
Notes(1)The model name label is attached on the control box lid.
(2)Prepare the connecting socket(VP20)on site.
(3)This unit is designed for 2x2 grid ceiling.
If it is installed on a ceiling other than 2x2 grid ceiling,
provide an inspection port on the control box side.
B
H H
Space for installation and service
418
420
or more
2500
648
1000
or more
Obstacle
140
260 Remote controller
60
Drain hose piece 345 303
88
(Option)
(Accessory)
(Installed on site)
140
100
□840
C
Hanger plate for
B A F Hole 100 6-φ4 □120 19
suspension bolt Holes for
H tapping screws 5-φ4
Holes for
tapping screws
Notes(1)The model name label is attached
246
173
150
123
40
(VP20) on site.
50 or more
35
PJF000Z045 c
112
137
76
'10 • PAC-DB-142
(Max. Drain lift)
700 or less
65 Hole
13 44
420
or more
2500
1000
648
or more
Obstacle
140
H Air return grille
60
Air supply
260
Drain hose piece 345 303 Remote controller
140
㧔Accessory㧕 㧔Option㧕
㧔Installed on site㧕
140
100
غ840
C B A F
Hanger plate for Hole 100 6-Ǿ4
suspension bolt Holes for
H tapping screws 5-Ǿ4 غ120 19
Holes for
tapping screws
298
173
150
123
40
35
112
137
76
Control box
Unit:mm
D
'10 • PAC-DB-142
50
65 Hole
13 44
53
10
40
215
210
31
173
108
53
27
27
15 60 7
109
40 990 40 690
1070 20 100
195
C1,C2
Air supply 235 Drain hose piece
(Accesory, 0.3m)
Receiving part
271 (Installed on site)
-
Symbol Content
Wireless remote controller Wired remote controller
96 -
F Unit:mm
or more
100 or more
G
'10 • PAC-DB-142
300
53
10
290(Suspension bolts pitch) D
135 410 145
40
215
210
31
173
108
53
27
27
15 60 7
109
40 1240 40 690
1320 20 100
195
C1, C2
Air supply 235 Drain hose piece
(Accesory, 0.3m)
271 (Installed on site)
Receiving part
-
Symbol Content
Model (Option) (Option)
FDEN60VA FDEN71VA
A Gas piping φ12.7(1/2")(Flare) φ15.88(5/8")(Flare)
308
150
C 1,2 Drain piping VP20
D Hole for suspension bolts (M10 or M8)
C2 75 E Back cutout PE cover
76 Air return grille
A C1 110 B F Top cutout Plate cover
135 G Hole for drain piping (for left back) (Knock out) 60 17 □120 19
Space for installation and service Position of top cutout and back cutout
Hole for Note(1)The model name label is attached on the
175 drain piping
0
12 19 (for left)
fan casing inside the air return grille.
20
PFA003Z817 A
F
or more
'10 • PAC-DB-142
300
10
53
135 410 145
40
255
250
31
173
108
53
27
27
60 7
109
40 1540 40 15
690
1620 20 100
195 C1,C2
Air supply 235 Drain hose piece
(Accesory, 0.3m)
Receiving part 271 (Installed on site)
-
Symbol Content
Wireless remote controller Wired remote controller
98 -
150
D Hole for suspension bolt (M10 or M8)
E Back cutout PE cover
F Top cutout Plate cover
75
C2 76 A C1 110 B G Hole for drain piping (for left back) (Knock out)
Air return grille 60 17 □120 19
135
Space for installation and service Position of top cutout and back cutout
Hole for Note(1)The model name label is attached on the
175 drain piping
0
12 19 (for left)
fan casing inside the air return grille.
20
PFA003Z818 A
F Unit:mm
or more
100 or more
G
'10 • PAC-DB-142
300
45 660(Duct dimension) 45
(Duct dimension)
Symbol Content
Model FDUM50VD
D Drain hose piece C1 Drain piping VP20 Note(2)
35
F
12-φ4 air intake
Holes for Return air duct G Ducting for air outlet (φ125)(Knock out)
tapping screw
Holes for
Control box φ149 tapping screws
Space for installation and service
F
(Suspension bolts
-
150
620
472
G 69
99 -
C1 Inspection
600
hole
pitch)
B φ170 φ170
1100
□90
100
Hole
A
59 F G
118
71 View M
Air supply duct
510
465
E
405 Notes(1)The model name label is attached
on the lid of the control box.
PJR002Z241 b
130
(VP20)on site.
'10 • PAC-DB-142
149
199
Unit:mm
35
274
299
M 0
φ20
C2 460
غ120 19
59
Holes for
Control box φ149 tapping screws
Space for installation and service
F
-
(Suspension bolts
150
620
472
100 -
G 69 C1 Inspection
600
hole
pitch)
B φ170 φ170
1300
غ90
A
100
Hole
59 F G
118
71 View M
Air supply duct
465
E
405
Notes(1)The model name label is attached
on the lid of the control box.
130
PJR002Z242
(VP20)on site.
149
'10 • PAC-DB-142
199
600
Unit:mm
35
274
299
M φ200
C2 460
B
Symbol Content
(Duct dimension)
(Gravity drainage)
(Accessory)
D Hole for wiring
(Installed on site)
E Suspension bolts (M10)
210
18-φ4
Holes for Return Air duct
tapping screws
1406 (Suspension bolts pitch)
18 1370 18
Hole Space for installation and service
284 205 213
4-φ4
80.5 φ149 Holes for
45
tapping screws
Control box 150 620
F
600
-
(Suspension bolts
Inspection
101 -
hole
472
69 C1
G φ170
pitch)
φ170
B
1720
F G □90
A Hole
58 View M
100
118
76
Hanger plate for
suspension bolt Air supply duct
1370 80 635
175 320 320 320 235 295 325 510
(Max. Drain lift)
Unit:mm
PJR002Z243 b
or less
200
250
'10 • PAC-DB-142
325
350
86
M
600
00
φ2
C2 460
50
32
φ15.88(5/8")(Flare)
600 850 100
Model FDU71VD
B Liquid piping φ9.52(3/8")(Flare)
C1 Drain piping VP20 Note(2)
Drain piping
C2
850
950
F Inspection hole (635X1200)
886
(Option)
28
35
71
284
50
32
58
Control box
C1
A B □120 19
-
Holes for
tapping screws 295 325 527 (Installed on site) Holes for
Hanger plate for tapping screws
E 482
Air supply suspension bolt
421 Return air duct
(Max. Drain lift)
43
43
19
19
or less
35
196
244
196
600
297
262
148
145
98
19
19
43
43
27
26
27
9 9 C2 240 80 D 9 9
43 200 190 190 200 43 477
43 200 190 190 200 43
16 848 (Duct dimension) 16
16 848 (Duct dimension) 16
PJD001Z214
Unit:mm
'10 • PAC-DB-142
Notes(1)The model name label is attached
on the lid of the control box.
(2)Prepare the connecting socket
(VP20)on site.
B
30 650 30
45 560 45
50
32
(Suspension bolts pitch)
Space for installation and service
1370
1470
E Suspension bolts (M10)
F Inspection hole (635X1200)
F 1720
Remote controller
(Option)
-
28
□120 19
284
50
32
53
58
77
103 -
C1 Control box
18-φ4 A B
(Duct dimension)
43
19
19
or less
85
297
249
249
350
600
265
173
151
101
19
19
43
43
26
27
27
9 9 C2 240 80 D
43 200 200 250 250 200 200 43 477 9 9
16 1368 (Duct dimension) 16 43 200 200 250 250 200 200 43
16 1368 (Duct dimension) 16
PJD001Z215
Unit:mm
'10 • PAC-DB-142
Notes(1)The model name label is attached
on the lid of the control box.
(2)Prepare the connecting socket
(VP20)on site.
B
60
Symbol Content
Model FDU200VD FDU250VD
A Gas piping Ǿ25.4㧔1"㧕㧔Brazing㧕
1570
ޓޓޓޓthe side plate of the control box. G Inspection hole 㧔900X1730㧕
1690
Remote controller
1640
㧔Option㧕
100
E
95
غ120 19
㧔Duct dimension㧕
㧔Duct dimension㧕
-
25
60
B A Control box
104 -
20-M5 Return air duct Hanger plate for 20-M5 Air supply
25 80 510 25
13
138
Holes for screws suspension bolt Holes for screws
138
Upper
13
250
250
360
310
44
30
13 200 13
138
65
13
138
106
Lower
13
163 1200 163 270 110 60 200
77
35 1500 㧔Duct dimension㧕 35 C 530 13 13
138 6x200=1200 138
Space for installation and service
or more
60 1450 60
900 or more 900 or more Front view
G 100 or more 㧔Duct dimension㧕
Plane view
300
35
F F
Slab
PJD001Z216
900
Ceiling
Unit:mm
'10 • PAC-DB-142
Service Service
35
space space
100 60
or more
400 or more
Piping space
200
Intake L3
L2 L4
( Service
space )
351.6
312.5
290
Intake
-
Outlet L1
105 -
83.5
327.3
14.8
Dimensions
L1 Open 280 280 180
Terminal block
L2 100 75 Open Open
L3 100 80 80 80
L4 250 Open 250 Open
148.4 33.5 C
640
40°
B
42.5
40°
'10 • PAC-DB-142
RCT000Z004
Unit:mm
12.4
A
93
Model FDC71VN
D Drain discharge hole φ20×3places to the dominant wind direction.
E Anchor bolt hole M10×4places (4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The model name label is attached on the lower right corner of the front panel.
223 310 60
E
15
2-R
7.5
47.5
L3
Intake
L2 L4
( )
340
380
418
Service
space
Intake
61
-
61 27
19
D Outlet
106 -
L1
150 580 150 32
880 88
Terminal block
C Examples of
installation
I I
I I
II
Dimensions
L1 Open Open 500
750
24
Unit:mm
'10 • PAC-DB-142
A
103.5
165.5 25
40
Terminal block 100
B
A
845
-
F F
F
107 -
279
242
110
110
195
195
150
70
10
50
50
50
55 52 40
C C C
50 15
27 50 15 50
E 970
Examples of
190 580 200 installation
Dimensions
I I
I I
II
Intake
L2 L3
15
Intake Unit:mm
55
103
410
370
L1
'10 • PAC-DB-142
Service Outlet
38
space
C
Minimum installation space
20
40
262 388 D
Model FDC200VS
E Anchor bolt hole M10×4places (4)Leave 1m or more space above the unit.
(5)A wall in front of the blower outlet must not exceed the units height.
※49
46
※46 φ30×2places(front)
(6)The model name label is attached on the lower right corner of the front panel.
F Cable draw-out hole φ45(side)
φ50(back) (7)Connect the Service valve with local pipe by using the pipe of the attachment.
(Gas side only)
113 G Connecting position of the local pipe.(gas side) φ22.22(7/8")
(Brazing)
(8)Mark ※ shows the connecting posotion of the local pipe.(Gas side only)
Terminal block
B
A
1300
G
-
F F C
108 -
624
538
35
※306
170
85
160
85
155
70
10
50
50
50
55 52 C 50 F
C
50 15 27 50 15 50 Examples of
installation
I I
I I
II
970 Dimensions
L1 Open Open 500
190 580 200 L3 L2 300 5 Open
Intake
60 60 60 15 L2
E L4
L3 150 300 150
L4 5 5 5
20
40
15
Intake
L1
PCA001Z536 a
103
space
'10 • PAC-DB-142
38
262 388
D
Notes
(1)It must not be surrounded by walls on the four sides.
B Symbol Content
(2)The unit must be fixed with anchor bolts. An anchor bolt must not
Service valve connection of the protrude more than 15mm.
A Ǿ19.05(3/4")
(Flare)
attached connecting pipe(gas side) (3)Where the unit is subject to strong winds, lay it in such
A,G B Service valve connection(liquid side) Ǿ12.7(1/2")
(Flare) a direction that the blower outlet faces perpendicularly
C Pipe/cable draw-out hole to the dominant wind direction.
D Drain discharge hole Ǿ20×3places (4)Leave 1m or more space above the unit.
(5)A wall in front of the blower outlet must not exceed the units height.
Model FDC250VS
43
Ǿ30×2places(front) (6)The model name label is attached on the lower right corner of the front panel.
F Cable draw-out hole Ǿ45(side) (7)Connect the Service valve with local pipe by using the pipe of the attachment.
Ǿ50(back) (Gas side only)
112 (8)Mark ※ shows the connecting posotion of the local pipe (Gas side only)
G Connecting position of the local pipe.(gas side) Ǿ22.22(7/8")
(Brazing)
B
A
1505
-
109 -
G
F F C
618
538
35
※306
170
160
85
85
155
70
10
50
50
50
55 52 C 50 F
C 50 15 Examples of
27 50 15 50 installation
I I
I I
II
970 Dimensions
L4 L4 5 5 5
103 15
PCA001Z537 a
Intake Unit:mm
55
L1
'10 • PAC-DB-142
410
370
Service Outlet
C
38
space
20
40
Lower case
LCD
Lower part
TEMP ON/OFF
Upper Sheath Upper Sheath
Board Board
X Y X Y
120
44
42
45
11.5 11
Wiring oulet
Electrical box 12×7 Slot hole
䋨Not included䋩 Installation hole
9.5×5 Slot hole 䋨4places䋩
Unit:mm
Wiring specifications
(1) If the prolongation is over 100m, change to the size below.
But, wiring in the remote controller case should be under 0.5mm2. Change the wire size outside of
the case according to wire connecting. Waterproof treatment is necessary at the wire connecting
section. Be careful about contact failure.
- 110 -
Unit: mm
150
60 17
- 111 -
Remote controller
TB2 Control PCB
WH FS
X X 1 CNB 1
WH 1 WH 1 RD
ThC t° BK WH CNI
Y Y 3
BL 2 WH 2 WH 2 RD
Y/GN
LED・2 LED・3 CNI2
WH
BL 3 BL 1 BK
Y/GN Y/GN CNH 1 t° ThI-A
BK 2 BL 4 BL 2 BK
Power PCB 1
RD
1 CNH2
Y/GN
RD WH
Connecting line between Y/GN 7 CNW2
2 2
CNW3
[ ]
indoor unit and outdoor unit F200(3.15A) 3
RD
3 SW2 1 RD 5 RD 1 BK
RD RD
-
RD 5 RD
1
Power circuit
4
RD
4
RD 6 RD 2 BK
t° ThI-R1
Power source line 1 2 2 WH 3 5 5 2
112 -
Signal line 3
3 BL 1 F201(3.15A) CNW1 BL
1 2
Earth BL 2 BL SW5 Y 7 Y 3 BK
1
CNW0 3 BL CNW4 CNN
3
Y/GN X4 3 t° ThI-R2
TB1 WH F203 F202 4 BL
4
BL
SW6 Y 4 Y 8 Y 4 BK
(0.16A) (1.0A) 5 BL
5
1 3 1 4 5 6 7 SW7 BK 9 BK 5 BK
5
CNR WH BR RD BL BR OR WH CNM t° ThI-R3
WH WH 1 BK 1 BK 6 BK 10 BK 6 BK
1
2 1 LM1 2 BK 2 BK CNC CNN2
CNR2 5 6 4 3 2
CNM3 3 BK 3 BK
2
WH BK
BL Y Y M 3
RD BL BR OR WH RD 4 BK 4 BK
4
5 BK 5 BK
5
M 5 6 4 3 2 1 BK 6 BK
DM 1∼ CNM4 LM2 2 BK 7 BK
6
RD BL BR OR WH WH
3 BK 8 BK
7
Option
M 8 +12 1
4 BK 9 BK
9 2 XR1 (Operation)
FMI M 5 BK 10 BK CNJ CNT 3 (Heating)
10 XR2
BK BK
LM3
1 11
11 WH BL 4 XR3 (Compressor ON)
2 BK 12 BK
12 5 XR4 (Inspection)
M 3 BK 13 BK
13 6
4 BK 14 BK
14 XR5(Remote operation input:volt-free contact)
5 BK 15 BK
15
1 BK 16 BK
16
LM4 2 BK 17 BK
PJA003Z340 A
17
M 3 BK 18 BK
18
Notes 1. indicates wiring on site. 4 BK 19 BK
19
BK BK
2. TB1 is the terminal block for heavy current(connecting line between
5 20
'10 • PAC-DB-142
20
CNJ2
indoor unit and outdoor unit), WH
and TB2 is the terminal block for weak current(remote controller).
3. See the wiring diagram of outside unit about the line between
inside unit and outside unit.
4. Use twin core cable(0.3mm 2 X2)at remote controller line. See spec
sheet of remote controller in case that the total length is more than 100m.
5. Do not put remote controller line alongside power source line.
Y㧛GN
TB2 BK
CNN 3
LED2 Indication lamp㧔Green-Normal operation㧕
Y
BK
t˚ ThI -R2
Y㧛GN
Power PCB 1
RD
1
4 LED3 Indication lamp㧔Red-Inspection㧕
Connecting line between Y㧛GN 7 CNW2 2 RD
2 CNW3 5
BK
indoor unit and outdoor unit F200㧔3.15A㧕 RD LM1ޓ4 Louver motor
RD 5
Power
RD 3
RD
3 RD
t˚ ThI -R3
1 4 4 BK
Panel switch
Power source line 1 2 WH 3 circuit 5
RD
5
6 PS
2
Signal line 3 BL 1 F201㧔3.15A㧕 CNW1 1 Remote controller communication
Earth 3 CNW0 BL
BL
2 SW2 SW2
2
3
BL
BL
1 CNW4 BK address
WH
3 CNH 1
4 BL BL t˚ Thl -A
X4 4 BK
SW5 Plural units Master㧛Slave setting
Y㧛GN
OR
RD
BR
BL
WH WH M 3 BK 3 BK BL
3
4 4 RD
BK BK
4 2 TB2 Terminal blockާSignal line㧕㧔غmark㧕
M
5 BK 5 BK
5 SW7
DM FMI M LM2
1 BK 6 BK Th 㧯 ThermistorާRemote controller㧕
-
6
1㨪 2 7
3
BK
8
BK
7 Option ThI -A ThermistorާReturn air㧕
113 -
BK BK
M 8 +12 1
4 BK 9 BK
9 2 XR1 㧔Operation㧕 ThI -R1,2,3 ThermistorާHeat exchanger㧕
5 BK 10 BK CNJ CNT 3
10 XR2 㧔Heating㧕
LM3
1 RD 11 BK
11
WH BL
4 XR3 㧔Compressor ON㧕 X4 Relay for DM
2 RD 12 BK
12 XR4
M 3 RD 13 BK
5 㧔Inspection㧕 عmark Closed-end connector
13 6
4 RD 14 BK
14
5 RD 15 BK XR5㧔Remote operation input:
15
1 RD 16 BK volt-free contact㧕
LM4 2 RD 17 BK
16
Color Marks
17
M 3 RD 18 BK
18 BK PS Mark Color Mark Color
4 RD 19 BK 1
19 CNV
5 20
CNJ2
RD BK
20 RD
2 BK Black RD Red
3
WH
4
BK BL Blue WH White
BR Brown Y Yellow
OR Orange Y㧛GN Yellow㧛Green
'10 • PAC-DB-142
ޓޓsheet of remote controller in case that the total length is more than 100m.
PJF000Z190
ޓޓ4. Do not put remote controller line alongside power source line.
BK
BK
BK
BK
BR
BR
BK
BK
BK
BK
BK
BK
C 19V 24V
Connecting line between TB1 1 2 3 4 5 CNW1 CNW2 1 2 3 4 5 6 1 2 Option
indoor unit and outdoor unit CNJ WH +12 1
Thl -A ThermistorާReturn air㧕
-
RD 5 WH BK CNN Y CNH
1 RD
F㧔3.15A㧕 WH 3
BK 2 XR1 㧔Operation㧕
ThermistorާHeat exchanger㧕
114 -
SW5
Power source line 1 2 2 X6 X2
X4 LED2 LED3 SW2 CNT 3 XR2 㧔Heating㧕 Thl -R1,2,3
WH BL 4
F㧔3.15A㧕 BL SW6
XR3 㧔Compressor ON㧕
Signal line 3 3
1
X1 X3 5 XR4 㧔Inspection㧕 Trl Transformer
CNW0
Earth Y㧛GN RD CNR CNI CNB WH SW7 6
X1 ޓ3,6 Relay for FM
1 3 5 7 9 WH 1 3 BL 1 3 Control PCB XR5㧔Remote operation input :
CNM3 volt-free contact㧕
C UH H M L
X4 Relay for DM
WH
WH
BK
WH
WH
Wireless specification
RD
BR
BK
BL
Wired specification
X Y TB2
CNB
AMP SW4 SW1
CNF1
WH 5 LED2 LED3 LED4 TB2 Remote
CNB2 controller
Y㧛GN
WH Receiver PCB X X
M Thc
FMI 1 1 Y Y t˚
CNFI 1
WH
OR
OR
'10 • PAC-DB-142
Notes 1. indicates wiring on site. P Pink
ޓޓ2. See the wiring diagram of outside unit about the line between SW4 Back-up switch㧔Operation㧛Stop㧕 ATTENTION
indoor unit and outdoor unit. ޓInsulate with tape the removed line.
Ԙ
ޓޓ3. Use twin core cable㧔0.3mm2 X2㧕at remote controller line. See spec ԙ The LED of that removed connector will
ޓޓsheet of remote controller in case that the total length is more than 100m. not be able to make any indication.
ޓޓ4. Do not put remote controller line alongside power source line.
Trl
t t t t SW7-1 Operation check, Drain motor test run
RD
RD
Thermistor㧔Remote controller㧕
BK
BK
BK
BK
BR
BR
BK
BK
BK
BK
BK
BK
C 19V 24V Thc
Connecting line between TB1 1 2 3 4 5 CNW1 CNW2 1 2 3 4 5 6 1 2 Option
indoor unit and outdoor unit RD 5
CNJ WH WH BK CNN Y CNH +12 1
Thl -A Thermistor㧔Return air㧕
1 RD
BK 2 XR1 㧔Operation㧕
Power source line 1 2
F㧔3.15A㧕 WH 3
X4 SW5
CNT 3 XR2 㧔Heating㧕 Thl -R1,2,3 Thermistor㧔Heat exchanger㧕
2 WH X6 X2
LED2 LED3 SW2
㧔Compressor ON㧕
-
F㧔3.15A㧕 BL 1 BL 4 XR3
SW6
Signal line 3 3 X1 X3 5 XR4 㧔Inspection㧕 Trl Transformer
115 -
CNW0
Earth Y㧛GN
RD CNR CNI CNB WH SW7 6
X1 ޓ3,6 Relay for FM
1 3 5 7 9 WH 1 3 BL 1 3 Control PCB XR5㧔Remote operation input :
CNM3 volt-free contact㧕
X4 Relay for DM
WH
C UH H M L
WH
BK
WH
WH
RD
BR
BK
BL
OR
OR
OR
'10 • PAC-DB-142
indoor unit and outdoor unit. ԙ The LED of that removed connector will
ޓޓ3. Use twin core cable㧔0.3mm2 X2㧕at remote controller line. See spec not be able to make any indication.
ޓޓsheet of remote controller in case that the total length is more than 100m.
ޓޓ4. Do not put remote controller line alongside power source line.
GR
RD
RD
BK
BK
BK
BK
BK
BK
BK
BK
BR
BR
SW2
2 XR1 (Operation)
F(3.15A) WH 3 SW5 SW7-1 Operation check, Drain motor test run
2
WH
Power source line 1 2 CNT 3 XR2 (Heating)
CNW0 SW6 BL
F(3.15A) 1
X6 X2 X4 LED・3 4 XR3 (Compressor ON) TB1 Terminal block(Power source)(□mark)
3
BL
Signal line 3 RD
SW7 5 XR4 (Inspection)
Earth Y/GN X1 X3 6 TB2 Terminal block(Signal line)(□mark)
-
1 3 5 7 9 WH 1 3 BL 1 3
C UH H M L
Thl -A Thermistor(Return air)
CNM3
WH
WH
BK
BR
RD
RD
WH
Thl -R1,2,3 Thermistor(Heat exchanger)
WH
RD
BR
BK
BL
F(0.16A) X Y TB2
Trl Transformer
WH
CNR2
BL X Y X1~3,6 Relay for FM
CNF3
Y
WH
Y
5
Remote X4 Relay for DM
M
Y/GN
FS controller
t° Thc
FMI1 1~
DM M
1~
CFI1
PJR002Z244
'10 • PAC-DB-142
3. Use twin core cable(0.3mm 2 X2)at remote controller line. See spec
sheet of remote controller in case that the total length is more than 100m.
4. Do not put remote controller line alongside power source line.
B
Color Marks
Mark Color
CFI 1,2 Capacitor for FMI
BK Black
GR
19V 24V
RD
RD
BK
BK
BK
BK
BK
BK
BK
BK
BR
BR
Control PCB 1 2 3 4 5 6 1 2
CNW1 CNW2 Plural units Master㧛Slave setting
CNN CNH WH BK SW5
Connecting line between TB1 Y BK Option
RD 5
+12 1 SW6 Model capacity setting
indoor unit and outdoor unit 1 LED2
RD
2 XR1 㧔Operation㧕
F㧔3.15A㧕 WH 3 SW5 SW2 SW7-1 Operation check, Drain motor test run
2
WH
Power source line 1 2 CNT 3 XR2 㧔Heating㧕
CNW0
F㧔3.15A㧕 BL 1
X6 X2 X4 SW6
LED3
BL 4
XR3 㧔Compressor ON㧕 TB1 Terminal block㧔Power source㧕㧔غmark㧕
3
RD
Signal line 3
SW7 5 XR4 㧔Inspection㧕
Earth Y㧛GN X1 X3 6 TB2 Terminal block㧔Signal line㧕㧔غmark㧕
XR5㧔Remote operation : Thc Thermistor㧔Remote controller㧕
-
CNB WH
1 3 5 7 9
CNR 1 3 CNI BL 1 3
volt-free contact㧕
WH
Thl -A Thermistor㧔Return air㧕
117 -
CNM3 C UH H M L
WH
WH
BR
RD
RD
BK
WH
Thl -R1,2,3 Thermistor㧔Heat exchanger㧕
WH
RD
BR
BK
BL
F㧔0.16A㧕 X Y TB2
Trl Transformer
WH
5
5
CNR2
BL X Y X1ޓ3,6 Relay for FM
CNF3 CNF4
Y
Y
WH WH
5 5
Remote X4 Relay for DM
Y㧛GN Y㧛GN
FS controller
M M
t° Thc عmark Closed-end connector
FM I 1 1
FMI 2 1
DM M
1㨪
CF I 1 CFI 2
ޓޓ2. See the wiring diagram of outside unit about the line between
inside unit and outside unit.
'10 • PAC-DB-142
ޓޓ3. Use twin core cable㧔0.3mm2 X2㧕at remote controller line. See spec
ޓޓsheet of remote controller in case that the total length is more than 100m.
ޓޓ4. Do not put remote controller line alongside power source line.
B
Model FDU71VD
Mark Color Mark Color CF I Capacitor for FMI
BK Black P Pink CNB Z Connector
BL Blue RD Red
DM Drain motor
BR Brown WH White
GR Gray Y Yellow F Fuse
OR Orange Y㧛GN Yellow㧛Green FMI Fan motor㧔with thermostat㧕
FS Float switch
Thl -R1 Thl -R2 Thl -R3 Thl -A
LED2 Indication lamp㧔Green-Normal operation㧕
FS Trl t t t t
LED3 Indication lamp㧔Red-Inspection㧕
220㨺240V SW2 Remote controller communication address
SW6 Model capacity setting
19V 24V
GR
GR
RD
RD
RD
RD
BK
BK
BR
BR
BK
BK
BK
BK
BK
BK
F㧔3.15A㧕
RD
LED2 +12 1 TB2 Terminal block㧔Signal line㧕㧔غmark㧕
-
XR1
Power source line 1 2 2 WH WH 3
SW2 SW6
2 㧔Operation㧕
Thc Thermistor㧔Remote controller㧕
118 -
F㧔3.15A㧕
1
CNW0 X6 X2 X4 CNT 3 XR2 㧔Heating㧕
Signal line 3 3 BL RD
LED3 SW7 BL 4 XR3 㧔Compressor ON㧕 Thl -A Thermistor㧔Return air㧕
Earth Y㧛GN X1 X3 5 XR4 㧔Inspection㧕
Thermistor㧔Heat exchanger㧕
6
Thl -R1,2,3
CNM3
1 3 5 7 9
CNR CNB XR5㧔Remote operation input: Trl Transformer
WH
WH WH volt-free contact㧕
C UH H M L 1 3 1 3 X1ޓ3,6 Relay for FM
WH
BK
WH
WH
X4 Relay for DM
RD
BK
BR
BR
BL
X Y TB2
F㧔0.16A㧕 عmark Closed-end connector
BL
WH
CNR2
BL
X Y
Remote
Y
Controller
Y㧛GN M M t Thc
1 1 DM
FMI
OR
Y
CFIޓ
'10 • PAC-DB-142
Notes 1. indicates wiring on site.
PJD001Z304
ޓޓ2. See the wiring diagram of outside unit about the line between
inside unit and outside unit.
ޓޓ3. Use twin core cable㧔0.3mm2 X2㧕at remote controller line. See spec
ޓޓsheet of remote controller in case that the total length is more than 100m.
ޓޓ4. Do not put remote controller line alongside power source line.
GR
RD
RD
RD
RD
BK
BR
BR
BK
BK
BK
BK
BK
BK
SW7-1
Control PCB CNI CNW1 CNW2 1 2 3 4 5 6 1 2
Connecting line between TB1 BL WH BK CNN CNH TB1 Terminal block㧔Power source㧕㧔غmark㧕
5 Y BK
Option
indoor unit and outdoor unit 1 RD
F㧔3.15A㧕
RD
LED2 +12 1 TB2 Terminal block㧔Signal line㧕㧔غmark㧕
XR1
Power source line 1 2 2 WH WH 3
SW2
2 㧔Operation㧕
Thc Thermistor㧔Remote controller㧕
-
SW6
F㧔3.15A㧕
1
CNW0 X6 X2 X4 CNT 3 XR2 㧔Heating㧕
Signal line 3 3 BL RD
119 -
RD
F㧔5A㧕 F㧔5A㧕
C UH H M L 1 3 1 3 X1ޓ3,6 Relay for FM
WH
BK
WH
WH
X4 Relay for DM
RD
BK
BR
BR
BL
WH
RD
X Y TB2
F㧔0.16A㧕 عmark Closed-end connector
P
BL
WH
WH
WH
C UH M L Remote
Y
Controller
WH
RD
BK
BL
M t° Thc
1 DM
Y㧛GN M
1
FMI
OR
Y
CFI
PJD001Z217
'10 • PAC-DB-142
ޓޓ2. See the wiring diagram of outside unit about the line between
inside unit and outside unit.
ޓޓ3. Use twin core cable㧔0.3mm2 X2㧕at remote controller line. See spec
ޓޓsheet of remote controller in case that the total length is more than 100m.
ޓޓ4. Do not put remote controller line alongside power source line.
B
6.'..
GR
RD
RD
BK
BK
BK
BK
BK
BK
BK
BK
BR
BR
19V 24V Indication lamp㧔Green-Normal operation㧕
LED2
1 2 3 4 5 6 1 2 CNW1 CNW2
Connecting line between TB1 CNN
Y
CNH WH BK LED3 Indication lamp㧔Red-Inspection㧕
F㧔3.15A㧕 RD BK Option
1
5
indoor unit and outdoor unit RD +12 1
SW2 Remote controller communication address
F㧔3.15A㧕 WH 3 LED2 2 XR1 㧔Operation㧕
Power source line 1 2 2 WH WH
CNW0 X6 X2
SW6
CNT 3 XR2 㧔Heating㧕 SW6 Model capacity setting
SW7 BL 4 XR3 㧔Compressor ON㧕
Signal line 3 3 BL 1 RD
5 XR4 㧔Inspection㧕 SW7-1 Operation check, Drain motor test run
WH
RD
X1 X3 LED3 SW2
Earth Y㧛GN 6
XR5㧔Remote operation input: TB1 Terminal block㧔Power source㧕㧔غmark㧕
volt-free contact㧕 Terminal block㧔Signal line㧕㧔غmark㧕
F F TB2
㧔6.3A㧕 㧔6.3A㧕 CNM3 1 CNI CNB
Control PCB 3 5 7 9 BL WH Thermistor㧔Remote controller㧕
2 1
WH Thc
C UH H M L 1 3
-
RD
RD
RD
RD
BR
BK
BL
120 -
X Y Trl Transformer
52FL 52FH 52FL 52FH
WH
RD
RD
BR
BK
FS
RD
BK
Thc
BK
RD
عmark
BK
CNF5 Option
WH
WH
WH
Electromagnetic contactor for FMI
RD
52FL,FH
BK
CNF2 CNF5
WH WH
WH
WH
CNF3
WH
WH
PJD001Z218
'10 • PAC-DB-142
inside unit and outside unit.
ޓޓ3. Use twin core cable㧔0.3mm 2 X2㧕at remote controller line. See spec
ޓޓsheet of remote controller in case that the total length is more than 100m.
ޓޓ4. Do not put remote controller line alongside power source line.
B
'..
L Reactor
T2
T1 FUSE
TRANSISTOR
㧔BK㧕 RIN F8 F2 TH2 Outdoor air temp.sensor
L RO P U 㧔RD㧕
250V 20A 㧔BK㧕 R U
250V 10A
㧔WH㧕 S IN 250V 20A ACTIVE 250V 20A TH3 Discharge pipe temp.sensor
N +
F10
+
+
NU V 㧔WH㧕 M
FILTER V
㧔WH㧕 SO 㧔WH㧕 S NV 3㨪 20S Solenoid valve for 4 way valve
㧔BR㧕 UNIT W 㧔BK㧕
㧔Y㧛G㧕 NW W CM
R OUT S-1 㧔WH㧕 S-2
㧔Y㧛G㧕 G1
TERMINAL 㧔BK㧕
BLOCK CNMAIN CNSUB
CN20S Mark Color
T2 㧔RD㧕
F3 250V 1A
BK Black
1
BR Brown
250V 2A
TO INDOOR UNIT 2
F1
-
M
N OR Orange
POWER WIRES 1 2 㧔RD㧕 C-2 CNFAN
3
121 -
N
SWITCHING POWER FMo
SIGNAL WIRE 3 CIRCUIT
RD Red
㧔Y㧛G㧕 WH White
CNTH CNEEV
Y Yellow
Y㧛G Yellow㧛Green
20S
tࠑ tࠑ tࠑ M
EEV 5 or 6 wires
TH1 TH2 TH3
Model MAX running current Power cable size Power cable length indoor-outdoor Earth wire size
㧔A㧕 㧔mm2 㧕 㧔m㧕 wire size x number 㧔mm㧕
40 12 21
The specifications shown in the above table are for units without heaters. For units with heaters, refer
RWC000Z214 A
'10 • PAC-DB-142
The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation
in effect in each country.
Model FDC71VN
3
Y/GN
CM Compressor motor
F Fuse
5 or 6 wires 5 or 6 wires
Y/GN T2 T1 F6(5A) T8 T9 SM2 SM1 FMO1 FM01 Fan motor
T4
RD IPM Intelligent power module
WH
T5
CNO2
NOISE FILTER
PWB3
T10
M M M
T6 (WH) T13 T11 L Reactor
LED1 Indication lamp(GREEN)
Y/GN
Indication lamp(RED)
WH
WH
WH
OR
OR
OR
RD
RD
RD
BR
BR
BR
LED2
BL
BL
BL
Y
Y
WH
GR
RD
BR
3 1 1 3 6 5 4 3 2 1 6 5 4 3 2 1 7 6 5 4 1 LPT
T21 T22 CNO1 CNW CNW2 CNEEV2 CNEEV1 CNFAN1
(WH)
BK
(WH) (OR) (RD) (WH) (WH) SM1 Expansion valve for cooling
CNG2 CNG1
INVERTER (BK) (BK)
Expansion valve for heating
T24 BL SM2
PWB2 CNI2 CNI1 CONTROL CNO1
BK
ON ON
L
IPM (WH)
BL
(WH) PWB1 (WH) 1 2 3 4
CNO1 SW5
1 2 3
SW8 SW9
SV1 Solenoid valve
T25 CNI4 CNI3 (WH) Mark Color
(WH) (WH) 52X1 52X3 SW9 Pump down switch
U V W T26 T27
52X4
BK Black SW3,5,7,8 Local setting switch
LED1 LED2 ON ON
RD
BK
WH
BL
RD
BL Blue
BL
RD CNO2
V W
(BK) 1 2 3 4 1 2 3 TB Terminal block
+ BL CNA1 CNO2 SW3 SW7
U
MS C1
RD
(WH) (BK) BR Brown THo-A Thermistor(Outdoor air temp.)
3∼ BL CNA2 CNR CNS CNN CNH CNTH CNIP CNPS CNB GR Gray Thermistor(Discharge pipe temp.)
(WH) (WH) (RD) (Y) (P) (WH) (Y) (WH) (RD) THo-D
P Pink THo-IPM Thermistor(IPM)
CM
WH
-
RD
BR
BR
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BL
BL
BL
BL
t° t° t° t° t° t°
CH 20S SV1 LPT RD Red THo-S Thermistor(Suction pipe temp.)
WH White 20S Solenoid valve for 4 way valve
63H1 THo-R1 THo-D THo-S THo-A THo-IPM THo-R2
Y Yellow 52X1 Auxilliary relay(for CH)
Y/GN Yellow/Green 52X3 Auxilliary relay(for 20S)
52X4 Auxilliary relay(for SV1)
63H1 High pressure switch
Local setting switch SW3(Set up at shipment OFF)
The defrosting operation interval becomes shorter
Defrost control change by turning ON this switch. This switch should be
Power cable, indoor-outdoor connecting wires SW3-1
turned ON in the area where outside temperature
becomes below the freezing point.
Model MAX over current Power cable size Power cable length indoor-outdoor Earth wire size When this switch is turned ON, the outdoor unit
(A) (mm 2 ) (m) wire size x number (mm) fan will run for 30 seconds in every 10 minutes,
SW3-2 Snow guard fan control when outdoor temperature falls to 3 or lower and
the compressor is not runnning when the unit is used
71 17 3.5 21 φ1.6mm x 3 φ1.6 in a very snowy country, set this switch to ON.
Method of trial operation
The specifications shown in the above table are for units without heaters. For units with heaters, refer 1 Trial operation can be performed by using SW3-3,4.
to the installation instructions or the construction instructions of the indoor unit. 2 Compressor will be in the operation when
Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen SW3-3 is ON.
PCA001Z538 a
'10 • PAC-DB-142
outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation is finished.
in effect in each country.
TB Item Description
TB F(30A) F(8A)
RD L1i RD
L1 1
WH
1 CnA∼Z Connector
N
WH
Ni NOISE FILTER 2 2 TO INDOOR UNIT
PWB3 E GN
3 CH Crankcase heater
L1o No
E1 GN POWER WIRES 1 2
GN
SIGNAL WIRE 3 CM Compressor motor
5 or 6 wires 5 or 6 wires
CT Current sensor
WH
WH
WH
OR
OR
OR
RD
RD
RD
L Reactor
BR
BR
BR
BL
BL
BL
Y
Y
RD
BL
WH
WH
BL
RD
BK
WH
BL
BL
RD
BL Blue
BL
RD
V
SW3,5 Local setting switch
W BL CNA2
U + -
(WH) BR Brown
MS P
RD TB Terminal block
3∼ A/F MODULE +
CNA1
N2
BL
(WH)
CNR
(WH)
CNS
(RD)
CNH
(BR)
CNTH
(WH)
CNIP
(Y)
CNPS
(WH)
CNB
(RD)
GN Green THo-A Thermistor(Outdoor air temp.)
L1 L2
RD
BR
BR
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BL
BL
Y
Y
Model MAX over current Power cable size Power cable length indoor-outdoor Earth wire size 63H1 High pressure switch
(A) (mm 2) (m) wire size x number (mm) Local setting switch SW3(Set up at shipment OFF)
The defrosting operation interval becomes shorter
100 by turning ON this switch. This switch should be
SW3-1 Defrost control change
turned ON in the area where outside temperature
125 24 5.5 25 φ1.6mm x 3 φ1.6 becomes below the freezing point.
140 When this switch is turned ON, the outdoor unit
fan will run for 30 seconds in every 10 minutes,
※At the connection with the duct type indoor unit. SW3-2 Snow guard fan control when outdoor temperature falls to 3 C or lower and
the compressor is not runnning when the unit is used
MAX over current Power cable size Power cable length indoor-outdoor Earth wire size in a very snowy country, set this switch to ON.
Model
(A) (mm 2) (m) wire size x number (mm) Method of trial operation
1 Trial operation can be performed by using SW3-3,4.
100 25 24 2 Compressor will be in the operation when
5.5 SW3-3 is ON.
125 27 22 φ1.6mm x 3 φ1.6 SW3-3,4 Trial operation 3 Cooling trial operation will be performed when
SW3-4 is OFF, and heating trial operation when
PCA001Z539 a
'10 • PAC-DB-142
The specifications shown in the above table are for units without heaters. For units with heaters, refer
to the installation instructions or the construction instructions of the indoor unit.
Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen
along the regulations in each country.
The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation
in effect in each country.
CN2-1 2 4
CM Compressor motor
BL
T12 GN
AC1 AC2 AC3
G
GN CT Current sensor
RD CNR
R5 DM BK (WH)
K DM Diode module
Va5
+4 -6 RD U
R1
U F Fuse
IPM WH V MS
U L
3∼
RD
RD RD RD
V FM01 Fan motor
RD
TB5
BL
W
+ P
R2
R3 C1 W IPM Intelligent power module
CM
WH L Reactor
+
R4 C2
LED1 Indication lamp(GREEN)
THo-IPM THo-R2 THo-A THo-S THo-D THo-R1 BL BL
TB6
N LED2 Indication lamp(RED)
t° t° t° t° t° t° 52C LPT RD
CNW2 LPT Low pressure sensor
BL (WH)
WH
RD
WH
RD
RD
BK
BK
BK
BK
BK
BK
BK
BK
BK
Y
Y
RD
BK
BL
BK
RD
TB CNW CNIP CNB CNTH CNM CNPS
CNW1 SM2 Expansion valve for heating
TO INDOOR UNIT 1
RD (BK) (Y) (RD) (WH) (GR) (WH)
CNI 3
18V BK (WH) Mark Color
BK 15V
POWER WIRES 1 2
2
BL
CNW2
BK Black SW1 Pump down switch
3 (OR) CONTROL
SIGNAL WIRE 3
PWB1 SW3,5 Local setting switch
CNI1 BL CNI2 BL Blue
(WH) (WH)
CNA2
CNR CNS CNEEV1 CNEEV2 CNFAN1 (WH) BL OR Orange
(WH) (RD) (WH) (RD) (WH)
63H1 1 2 3 4 5 6 1 2 3 4 5 6 1 4 5 6 7
BR
BR
BL
BL
WH
OR
RD
BR
BL
OR
OR
RD
RD
BR
BR
BL
BL
Y
Local setting switch SW3(Set up at shipment OFF) 63H1 High pressure switch
Power cable, indoor-outdoor connecting wires
The defrosting operation interval becomes shorter
Model MAX over current Power cable size Power cable length indoor-outdoor Earth wire size by turning ON this switch. This switch should be
SW3-1 Defrost control change
(A) (mm 2) (m) wire size x number (mm) turned ON in the area where outside temperature
becomes below the freezing point.
100 When this switch is turned ON, the outdoor unit
125 15 3.5 27 φ1.6mm x 3 φ1.6 fan will run for 30 seconds in every 10 minutes,
SW3-2 Snow guard fan control when outdoor temperature falls to 3 C or lower and
140 the compressor is not runnning when the unit is used
in a very snowy country, set this switch to ON.
※At the connection with the duct type indoor unit.
Method of trial operation
Model MAX over current Power cable size Power cable length indoor-outdoor Earth wire size 1 Trial operation can be performed by using SW3-3,4.
(A) (mm 2) (m) wire size x number (mm) 2 Compressor will be in the operation when
SW3-3 is ON.
100 16 26 SW3-3,4 Trial operation 3 Cooling trial operation will be performed when
PCA001Z540 a
'10 • PAC-DB-142
The specifications shown in the above table are for units without heaters. For units with heaters, refer
to the installation instructions or the construction instructions of the indoor unit.
Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen
along the regulations in each country.
The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation
in effect in each country.
Item Description
CnA∼Z Connector
POWER SOURCE 3∼380ー415V 50Hz/380V 60Hz
CH Crankcase heater
TB TB
F(10A)
RD RD CM Compressor motor
L1 RD
WH BK
1 TO INDOOR UNIT
L2 2
BK
BL
WH
WH
WH
WH
OR
OR
OR
OR
RD
RD
RD
RD
BR
BR
BR
BR
BL
BL
BL
BL
Y
6 5 4 3 2 1 6 5 4 3 2 1 7 6 5 4 1 7 6 5 4 1
RD
BK
BK
BL
CT
CNW CNW2 CNEEV1 CNEEV2 CNFAN1 CNFAN2 LPT Low pressure sensor
(BK) (OR) (WH) (RD) (WH) (WH)
BL
RD
SM2 Expansion valve for heating
R5 AC1 AC2 AC3 CNW1 CNO1 CNA1 ON ON
+4
DM
(WH) (RD) BL (WH)
RD 52X1 52X3 52X6 OFF OFF Mark Color SW1 Pump down switch
BL
-6 DC FAN CNO2 CNA2 1 2 3 4 1 2 3 4
PWB4 (RD) BL (WH)
LED1 LED2 SW1 BK Black SW3,5 Local setting switch
SW3 SW5
TB Terminal block
GN
BK
L BL Blue
BR Brown THo-A Thermistor(Outdoor air temp.)
INVERTER CNI3 CNI1 CNR CNS CNM CNH CNU CNB CNTH CNPS
CNIP
P2
PWB2
(WH) (WH) (WH) (RD) (GR) (BR) (BL) (RD) (WH) (Y) (WH)
GR Gray THo-D Thermistor(Discharge pipe temp.)
P3
Thermistor(Camp.undeneth temp.)
WH
RD
RD
RD
BR
BR
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
THo-H
BL
BL
BL
BL
N2 IPM
Y
Y
P Pink
P N U V W t° t° t° t° t° t° t°
THo-IPM Thermistor(IPM)
-
BR
+
RD THo-R1,2 Thermistor(Heat exchanger pipe temp. )
125 -
V W
LPT Red
U 63H1 THo-H THo-R2 THo-R1 THo-D THo-S THo-A THo-IPM
MS WH White THo-S Thermistor(Suction pipe temp.)
+
3∼
Y Yellow 20S Solenoid valve for 4 way valve
CM Y/GN Yellow/Green 52X1 Auxilliary relay(for CH)
52X3 Auxilliary relay(for 20S)
52X6 Auxilliary relay(for 52X)
Power cable, indoor-outdoor connecting wires Local setting switch SW3(Set up at shipment OFF) 63H1 High pressure switch
The defrosting operation interval becomes shorter
Model MAX over current Power cable size Power cable length indoor-outdoor Earth wire size by turning ON this switch. This switch should be
SW3-1 Defrost control change
(A) (mm)2 (m) wire size x number (mm) turned ON in the area where outside temperature
becomes below the freezing point.
When this switch is turned ON, the outdoor unit
200 19 3.5 21
φ1.6mm x 3 φ1.6 fan will run for 30 seconds in every 10 minutes,
250 22 5.5 31 SW3-2 Snow guard fan control when outdoor temperature falls to 3 or lower and
the compressor is not runnning when the unit is used
in a very snowy country, set this switch to ON.
※At the connection with the duct type indoor unit. Method of trial operation
1 Trial operation can be performed by using SW3-3,4.
Model MAX over current Power cable size Power cable length indoor-outdoor Earth wire size
2 Compressor will be in the operation when
(A) (mm)2 (m) wire size x number (mm) SW3-3 is ON.
SW3-3,4 Trial operation 3 Cooling trial operation will be performed when
PCA001Z541 a
'10 • PAC-DB-142
The specifications shown in the above table are for units without heaters. For units with heaters, refer
to the installation instructions or the construction instructions of the indoor unit.
Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen
along the regulations in each country.
The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation
in effect in each country.
50 50 50 50
N50 N50
40 40 40 40
N40 N40
30 30 30 30
N30 N30
20 20 20 20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
Model FDTC60VD
Cooling noise level 47 dB (A) at P-HIGH Heating noise level 47 dB (A) at P-HIGH
46 dB (A) at HIGH 46 dB (A) at HIGH
39 dB (A) at MEDIUM 39 dB (A) at MEDIUM
30 dB (A) at LOW 32 dB (A) at LOW
60 60 60 60
N60 N60
Souud Pressure Level
50 50 50 50
N50 N50
40 40 40 40
N40 N40
30 30 30 30
N30 N30
20 20 20 20
N10 N20 N10 N20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
50 50 50 50 50 50
N50 N50 N50
40 40 40 40 40 40
N40 N40 N40
30 30 30 30 30 30
N30 N30 N30
20 20 20 20 20 20
N10 N20 N10 N20 N10 N20
10 10 10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
- 126 -
50 50 50 50 50 50
N50 N50 N50
40 40 40 40 40 40
N40 N40 N40
30 30 30 30 30 30
N30 N30 N30
20 20 20 20 20 20
N20 N10 N20 N10 N20
N10
10 10 10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
1m
1m
50 50 50 50 50 50
N50 N50 N50
40 40 40 40 40 40
N40 N40 N40
30 30 30 30 30 30
N30 N30 N30
20 20 20 20 20 20
N20 N10 N20 N10 N20
N10
10 10 10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
Models FDEN125,140VD
Noise level 50 dB (A) at P-HIGH
46 dB (A) at HIGH
44 dB (A) at MEDIUM
43 dB (A) at LOW
60 60
N60
Souud Pressure Level
(standard 2×10-5 Pa)
50 50
N50
40 40
N40
30 30
N30
20 20
N10 N20
10 10
63 125 250 500 1000 2000 4000 8000
- 127 -
Unit
Measured based on JIS B 8616 1.5 m
Mike position as right Mike (at center & below unit)
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
50 50 50 50
N50 N50
40 40 40 40
N40 N40
30 30 30 30
N30 N30
20 20 20 20
N10 N20 N10 N20
10 10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
60 60 60 60 60 60
N60 N60 N60
50 50 50 50 50 50
N50 N50 N50
40 40 40 40 40 40
N40 N40 N40
30 30 30 30 30 30
20 20 20 20 20 20
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
- 128 -
50 50 50 50
N50 N50
40 40 40 40
N40 N40
30 30 30 30
20 20 20 20
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
Power level
(Measurement conditions: JIS-B8616, measurement location: reverberation chamber)
Unit: dB Unit: dB
Model Air supply side Air return side Model Air supply side Air return side
FDU71VD 65 65 FDU200VD 75 64
FDU100VD 66 66 FDU250VD 76 65
FDU125VD, 140VD 67 67 Note(1) Values are for external static pressure of 200Pa.
- 129 -
Cooling noise level 47 dB (A) Heating noise level 47 dB (A) Cooling noise level 48 dB (A)
70 70 70 70 70 70
N7 0 N7 0 N70
Souud Pressure Level
(standard 2×10-5Pa)
(standard 2×10-5Pa)
60 60 60 60 60 60
N6 0 N6 0 N60
50 50 50 50 50 50
N5 0 N5 0 N50
40 40 40 40 40 40
N4 0 N4 0 N40
30 30 30 30 30 30
N20 N3 0 N20 N3 0 N20 N30
20 20 20 20 20 20
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
Heating noise level 48 dB (A) Noise level 48 dB (A) Noise level 49 dB (A)
70 70 70 70 70 70
N7 0 N7 0 N 70
Souud Pressure Level
(standard 2×10-5Pa)
(standard 2×10-5Pa)
60 60 60 60 60 60
N6 0 N6 0 N 60
50 50 50 50 50 50
N5 0 N5 0 N 50
40 40 40 40 40 40
N4 0 N4 0 N 40
30 30 30 30 30 30
N30 N20 N30 N20 N30
N20
20 20 20 20 20 20
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
Cooling noise level 50 dB (A) Heating noise level 51 dB (A) Noise level 51 dB (A)
70 70 70 70 70 70
N70 N70
Souud Pressure Level
N70
(standard 2×10-5Pa)
(standard 2×10-5Pa)
(standard 2×10-5Pa)
60 60 60 60 60 60
N60 N60 N60
50 50 50 50 50 50
N50 N50 N50
40 40 40 40 40 40
N40 N40 N40
30 30 30 30 30 30
N20 N30 N20 N30 N20 N30
20 20 20 20 20 20
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
Noise level 57 dB (A) Cooling noise level 57 dB (A) Heating noise level 58 dB (A)
70 70 70 70 70 70
N70 N70 N70
Souud Pressure Level
(standard 2×10-5Pa)
60 60 60 60 60 60
N60 N60 N60
50 50 50 50 50 50
N50 N50 N50
40 40 40 40 40 40
N40 N40 N40
30 30 30 30 30 30
N 20 N30 N 20 N30 N20 N30
20 20 20 20 20 20
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz) Mid Octave Band Frequency (Hz)
- 130 -
• External static pressure table How to interpret the blower characteristics table
Unit : Pa (50Hz/60Hz)
Duct specs. Example : Case of FDUM60VD (50Hz)
Air flow 1 spot closing (1) Standard (2) Square duct (3)
(m3 /min) 40
Model
Hi
gh
FDUM50VD 14 - 85/90 90/90
M
ed
Lo
FDUM60VD 18 70/85 85/100 90/100
iu
w
20
m
FDUM71VD 20 65/80 85/100 90/105
FDUM100VD 28 80/90 90/100 95/105
2-spot blower
FDUM125VD internal resistance
34 75/90 85/100 95/105 0
FDUM140VD
–10 3-spot blower
Notes(1) 1 spot closing: Round duct flange at center is removed and shield with a internal resistance
special panel (option). Square duct blower
–20 internal resistance
Notes(2) Standard: ø200 duct are installed at all blowout holes.
Notes(3) Square duct: All round ducts are removed and replaced with special
square duct flanges (option) 13 14 16 18 20
Air flow (m3/min)
① 2-spot blowout.....................
Internal resistance increases more than
the standard 3-spot blowout.Approx.
14Pa at 17m3/min
② Square duct blowout...........
Internal resistance decreases more than
the standard round duct (ø200 3-spot).
3Pa at 17m3/min. (External static
pressure increases in reverse.)
Model FDUM50VD
50Hz 60Hz
120 120
100 it 100
lim
per
Up
it
P-
lim
per
Hi
U p
gh
P-H
80 80
igh
Hi
gh
Static pressure (Pa)
Hig
h
60 60
Me
40 40
Me
diu
dium
m
Low
20 20
Low
0 0
[Standard] [Standard]
2-spot blower internal resistance 2-spot blower internal resistance
-10 -10
Square duct blower intermalresistance. Square duct blower intermalresistance.
10 12 14 15.5 10 12 14 15.5
Lower Air flow (m /min) 3
Upper Lower Air flow (m3/min) Upper
limit limit limit limit
- 131 -
Model FDUM60VD
50Hz 60Hz
120 120
100 100
P-H
it
lim
ig h
m it er
r li pp
P-H
pe U
80 Up 80
igh
Hi
Static pressure (Pa)
Hig
gh
60 60
h
40 40
Me
Me
diu
diu
m
Lo
m
w
20 20
Lo
w
0 0
2-spot blower internal resistance 2-spot blower internal resistance
-10 -10 [Standard]
[Standard]
3-spot blower internal resistance 3-spot blower internal resistance
-20 -20
Square duct blower intermalresistance. Square duct blower intermalresistance.
13 14 16 18 20 13 14 16 18 20
Lower Air flow(m /min) 3
Upper Lower Air flow(m /min) 3
Upper
limit limit limit limit
Model FDUM71VD
50Hz 60Hz
120 120
100 100
it
P-H
r lim it
e lim
igh
p
Up er
P-
pp
Hi
U
gh
80 80
Hig
Static pressure (Pa)
60 60
Me
diu
40 40
m
Me
diu
Low
m
Lo
20 20
w
0 0
2-spot blower internal resistance 2-spot blower internal resistance
-10 [Standard] -10 [Standard]
3-spot blower internal resistance 3-spot blower internal resistance
Square duct blower intermalresistance Square duct blower intermalresistance
.
14 17 20 23 14 17 20 23
Lower Air flow(m3/min) Upper Lower Air flow(m3/min) Upper
limit limit limit limit
- 132 -
Model FDUM100VD
120 50Hz 120 60Hz
100 100
it
lim
P-H
t
mi er
r li pp
igh
pe P- U
Hi
Up gh
80 80
Static pressure (Pa)
Hi
Hi
gh
60 gh 60
Me
M
40
ed
40
diu
ium
m
Lo
w
20 20
Lo
w
3-spot blower internal resistance 3-spot blower internal resistance
0 0
[Standard] 4-spot blower internal resistance [Standard] 4-spot blower internal resistance
-10 -10
Square duct blower intermalresistance Square duct blower intermalresistance
21 25 28 31 34 21 25 28 31 34
Lower Air flow (m /min) 3
Upper Lower Air flow (m /min) 3
Upper
limit limit limit limit
80
h
80
Hi
gh
Static pressure (Pa)
60 60
M
ed
iu
m
Med
ium
40 40
Lo
w
Low
20 20
-10 -10
Square duct blower intermalresistance Square duct blower intermalresistance
24 26 30 34 38 24 26 30 34 38
Lower Air flow (m3/min) Upper Lower Air flow (m3/min) Upper
limit limit limit limit
- 133 -
200 200
180 180
160 160
External static pressure (Pa)
d-H ed
pp
-H
igh igh
U
100
Hi
100 High static High static
Hi
gh
pressure setting
gh
pressure setting
spe
spe
t it
limi 80
ed
80 er r lim
ed-
-L
Low Low
ow
Lo
Standard 60
w
Standard
pressure 60 it
mit pressure r lim
er li Uppe
Upp
Sta
40
St
40
nd
Stand
an
Stan
da
ard
Standard
Standard static
rd
static
ard-L
dard
-H
20 pressure setting
-
pressure
Hi
20
igh
gh
setting
ower
-Low
0
0 27 29 31 33 34 35 37 39 41
17 18 19 20 21 22 23 24
Lower Upper Lower Standard Upper
Standard
limit limit limit air flow limit
air flow
Air flow (m3/min) Air flow (m3/min)
Models FDU125,140VD
200
180
160
External static pressure (Pa)
140
it Hi
120 r lim gh
pe sp
e
Up ed
-H
i gh
100
Hi
High static
gh
pressure setting
sp
it
ee
80 m
er li
d-L
Low
ow
Standard
pressure 60 r lim
it
Uppe
St
40
an
Stan
da
Standard static
rd
dard
-H
20 pressure setting
igh
-Low
er
0
34 36 38 40 42 44 46 48 50
33.5 Standard Upper
Lower air flow limit
limit
Air flow (m3/min)
Notes 1) Factory default setting of fan speed is [STANDARD] which has standard static pressure.
If high static pressure setting is required, change setting to [HIGH SPEED 1] with remote controller on site.
(Regarding the setting method, refer to the user's manual of remote controller for detail)
Notes 2) When setting up high static pressure, do not operate the unit under the condition of 60Pa or lower of the external static pressure.
Notes 3) The fan speed of this model can be switched between two speeds.
- 134 -
Model FDU200VD
■Standard (Factory Settings)
High High
50Hz Low 60Hz Low
200 200
Example
150 of duct
150
External static pressure (Pa)
50 50
0 0
38 40 45 50 55 60 65 45 50 55 60 65
Lower 51 Upper Lower Standard 66
limit Standard limit limit Upper
limit
Air flow(m3/min) Air flow(m3/min)
■When the fan controller kit is used (Option : Refer to page 290)
•Standard rating point rated air volume at 100Pa
High High
50Hz Low 60Hz Low
200 200
8 8
7 6 7
6 4
5
5 Example
4 of duct
150 150
3
External static pressure (Pa)
Example
of duct
100 100
7 8
6 7
50 5 50 6
5
4
3 4
0 0
38 40 45 50 55 60 65 45 50 55 60 65
Lower 51 Upper Lower Standard 66
limit Standard limit limit Upper
limit
Air flow(m3/min) Air flow(m3/min)
Note (1) Nos.②, ① of fan controller should not be used Note (1) Nos.③, ② and ① of fan controller should not be used
because the fan motor could produce electromagnetic because the fan motor could produce electromagnetic
noise. noise.
- 135 -
Model FDU250VD
■Standard (Factory Settings)
High High
50Hz Low 60Hz Low
200 200
Example
150 of duct 150
Example
of duct
100 100
50 50
0 0
51 55 60 65 68 70 75 80 85 87 60 65 70 80 7585 88
Lower Standard Upper Lower Standard Upper
limit limit limit limit
Air flow(m3/min) Air flow(m3/min)
7
Example
of duct
150 150
6
External static pressure (Pa)
Example
4 of duct
100 8 100
7
6
8
5
4
7
50 8
3
50
7
6 6
5
5
4
3
4
0 0
51 55 60 65 68 70 75 80 85 87 60 65 70 80 7585 88
Lower Standard Upper Lower Standard Upper
limit limit limit limit
Air flow(m3/min) Air flow(m3/min)
Note (1) Nos.②, ① of fan controller should not be used Note (1) Nos.③, ② and ① of fan controller should not be used
because the fan motor could produce electromagnetic because the fan motor could produce electromagnetic
noise. noise.
- 136 -
ISD09407
- 137 -
ISD09406
- 138 -
ISD09406
- 139 -
ISD09406
- 140 -
ISD09408
- 141 -
ISD09408
- 142 -
Models FDEN100VD
Cooling Air flow : P-Hi
ISD09408
- 143 -
ISD09408
- 144 -
Strainer
Model 71
- 145 -
Electronic Electronic
expansion valve expansion valve
(cooling)(EEVC) (heating)(EEVH)
Receiver
- 146 -
( 50,60:ø12.7
71:ø15.88 )
Indoor unit Indoor unit Outdoor unit Cooling cycle Heating cycle
Check joint 4way valve Thermistor
Gas line (ThO-A)
(ø15.88)
Service valve
Flare connecting (Flare connecting)
Check joint
Thermistor
(Heat exchanger) Heat exchanger
High pressure
(ThI-R3) Check
switch
valve Thermistor
Thermistor 63H1
(Return air) Muffler (ThO-S)
Lower pressure sensor
(ThI-A) Thermistor
(LPT)
Heat exchanger (ThO-D)
Thermistor
(ThO-R1)
Thermistor
(Heat exchanger)
(ThI-R2) (Discharge)
Accumlator
Thermistor Compressor
(Heat exchanger) Thermistor
(ThI-R1)
Check joint (Suction) (ThO-R2)
Flare connecting
(ø6.35) Liquid line Sub-cooling
(ø9.52) coil
Service valve
(Flare connecting) Strainer Strainer Strainer Strainer
Diameter joint Liquid
of different branch pipe
(50,60 only) Electronic Electronic
(ø9.52) expansion valve expansion valve
(cooling)(EEVC) (heating)(EEVH)
Receiver
- 147 -
Indoor unit Indoor unit Outdoor unit Cooling cycle Heating cycle
Check joint 4way valve Thermistor
Muffler (ThO-A)
Gas line
Service valve
Flare connecting (Flare connecting)
Check joint
High pressure
Thermistor switch Lower pressure
(Heat exchanger) sensor
63H Check
(ThI-R3) valve (LPT)
Thermistor Oil
(Return air) separator Heat exchanger
(ThI-A)
Strainer Thermistor
Heat exchanger Thermistor (ThO-S)
(ThO-D)
Thermistor
(Heat exchanger)
Capillaly (Discharge) Thermistor Thermistor
(ThI-R2) tube (ThO-R2)
(ThO-R1)
Compressor
Thermistor (Suction)
(Heat exchanger)
(ThI-R1) Thermistor
Sub-cooling
Flare connecting Check joint (ThO-H) coil
٨Refrigerant
Receiver
line (one way) pipe size
Model Gas line Liquid line
In case of ø9.52 : 40m
200 In case of ø22.22 : 35m
In case of ø12.7 : 70m
In case of ø25.4 or ø28.58 : 70m
250 In case of ø12.7 : 70m
- 148 -
Gas branch
pipe
Indoor unit Indoor unit Indoor unit (ø12.7)
Cooling cycle Heating cycle
Check joint Thermistor
Gas line (ThO-A)
(ø15.88)
Flare connecting
Service valve 4way valve
Thermistor (Flare connecting) Check joint
(Heat exchanger)
(ThI-R3) High pressure Heat exchanger
Thermistor switch Check
(Return air) valve Thermistor
63H1
(ThI-A) Muffler (ThO-S) Lower pressure sensor
Heat exchanger Thermistor
(LPT)
(ThO-D)
Thermistor Thermistor
(Heat exchanger)
(ThO-R1)
(ThI-R1)
(Discharge)
Thermistor
(Heat exchanger) Accumlator
(ThI-R2) Compressor
Thermistor
Liquid branch pipe Check joint (Suction) (ThO-R2)
(ø9.52) Sub-cooling
coil
Receiver
Model 200
Gas branch
pipe
Indoor unit Indoor unit Indoor unit (ø15.88)
Outdoor unit Cooling cycle Heating cycle
Check joint 4way valve Thermistor
Muffler (ThO-A)
Gas line
Flare connecting Service valve
(Flare connecting)
Thermistor Check joint
(Heat exchanger) High pressure
switch Lower pressure
(ThI-R3) sensor
Thermistor 63H Check
(Return air) valve (LPT)
(ThI-A) Oil
Heat exchanger separator Heat exchanger
Thermistor Strainer Thermistor
(Heat exchanger) Thermistor (ThO-S)
(ThI-R1) (ThO-D)
Thermistor
(Heat exchanger) Capillaly Thermistor Thermistor
(Discharge)
(ThI-R2) tube (ThO-R1) (ThO-R2)
Compressor
Liquid branch pipe (Suction)
(ø9.52) Thermistor
Sub-cooling
Check joint (ThO-H) coil
Liquid line
Strainer Strainer Strainer Strainer
Receiver
٨Refrigerant line (one way) pipe size
Gas line Liquid line
In case of ø22.22 : 35m In case of ø9.52 : 40m
In case of ø12.7 : 70m
- 149 -
2nd branch
pipe of gas
(ø12.7)
1nd branch Outdoor unit Cooling cycle Heating cycle
Indoor unit Indoor unit
pipe of gas Check joint 4way valve Thermistor
Thermistor (ø15.88) Gas line (ThO-A)
Muffler
(ThI-R3)
Service valve
Branch pipe (Flare connecting)
Heat Check joint
(Brazing) High pressure
exchanger switch Lower pressure
Branch pipe sensor
Flare connecting (Brazing) 63H Check (LPT)
valve
Oil
Thermistor separator Heat exchanger
(ThI-A) Thermistor
Strainer
Thermistor (ThO-S)
(ThO-D)
Thermistor
(ThI-R1) Capillaly (Discharge) Thermistor Thermistor
Thermistor tube (ThO-R1) (ThO-R2)
Compressor
(ThI-R2) (Suction)
Flare connecting
Thermistor
(ø6.35) Sub-cooling
1nd branch Check joint (ThO-H) coil
pipe of liquid
Branch pipe
(Brazing) (ø9.52) Strainer Strainer Strainer Strainer
2nd branch
pipe of gas
(ø12.7) ●Refrigerant line (one way) pipe size
Indoor unit Indoor unit Model Gas line Liquid line
In case of ø9.52 : 40m
Thermistor 200 In case of ø22.22 : 35m In case of ø12.7 : 70m
(ThI-R3) In case of ø25.4 orø28.58 : 70m
250 In case of ø12.7 : 70m
Branch pipe
Heat (Brazing)
exchanger
Thermistor
(ThI-R1)
Thermistor
(ThI-R2)
Flare connecting
(ø6.35)
Branch pipe
(Brazing)
2nd branch
pipe of gas
(ø9.52)
Diameter joint
of different
- 150 -
Thermistor
OFF 63˚C
(for protection over-
ON 56˚C
loading in heating)
ThI-R Indoor unit
Thermistor OFF 1.0˚C
(for frost prevention) ON 10˚C
Thermistor
Tho-R OFF 53˚C OFF 51˚C
(for protection high Outdoor unit
(TH1) ON 63˚C ON 65˚C
pressure in cooling.)
Thermistor
Tho-D OFF 115˚C OFF 115˚C OFF 135˚C
(for detecting dis- Outdoor unit
(TH3) ON 95˚C ON 85˚C ON 90˚C
charge pipe temp.)
- 151 -
Considering to get sufficient heating capacity, the area where the averaged lowest ambient
Recommendable area to install
air temperature in day time during winter is above 0˚C, and it has no accumulation of snow.
The limitations of installation space are shown in the page for exterior dimensions.
Installation site
Install the indoor unit at least 2.5m higher than the floor surface.
Temperature and humidity conditions surrounding the Model FDE Dew point temperature : 23˚C or less, relative hummdity : 80% or less
indoor unit in the ceiling (Note 2) Other models Dew point temperature : 28˚C or less, relative hummdity : 80% or less
Limitations on unit and piping installation See page 154 and 155
PCA001Z561 A
- 152 -
㪌㪇
͠&$
㪋㪇
temperature㩿㷄㪛㪙㪀
㪉㪇
㪈㪇
㪄㪈㪇
͠&$
㪄㪉㪇
㪈㪇 㪈㪉 㪈㪋 㪈㪍 㪈㪏 㪉㪇 㪉㪉 㪉㪋 㪉㪍
Indoor air temperature㩿㷄㪮㪙㪀
عHeating
㪊㪇
temperature㩿㷄㪛㪙㪀
㪉㪌
Indoor air
㪌
㪄㪉㪌 㪄㪉㪇 㪄㪈㪌 㪄㪈㪇 㪄㪌 㪇 㪌 㪈㪇 㪈㪌 㪉㪇 㪉㪌
Outdoor air temperature㩿㷄㪮㪙㪀
Decline in cooling and heating capacity or operation stop may occur when the outdoor unit is installed in
places where natural wind can increase or decrease its design airflow rate.
PCA001Z561 A
- 153 -
'10 • PAC-DB-142
DIS-WA1
125V・140V Outdoor unit
L (riser)
φ22.22 ≦ 35m
Main pipe length Gas piping L
φ25.4 or φ28.58 ≦ 70m
One-way pipe length between the first branching point from to the second branching point ≦ 5m La
Prohibition of the use
One-way pipe length between the first branching point and indoor units ≦ 30m L1, La+L2, La+L3 ※2
L1-(La+L2), L1-(La+L3)
Piping length difference from the first branching point to indoor unit < 3m
L2-L3, L3-L2 ※2
When the outdoor unit is positioned higher ≦ 30m
Elevation difference between indoor and outdoor units H
When the outdoor unit is positioned lower ≦ 15m
Elevation difference among indoor units ≦ 0.5m h1, h2, h3
Triple type A Triple type B ※ 1 Install the indoor units so that L+L1
Indoor unit Indoor unit
h1
becomes the longest one-way pipe.
h1
h3
h3 Indoor unit h2
Keep the pipe length difference between
Indoor unit
h2
L1 and (La+L2) or (La+L3) within 10m.
L2 H
L1 L3 ※ 2 Connect the unit that is the maximum
L2
H L1
L3 Second Branch capacity with L1.
PCA001Z561 A
La
'10 • PAC-DB-142
First Branch Triple type
L (riser)
Outdoor unit
Outdoor unit
L (riser) Branch piping set(option)
Model for
Type A Type B
outdoor units
Branch pipe First Branch Second Branch
(1) A riser pipe must be part of the main.
A branching pipe set should be installed horizontally at a point as close to an indoor unit as possible.
140V DIS-TA1 DIS-WA1 DIS-WA1
(2) Reduce refrigerant amount by 1.0kg from the factory charge when refrigerant piping is shorter than 3m. 200V・250V DIS-TB1 DIS-WB1 DIS-WA1
Net capacity = Capacity shown in the capacity tables (1.9.1) × Correction factors shown in he table (1.9.2) (1.9.3) (1.9.4).
Caution: In case that the cooling operation during low outdoor air temperature below -5°C is expected, install the outdoor unit
where it is not influenced by natural wind. Otherwise protection control by low pressure will be activated much more
frequently and it will cause insufficient capacity or breakdown of the compressor in worst case.
PJA003Z377 A
PJA003Z377 A
- 156 -
PJA003Z377 A
Model FDTC100VNPVD Indoor unit FDTC50VD (2 units) Outdoor unit FDC100VN
Model FDTC100VSPVD Indoor unit FDTC50VD (2 units) Outdoor unit FDC100VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 6.89 6.51 6.13 5.75 5.50
20 9.98 7.36 10.55 7.74 10.84 7.66 11.15 7.57 11.78 7.91 12.41 7.70 -9.6 -10 7.40 7.38 7.00 6.62 6.24
25 9.71 7.25 10.28 7.64 10.56 7.55 10.87 7.47 11.49 7.82 12.12 7.62 -3.4 -4 7.53 7.51 7.49 7.11 6.74
30 9.44 7.14 10.00 7.53 10.28 7.45 10.59 7.37 11.21 7.73 1.8 1 8.55 8.52 8.06 7.45 6.99
35 9.05 6.98 9.68 7.41 10.00 7.35 10.30 7.28 10.90 7.63 4.9 4 10.28 10.14 9.33 8.47 7.84
40 8.45 6.74 9.15 7.21 9.50 7.17 9.78 7.10 10.34 7.46 7.0 6 11.35 11.27 11.20 10.92 10.40
43 8.00 6.56 8.72 7.06 9.08 7.03 9.40 6.97 10.05 7.37 11.2 10 12.19 12.10 12.02 11.73 10.69
PJA003Z377 A
Model FDTC125VNPVD Indoor unit FDTC60VD (2 units) Outdoor unit FDC125VN
Model FDTC125VSPVD Indoor unit FDTC60VD (2 units) Outdoor unit FDC125VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 8.62 8.14 7.67 7.19 6.88
20 12.31 8.39 12.97 8.72 13.30 8.61 13.66 8.50 14.38 8.78 15.10 -9.6 -10 9.25 9.22 8.75 8.28 7.81
25 12.05 8.27 12.71 8.61 13.03 8.50 13.39 8.39 14.11 8.69 14.83 -3.4 -4 9.41 9.39 9.36 8.89 8.42
30 11.79 8.15 12.44 8.50 12.77 8.40 13.13 8.30 13.84 8.59 1.8 1 10.68 10.65 10.08 9.32 8.74
35 11.31 7.94 12.10 8.36 12.50 8.29 12.86 8.19 13.58 8.50 4.9 4 12.85 12.68 11.74 10.58 9.80
40 10.56 7.61 11.44 8.09 11.88 8.05 12.23 7.96 12.93 8.28 7.0 6 14.19 14.09 14.00 13.65 13.00
43 10.00 7.37 10.90 7.88 11.35 7.85 11.76 7.79 12.57 8.16 11.2 10 15.16 15.06 14.97 14.66 13.36
PJA003Z377 A
(c) Triple type
Model FDTC140VNTVD Indoor unit FDTC50VD (3 units) Outdoor unit FDC140VN
Model FDTC140VSTVD Indoor unit FDTC50VD (3 units) Outdoor unit FDC140VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 9.85 9.31 8.76 8.22 7.86
20 13.11 10.28 13.91 10.89 14.31 10.78 14.62 10.63 15.23 11.10 15.85 10.78 -9.6 -10 10.57 10.54 10.00 9.46 8.92
25 12.92 10.20 13.78 10.84 14.21 10.74 14.48 10.59 15.04 11.05 15.59 10.71 -3.4 -4 10.75 10.73 10.69 10.16 9.63
30 12.73 10.13 13.65 10.79 14.10 10.71 14.35 10.54 14.84 10.99 1.8 1 12.21 12.17 11.52 10.65 9.99
35 12.53 10.05 13.51 10.74 14.00 10.67 14.21 10.50 14.64 10.93 4.9 4 14.69 14.49 13.36 12.09 11.20
40 11.83 9.77 12.59 10.41 12.97 10.31 13.27 10.19 13.86 10.70 7.0 6 16.18 16.09 16.00 15.60 14.86
43 11.20 9.53 12.04 10.21 12.35 10.11 12.70 10.00 13.39 10.56 11.2 10 17.47 17.36 17.26 16.75 15.27
- 157 -
PJA003Z377 A
PJA003Z377 A
(2) Ceiling cassette-4way type (FDT)
(a) Single type
Model FDT40ZIXVD Indoor unit FDT40VD Outdoor unit SRC40ZIX-S
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 2.56 2.53 2.48 2.43 2.38
20 3.83 3.27 4.06 3.51 4.17 3.42 4.30 3.34 4.54 3.54 4.78 3.35 -9.6 -10 3.79 3.74 3.69 3.64 3.47
25 3.97 3.29 4.19 3.52 4.31 3.44 4.44 3.35 4.70 3.55 4.97 3.35 -3.4 -4 4.19 4.17 4.06 3.74 3.54
30 3.82 3.27 4.04 3.50 4.15 3.42 4.28 3.33 4.54 3.54 1.8 1 4.28 4.25 4.15 3.81 3.62
35 3.62 3.23 3.87 3.48 4.00 3.40 4.12 3.32 4.36 3.54 4.9 4 4.36 4.34 4.23 3.89 3.69
40 3.38 3.20 3.66 3.46 3.80 3.39 3.91 3.31 4.14 3.53 7.0 6 4.56 4.53 4.50 4.39 4.23
43 3.20 3.17 3.49 3.44 3.63 3.37 3.76 3.30 4.02 3.52 11.2 10 4.99 4.96 4.92 4.89 4.85
PJF002Z192 A
- 158 -
PJF002Z192 A
PJF002Z192 A
Model FDT100VNVD Indoor unit FDTC100VD Outdoor unit FDC100VN
Model FDT100VSVD Indoor unit FDTC100VD Outdoor unit FDC100VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 6.89 6.51 6.13 5.75 5.50
20 9.98 7.24 10.55 7.64 10.84 7.47 11.15 7.29 11.78 7.64 12.41 7.24 -9.6 -10 7.40 7.38 7.00 6.62 6.24
25 9.71 7.16 10.28 7.58 10.56 7.41 10.87 7.24 11.49 7.59 12.12 7.21 -3.4 -4 7.53 7.51 7.49 7.11 6.74
30 9.44 7.09 10.00 7.52 10.28 7.36 10.59 7.19 11.21 7.55 1.8 1 8.55 8.52 8.06 7.45 6.99
35 9.05 6.99 9.68 7.45 10.00 7.30 10.30 7.14 10.90 7.51 4.9 4 10.28 10.14 9.33 8.47 7.84
40 8.45 6.84 9.15 7.34 9.50 7.20 9.78 7.05 10.34 7.44 7.0 6 11.35 11.27 11.20 10.92 10.40
43 8.00 6.73 8.72 7.25 9.08 7.13 9.40 6.98 10.05 7.40 11.2 10 12.19 12.10 12.02 11.73 10.69
PJF002Z192 A
Model FDT125VNVD Indoor unit FDT125VD Outdoor unit FDC125VN
Model FDT125VSVD Indoor unit FDT125VD Outdoor unit FDC125VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 8.62 8.14 7.67 7.19 6.88
20 12.31 8.65 12.97 9.06 13.30 8.89 13.66 8.72 14.38 9.08 15.10 8.69 -9.6 -10 9.25 9.22 8.75 8.28 7.81
25 12.05 8.56 12.71 8.98 13.03 8.81 13.39 8.65 14.11 9.02 14.83 8.64 -3.4 -4 9.41 9.39 9.36 8.89 8.42
30 11.79 8.47 12.44 8.90 12.77 8.74 13.13 8.58 13.84 8.95 1.8 1 10.68 10.65 10.08 9.32 8.74
35 11.31 8.30 12.10 8.80 12.50 8.66 12.86 8.51 13.58 8.89 4.9 4 12.85 12.68 11.74 10.58 9.80
40 10.56 8.05 11.44 8.60 11.88 8.49 12.23 8.34 12.93 8.75 7.0 6 14.19 14.09 14.00 13.65 13.00
43 10.00 7.87 10.90 8.44 11.35 8.34 11.76 8.22 12.57 8.67 11.2 10 15.16 15.06 14.97 14.66 13.36
- 159 -
PJF002Z192 A
(b) Twin type
Model FDT71VNPVD Indoor unit FDT40VD (2 units) Outdoor unit FDC71VN
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 4.53 4.51 4.50 4.48 4.46
20 6.96 5.66 7.39 6.07 7.61 5.87 7.84 5.67 8.31 6.01 8.78 5.55 -9.6 -10 5.11 5.09 5.06 5.03 5.00
25 6.86 5.65 7.44 6.07 7.72 5.87 7.98 5.66 8.49 6.00 8.91 5.54 -3.4 -4 5.69 5.66 5.62 5.59 5.55
30 6.67 5.64 7.17 6.07 7.41 5.88 7.67 5.67 8.14 6.02 1.8 1 6.13 6.09 6.04 6.00 5.96
35 6.43 5.63 6.88 6.07 7.10 5.88 7.31 5.69 7.74 6.06 4.9 4 7.78 7.71 7.52 6.92 6.56
40 6.00 5.61 6.50 6.07 6.75 5.89 6.94 5.70 7.34 6.09 7.0 6 8.16 8.08 8.00 7.80 7.52
43 5.68 5.60 6.19 6.07 6.45 5.90 6.68 5.72 7.14 6.11 11.2 10 8.86 8.75 8.64 8.52 8.41
PJF002Z192 A
Model FDT100VNPVD Indoor unit FDT50VD (2 units) Outdoor unit FDC100VN
Model FDT100VSPVD Indoor unit FDT50VD (2 units) Outdoor unit FDC100VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 6.89 6.51 6.13 5.75 5.50
20 9.98 7.80 10.55 8.29 10.84 8.12 11.15 7.96 11.78 8.38 12.41 8.01 -9.6 -10 7.40 7.38 7.00 6.62 6.24
25 9.71 7.73 10.28 8.22 10.56 8.06 10.87 7.90 11.49 8.34 12.12 7.97 -3.4 -4 7.53 7.51 7.49 7.11 6.74
30 9.44 7.66 10.00 8.16 10.28 8.01 10.59 7.85 11.21 8.30 1.8 1 8.55 8.52 8.06 7.45 6.99
35 9.05 7.55 9.68 8.09 10.00 7.95 10.30 7.80 10.90 8.25 4.9 4 10.28 10.14 9.33 8.47 7.84
40 8.45 7.40 9.15 7.97 9.50 7.85 9.78 7.70 10.34 8.17 7.0 6 11.35 11.27 11.20 10.92 10.40
43 8.00 7.29 8.72 7.88 9.08 7.77 9.40 7.64 10.05 8.13 11.2 10 12.19 12.10 12.02 11.73 10.69
PJF002Z192 A
Model FDT125VNPVD Indoor unit FDT60VD (2 units) Outdoor unit FDC125VN
Model FDT125VSPVD Indoor unit FDT60VD (2 units) Outdoor unit FDC125VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 8.62 8.14 7.67 7.19 6.88
20 12.31 9.43 12.97 10.03 13.30 9.76 13.66 9.49 14.38 10.00 15.10 9.40 -9.6 -10 9.25 9.22 8.75 8.28 7.81
25 12.05 9.38 12.71 9.99 13.03 9.73 13.39 9.46 14.11 9.99 14.83 9.39 -3.4 -4 9.41 9.39 9.36 8.89 8.42
30 11.79 9.34 12.44 9.96 12.77 9.70 13.13 9.44 13.84 9.97 1.8 1 10.68 10.65 10.08 9.32 8.74
35 11.31 9.25 12.10 9.91 12.50 9.67 12.86 9.41 13.58 9.96 4.9 4 12.85 12.68 11.74 10.58 9.80
40 10.56 9.12 11.44 9.83 11.88 9.60 12.23 9.36 12.93 9.93 7.0 6 14.19 14.09 14.00 13.65 13.00
43 10.00 9.03 10.90 9.76 11.35 9.55 11.76 9.32 12.57 9.91 11.2 10 15.16 15.06 14.97 14.66 13.36
- 160 -
PJF002Z192 A
PJF002Z192 A
PJF002Z192 A
(c) Triple type
Model FDT140VNTVD Indoor unit FDT50VD (3 units) Outdoor unit FDC140VN
Model FDT140VSTVD Indoor unit FDT50VD (3 units) Outdoor unit FDC140VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 9.85 9.31 8.76 8.22 7.86
20 13.11 11.21 13.91 12.00 14.31 11.78 14.62 11.55 15.23 12.21 15.85 11.70 -9.6 -10 10.57 10.54 10.00 9.46 8.92
25 12.92 11.16 13.78 11.97 14.21 11.76 14.48 11.52 15.04 12.18 15.59 11.67 -3.4 -4 10.75 10.73 10.69 10.16 9.63
30 12.73 11.11 13.65 11.94 14.10 11.74 14.35 11.50 14.84 12.16 1.8 1 12.21 12.17 11.52 10.65 9.99
35 12.53 11.06 13.51 11.91 14.00 11.72 14.21 11.47 14.64 12.13 4.9 4 14.69 14.49 13.36 12.09 11.20
40 11.83 10.89 12.59 11.72 12.97 11.52 13.27 11.31 13.86 12.02 7.0 6 16.18 16.09 16.00 15.60 14.86
43 11.20 10.73 12.04 11.60 12.35 11.41 12.70 11.21 13.39 11.96 11.2 10 17.47 17.36 17.26 16.75 15.27
- 161 -
PJF002Z192 A
(d) Double Twin type
Model FDT200VSDVD Indoor unit FDT50VD (4 units) Outdoor unit FDC200VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 12.86 12.83 12.79 12.75 12.72
20 20.36 16.78 21.49 17.87 22.06 17.57 22.70 17.27 23.99 18.25 25.28 17.56 -9.6 -10 14.51 14.47 14.42 14.37 14.32
25 19.71 16.59 20.82 17.70 21.37 17.41 22.00 17.12 23.26 18.12 24.52 17.45 -3.4 -4 15.89 15.82 15.76 15.70 15.63
30 19.07 16.41 20.15 17.54 20.69 17.25 21.30 16.97 22.53 17.99 1.8 1 17.03 16.95 16.88 16.80 16.72
35 18.10 16.13 19.37 17.34 20.00 17.09 20.60 16.82 21.80 17.87 4.9 4 21.70 21.57 21.06 19.38 18.37
40 16.90 15.80 18.30 17.09 18.97 16.86 19.54 16.60 20.68 17.68 7.0 6 22.68 22.54 22.40 21.84 21.06
43 16.00 15.56 17.44 16.89 18.16 16.69 18.81 16.46 20.01 17.56 11.2 10 24.90 24.73 24.57 24.40 24.23
PJF002Z192 A
PJF002Z192 A
(3) Ceiling suspended type (FDEN)
(a) Single type
Model FDEN40ZIXVD Indoor unit FDEN40VD Outdoor unit SRC40ZIX-S
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 2.56 2.53 2.48 2.43 2.38
20 3.83 2.96 4.06 3.13 4.17 3.09 4.30 3.04 4.54 3.20 4.78 3.09 -9.6 -10 3.79 3.74 3.69 3.64 3.47
25 3.97 3.01 4.19 3.18 4.31 3.13 4.44 3.08 4.70 3.24 4.97 3.13 -3.4 -4 4.19 4.17 4.06 3.74 3.54
30 3.82 2.96 4.04 3.13 4.15 3.08 4.28 3.04 4.54 3.20 1.8 1 4.28 4.25 4.15 3.81 3.62
35 3.62 2.89 3.87 3.08 4.00 3.04 4.12 3.00 4.36 3.15 4.9 4 4.36 4.34 4.23 3.89 3.69
40 3.38 2.80 3.66 3.01 3.80 2.98 3.91 2.94 4.14 3.10 7.0 6 4.56 4.53 4.50 4.39 4.23
43 3.20 2.74 3.49 2.96 3.63 2.93 3.76 2.90 4.02 3.07 11.2 10 4.99 4.96 4.92 4.89 4.85
- 162 -
PFA003Z902 A
PFA003Z902 A
PFA003Z902 A
Model FDEN100VNVD Indoor unit FDEN100VD Outdoor unit FDC100VN
Model FDEN100VSVD Indoor unit FDEN100VD Outdoor unit FDC100VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 6.89 6.51 6.13 5.75 5.50
20 9.98 7.01 10.55 7.35 10.84 7.23 11.15 7.11 11.78 7.40 12.41 7.13 -9.6 -10 7.40 7.38 7.00 6.62 6.24
25 9.71 6.90 10.28 7.25 10.56 7.14 10.87 7.03 11.49 7.33 12.12 7.06 -3.4 -4 7.53 7.51 7.49 7.11 6.74
30 9.44 6.80 10.00 7.16 10.28 7.05 10.59 6.94 11.21 7.25 1.8 1 8.55 8.52 8.06 7.45 6.99
35 9.05 6.66 9.68 7.05 10.00 6.96 10.30 6.86 10.90 7.17 4.9 4 10.28 10.14 9.33 8.47 7.84
40 8.45 6.44 9.15 6.88 9.50 6.81 9.78 6.71 10.34 7.03 7.0 6 11.35 11.27 11.20 10.92 10.40
43 8.00 6.29 8.72 6.74 9.08 6.68 9.40 6.60 10.05 6.95 11.2 10 12.19 12.10 12.02 11.73 10.69
- 163 -
PFA003Z902 A
Model FDEN140VNVD Indoor unit FDEN140VD Outdoor unit FDC140VN
Model FDEN140VSVD Indoor unit FDEN140VD Outdoor unit FDC140VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 9.85 9.31 8.76 8.22 7.86
20 13.11 8.68 13.91 9.06 14.31 8.91 14.62 8.73 15.23 8.96 15.85 8.55 -9.6 -10 10.57 10.54 10.00 9.46 8.92
25 12.92 8.60 13.78 9.01 14.21 8.88 14.48 8.68 15.04 8.90 15.59 8.49 -3.4 -4 10.75 10.73 10.69 10.16 9.63
30 12.73 8.53 13.65 8.96 14.10 8.84 14.35 8.64 14.84 8.84 1.8 1 12.21 12.17 11.52 10.65 9.99
35 12.53 8.45 13.51 8.91 14.00 8.80 14.21 8.59 14.64 8.79 4.9 4 14.69 14.49 13.36 12.09 11.20
40 11.83 8.17 12.59 8.58 12.97 8.45 13.27 8.29 13.86 8.57 7.0 6 16.18 16.09 16.00 15.60 14.86
43 11.20 7.93 12.04 8.39 12.35 8.25 12.70 8.12 13.39 8.44 11.2 10 17.47 17.36 17.26 16.75 15.27
PFA003Z902 A
(b) Twin type
Model FDEN71VNPVD Indoor unit FDEN40VD (2 units) Outdoor unit FDC71VN
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 4.53 4.51 4.50 4.48 4.46
20 6.96 5.68 7.39 6.04 7.61 5.96 7.84 5.88 8.31 6.21 8.78 6.02 -9.6 -10 5.11 5.09 5.06 5.03 5.00
25 6.86 5.64 7.44 6.06 7.72 6.00 7.98 5.92 8.49 6.25 8.91 6.04 -3.4 -4 5.69 5.66 5.62 5.59 5.55
30 6.67 5.58 7.17 5.98 7.41 5.91 7.67 5.84 8.14 6.17 1.8 1 6.13 6.09 6.04 6.00 5.96
35 6.43 5.50 6.88 5.89 7.10 5.82 7.31 5.74 7.74 6.08 4.9 4 7.78 7.71 7.52 6.92 6.56
40 6.00 5.36 6.50 5.78 6.75 5.72 6.94 5.65 7.34 5.99 7.0 6 8.16 8.08 8.00 7.80 7.52
43 5.68 5.26 6.19 5.69 6.45 5.64 6.68 5.58 7.14 5.95 11.2 10 8.86 8.75 8.64 8.52 8.41
PFA003Z902 A
Model FDEN100VNPVD Indoor unit FDEN50VD (2 units) Outdoor unit FDC100VN
Model FDEN100VSPVD Indoor unit FDEN50VD (2 units) Outdoor unit FDC100VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 6.89 6.51 6.13 5.75 5.50
20 9.98 6.78 10.55 7.09 10.84 6.97 11.15 6.85 11.78 7.11 12.41 6.83 -9.6 -10 7.40 7.38 7.00 6.62 6.24
25 9.71 6.68 10.28 6.99 10.56 6.88 10.87 6.76 11.49 7.03 12.12 6.76 -3.4 -4 7.53 7.51 7.49 7.11 6.74
30 9.44 6.57 10.00 6.89 10.28 6.78 10.59 6.68 11.21 6.95 1.8 1 8.55 8.52 8.06 7.45 6.99
35 9.05 6.42 9.68 6.78 10.00 6.69 10.30 6.59 10.90 6.86 4.9 4 10.28 10.14 9.33 8.47 7.84
40 8.45 6.20 9.15 6.60 9.50 6.53 9.78 6.43 10.34 6.71 7.0 6 11.35 11.27 11.20 10.92 10.40
43 8.00 6.04 8.72 6.46 9.08 6.40 9.40 6.32 10.05 6.64 11.2 10 12.19 12.10 12.02 11.73 10.69
- 164 -
PFA003Z902 A
Model FDEN140VNPVD Indoor unit FDEN71VD (2 units) Outdoor unit FDC140VN
Model FDEN140VSPVD Indoor unit FDEN71VD (2 units) Outdoor unit FDC140VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 9.85 9.31 8.76 8.22 7.86
20 13.11 10.07 13.91 10.66 14.31 10.51 14.62 10.33 15.23 10.79 15.85 10.39 -9.6 -10 10.57 10.54 10.00 9.46 8.92
25 12.92 10.00 13.78 10.62 14.21 10.48 14.48 10.29 15.04 10.74 15.59 10.33 -3.4 -4 10.75 10.73 10.69 10.16 9.63
30 12.73 9.93 13.65 10.58 14.10 10.45 14.35 10.25 14.84 10.70 1.8 1 12.21 12.17 11.52 10.65 9.99
35 12.53 9.86 13.51 10.54 14.00 10.42 14.21 10.21 14.64 10.65 4.9 4 14.69 14.49 13.36 12.09 11.20
40 11.83 9.62 12.59 10.25 12.97 10.12 13.27 9.96 13.86 10.46 7.0 6 16.18 16.09 16.00 15.60 14.86
43 11.20 9.41 12.04 10.09 12.35 9.94 12.70 9.81 13.39 10.36 11.2 10 17.47 17.36 17.26 16.75 15.27
PFA003Z902 A
PFA003Z902 A
- 165 -
PFA003Z902 A
PFA003Z902 A
(d) Double Twin type
Model FDEN200VSDVD Indoor unit FDEN50VD (4 units) Outdoor unit FDC200VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 12.86 12.83 12.79 12.75 12.72
20 20.36 13.72 21.49 14.31 22.06 14.07 22.70 13.84 23.99 14.34 25.28 13.78 -9.6 -10 14.51 14.47 14.42 14.37 14.32
25 19.71 13.47 20.82 14.07 21.37 13.83 22.00 13.61 23.26 14.13 24.52 13.59 -3.4 -4 15.89 15.82 15.76 15.70 15.63
30 19.07 13.22 20.15 13.84 20.69 13.61 21.30 13.39 22.53 13.93 1.8 1 17.03 16.95 16.88 16.80 16.72
35 18.10 12.85 19.37 13.57 20.00 13.38 20.60 13.18 21.80 13.73 4.9 4 21.70 21.57 21.06 19.38 18.37
40 16.90 12.40 18.30 13.21 18.97 13.05 19.54 12.86 20.68 13.43 7.0 6 22.68 22.54 22.40 21.84 21.06
43 16.00 12.08 17.44 12.92 18.16 12.80 18.81 12.64 20.01 13.26 11.2 10 24.90 24.73 24.57 24.40 24.23
PFA003Z902 A
- 166 -
PJR002Z391
PJR002Z391
PJR002Z391
Model FDUM100VNVD Indoor unit FDUM100VD Outdoor unit FDC100VN
Model FDUM100VSVD Indoor unit FDUM100VD Outdoor unit FDC100VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 6.89 6.51 6.13 5.75 5.50
20 9.98 8.02 10.55 8.50 10.84 8.40 11.15 8.30 11.78 8.74 12.41 8.50 -9.6 -10 7.40 7.38 7.00 6.62 6.24
25 9.71 7.92 10.28 8.41 10.56 8.31 10.87 8.22 11.49 8.66 12.12 8.43 -3.4 -4 7.53 7.51 7.49 7.11 6.74
30 9.44 7.82 10.00 8.32 10.28 8.22 10.59 8.13 11.21 8.59 1.8 1 8.55 8.52 8.06 7.45 6.99
35 9.05 7.68 9.68 8.21 10.00 8.14 10.30 8.05 10.90 8.51 4.9 4 10.28 10.14 9.33 8.47 7.84
40 8.45 7.46 9.15 8.04 9.50 7.98 9.78 7.89 10.34 8.36 7.0 6 11.35 11.27 11.20 10.92 10.40
43 8.00 7.30 8.72 7.90 9.08 7.85 9.40 7.78 10.05 8.28 11.2 10 12.19 12.10 12.02 11.73 10.69
- 167 -
PJR002Z391
Model FDUM140VNVD Indoor unit FDUM140VD Outdoor unit FDC140VN
Model FDUM140VSVD Indoor unit FDUM140VD Outdoor unit FDC140VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 9.85 9.31 8.76 8.22 7.86
20 13.11 9.58 13.91 10.08 14.31 9.98 14.62 9.84 15.23 10.20 15.85 9.88 -9.6 -10 10.57 10.54 10.00 9.46 8.92
25 12.92 9.50 13.78 10.03 14.21 9.94 14.48 9.79 15.04 10.13 15.59 9.80 -3.4 -4 10.75 10.73 10.69 10.16 9.63
30 12.73 9.42 13.65 9.98 14.10 9.90 14.35 9.74 14.84 10.07 1.8 1 12.21 12.17 11.52 10.65 9.99
35 12.53 9.33 13.51 9.92 14.00 9.86 14.21 9.69 14.64 10.00 4.9 4 14.69 14.49 13.36 12.09 11.20
40 11.83 9.04 12.59 9.57 12.97 9.48 13.27 9.36 13.86 9.75 7.0 6 16.18 16.09 16.00 15.60 14.86
43 11.20 8.78 12.04 9.36 12.35 9.25 12.70 9.16 13.39 9.61 11.2 10 17.47 17.36 17.26 16.75 15.27
PJR002Z391
(b) Twin type
Model FDUM100VNPVD Indoor unit FDUM50VD (2 units) Outdoor unit FDC100VN
Model FDUM100VSPVD Indoor unit FDUM50VD (2 units) Outdoor unit FDC100VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 6.89 6.51 6.13 5.75 5.50
20 9.98 8.29 10.55 8.81 10.84 8.72 11.15 8.64 11.78 9.11 12.41 8.91 -9.6 -10 7.40 7.38 7.00 6.62 6.24
25 9.71 8.18 10.28 8.71 10.56 8.62 10.87 8.54 11.49 9.03 12.12 8.83 -3.4 -4 7.53 7.51 7.49 7.11 6.74
30 9.44 8.08 10.00 8.61 10.28 8.53 10.59 8.45 11.21 8.94 1.8 1 8.55 8.52 8.06 7.45 6.99
35 9.05 7.93 9.68 8.49 10.00 8.43 10.30 8.36 10.90 8.85 4.9 4 10.28 10.14 9.33 8.47 7.84
40 8.45 7.70 9.15 8.31 9.50 8.26 9.78 8.19 10.34 8.69 7.0 6 11.35 11.27 11.20 10.92 10.40
43 8.00 7.53 8.72 8.16 9.08 8.12 9.40 8.07 10.05 8.61 11.2 10 12.19 12.10 12.02 11.73 10.69
PJR002Z391
Model FDUM125VNPVD Indoor unit FDUM60VD (2 units) Outdoor unit FDC125VN
Model FDUM125VSPVD Indoor unit FDUM60VD (2 units) Outdoor unit FDC125VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 8.62 8.14 7.67 7.19 6.88
20 12.31 9.40 12.97 9.90 13.30 9.79 13.66 9.68 14.38 10.13 15.10 9.86 -9.6 -10 9.25 9.22 8.75 8.28 7.81
25 12.05 9.30 12.71 9.81 13.03 9.69 13.39 9.58 14.11 10.04 14.83 9.78 -3.4 -4 9.41 9.39 9.36 8.89 8.42
30 11.79 9.19 12.44 9.71 12.77 9.60 13.13 9.50 13.84 9.96 1.8 1 10.68 10.65 10.08 9.32 8.74
35 11.31 9.00 12.10 9.58 12.50 9.50 12.86 9.41 13.58 9.88 4.9 4 12.85 12.68 11.74 10.58 9.80
40 10.56 8.70 11.44 9.34 11.88 9.29 12.23 9.20 12.93 9.69 7.0 6 14.19 14.09 14.00 13.65 13.00
43 10.00 8.49 10.90 9.15 11.35 9.11 11.76 9.04 12.57 9.58 11.2 10 15.16 15.06 14.97 14.66 13.36
- 168 -
PJR002Z391
PJR002Z391
- 169 -
PJR002Z391
PJD001Z306
Model FDU100VNVD Indoor unit FDU100VD Outdoor unit FDC100VN
Model FDU100VSVD Indoor unit FDU100VD Outdoor unit FDC100VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 6.89 6.51 6.13 5.75 5.50
20 9.98 8.22 10.55 8.73 10.84 8.64 11.15 8.55 11.78 9.02 12.41 8.81 -9.6 -10 7.40 7.38 7.00 6.62 6.24
25 9.71 8.12 10.28 8.64 10.56 8.55 10.87 8.46 11.49 8.94 12.12 8.74 -3.4 -4 7.53 7.51 7.49 7.11 6.74
30 9.44 8.01 10.00 8.54 10.28 8.45 10.59 8.37 11.21 8.86 1.8 1 8.55 8.52 8.06 7.45 6.99
35 9.05 7.86 9.68 8.43 10.00 8.36 10.30 8.28 10.90 8.77 4.9 4 10.28 10.14 9.33 8.47 7.84
40 8.45 7.64 9.15 8.24 9.50 8.20 9.78 8.12 10.34 8.61 7.0 6 11.35 11.27 11.20 10.92 10.40
43 8.00 7.47 8.72 8.10 9.08 8.06 9.40 8.00 10.05 8.53 11.2 10 12.19 12.10 12.02 11.73 10.69
PJD001Z306
Model FDU125VNVD Indoor unit FDU125VD Outdoor unit FDC125VN
Model FDU125VSVD Indoor unit FDU125VD Outdoor unit FDC125VS
Cool Mode Heat Mode
Indoor air temperature Outdoor Indoor air temperature
Outdoor air temp.
23℃DB 26℃DB 27℃DB 28℃DB 31℃DB 33℃DB ℃DB
air temp.
16℃WB 18℃WB 19℃WB 20℃WB 22℃WB 24℃WB ℃DB ℃WB 16 18 20 22 24
℃DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -14.7 -15 8.62 8.14 7.67 7.19 6.88
20 12.31 10.15 12.97 10.76 13.30 10.65 13.66 10.53 14.38 11.10 15.10 10.82 -9.6 -10 9.25 9.22 8.75 8.28 7.81
25 12.05 10.05 12.71 10.67 13.03 10.55 13.39 10.44 14.11 11.02 14.83 10.75 -3.4 -4 9.41 9.39 9.36 8.89 8.42
30 11.79 9.95 12.44 10.58 12.77 10.47 13.13 10.36 13.84 10.94 1.8 1 10.68 10.65 10.08 9.32 8.74
35 11.31 9.77 12.10 10.46 12.50 10.38 12.86 10.27 13.58 10.86 4.9 4 12.85 12.68 11.74 10.58 9.80
40 10.56 9.48 11.44 10.23 11.88 10.17 12.23 10.08 12.93 10.68 7.0 6 14.19 14.09 14.00 13.65 13.00
43 10.00 9.27 10.90 10.04 11.35 10.00 11.76 9.93 12.57 10.58 11.2 10 15.16 15.06 14.97 14.66 13.36
- 170 -
PJD001Z306
PJD001Z306
PJD001Z306
Note(1) These data show average statuses.
Depending on the system control, there may be ranges where the operation is not conducted continuously.
(2) Capacities are based on the following conditions.
Corresponding refrigerant piping length :7.5m
Level difference of Zero.
(3) Symbols are as follows.
TC : Total cooling capacity (kW)
SHC : Sensible heat capacity (kW)
HC : Heating capacity (kW)
- 171 -
1.9.2 Correction of cooling and heating capacity in relation to air flow rate control
(fan speed)
Fan speed P-Hi or Hi 1
( )
Me Lo
Coefficient 1.00 0.97 0.95
Note (1) Models FDU only.
1.9.3 Correction of cooling and heating capacity in relation to one way length of
refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
(1) Models 40~60
Equivalent piping length(1) (m) 7.5 10 15 20 25 30 35
• Equivalent Length =Actual Length + (Equivalent bend length x number of bends in the piping.)
Equivalent length per bend.
Gas Pipe Diameter (mm) φ12.7 φ15.88 φ19.05 φ22.22 φ25.4 φ28.58
Equivalent Bend Length 0.20 0.25 0.30 0.35 0.40 0.45
- 172 -
1.9.4 Height difference between the indoor unit and outdoor unit
When the outdoor unit is located below indoor units in cooling mode, or when the outdoor unit is located above indoor units in
heating mode, the correction coefficient mentioned in the below table should be subtracted from the value in the above table.
Max. vertical height difference Outdoor unit is higher 20m Outdoor unit is higher 30m
Outdoor unit is lower 20m Outdoor unit is lower 15m
Notes (1) Values in the table indicate the one way piping length between the indoor and outdoor units.
(2) When φ22.22 gas pipe is applied to 200 and 250, maximum one way length is limited to 35m.
Example : The net cooling capacity of the model FDUM100VNVD with the air flow “High”, the piping length of 15m, the outdoor unit
located 5m lower than the indoor unit, indoor wet-bulb temperature at 19.0℃ and outdoor dry-bulb temperature 35℃ is
Net cooling capacity = 10.0 × 1.00 × (0.978 - 0.01) .=. 9.7kW
Net cooling total capacity Air flow : High Height diff. :5m
of FDUM100VNVD shown in table (1.9.2) (Outdoor unit : below)
(Outdoor temp. : 35℃DB shown in table 1.9.4
Indoor temp. : 19℃WB) Piping length :15m
shown in table 1.9.1 (Gas pipe size is φ15.88)
shown in table 1.9.3
- 173 -
- 174 -
JA012D786
JA012D781 ① Before installation ③ Preparation before installation
l Install correctly according to the installation manual. l If suspension bolt becomes longer, do reinforcement of earthquake resistant.
l Confirm the following points: For grid ceiling
Unit type/Power supply specification Pipes/Wires/Small parts Accessory items When suspension bolt length is over 500mm, or the gap between the ceiling and roof is over
700mm, apply earthquake resistant brace to the bolt.
Accessory itme In case the unit is hanged directly from the slab and is installed on the ceiling plane which has
For unit hanging For refrigerant pipe For draom pipe
enough strength.
Flat washer Level gauge
Pipe cover(big)
Pipe cover
Strap Pipe cover(big) Pipe cover(small) Drain hose Hose clamp
When suspension bolt length is over 1000mm, apply the earthquake resistant brace to the bolt.
H*NQSPQFSFBSUIDPVME
*NQSPQFSFBSUIDPVME (M10) (Insulation) (small)
l Prepare four (4) sets of suspension bolt, nut and spring washer (M10 or M8) on site.
iring. Improper
Ceiling opening, Suspension bolts pitch, Pipe position
8 4 1 1 4 1 1 1 1
For adjustment For heat For heat For heat For heat
EJTDPOOFDUBMM For unit hanging in hoisting in the insulation insulation
For pipe cover
fixing
insulation insulation
For drain pipe
connecting
For drain hose
mounting 530 (Suspension bolts pitch) F Decorative panel
unit's main body of gas pipe of liquid tube of drain socket of drain socket
326
350
etc.) or Areas where the indoor unit can deliver hot and cold wind sufficiently. Suggest to the user to use
nBNNBCMFHBT TVDI
ed, or volatile a circulator if the ceiling height is over 3m to avoid warm air being accumulated on the ceiling.
556
TUBODFTBSFIBOEMFE
67
TDPVMEDBVTFmSF Areas where there is enough space to install and service. Control Air return
35
185 box Air supply grille
s could cause fire. Areas where it can be drained properly. Areas where drain pipe descending slope can be taken. D
VBM 190 223
21 □413
Areas where there is no obstruction of airflow on both air return grille and air supply port. 200 48 □700
OQMBDF
QMBDF Drain hose piece
Areas where fire alarm will not be accidentally activated by the air conditioner. (Accessory)
or precision Areas where the supply air does not short-circuit. □570
(Installed on site)
140 6-φ4
Areas where it is not influenced by draft air. A B 145
325
C E
60 Holes for
tapping screws
QSFDJTJPO Areas not exposed to direct sunlight.
88
Hole
etic wave or Areas where dew point is lower than around 28°C and relative humidity is lower than 80%.
140
248
This indoor unit is tested under the condition of JIS (Japan Industrial Standard) high humidity
210
192
100
132
88
PSIJHIIBSNPOJDT
nt, or condition and confirmed there is no problem. However, there is some risk of condensation drop 100
45 or more
breakdown. Or the
PSUFMFDPNNVOJDBUJPO if the air conditioner is operated under the severer condition than mentioned above.
35
Hanger plate for F
suspension bolt
ruct their medical
DPOEJUJPOFSNJHIU If there is a possibility to use it under such a condition, attach additional insulation of 10 to
WJUZPSDBVTFKBNNJOH
JUZPSDBVTFKBNNJOH 20mm thick for entire surface of indoor unit, refrigeration pipe and drain pipe.
Areas where TV and radio stays away more than 1m. (It could cause jamming and noise.)
Areas where any items which will be damaged by getting wet are not placed such as food, table
DTPSTQFDJBMTQSBZTBSF
wares, server, or medical equipment under the unit. ④ Installation of indoor unit
TPSTQFDJBMTQSBZTBSF Areas where there is no influence by the heat which cookware generates.
Areas where not exposed to oil mist, powder and/or steam directly such as above fryer. Work procedure
s, chloride gas,
IBTCFBDI
Areas where lighting device such as fluorescent light or incandescent light doesn’t affect the 1. This units is designed for 2 x 2 grid ceiling.
FNJTBGGFDUFECZ
NJTBGGFDUFECZ operation. If necessary, please detach the T bar temporarily before you install it.
(A beam from lighting device sometimes affects the infrared receiver for the wireless remote If it is installed on a ceiling other than 2 x 2 grid ceiling, provide an inspection port on the control box
controller and the air conditioner might not work properly.) side.
EPPSVOJU k Check if the place where the air conditioner is installed can hold the weight of the unit. If it is not 2. Arrange the suspension bolt at the right position (530mm×530mm).
TFBDIMJNJUBUJPO
FBDIMJNJUBUJPO
able to hold, reinforce the structure with boards and beams strong enough to hold it. If the strength 3. Make sure to use four suspension bolts and fix them so as to be able to hold 500N load.
is not enough, it could cause injury due to unit falling. 4. Ensure that the lower end of the suspension bolt should be 45mm above the ceiling plane.
JODBTFPGUIF l If there are 2 units of wireless type, keep them away for more than 5m to avoid malfunction due to Temporarily put the four lower nuts 88mm above the ceiling plane and the upper nuts on distant
JODBTFPGUIF
nditioner. cross communication. place from the lower nuts in order not to obstruct hanging the indoor unit or adjust the indoor unit
QMBDFEXJUIJON
, and it damages m When plural indoor units are installed nearby, keep them away for more than 4m. position, and then hang the indoor unit.
Control box
fter a long Space for installation and service
EJUJPOFS T bar Ceiling
BHFTVTFSTCFMPOHJOHT
l When it is not possible to keep enough space between indoor unit and wall or between indoor units, panel
close the air supply port where it is not possible to keep space and confirm there is no short circuit
MPOHQFSJPEPGVTF
done near the
of airflow.
l Install the indoor unit at a height of more than 2.5m above the floor.
n and leakage of
EPOFOFBSUIFVOJU
5. Adjust the indoor unit position after hanging it by inserting the level gauge attached on the package
BOEMFBLBHFPGXBUFS
ual. 4000mm or more into the air supply port and checking if the gap between the ceiling plane and the indoor unit is
s belongings. appropriate. In order to adjust the indoor unit position, adjust the lower nuts while the upper nuts are
BM
gas is
CFMPOHJOHT
Indoor unit Indoor unit put on distant place. Confirm there is no backlash between the hanger plate for suspension bolt and
the lower nut and washer.
PPSVOJU
ety. Drain piping
FmDJFODZPGPYZHFO
UP Suspension bolt
utdoor unit. Ceiling Refrigerant piping
deficiency of
SJHFSBOUQJQJOHXPSL Wall surface
1000mm or more
Nut (upper)
MBDLPGPYZHFODBO Decorative panel 2500mm or more
100, not to
1000mm or more Flat washer
OPUUPNBLFUSBQT
OPUUPNBLFUSBQT
Obstacle
on and Spring washer
OBOENBJOUFOBODF
BOENBJOUFOBODF Nut (lower)
e water. Floor 88mm
XBUFS
aluables. 45mm
VBCMFT
BCMFT Level gauge
animals.
OJNBMT
d fire. Instruct the Ceiling surface
SF*OTUSVDUUIFVTFSUP
Use level gauges as Use level gauges as
reference, adjust the reference, adjust the
bing place, moving bottom to the face of bottom to the face of
30
30
QMBDF
NPWJOHUIFVOJU
QMBDF
NPWJOHUIFVOJU the indoor unit. the indoor unit.
Diffuser Diffuser
Level gauge
(insulation)
T-bar Level gauge Ceiling panel T-bar
Ceiling panel
(insulation)
When the ceiling panel comes below the T
bar, align the bottom of the level gauge to
the lower face of the ceiling panel.
Correct Wrong
and it could cause
DBVTFBCVSOPSGSPTUCJUF
DBVTFBCVSOPSGSPTUCJUF
Unit Unit
Touch the nut (lower) and Play is left between the fixture
washer without any play and the nut (lower) and washer.
- 175 -
inflammable gas is generated. Toxic gas would flow into the room and it would cause serious
damage to user’s health and safety (some poisoning or deficiency of oxygen). In addition, it may
cause corrosion of heat exchanger and bad smell.
l Connect the pipe securely to avoid water leakage from the joint.
l Insulate the pipe properly to avoid condensation drop.
Joint for VP-20
l Check if the water can flow out properly from both the drain outlet on the indoor unit and the end of
(Prepare on site)
the drain pipe after installation.
l Make sure to make descending slope of greater than 1/100 and do not make up-down bend and/or
trap in the midway. In addition, do not put air vent on the drain pipe. Check if water is drained
out properly from the pipe during commissioning. Also, keep sufficient space for inspection and
maintenance.
- 176 -
e water
Power source side terminal block
Earth
e Wiring between indoor
and outdoor unit
Remote controller line
Wiring clamp
VP-30 or bigger
er than 1/100
Signal side terminal block
otherwise it may cause
VRF (KX) series
pe cover (small size),
clamps and part of the 6
gapless. 6
PJA012D786
PJA012D781
- 177 -
PJA012D783 a
- 178 -
- 179 -
- 180 -
- 181 -
- 182 -
- 183 -
PJF012D003A A
- 184 -
- 185 -
- 186 -
- 187 -
- 188 -
- 189 -
● 3FBEUIFi4"'&5:13&$"65*0/4wDBSFGVMMZmSTUPGBMMBOEUIFOTUSJDUMZGPMMPXJUEVSJOHUIFJOTUBMMBUJPOXPSL 6TJOHUIFJODPSSFDUPOFDPVMEDBVTFUIFTZTUFNGBJMVSFBOEmSF
JOPSEFSUPQSPUFDUZPVSTFMG ● %POPUVTFBOZNBUFSJBMTPUIFSUIBOBGVTFPGDPSSFDUDBQBDJUZXIFSFBGVTFTIPVMECFVTFE
● 5IFQSFDBVUJPOBSZJUFNTNFOUJPOFECFMPXBSFEJTUJOHVJTIFEJOUPUXPMFWFMT
BOE
$"65*0/ $POOFDUJOHUIFDJSDVJUCZXJSFPSDPQQFSXJSFDPVMEDBVTFVOJUGBJMVSFBOEmSF
8SPOHJOTUBMMBUJPOXPVMEDBVTFTFSJPVTDPOTFRVFODFTTVDIBTJOKVSJFTPSEFBUI ● %POPUJOTUBMMUIFJOEPPSVOJUOFBSUIFMPDBUJPOXIFSFUIFSFJTQPTTJCJMJUZPGnBNNBCMFHBTMFBLBHFT 'PSIFBUJOTVMBUJPO 'PSIFBUJOTVMBUJPO
$"65*0/ 8SPOHJOTUBMMBUJPONJHIUDBVTFTFSJPVTDPOTFRVFODFTEFQFOEJOHPODJSDVNTUBODFT *GUIFHBTMFBLTBOEHBUIFSTBSPVOEUIFVOJU
JUDPVMEDBVTFmSF PGHBTQJQF PGMJRVJEUVCF
・"SFBTXIFSFO
r -PDBUJPOTXIFSFBOFRVJQNFOUBGGFDUFECZIJHIIBSNPOJDTJTQMBDFE 57TFUPSSBEJPSFDFJWFSJTQMBDFEXJUIJON
・"SFBTXIFSFM
●%POPUNJYBJSJOUPUIFDPPMJOHDZDMFPOJOTUBMMBUJPOPSSFNPWBMPGUIFBJSDPOEJUJPOFS
r -PDBUJPOTXIFSFESBJOBHFDBOOPUSVOPGGTBGFMZ UIFPQFSBUJPO
*GBJSJTNJYFEJO
UIFQSFTTVSFJOUIFDPPMJOHDZDMFXJMMSJTFBCOPSNBMMZBOENBZDBVTFFYQMPTJPOBOEJOKVSJFT
*UDBOBGGFDUQFSGPSNBODFPSGVODUJPOBOEFUD "CFBNGSPN
●#FTVSFUPIBWFUIFFMFDUSJDBMXJSJOHXPSLEPOFCZRVBMJmFEFMFDUSJDBMJOTUBMMFS
BOEVTFFYDMVTJWFDJSDVJU ●%POPUQVUBOZWBMVBCMFTXIJDIXJMMCSFBLEPXOCZHFUUJOHXFUVOEFSUIFBJSDPOEJUJPOFS DPOUSPMMFSBOE
1PXFSTPVSDFXJUIJOTVGmDJFOUDBQBDJUZBOEJNQSPQFSXPSLDBODBVTFFMFDUSJDTIPDLBOEmSF $POEFOTBUJPODPVMEESPQXIFOUIFSFMBUJWFIVNJEJUZJTIJHIFSUIBOPSESBJOQJQFJTDMPHHFE
BOEJUEBNBHFTVTFSTCFMPOHJOHT ②$IFDLJGUIFQMBD
●6TFTQFDJmFEXJSFGPSFMFDUSJDBMXJSJOH
GBTUFOUIFXJSJOHUPUIFUFSNJOBMTFDVSFMZ
BOEIPMEUIFDBCMFTFDVSFMZJO ●%POPUVTFUIFCBTFGSBNFGPSUIFPVUEPPSVOJUXIJDIJTDPSSPEFEPSEBNBHFEBGUFSBMPOHQFSJPEPGVTF OPUBCMFUPIPME
S
PSEFSOPUUPBQQMZVOFYQFDUFETUSFTTPOUIFUFSNJOBM *UDPVMEDBVTFUIFVOJUGBMMJOHEPXOBOEJOKVSZ TUSFOHUIJTOPUFO
-PPTFDPOOFDUJPOTPSIPMEDPVMESFTVMUJOBCOPSNBMIFBUHFOFSBUJPOPSmSF ●1BZBUUFOUJPOOPUUPEBNBHFUIFESBJOQBOCZXFMETQVUUFSXIFOCSB[JOHXPSLJTEPOFOFBSUIFVOJU 4QBDFGPSJOTUBMMBUJP
●"SSBOHFUIFFMFDUSJDBMXJSFTJOUIFDPOUSPMCPYQSPQFSMZUPQSFWFOUUIFNGSPNSJTJOH'JUUIFMJEPGUIFTFSWJDFT *GTQVUUFSFOUFSFEJOUPUIFVOJUEVSJOHCSB[JOHXPSL
JUDPVMEDBVTFEBNBHF QJOIPMF
PGESBJOQBOBOEMFBLBHFPGXBUFS ●.BLFJOTUBMMBUJPO
QBOFMQSPQFSUZ 5PBWPJEEBNBHJOH
LFFQUIFJOEPPSVOJUQBDLFEPSDPWFSUIFJOEPPSVOJU
*OEPPS6OJU
*NQSPQFSmUUJOHNBZDBVTFBCOPSNBMIFBUBOEmSF ●*OTUBMMUIFESBJOQJQFUPESBJOUIFXBUFSTVSFMZBDDPSEJOHUPUIFJOTUBMMBUJPONBOVBM
*OTUBMMBUJPO4QBDF
*NQSPQFSDPOOFDUJPOPGUIFESBJOQJQFNBZDBVTFESPQQJOHXBUFSJOUPSPPNBOEEBNBHJOHVTFSTCFMPOHJOHT
●$IFDLGPSSFGSJHFSBOUHBTMFBLBHFBGUFSJOTUBMMBUJPOJTDPNQMFUFE
*GUIFSFGSJHFSBOUHBTMFBLTJOUPUIFIPVTFBOEDPNFTJODPOUBDUXJUIBGBOIFBUFS
BTUPWF
PSBOPWFO
UPYJDHBTJTQSPEVDFE
●%POPUTIBSFUIFESBJOQJQFGPSJOEPPSVOJUBOE()1 (BT)FBU1VNQTZTUFN
PVUEPPSVOJU
5PYJDFYIBVTUHBTXPVMEnPXJOUPSPPNBOEJUNJHIUDBVTFTFSJPVTEBNBHF TPNFQPJTPOJOHPSEFmDJFODZPGPYZHFO
UP
●6TFUIFTQFDJmFEQJQF
nBSFOVU
BOEUPPMTGPS3" VTFSTIFBMUIBOETBGFUZ
6TJOHFYJTUJOHQBSUT 3
DPVMEDBVTFUIFVOJUGBJMVSFBOETFSJPVTBDDJEFOUEVFUPFYQMPTJPOPGUIFDPPMJOHDZDMF ●#FTVSFUPQFSGPSNBJSUJHIUOFTTUFTUCZQSFTTVSJ[JOHXJUIOJUSPHFOHBTBGUFSDPNQMFUFESFGSJHFSBOUQJQJOHXPSL
●5JHIUFOUIFnBSFOVUBDDPSEJOHUPUIFTQFDJmFENFUIPECZXJUIUPSRVFXSFODI *GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJUJOUIFFWFOUPGSFGSJHFSBOUMFBLBHFJOUIFTNBMMSPPN
MBDLPGPYZHFODBO
*GUIFnBSFOVUXFSFUJHIUFOFEXJUIFYDFTTUPSRVF
JUDPVMEDBVTFCVSTUBOESFGSJHFSBOUMFBLBHFBGUFSBMPOHQFSJPE PDDVS
XIJDIDBODBVTFTFSJPVTBDDJEFOUT
●'PSESBJOQJQFJOTUBMMBUJPO
CFTVSFUPNBLFEFTDFOEJOHTMPQFPGHSFBUFSUIBO
OPUUPNBLFUSBQT
●%POPUQVUUIFESBJOBHFQJQFEJSFDUMZJOUPESBJOBHFDIBOOFMTXIFSFQPJTPOPVTHBTFTTVDIBTTVMmEFHBTDBO BOEOPUUPNBLFBJSCMFFEJOH
PDDVS $IFDLJGUIFESBJOBHFJTDPSSFDUMZEPOFEVSJOHDPNNJTTJPOJOHBOEFOTVSFUIFTQBDFGPSJOTQFDUJPOBOENBJOUFOBODF
1PJTPOPVTHBTFTXJMMnPXJOUPUIFSPPNUISPVHIESBJOBHFQJQFBOETFSJPVTMZBGGFDUUIFVTFShTIFBMUIBOETBGFUZ5IJTDBOBMTP
DBVTFUIFDPSSPTJPOPGUIFJOEPPSVOJUBOEBSFTVMUBOUVOJUGBJMVSFPSSFGSJHFSBOUMFBL
●&OTVSFUIFJOTVMBUJPOPOUIFQJQFTGPSSFGSJHFSBUJPODJSDVJUTPBTOPUUPDPOEFOTFXBUFS
*ODPNQMFUFJOTVMBUJPODPVMEDBVTFDPOEFOTBUJPOBOEJUXPVMEXFUDFJMJOH
nPPS
BOEBOZPUIFSWBMVBCMFT
●$POOFDUUIFQJQFTGPSSFGSJHFSBUJPODJSDVJUTFDVSFMZJOJOTUBMMBUJPOXPSLCFGPSFDPNQSFTTPSJTPQFSBUFE
●%POPUJOTUBMMUIFPVUEPPSVOJUXIFSFJTMJLFMZUPCFBOFTUGPSJOTFDUTBOETNBMMBOJNBMT ③1SFQBSBUJP
*GUIFDPNQSFTTPSJTPQFSBUFEXIFOUIFTFSWJDFWBMWFJTPQFOXJUIPVUDPOOFDUJOHUIFQJQF
JUDPVMEDBVTFFYQMPTJPOBOEJOKVSJFTEVF *OTFDUTBOETNBMMBOJNBMTDPVMEDPNFJOUPUIFFMFDUSPOJDDPNQPOFOUTBOEDBVTFCSFBLEPXOBOEmSF*OTUSVDUUIFVTFSUP
UPBCOPSNBMIJHIQSFTTVSFJOUIFTZTUFN LFFQUIFTVSSPVOEJOHTDMFBO ●*GTVTQFOTJPOCP
●4UPQUIFDPNQSFTTPSCFGPSFSFNPWJOHUIFQJQFBGUFSTIVUUJOHUIFTFSWJDFWBMWFPOQVNQEPXOXPSL ●1BZFYUSBBUUFOUJPO
DBSSZJOHUIFVOJUCZIBOE ○'PSHSJEDFJMJO
*GUIFQJQFJTSFNPWFEXIFOUIFDPNQSFTTPSJTJOPQFSBUJPOXJUIUIFTFSWJDFWBMWFPQFO
BJSXPVMECFNJYFEJOUIFSFGSJHFSBUJPODJSDVJU $BSSZUIFVOJUXJUIQFPQMFJGJUJTIFBWJFSUIBOLH%POPUVTFUIFQMBTUJDTUSBQTCVUUIFHSBCCJOHQMBDF
NPWJOHUIFVOJU 8IFOUIFTVT
BOEJUDPVMEDBVTFFYQMPTJPOBOEJOKVSJFTEVFUPBCOPSNBMIJHIQSFTTVSFJOUIFDPPMJOHDZDMF CZIBOE6TFQSPUFDUJWFHMPWFTJOPSEFSUPBWPJEJOKVSZCZUIFBMVNJOVNmO JTPWFSN
●0OMZVTFQSFTDSJCFEPQUJPOBMQBSUT5IFJOTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEJOTUBMMFS ●.BLFTVSFUPEJTQPTFPGUIFQBDLBHJOHNBUFSJBM ○*ODBTFUIFV
*GZPVJOTUBMMUIFTZTUFNCZZPVSTFMG
JUDBODBVTFTFSJPVTUSPVCMFTVDIBTXBUFSMFBLT
FMFDUSJDTIPDLT
mSF -FBWJOHUIFNBUFSJBMTNBZDBVTFJOKVSZBTNFUBMTMJLFOBJMBOEXPPETBSFVTFEJOUIFQBDLBHF
XIJDIIBTFO
●%POPUSFQBJSCZZPVSTFMG"OEDPOTVMUXJUIUIFEFBMFSBCPVUSFQBJS ●%POPUPQFSBUFUIFTZTUFNXJUIPVUUIFBJSmMUFS
8IFOTVTQFOT
*UNBZDBVTFUIFCSFBLEPXOPGUIFTZTUFNEVFUPDMPHHJOHPGUIFIFBUFYDIBOHFS
*NQSPQFSSFQBJSNBZDBVTFXBUFSMFBLBHF
FMFDUSJDTIPDLPSmSF ●1SFQBSFGPVS
●%POPUUPVDIBOZCVUUPOXJUIXFUIBOET
●$POTVMUUIFEFBMFSPSBTQFDJBMJTUBCPVUSFNPWBMPGUIFBJSDPOEJUJPOFS *UDPVMEDBVTFFMFDUSJDTIPDL 4VTQFOTJPO#PMU-P
*NQSPQFSJOTUBMMBUJPONBZDBVTFXBUFSMFBLBHF
FMFDUSJDTIPDLPSmSF
●%POPUUPVDIUIFSFGSJHFSBOUQJQJOHXJUICBSFIBOETXIFOJOPQFSBUJPO
●5VSOPGGUIFQPXFSTPVSDFEVSJOHTFSWJDJOHPSJOTQFDUJPOXPSL 5IFQJQFEVSJOHPQFSBUJPOXPVMECFDPNFWFSZIPUPSDPMEBDDPSEJOHUPUIFPQFSBUJOHDPOEJUJPO
BOEJUDPVMEDBVTFBCVSOPSGSPTUCJUF
*GUIFQPXFSJTTVQQMJFEEVSJOHTFSWJDJOHPSJOTQFDUJPOXPSL
JUDPVMEDBVTFFMFDUSJDTIPDLBOEJOKVSZCZUIFPQFSBUJOHGBO ● %POPUDMFBOVQUIFBJSDPOEJUJPOFSXJUIXBUFS
●%POPUSVOUIFVOJUXIFOUIFQBOFMPSQSPUFDUJPOHVBSEBSFUBLFOPGG *UDPVMEDBVTFFMFDUSJDTIPDL
5PVDIJOHUIFSPUBUJOHFRVJQNFOU
IPUTVSGBDF
PSIJHIWPMUBHFTFDUJPODPVMEDBVTFBOJOKVSZUPCFDBVHIUJOUIFNBDIJOF
UPHFU ● %POPUUVSOPGGUIFQPXFSTPVSDFJNNFEJBUFMZBGUFSTUPQQJOHUIFPQFSBUJPO
CVSOFE
PSFMFDUSJDTIPDL #FTVSFUPXBJUGPSNPSFUIBONJOVUFT0UIFSXJTFJUDPVMEDBVTFXBUFSMFBLBHFPSCSFBLEPXO
●4IVUPGGUIFQPXFSCFGPSFFMFDUSJDBMXJSJOHXPSL ● %POPUDPOUSPMUIFPQFSBUJPOXJUIUIFDJSDVJUCSFBLFS .VMUJUZQF
*UDPVMEDBVTFmSFPSXBUFSMFBLBHF*OBEEJUJPO
UIFGBONBZTUBSUPQFSBUJPOVOFYQFDUFEMZBOEJUNBZDBVTFJOKVSZ 4JOHMFUZQF
*UDPVMEDBVTFFMFDUSJDTIPDL
VOJUGBJMVSFBOEJNQSPQFSSVOOJOH
"
- 190 -
12D319 "
○5IJTNPEFMJTNJEEMFTUBUJDEVDUFEUZQFBJSDPOEJUJPOJOHVOJU5IFSFGPSF
EPOPUVTFUIJTNPEFMGPSEJSFDU
CMPXUZQFBJSDPOEJUJPOJOHVOJU ③1SFQBSBUJPOCFGPSFJOTUBMMBUJPO DPOUJOVFE
%SBJOQJQF
DPOOFDUJPO
"DDFTTPSZJUFN
71 17$QJQF
1JQFDPWFS CJH
1JQFDPWFS TNBMM
4USBQ 1JQFDPWFS CJH
1JQFDPWFS TNBMM
%SBJOIPTF )PTFDMBNQ
)PMFGPSFMFDUSJDBMXJSJOH
CFVTFE PVUFSQBOFMIPMF
3FGSJHFSBOUHBTQJQF
'PSOBUVSBMESBJOBHF
・"SFBTXIFSFUIFJOEPPSVOJUDBOEFMJWFSIPUBOEDPMEXJOETVGmDJFOUMZ4VHHFTUUPUIFVTFS
UPVTFBDJSDVMBUPSJGUIFDFJMJOHIFJHIUJTPWFSNUPBWPJEXBSNBJSCFJOHBDDVNVMBUFEPO
FDJTJPO UIFDFJMJOH
・"SFBTXIFSFUIFSFJTFOPVHITQBDFUPJOTUBMMBOETFSWJDF
・"SFBTXIFSFJUDBOCFESBJOFEQSPQFSMZ"SFBTXIFSFESBJOQJQFEFTDFOEJOHTMPQFDBOCF )PMFGPSFMFDUSJDBMXJSJOH
PVUFSQBOFMIPMF
POEJUJPOFSNJHIU ・"SFBTXIFSFmSFBMBSNXJMMOPUCFBDDJEFOUBMMZBDUJWBUFECZUIFBJSDPOEJUJPOFS
PSDBVTFKBNNJOH ・"SFBTXIFSFUIFTVQQMZBJSEPFTOPUTIPSUDJSDVJU
・"SFBTXIFSFJUJTOPUJOnVFODFECZESBGUBJS
・"SFBTOPUFYQPTFEUPEJSFDUTVOMJHIU ④*OTUBMMBUJPOPGJOEPPSVOJU
・"SFBTXIFSFEFXQPJOUJTMPXFSUIBOBSPVOE¡$BOESFMBUJWFIVNJEJUZJTMPXFSUIBO
PSTQFDJBMTQSBZTBSF 5IJTJOEPPSVOJUJTUFTUFEVOEFSUIFDPOEJUJPOPG+*4 +BQBO*OEVTUSJBM4UBOEBSE
IJHIIVNJE
*OTUBMMBUJPO
JUZDPOEJUJPOBOEDPOmSNFEUIFSFJTOPQSPCMFN)PXFWFS
UIFSFJTTPNFSJTLPGDPOEFOTB
TCFBDI UJPOESPQ JG UIFBJS DPOEJUJPOFSJTPQFSBUFE VOEFSUIFTFWFSFSDPOEJUJPOUIBONFOUJPOFE <)BOHJOH>
JTBGGFDUFECZ BCPWF )BOHUIFVOJUVQ 4VTQFOTJPOCPMU *GUIFNFBTVSFNFOUTCFUXFFO
*GUIFSFJTBQPTTJCJMJUZUPVTFJUVOEFSTVDIBDPOEJUJPO
BUUBDIBEEJUJPOBMJOTVMBUJPOPGUP
.OVU 8BTIFSGPS. UIFVOJUBOEUIFDFJMJOHIPMFEP
NNUIJDLGPSFOUJSFTVSGBDFPGJOEPPSVOJU
SFGSJHFSBUJPOQJQFBOEESBJOQJQF
OPUNBUDIVQPOJOTUBMMBUJPO
JU
PPSVOJU ・"SFBTXIFSF57BOESBEJPTUBZTBXBZNPSFUIBON *UDPVMEDBVTFKBNNJOHBOEOPJTF
6OJU NBZCFBEKVTUFEXJUIUIFMPOH
BDIMJNJUBUJPO
・"SFBTXIFSFBOZJUFNTXIJDIXJMMCFEBNBHFECZHFUUJOHXFUBSFOPUQMBDFETVDIBTGPPE
4QSJOHXBTIFSGPS. IPMFEJOTUBMMBUJPOUPPM
UBCMFXBSFT
TFSWFS
PSNFEJDBMFRVJQNFOUVOEFSUIFVOJU
・"SFBTXIFSFUIFSFJTOPJOnVFODFCZUIFIFBUXIJDIDPPLXBSFHFOFSBUFT
DBTFPGUIF
・"SFBTXIFSFOPUFYQPTFEUPPJMNJTU
QPXEFSBOEPSTUFBNEJSFDUMZTVDIBTBCPWFGSZFS
BDFEXJUIJON
・"SFBTXIFSFMJHIUJOHEFWJDFTVDIBTnVPSFTDFOUMJHIUPSJODBOEFTDFOUMJHIUEPFTOUBGGFDU
UIFPQFSBUJPO "EKVTUNFOUGPSIPSJ[POUBMJUZ
"CFBNGSPNMJHIUJOHEFWJDFTPNFUJNFTBGGFDUTUIFJOGSBSFESFDFJWFSGPSUIFXJSFMFTTSFNPUF
○&JUIFSVTFBMFWFMWJBM
PSBEKVTUUIFMFWFMBDDPSEJOHUPUIFNFUIPECFMPX
POFS DPOUSPMMFSBOEUIFBJSDPOEJUJPOFSNJHIUOPUXPSLQSPQFSMZ
SVOJU *OTQFDUJPO
"
IPMF
DJFODZPGPYZHFO
UP ○*GUIFVOJUJTOPUMFWFMFE
JUNBZDBVTFNBMGVODUJPOTPSJOPQFSBUJPOPGUIFnPBUTXJUDI
FSBOUQJQJOHXPSL
"
DLPGPYZHFODBO ⑤%VDU8PSL
PUUPNBLFUSBQT
①"DPSSVHBUFECPBSE GPSQSFWFOUJOHTQVUUFSJOH
JTBUUBDIFEUPUIFNBJOCPEZPGUIFBJSDPOEJUJPOFS
OENBJOUFOBODF POUIFPVUMFUQPSU
%POPUSFNPWFJUVOUJMDPOOFDUJOHUIFEVDU
UFS ●"OBJSmMUFSDBOCFQSPWJEFEPOUIFNBJOCPEZPGUIFBJSDPOEJUJPOFS POUIFJOMFUQPSU
3FNPWF
MFT JUXIFODPOOFDUJOHUIFEVDUPOUIFJOMFUQPSU
NBMT ③1SFQBSBUJPOCFGPSFJOTUBMMBUJPO ②#MPXPVUEVDU
*OTUSVDUUIFVTFSUP ●6TFBDDPSEJOHUPUIFTQPUOVNCFSTTIPXOJOUIFUBCMFCFMPXXJUIBDJSDVMBSEVDU
●*GTVTQFOTJPOCPMUCFDPNFTMPOHFS
EPSFJOGPSDFNFOUPGFBSUIRVBLFSFTJTUBOU
.VMUJUZQF
○'PSHSJEDFJMJOH
4JOHMFUZQF
_
BDF
NPWJOHUIFVOJU 8IFOUIFTVTQFOTJPOCPMUMFOHUIJTPWFSNN
PSUIFHBQCFUXFFOUIFDFJMJOHBOESPPG 4QPUOVNCFST TQPU TQPUT PSTQPUT PSTQPUT
JTPWFSNN
BQQMZFBSUIRVBLFSFTJTUBOUCSBDFUPUIFCPMU
●5IFEJGGFSFODFPGUIFEVDUMFOHUITCFUXFFOFBDITQPUTIPVMECFMFTTUIBO
○*ODBTFUIFVOJUJTIBOHFEEJSFDUMZGSPNUIFTMBCBOEJTJOTUBMMFEPOUIFDFJMJOHQMBOF
●5IFEVDUTTIPVMECFBUUIFJSNJOJNVNMFOHUIT
XIJDIIBTFOPVHITUSFOHUI
●,FFQUIFCFOETUPBNJOJNVN 5IFCFOEJOHSBEJVTTIPVMECFBTMBSHFBTQPTTJCMF
8IFOTVTQFOTJPOCPMUMFOHUIJTPWFSNN
BQQMZUIFFBSUIRVBLFSFTJTUBOUCSBDFUPUIFCPMU
#BEFYBNQMF #BEFYBNQMF (PPEFYBNQMF
●1SFQBSFGPVS
TFUTPGTVTQFOTJPOCPMU
OVUBOETQSJOHXBTIFS .
POTJUF
4VTQFOTJPO#PMU-PDBUJPO
4VTQFOTJPOCPMU .
●5JFBOETFDVSFUIFDPOOFDUJPOUPUIFEVDUnBOHFPGUIFNBJOVOJUCMPXPVUIPMFXJUIBCBOE
TFBCVSOPSGSPTUCJUF 5IFO
BQQMZJOTVMBUJPONBUFSJBMTUPUIFTFDVSFEQBSUGPSEFXDPOEFOTBUJPOQSFWFOUJPO
○"EIFSFUPUIF
NFBTVSFNFOUTHJWFO ●6TFPGUIFTPVOEBOEIFBUJOTVMBUFEnFYJCMFEVDUJTSFDPNNFOEFEGPSDPOEFOTBUJPOQSFWFO
6OJU
6OEFSNN
UIFTVTQFOTJPOCPMUT
●$POEVDUUIFEVDUXPSLCFGPSFDFJMJOHBUUBDINFOU
" ③*OMFUQPSU
6/*5NN
.VMUJUZQF _
●8IFOTIJQQFEUIFJOMFUQPSUMJFTPOUIFCBDL
DBVTFJOKVSZ 4JOHMFUZQF
_
●8IFODPOOFDUJOHUIFEVDUUPUIFJOMFUQPSU
SFNPWFUIFBJSmMUFSJGJUJTmUUFEUPUIFJOMFUQPSU
"
- 191 -
⑤%VDU8PSL DPOUJOVFE
⑥3FGSJHFSBOUQJQF ⑦%SBJOQJQF
●8IFOQMBDJOHUIFJOMFUQPSUUPDBSSZPVUTVDUJPOGSPNUIFCPUUPNTJEF
VTFUIFGPMMPXJOH $BVUJPO 1SFQBSFBKPJOU
QSPDFEVSFUPSFQMBDFUIFTVDUJPOEVDUKPJOUBOEUIFCPUUPNQMBUF UIFFOENBEF
●6TFUIFOFXSFGSJHFSBOUQJQF ※"TGPSESBJOQ
8IFOSFVTJOHUIFFYJTUJOHQJQFTZTUFNGPS3PS3$
QBZBUUFOUJPOUPUIFGPMMPXJOHJUFNT ● .BLFTVSFU
・$IBOHFUIFnBSFOVUTXJUIUIFBUUBDIFEPOFT +*4DBUFHPSZ
BOESFQSPDFTTUIFnBSFQBSUT
*UNBZDBVTFU
・%POPUVTFUIJOXBMMFEQJQFT
●6TFQIPTQIPSVTEFPYJEJ[FEDPQQFSBMMPZTFBNMFTTQJQF $5TQFDJmFEJO+*4)
GPSSFGSJHFSBUJPOQJQFJOTUBMMBUJPO ● 5IFnFYJCMF
*OBEEJUJPO
NBLFTVSFUIFSFJTOPEBNBHFCPUIJOTJEFBOEPVUTJEFPGUIFQJQF
BOEOPIBSNGVM PSESBJOQJQ
●3FNPWFUIFTDSFXTXIJDIGBTUFOUIF ●3FQMBDFUIFSFNPWFECPUUPNQMBUF
TVCTUBODFTTVDIBTTVMGVS
PYJEF
EVTUPSBDPOUBNJOBOUTUVDLPOUIFQJQFT XBUFSMFBLB
CPUUPNQMBUFBOEUIFEVDUKPJOUPOUIF BOEEVDUKPJOU
JOMFUQPSUTJEFPGUIFVOJU ●%POPUVTFBOZSFGSJHFSBOUPUIFSUIBO3"
6TJOHPUIFSSFGSJHFSBOUFYDFQU3" 3FUD
NBZEFHSBEFJOTJEFSFGSJHFSBUJPOPJM"OEBJSHFUUJOHJOUP
SFGSJHFSBUJPODJSDVJUNBZDBVTFPWFSQSFTTVSFBOESFTVMUBOUJUNBZSFTVMUJOCVSTUJOH
FUD
●4UPSFUIFDPQQFSQJQFTJOEPPSTBOETFBMUIFCPUIFOEPGUIFNVOUJMUIFZBSFCSB[FEJOPSEFSUPBWPJEBOZEVTU
EJSUPS
XBUFSHFUUJOHJOUPQJQF0UIFSXJTFJUXJMMDBVTFEFHSBEBUJPOPGSFGSJHFSBUJPOPJMBOEDPNQSFTTPSCSFBLEPXO
FUD
●6TFTQFDJBMUPPMTGPS3SFGSJHFSBOU .BLFTVSFUPN
●'JUUIFEVDUKPJOXJUIBTDSFXmUUIFCPUUPNQMBUF BOEPSUSBQJOU
●.BLFTVSFUPJOTVMBUFUIFEVDUUPQSFWFOUEFXJOHPOJU 1JQJOHXPSL
●1BZBUUFOUJPO
④*OTUBMMUIFTQFDJmDCMPXPVUEVDUJOBMPDBUJPOXIFSFUIFBJSXJMM 4FDVSFXJUIBCBOE
FUD 3FGSJHFSBOUQJQF 8IFODPOEVDUJOHQJQJOHXPSL
NBLFTVSFUPBMMPXUIFQJQFT
UPCFBMJHOFEJOBTUSBJHIUMJOFGPSBUMFBTUNN
BTTIPXO QJQFBTDMPTF
DJSDVMBUFUPUIFFOUJSFSPPN ●%POPUTFUV
JOUIFMFGUJMMVTUSBUJPO 5IJTJTOFDFTTBSZGPSUIFESBJOQVNQ
●5IFEVDUDPOOFDUJPOJTTQFDJmDUPUIFDJSDVMBSEVDU
NN UPGVODUJPO
N_N
●$POEVDUUIFJOTUBMMBUJPOPGUIFTQFDJmDCMPXPVUIPMFBOEUIF #MPXPVU 4FDUJPOXIFSFBUUBDIFE
DPOOFDUJPOPGUIFEVDUCFGPSFBUUBDIJOHUIFNUPUIFDFJMJOH EVDU JOBTUSBJHIUMJOF
*OTVMBUJPONBUFSJBM
●*OTVMBUFUIFBSFBXIFSFUIFEVDUJTTFDVSFECZBCBOEGPS
8PSLQSPDFEVSF
EFXDPOEFOTBUJPOQSFWFOUJPO %FTDFOEJOHTMPQFH
⑤.BLFTVSFQSPWJEFBOJOTQFDUJPOIPMFPOUIFDFJMJOH*UJTJOEJTQFOTBCMFUPTFSWJDFFMFDSJD 3FNPWFUIFnBSFOVUBOECMJOEnBOHFTPOUIFQJQFPGUIFJOEPPSVOJU
FRVJQNFOU
NPUPS
GVODUJPOBMDPNQPOFOUTBOEDMFBOJOHPGIFBUFYDIBOHFS ※ .BLFTVSFUPMPPTFOUIFnBSFOVUXJUIIPMEJOHUIFOVUPOQJQFTJEFXJUIBTQBOOFSBOEHJWJOHUPSRVFUPUIF ●8IFOTIBSJOH
"JSDPOEJUJPOFSNBJOVOJU OVUXJUIBOPUIFSTQBOOFSJOPSEFSUPBWPJEVOFYQFDUFETUSFTTUPUIFDPQQFSQJQF
BOEUIFOSFNPWFUIFN POF VOJU
MBZ
(BTNBZDPNFPVUBUUIJTUJNF
CVUJUJTOPUBCOPSNBM
CFMPX UIF E
● 1BZBUUFOUJPOXIFUIFSUIFnBSFOVUQPQTPVU BTUIFJOEPPSVOJUJTTPNFUJNFTQSFTTVSFE
BEEJUJPO
TFMF
.BLFBnBSFPOMJRVJEQJQFBOEHBTQJQF
BOEDPOOFDUUIFSFGSJHFSBUJPOQJQFTPOUIFJOEPPSVOJU NBJOESBJOQJ
$FJMJOHTVSJBDF ※#FOEUIFQJQFXJUIBTCJHSBEJVTBTQPTTJCMFBOEEPOPUCFOEUIFQJQFSFQFBUFEMZ*OBEEJUJPO
EPOPUUXJTUBOEDSVTIUIFQJQFT *OTVMBUFUIFESB
#MPXPVUMFU 4VDUJPOEVDU
NBSLFUFEJUFN
4VDUJPOIPMF
NBSLFUFEJUFN
※%PBnBSFDPOOFDUJPOBTGPMMPXT ● #FTVSFUPJO
#MPXPVUEVDU XJUIBJSmMUFS
PQUJPOBMPSNBSLFUFEJUFN
*OTQFDUJPOIPMF ● .BLFTVSFUPMPPTFOUIFnBSFOVUXJUIIPMEJOHUIFOVUPOQJQFTJEFXJUIBTQBOOFSBOEHJWJOH DBVTFEFXD
UPSRVFUPUIFOVUXJUIBOPUIFSTQBOOFSJOPSEFSUPBWPJEVOFYQFDUFETUSFTTUPUIFDPQQFS
※ "GUFSESBJOB
QJQF
BOEUIFOSFNPWFUIFN
● 8IFOGBTUFOJOHUIFnBSFOVU
BMJHOUIFSFGSJHFSBUJPOQJQFXJUIUIFDFOUFSPGnBSFOVU
TDSFX VTFUIFQJQ
4VDUJPOHSJMMF 4VDUJPOHSJMMF
#BEFYBNQMFPGEVDUXPSL PQUJPO
-PDBMJUZ
UIFOVUGPSUJNFTCZIBOEBOEUIFOUJHIUFOJUCZTQBOOFSXJUIUIFTQFDJmFEUPSRVF IPTF
BOEm
NFOUJPOFEJOUIFUBCMFCFMPX.BLFTVSFUPIPMEUIFQJQFPOUIFJOEPPSVOJUTFDVSFMZCZB %SBJOVQ
①*GBEVDUJTOPUQSPWJEFEBUUIFTVDUJPOTJEFCVUJUJTTVCTUJUVUFEXJUIUIFTQBDFPWFSUIFDFJMJOH
TQBOOFSXIFOUJHIUFOJOHUIFOVUJOPSEFSUPBWPJEVOFYQFDUFETUSFTTPOUIFDPQQFSQJQF
IVNJEJUZJOUIFTQBDFXJMMJODSFBTFCZUIFJOnVFODFPGDBQBDJUZPGWFOUJMBUJPOGBO
TUSFOHUIPG $PWFSUIFnBSFDPOOFDUJPOQBSUPGUIFJOEPPSVOJUXJUIBUUBDIFEJOTVMBUJPONBUFSJBMBGUFSBHBT ● 5IFQPTJUJPOGPSE
XJOECMPXJOHBHBJOTUUIFPVUEPPSBJSMPVWFS
XFBUIFS SBJOZEBZ
BOEPUIFST MFBLBHFJOTQFDUJPO
BOEUJHIUFOCPUIFOETXJUIBUUBDIFETUSBQT JOTUBMMBUJPOUPBW
B
.PJTUVSFJOBJSJTMJLFMZUPDPOEFOTFPWFSUIFFYUFSOBMQMBUFTPGUIFVOJUBOEUPESJQPOUIF ●.BLFTVSFUPJOTVMBUFCPUIHBTQJQFTBOEMJRVJEQJQFTDPNQMFUFMZ UIFCBDLnPXPGX
DFJMJOH6OJUTIPVMECFPQFSBUFEVOEFSUIFDPOEJUJPOTBTMJTUFEJOUIFBCPWFUBCMFBOEXJUIJO ※ *ODPNQMFUFJOTVMBUJPONBZDBVTFEFXDPOEFOTBUJPOPSXBUFSESPQQJOH ESBJOQBOPOUIF
UIFMJNJUBUJPOPGXJOEWPMVNF8IFOUIFCVJMEJOHJTBDPODSFUFTUSVDUVSF
FTQFDJBMMZJNNF 3FGSJHFSBOUJTDIBSHFEJOUIFPVUEPPSVOJU QJQFXJUIJOUIFMJN
EJBUFMZBGUFSUIFDPOTUSVDUJPO
IVNJEJUZUFOETUPSJTFFWFOJGUIFTQBDFPWFSUIFDFJMJOHJTOPU "TGPSUIFBEEJUJPOBMSFGSJHFSBOUDIBSHFGPSUIFJOEPPSVOJUBOEQJQJOH
SFGFSUPUIFJOTUBMMBUJPO
TVCTUJUVUFEJOQMBDFPGBEVDU*OTVDIPDDBTJPO
JUJTOFDFTTBSZUPJOTVMBUFUIFFOUJSFVOJUXJUI NBOVBMBUUBDIFEUPUIFPVUEPPSVOJU
HMBTTXPPM NN
6TFBXJSFOFUPSFRVJWBMFOUUPIPMEUIFHMBTTXPPMJOQMBDF
1JQFEJBNFUFS 5JHIUFOJOHUPSRVF/rN 4USBQ "DDFTTPSZ
1JQFDPWFS "DDFTTPSZ
C
*UNBZSVOPVUUIFBMMPXBCMFMJNJUPGVOJUPQFSBUJPO &YBNQMF8IFOPVUEPPSBJSUFNQFSBUVSF φ UP
JT¡$%#
TVDUJPOBJSUFNQFSBUVSFJT¡$8#
BOEJUDPVMESFTVMUJOTVDIUSPVCMFTBT φ UP
DPNQSFTTPSPWFSMPBE
FUD φ UP
D
5IFSFJTBQPTTJCJMJUZUIBUUIFCMPXBJSWPMVNFNBZFYDFFEUIFBMMPXBCMFSBOHFPGPQFSBUJPO φ UP
EVFUPUIFDBQBDJUZPGWFOUJMBUJPOGBOPSTUSFOHUIPGXJOECMPXJOHBHBJOTUFYUFSOBMBJSMPVWFS φ UP 5IFUIJDLOFTTPGJOTVMBUJPOTIPVMECFNNPSNPSF
TPUIBUESBJOBHFGSPNCFIFBUFYDIBOHFSNBZGBMMUPSFBDIUIFESBJOQBOCVUMFBLPVUTJEF 0UIFSXJTF
UIFDPO
&YBNQMFESJQPOUPUIFDFJMJOH
XJUIDPOTFRVFOUJBMXBUFSMFBLBHFJOUIFSPPN
②*GWJCSBUJPOEBNQJOHJTOPUDPOEVDUFECFUXFFOUIFVOJUBOEUIFEVDU
BOECFUXFFOUIFVOJUBOE %SBJOUFTU
UIFTMBC
WJCSBUJPOXJMMCFUSBOTNJUUFEUPUIFEVDUBOEWJCSBUJPOOPJTFNBZPDDVS"MTP
WJCSBUJPO $POEVDUBESBJ
NBZCFUSBOTNJUUFEGSPNUIFVOJUUPUIFTMBC7JCSBUJPOEBNQJOHNVTUCFQFSGPSNFE ⑦%SBJOQJQF %VSJOHUIFUSBJM
#BEFYBNQMFPGEVDUXPSL MFBLTGSPNDPO
$BVUJPO *ODBTFPGBOF
-PVWFSUP #FTVSFUPDPO
PVUEPPSBJS
● *OTUBMMUIFESBJOQJQFBDDPSEJOHUPUIFJOTUBMMBUJPONBOVBMJOPSEFSUPESBJOQSPQFSMZ
*NQFSGFDUJPOJOESBJOJOHNBZDBVTFnPPEJOEPPSTBOEXFUUJOHUIFIPVTFIPMEHPPET
FUD 1SPDFEVSFT
/PUJDF 'PSWFOUJMBUJPO ● %POPUQVUUIFESBJOQJQFEJSFDUMZJOUPUIFEJUDIXIFSFUPYJDHBTTVDIBTTVMGVS
UIFPUIFSIBSNGVMBOE 4VQQMZBCPVU
JOnBNNBCMFHBTJTHFOFSBUFE5PYJDHBTXPVMEnPXJOUPUIFSPPNBOEJUXPVMEDBVTFTFSJPVT $IFDLUIFESBJ
"TQFDJmDDPWFSQMBUFJTBWBJMBCMFXIFODIBOHJOHUIFTQPUUPUIFTQPU
PSXIFODIBOHJOHUIF EBNBHFUPVTFSTIFBMUIBOETBGFUZ TPNFQPJTPOJOHPSEFmDJFODZPGPYZHFO
*OBEEJUJPO
JUNBZ
TQPUUPUIFTQPU DBVTFDPSSPTJPOPGIFBUFYDIBOHFSBOECBETNFMM
/PUF%POPUDIBOHFGSPNTQPUUPTQPU ● $POOFDUUIFQJQFTFDVSFMZUPBWPJEXBUFSMFBLBHFGSPNUIFKPJOU
● *OTVMBUFUIFQJQFQSPQFSMZUPBWPJEDPOEFOTBUJPOESPQ
$POOFDUJOHUIFBJSJOUBLFWFOUEVDUT
● $IFDLJGUIFXBUFSDBOnPXPVUQSPQFSMZGSPNCPUIUIFESBJOPVUMFUPOUIFJOEPPSVOJUBOEUIFFOE
4JEFGSFTIBJSJOUBLFIPMF
PGUIFESBJOQJQFBGUFSJOTUBMMBUJPO
1JQFTJEF
①'SFTI"JS*OUBLF
<GPSBJSJOUBLFEVDUPOMZ> ● .BLFTVSFUPNBLFEFTDFOEJOHTMPQFPGHSFBUFSUIBOBOEEPOPUNBLFVQEPXOCFOEBOEPSUSBQ 3FNPWFHSPNNF
○6TFUIFTJEFGSFTIBJSJOUBLFIPMF
PSTVQQMZ JOUIFNJEXBZ*OBEEJUJPO
EPOPUQVUBJSWFOUPOUIFESBJOQJQF$IFDLJGXBUFSJTESBJOFEPVUQSPQFSMZGSPN .BLFTVSFUP*OTU
UISPVHIBQBSUPGUIFTVDUJPOEVDU UIFQJQFEVSJOHDPNNJTTJPOJOH"MTP
LFFQTVGmDJFOUTQBDFGPSJOTQFDUJPOBOENBJOUFOBODF JUCBDLBGUFSUFTU
'SFTIBJSJOUBLFUISPVHIUIF
TVDUJPOEVDU 8PSLQSPDFEVSF
.BLFTVSFUPJOTFSUUIFESBJOIPTF UIFFOENPEFPGTPGU17$
UPUIFFOEPGUIFTUFQQBSUPG 0VUMJOFPGCPUUPN
ESBJOTPDLFU
1JQFTJEF
4UBHFEJGnFSODFQBSU "DDFTTPSZ
6OJU
1JQFTJEF
②"JS7FOU %SBJOIPTF
"JSWFOUIPMF
%SBJOIPTF "EIFTJPO 71 6ODPVQMJOHUIFESB
○6TFUIFTJEFBJSWFOUIPMF "DDFTTPSZ
1SFQBSFPOTJUF
BMXBZTVTFUPHFUIFSXJUIUIFBJSJOUBLF
'BTUFOUIFTDSFXXJUIJO %SBJOTPDLFU ● 6ODPVQMFUIFD
NNMFGUUPUIFOVU $MBNQ "DDFTTPSZ
1JQFDPWFS TNBMM
TVDUJPOEVDU
/PUF*GUIFVOJUJTS
○6TFUIFEVDUnBOHFGPSUIFBJSJOUBLFWFOU TPMETFQBSBUFMZGPSDJSDVMBSEVDUDPOOFDUJPO
ESBJOXBUFSXJMMCF
BOEDPOOFDUUIFDJSDVMBSEVDU UJHIUFOXJUICBOE
QJQFKPJOU
DBVTJOH
.FUBMQMBUF NN
○*OTVMBUFUIFEVDUUPQSPUFDUJUGSPNEFXDPOEFOTBUJPO
- 192 -
⑦%SBJOQJQF DPOUJOVFE
⑦%SBJOQJQF DPOUJOVFE
$/,
$/% $/, $/,
FSPGnBSFOVU
TDSFX VTFUIFQJQFDPWFS CJHTJ[F
UPDPWFSUIFQJQFDPWFS TNBMMTJ[F
DMBNQTBOEQBSUPGUIFESBJO 4JHOBMTJEF
1PXFSTPVSDFTJEF 4JHOBMTJEF
$/"$/% $/,
1PXFSTPVSDFTJEF UFSNJOBMCMPDL UFSNJOBMCMPDL 4JHOBMMJOF 4IJFMEFEDPSE
UFSNJOBMCMPDL UFSNJOBMCMPDL
IFTQFDJmFEUPSRVF IPTF
BOEmYBOEXSBQJUXJUIUBQFTUPXSBQBOENBLFKPJOUQBSUHBQMFTT
$/"
PSVOJUTFDVSFMZCZB %SBJOVQ $/ $/4 $/7 $/5 $// $/) $/;
3FNPUFDPOUSPMMFSMJOF $/* $/4 $/7 $/5 $// $/) $/;
POUIFDPQQFSQJQF
NBUFSJBMBGUFSBHBT ● 5IFQPTJUJPOGPSESBJOQJQFPVUMFUDBOCFSBJTFEVQUPNNBCPWFUIFDFJMJOH6TFFMCPXTGPS
1PXFSTPVSDF 1PXFSTPVSDF
JOTUBMMBUJPOUPBWPJEPCTUBDMFTJOTJEFDFJMJOH*GUIFIPSJ[POUBMESBJOQJQFJTUPPMPOHCFGPSFWFSUJDBMQJQF
MJOFDMBNQ MJOFDMBNQ
UIFCBDLnPXPGXBUFSXJMMJODSFBTFXIFOUIFVOJUJTTUPQQFE
BOEJUNBZDBVTFPWFSnPXPGXBUFSGSPNUIF
QJOH ESBJOQBOPOUIFJOEPPSVOJU*OPSEFSUPBWPJEPWFSnPX
LFFQUIFIPSJ[POUBMQJQFMFOHUIBOEPGGTFUPGUIF *OOFSPVUFS
3FNPUFDPOUSPMMFSMJOF
*OEPPSQPXFSTPVSDFMJOF
QJQFXJUIJOUIFMJNJUTIPXOJOUIFmHVSFCFMPX DPOOFDUJOHMJOF
&BSUI 4IJFMEFEDPSE
JQFDPWFS "DDFTTPSZ
%SBJOIPTF
NBY
⑨$IFDLMJTUBGUFSJOTUBMMBUJPO
EPXOCFOEBOEPSUSBQ 3FNPWFHSPNNFU
BJOFEPVUQSPQFSMZGSPN *GUIFFMFDUSJDBMXPSLIBTOPUCFFODPNQMFUFE
DPOOFDUBDPOWFY
.BLFTVSFUP*OTUBMM
KPJOUJOUIFESBJOQJQFDPOOFDUJPOUPQSPWJEFBXBUFSJOMFU Following table shows the maximum external static pressure for models adapted to the
'PMMPXJOHUBCMFTIPXTUIFNBYJNVNTUBUJDQSFTTVSFBUUIFPVUTJEFPGNBDIJOFGPSNPEFMTBEBQUFEUP
JOUFOBODF JUCBDLBGUFSUFTU
5IFO
DIFDLJGXBUFSMFBLTGSPNUIFQJQJOHTZTUFNBOEUIBU fan setting speed (Hi, UH). Select at site the fan setting speed according to the external
UIFGBOTFUUJOHTQFFE )J
6)
4FMFDUBUTJUFUIFGBOTFUUJOHTQFFEBDDPSEJOHUPUIFTUBUJDQSFTTVSFBU
ESBJOnPXTUISPVHIUIFESBJOQJQFOPSNBMMZ
static pressure.
UIFPVUTJEFPGNBDIJOF
OEPGUIFTUFQQBSUPG 0VUMJOFPGCPUUPNESBJOQJQJOHXPSL
)[
BOEGBTUFOUIFTDSFX ● *GUIFCPUUPNESBJOQJQJOHDBOCFEPOFXJUIB $POOFDUJOHQPSUPGUPQESBJOQJQF .VMUJUZQF _
EFTDFOEJOHHSBEJFOU
JUJTQPTTJCMFUP 4JOHMFUZQF 60,71,125,140
DPOOFDUUIFQJQFTBTTIPXOJOUIFESBXJOHCFMPX
'BO )J
4UBOEBSEIBSEQPMZWJOZM 4QFFE 6)
JOTVMBUJPO
DIMPSJEFQJQFT
$POOFDUJOHQPSUPGCPUUPNESBJOQJQFT 6OJU1B
1KPJOU 1SFQBSFPOTJUF
*OTVMBUJOHNBUFSJBM
3VCCFSTUPQQFS UPCFSFNPWFE
71 6ODPVQMJOHUIFESBJONPUPSDPOOFDUPS
$"65*0/
FTJPO 1SFQBSFPOTJUF
1$CPBSE 5BQTTIPVMEOPUCFVTFEVOEFSTUBUJDQSFTTVSFPVUTJEFUIFVOJUNFOUJPOFEBCPWF
● Taps should not be used under external static pressure mentioned above.
● 6ODPVQMFUIFDPOOFDUPS$/3GPSUIFESBJONPUPS %FXDPOEFOTBUJPONBZPDDVSXJUIUIFVOJUBOEXFUUIFDFJMJOHPSGVSOJUVSF
1JQFDPWFS TNBMM
Dew condensation may occur with the unit and wet the ceiling or furniture.
'PSJOTVMBUJPO
BTJMMVTUSBUFEJOUIFESBXJOHPOUIFSJHIU
1SFQBSFPOTJUF
● Do %POPUVTFVOEFSTUBUJDQSFTTVSFPVUTJEFUIFVOJUPG1BPSMFTT8BUFSESPQTNBZCF
not use under external static pressure of 60Pa or less. Water drops may be
/PUF*GUIFVOJUJTSVOXJUIUIFDPOOFDUPSDPVQMFE
CMPXOGSPNUIFEJGGVTFSPVUMFUPGUIFVOJUBOEXFUUIFDFJMJOHPSGVSOJUVSF
blown from the diffuser outlet of the unit and wet the ceiling or furniture.
TF
'V
ESBJOXBUFSXJMMCFEJTDIBSHFEGSPNUIFVQQFSESBJO 'PSESBJONPUPS
QJQFKPJOU
DBVTJOHBXBUFSMFBL DPOOFDUPS$/3 CMVF
PJR012D319 "
- 193 -
%6$5$0//&$5&%)*()45"5*$13&4463&"*3 PJD012D052 "
(5) Duct connected-High static pressure type (FDU)
$0/%*5*0/*/(6/*5*/45"--"5*0/."/6"-
(a) Models FDU71 ~ 140 ○5IJTNPEFMJTNJEEMF
CMPXUZQFBJSDPOEJUJP
5IJTNBOVBMJTGPSUIFJOTUBMMBUJPOPGBOJOEPPSVOJU
①#FGPSFJ
'PSFMFDUSJDBMXJSJOHXPSL *OEPPS
SFGFSUPUIFFMFDUSJDBMXJSJOHXPSLJOTUBMMBUJPONBOVBM'PSSFNPUF $"65*0/
DPOUSPMMFSJOTUBMMBUJPO
SFGFSUPUIFJOTUBMMBUJPONBOVBMBUUBDIFEUPBSFNPUFDPOUSPMMFS'PSXJSFMFTTLJU
●*OTUBMMDPSSFDUM
JOTUBMMBUJPO
SFGFSUPUIFJOTUBMMBUJPONBOVBMBUUBDIFEUPBXJSFMFTTLJU'PSFMFDUSJDBMXJSJOHXPSL ● 1FSGPSNFBSUIXJSJOHTVSFMZ
0VUEPPS
BOESFGSJHFSBOUQJQFXPSLJOTUBMMBUJPOGPSPVUEPPSVOJU
SFGFSUPUIFJOTUBMMBUJPONBOVBM %POPUDPOOFDUUIFFBSUIXJSJOHUPUIFHBTQJQF
XBUFSQJQF
MJHIUOJOHSPEBOEUFMFQIPOFFBSUIXJSJOH*NQSPQFSFBSUIDPVME ●$POmSNUIFGP
BUUBDIFEUPBOPVUEPPSVOJU DBVTFVOJUGBJMVSFBOEFMFDUSJDTIPDLEVFUPBTIPSUDJSDVJU ○6OJUUZQF1P
● &BSUIMFBLBHFCSFBLFSNVTUCFJOTUBMMFE ○1JQFT8JSFT
*GUIFFBSUIMFBLBHFCSFBLFSJTOPUJOTUBMMFE
JUDBODBVTFFMFDUSJDTIPDLT ○"DDFTTPSZJU
● 6TFUIFDJSDVJUCSFBLFSPGDPSSFDUDBQBDJUZ$JSDVJUCSFBLFSTIPVMECFUIFPOFUIBUEJTDPOOFDUBMM
4"'&5:13&$"65*0/4 QPMFTVOEFSPWFSDVSSFOU
● 3FBEUIFi4"'&5:13&$"65*0/4wDBSFGVMMZmSTUPGBMMBOEUIFOTUSJDUMZGPMMPXJUEVSJOHUIFJOTUBMMBUJPOXPSL 6TJOHUIFJODPSSFDUPOFDPVMEDBVTFUIFTZTUFNGBJMVSFBOEmSF "DDFTTPSZJUFN
JOPSEFSUPQSPUFDUZPVSTFMG ● %POPUVTFBOZNBUFSJBMTPUIFSUIBOBGVTFPGDPSSFDUDBQBDJUZXIFSFBGVTFTIPVMECFVTFE
● 5IFQSFDBVUJPOBSZJUFNTNFOUJPOFECFMPXBSFEJTUJOHVJTIFEJOUPUXPMFWFMT
BOE
$"65*0/ $POOFDUJOHUIFDJSDVJUCZXJSFPSDPQQFSXJSFDPVMEDBVTFVOJUGBJMVSFBOEmSF
8SPOHJOTUBMMBUJPOXPVMEDBVTFTFSJPVTDPOTFRVFODFTTVDIBTJOKVSJFTPSEFBUI ● %POPUJOTUBMMUIFJOEPPSVOJUOFBSUIFMPDBUJPOXIFSFUIFSFJTQPTTJCJMJUZPGnBNNBCMFHBTMFBLBHFT 1JQFDPWFS CJH
8"3/*/( *UDPVMEDBVTFUIFEBNBHFPGUIFJUFNT
●%POPUJOTUBMMOPSVTFUIFTZTUFNOFBSFRVJQNFOUTXIJDIHFOFSBUFFMFDUSPNBHOFUJDXBWFPSIJHIIBSNPOJDT
●*OTUBMMBUJPOTIPVMECFQFSGPSNFECZUIFTQFDJBMJTU &RVJQNFOUTMJLFJOWFSUFSFRVJQNFOU
QSJWBUFQPXFSHFOFSBUPS
IJHIGSFRVFODZNFEJDBMFRVJQNFOU
PSUFMFDPNNVOJDBUJPO
*GZPVJOTUBMMUIFVOJUCZZPVSTFMG
JUNBZMFBEUPTFSJPVTUSPVCMFTVDIBTXBUFSMFBLBHF
FMFDUSJDTIPDL
mSF
BOEJOKVSZEVFUPPWFSUVSO FRVJQNFOUNJHIUJOnVFODFUIFBJSDPOEJUJPOFSBOEDBVTFBNBMGVODUJPOBOECSFBLEPXO0SUIFBJSDPOEJUJPOFSNJHIU
PGUIFVOJU JOnVFODFNFEJDBMFRVJQNFOUTPSUFMFDPNNVOJDBUJPOFRVJQNFOUT
BOEPCTUSVDUUIFJSNFEJDBMBDUJWJUZPSDBVTFKBNNJOH
●*OTUBMMUIFTZTUFNDPSSFDUMZBDDPSEJOHUPUIFTFJOTUBMMBUJPONBOVBMT ●%POPUJOTUBMMUIFSFNPUFDPOUSPMMFSBUUIFEJSFDUTVOMJHIU
'PSIFBUJOTVMBUJ
*NQSPQFSJOTUBMMBUJPONBZDBVTFFYQMPTJPO
JOKVSZ
XBUFSMFBLBHF
FMFDUSJDTIPDL
BOEmSF *UDPVMEDBVTFCSFBLEPXOPSEFGPSNBUJPOPGUIFSFNPUFDPOUSPMMFS PGESBJOTPDLFU
●$IFDL UIF EFOTJUZ SFGFSFE CZ UIF GPVNVMB BDDPSEBODF XJUI *40
●%POPUJOTUBMMUIFJOEPPSVOJUBUUIFQMBDFMJTUFECFMPX
r 1MBDFTXIFSFnBNNBCMFHBTDPVMEMFBL r 1MBDFTXIFSFDPTNFUJDTPSTQFDJBMTQSBZTBSF
*G UIF EFOTJUZ FYDFFET UIF MJNJU EFOTJUZ
QMFBTF DPOTVMU UIFEFBMFSBOE JOTUBMMBUF UIF WFOUJMBUJPO TZTUFN GSFRVFOUMZVTFE
r 1MBDFTXIFSFDBSCPOmCFS
NFUBMQPXEFSPSBOZQPXEFSJTnPBUFE
r 1MBDFXIFSFUIFTVCTUBODFTXIJDIBGGFDUUIFBJSDPOEJUJPOFSBSFHFOFSBUFE r )JHIMZTBMUFEBSFBTVDIBTCFBDI
●6TFUIFHFOVJOFBDDFTTPSJFTBOEUIFTQFDJmFEQBSUTGPSJOTUBMMBUJPO
TVDIBTTVMmEFHBT
DIMPSJEFHBT
BDJE
BMLBMJPSBNNPOJDBUNPTQIFSFT r )FBWZTOPXBSFB
②4FMFDUJP
*GQBSUTVOTQFDJmFECZPVSDPNQBOZBSFVTFEJUDPVMEDBVTFXBUFSMFBLBHF
FMFDUSJDTIPDL
mSF
BOEJOKVSZEVFUPPWFSUVSOPGUIFVOJU
r 1MBDFTFYQPTFEUPPJMNJTUPSTUFBNEJSFDUMZ r 1MBDFTXIFSFUIFTZTUFNJTBGGFDUFECZ
TNPLFGSPNBDIJNOFZ
① 4FMFDUUIFTVJ
●7FOUJMBUFUIFXPSLJOHBSFBXFMMJODBTFUIFSFGSJHFSBOUMFBLTEVSJOHJOTUBMMBUJPO r 0OWFIJDMFTBOETIJQT
*GUIFSFGSJHFSBOUDPOUBDUTUIFmSF
UPYJDHBTJTQSPEVDFE r 1MBDFTXIFSFNBDIJOFSZXIJDIHFOFSBUFTIJHIIBSNPOJDTJTVTFE r "MUJUVEFPWFSN ・"SFBTXIFSF
●%POPUJOTUBMMUIFJOEPPSVOJUJOUIFMPDBUJPOTMJTUFECFMPX #FTVSFUPJOTUBMMUIFJOEPPSVOJU UPVTFBDJSDV
●*OTUBMMUIFVOJUJOBMPDBUJPOUIBUDBOIPMEIFBWZXFJHIU UIFDFJMJOH
BDDPSEJOHUPUIFJOTUBMMBUJPONBOVBMGPSFBDINPEFMCFDBVTFFBDIJOEPPSVOJUIBTFBDIMJNJUBUJPO
*NQSPQFSJOTUBMMBUJPONBZDBVTFUIFVOJUUPGBMMMFBEJOHUPBDDJEFOUT r -PDBUJPOTXJUIBOZPCTUBDMFTXIJDIDBOQSFWFOUJOMFUBOEPVUMFUBJSPGUIFVOJU ・"SFBTXIFSF
●*OTUBMMUIFVOJUQSPQFSMZJOPSEFSUPCFBCMFUPXJUITUBOETUSPOHXJOETTVDIBTUZQIPPOT
BOEFBSUIRVBLFT r -PDBUJPOTXIFSFWJCSBUJPODBOCFBNQMJmFEEVFUPJOTVGmDJFOUTUSFOHUIPGTUSVDUVSF ・"SFBTXIFSF
r -PDBUJPOTXIFSFUIFJOGSBSFESFDFJWFSJTFYQPTFEUPUIFEJSFDUTVOMJHIUPSUIFTUSPOHMJHIUCFBN JODBTFPGUIF UBLFO
*NQSPQFSJOTUBMMBUJPONBZDBVTFUIFVOJUUPGBMMMFBEJOHUPBDDJEFOUT JOGSBSFETQFDJmDBUJPOVOJU
r -PDBUJPOTXIFSFBOFRVJQNFOUBGGFDUFECZIJHIIBSNPOJDTJTQMBDFE 57TFUPSSBEJPSFDFJWFSJTQMBDFEXJUIJON
・"SFBTXIFSF
●%POPUNJYBJSJOUPUIFDPPMJOHDZDMFPOJOTUBMMBUJPOPSSFNPWBMPGUIFBJSDPOEJUJPOFS
r -PDBUJPOTXIFSFESBJOBHFDBOOPUSVOPGGTBGFMZ ・"SFBTXIFSF
*GBJSJTNJYFEJO
UIFQSFTTVSFJOUIFDPPMJOHDZDMFXJMMSJTFBCOPSNBMMZBOENBZDBVTFFYQMPTJPOBOEJOKVSJFT
*UDBOBGGFDUQFSGPSNBODFPSGVODUJPOBOEFUD ・"SFBTXIFSF
●#FTVSFUPIBWFUIFFMFDUSJDBMXJSJOHXPSLEPOFCZRVBMJmFEFMFDUSJDBMJOTUBMMFS
BOEVTFFYDMVTJWFDJSDVJU ●%POPUQVUBOZWBMVBCMFTXIJDIXJMMCSFBLEPXOCZHFUUJOHXFUVOEFSUIFBJSDPOEJUJPOFS ・"SFBTXIFSF
1PXFSTPVSDFXJUIJOTVGmDJFOUDBQBDJUZBOEJNQSPQFSXPSLDBODBVTFFMFDUSJDTIPDLBOEmSF $POEFOTBUJPODPVMEESPQXIFOUIFSFMBUJWFIVNJEJUZJTIJHIFSUIBOPSESBJOQJQFJTDMPHHFE
BOEJUEBNBHFTVTFSTCFMPOHJOHT ・"SFBTOPUFY
●6TFTQFDJmFEXJSFGPSFMFDUSJDBMXJSJOH
GBTUFOUIFXJSJOHUPUIFUFSNJOBMTFDVSFMZ
BOEIPMEUIFDBCMFTFDVSFMZJO ●%POPUVTFUIFCBTFGSBNFGPSUIFPVUEPPSVOJUXIJDIJTDPSSPEFEPSEBNBHFEBGUFSBMPOHQFSJPEPGVTF ・"SFBTXIFSF
PSEFSOPUUPBQQMZVOFYQFDUFETUSFTTPOUIFUFSNJOBM *UDPVMEDBVTFUIFVOJUGBMMJOHEPXOBOEJOKVSZ 5IJTJOEPPSV
-PPTFDPOOFDUJPOTPSIPMEDPVMESFTVMUJOBCOPSNBMIFBUHFOFSBUJPOPSmSF JUZDPOEJUJPO
●1BZBUUFOUJPOOPUUPEBNBHFUIFESBJOQBOCZXFMETQVUUFSXIFOCSB[JOHXPSLJTEPOFOFBSUIFVOJU
UJPO ESPQ JG
●"SSBOHFUIFFMFDUSJDBMXJSFTJOUIFDPOUSPMCPYQSPQFSMZUPQSFWFOUUIFNGSPNSJTJOH'JUUIFMJEPGUIFTFSWJDFT *GTQVUUFSFOUFSFEJOUPUIFVOJUEVSJOHCSB[JOHXPSL
JUDPVMEDBVTFEBNBHF QJOIPMF
PGESBJOQBOBOEMFBLBHFPGXBUFS
5PBWPJEEBNBHJOH
LFFQUIFJOEPPSVOJUQBDLFEPSDPWFSUIFJOEPPSVOJU BCPWF
QBOFMQSPQFSUZ
*GUIFSFJTBQ
*NQSPQFSmUUJOHNBZDBVTFBCOPSNBMIFBUBOEmSF ●*OTUBMMUIFESBJOQJQFUPESBJOUIFXBUFSTVSFMZBDDPSEJOHUPUIFJOTUBMMBUJPONBOVBM
NNUIJDL
*NQSPQFSDPOOFDUJPOPGUIFESBJOQJQFNBZDBVTFESPQQJOHXBUFSJOUPSPPNBOEEBNBHJOHVTFSTCFMPOHJOHT
●$IFDLGPSSFGSJHFSBOUHBTMFBLBHFBGUFSJOTUBMMBUJPOJTDPNQMFUFE ・"SFBTXIFSF
*GUIFSFGSJHFSBOUHBTMFBLTJOUPUIFIPVTFBOEDPNFTJODPOUBDUXJUIBGBOIFBUFS
BTUPWF
PSBOPWFO
UPYJDHBTJTQSPEVDFE
●%POPUTIBSFUIFESBJOQJQFGPSJOEPPSVOJUBOE()1 (BT)FBU1VNQTZTUFN
PVUEPPSVOJU ・"SFBTXIFSF
5PYJDFYIBVTUHBTXPVMEnPXJOUPSPPNBOEJUNJHIUDBVTFTFSJPVTEBNBHF TPNFQPJTPOJOHPSEFmDJFODZPGPYZHFO
UP UBCMFXBSFT
●6TFUIFTQFDJmFEQJQF
nBSFOVU
BOEUPPMTGPS3" VTFSTIFBMUIBOETBGFUZ
・"SFBTXIFSF
6TJOHFYJTUJOHQBSUT 3
DPVMEDBVTFUIFVOJUGBJMVSFBOETFSJPVTBDDJEFOUEVFUPFYQMPTJPOPGUIFDPPMJOHDZDMF ●#FTVSFUPQFSGPSNBJSUJHIUOFTTUFTUCZQSFTTVSJ[JOHXJUIOJUSPHFOHBTBGUFSDPNQMFUFESFGSJHFSBOUQJQJOHXPSL ・"SFBTXIFSF
●5JHIUFOUIFnBSFOVUBDDPSEJOHUPUIFTQFDJmFENFUIPECZXJUIUPSRVFXSFODI *GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJUJOUIFFWFOUPGSFGSJHFSBOUMFBLBHFJOUIFTNBMMSPPN
MBDLPGPYZHFODBO ・"SFBTXIFSF
*GUIFnBSFOVUXFSFUJHIUFOFEXJUIFYDFTTUPSRVF
JUDPVMEDBVTFCVSTUBOESFGSJHFSBOUMFBLBHFBGUFSBMPOHQFSJPE PDDVS
XIJDIDBODBVTFTFSJPVTBDDJEFOUT
UIFPQFSBUJPO
●'PSESBJOQJQFJOTUBMMBUJPO
CFTVSFUPNBLFEFTDFOEJOHTMPQFPGHSFBUFSUIBO
OPUUPNBLFUSBQT
"CFBNGSPN
●%POPUQVUUIFESBJOBHFQJQFEJSFDUMZJOUPESBJOBHFDIBOOFMTXIFSFQPJTPOPVTHBTFTTVDIBTTVMmEFHBTDBO BOEOPUUPNBLFBJSCMFFEJOH
PDDVS DPOUSPMMFSBOE
$IFDLJGUIFESBJOBHFJTDPSSFDUMZEPOFEVSJOHDPNNJTTJPOJOHBOEFOTVSFUIFTQBDFGPSJOTQFDUJPOBOENBJOUFOBODF
1PJTPOPVTHBTFTXJMMnPXJOUPUIFSPPNUISPVHIESBJOBHFQJQFBOETFSJPVTMZBGGFDUUIFVTFShTIFBMUIBOETBGFUZ5IJTDBOBMTP ②$IFDLJGUIFQMB
●&OTVSFUIFJOTVMBUJPOPOUIFQJQFTGPSSFGSJHFSBUJPODJSDVJUTPBTOPUUPDPOEFOTFXBUFS
DBVTFUIFDPSSPTJPOPGUIFJOEPPSVOJUBOEBSFTVMUBOUVOJUGBJMVSFPSSFGSJHFSBOUMFBL OPUBCMFUPIPME
*ODPNQMFUFJOTVMBUJPODPVMEDBVTFDPOEFOTBUJPOBOEJUXPVMEXFUDFJMJOH
nPPS
BOEBOZPUIFSWBMVBCMFT
●$POOFDUUIFQJQFTGPSSFGSJHFSBUJPODJSDVJUTFDVSFMZJOJOTUBMMBUJPOXPSLCFGPSFDPNQSFTTPSJTPQFSBUFE TUSFOHUIJTOPUF
●%POPUJOTUBMMUIFPVUEPPSVOJUXIFSFJTMJLFMZUPCFBOFTUGPSJOTFDUTBOETNBMMBOJNBMT
*GUIFDPNQSFTTPSJTPQFSBUFEXIFOUIFTFSWJDFWBMWFJTPQFOXJUIPVUDPOOFDUJOHUIFQJQF
JUDPVMEDBVTFFYQMPTJPOBOEJOKVSJFTEVF *OTFDUTBOETNBMMBOJNBMTDPVMEDPNFJOUPUIFFMFDUSPOJDDPNQPOFOUTBOEDBVTFCSFBLEPXOBOEmSF*OTUSVDUUIFVTFSUP
UPBCOPSNBMIJHIQSFTTVSFJOUIFTZTUFN LFFQUIFTVSSPVOEJOHTDMFBO
●4UPQUIFDPNQSFTTPSCFGPSFSFNPWJOHUIFQJQFBGUFSTIVUUJOHUIFTFSWJDFWBMWFPOQVNQEPXOXPSL ●1BZFYUSBBUUFOUJPO
DBSSZJOHUIFVOJUCZIBOE 4QBDFGPSJOTUBMMB
*GUIFQJQFJTSFNPWFEXIFOUIFDPNQSFTTPSJTJOPQFSBUJPOXJUIUIFTFSWJDFWBMWFPQFO
BJSXPVMECFNJYFEJOUIFSFGSJHFSBUJPODJSDVJU $BSSZUIFVOJUXJUIQFPQMFJGJUJTIFBWJFSUIBOLH%POPUVTFUIFQMBTUJDTUSBQTCVUUIFHSBCCJOHQMBDF
NPWJOHUIFVOJU ●.BLFJOTUBMMBUJ
BOEJUDPVMEDBVTFFYQMPTJPOBOEJOKVSJFTEVFUPBCOPSNBMIJHIQSFTTVSFJOUIFDPPMJOHDZDMF CZIBOE6TFQSPUFDUJWFHMPWFTJOPSEFSUPBWPJEJOKVSZCZUIFBMVNJOVNmO *OEPPS6OJU
●0OMZVTFQSFTDSJCFEPQUJPOBMQBSUT5IFJOTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEJOTUBMMFS ●.BLFTVSFUPEJTQPTFPGUIFQBDLBHJOHNBUFSJBM
*GZPVJOTUBMMUIFTZTUFNCZZPVSTFMG
JUDBODBVTFTFSJPVTUSPVCMFTVDIBTXBUFSMFBLT
FMFDUSJDTIPDLT
mSF -FBWJOHUIFNBUFSJBMTNBZDBVTFJOKVSZBTNFUBMTMJLFOBJMBOEXPPETBSFVTFEJOUIFQBDLBHF *OTUBMMBUJPO4QBDF
●%POPUSFQBJSCZZPVSTFMG"OEDPOTVMUXJUIUIFEFBMFSBCPVUSFQBJS ●%POPUPQFSBUFUIFTZTUFNXJUIPVUUIFBJSmMUFS
*UNBZDBVTFUIFCSFBLEPXOPGUIFTZTUFNEVFUPDMPHHJOHPGUIFIFBUFYDIBOHFS
*NQSPQFSSFQBJSNBZDBVTFXBUFSMFBLBHF
FMFDUSJDTIPDLPSmSF
●%POPUUPVDIBOZCVUUPOXJUIXFUIBOET
●$POTVMUUIFEFBMFSPSBTQFDJBMJTUBCPVUSFNPWBMPGUIFBJSDPOEJUJPOFS *UDPVMEDBVTFFMFDUSJDTIPDL
*NQSPQFSJOTUBMMBUJPONBZDBVTFXBUFSMFBLBHF
FMFDUSJDTIPDLPSmSF
●%POPUUPVDIUIFSFGSJHFSBOUQJQJOHXJUICBSFIBOETXIFOJOPQFSBUJPO
●5VSOPGGUIFQPXFSTPVSDFEVSJOHTFSWJDJOHPSJOTQFDUJPOXPSL 5IFQJQFEVSJOHPQFSBUJPOXPVMECFDPNFWFSZIPUPSDPMEBDDPSEJOHUPUIFPQFSBUJOHDPOEJUJPO
BOEJUDPVMEDBVTFBCVSOPSGSPTUCJUF
*GUIFQPXFSJTTVQQMJFEEVSJOHTFSWJDJOHPSJOTQFDUJPOXPSL
JUDPVMEDBVTFFMFDUSJDTIPDLBOEJOKVSZCZUIFPQFSBUJOHGBO
"
● %POPUDMFBOVQUIFBJSDPOEJUJPOFSXJUIXBUFS
●%POPUSVOUIFVOJUXIFOUIFQBOFMPSQSPUFDUJPOHVBSEBSFUBLFOPGG *UDPVMEDBVTFFMFDUSJDTIPDL
5PVDIJOHUIFSPUBUJOHFRVJQNFOU
IPUTVSGBDF
PSIJHIWPMUBHFTFDUJPODPVMEDBVTFBOJOKVSZUPCFDBVHIUJOUIFNBDIJOF
UPHFU ● %POPUUVSOPGGUIFQPXFSTPVSDFJNNFEJBUFMZBGUFSTUPQQJOHUIFPQFSBUJPO
- 194 -
12D052 "
○5IJTNPEFMJTNJEEMFTUBUJDEVDUFEUZQFBJSDPOEJUJPOJOHVOJU5IFSFGPSF
EPOPUVTFUIJTNPEFMGPSEJSFDU
CMPXUZQFBJSDPOEJUJPOJOHVOJU ③1SFQBSBUJPOCFGPSFJOTUBMMBUJPO
①#FGPSFJOTUBMMBUJPO ●*GTVTQFOTJPOCPMUCFDPNFTMPOHFS
EPSFJOGPSDFNFOUPGFBSUIRVBLFSFTJTUBOU
○'PSHSJEDFJMJOH
●*OTUBMMDPSSFDUMZBDDPSEJOHUPUIFJOTUBMMBUJPONBOVBM 8IFOUIFTVTQFOTJPOCPMUMFOHUIJTPWFSNN
PSUIFHBQCFUXFFOUIFDFJMJOHBOESPPG
QSPQFSFBSUIDPVME ●$POmSNUIFGPMMPXJOHQPJOUT JTPWFSNN
BQQMZFBSUIRVBLFSFTJTUBOUCSBDFUPUIFCPMU
○6OJUUZQF1PXFSTVQQMZTQFDJmDBUJPO ○*ODBTFUIFVOJUJTIBOHFEEJSFDUMZGSPNUIFTMBCBOEJTJOTUBMMFEPOUIFDFJMJOHQMBOFXIJDI
○1JQFT8JSFT4NBMMQBSUT IBTFOPVHITUSFOHUI
○"DDFTTPSZJUFNT 8IFOTVTQFOTJPOCPMUMFOHUIJTPWFSNN
BQQMZUIFFBSUIRVBLFSFTJTUBOUCSBDFUPUIFCPMU
DPOOFDUBMM
●1SFQBSFGPVS
TFUTPGTVTQFOTJPOCPMU
OVUBOETQSJOHXBTIFS .
POTJUF
"DDFTTPSZJUFN
FVTFE 4VTQFOTJPO#PMU-PDBUJPO
'PSSFGSJHFSBOUQJQF
FHBTMFBLBHFT 1JQFDPWFS CJH
1JQFDPWFS TNBMM
4USBQ
4VTQFOTJPOCPMU .
NBCMFHBT TVDI
DFTBSFIBOEMFE "DDFTTPSZQBSUTBSFTUPSFEJOTJEF
VMEDBVTFmSF UIJTTVDUJPOTJEF ○"EIFSFUPUIF
6OJU NFBTVSFNFOUTHJWFO
6OEFSNN
" CFMPXGPSUIFMFOHUIPG
DF 'PSIFBUJOTVMBUJPO 'PSIFBUJOTVMBUJPO 'PSQJQFDPWFSmYJOH UIFTVTQFOTJPOCPMUT
PGHBTQJQF PGMJRVJEUVCF 6/*5NN
.VMUJUZQF
4JOHMFUZQF
'PSESBJOQJQF
DJTJPO "
1JQFDPWFS CJH
1JQFDPWFS TNBMM
%SBJOIPTF )PTFDMBNQ
1JQFMPDBUJPOT 6/*5NN
IJHIIBSNPOJDT
FMFDPNNVOJDBUJPO .VMUJUZQF
OEJUJPOFSNJHIU 4JOHMFUZQF
PSDBVTFKBNNJOH
'PSIFBUJOTVMBUJPO 'PSIFBUJOTVMBUJPO 'PSESBJOQJQF 'PSESBJOIPTF
PGESBJOTPDLFU PGESBJOTPDLFU DPOOFDUJOH NPVOUJOH
TQFDJBMTQSBZTBSF
CFBDI -JRVJE
②4FMFDUJPOPGJOTUBMMBUJPOMPDBUJPOGPSUIFJOEPPSVOJU QJQJOH
TBGGFDUFECZ (BT
① 4FMFDUUIFTVJUBCMFBSFBTUPJOTUBMMUIFVOJUVOEFSBQQSPWBMPGUIFVTFS QJQJOH
"JSPVUMFUEVDU
・"SFBTXIFSFUIFJOEPPSVOJUDBOEFMJWFSIPUBOEDPMEXJOETVGmDJFOUMZ4VHHFTUUPUIFVTFS
UPVTFBDJSDVMBUPSJGUIFDFJMJOHIFJHIUJTPWFSNUPBWPJEXBSNBJSCFJOHBDDVNVMBUFEPO %SBJO
PSVOJU $POOFDUBCMFXJUI71
DIMJNJUBUJPO
UIFDFJMJOH %SBJO
・"SFBTXIFSFUIFSFJTFOPVHITQBDFUPJOTUBMMBOETFSWJDF /BUVSBMESBJOBHF71
・"SFBTXIFSFJUDBOCFESBJOFEQSPQFSMZ"SFBTXIFSFESBJOQJQFEFTDFOEJOHTMPQFDBOCF
DBTFPGUIF UBLFO .VMUJUZQF
DFEXJUIJON
・"SFBTXIFSFUIFSFJTOPPCTUSVDUJPOPGBJSnPXPOCPUIBJSSFUVSOHSJMMFBOEBJSTVQQMZQPSU 4JOHMFUZQF
・"SFBTXIFSFmSFBMBSNXJMMOPUCFBDDJEFOUBMMZBDUJWBUFECZUIFBJSDPOEJUJPOFS
・"SFBTXIFSFUIFTVQQMZBJSEPFTOPUTIPSUDJSDVJU
OFS ・"SFBTXIFSFJUJTOPUJOnVFODFECZESBGUBJS
・"SFBTOPUFYQPTFEUPEJSFDUTVOMJHIU
VTFSTCFMPOHJOHT
・"SFBTXIFSFEFXQPJOUJTMPXFSUIBOBSPVOE¡$BOESFMBUJWFIVNJEJUZJTMPXFSUIBO
HQFSJPEPGVTF
5IJTJOEPPSVOJUJTUFTUFEVOEFSUIFDPOEJUJPOPG+*4 +BQBO*OEVTUSJBM4UBOEBSE
IJHIIVNJE
JUZDPOEJUJPOBOEDPOmSNFEUIFSFJTOPQSPCMFN)PXFWFS
UIFSFJTTPNFSJTLPGDPOEFOTB -JRVJE
FOFBSUIFVOJU QJQJOH
UJPO ESPQ JG UIF BJS DPOEJUJPOFS JT PQFSBUFE VOEFS UIF TFWFSFS DPOEJUJPO UIBO NFOUJPOFE
MFBLBHFPGXBUFS
BCPWF (BT
QJQJOH
*GUIFSFJTBQPTTJCJMJUZUPVTFJUVOEFSTVDIBDPOEJUJPO
BUUBDIBEEJUJPOBMJOTVMBUJPOPGUP "JSPVUMFUEVDU
NNUIJDLGPSFOUJSFTVSGBDFPGJOEPPSVOJU
SFGSJHFSBUJPOQJQFBOEESBJOQJQF %SBJO
OHJOHT $POOFDUBCMFXJUI71
・"SFBTXIFSF57BOESBEJPTUBZTBXBZNPSFUIBON *UDPVMEDBVTFKBNNJOHBOEOPJTF
*OTUBMMBUJPO4QBDF
"EKVTUNFOUGPSIPSJ[POUBMJUZ
6/*5NN
.VMUJUZQF
○&JUIFSVTFBMFWFMWJBM
PSBEKVTUUIFMFWFMBDDPSEJOHUPUIFNFUIPECFMPX
4JOHMFUZQF
8BUFS
TVSGBDF
_NN
7JOZMIPTF
-FUUIFQJQFTJEFCFTMJHIUMZTMPQFE
DBVTFJOKVSZ
○*GUIFVOJUJTOPUMFWFMFE
JUNBZDBVTFNBMGVODUJPOTPSJOPQFSBUJPOPGUIFnPBUTXJUDI
- 195 -
PQUJPOBMPSNBSLFUFEJUFN
φ UP BEEJUJPO
TFMF
φ UP NBJOESBJOQ
#BEFYBNQMFPGEVDUXPSL φ UP 5IFUIJDLOFTTPGJOTVMBUJPOTIPVMECFNNPSNPSF *OTVMBUFUIFES
①*GBEVDUJTOPUQSPWJEFEBUUIFTVDUJPOTJEFCVUJUJTTVCTUJUVUFEXJUIUIFTQBDFPWFSUIFDFJMJOH
● #FTVSFUPJO
IVNJEJUZJOUIFTQBDFXJMMJODSFBTFCZUIFJOnVFODFPGDBQBDJUZPGWFOUJMBUJPOGBO
TUSFOHUIPG DBVTFEFXD
XJOECMPXJOHBHBJOTUUIFPVUEPPSBJSMPVWFS
XFBUIFS SBJOZEBZ
BOEPUIFST ※ "GUFSESBJOB
B
.PJTUVSFJOBJSJTMJLFMZUPDPOEFOTFPWFSUIFFYUFSOBMQMBUFTPGUIFVOJUBOEUPESJQPOUIF ⑦%SBJOQJQF VTFUIFQJQ
DFJMJOH6OJUTIPVMECFPQFSBUFEVOEFSUIFDPOEJUJPOTBTMJTUFEJOUIFBCPWFUBCMFBOEXJUIJO
UIFMJNJUBUJPOPGXJOEWPMVNF8IFOUIFCVJMEJOHJTBDPODSFUFTUSVDUVSF
FTQFDJBMMZJNNFEJ IPTF
BOEm
BUFMZBGUFSUIFDPOTUSVDUJPO
IVNJEJUZUFOETUPSJTFFWFOJGUIFTQBDFPWFSUIFDFJMJOHJTOPU $BVUJPO %SBJOVQ
TVCTUJUVUFEJOQMBDFPGBEVDU*OTVDIPDDBTJPO
JUJTOFDFTTBSZUPJOTVMBUFUIFFOUJSFVOJUXJUI ● *OTUBMMUIFESBJOQJQFBDDPSEJOHUPUIFJOTUBMMBUJPONBOVBMJOPSEFSUPESBJOQSPQFSMZ ● 5IFQPTJUJPOGPS
HMBTTXPPM NN
6TFBXJSFOFUPSFRVJWBMFOUUPIPMEUIFHMBTTXPPMJOQMBDF
*NQFSGFDUJPOJOESBJOJOHNBZDBVTFnPPEJOEPPSTBOEXFUUJOHUIFIPVTFIPMEHPPET
FUD JOTUBMMBUJPOUPBW
C
*UNBZSVOPVUUIFBMMPXBCMFMJNJUPGVOJUPQFSBUJPO &YBNQMF8IFOPVUEPPSBJSUFNQFSBUVSF ● %POPUQVUUIFESBJOQJQFEJSFDUMZJOUPUIFEJUDIXIFSFUPYJDHBTTVDIBTTVMGVS
UIFPUIFSIBSNGVMBOE UIFCBDLnPXPGX
JT ¡$ %#
TVDUJPO BJS UFNQFSBUVSF JT ¡$8#
BOE JU DPVME SFTVMU JO TVDI USPVCMFT BT JOnBNNBCMFHBTJTHFOFSBUFE5PYJDHBTXPVMEnPXJOUPUIFSPPNBOEJUXPVMEDBVTFTFSJPVT ESBJOQBOPOUIF
DPNQSFTTPSPWFSMPBE
FUD EBNBHFUPVTFSTIFBMUIBOETBGFUZ TPNFQPJTPOJOHPSEFmDJFODZPGPYZHFO
*OBEEJUJPO
JUNBZ QJQFXJUIJOUIFMJN
D
5IFSFJTBQPTTJCJMJUZUIBUUIFCMPXBJSWPMVNFNBZFYDFFEUIFBMMPXBCMFSBOHFPGPQFSBUJPO DBVTFDPSSPTJPOPGIFBUFYDIBOHFSBOECBETNFMM
EVFUPUIFDBQBDJUZPGWFOUJMBUJPOGBOPSTUSFOHUIPGXJOECMPXJOHBHBJOTUFYUFSOBMBJSMPVWFS ● $POOFDUUIFQJQFTFDVSFMZUPBWPJEXBUFSMFBLBHFGSPNUIFKPJOU
TPUIBUESBJOBHFGSPNCFIFBUFYDIBOHFSNBZGBMMUPSFBDIUIFESBJOQBOCVUMFBLPVUTJEF ● *OTVMBUFUIFQJQFQSPQFSMZUPBWPJEDPOEFOTBUJPOESPQ
&YBNQMFESJQPOUPUIFDFJMJOH
XJUIDPOTFRVFOUJBMXBUFSMFBLBHFJOUIFSPPN
● $IFDLJGUIFXBUFSDBOnPXPVUQSPQFSMZGSPNCPUIUIFESBJOPVUMFUPOUIFJOEPPSVOJUBOEUIFFOE
②*GWJCSBUJPOEBNQJOHJTOPUDPOEVDUFECFUXFFOUIFVOJUBOEUIFEVDU
BOECFUXFFOUIFVOJUBOE
PGUIFESBJOQJQFBGUFSJOTUBMMBUJPO
UIFTMBC
WJCSBUJPOXJMMCFUSBOTNJUUFEUPUIFEVDUBOEWJCSBUJPOOPJTFNBZPDDVS"MTP
WJCSBUJPO
● .BLFTVSFUPNBLFEFTDFOEJOHTMPQFPGHSFBUFSUIBOBOEEPOPUNBLFVQEPXOCFOEBOEPSUSBQ
NBZCFUSBOTNJUUFEGSPNUIFVOJUUPUIFTMBC7JCSBUJPOEBNQJOHNVTUCFQFSGPSNFE 0UIFSXJTF
UIFDPO
JOUIFNJEXBZ*OBEEJUJPO
EPOPUQVUBJSWFOUPOUIFESBJOQJQF$IFDLJGXBUFSJTESBJOFEPVUQSPQFSMZGSPN
#BEFYBNQMFPGEVDUXPSL
UIFQJQFEVSJOHDPNNJTTJPOJOH"MTP
LFFQTVGmDJFOUTQBDFGPSJOTQFDUJPOBOENBJOUFOBODF
%SBJOUFTU
$POEVDUBESBJ
-PVWFSUP 8PSLQSPDFEVSF
PVUEPPSBJS %VSJOHUIFUSBJ
.BLFTVSFUPJOTFSUUIFESBJOIPTF UIFFOENPEFPGTPGU17$
UPUIFFOEPGUIFTUFQQBSUPG MFBLTGSPNDPO
ESBJOTPDLFU *ODBTFPGBOF
'PSWFOUJMBUJPO
"UUBDIUIFIPTFDMBNQUPUIFESBJOIPTFBSPVOENNGSPNUIFFOE
BOEGBTUFOUIFTDSFX #FTVSFUPDPO
XJUIJONNMFGUUPUIFOVU
1SPDFEVSFT
●%POPUBQQMZBEIFTJWFTPOUIJTFOE
●%POPUVTFBDFUPOFCBTFEBEIFTJWFTUPDPOOFDUUPUIFESBJOTPDLFU 4VQQMZBCPVU
$IFDLUIFESBJ
⑥3FGSJHFSBOUQJQF
71
1SFQBSFPOTJUF
$BVUJPO
71
●6TFUIFOFXSFGSJHFSBOUQJQF 1SFQBSFPOTJUF
'PSJOTVMBUJPO
"DDFTTPSZ
3FNPWFHSPNNF
・$IBOHFUIFnBSFOVUTXJUIUIFBUUBDIFEPOFT +*4DBUFHPSZ
BOESFQSPDFTTUIFnBSFQBSUT .BLFTVSFUP*OTU
・%POPUVTFUIJOXBMMFEQJQFT %SBJOTPDLFU 4UBHFEJGnFSODFQBSU +PJOUGPS71 JUCBDLBGUFSUFTU
6OJU
1SFQBSFPOTJUF
●6TFQIPTQIPSVTEFPYJEJ[FEDPQQFSBMMPZTFBNMFTTQJQF $5TQFDJmFEJO+*4)
GPSSFGSJHFSBUJPOQJQFJOTUBMMBUJPO
*OBEEJUJPO
NBLFTVSFUIFSFJTOPEBNBHFCPUIJOTJEFBOEPVUTJEFPGUIFQJQF
BOEOPIBSNGVM %SBJOIPTF %SBJOIPTF
TVCTUBODFTTVDIBTTVMGVS
PYJEF
EVTUPSBDPOUBNJOBOUTUVDLPOUIFQJQFT "DDFTTPSZ
0VUMJOFPGCPUUPN
$MBNQ "DDFTTPSZ
1JQFDPWFS 'PSJOTVMBUJPO
6TJOHPUIFSSFGSJHFSBOUFYDFQU3" 3FUD
NBZEFHSBEFJOTJEFSFGSJHFSBUJPOPJM"OEBJSHFUUJOHJOUP 1SFQBSFPOTJUF
● *GUIFCPUUPNE
1JQFDPWFS TNBMM
/PUF*GUIFVOJUJTS
JOBTUSBJHIUMJOF
ESBJOXBUFSXJMMCF
QJQFKPJOU
DBVTJOH
- 196 -
⑦%SBJOQJQF DPOUJOVFE
⑦%SBJOQJQF DPOUJOVFE
$/% $/,
$/"
4IJFMEFEDPSE
$/"
※ "GUFSESBJOBHFUFTUJNQMFNFOUBUJPO
DPWFSUIFESBJOTPDLFUQBSUXJUIQJQFDPWFS TNBMMTJ[F
UIFO
$/4 $/7 $/5 $// $/) $/;
VTFUIFQJQFDPWFS CJHTJ[F
UPDPWFSUIFQJQFDPWFS TNBMMTJ[F
DMBNQTBOEQBSUPGUIFESBJO
3FNPUF
IPTF
BOEmYBOEXSBQJUXJUIUBQFTUPXSBQBOENBLFKPJOUQBSUHBQMFTT
$/3
DPOUSPMMFSMJOF
$/3
%SBJOVQ *OOFSPVUFS
DPOOFDUJOHMJOF *OEPPSQPXFSTPVSDFMJOF
&BSUI
QFSMZ ● 5IFQPTJUJPOGPSESBJOQJQFPVUMFUDBOCFSBJTFEVQUPNNBCPWFUIFDFJMJOH6TFFMCPXTGPS $MBNQGPSXJSJOHBUTJUF &BSUI $MBNQGPSXJSJOHBUTJUF
IPMEHPPET
FUD JOTUBMMBUJPOUPBWPJEPCTUBDMFTJOTJEFDFJMJOH*GUIFIPSJ[POUBMESBJOQJQFJTUPPMPOHCFGPSFWFSUJDBMQJQF
4JOHMFVOJUXJSJOHDPOOFDUJPO .VMUJVOJUXJSJOHDPOOFDUJPO
%SBJOIPTF
3JHIUPWFSIFBE
●$IFDLUIFGPMMPXJOHJUFNTBGUFSBMMJOTUBMMBUJPOXPSLDPNQMFUFE
.BYJNVNMPDBM
OEPPSVOJUBOEUIFFOE
$IFDLJG &YQFDUFEUSPVCMF $IFDL
5IFJOEPPSBOEPVUEPPSVOJUTBSFmYFETFDVSFMZ 'BMMJOH
WJCSBUJPO
OPJTF
EPXOCFOEBOEPSUSBQ +PJOUGPS71 MPDBMQSPDVSFNFOU
U 4VQQMZBCPVUDDPGXBUFSUPUIFVOJUUISPVHIUIFBJSPVUMFUCZVTJOHBGFFEXBUFSQVNQ
$IFDLUIFESBJOXIJMFDPPMJOHPQFSBUJPO
⑩5BQTFMFDUJPOPOCMPXFSVOJU XIFOUIFIJHIQFGPSNBODFmMUFSJTVTFE
*OTFSUXBUFSTVQQMZIPTF
71 GPSNNUP "UUBDIFEESBJOIPTFDMBNQ
1SFQBSFPOTJUF
TVQQMZXBUFS
1PVSXBUFSJOUPBDPOWFYKPJOU 5IFGBOUBQTGBDUPSZTFUUJOHJTi4UBOEBSEw*GZPVXBOUUPDIBOHFJUUPUIFIJHITUBUJDQSFTTVSFTFUUJOH
*OTFSUIPTFGBDJOH %SBJO
UPXBSECPUUPN
.BJO QJQJOH ZPVDBOBWBJMZPVSTFMGPGUIFGPMMPXJOHUXPNFUIPET6TFPOFPGUIFUXPNFUIPETUPTFUUIFGBOUBQ
VOJU
%SBJOTJUVBUJPODBOCFDIFDLFEXJUIUSBOTQBSFOUTPDLFU
.BLFTVSFUPQFSGPSNUIFGVODUJPOBMTFUUJOHXJUISFNPUFDPOUSPMMFS
3FNPWFHSPNNFU
*GUIFFMFDUSJDBMXPSLIBTOPUCFFODPNQMFUFE
DPOOFDUBDPOWFY
4FMFDU<*6'6/$5*0/>JOUIFGVODUJPOBMTFUUJOHNPEF
BOEDIBOHFUIFGVODUJPOOVNCFS<>
.BLFTVSFUP*OTUBMM
71 JUCBDLBGUFSUFTU KPJOUJOUIFESBJOQJQFDPOOFDUJPOUPQSPWJEFBXBUFSJOMFU <'"/41&&%4&5>
5IFO
DIFDLJGXBUFSMFBLTGSPNUIFQJQJOHTZTUFNBOEUIBU
POTJUF
6ODPVQMJOHUIFESBJONPUPSDPOOFDUPS
$"65*0/
1$CPBSE *GUIFFYUFSOBMTUBUJDQSFTTVSFJT1BPSMFTT
EPOPUTFUUIFGBOTQFFEUP)JHITQFFE
● 6ODPVQMFUIFDPOOFDUPS$/3GPSUIFESBJONPUPS *G)JHITQFFETFUUJOHJTEPOF
BJSPVUMFUTQFFEGSPNJOEPPSVOJUXJMMJODSFBTFBOE
BTJMMVTUSBUFEJOUIFESBXJOHPOUIFSJHIU
XBUFSESPQNBZCFCMPXOPVUBOEXFUUIFDFJMJOHPSUIFGVSOJUVSF
/PUF*GUIFVOJUJTSVOXJUIUIFDPOOFDUPSDPVQMFE
ESBJOXBUFSXJMMCFEJTDIBSHFEGSPNUIFVQQFSESBJO
QJQFKPJOU
DBVTJOHBXBUFSMFBL
'PSESBJONPUPS
'V
DPOOFDUPS$/3 CMVF
TF
PJD012D052 "
- 197 -
- 198 -
- 199 -
- 200 -
- 201 -
PJA012D729A A
Prepare two M4 screws (recommended length is 12-16mm) on site, and install the lower case to erectrical box.
Choose either of the following two positions in fixing it with screws.
Upper part Upper part Set SW1 to "Slave" for the slave re
Tighten the screws after
Note: The setting "Remote controller th
cutting off the thin part of controller in the position where y
Lower case Lower case screw mounting part. The air conditioner operation fol
master/ slave setting of it.
Wiring oulet Lower part Lower part The indication when power source i
Wiring oulet
When power source is turned on, the f
communication between the remote co
Connect the remote controller cord to the terminal block. Master remote controller : "
Connect the terminal of remote controller (X,Y) with the terminal of M4 screw 2 (Prepare on site)
Slave remote controller : "
indoor unit (X,Y). (X and Y are no polarity) The thin part
Upper At the same time, a mark or a number
Install the upper case as before so as not to catch up the remote controller cord, This is the software's administration nu
and tighten with the screws. Lower case
T
e
[In case of exposing cord] a
Lower
You can pull out the remote controller cord from left upper part or center upper part. Upper When remote controller cannot commu
Cut off the upper thin part of remote controller lower case with a nipper or knife, appear.
and grind burrs with a file etc. Check wiring of the indoor unit and the
Lower case
Install the lower case to the flat wall with attached two wooden screws.
Lower
- 202 -
remote controller Connect the remote controller cord to the Sheath Sheath
Upper Upper The range of temperature setting
terminal block.
Connect the terminal of remote controller (X,Y) Upper case Upper case When shipped, the range of set temperatur
Board Board
with the terminal of indoor unit (X,Y). Heating : 16~30˚C (55~86˚F)
(X and Y are no polarity) Except heating (cooling, fan, dry, aut
Wiring route is as shown in the right diagram
s not to apply unexpected stress on the Upper limit and lower limit of s
depending on the pulling out direction. Lower Lower
Wiring Wiring Upper limit setting: valid during heating
In case of pulling out from In case of pulling out from
upper left upper center Lower limit setting: valid except heating
The wiring inside the remote controller case should be within 0.3mm2 (recommended) to 0.5mm2. 79˚F).
The sheath should be peeled off inside the remote controller case. When you set upper and lower limit by t
The peeling-off length of each wire is as below.
1. When TEMP RANGE SET, remote
Pulling out from upper left Pulling out from upper center If upper limit value is set
id malfunction. X wiring : 215mm X wiring : 170mm The peeling-off length During heating, you cannot set the v
rface enough to generate condensation Y wiring : 195mm Y wiring : 190mm of sheath
mist or steam directly If lower limit value is set
Install the upper case as before so as not to catch up the remote controller cord, and tighten with During operation mode except heatin
the screws.
In case of exposing cord, fix the cord on the wall with cord clamp so as not to slack. 2. When TEMP RANGE SET, remot
If upper limit value is set
with a packaging box or bag in Installation and wiring of remote controller During heating, even if the value exc
Wiring of remote controller should use 0.3mm2 2 core wires or cables. (on-site configuration) But, the indication is the same as the
Maximum prolongation of remote controller wiring is 600 m. If lower limit value is set
pieces
If the prolongation is over 100m, change to the size below. During except heating, even if the val
d thickness in 1mm or more. But, wiring in the remote controller case should be under 0.5mm2 . Change the wire size outside
box, M4 screw (2 pieces) But, the indication is the same as the
of the case according to wire connecting. Waterproof treatment is necessary at the wire
if needed) connecting section. Be careful about contact failure. How to set upper and lower lim
100 - 200m.........................0.5mm2 2 cores 1. Stop the air-conditioner, and press
Under 300m .......................0.75mm2 2 cores seconds .
r the Under 400m .......................1.25mm2 2 cores The indication changes to "FUNCTI
500m .......................2.0mm2 2 cores
Under 600 2. Press button once, and change
3. Press (SET) button, and ent
Master/ slave setting when more than one remote controllers are used 4. Select "UPPER LIMIT " or "LOW
Screw
art A maximum of two remote controllers can be connected to one indoor unit (or one group of indoor units.) 5. Press (SET) button to fix.
6. When "UPPER LIMIT " is selecte
Switch Setting Contents
Indication: " SET UP"
Indoor units M Master remote controller Select the upper limit value with
SW1
S Slave remote controller (blinking)
Remote controller cord (no polarity) Press (SET) button to fix.
Controller cord
Upper After the fixed upper limit value
Erectrical box
(Prepare on site) Master 7. When "LOWER LIMIT " is select
Remote controller Remote controller
SW1 "Master" SW1 "Slave" Slave Board Indication: " SET UP"
Select the lower limit value with
and install the lower case to erectrical box. Lower
(blinking)
s.
Set SW1 to "Slave" for the slave remote controller. It was factory set to "Master" for shipment. Press (SET) button to fix
Tighten the screws after
Note: The setting "Remote controller thermistor enabled" is only selectable with the master remote After the fixed lower limit value d
cutting off the thin part of controller in the position where you want to check room temperature. 8. Press ON/OFF button to finish.
screw mounting part. The air conditioner operation follows the last operation of the remote controller regardless of the
master/ slave setting of it.
rews.
Lower
- 203 -
PJA012D729A
Sheath Sheath
Upper The range of temperature setting
Upper case Upper case When shipped, the range of set temperature differs depending on the operation mode as below.
Board
Heating : 16~30˚C (55~86˚F)
Except heating (cooling, fan, dry, automatic) : 18~30˚C (62~86˚F)
Upper limit and lower limit of set temperature can be changed with remote controller.
Lower
g Wiring Upper limit setting: valid during heating operation. Possible to set in the range of 20 to 30˚C (68 to 86˚F).
om In case of pulling out from
upper center Lower limit setting: valid except heating (automatic, cooling, fan, dry) Possible to set in the range of 18 to 26˚C (62 to
mm2 (recommended) to 0.5mm2. 79˚F).
. When you set upper and lower limit by this function, control as below.
1. When TEMP RANGE SET, remote controller function of function setting mode is "INDN CHANGE" (factory setting),
If upper limit value is set
The peeling-off length During heating, you cannot set the value exceeding the upper limit.
of sheath
If lower limit value is set
controller cord, and tighten with During operation mode except heating, you cannot set the value below the lower limit.
so as not to slack. 2. When TEMP RANGE SET, remote controller function of function setting mode is "NO INDN CHANGE"
If upper limit value is set
During heating, even if the value exceeding the upper limit is set, upper limit value will be sent to the indoor unit.
ables. (on-site configuration) But, the indication is the same as the temperature set.
If lower limit value is set
During except heating, even if the value lower than the lower limit is set, lower limit value will be sent to the indoor unit.
. Change the wire size outside But, the indication is the same as the temperature set.
necessary at the wire
How to set upper and lower limit value
1. Stop the air-conditioner, and press (SET) and (MODE) button at the same time for over three
seconds .
The indication changes to "FUNCTION SET ".
2. Press button once, and change to the "TEMP RANGE " indication.
3. Press (SET) button, and enter the temperature range setting mode.
used 4. Select "UPPER LIMIT " or "LOWER LIMIT " by using button.
unit (or one group of indoor units.) 5. Press (SET) button to fix.
6. When "UPPER LIMIT " is selected (valid during heating)
Contents
Indication: " SET UP" "UPPER 30˚C "
remote controller Select the upper limit value with temperature setting button . Indication example: "UPPER 26˚C "
emote controller (blinking)
Press (SET) button to fix. Indication example: "UPPER 26˚C" (Displayed for two seconds)
Upper After the fixed upper limit value displayed for two seconds, the indication will return to "UPPER LIMIT ".
7. When "LOWER LIMIT " is selected (valid during cooling, dry, fan, automatic)
Board Indication: " SET UP" "LOWER 18˚C "
Lower
Select the lower limit value with temperature setting button . Indication example: "LOWER 24˚C "
(blinking)
set to "Master" for shipment. Press (SET) button to fix. Indication for example: "LOWER 24˚C" (Displayed for two seconds)
able with the master remote After the fixed lower limit value displayed for two seconds, the indication will return to "LOWER LIMIT ".
ure. 8. Press ON/OFF button to finish.
mote controller regardless of the
- 204 -
PJA012D729A
automatically defined as following table.
Operation message
How to set function Function description: ,
e indoor unit. Function No.
1. Stop air-conditioner and press (SET) (MODE) setting description:
UN" mode
e step of air flow setting buttons at the same time for over three seconds, and the
"FUNCTION SET " will be displayed.
air flow setting
ly swing louver Fixing button
cally swing louver
of air flow setting
air flow setting 2. Press (SET) button.
7 Finishing button
3. Make sure which do you want to set, " FUNCTION "
air flow setting (remote controller function) or "I/U FUNCTION " (indoor
unit function).
4. Press or button. 2 Starting button
Selecct " FUNCTION " (remote controller function) or "I/U
TERNAL INPUT” and “06 PERMISSION / 1
FUNCTION " (indoor unit function).
e UH - Hi - Me UH - Me UH - Hi "DATA LOADING" (Indication with blinking) "DATA LOADING" (Blinking for 2 to 23 seconds to read the data)
GH SPEED". Display is changed to "01 GRILLE SET". Indication is changed to "02 FAN SPEED SET".
urs. Go to .
urs. Press or button.
ours. "No. and function"are indicated by turns on the remote [Note]
ours, then the indoor unit will be stopped by
controller function table, then you can select from them. (1) If plural indoor units are connected to a remote controller,
(For example) the indication is "I/U 000" (blinking) The lowest number of
",
4 " accordingly. the indoor unit connected is indicated.
Function No.
Function
Function No.
r temperature of indoor unit. Function
r temperature of indoor unit.
r temperature of indoor unit.
Press (SET) button.
r temperature of indoor unit. The current setting of selected function is indicated.
r temperature of indoor unit. (For example) "STANDARD" If "02 FAN SPEED SET" is
r temperature of indoor unit. Press (SET) selected.
"SET COMPLETE" will be indicated, and the setting will be
w speed.
speed.
completed.
Then after "No. and function" indication returns, Set as the Setting
erated intermittently. same procedure if you want to set continuously ,and if to
ed. finish, go to 7. Press or button.
F" is set automatically.
mistor is working.
Select the setting.
fan.
When plural indoor units are connected to a remote controller,
press the AIRCON NO. button, which allows you to go back to
FF, the fan does not perform extra operation. the indoor unit selection screen. (example "I/U 000 ")
FF, the fan perform extra operation for half an hour.
FF, the fan perform extra operation for an hour.
FF, the fan perform extra operation for six hours.
It is possible to finish by pressing ON/OFF button on the way, but unfinished change of setting is
OFF, the fan does not perform extra operation.
unavailable.
OFF,the fan perform extra operation for half an hour. During setting, if you press (RESET) button, you return to the previous screen.
OFF,the fan perform extra operation for two hours. Setting is memorized in the controller and it is saved independently of power failure.
OFF, the fan perform extra operation for six hours.
OFF, the fan perform intermittent operation for five minutes How to check the current setting
When you select from "No. and funcion" and press set button by the previous operation, the "Setting" displayed first is the current
OFF, the fan perform intermittent operation for five minutes
setting.
(But, if you select "ALL UNIT ", the setting of the lowest number indoor unit is displayed.)
is automatically defined.
- 205 -
●A
not use any refrigerant othe
A cylinder containing R410A ha
unit designed for R410A has
The processed dimension of the
• This installation manual deals with outdoor units and general installation specifications only. For indoor units, refer to the respective installation manuals supplied with the units.
Accordingly, you are required to
• When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, power ● Do not use a charge cylinder.
supply voltage and etc.) and installation spaces. ● In charging refrigerant, always t
• We recommend you to read this “SAFETY PRECAUTIONS” carefully before the installation work in order to • Keep the installation manual together with owner’s manual at a place where any user can read at any time.
gain full advantage of the functions of the unit and to avoid malfunction due to mishandling. Moreover if necessary, ask to hand them to a new user.
• The precautions described below are divided into WARNING and CAUTION . The matters with
possibilities leading to serious consequences such as death or serious personal injury due to erroneous handling
• For installing qualified personnel, take precautions in respect to themselves by using suitable protective
clothing, groves, etc., and then perform the installation works.
1. HAULAGE AND
are listed in the WARNING and the matters with possibilities leading to personal injury or damage of the • Please pay attention not to fall down the tools, etc. when installing the unit at the high position.
unit due to erroneous handling including probability leading to serious consequences in some cases are listed • If unusual noise can be heard during operation, consult the dealer. When a unit i
in CAUTION . These are very important precautions for safety. Be sure to observe all of them without fail. • Symbols which appear frequently in the text have the following meaning: CAUTION center positio
• Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the Observe instructions
operating methods as well as the maintenance methods of this equipment to the user according to the owner’s Strictly prohibited Provide proper earthing
with great care
manual. 1) Delivery
● Deliver the unit as close as
WARNING the packaging.
● When you have to unpack th
• Installation must be carried out by the qualified installer. • Tighten the flare nut by torque wrench with specified method. • Use the prescribed cables for electrical connection, tighten the
If you install the system by yourself, it may cause serious trouble such If the flare nut were tightened with excess torque, this may cause cables securely in terminal block and relieve the cables installation point, hoist the u
as water leaks, electric shocks, fire and personal injury, as a result of a burst and refrigerant leakage after a long period. correctly to prevent overloading the terminal blocks. you may not damage the un
-
system malfunction. • Do not open the operation valves for liquid line and gas line Loose connections or cable mountings can cause anomalous heat
• Install the system in full accordance with the instruction until completed refrigerant piping work, air tightness test and production or fire. 2) Portage
206 -
manual. evacuation. • Arrange the wiring in the control box so that it cannot be
Incorrect installation may cause bursts, personal injury, water leaks, If the compressor is operated in state of opening operation valves pushed up further into the box. Install the service panel ● The right hand side of the un
electric shocks and fire. before completed connection of refrigerant piping work, air can be correctly. A person carrying the right h
• Be sure to use only for household and residence. sucked into refrigerant circuit, which can cause bust or personal injury Incorrect installation may result in overheating and fire. the left hand side must hold
If this appliance is installed in inferior environment such as machine due to anomalously high pressure in the refrigerant. • Be sure to fix up the service panels. of the unit and with his left
shop and etc., it can cause malfunction. • The electrical installation must be carried out by the qualified Incorrect fixing can cause electric shocks or fire due to intrusion of
• Use the original accessories and the specified components for electrician in accordance with “the norm for electrical work” dust or water.
installation. and “national wiring regulation”, and the system must be • Be sure to switch off the power supply in the event of 3) Selection of instal
If parts other than those prescribed by us are used, It may cause connected to the dedicated circuit. installation, inspection or servicing. Be sure to select a suitable in
water leaks, electric shocks, fire and personal injury. Power supply with insufficient capacity and incorrect function done by If the power supply is not shut off, there is a risk of electric shocks, 〇 A place where it is horizon
• Install the unit in a location with good support. improper work can cause electric shocks and fire. unit failure or personal injury due to the unexpected start of fan. of the unit.
Unsuitable installation locations can cause the unit to fall and cause • Be sure to shut off the power before starting electrical work. • Stop the compressor before disconnecting refrigerant pipes in 〇 A place where it can be fr
material damage and personal injury. Failure to shut off the power can cause electric shocks, unit failure or case of pump down operation. 〇 A place where the unit is
• Ensure the unit is stable when installed, so that it can incorrect function of equipment. If disconnecting refrigerant pipes in state of opening operation valves 〇 A place where it can be fr
withstand earthquakes and strong winds. • Be sure to use the cables conformed to safety standard and before compressor stopping, air can be sucked, which can cause 〇 A place where drain water
Unsuitable installation locations can cause the unit to fall and cause cable ampacity for power distribution work. burst or personal injury due to anomalously high pressure in the 〇 A place where the unit wil
material damage and personal injury. Unconformable cables can cause electric leak, anomalous heat refrigerant circuit. 〇 A place where snow will n
• Ventilate the working area well in the event of refrigerant production or fire. • Only use prescribed optional parts. The installation must be 〇 A place where the unit ca
leakage during installation. • This appliance must be connected to main power supply by carried out by the qualified installer. radio or TV interference.
If the refrigerant comes into contact with naked flames, poisonous gas means of a circuit breaker or switch (fuse:16A) with a contact If you install the system by yourself, it can cause serious trouble such 〇 A place where good air ci
is produced. separation of at least 3mm. as water leaks, electric shocks, fire. and service of the unit saf
• Use the prescribed pipes, flare nuts and tools for R410A. 〇 A place where the unit wil
Using existing parts (for R22 or R407C) can cause the unit failure and other equipment.
serious accidents due to burst of the refrigerant circuit. 〇 A place where chemical su
harm the unit, will not be
'10 • PAC-DB-142
• Ensure that no air enters in the refrigerant circuit when the unit • Do not bundling, winding or processing for the power cord. Or, • Do not perform any change of protective device itself or its 〇
is installed and removed. do not deforming the power plug due to tread it. setup condition. at a place where it is not i
If air enters in the refrigerant circuit, the pressure in the refrigerant This may cause fire or heating. The forced operation by short-circuiting protective device of pressure 〇 A place where strong wind
circuit becomes too high, which can cause burst and personal injury. • Do not run the unit with removed panels or protections. switch and temperature controller or the use of non specified
• Do not processing, splice the power cord, or share a socket Touching rotating equipments, hot surfaces or high voltage parts can component can cause fire or burst.
with other power plugs. cause personal injury due to entrapment, burn or electric shocks. 4) Caution about sele
This may cause fire or electric shock due to defecting contact, (1) If the unit is installed in th
defecting insulation and over-current etc. The bottom plate of unit an
• Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting. 1 Install the unit on the b
that the bottom is high
CAUTION snow cover surface.
• Use the circuit breaker with sufficient breaking capacity. • Take care when carrying the unit by hand. • When perform the air conditioner operation (cooling or drying
If the breaker does not have sufficient breaking capacity, it can cause If the unit weights more than 20kg, it must be carried by two or more operation) in which ventilator is installed in the room. In this
the unit malfunction and fire. persons. Do not carry by the plastic straps, always use the carry case, using the air conditioner in parallel with the ventilator,
• Earth leakage breaker must be installed. handle when carrying the unit by hand. Use gloves to minimize the risk there is the possibility that drain water may backflow in
If the earth leakage breaker is not installed, it can cause electric of cuts by the aluminum fins. accordance with the room lapse into the negative pressure
shocks. • Dispose of any packing materials correctly. status. Therefore, set up the opening port such as incorporate
• Install isolator or disconnect switch on the power supply wiring Any remaining packing materials can cause personal injury as it the air into the room that may appropriate to ventilation (For
in accordance with the local codes and regulations. contains nails and wood. And to avoid danger of suffocation, be sure example; Open the door a little). In addition, just as above, so
• After maintenance, all wiring, wiring ties and the like, should be to keep the plastic wrapper away from children and to dispose after set up the opening port if the room lapse into negative
returned to their original state and wiring route, and the tear it up. pressure status due to register of the wind for the high rise
necessary clearance from all metal parts should be secured. • Be sure to insulate the refrigerant pipes so as not to condense apartment etc. Since drain water generate
• Secure a space for installation, inspection and maintenance the ambient air moisture on them. ● Don’t execute drain pipin
specified in the manual. Insufficient insulation can cause condensation, which can lead to piping work.]
Insufficient space can result in accident such as personal injury due to moisture damage on the ceiling, floor, furniture and any other ● Recommend setting Defr
falling from the installation place. valuables. SW3-2.]
• Do not install the unit in the locations listed below. • Do not install the outdoor unit in the locations listed below. the system, and cause malfunctions and breakdowns. The system
• Locations where carbon fiber, metal powder or any powder is floating. • Locations where discharged hot air or operating sound of the can also affect medical equipment and telecommunication equipment,
• Locations where any substances that can affect the unit such as outdoor unit can bother neighborhood. and obstruct its function or cause jamming.
sulphide gas, chloride gas, acid and alkaline can occur.
• Vehicles and ships.
• Locations where outlet air of the outdoor unit blows directly to
plants.
• Do not install the outdoor unit in a location where insects and
small animals can inhabit.
2. REFRIGERANT
• Locations where cosmetic or special sprays are often used. • Locations where vibration can be amplified and transmitted due to Insects and small animals can enter the electric parts and cause
• Locations with direct exposure of oil mist and steam such as kitchen insufficient strength of structure. damage or fire. Instruct the user to keep the surroundings clean.
and machine plant. • Locations where vibration and operation sound generated by the • Do not use the base flame for outdoor unit which is corroded
1) Restrictions on u
• Locations where any machines which generate high frequency outdoor unit can affect seriously (on the wall or at the place near bed or damaged due to long periods of operation. ● Check the following points
harmonics are used. room). Using an old and damage base flame can cause the unit falling down ● Observe the following restric
• Locations with salty atmospheres such as coastlines. • Locations where an equipment affected by high harmonics is placed and cause personal injury.
• Locations with heavy snow (If installed, be sure to provide base (TV set or radio receiver is placed within 5m). • Do not use any materials other than a fuse with the correct
flame and snow hood mentioned in the manual). • Locations where drainage cannot run off safely. rating in the location where fuses are to be used.
• Locations where the unit is exposed to chimney smoke. It can affect surrounding environment and cause a claim. Connecting the circuit with copper wire or other metal thread can M
• Locations at high altitude (more than 1000m high). • Do not install the unit near the location where leakage of cause unit failure and fire.
• Locations with ammonic atmospheres. combustible gases can occur. • Do not touch any buttons with wet hands.
• Locations where heat radiation from other heat source can affect the If leaked gases accumulate around the unit, it can cause fire. It can cause electric shocks. Elevation difference between
unit. • Do not install the unit where corrosive gas (such as sulfurous • Do not touch any refrigerant pipes with your hands when the indoor and outdoor units
• Locations without good air circulation. acid gas etc.) or combustible gas (such as thinner and system is in operation.
• Locations with any obstacles which can prevent inlet and outlet air petroleum gases) can accumulate or collect, or where volatile During operation the refrigerant pipes become extremely hot or ● The use
of the unit. combustible substances are handled. extremely cold depending the operating condition, and it can cause CAUTION Where a
• Locations where short circuit of air can occur (in case of multiple Corrosive gas can cause corrosion of heat exchanger, breakage of burn injury or frost injury. For mor
units installation). plastic parts and etc. And combustible gas can cause fire. • Do not touch the suction or aluminum fin on the outdoor unit.
• Locations where strong air blows against the air outlet of outdoor • Do not install nor use the system close to the equipment that This may cause injury.
unit. generates electromagnetic fields or high frequency harmonics. • Do not put anything on the outdoor unit and operating unit. 2) Determination of
It can cause remarkable decrease in performance, corrosion and Equipment such as inverters, standby generators, medical high This may cause damage the objects or injury due to falling to the ● Determine refrigerant pipe s
damage of components, malfunction and fire. frequency equipments and telecommunication equipments can affect object. indoor unit specifications.
Downloaded from www.Manualslib.com manuals search engine
9 Wrench key (Hexagon) [4m/m]
• Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the Observe instructions
operating methods as well as the maintenance methods of this equipment to the user according to the owner’s Strictly prohibited Provide proper earthing
with great care
manual. 1) Delivery
● Deliver the unit as close as pos
WARNING the packaging.
● When you have to unpack the u
• Installation must be carried out by the qualified installer. • Tighten the flare nut by torque wrench with specified method. • Use the prescribed cables for electrical connection, tighten the
If you install the system by yourself, it may cause serious trouble such If the flare nut were tightened with excess torque, this may cause cables securely in terminal block and relieve the cables installation point, hoist the unit w
as water leaks, electric shocks, fire and personal injury, as a result of a burst and refrigerant leakage after a long period. correctly to prevent overloading the terminal blocks. you may not damage the unit.
system malfunction. • Do not open the operation valves for liquid line and gas line Loose connections or cable mountings can cause anomalous heat
• Install the system in full accordance with the instruction
manual.
until completed refrigerant piping work, air tightness test and
evacuation.
production or fire.
• Arrange the wiring in the control box so that it cannot be
2) Portage
Incorrect installation may cause bursts, personal injury, water leaks, If the compressor is operated in state of opening operation valves pushed up further into the box. Install the service panel ● The right hand side of the unit a
electric shocks and fire. before completed connection of refrigerant piping work, air can be correctly. A person carrying the right hand
• Be sure to use only for household and residence. sucked into refrigerant circuit, which can cause bust or personal injury Incorrect installation may result in overheating and fire. the left hand side must hold with
If this appliance is installed in inferior environment such as machine due to anomalously high pressure in the refrigerant. • Be sure to fix up the service panels. of the unit and with his left han
shop and etc., it can cause malfunction. • The electrical installation must be carried out by the qualified Incorrect fixing can cause electric shocks or fire due to intrusion of
• Use the original accessories and the specified components for electrician in accordance with “the norm for electrical work” dust or water.
installation. and “national wiring regulation”, and the system must be • Be sure to switch off the power supply in the event of 3) Selection of installa
If parts other than those prescribed by us are used, It may cause connected to the dedicated circuit. installation, inspection or servicing. Be sure to select a suitable insta
water leaks, electric shocks, fire and personal injury. Power supply with insufficient capacity and incorrect function done by If the power supply is not shut off, there is a risk of electric shocks, 〇 A place where it is horizontal
• Install the unit in a location with good support. improper work can cause electric shocks and fire. unit failure or personal injury due to the unexpected start of fan. of the unit.
Unsuitable installation locations can cause the unit to fall and cause • Be sure to shut off the power before starting electrical work. • Stop the compressor before disconnecting refrigerant pipes in 〇 A place where it can be free f
material damage and personal injury. Failure to shut off the power can cause electric shocks, unit failure or case of pump down operation. 〇 A place where the unit is not
• Ensure the unit is stable when installed, so that it can incorrect function of equipment. If disconnecting refrigerant pipes in state of opening operation valves 〇 A place where it can be free f
withstand earthquakes and strong winds. • Be sure to use the cables conformed to safety standard and before compressor stopping, air can be sucked, which can cause 〇 A place where drain water can
Unsuitable installation locations can cause the unit to fall and cause cable ampacity for power distribution work. burst or personal injury due to anomalously high pressure in the 〇 A place where the unit will no
material damage and personal injury. Unconformable cables can cause electric leak, anomalous heat refrigerant circuit. 〇 A place where snow will not a
• Ventilate the working area well in the event of refrigerant production or fire. • Only use prescribed optional parts. The installation must be 〇 A place where the unit can b
leakage during installation. • This appliance must be connected to main power supply by carried out by the qualified installer. radio or TV interference.
If the refrigerant comes into contact with naked flames, poisonous gas means of a circuit breaker or switch (fuse:16A) with a contact If you install the system by yourself, it can cause serious trouble such 〇 A place where good air circul
is produced. separation of at least 3mm. as water leaks, electric shocks, fire. and service of the unit safely.
• Use the prescribed pipes, flare nuts and tools for R410A. 〇 A place where the unit will no
Using existing parts (for R22 or R407C) can cause the unit failure and other equipment.
serious accidents due to burst of the refrigerant circuit. 〇 A place where chemical substa
harm the unit, will not be gen
• Ensure that no air enters in the refrigerant circuit when the unit • Do not bundling, winding or processing for the power cord. Or, • Do not perform any change of protective device itself or its 〇
is installed and removed. do not deforming the power plug due to tread it. setup condition. at a place where it is not influ
If air enters in the refrigerant circuit, the pressure in the refrigerant This may cause fire or heating. The forced operation by short-circuiting protective device of pressure 〇 A place where strong wind wi
circuit becomes too high, which can cause burst and personal injury. • Do not run the unit with removed panels or protections. switch and temperature controller or the use of non specified
• Do not processing, splice the power cord, or share a socket Touching rotating equipments, hot surfaces or high voltage parts can component can cause fire or burst.
with other power plugs. cause personal injury due to entrapment, burn or electric shocks. 4) Caution about select
This may cause fire or electric shock due to defecting contact, (1) If the unit is installed in the a
defecting insulation and over-current etc. The bottom plate of unit and i
• Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as electric shocks due to short-circuiting. 1 Install the unit on the base
that the bottom is higher t
CAUTION snow cover surface.
• Use the circuit breaker with sufficient breaking capacity. • Take care when carrying the unit by hand. • When perform the air conditioner operation (cooling or drying
If the breaker does not have sufficient breaking capacity, it can cause If the unit weights more than 20kg, it must be carried by two or more operation) in which ventilator is installed in the room. In this
the unit malfunction and fire. persons. Do not carry by the plastic straps, always use the carry case, using the air conditioner in parallel with the ventilator,
• Earth leakage breaker must be installed. handle when carrying the unit by hand. Use gloves to minimize the risk there is the possibility that drain water may backflow in
If the earth leakage breaker is not installed, it can cause electric of cuts by the aluminum fins. accordance with the room lapse into the negative pressure
shocks. • Dispose of any packing materials correctly. status. Therefore, set up the opening port such as incorporate
• Install isolator or disconnect switch on the power supply wiring Any remaining packing materials can cause personal injury as it the air into the room that may appropriate to ventilation (For
in accordance with the local codes and regulations. contains nails and wood. And to avoid danger of suffocation, be sure example; Open the door a little). In addition, just as above, so
• After maintenance, all wiring, wiring ties and the like, should be to keep the plastic wrapper away from children and to dispose after set up the opening port if the room lapse into negative
returned to their original state and wiring route, and the tear it up. pressure status due to register of the wind for the high rise
necessary clearance from all metal parts should be secured. • Be sure to insulate the refrigerant pipes so as not to condense apartment etc. Since drain water generated b
• Secure a space for installation, inspection and maintenance the ambient air moisture on them. ● Don’t execute drain piping w
specified in the manual. Insufficient insulation can cause condensation, which can lead to piping work.]
Insufficient space can result in accident such as personal injury due to moisture damage on the ceiling, floor, furniture and any other ● Recommend setting Defrost
falling from the installation place. valuables. SW3-2.]
• Do not install the unit in the locations listed below. • Do not install the outdoor unit in the locations listed below. the system, and cause malfunctions and breakdowns. The system
• Locations where carbon fiber, metal powder or any powder is floating. • Locations where discharged hot air or operating sound of the can also affect medical equipment and telecommunication equipment,
• Locations where any substances that can affect the unit such as outdoor unit can bother neighborhood. and obstruct its function or cause jamming.
sulphide gas, chloride gas, acid and alkaline can occur.
• Vehicles and ships.
• Locations where outlet air of the outdoor unit blows directly to
plants.
• Do not install the outdoor unit in a location where insects and
small animals can inhabit.
2. REFRIGERANT
• Locations where cosmetic or special sprays are often used. • Locations where vibration can be amplified and transmitted due to Insects and small animals can enter the electric parts and cause
• Locations with direct exposure of oil mist and steam such as kitchen insufficient strength of structure. damage or fire. Instruct the user to keep the surroundings clean.
and machine plant. • Locations where vibration and operation sound generated by the • Do not use the base flame for outdoor unit which is corroded
1) Restrictions on unit
• Locations where any machines which generate high frequency outdoor unit can affect seriously (on the wall or at the place near bed or damaged due to long periods of operation. ● Check the following points in l
harmonics are used. room). Using an old and damage base flame can cause the unit falling down ● Observe the following restriction
• Locations with salty atmospheres such as coastlines. • Locations where an equipment affected by high harmonics is placed and cause personal injury.
• Locations with heavy snow (If installed, be sure to provide base (TV set or radio receiver is placed within 5m). • Do not use any materials other than a fuse with the correct Re
flame and snow hood mentioned in the manual). • Locations where drainage cannot run off safely. rating in the location where fuses are to be used.
• Locations where the unit is exposed to chimney smoke. It can affect surrounding environment and cause a claim. Connecting the circuit with copper wire or other metal thread can Main
• Locations at high altitude (more than 1000m high). • Do not install the unit near the location where leakage of cause unit failure and fire.
-
• Locations with ammonic atmospheres. combustible gases can occur. • Do not touch any buttons with wet hands.
• Locations where heat radiation from other heat source can affect the If leaked gases accumulate around the unit, it can cause fire. It can cause electric shocks. Elevation difference between
207 -
unit. • Do not install the unit where corrosive gas (such as sulfurous • Do not touch any refrigerant pipes with your hands when the indoor and outdoor units
• Locations without good air circulation. acid gas etc.) or combustible gas (such as thinner and system is in operation.
• Locations with any obstacles which can prevent inlet and outlet air petroleum gases) can accumulate or collect, or where volatile During operation the refrigerant pipes become extremely hot or ● The use res
of the unit. combustible substances are handled. extremely cold depending the operating condition, and it can cause CAUTION Where an e
• Locations where short circuit of air can occur (in case of multiple Corrosive gas can cause corrosion of heat exchanger, breakage of burn injury or frost injury. For more in
units installation). plastic parts and etc. And combustible gas can cause fire. • Do not touch the suction or aluminum fin on the outdoor unit.
• Locations where strong air blows against the air outlet of outdoor • Do not install nor use the system close to the equipment that This may cause injury.
unit. generates electromagnetic fields or high frequency harmonics. • Do not put anything on the outdoor unit and operating unit. 2) Determination of pi
It can cause remarkable decrease in performance, corrosion and Equipment such as inverters, standby generators, medical high This may cause damage the objects or injury due to falling to the ● Determine refrigerant pipe size
damage of components, malfunction and fire. frequency equipments and telecommunication equipments can affect object. indoor unit specifications.
'10 • PAC-DB-142
RWC012A029B Notabilia as a unit designed for R410A
Model 40·50·60 ● Do not use any refrigerant other than R410A. R410A will rise to pressure about 1.6 times higher than that of a conventional refrigerant.
A cylinder containing R410A has a pink indication mark on the top.
REFRIGERANT USED ●A unit designed for R410A has adopted a different size indoor unit operation valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake.
its. The processed dimension of the flared part of a refrigerant pipe and a flare nut's parallel side measurement have also been altered to raise strength against pressure.
Accordingly, you are required to arrange dedicated R410A tools listed in the table on the right before installing or servicing this unit.
oor and outdoor units, power ● Do not use a charge cylinder. The use of a charge cylinder will cause the refrigerant composition to change, which results in performance degradation.
● In charging refrigerant, always take it out from a cylinder in the liquid phase.
● All indoor units must be models designed exclusively for R410A. Check connectable indoor unit models in a catalog, etc. (A wrong indoor unit, if connected into the system, will impair proper system operation)
y using suitable protective 1. HAULAGE AND INSTALLATION (Take particular care in carrying in or moving the unit, and always perform such an operation with two or more persons.)
the high position.
When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity
CAUTION center position. If not properly balanced, the unit can be thrown off-balance and fall.
e proper earthing
1) Delivery Pad (2) If the unit can be affected by strong wind, following measures are required.
Strong wind can cause damage of fan (fan motor), or can cause performance degradation, or can trigger
● Deliver the unit as close as possible to the installation site before removing it from anomalous stop of the unit due to rising of high pressure.
the packaging.
● When you have to unpack the unit for a compelling reason before you haul it to the
ctrical connection, tighten the 1.Install the outlet air blow side of the unit to face a
and relieve the cables installation point, hoist the unit with nylon slings or ropes and protection pads so that
wall of building, or provide a fence or a windbreak screen.
he terminal blocks. you may not damage the unit.
gs can cause anomalous heat
stall the service panel ● The right hand side of the unit as viewed from the front (diffuser side) is heavier. Over 500mm
A person carrying the right hand side must take heed of this fact. A person carrying
rheating and fire. the left hand side must hold with his right hand the handle provided on the front panel
ls. of the unit and with his left hand the corner column section. 2.Install the outlet air blow side of the unit in a position
ocks or fire due to intrusion of perpendicular to the direction of wind.
Wind direction
upply in the event of 3) Selection of installation location for the outdoor unit
g. Be sure to select a suitable installation place in consideration of following conditions. Wind direction
ere is a risk of electric shocks, 〇 A place where it is horizontal, stable and can endure the unit weight and will not allow vibration transmittance
he unexpected start of fan. of the unit.
onnecting refrigerant pipes in 〇 A place where it can be free from possibility of bothering neighbors due to noise or exhaust air from the unit.
〇 A place where the unit is not exposed to oil splashes. 5) Installation space
ate of opening operation valves 〇 A place where it can be free from danger of flammable gas leakage.
be sucked, which can cause 〇 A place where drain water can be disposed without any trouble. ● Walls surrounding the unit in the four sides are not acceptable.
alously high pressure in the 〇 A place where the unit will not be affected by heat radiation from other heat source. ● There must be a 1-meter or larger space in the above.
〇 A place where snow will not accumulate. ● When more than one unit are installed side by side, provide a 250mm or wider interval between them as a service
s. The installation must be 〇 A place where the unit can be kept away 5m or more from TV set and/or radio receiver in order to avoid any space. In order to facilitate servicing of controllers, please provide a sufficient space between units so that their
er. radio or TV interference. top plates can be removed easily.
can cause serious trouble such 〇 A place where good air circulation can be secured, and enough service space can be secured for maintenance ● Where a danger of short-circuiting exists, install guide louvers.
and service of the unit safely. ● When more than one unit are installed, provide sufficient intake space consciously so that short-circuiting may not occur.
〇 A place where the unit will not be affected by electromagnetic waves and/or high-harmonic waves generated by
● Where piling snow can bury the outdoor unit, provide proper snow guards.
other equipment.
〇 A place where chemical substances like sulfuric gas, chloric gas, acid and alkali (including ammonia), which can
The height of a wall is 1200mm or less.
harm the unit, will not be generated and not remain.
otective device itself or its 〇 (mm)
by using suitable protective 1. HAULAGE AND INSTALLATION (Take particular care in carrying in or moving the unit, and always perform such an operation with two or more persons.)
t the high position.
When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity
CAUTION center position. If not properly balanced, the unit can be thrown off-balance and fall.
de proper earthing
1) Delivery Pad (2) If the unit can be affected by strong wind, following measures are required.
Strong wind can cause damage of fan (fan motor), or can cause performance degradation, or can trigger
● Deliver the unit as close as possible to the installation site before removing it from anomalous stop of the unit due to rising of high pressure.
the packaging.
● When you have to unpack the unit for a compelling reason before you haul it to the
ectrical connection, tighten the 1.Install the outlet air blow side of the unit to face a
and relieve the cables installation point, hoist the unit with nylon slings or ropes and protection pads so that
wall of building, or provide a fence or a windbreak screen.
the terminal blocks. you may not damage the unit.
ngs can cause anomalous heat
nstall the service panel ● The right hand side of the unit as viewed from the front (diffuser side) is heavier. Over 500mm
A person carrying the right hand side must take heed of this fact. A person carrying
erheating and fire. the left hand side must hold with his right hand the handle provided on the front panel
els. of the unit and with his left hand the corner column section. 2.Install the outlet air blow side of the unit in a position
ocks or fire due to intrusion of perpendicular to the direction of wind.
Wind direction
supply in the event of 3) Selection of installation location for the outdoor unit
ng. Be sure to select a suitable installation place in consideration of following conditions. Wind direction
here is a risk of electric shocks, 〇 A place where it is horizontal, stable and can endure the unit weight and will not allow vibration transmittance
he unexpected start of fan. of the unit.
connecting refrigerant pipes in 〇 A place where it can be free from possibility of bothering neighbors due to noise or exhaust air from the unit.
〇 A place where the unit is not exposed to oil splashes. 5) Installation space
state of opening operation valves 〇 A place where it can be free from danger of flammable gas leakage.
n be sucked, which can cause 〇 A place where drain water can be disposed without any trouble. ● Walls surrounding the unit in the four sides are not acceptable.
alously high pressure in the 〇 A place where the unit will not be affected by heat radiation from other heat source. ● There must be a 1-meter or larger space in the above.
-
〇 A place where snow will not accumulate. ● When more than one unit are installed side by side, provide a 250mm or wider interval between them as a service
ts. The installation must be 〇 A place where the unit can be kept away 5m or more from TV set and/or radio receiver in order to avoid any
208 -
space. In order to facilitate servicing of controllers, please provide a sufficient space between units so that their
ler. radio or TV interference. top plates can be removed easily.
t can cause serious trouble such 〇 A place where good air circulation can be secured, and enough service space can be secured for maintenance ● Where a danger of short-circuiting exists, install guide louvers.
and service of the unit safely. ● When more than one unit are installed, provide sufficient intake space consciously so that short-circuiting may not occur.
〇 A place where the unit will not be affected by electromagnetic waves and/or high-harmonic waves generated by
● Where piling snow can bury the outdoor unit, provide proper snow guards.
other equipment.
〇 A place where chemical substances like sulfuric gas, chloric gas, acid and alkali (including ammonia), which can
The height of a wall is 1200mm or less.
harm the unit, will not be generated and not remain.
otective device itself or its 〇 (mm)
at a place where it is not influenced by natural wind. Model 40, 50, 60 Intake L3
ting protective device of pressure 〇 A place where strong wind will not blow against the outlet air blow of the unit. Example installation L2 service
( space )
Size Ⅰ Ⅱ Ⅲ Ⅳ
the use of non specified L1 Open 280 280 180
L4
Intake
4) Caution about selection of installation location L2 100 75 Open Open
L3 100 80 80 80 Outlet
(1) If the unit is installed in the area where the snow will accumulate, following measures are required. L1
L4 250 Open 250 Open
The bottom plate of unit and intake, outlet may be blocked by snow.
6) Installation
hort-circuiting. 1 Install the unit on the base so 2 Provide a snow hood to 3 Install the unit under eaves
the outdoor unit on site. or provide the roof on site. ① Anchor bolt fixed position ② Notabilia for installation
that the bottom is higher than
snow cover surface. Regarding outline of a snow 88.4 510 200
24.3
312.5
351.6
'10 • PAC-DB-142
into the negative pressure
ning port such as incorporate
Use a long block to
propriate to ventilation (For Outlet extend the width. Use a thicker block to anchor deeper.
In addition, just as above, so
14.8
oor unit and operating unit. 2) Determination of pipe size When pipe is brazing.
or injury due to falling to the ● Determine refrigerant pipe size pursuant to the following guidelines based on the
indoor unit specifications. About brazing
Model 40, 50, 60
[4m/m] Brazing must be performed under a nitrogen gas flow.
Gas pipe Liquid pipe
Without nitrogen gas, a large quantity of foreign matters (oxidized film) are created,
r (Anti-reverse flow type) Ǿ12.7 Ǿ6.35
Outdoor unit connected causing a critical failure from capillary tube or expansion valve clogging.
Flare Flare
or R410A)
Primary side Secondary side
Plug the end of the pipe with tape, or other
ned specifically for R410A) Refrigerant piping (branch pipeL) Ǿ12.7 Ǿ6.35
material, and fill the pipe with nitrogen gas. Station valve
0.5MPa
d specifically for R410A)
Indoor unit connected Ǿ12.7 Ǿ6.35 <N2> Hand
ed specifically for R410A) Taping
Nitrogen
24.3
hood, refer to our technical Fasten with bolts
operation (cooling or drying manual. Intake
(M10-12)
stalled in the room. In this
parallel with the ventilator,
288.7
312.5
351.6
water may backflow in
nto the negative pressure
ing port such as incorporate
Use a long block to
ropriate to ventilation (For Outlet extend the width. Use a thicker block to anchor deeper.
n addition, just as above, so
14.8
m lapse into negative
the wind for the high rise ● In installing the unit, fix the unit’s legs with bolts specified on the left.
Since drain water generated by defrost control may freeze, following measures are required. ● The protrusion of an anchor bolt on the front side must be kept within 15 mm.
● Don’t execute drain piping work by using a drain elbow and drain grommets (optional parts). [Refer to Drain ● Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.
piping work.] ● Refer to the above illustrations for information regarding concrete foundations.
● Recommend setting Defrost Control (SW3-1) and Snow Guard Fan Control (SW3-2). [Refer to Setting SW3-1, ● Install the unit in a level area. (With a gradient of 5 mm or less.)
SW3-2.] Improper installation can result in a compressor failure, broken piping within the unit and abnormal noise generation.
nd breakdowns. The system
d telecommunication equipment,
ming.
location where insects and 2. REFRIGERANT PIPING WORK
he electric parts and cause
ep the surroundings clean.
door unit which is corroded
1) Restrictions on unit installation and use
f operation. ● Check the following points in light of the indoor unit specifications and the installation site.
can cause the unit falling down ● Observe the following restrictions on unit installation and use. Improper installation can result in a compressor failure or performance degradation.
Indoor unit
an a fuse with the correct Restrictions Dimensional restrictions Marks appearing in the drawing on the right
are to be used.
e or other metal thread can Main pipe length 30m or less L
H
t hands. When the outdoor unit is positioned higher, 20m or less H
Elevation difference between
with your hands when the indoor and outdoor units
When the outdoor unit is positioned lower, 20m or less H L
Outdoor unit
become extremely hot or ● The use restrictions appearing in the table above are applicable to the standard pipe size combinations shown in the table below.
ng condition, and it can cause CAUTION Where an existing pipe system is utilized, different one-way pipe length restrictions should apply depending on its pipe size.
For more information, please see “ 5. UTILIZATION OF EXISTING PIPING.”
num fin on the outdoor unit.
or unit and operating unit. 2) Determination of pipe size When pipe is brazing.
or injury due to falling to the ● Determine refrigerant pipe size pursuant to the following guidelines based on the
indoor unit specifications. About brazing
Model 40, 50, 60
4m/m] Brazing must be performed under a nitrogen gas flow.
Gas pipe Liquid pipe
Without nitrogen gas, a large quantity of foreign matters (oxidized film) are created,
Anti-reverse flow type) Ǿ12.7 Ǿ6.35
Outdoor unit connected causing a critical failure from capillary tube or expansion valve clogging.
Flare Flare
R410A)
Primary side Secondary side
Plug the end of the pipe with tape, or other
ed specifically for R410A) Refrigerant piping (branch pipeL) Ǿ12.7 Ǿ6.35
material, and fill the pipe with nitrogen gas. Station valve
0.5MPa
specifically for R410A)
Indoor unit connected Ǿ12.7 Ǿ6.35 <N2> Hand
d specifically for R410A) Taping
-
Nitrogen
3) Refrigerant pipe wall thickness and material Pipe diameter [mm] 6.35 12.7
● Select refrigerant pipes of the table shown on the right wall thickness and material as specified for each pipe size. Minimum pipe wall thickness [mm] 0.8 0.8 4. ELECTRICAL WI
NOTE ● Select pipes having a wall thickness larger than the specified minimum pipe thickness. Pipe material* O-type pipe O-type pipe
Electrical installation work must be perfo
*Phosphorus deoxidized seamless copper pipe ICS 23.040.15, ICS 77.150.30
Electrical installation work must be exec
Do not use any supply cord lighter th
4) On-site piping work
●
●
Do not turn on the power until the el
its form. Copper In the case of a rigid (clutch) type
pipe outer
●
Do not use a condensive capacitor fo
● Flare connection is used between the unit and refrigerant pipe. Flare a pipe after engaging a
diameter With an R410A tool With a conventional tool an abnormal overheat accident)
flare nut onto it. Flare dimensions for R410A are different from those for conventional R407C. Ǿ6.35 ●
For power supply cables, use condui
Although we recommend the use of flaring tools designed specifically for R410A, conventional Screw 0∼0.5 1.0∼1.5
Ǿ12.7 ●
Do not lay electronic control cables (r
'10 • PAC-DB-142
flaring tools can also be used by adjusting the measurement of protrusion B with a protrusion
control gauge. in the malfunctioning or a failure of
● The pipe should be anchored every 1.5m or less to isolate the vibration. Side cover ●
Fasten cables so that may not touch
●Tighten a flare joint securely with a double spanner. ●
When cables are connected, make su
terminal connection and then attach
penetrates into the box.)
CAUTION Do not apply force beyond proper fastening torque in tightening the flare nut. ●
Always use a three-core cable for an
Fix both liquid and gas operation valves at the valve main bodies as illustrated on the right, and then fasten them,
applying appropriate fastening torque.
Operation valve size (mm) Tightening torque (N㨯m) Tightening angle (°) Recommended length of a tool handle (mm)
Ǿ6.35 (1/4") 14∼18 45∼60 150 Use a torque wrench. If a torque wrench is
not available, fasten the flare nut manually
Ǿ12.7 (1/2") 49∼61 30∼45 250 first and then tighten it further, using the
Do not hold the valve cap area with a spanner. left table as a guide.
5) Air tightness test ○
① Although outdoor and indoor units themselves have been tested for air tightness at the factory, check the connecting pipes after the installation work for air tightness from the Gas side
operation valve’s check joint equipped on the outdoor unit side. While conducting a test, keep the operation valve shut all the time. Outdoor unit operation valve Indoor unit ○
a) Raise the pressure to 0.5 MPa, and then stop. Leave it for five minutes to see if the pressure drops. Check joint
b) Then raise the pressure to 1.5 MPa, and stop. Leave it for five more minutes to see if the pressure drops.
c) Then raise the pressure to the specified level (4.15 MPa), and record the ambient temperature and the pressure. ur ize
d) If no pressure drop is observed with an installation pressurized to the specified level and left for about one day, it is acceptable. When the ambient Temperature fall 1℃, the pressure Press
Close
also fall approximately 0.01 MPa. The pressure, if changed, should be compensated for.
e) If a pressure drop is observed in checking e) and a) – d), a leak exists somewhere. Find a leak by applying bubble test liquid to welded parts and flare joints and repair it. After ○
repair, conduct an air-tightness test again.
② In conducting an air-tightness test, use nitrogen gas and pressurize the system with nitrogen gas from the gas side. Do not use a medium other than nitrogen gas under any circumstances.
Compound pressure gauge
Operation Valve
Pressure gauge ○
6) Evacuation Cap
<Work flow> Airtighteness test completed Operation Valve
(two-way valve)
Gauge Manifold
-0.1MPa (Designed specifically for R410A)
(-76cmHg)
Vacuuming begins
Handle Lo Handle Hi.
When the system has remaining moisture Run the vacuum pump for at least one hour after the vacuum
Operation Valve
inside or a leaky point, the vacuum gauge gauge shows -101kPa or lower. (-755mmHg or lower) (three-way valve)
Charge hose
(Designed specifically for R410A)
indicator will rise. Vacuuming completed
5. UTILIZATION OF
Vacuum pump adapter
Check the system for a leaky point and Operation Valve (Anti-reverse flow type)
then draw air to create a vacuum again. Confirm that the vacuum gauge indicator does not rise even if (Designed specifically for R410A)
Cap
the system is left for one hour or more.
Vacuum gauge check Check joint Vacuum pump
Charge hose
(Designed specifically for R410A) Check whether an existing pipe
Fill refrigerant
Securely tighten the operation valve cap and the check joint blind nut after adjustment.
Pay attention to the following points in addition to the above for the R410A and compatible machines. START
Operation valve size Operation valve cap Check joint blind nut
○To prevent a different oil from entering, assign dedicated tools, etc. to each refrigerant type. Under no circumstances must a (mm) tightening torque (N·m) tightening torque (N·m)
Are an outdoor unit and an indoor unit connec
gauge manifold and a charge hose in particular be shared with other refrigerant types (R22, R407C, etc.). φ6.35 (1/4") 20∼30 existing pipe system to reuse?
○Use a counterflow prevention adapter to prevent vacuum pump oil from entering the refrigerant system. 10∼12
φ12.7 (1/2") YES
25∼35
B
●
Do not turn on the power until the e
its form. Copper In the case of a rigid (clutch) type
pipe outer
●
Do not use a condensive capacitor
● Flare connection is used between the unit and refrigerant pipe. Flare a pipe after engaging a
diameter With an R410A tool With a conventional tool an abnormal overheat accident)
flare nut onto it. Flare dimensions for R410A are different from those for conventional R407C. Ǿ6.35 ●
For power supply cables, use condu
Although we recommend the use of flaring tools designed specifically for R410A, conventional Screw 0∼0.5 1.0∼1.5
Ǿ12.7 ●
Do not lay electronic control cables
flaring tools can also be used by adjusting the measurement of protrusion B with a protrusion
control gauge. in the malfunctioning or a failure o
Side cover ●
Fasten cables so that may not touch
●Tighten a flare joint securely with a double spanner. ●
When cables are connected, make s
terminal connection and then attac
penetrates into the box.)
CAUTION Do not apply force beyond proper fastening torque in tightening the flare nut. ●
Always use a three-core cable for a
Fix both liquid and gas operation valves at the valve main bodies as illustrated on the right, and then fasten them,
applying appropriate fastening torque.
Operation valve size (mm) Tightening torque (N㨯m) Tightening angle (°) Recommended length of a tool handle (mm)
Ǿ6.35 (1/4") 14∼18 45∼60 150 Use a torque wrench. If a torque wrench is
not available, fasten the flare nut manually
Ǿ12.7 (1/2") 49∼61 30∼45 250 first and then tighten it further, using the
Do not hold the valve cap area with a spanner. left table as a guide.
5) Air tightness test
① Although outdoor and indoor units themselves have been tested for air tightness at the factory, check the connecting pipes after the installation work for air tightness from the Gas side
operation valve’s check joint equipped on the outdoor unit side. While conducting a test, keep the operation valve shut all the time. Outdoor unit operation valve Indoor unit
a) Raise the pressure to 0.5 MPa, and then stop. Leave it for five minutes to see if the pressure drops. Check joint
b) Then raise the pressure to 1.5 MPa, and stop. Leave it for five more minutes to see if the pressure drops.
c) Then raise the pressure to the specified level (4.15 MPa), and record the ambient temperature and the pressure. urize
d) If no pressure drop is observed with an installation pressurized to the specified level and left for about one day, it is acceptable. When the ambient Temperature fall 1℃, the pressure Press
Close
also fall approximately 0.01 MPa. The pressure, if changed, should be compensated for.
e) If a pressure drop is observed in checking e) and a) – d), a leak exists somewhere. Find a leak by applying bubble test liquid to welded parts and flare joints and repair it. After
repair, conduct an air-tightness test again.
② In conducting an air-tightness test, use nitrogen gas and pressurize the system with nitrogen gas from the gas side. Do not use a medium other than nitrogen gas under any circumstances.
Compound pressure gauge
Operation Valve
Pressure gauge
6) Evacuation Cap
<Work flow> Airtighteness test completed Operation Valve
(two-way valve)
Gauge Manifold
-0.1MPa (Designed specifically for R410A)
(-76cmHg)
Vacuuming begins
Handle Lo Handle Hi.
When the system has remaining moisture Run the vacuum pump for at least one hour after the vacuum
Operation Valve
inside or a leaky point, the vacuum gauge gauge shows -101kPa or lower. (-755mmHg or lower) (three-way valve)
Charge hose
(Designed specifically for R410A)
indicator will rise. Vacuuming completed
5. UTILIZATION OF
Vacuum pump adapter
Check the system for a leaky point and Operation Valve (Anti-reverse flow type)
then draw air to create a vacuum again. Confirm that the vacuum gauge indicator does not rise even if (Designed specifically for R410A)
Cap
the system is left for one hour or more.
Vacuum gauge check Check joint Vacuum pump
Charge hose
(Designed specifically for R410A) Check whether an existing pipe
Fill refrigerant
Securely tighten the operation valve cap and the check joint blind nut after adjustment.
Pay attention to the following points in addition to the above for the R410A and compatible machines. START
Operation valve size Operation valve cap Check joint blind nut
○To prevent a different oil from entering, assign dedicated tools, etc. to each refrigerant type. Under no circumstances must a (mm) tightening torque (N·m) tightening torque (N·m)
Are an outdoor unit and an indoor unit conne
gauge manifold and a charge hose in particular be shared with other refrigerant types (R22, R407C, etc.). φ6.35 (1/4") 20∼30 existing pipe system to reuse?
○Use a counterflow prevention adapter to prevent vacuum pump oil from entering the refrigerant system. 10∼12
φ12.7 (1/2") YES
-
25∼35
'10 • PAC-DB-142
reuse free of peel-offs or deterioration?
㨯 Improper heat insulation/anti-dew dressing can result in a water leak or dripping causing damage to household effects, etc. (Heat insulation is necessary for both gas and liq
(2) Use a heat insulating material that can withstand 120℃ or a higher temperature. Poor heat insulating capacity can cause heat insulation problems or cable NO
deterioration.
㨯 All gas pipes must be securely heat insulated in order to prevent damage from dripping water that comes from the condensation formed on them during a cooling operation Aren’t there any loose pipe support
or personal injury from burns because their surface can reach quite a high temperature due to discharged gas flowing inside during a heating operation. Wires for connecting indoor No loose pipe supports
㨯 Wrap indoor units’ flare joints with heat insulating parts (pipe cover) for heat insulation (both gas and liquid pipes). Exterior tape
and outdoor units
㨯 Give heat insulation to both gas and liquid side pipes. Bundle a heat insulating material and a pipe tightly together so that no gaps may be left between them and wrap them
Gas piping
together with a connecting cable by a dressing tape. Liquid piping The existing pipe system is re
㨯 Both gas and liquid pipes need to be dressed with 20 mm or thicker heat insulation materials above the ceiling where relative humidity exceeds 70%.
Insulation
RWC012A029B
4. ELECTRICAL WIRING WORK For details of electrical cabling, refer to the indoor unit installation manual.
Electrical installation work must be performed by an electrical installation service provider qualified by a power provider of the country.
Electrical installation work must be executed according to the technical standards and other regulations applicable to electrical installations in the country.
●
Do not use any supply cord lighter than one specified in parentheses for each type below. CAUTION
㨯 braided cord (code designation 60245 IEC 51),
mm) 㨯 ordinary tough rubber sheathed cord (code designation 60245 IEC 53) In case of faulty wiring connection, the indoor unit stops,
㨯 flat twin tinsel cord (code designation 60227 IEC 41); and then the run lamp turns on and the timer lamp blinks.
.
4 Use polychloroprene sheathed flexible cord (code designation 60245 IEC57) for supply cords of parts of appliances for outdoor use.
.
●
Ground the unit. Do not connect the grounding wire to a gas pipe, water pipe, lightning rod or telephone grounding wire.
If impropery grounded, an electric shock or malfunction may result.
●
A grounding wire must be connected before connecting the power cable. Provide a grounding wire longer than the power cable. Use cables for interconnection wiring to avoid loosening of the wires.
CENELEC code for cables Required field cables.
-
The installation of an impulse withstanding type earth leakage breaker is necessary. A failure to install an earth leakage breaker can result in an
●
'10 • PAC-DB-142
Please adjust it when not suitable. 1 2/N 3
ize
s sur Indoor unit 40
Pre Cable clamp Single-phase 50
15A,30mA,
30A 16A 2.0mm2 1.5mm×4
0.1sec or less
○It holds cables in place and protect the terminal 60
connection from external force. ●The specifications shown in the above table are for units without heaters. For units with heaters, refer to
Grounding terminal the installation instructions or the construction instructions of the indoor unit.
ound pressure gauge ●Switchgear or Circuit breaker capacity which is calculated from MAX. over current should be chosen along the
essure gauge ○Please be sure to carry out D-type (type III) regulations in each country.
uge Manifold
grounding work. ●The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than
esigned specifically for R410A) three cables contained in a conduit and a voltage drop is 2%. For an installation falling outside of these
conditions, please follow the internal cabling regulations. Adapt it to the regulation in effect in each country.
ndle Hi.
arge hose
esigned specifically for R410A)
cuum pump
r R410A) Check whether an existing pipe system is reusable or not by using the following flow chart. <Table of pipe size restrictions>
◎:Standard pipe size ○:Usable △:Restricted to shorter pipe length limits
er adjustment.
START Additional charge volume per meter of pipe 0.02kg/m 0.06kg/m
nt blind nut
g torque (N·m) Liquid pipe ø6.35 ø9.52
Are an outdoor unit and an indoor unit connected to the NO Pipe size
existing pipe system to reuse? Gas pipe ø 12.7 ø 12.7
0∼12 YES Usability ◎ △
NO Which of the following refrigeration oils Can‘t
Are the existing units our products? does the existing unit use? Please make an 40 Maximum one-way pipe length 30 10
NO Use
Suniso, MS, Barrel Freeze, HAB, Freol, inquiry for
YES YES reusability. Length covered without additional charge 15 5
ether oil, ester oil
Can Use Usability ◎ △
charge it, keeping the container 50 Maximum one-way pipe length 30 10
on tube. Does the existing pipe system to reuse satisfy all of the following?
(1) The pipe length is 30m or less. Length covered without additional charge 15 15
tion valve shut. When you find it (2) The pipe size conforms to the table of pipe size restrictions.
n both liquid and gas sides and (3) The elevation difference between the indoor and outdoor units NO Usability ◎ △
the unit in the cooling mode. In conforms to the following restrictions.
Where the outdoor unit is above: 15m or less 60 Maximum one-way pipe length 30 10
the cylinder in the liquid phase all Where the outdoor unit is below: 15m or less ※Check with the flow chart developed for a case where
an existing pipe system is reused for a Length covered without additional charge 15 5
rsion tool to change liquid-phase YES twin-triple-double-twin model published as a
charge conditions so that technical data sheet.
YES Change is impossible. ● Pleaseconsult with our distributor in the area, if you need to recover refrigerant and charge it again.
Is the unit to install in the existing pipe system a
Change the branching pipe to a specified type.
twin-triple-double-twin model? ● Any combinations of pipe sizes not listed in the table are not usable.
ale to measure the charge volume.
Change
peration within 30 minutes. NO
e can cause a compressor failure. YES Repair is impossible.
Formula to calculate additional charge volume
Is the existing pipe system to reuse free of corrosion, flaws or dents? Repair the damaged parts.
onto the caution label attached on NO Repair Additional charge volume (kg) = {Main pipe length (m) – Length covered without additional charge shown in the table (m)} ×
Is the existing pipe system to reuse free of gas leaks?
Air tightness is Additional charge volume per meter of pipe shown in the table (kg/m)
impossible.
(Check whether refrigerant charge was required frequently for Check the pipe system for air tightness on the site.
the system before) ※ If you obtain a negative figure as a result of calculation, no additional refrigerant needs to be charged.
Air tightness is OK
NO Remove is Example) When an 60 is installed in a 10m long existing pipe system (liquid Ǿ9.52, gas Ǿ12.7),
Are there any branch pipes with no indoor unit connected? Remove those branches.
impossible the quantity of refrigerant to charge additionally should be (10m-5m) x 0.06kg/m = 0.3 kg.
NO Remove
) Pipe cover (accessory)
Are heat insulation materials of the existing pipe system to Repair is impossible. WARNING <Where the existing unit can be run for a cooling operation.>
reuse free of peel-offs or deterioration? Repair the damaged parts.
(Heat insulation is necessary for both gas and liquid pipes)
Carry out the following steps with the excising unit (in the order of (1), (2), (3) and (4))
Repair
NO (1) Run the unit for 30 minutes for a cooling operation.
(2) Stop the indoor fan and run the unit for 3 minutes for a cooling operation (returning liquid)
Aren’t there any loose pipe supports? Repair the damaged parts. (3) Close the liquid side operation valve of the outdoor unit and pump down (refrigerant recovery)
oorDownloaded from www.Manualslib.com manuals search engine
No loose pipe supports Some loose pipe supports Repair (4) Blow with nitrogen gas. ※ If discolored refrigeration oil or any foreign matters is discharged
Exterior tape by the blow, wash the pipe system or install a new pipe system.
㨯 braided cord (code designation 60245 IEC 51),
mm) 㨯 ordinary tough rubber sheathed cord (code designation 60245 IEC 53) In case of faulty wiring connection, the indoor unit stops,
㨯 flat twin tinsel cord (code designation 60227 IEC 41); and then the run lamp turns on and the timer lamp blinks.
.
4 Use polychloroprene sheathed flexible cord (code designation 60245 IEC57) for supply cords of parts of appliances for outdoor use.
●
Ground the unit. Do not connect the grounding wire to a gas pipe, water pipe, lightning rod or telephone grounding wire.
If impropery grounded, an electric shock or malfunction may result.
●
A grounding wire must be connected before connecting the power cable. Provide a grounding wire longer than the power cable. Use cables for interconnection wiring to avoid loosening of the wires.
●
The installation of an impulse withstanding type earth leakage breaker is necessary. A failure to install an earth leakage breaker can result in an CENELEC code for cables Required field cables.
acccident such as an electric shock or a fire. H05RNR4G1.5 (Example) or 245IEC57
sion for flaring : B (mm) ●
Do not turn on the power until the electrical work is completeted .
e case of a rigid (clutch) type H Harmonized cable type
●
Do not use a condensive capacitor for power factor improvement under any circumstances. (It dose not improve power factor, while it can cause
R410A tool With a conventional tool
05 300/500 volts
an abnormal overheat accident)
R Natural-and/or synth. rubber wire insulation
●
For power supply cables, use conduits.
∼0.5 1.0∼1.5 ●
Do not lay electronic control cables (remote control and signaling wires) and other cables together outside the unit. Laying them together can result
N Polychloroprene rubber conductors insulation
in the malfunctioning or a failure of the unit due to electric noises. R Stranded core
●
Fasten cables so that may not touch the piping, etc. 4or5 Number of conductors
●
When cables are connected, make sure that all electrical components within the electrical component box are free of loose connector coupling or G One conductor of the cable is the earth conductor
terminal connection and then attach the cover securely. (Improper cover attachment can result in malfunctioning or a failure of the unit, if water (yellow/green)
penetrates into the box.) 1.5 Section of copper wire (mm2)
●
Always use a three-core cable for an indoor-outdoor connecting cable. Never use a shield cable.
rge hose
signed specifically for R410A)
uum pump
r R410A) Check whether an existing pipe system is reusable or not by using the following flow chart. <Table of pipe size restrictions>
◎:Standard pipe size ○:Usable △:Restricted to shorter pipe length limits
r adjustment.
START Additional charge volume per meter of pipe 0.02kg/m 0.06kg/m
t blind nut
torque (N·m) Liquid pipe ø6.35 ø9.52
Are an outdoor unit and an indoor unit connected to the NO Pipe size
existing pipe system to reuse? Gas pipe ø 12.7 ø 12.7
0∼12 YES Usability ◎ △
NO Which of the following refrigeration oils Can‘t
Are the existing units our products? does the existing unit use? Please make an 40 Maximum one-way pipe length 30 10
NO Use
Suniso, MS, Barrel Freeze, HAB, Freol, inquiry for
YES YES reusability. Length covered without additional charge 15 5
ether oil, ester oil
Can Use Usability ◎ △
charge it, keeping the container 50 Maximum one-way pipe length 30 10
on tube. Does the existing pipe system to reuse satisfy all of the following?
(1) The pipe length is 30m or less. Length covered without additional charge 15 15
ion valve shut. When you find it (2) The pipe size conforms to the table of pipe size restrictions.
n both liquid and gas sides and (3) The elevation difference between the indoor and outdoor units NO Usability ◎ △
the unit in the cooling mode. In conforms to the following restrictions.
Where the outdoor unit is above: 15m or less 60 Maximum one-way pipe length 30 10
the cylinder in the liquid phase all Where the outdoor unit is below: 15m or less ※Check with the flow chart developed for a case where
an existing pipe system is reused for a Length covered without additional charge 15 5
sion tool to change liquid-phase YES twin-triple-double-twin model published as a
harge conditions so that technical data sheet.
YES Change is impossible. ● Pleaseconsult with our distributor in the area, if you need to recover refrigerant and charge it again.
Is the unit to install in the existing pipe system a
Change the branching pipe to a specified type.
twin-triple-double-twin model? ● Any combinations of pipe sizes not listed in the table are not usable.
le to measure the charge volume.
Change
peration within 30 minutes. NO
e can cause a compressor failure. YES Repair is impossible.
Formula to calculate additional charge volume
Is the existing pipe system to reuse free of corrosion, flaws or dents? Repair the damaged parts.
onto the caution label attached on NO Repair Additional charge volume (kg) = {Main pipe length (m) – Length covered without additional charge shown in the table (m)} ×
Is the existing pipe system to reuse free of gas leaks?
Air tightness is Additional charge volume per meter of pipe shown in the table (kg/m)
impossible.
(Check whether refrigerant charge was required frequently for Check the pipe system for air tightness on the site.
the system before) ※ If you obtain a negative figure as a result of calculation, no additional refrigerant needs to be charged.
Air tightness is OK
-
NO Remove is Example) When an 60 is installed in a 10m long existing pipe system (liquid Ǿ9.52, gas Ǿ12.7),
impossible the quantity of refrigerant to charge additionally should be (10m-5m) x 0.06kg/m = 0.3 kg.
212 -
Are there any branch pipes with no indoor unit connected? Remove those branches.
NO Remove
Pipe cover (accessory)
Are heat insulation materials of the existing pipe system to Repair is impossible. WARNING <Where the existing unit can be run for a cooling operation.>
reuse free of peel-offs or deterioration? Repair the damaged parts.
(Heat insulation is necessary for both gas and liquid pipes)
Carry out the following steps with the excising unit (in the order of (1), (2), (3) and (4))
Repair
NO (1) Run the unit for 30 minutes for a cooling operation.
(2) Stop the indoor fan and run the unit for 3 minutes for a cooling operation (returning liquid)
Aren’t there any loose pipe supports? Repair the damaged parts. (3) Close the liquid side operation valve of the outdoor unit and pump down (refrigerant recovery)
oor No loose pipe supports Some loose pipe supports Repair (4) Blow with nitrogen gas. ※ If discolored refrigeration oil or any foreign matters is discharged
Exterior tape by the blow, wash the pipe system or install a new pipe system.
● For the flare nut, do not use the old one, but use the one supplied with the outdoor unit.
Gas piping The existing pipe system is not reusable.
The existing pipe system is reusable. Process a flare to the dimensions specified for R410A.
Install a new pipe system.
<Where the existing unit cannot be run for a cooling operation.>
Insulation
Wash the pipe system or install a new pipe system.
● If you choose to wash the pipe system, please contact our distributor in the area.
'10 • PAC-DB-142
to a drain, etc., install the unit on
t base (supplied separately as an
onal part) or concrete blocks. After installation
, please secure space for the drain
Power cables and connecting wires are securely fixed to the terminal block. The pipe joints for indoor and outdoor pipes have been insulated.
w and the drain hose.
The power supply voltage is correct as the rating. The reverse flow check cap is attached.
The drain hose is fixed securely. The cover of the pipe cover (A) faces downward to prevent rain from entering.
Operational valve is fully open. Gaps are properly sealed between the pipe covers (A) (B) and the wall surface / pipes.
No gas leaks from the joints of the operational valve.
PSB012D909G
4FMFDUJPO P
14#%( K
K
#F TVSF UP TFMFDU B
(2) Model FDC71VN 〇" QMBDF XIFSF J
*OWFSUFSESJWFOTJOHMFTQMJU1"$
*/45"--"5*0/."/6"-'03065%0036/*5
〇" QMBDF XIFSF J
〇" QMBDF XIFSF U
7 〇" QMBDF XIFSF J
%FTJHOFEGPS3"SFGSJHFSBOU 〇" QMBDF XIFSF E
〇" QMBDF XIFSF U
◎5IJT JOTUBMMBUJPO NBOVBM EFBMT XJUI PVUEPPS VOJUT BOE HFOFSBM JOTUBMMBUJPO TQFDJmDBUJPOT POMZ 'PS JOEPPS VOJUT
SFGFS UP UIF SFTQFDUJWF JOTUBMMBUJPO NBOVBMT TVQQMJFE XJUI UIF VOJUT 〇" QMBDF XIFSF T
◎8IFO JOTUBMM UIF VOJU
CF TVSF UP DIFDL XIFUIFS UIF TFMFDUJPO PG JOTUBMMBUJPO QMBDF
QPXFS TVQQMZ TQFDJmDBUJPOT
VTBHF MJNJUBUJPO QJQJOH MFOHUI
IFJHIU 〇 " QMBDF XIFSF UI
〇 " QMBDF XIFSF HPP
EJGGFSFODFT CFUXFFO JOEPPS BOE PVUEPPS VOJUT
QPXFS TVQQMZ WPMUBHF BOE FUD
BOE JOTUBMMBUJPO TQBDFT 〇 " QMBDF XIFSF UI
〇" QMBDF XIFSF D
$IFDLCFGPSFJOTUBMMBUJPOXPSL
4"'&5: 13&$"65*0/4 VOJU
XJMM OPU CF
〇" QMBDF XIFSF T
●8F SFDPNNFOE ZPV UP SFBE UIJTi4"'&5: 13&$"65*0/4w DBSFGVMMZ CFGPSF UIF JOTUBMMBUJPO XPSL JO PSEFS UP HBJO GVMM BEWBOUBHF PG UIF GVODUJPOT PG UIF VOJU BOE UP BWPJE NBMGVODUJPO EVF UP ● .PEFMOBNFBOEQPXFSTPVSDF
NJTIBOEMJOH
● 3FGSJHFSBOUQJQJOHMFOHUI
$BVUJPO BC
●5IF QSFDBVUJPOT EFTDSJCFE CFMPX BSF EJWJEFE JOUP 8"3/*/(
BOE $"65*0/
5IF NBUUFST XJUI QPTTJCJMJUJFT MFBEJOH UP TFSJPVT DPOTFRVFODFT TVDI BT EFBUI PS TFSJPVT QFSTPOBM
*G UIF VOJU JT JOT
JOKVSZ EVF UP FSSPOFPVT IBOEMJOH BSF MJTUFE JO UIF 8"3/*/(
BOE UIF NBUUFST XJUI QPTTJCJMJUJFT MFBEJOH UP QFSTPOBM JOKVSZ PS EBNBHF PG UIF VOJU EVF UP FSSPOFPVT IBOEMJOH JODMVEJOH ● 1JQJOH
XJSJOHBOENJTDFMMBOFPVTTNBMMQBSUT 5IF CPUUPN QMB
QSPCBCJMJUZ MFBEJOH UP TFSJPVT DPOTFRVFODFT JO TPNF DBTFT BSF MJTUFE JO $"65*0/ 5IFTF BSF WFSZ JNQPSUBOU QSFDBVUJPOT GPS TBGFUZ #F TVSF UP PCTFSWF BMM PG UIFN XJUIPVU GBJM ● *OEPPSVOJUJOTUBMMBUJPONBOVBM *OTUBMM UIF VO
●5IF NFBOJOH PG .BSLT VTFE IFSF BSF BT TIPXO CFMPX UIBU UIF CPUU
TOPX DPWFS
/FWFS EP JU VOEFS BOZ DJSDVNTUBODF "MXBZT EP JU BDDPSEJOH UP UIF JOTUSVDUJPO
●#F TVSF UP DPOmSN OP BOPNBMZ PO UIF FRVJQNFOU CZ DPNNJTTJPOJOH BGUFS DPNQMFUFE JOTUBMMBUJPO BOE FYQMBJO UIF PQFSBUJOH NFUIPET BT XFMM BT UIF NBJOUFOBODF NFUIPET PG UIJT FRVJQNFOU
UP UIF VTFS BDDPSEJOH UP UIF PXOFShT NBOVBM
●,FFQ UIF JOTUBMMBUJPO NBOVBM UPHFUIFS XJUI PXOFShT NBOVBM BU B QMBDF XIFSF BOZ VTFS DBO SFBE BU BOZ UJNF .PSFPWFS JG OFDFTTBSZ
BTL UP IBOE UIFN UP B OFX VTFS
-
● %POUFYFDVUFESBJ
● 3FDPNNFOETFUUJO
● *OTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEJOTUBMMFS ● %POPUQFSGPSNCSB[JOHXPSLJOUIFBJSUJHIUSPPN
*G UIF VOJU DBO C
*GZPVJOTUBMMUIFTZTUFNCZZPVSTFMG
JUNBZDBVTFTFSJPVTUSPVCMFTVDIBTXBUFSMFBLT
FMFDUSJDTIPDLT
mSFBOEQFSTPOBMJOKVSZ
BTBSFTVMUPGBTZTUFN *UDBODBVTFMBDLPGPYZHFO 4USPOH XJOE DBO
NBMGVODUJPO ● 6TFUIFQSFTDSJCFEQJQFT
nBSFOVUTBOEUPPMTGPS3" PG UIF VOJU EVF U
● *OTUBMMUIFTZTUFNJOGVMMBDDPSEBODFXJUIUIFJOTUSVDUJPONBOVBM 6TJOHFYJTUJOHQBSUT GPS3PS3$
DBODBVTFUIFVOJUGBJMVSFBOETFSJPVTBDDJEFOUTEVFUPCVSTUPGUIFSFGSJHFSBOUDJSDVJU
*ODPSSFDUJOTUBMMBUJPONBZDBVTFCVSTUT
QFSTPOBMJOKVSZ
XBUFSMFBLT
FMFDUSJDTIPDLTBOEmSF ● 5JHIUFO UIF nBSF OVU CZ VTJOH EPVCMF TQBOOFST BOE UPSRVF XSFODI BDDPSEJOH UP QSFTDSJCFE NFUIPE #F TVSF OPU UP *OTUBMM UIF PVUMF
● 6TFUIFPSJHJOBMBDDFTTPSJFTBOEUIFTQFDJmFEDPNQPOFOUTGPSJOTUBMMBUJPO UJHIUFOUIFnBSFOVUUPPNVDI VOJU UP GBDF B
*G QBSUT PUIFS UIBO UIPTF QSFTDSJCFE CZ VT BSF VTFE
*U NBZ DBVTF GBMM PG UIF VOJU
XBUFS MFBLT
FMFDUSJD TIPDLT
mSF
SFGSJHFSBOU MFBL
TVCTUBOEBSE -PPTFnBSFDPOOFDUJPOPSEBNBHFPOUIFnBSFQBSUCZUJHIUFOJOHXJUIFYDFTTUPSRVFDBODBVTFCVSTUPSSFGSJHFSBOUMFBLTXIJDI QSPWJEF B GFOD
QFSGPSNBODF
DPOUSPMGBJMVSFBOEQFSTPOBMJOKVSZ NBZSFTVMUJOMBDLPGPYZHFO
● 8IFOJOTUBMMJOHJOTNBMMSPPNT
UBLFQSFWFOUJPONFBTVSFTOPUUPFYDFFEUIFEFOTJUZMJNJUPGSFGSJHFSBOUJOUIFFWFOUPGMFBLBHFBDDPSEBODF ● %POPUPQFOUIFTFSWJDFWBMWFTGPSMJRVJEMJOFBOEHBTMJOFVOUJMDPNQMFUFESFGSJHFSBOUQJQJOHXPSL
BJSUJHIUOFTTUFTU
XJUI*40 BOEFWBDVBUJPO
$POTVMUUIFFYQFSUBCPVUQSFWFOUJPONFBTVSFT*GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJUJOUIFFWFOUPGMFBLBHF
MBDLPGPYZHFODBOPDDVS
XIJDI *GUIFDPNQSFTTPSJTPQFSBUFEJOTUBUFPGPQFOJOH TFSWJDFWBMWFTCFGPSFDPNQMFUFEDPOOFDUJPOPGSFGSJHFSBOU QJQJOH XPSL
ZPV
DBODBVTFTFSJPVTBDDJEFOUT NBZJODVSGSPTUCJUFPSJOKVSZGSPNBOBCSVQUSFGSJHFSBOUPVUnPXBOEBJSDBOCFTVDLFEJOUPSFGSJHFSBOUDJSDVJU
XIJDIDBODBVTF
● 7FOUJMBUFUIFXPSLJOHBSFBXFMMJOUIFFWFOUPGSFGSJHFSBOUMFBLBHFEVSJOHJOTUBMMBUJPO CVSTUPSQFSTPOBMJOKVSZEVFUPBOPNBMPVTMZIJHIQSFTTVSFJOUIFSFGSJHFSBOU
*GUIFSFGSJHFSBOUDPNFTJOUPDPOUBDUXJUIOBLFEnBNFT
QPJTPOPVTHBTJTQSPEVDFE ● 0OMZVTFQSFTDSJCFEPQUJPOBMQBSUT5IFJOTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEJOTUBMMFS
● "GUFSDPNQMFUFEJOTUBMMBUJPO
DIFDLUIBUOPSFGSJHFSBOUMFBLTGSPNUIFTZTUFN *GZPVJOTUBMMUIFTZTUFNCZZPVSTFMG
JUDBODBVTFTFSJPVTUSPVCMFTVDIBTXBUFSMFBLT
FMFDUSJDTIPDLT
mSF 0WFS N
*GSFGSJHFSBOUMFBLTJOUPUIFSPPNBOEDPNFTJOUPDPOUBDUXJUIBOPWFOPSPUIFSIPUTVSGBDF
QPJTPOPVTHBTJTQSPEVDFE ● %POPUQFSGPSNBOZDIBOHFPGQSPUFDUJWFEFWJDFJUTFMGPSJUTTFUVQDPOEJUJPO
● )BOHVQUIFVOJUBUUIFTQFDJmFEQPJOUTXJUISPQFTXIJDIDBOTVQQPSUUIFXFJHIUJOMJGUJOHGPSQPSUBHF"OEUPBWPJEKPMUJOHPVUPGBMJHONFOU
5IF GPSDFE PQFSBUJPO CZ TIPSUDJSDVJUJOH QSPUFDUJWF EFWJDF PG QSFTTVSF TXJUDI BOE UFNQFSBUVSF DPOUSPMMFS PS UIF VTF PG OPO
3&'3*(&3
CFTVSFUPIBOHVQUIFVOJUBUQPJOUTVQQPSU TQFDJmFEDPNQPOFOUDBODBVTFmSFPSCVSTU
"OJNQSPQFSNBOOFSPGQPSUBHFTVDIBTQPJOUTVQQPSUDBODBVTFEFBUIPSTFSJPVTQFSTPOBMJOKVSZEVFUPGBMMJOHPGUIFVOJU ● #FTVSFUPTXJUDIPGGUIFQPXFSTVQQMZJOUIFFWFOUPGJOTUBMMBUJPO
JOTQFDUJPOPSTFSWJDJOH
● *OTUBMMUIFVOJUJOBMPDBUJPOXJUIHPPETVQQPSU *GUIFQPXFSTVQQMZJTOPUTIVUPGG
UIFSFJTBSJTLPGFMFDUSJDTIPDLT
VOJUGBJMVSFPSQFSTPOBMJOKVSZEVFUPUIFVOFYQFDUFETUBSUPGGBO
6OTVJUBCMFJOTUBMMBUJPOMPDBUJPOTDBODBVTFUIFVOJUUPGBMMBOEDBVTFNBUFSJBMEBNBHFBOEQFSTPOBMJOKVSZ ● $POTVMUUIFEFBMFSPSBOFYQFSUSFHBSEJOHSFNPWBMPGUIFVOJU
● &OTVSFUIFVOJUJTTUBCMFXIFOJOTUBMMFE
TPUIBUJUDBOXJUITUBOEFBSUIRVBLFTBOETUSPOHXJOET *ODPSSFDUJOTUBMMBUJPODBODBVTFXBUFSMFBLT
FMFDUSJDTIPDLTPSmSF
3FTUSJDUJPO
6OTVJUBCMFJOTUBMMBUJPOMPDBUJPOTDBODBVTFUIFVOJUUPGBMMBOEDBVTFNBUFSJBMEBNBHFBOEQFSTPOBMJOKVSZ ● 4UPQUIFDPNQSFTTPSCFGPSFDMPTJOHWBMWFBOEEJTDPOOFDUJOHSFGSJHFSBOUQJQFTJODBTFPGQVNQEPXOPQFSBUJPO ● $IFDL UIF GPMMPX
'10 • PAC-DB-142
● 5IFFMFDUSJDBMJOTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEFMFDUSJDJBOJOBDDPSEBODFXJUIiUIFOPSNGPSFMFDUSJDBMXPSLwBOEiOBUJPOBM *G EJTDPOOFDUJOH SFGSJHFSBOU QJQFT JO TUBUF PG PQFOJOH TFSWJDF WBMWFT CFGPSF DPNQSFTTPS TUPQQJOH
ZPV NBZ JODVS GSPTU CJUF PS
JOKVSZGSPNBOBCSVQUSFGSJHFSBOUPVUnPXBOEBJSDBOCFTVDLFE
XIJDIDBODBVTFCVSTUPSQFSTPOBMJOKVSZEVFUPBOPNBMPVTMZ ● 0CTFSWF UIF GPMMP
XJSJOHSFHVMBUJPOw
BOEUIFTZTUFNNVTUCFDPOOFDUFEUPUIFEFEJDBUFEDJSDVJU
1PXFSTVQQMZXJUIJOTVGmDJFOUDBQBDJUZBOEJODPSSFDUGVODUJPOEPOFCZJNQSPQFSXPSLDBODBVTFFMFDUSJDTIPDLTBOEmSF
IJHIQSFTTVSFJOUIFSFGSJHFSBOUDJSDVJU
● #FTVSFUPTIVUPGGUIFQPXFSCFGPSFTUBSUJOHFMFDUSJDBMXPSL ● &OTVSFUIBUOPBJSFOUFSTJOUIFSFGSJHFSBOUDJSDVJUXIFOUIFVOJUJTJOTUBMMFEBOESFNPWFE
'BJMVSFUPTIVUPGGUIFQPXFSDBODBVTFFMFDUSJDTIPDLT
VOJUGBJMVSFPSJODPSSFDUGVODUJPOPGFRVJQNFOU *G BJS FOUFST JO UIF SFGSJHFSBOU DJSDVJU
UIF QSFTTVSF JO UIF SFGSJHFSBOU DJSDVJU CFDPNFT UPP IJHI
XIJDI DBO DBVTF CVSTU BOE
QFSTPOBMJOKVSZ
● #FTVSFUPVTFUIFDBCMFTDPOGPSNFEUPTBGFUZTUBOEBSEBOEDBCMFBNQBDJUZGPSQPXFSEJTUSJCVUJPOXPSL 0OFXBZQJQFMFO
6ODPOGPSNBCMFDBCMFTDBODBVTFFMFDUSJDMFBL
BOPNBMPVTIFBUQSPEVDUJPOPSmSF ● %POPUSVOUIFVOJUXJUISFNPWFEQBOFMTPSQSPUFDUJPOT
5PVDIJOHSPUBUJOHFRVJQNFOUT
IPUTVSGBDFTPSIJHIWPMUBHFQBSUTDBODBVTFQFSTPOBMJOKVSZEVFUPFOUSBQNFOU
CVSOPSFMFDUSJD .BJOQJ
● 6TFUIFQSFTDSJCFEDBCMFTGPSFMFDUSJDBMDPOOFDUJPO
UJHIUFOUIFDBCMFTTFDVSFMZJOUFSNJOBMCMPDLBOESFMJFWFUIFDBCMFTDPSSFDUMZUPQSFWFOU TIPDLT
PWFSMPBEJOHUIFUFSNJOBMCMPDLT
-PPTFDPOOFDUJPOTPSDBCMFNPVOUJOHTDBODBVTFBOPNBMPVTIFBUQSPEVDUJPOPSmSF ● #FTVSFUPmYVQUIFTFSWJDFQBOFMT
*ODPSSFDUmYJOHDBODBVTFFMFDUSJDTIPDLTPSmSFEVFUPJOUSVTJPOPGEVTUPSXBUFS
● "SSBOHFUIFXJSJOHJOUIFDPOUSPMCPYTPUIBUJUDBOOPUCFQVTIFEVQGVSUIFSJOUPUIFCPY*OTUBMMUIFTFSWJDFQBOFMDPSSFDUMZ %
*ODPSSFDUJOTUBMMBUJPONBZSFTVMUJOPWFSIFBUJOHBOEmSF ● %POPUQFSGPSNBOZSFQBJSTPSNPEJmDBUJPOTCZZPVSTFMG$POTVMUUIFEFBMFSJGUIFVOJUSFRVJSFTSFQBJS
*GZPVSFQBJSPSNPEJGZUIFVOJU
JUDBODBVTFXBUFSMFBLT
FMFDUSJDTIPDLTPSmSF
&MFWBUJPOEJGG
JOEPPSBOEPV
$"65*0/
● $BSSZPVUUIFFMFDUSJDBMXPSLGPSHSPVOEMFBEXJUIDBSF ● %POPUVTFUIFCBTFnBNFGPSPVUEPPSVOJUXIJDIJTDPSSPEFEPSEBNBHFEEVFUPMPOHQFSJPETPGPQFSBUJPO
%POPUDPOOFDUUIFHSPVOEMFBEUPUIFHBTMJOF
XBUFSMJOF
MJHIUOJOHDPOEVDUPSPSUFMFQIPOFMJOFhTHSPVOEMFBE*ODPSSFDUHSPVOEJOHDBODBVTFVOJUGBVMUTTVDIBT
FMFDUSJDTIPDLTEVFUPTIPSUDJSDVJUJOH/FWFSDPOOFDUUIFHSPVOEJOHXJSFUPBHBTQJQFCFDBVTFJGHBTMFBLT
JUDPVMEDBVTFFYQMPTJPOPSJHOJUJPO
6TJOHBOPMEBOEEBNBHFCBTFnBNFDBODBVTFUIFVOJUGBMMJOHEPXOBOEDBVTFQFSTPOBMJOKVSZ $"65*0/
● %POPUJOTUBMMUIFVOJUJOUIFMPDBUJPOTMJTUFECFMPX
● 6TFUIFDJSDVJUCSFBLFSGPSBMMQPMFXJUIDPSSFDUDBQBDJUZ ・-PDBUJPOTXIFSFDBSCPOmCFS
NFUBMQPXEFSPSBOZQPXEFSJTnPBUJOH
6TJOHUIFJODPSSFDUDJSDVJUCSFBLFS
JUDBODBVTFUIFVOJUNBMGVODUJPOBOEmSF ・-PDBUJPOTXIFSFBOZTVCTUBODFTUIBUDBOBGGFDUUIFVOJUTVDIBTTVMQIJEFHBT
DIMPSJEFHBT
BDJEBOEBMLBMJOFDBOPDDVS
%FUFSNJOBU
● *OTUBMMJTPMBUPSPSEJTDPOOFDUTXJUDIPOUIFQPXFSTVQQMZXJSJOHJOBDDPSEBODFXJUIUIFMPDBMDPEFTBOESFHVMBUJPOT ・7FIJDMFTBOETIJQT
5IFJTPMBUPSTIPVMECFMPDLFEJOBDDPSEBODFEXJUI&/. ・-PDBUJPOTXIFSFDPTNFUJDPSTQFDJBMTQSBZTBSFPGUFOVTFE ● %FUFSNJOF SFGSJH
● 5BLFDBSFXIFODBSSZJOHUIFVOJUCZIBOE ・-PDBUJPOTXJUIEJSFDUFYQPTVSFPGPJMNJTUBOETUFBNTVDIBTLJUDIFOBOENBDIJOFQMBOU
*GUIFVOJUXFJHIUTNPSFUIBOLH
JUNVTUCFDBSSJFECZUXPPSNPSFQFSTPOT%POPUDBSSZCZUIFQMBTUJDTUSBQT
BMXBZTVTFUIFDBSSZIBOEMFXIFODBSSZJOHUIF ・-PDBUJPOTXIFSFBOZNBDIJOFTXIJDIHFOFSBUFIJHIGSFRVFODZIBSNPOJDTBSFVTFE
VOJUCZIBOE6TFHMPWFTUPNJOJNJ[FUIFSJTLPGDVUTCZUIFBMVNJOVNmOT ・-PDBUJPOTXJUITBMUZBUNPTQIFSFTTVDIBTDPBTUMJOFT
・-PDBUJPOTXJUIIFBWZTOPX *GJOTUBMMFE
CFTVSFUPQSPWJEFCBTFnBNFBOETOPXIPPENFOUJPOFEJOUIFNBOVBM
● %JTQPTFPGBOZQBDLJOHNBUFSJBMTDPSSFDUMZ ・-PDBUJPOTXIFSFUIFVOJUJTFYQPTFEUPDIJNOFZTNPLF
"OZSFNBJOJOHQBDLJOHNBUFSJBMTDBODBVTFQFSTPOBMJOKVSZBTJUDPOUBJOTOBJMTBOEXPPE"OEUPBWPJEEBOHFSPGTVGGPDBUJPO
CFTVSFUPLFFQUIFQMBTUJD ・-PDBUJPOTBUIJHIBMUJUVEF NPSFUIBONIJHI
XSBQQFSBXBZGSPNDIJMESFOBOEUPEJTQPTFBGUFSUFBSJUVQ ・-PDBUJPOTXJUIBNNPOJDBUNPTQIFSFT
● 1BZBUUFOUJPOOPUUPEBNBHFUIFESBJOQBOCZXFMETQBUUFSXIFOXFMEJOHXPSLJTEPOFOFBSUIFJOEPPSVOJU ・-PDBUJPOTXIFSFIFBUSBEJBUJPOGSPNPUIFSIFBUTPVSDFDBOBGGFDUUIFVOJU
*GXFMETQBUUFSFOUFSFEJOUPUIFJOEPPSVOJUEVSJOHXFMEJOHXPSL
JUDBODBVTFQJOIPMFJOESBJOQBOBOESFTVMUJOXBUFSMFBLBHF5PQSFWFOUTVDIEBNBHF
LFFQUIFJOEPPSVOJUJOJUTQBDLJOHPSDPWFSJU ・-PDBUJPOTXJUIPVUHPPEBJSDJSDVMBUJPO
● #FTVSFUPJOTVMBUFUIFSFGSJHFSBOUQJQFTTPBTOPUUPDPOEFOTFUIFBNCJFOUBJSNPJTUVSFPOUIFN ・-PDBUJPOTXJUIBOZPCTUBDMFTXIJDIDBOQSFWFOUJOMFUBOEPVUMFUBJSPGUIFVOJU *O UIF DBTF P
*OTVGmDJFOUJOTVMBUJPODBODBVTFDPOEFOTBUJPO
XIJDIDBOMFBEUPNPJTUVSFEBNBHFPOUIFDFJMJOH
nPPS
GVSOJUVSFBOEBOZPUIFSWBMVBCMFT ・-PDBUJPOTXIFSFTIPSUDJSDVJUPGBJSDBOPDDVS JODBTFPGNVMUJQMFVOJUTJOTUBMMBUJPO
・-PDBUJPOTXIFSFTUSPOHBJSCMPXTBHBJOTUUIFBJSPVUMFUPGPVUEPPSVOJU
● #FTVSFUPQFSGPSNBJSUJHIUOFTTUFTUCZQSFTTVSJ[JOHXJUIOJUSPHFOHBTBGUFSDPNQMFUFESFGSJHFSBOUQJQJOHXPSL *UDBODBVTFSFNBSLBCMFEFDSFBTFJOQFSGPSNBODF
DPSSPTJPOBOEEBNBHFPGDPNQPOFOUT
NBMGVODUJPOBOEmSF
*GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJUJOUIFFWFOUPGSFGSJHFSBOUMFBLBHFJOUIFTNBMMSPPN
MBDLPGPYZHFODBOPDDVS
XIJDIDBODBVTFTFSJPVTBDDJEFOUT
● %POPUJOTUBMMUIFPVUEPPSVOJUJOUIFMPDBUJPOTMJTUFECFMPX
● 1FSGPSNJOTUBMMBUJPOXPSLQSPQFSMZBDDPSEJOHUPUIJTJOTUBMMBUJPONBOVBM
・-PDBUJPOTXIFSFEJTDIBSHFEIPUBJSPSPQFSBUJOHTPVOEPGUIFPVUEPPSVOJUDBOCPUIFSOFJHICPSIPPE
*NQSPQFSJOTUBMMBUJPODBODBVTFBCOPSNBMWJCSBUJPOTPSJODSFBTFEOPJTFHFOFSBUJPO
・-PDBUJPOTXIFSFPVUMFUBJSPGUIFPVUEPPSVOJUCMPXTEJSFDUMZUPBOBOJNBMPSQMBOUT5IFPVUMFUBJSDBOBGGFDUBEWFSTFMZUPUIFQMBOUFUD *O UIF DBTF
● &BSUIMFBLBHFCSFBLFSNVTUCFJOTUBMMFE ・-PDBUJPOTXIFSFWJCSBUJPODBOCFBNQMJmFEBOEUSBOTNJUUFEEVFUPJOTVGmDJFOUTUSFOHUIPGTUSVDUVSF
*GUIFFBSUIMFBLBHFCSFBLFSJTOPUJOTUBMMFE
JUDBODBVTFmSFPSFMFDUSJDTIPDLT ・-PDBUJPOTXIFSFWJCSBUJPOBOEPQFSBUJPOTPVOEHFOFSBUFECZUIFPVUEPPSVOJUDBOBGGFDUTFSJPVTMZ POUIFXBMMPSBUUIFQMBDFOFBSCFESPPN
$POOFDUJOHUIFDJSDVJUXJUIDPQQFSXJSFPSPUIFSNFUBMUISFBEDBODBVTFVOJUGBJMVSFBOEmSF ・-PDBUJPOTXIFSFESBJOBHFDBOOPUSVOPGGTBGFMZ
● %POPUJOTUBMMUIFVOJUOFBSUIFMPDBUJPOXIFSFMFBLBHFPGDPNCVTUJCMFHBTFTDBOPDDVS *UDBOBGGFDUTVSSPVOEJOHFOWJSPONFOUBOEDBVTFBDMBJN
*GMFBLFEHBTFTBDDVNVMBUFBSPVOEUIFVOJU
JUDBODBVTFmSF ● %POPUVTFUIFVOJUGPSTQFDJBMQVSQPTFTTVDIBTTUPSJOHGPPET
DPPMJOHQSFDJTJPOJOTUSVNFOUTBOEQSFTFSWBUJPOPGBOJNBMT
QMBOUTPSBSU
*UDBODBVTFUIFEBNBHFPGUIFJUFNT
$"65*0/
● %P OPU JOTUBMM UIF VOJU XIFSF DPSSPTJWF HBT TVDI BT TVMGVSPVT BDJE HBT FUD
PS DPNCVTUJCMF HBT TVDI BT UIJOOFS BOE QFUSPMFVN HBTFT
DBO
BDDVNVMBUFPSDPMMFDU
PSXIFSFWPMBUJMFDPNCVTUJCMFTVCTUBODFTBSFIBOEMFE ● %POPUUPVDIBOZCVUUPOTXJUIXFUIBOET
$PSSPTJWFHBTDBODBVTFDPSSPTJPOPGIFBUFYDIBOHFS
CSFBLBHFPGQMBTUJDQBSUTBOEFUD"OEDPNCVTUJCMFHBTDBODBVTFmSF *UDBODBVTFFMFDUSJDTIPDLT
● 4FDVSFBTQBDFGPSJOTUBMMBUJPO
JOTQFDUJPOBOENBJOUFOBODFTQFDJmFEJOUIFNBOVBM ● %POPUUPVDIBOZSFGSJHFSBOUQJQFTXJUIZPVSIBOETXIFOUIFTZTUFNJTJOPQFSBUJPO
*OTVGmDJFOUTQBDFDBOSFTVMUJOBDDJEFOUTVDIBTQFSTPOBMJOKVSZEVFUPGBMMJOHGSPNUIFJOTUBMMBUJPOQMBDF %VSJOHPQFSBUJPOUIFSFGSJHFSBOUQJQFTCFDPNFFYUSFNFMZIPUPSFYUSFNFMZDPMEEFQFOEJOHUIFPQFSBUJOHDPOEJUJPO
BOEJUDBODBVTFCVSOJOKVSZPSGSPTUJOKVSZ
● 8IFOUIFPVUEPPSVOJUJTJOTUBMMFEPOBSPPGPSBIJHIQMBDF
QSPWJEFQFSNBOFOUMBEEFSTBOEIBOESBJMTBMPOHUIFBDDFTTSPVUFBOEGFODFTBOEIBOESBJMTBSPVOEUIFPVUEPPSVOJU
● %POPUDMFBOVQUIFVOJUXJUIXBUFS
*GTBGFUZGBDJMJUJFTBSFOPUQSPWJEFE
JUDBODBVTFQFSTPOBMJOKVSZEVFUPGBMMJOHGSPNUIFJOTUBMMBUJPOQMBDF
● %POPUJOTUBMMOPSVTFUIFTZTUFNDMPTFUPUIFFRVJQNFOUUIBUHFOFSBUFTFMFDUSPNBHOFUJDmFMETPSIJHIGSFRVFODZIBSNPOJDT
*UDBODBVTFFMFDUSJDTIPDLT
3FGSJHFSBOU
● %POPUPQFSBUFUIFPVUEPPSVOJUXJUIBOZBSUJDMFQMBDFEPOJU
&RVJQNFOUTVDIBTJOWFSUFST
TUBOECZHFOFSBUPST
NFEJDBMIJHIGSFRVFODZFRVJQNFOUTBOEUFMFDPNNVOJDBUJPOFRVJQNFOUTDBOBGGFDUUIFTZTUFN
BOEDBVTF
:PVNBZJODVSQSPQFSUZEBNBHFPSQFSTPOBMJOKVSFGSPNBGBMMPGUIFBSUJDMF ● 4FMFDU SFGSJHFSBO
NBMGVODUJPOTBOECSFBLEPXOT5IFTZTUFNDBOBMTPBGGFDUNFEJDBMFRVJQNFOUBOEUFMFDPNNVOJDBUJPOFRVJQNFOU
BOEPCTUSVDUJUTGVODUJPOPSDBVTFKBNNJOH
● %POPUTUFQPOUPUIFPVUEPPSVOJU
BOE NBUFSJBM BT
● %POPUJOTUBMMUIFPVUEPPSVOJUJOBMPDBUJPOXIFSFJOTFDUTBOETNBMMBOJNBMTDBOJOIBCJU
:PVNBZJODVSJOKVSZGSPNBESPQPSGBMM
*OTFDUTBOETNBMMBOJNBMTDBOFOUFSUIFFMFDUSJDQBSUTBOEDBVTFEBNBHFPSmSF*OTUSVDUUIFVTFSUPLFFQUIFTVSSPVOEJOHTDMFBO
0OTJUFQJQJ
*.1035"/
/PUBCJMJBBTBVOJUEFTJHOFEGPS3" %FEJDBUFE 3" UPPMT
Downloaded from www.Manualslib.com
● %P OPU VTF BOZ SFGSJHFSBOU PUIFSmanuals search
UIBO 3" 3" XJMM SJTFengine
UP QSFTTVSF BCPVU UJNFT IJHIFS UIBO UIBU PG B DPOWFOUJPOBM SFGSJHFSBOU B) (BVHF NBOJGPME )PXUPSFNPWF
C) $IBSHF IPTF
●5IF NFBOJOH PG .BSLT VTFE IFSF BSF BT TIPXO CFMPX UIBU UIF CPUU
TOPX DPWFS T
/FWFS EP JU VOEFS BOZ DJSDVNTUBODF "MXBZT EP JU BDDPSEJOH UP UIF JOTUSVDUJPO
●#F TVSF UP DPOmSN OP BOPNBMZ PO UIF FRVJQNFOU CZ DPNNJTTJPOJOH BGUFS DPNQMFUFE JOTUBMMBUJPO BOE FYQMBJO UIF PQFSBUJOH NFUIPET BT XFMM BT UIF NBJOUFOBODF NFUIPET PG UIJT FRVJQNFOU
UP UIF VTFS BDDPSEJOH UP UIF PXOFShT NBOVBM
●,FFQ UIF JOTUBMMBUJPO NBOVBM UPHFUIFS XJUI PXOFShT NBOVBM BU B QMBDF XIFSF BOZ VTFS DBO SFBE BU BOZ UJNF .PSFPWFS JG OFDFTTBSZ
BTL UP IBOE UIFN UP B OFX VTFS
● *OTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEJOTUBMMFS ● %POPUQFSGPSNCSB[JOHXPSLJOUIFBJSUJHIUSPPN
*G UIF VOJU DBO C
*GZPVJOTUBMMUIFTZTUFNCZZPVSTFMG
JUNBZDBVTFTFSJPVTUSPVCMFTVDIBTXBUFSMFBLT
FMFDUSJDTIPDLT
mSFBOEQFSTPOBMJOKVSZ
BTBSFTVMUPGBTZTUFN *UDBODBVTFMBDLPGPYZHFO 4USPOH XJOE DBO
NBMGVODUJPO ● 6TFUIFQSFTDSJCFEQJQFT
nBSFOVUTBOEUPPMTGPS3" PG UIF VOJU EVF U
● *OTUBMMUIFTZTUFNJOGVMMBDDPSEBODFXJUIUIFJOTUSVDUJPONBOVBM 6TJOHFYJTUJOHQBSUT GPS3PS3$
DBODBVTFUIFVOJUGBJMVSFBOETFSJPVTBDDJEFOUTEVFUPCVSTUPGUIFSFGSJHFSBOUDJSDVJU
*ODPSSFDUJOTUBMMBUJPONBZDBVTFCVSTUT
QFSTPOBMJOKVSZ
XBUFSMFBLT
FMFDUSJDTIPDLTBOEmSF ● 5JHIUFO UIF nBSF OVU CZ VTJOH EPVCMF TQBOOFST BOE UPSRVF XSFODI BDDPSEJOH UP QSFTDSJCFE NFUIPE #F TVSF OPU UP *OTUBMM UIF PVUMF
● 6TFUIFPSJHJOBMBDDFTTPSJFTBOEUIFTQFDJmFEDPNQPOFOUTGPSJOTUBMMBUJPO UJHIUFOUIFnBSFOVUUPPNVDI VOJU UP GBDF B
*G QBSUT PUIFS UIBO UIPTF QSFTDSJCFE CZ VT BSF VTFE
*U NBZ DBVTF GBMM PG UIF VOJU
XBUFS MFBLT
FMFDUSJD TIPDLT
mSF
SFGSJHFSBOU MFBL
TVCTUBOEBSE -PPTFnBSFDPOOFDUJPOPSEBNBHFPOUIFnBSFQBSUCZUJHIUFOJOHXJUIFYDFTTUPSRVFDBODBVTFCVSTUPSSFGSJHFSBOUMFBLTXIJDI QSPWJEF B GFOD
QFSGPSNBODF
DPOUSPMGBJMVSFBOEQFSTPOBMJOKVSZ NBZSFTVMUJOMBDLPGPYZHFO
● 8IFOJOTUBMMJOHJOTNBMMSPPNT
UBLFQSFWFOUJPONFBTVSFTOPUUPFYDFFEUIFEFOTJUZMJNJUPGSFGSJHFSBOUJOUIFFWFOUPGMFBLBHFBDDPSEBODF ● %POPUPQFOUIFTFSWJDFWBMWFTGPSMJRVJEMJOFBOEHBTMJOFVOUJMDPNQMFUFESFGSJHFSBOUQJQJOHXPSL
BJSUJHIUOFTTUFTU
XJUI*40 BOEFWBDVBUJPO
$POTVMUUIFFYQFSUBCPVUQSFWFOUJPONFBTVSFT*GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJUJOUIFFWFOUPGMFBLBHF
MBDLPGPYZHFODBOPDDVS
XIJDI *GUIFDPNQSFTTPSJTPQFSBUFEJOTUBUFPGPQFOJOH TFSWJDFWBMWFTCFGPSFDPNQMFUFEDPOOFDUJPOPGSFGSJHFSBOU QJQJOH XPSL
ZPV
DBODBVTFTFSJPVTBDDJEFOUT NBZJODVSGSPTUCJUFPSJOKVSZGSPNBOBCSVQUSFGSJHFSBOUPVUnPXBOEBJSDBOCFTVDLFEJOUPSFGSJHFSBOUDJSDVJU
XIJDIDBODBVTF
● 7FOUJMBUFUIFXPSLJOHBSFBXFMMJOUIFFWFOUPGSFGSJHFSBOUMFBLBHFEVSJOHJOTUBMMBUJPO CVSTUPSQFSTPOBMJOKVSZEVFUPBOPNBMPVTMZIJHIQSFTTVSFJOUIFSFGSJHFSBOU
*GUIFSFGSJHFSBOUDPNFTJOUPDPOUBDUXJUIOBLFEnBNFT
QPJTPOPVTHBTJTQSPEVDFE ● 0OMZVTFQSFTDSJCFEPQUJPOBMQBSUT5IFJOTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEJOTUBMMFS
● "GUFSDPNQMFUFEJOTUBMMBUJPO
DIFDLUIBUOPSFGSJHFSBOUMFBLTGSPNUIFTZTUFN *GZPVJOTUBMMUIFTZTUFNCZZPVSTFMG
JUDBODBVTFTFSJPVTUSPVCMFTVDIBTXBUFSMFBLT
FMFDUSJDTIPDLT
mSF 0WFS N
*GSFGSJHFSBOUMFBLTJOUPUIFSPPNBOEDPNFTJOUPDPOUBDUXJUIBOPWFOPSPUIFSIPUTVSGBDF
QPJTPOPVTHBTJTQSPEVDFE ● %POPUQFSGPSNBOZDIBOHFPGQSPUFDUJWFEFWJDFJUTFMGPSJUTTFUVQDPOEJUJPO
● )BOHVQUIFVOJUBUUIFTQFDJmFEQPJOUTXJUISPQFTXIJDIDBOTVQQPSUUIFXFJHIUJOMJGUJOHGPSQPSUBHF"OEUPBWPJEKPMUJOHPVUPGBMJHONFOU
5IF GPSDFE PQFSBUJPO CZ TIPSUDJSDVJUJOH QSPUFDUJWF EFWJDF PG QSFTTVSF TXJUDI BOE UFNQFSBUVSF DPOUSPMMFS PS UIF VTF PG OPO
3&'3*(&3
CFTVSFUPIBOHVQUIFVOJUBUQPJOUTVQQPSU TQFDJmFEDPNQPOFOUDBODBVTFmSFPSCVSTU
"OJNQSPQFSNBOOFSPGQPSUBHFTVDIBTQPJOUTVQQPSUDBODBVTFEFBUIPSTFSJPVTQFSTPOBMJOKVSZEVFUPGBMMJOHPGUIFVOJU ● #FTVSFUPTXJUDIPGGUIFQPXFSTVQQMZJOUIFFWFOUPGJOTUBMMBUJPO
JOTQFDUJPOPSTFSWJDJOH
● *OTUBMMUIFVOJUJOBMPDBUJPOXJUIHPPETVQQPSU *GUIFQPXFSTVQQMZJTOPUTIVUPGG
UIFSFJTBSJTLPGFMFDUSJDTIPDLT
VOJUGBJMVSFPSQFSTPOBMJOKVSZEVFUPUIFVOFYQFDUFETUBSUPGGBO
6OTVJUBCMFJOTUBMMBUJPOMPDBUJPOTDBODBVTFUIFVOJUUPGBMMBOEDBVTFNBUFSJBMEBNBHFBOEQFSTPOBMJOKVSZ ● $POTVMUUIFEFBMFSPSBOFYQFSUSFHBSEJOHSFNPWBMPGUIFVOJU
● &OTVSFUIFVOJUJTTUBCMFXIFOJOTUBMMFE
TPUIBUJUDBOXJUITUBOEFBSUIRVBLFTBOETUSPOHXJOET *ODPSSFDUJOTUBMMBUJPODBODBVTFXBUFSMFBLT
FMFDUSJDTIPDLTPSmSF
3FTUSJDUJPO
6OTVJUBCMFJOTUBMMBUJPOMPDBUJPOTDBODBVTFUIFVOJUUPGBMMBOEDBVTFNBUFSJBMEBNBHFBOEQFSTPOBMJOKVSZ ● 4UPQUIFDPNQSFTTPSCFGPSFDMPTJOHWBMWFBOEEJTDPOOFDUJOHSFGSJHFSBOUQJQFTJODBTFPGQVNQEPXOPQFSBUJPO ● $IFDL UIF GPMMPX
● 5IFFMFDUSJDBMJOTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEFMFDUSJDJBOJOBDDPSEBODFXJUIiUIFOPSNGPSFMFDUSJDBMXPSLwBOEiOBUJPOBM *G EJTDPOOFDUJOH SFGSJHFSBOU QJQFT JO TUBUF PG PQFOJOH TFSWJDF WBMWFT CFGPSF DPNQSFTTPS TUPQQJOH
ZPV NBZ JODVS GSPTU CJUF PS
JOKVSZGSPNBOBCSVQUSFGSJHFSBOUPVUnPXBOEBJSDBOCFTVDLFE
XIJDIDBODBVTFCVSTUPSQFSTPOBMJOKVSZEVFUPBOPNBMPVTMZ ● 0CTFSWF UIF GPMMP
XJSJOHSFHVMBUJPOw
BOEUIFTZTUFNNVTUCFDPOOFDUFEUPUIFEFEJDBUFEDJSDVJU
1PXFSTVQQMZXJUIJOTVGmDJFOUDBQBDJUZBOEJODPSSFDUGVODUJPOEPOFCZJNQSPQFSXPSLDBODBVTFFMFDUSJDTIPDLTBOEmSF
IJHIQSFTTVSFJOUIFSFGSJHFSBOUDJSDVJU
● #FTVSFUPTIVUPGGUIFQPXFSCFGPSFTUBSUJOHFMFDUSJDBMXPSL ● &OTVSFUIBUOPBJSFOUFSTJOUIFSFGSJHFSBOUDJSDVJUXIFOUIFVOJUJTJOTUBMMFEBOESFNPWFE
'BJMVSFUPTIVUPGGUIFQPXFSDBODBVTFFMFDUSJDTIPDLT
VOJUGBJMVSFPSJODPSSFDUGVODUJPOPGFRVJQNFOU *G BJS FOUFST JO UIF SFGSJHFSBOU DJSDVJU
UIF QSFTTVSF JO UIF SFGSJHFSBOU DJSDVJU CFDPNFT UPP IJHI
XIJDI DBO DBVTF CVSTU BOE
QFSTPOBMJOKVSZ
● #FTVSFUPVTFUIFDBCMFTDPOGPSNFEUPTBGFUZTUBOEBSEBOEDBCMFBNQBDJUZGPSQPXFSEJTUSJCVUJPOXPSL 0OFXBZQJQFMFO
6ODPOGPSNBCMFDBCMFTDBODBVTFFMFDUSJDMFBL
BOPNBMPVTIFBUQSPEVDUJPOPSmSF ● %POPUSVOUIFVOJUXJUISFNPWFEQBOFMTPSQSPUFDUJPOT
5PVDIJOHSPUBUJOHFRVJQNFOUT
IPUTVSGBDFTPSIJHIWPMUBHFQBSUTDBODBVTFQFSTPOBMJOKVSZEVFUPFOUSBQNFOU
CVSOPSFMFDUSJD .BJOQJ
● 6TFUIFQSFTDSJCFEDBCMFTGPSFMFDUSJDBMDPOOFDUJPO
UJHIUFOUIFDBCMFTTFDVSFMZJOUFSNJOBMCMPDLBOESFMJFWFUIFDBCMFTDPSSFDUMZUPQSFWFOU TIPDLT
PWFSMPBEJOHUIFUFSNJOBMCMPDLT
-PPTFDPOOFDUJPOTPSDBCMFNPVOUJOHTDBODBVTFBOPNBMPVTIFBUQSPEVDUJPOPSmSF ● #FTVSFUPmYVQUIFTFSWJDFQBOFMT
*ODPSSFDUmYJOHDBODBVTFFMFDUSJDTIPDLTPSmSFEVFUPJOUSVTJPOPGEVTUPSXBUFS
● "SSBOHFUIFXJSJOHJOUIFDPOUSPMCPYTPUIBUJUDBOOPUCFQVTIFEVQGVSUIFSJOUPUIFCPY*OTUBMMUIFTFSWJDFQBOFMDPSSFDUMZ %
*ODPSSFDUJOTUBMMBUJPONBZSFTVMUJOPWFSIFBUJOHBOEmSF ● %POPUQFSGPSNBOZSFQBJSTPSNPEJmDBUJPOTCZZPVSTFMG$POTVMUUIFEFBMFSJGUIFVOJUSFRVJSFTSFQBJS
*GZPVSFQBJSPSNPEJGZUIFVOJU
JUDBODBVTFXBUFSMFBLT
FMFDUSJDTIPDLTPSmSF
&MFWBUJPOEJGG
JOEPPSBOEPV
$"65*0/
● $BSSZPVUUIFFMFDUSJDBMXPSLGPSHSPVOEMFBEXJUIDBSF ● %POPUVTFUIFCBTFnBNFGPSPVUEPPSVOJUXIJDIJTDPSSPEFEPSEBNBHFEEVFUPMPOHQFSJPETPGPQFSBUJPO
%POPUDPOOFDUUIFHSPVOEMFBEUPUIFHBTMJOF
XBUFSMJOF
MJHIUOJOHDPOEVDUPSPSUFMFQIPOFMJOFhTHSPVOEMFBE*ODPSSFDUHSPVOEJOHDBODBVTFVOJUGBVMUTTVDIBT
FMFDUSJDTIPDLTEVFUPTIPSUDJSDVJUJOH/FWFSDPOOFDUUIFHSPVOEJOHXJSFUPBHBTQJQFCFDBVTFJGHBTMFBLT
JUDPVMEDBVTFFYQMPTJPOPSJHOJUJPO
6TJOHBOPMEBOEEBNBHFCBTFnBNFDBODBVTFUIFVOJUGBMMJOHEPXOBOEDBVTFQFSTPOBMJOKVSZ $"65*0/
● %POPUJOTUBMMUIFVOJUJOUIFMPDBUJPOTMJTUFECFMPX
● 6TFUIFDJSDVJUCSFBLFSGPSBMMQPMFXJUIDPSSFDUDBQBDJUZ ・-PDBUJPOTXIFSFDBSCPOmCFS
NFUBMQPXEFSPSBOZQPXEFSJTnPBUJOH
6TJOHUIFJODPSSFDUDJSDVJUCSFBLFS
JUDBODBVTFUIFVOJUNBMGVODUJPOBOEmSF ・-PDBUJPOTXIFSFBOZTVCTUBODFTUIBUDBOBGGFDUUIFVOJUTVDIBTTVMQIJEFHBT
DIMPSJEFHBT
BDJEBOEBMLBMJOFDBOPDDVS
%FUFSNJOBU
● *OTUBMMJTPMBUPSPSEJTDPOOFDUTXJUDIPOUIFQPXFSTVQQMZXJSJOHJOBDDPSEBODFXJUIUIFMPDBMDPEFTBOESFHVMBUJPOT ・7FIJDMFTBOETIJQT
5IFJTPMBUPSTIPVMECFMPDLFEJOBDDPSEBODFEXJUI&/. ・-PDBUJPOTXIFSFDPTNFUJDPSTQFDJBMTQSBZTBSFPGUFOVTFE ● %FUFSNJOF SFGSJH
● 5BLFDBSFXIFODBSSZJOHUIFVOJUCZIBOE ・-PDBUJPOTXJUIEJSFDUFYQPTVSFPGPJMNJTUBOETUFBNTVDIBTLJUDIFOBOENBDIJOFQMBOU
*GUIFVOJUXFJHIUTNPSFUIBOLH
JUNVTUCFDBSSJFECZUXPPSNPSFQFSTPOT%POPUDBSSZCZUIFQMBTUJDTUSBQT
BMXBZTVTFUIFDBSSZIBOEMFXIFODBSSZJOHUIF ・-PDBUJPOTXIFSFBOZNBDIJOFTXIJDIHFOFSBUFIJHIGSFRVFODZIBSNPOJDTBSFVTFE
VOJUCZIBOE6TFHMPWFTUPNJOJNJ[FUIFSJTLPGDVUTCZUIFBMVNJOVNmOT ・-PDBUJPOTXJUITBMUZBUNPTQIFSFTTVDIBTDPBTUMJOFT
・-PDBUJPOTXJUIIFBWZTOPX *GJOTUBMMFE
CFTVSFUPQSPWJEFCBTFnBNFBOETOPXIPPENFOUJPOFEJOUIFNBOVBM
● %JTQPTFPGBOZQBDLJOHNBUFSJBMTDPSSFDUMZ ・-PDBUJPOTXIFSFUIFVOJUJTFYQPTFEUPDIJNOFZTNPLF
"OZSFNBJOJOHQBDLJOHNBUFSJBMTDBODBVTFQFSTPOBMJOKVSZBTJUDPOUBJOTOBJMTBOEXPPE"OEUPBWPJEEBOHFSPGTVGGPDBUJPO
CFTVSFUPLFFQUIFQMBTUJD ・-PDBUJPOTBUIJHIBMUJUVEF NPSFUIBONIJHI
XSBQQFSBXBZGSPNDIJMESFOBOEUPEJTQPTFBGUFSUFBSJUVQ ・-PDBUJPOTXJUIBNNPOJDBUNPTQIFSFT
● 1BZBUUFOUJPOOPUUPEBNBHFUIFESBJOQBOCZXFMETQBUUFSXIFOXFMEJOHXPSLJTEPOFOFBSUIFJOEPPSVOJU ・-PDBUJPOTXIFSFIFBUSBEJBUJPOGSPNPUIFSIFBUTPVSDFDBOBGGFDUUIFVOJU
*GXFMETQBUUFSFOUFSFEJOUPUIFJOEPPSVOJUEVSJOHXFMEJOHXPSL
JUDBODBVTFQJOIPMFJOESBJOQBOBOESFTVMUJOXBUFSMFBLBHF5PQSFWFOUTVDIEBNBHF
LFFQUIFJOEPPSVOJUJOJUTQBDLJOHPSDPWFSJU ・-PDBUJPOTXJUIPVUHPPEBJSDJSDVMBUJPO
● #FTVSFUPJOTVMBUFUIFSFGSJHFSBOUQJQFTTPBTOPUUPDPOEFOTFUIFBNCJFOUBJSNPJTUVSFPOUIFN ・-PDBUJPOTXJUIBOZPCTUBDMFTXIJDIDBOQSFWFOUJOMFUBOEPVUMFUBJSPGUIFVOJU *O UIF DBTF P
*OTVGmDJFOUJOTVMBUJPODBODBVTFDPOEFOTBUJPO
XIJDIDBOMFBEUPNPJTUVSFEBNBHFPOUIFDFJMJOH
nPPS
GVSOJUVSFBOEBOZPUIFSWBMVBCMFT ・-PDBUJPOTXIFSFTIPSUDJSDVJUPGBJSDBOPDDVS JODBTFPGNVMUJQMFVOJUTJOTUBMMBUJPO
・-PDBUJPOTXIFSFTUSPOHBJSCMPXTBHBJOTUUIFBJSPVUMFUPGPVUEPPSVOJU
● #FTVSFUPQFSGPSNBJSUJHIUOFTTUFTUCZQSFTTVSJ[JOHXJUIOJUSPHFOHBTBGUFSDPNQMFUFESFGSJHFSBOUQJQJOHXPSL *UDBODBVTFSFNBSLBCMFEFDSFBTFJOQFSGPSNBODF
DPSSPTJPOBOEEBNBHFPGDPNQPOFOUT
NBMGVODUJPOBOEmSF
*GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJUJOUIFFWFOUPGSFGSJHFSBOUMFBLBHFJOUIFTNBMMSPPN
MBDLPGPYZHFODBOPDDVS
XIJDIDBODBVTFTFSJPVTBDDJEFOUT
● %POPUJOTUBMMUIFPVUEPPSVOJUJOUIFMPDBUJPOTMJTUFECFMPX
● 1FSGPSNJOTUBMMBUJPOXPSLQSPQFSMZBDDPSEJOHUPUIJTJOTUBMMBUJPONBOVBM
・-PDBUJPOTXIFSFEJTDIBSHFEIPUBJSPSPQFSBUJOHTPVOEPGUIFPVUEPPSVOJUDBOCPUIFSOFJHICPSIPPE
*NQSPQFSJOTUBMMBUJPODBODBVTFBCOPSNBMWJCSBUJPOTPSJODSFBTFEOPJTFHFOFSBUJPO
・-PDBUJPOTXIFSFPVUMFUBJSPGUIFPVUEPPSVOJUCMPXTEJSFDUMZUPBOBOJNBMPSQMBOUT5IFPVUMFUBJSDBOBGGFDUBEWFSTFMZUPUIFQMBOUFUD *O UIF DBTF
● &BSUIMFBLBHFCSFBLFSNVTUCFJOTUBMMFE ・-PDBUJPOTXIFSFWJCSBUJPODBOCFBNQMJmFEBOEUSBOTNJUUFEEVFUPJOTVGmDJFOUTUSFOHUIPGTUSVDUVSF
*GUIFFBSUIMFBLBHFCSFBLFSJTOPUJOTUBMMFE
JUDBODBVTFmSFPSFMFDUSJDTIPDLT ・-PDBUJPOTXIFSFWJCSBUJPOBOEPQFSBUJPOTPVOEHFOFSBUFECZUIFPVUEPPSVOJUDBOBGGFDUTFSJPVTMZ POUIFXBMMPSBUUIFQMBDFOFBSCFESPPN
$POOFDUJOHUIFDJSDVJUXJUIDPQQFSXJSFPSPUIFSNFUBMUISFBEDBODBVTFVOJUGBJMVSFBOEmSF ・-PDBUJPOTXIFSFESBJOBHFDBOOPUSVOPGGTBGFMZ
● %POPUJOTUBMMUIFVOJUOFBSUIFMPDBUJPOXIFSFMFBLBHFPGDPNCVTUJCMFHBTFTDBOPDDVS *UDBOBGGFDUTVSSPVOEJOHFOWJSPONFOUBOEDBVTFBDMBJN
*GMFBLFEHBTFTBDDVNVMBUFBSPVOEUIFVOJU
JUDBODBVTFmSF ● %POPUVTFUIFVOJUGPSTQFDJBMQVSQPTFTTVDIBTTUPSJOHGPPET
DPPMJOHQSFDJTJPOJOTUSVNFOUTBOEQSFTFSWBUJPOPGBOJNBMT
QMBOUTPSBSU
*UDBODBVTFUIFEBNBHFPGUIFJUFNT
$"65*0/
● %P OPU JOTUBMM UIF VOJU XIFSF DPSSPTJWF HBT TVDI BT TVMGVSPVT BDJE HBT FUD
PS DPNCVTUJCMF HBT TVDI BT UIJOOFS BOE QFUSPMFVN HBTFT
DBO
BDDVNVMBUFPSDPMMFDU
PSXIFSFWPMBUJMFDPNCVTUJCMFTVCTUBODFTBSFIBOEMFE ● %POPUUPVDIBOZCVUUPOTXJUIXFUIBOET
$PSSPTJWFHBTDBODBVTFDPSSPTJPOPGIFBUFYDIBOHFS
CSFBLBHFPGQMBTUJDQBSUTBOEFUD"OEDPNCVTUJCMFHBTDBODBVTFmSF *UDBODBVTFFMFDUSJDTIPDLT
● 4FDVSFBTQBDFGPSJOTUBMMBUJPO
JOTQFDUJPOBOENBJOUFOBODFTQFDJmFEJOUIFNBOVBM ● %POPUUPVDIBOZSFGSJHFSBOUQJQFTXJUIZPVSIBOETXIFOUIFTZTUFNJTJOPQFSBUJPO
-
● %POPUDMFBOVQUIFVOJUXJUIXBUFS
*GTBGFUZGBDJMJUJFTBSFOPUQSPWJEFE
JUDBODBVTFQFSTPOBMJOKVSZEVFUPGBMMJOHGSPNUIFJOTUBMMBUJPOQMBDF
● %POPUJOTUBMMOPSVTFUIFTZTUFNDMPTFUPUIFFRVJQNFOUUIBUHFOFSBUFTFMFDUSPNBHOFUJDmFMETPSIJHIGSFRVFODZIBSNPOJDT
*UDBODBVTFFMFDUSJDTIPDLT
3FGSJHFSBOU
● %POPUPQFSBUFUIFPVUEPPSVOJUXJUIBOZBSUJDMFQMBDFEPOJU
&RVJQNFOUTVDIBTJOWFSUFST
TUBOECZHFOFSBUPST
NFEJDBMIJHIGSFRVFODZFRVJQNFOUTBOEUFMFDPNNVOJDBUJPOFRVJQNFOUTDBOBGGFDUUIFTZTUFN
BOEDBVTF
:PVNBZJODVSQSPQFSUZEBNBHFPSQFSTPOBMJOKVSFGSPNBGBMMPGUIFBSUJDMF ● 4FMFDU SFGSJHFSBO
NBMGVODUJPOTBOECSFBLEPXOT5IFTZTUFNDBOBMTPBGGFDUNFEJDBMFRVJQNFOUBOEUFMFDPNNVOJDBUJPOFRVJQNFOU
BOEPCTUSVDUJUTGVODUJPOPSDBVTFKBNNJOH
● %POPUTUFQPOUPUIFPVUEPPSVOJU
BOE NBUFSJBM BT
● %POPUJOTUBMMUIFPVUEPPSVOJUJOBMPDBUJPOXIFSFJOTFDUTBOETNBMMBOJNBMTDBOJOIBCJU
:PVNBZJODVSJOKVSZGSPNBESPQPSGBMM
*OTFDUTBOETNBMMBOJNBMTDBOFOUFSUIFFMFDUSJDQBSUTBOEDBVTFEBNBHFPSmSF*OTUSVDUUIFVTFSUPLFFQUIFTVSSPVOEJOHTDMFBO
0OTJUFQJQJ
*.1035"/
/PUBCJMJBBTBVOJUEFTJHOFEGPS3" %FEJDBUFE 3" UPPMT
● %P OPU VTF BOZ SFGSJHFSBOU PUIFS UIBO 3" 3" XJMM SJTF UP QSFTTVSF BCPVU UJNFT IJHIFS UIBO UIBU PG B DPOWFOUJPOBM SFGSJHFSBOU B) (BVHF NBOJGPME )PXUPSFNPWF
" DZMJOEFS DPOUBJOJOH 3" IBT B QJOL JOEJDBUJPO NBSL PO UIF UPQ C) $IBSHF IPTF
● " VOJU EFTJHOFE GPS 3" IBT BEPQUFE B EJGGFSFOU TJ[F JOEPPS VOJU PQFSBUJPO WBMWF DIBSHF QPSU BOE B EJGGFSFOU TJ[F DIFDL KPJOU QSPWJEFE JO UIF VOJU UP QSFWFOU UIF DIBSHJOH PG B XSPOH SFGSJHFSBOU CZ D) &MFDUSPOJD TDBMF GPS SFGSJHFSBOU DIBSHJOH ● $BSSZ PVU UIF PO
NJTUBLF 5IF QSPDFTTFE EJNFOTJPO PG UIF nBSFE QBSU PG B SFGSJHFSBOU QJQF BOE B nBSF OVUhT QBSBMMFM TJEF NFBTVSFNFOU IBWF BMTP CFFO BMUFSFE UP SBJTF TUSFOHUI BHBJOTU QSFTTVSF "DDPSEJOHMZ
ZPV BSF ● (JWF TVGmDJFOU Q
E) 5PSRVF XSFODI
SFRVJSFE UP BSSBOHF EFEJDBUFE 3" UPPMT MJTUFE JO UIF UBCMF PO UIF SJHIU CFGPSF JOTUBMMJOH PS TFSWJDJOH UIJT VOJU F) 'MBSF UPPM
XBUFS PS GPSFJHO
● %P OPU VTF B DIBSHF DZMJOEFS 5IF VTF PG B DIBSHF DZMJOEFS XJMM DBVTF UIF SFGSJHFSBOU DPNQPTJUJPO UP DIBOHF
XIJDI SFTVMUT JO QFSGPSNBODF EFHSBEBUJPO ● #FOE B QJQF UP
G) 1SPUSVTJPO DPOUSPM DPQQFS QJQF HBVHF JUT GPSN
● *O DIBSHJOH SFGSJHFSBOU
BMXBZT UBLF JU PVU GSPN B DZMJOEFS JO UIF MJRVJE QIBTF
H) 7BDVVN QVNQ BEBQUFS ● 'MBSF DPOOFDUJPO
● "MM JOEPPS VOJUT NVTU CF NPEFMT EFTJHOFE FYDMVTJWFMZ GPS 3" $IFDL DPOOFDUBCMF JOEPPS VOJU NPEFMT JO B DBUBMPH
FUD " XSPOH JOEPPS VOJU
JG DPOOFDUFE JOUP UIF TZTUFN
XJMM JNQBJS QSPQFS TZTUFN
PQFSBUJPO
I) (BT MFBL EFUFDUPS OVU POUP JU 'MB
XF SFDPNNFOE
BMTP CF VTFE CZ
)"6-"(&"/%*/45"--"5*0/ 5BLFQBSUJDVMBSDBSFJODBSSZJOHJOPSNPWJOHUIFVOJU
BOEBMXBZTQFSGPSNTVDIBOPQFSBUJPOXJUIUXPPSNPSFQFSTPOT
● 5IF QJQF TIPVME
●5JHIUFOBnBSFKP
'10 • PAC-DB-142
8IFO B VOJU JT IPJTUFE XJUI TMJOHT GPS IBVMBHF
UBLF JOUP DPOTJEFSBUJPO UIF PGGTFU PG JUT HSBWJUZ $"65*0/
$"65*0/ DFOUFS QPTJUJPO *G OPU QSPQFSMZ CBMBODFE
UIF VOJU DBO CF UISPXO PGGCBMBODF BOE GBMM )FBWZ
1BE
%FMJWFSZ
1PSUBHF
● %FMJWFS UIF VOJU BT DMPTF BT QPTTJCMF UP UIF JOTUBMMBUJPO TJUF CFGPSF SFNPWJOH JU GSPN UIF QBDLBHJOH ● 5IF SJHIU IBOE TJEF PG UIF VOJU BT WJFXFE GSPN UIF GSPOU EJGGVTFS TJEF
JT IFBWJFS " QFSTPO
● 8IFO TPNF DPNQFMMJOH SFBTPO OFDFTTJUBUFT UIF VOQBDLJOH PG UIF VOJU CFGPSF JU JT DBSSJFE JO
VTF DBSSZJOH UIF SJHIU IBOE TJEF NVTU UBLF IFFE PG UIJT GBDU " QFSTPO DBSSZJOH UIF MFGU IBOE
OZMPO TMJOHT PS QSPUFDUJWF XPPE QJFDFT TP BT OPU UP EBNBHF UIF VOJU CZ SPQFT MJGUJOH JU TJEF NVTU IPME XJUI IJT SJHIU IBOE UIF IBOEMF QSPWJEFE PO UIF GSPOU QBOFM PG UIF VOJU BOE
8PPEFO QBMMFU XJUI IJT MFGU IBOE UIF DPSOFS DPMVNO TFDUJPO
〇 " QMBDF XIFSF HPPE BJS DJSDVMBUJPO DBO CF TFDVSFE
BOE FOPVHI TFSWJDF TQBDF DBO CF TFDVSFE GPS NBJOUFOBODF BOE TFSWJDF PG UIF VOJU TBGFMZ
〇 " QMBDF XIFSF UIF VOJU XJMM OPU CF BGGFDUFE CZ FMFDUSPNBHOFUJD XBWFT BOEPS IJHIIBSNPOJD XBWFT HFOFSBUFE CZ PUIFS FRVJQNFOU 7 -
*OUBLF
〇" QMBDF XIFSF DIFNJDBM TVCTUBODFT MJLF TVMGVSJD HBT
DIMPSJD HBT
BDJE BOE BMLBMJ JODMVEJOH BNNPOJB
XIJDI DBO IBSN UIF &YBNQMFJOTUBMMBUJPO -
Ⅱ Ⅲ
BUJPOXPSL VOJU
XJMM OPU CF HFOFSBUFE BOE OPU SFNBJO
4J[F Ⅰ
0QFO -
〇" QMBDF XIFSF TUSPOH XJOE XJMM OPU CMPX BHBJOTU UIF PVUMFU BJS CMPX PG UIF VOJU - 0QFO
*OUBLF
- 0QFO
SDF 0VUMFU
$BVUJPO BCPVU TFMFDUJPO PG JOTUBMMBUJPO MPDBUJPO -
TFSWJDF
TQBDF
-
-
*G UIF VOJU JT JOTUBMMFE JO UIF BSFB XIFSF UIF TOPX XJMM BDDVNVMBUF
GPMMPXJOH NFBTVSFT BSF SFRVJSFE
FPVTTNBMMQBSUT 5IF CPUUPN QMBUF PG VOJU BOE JOUBLF
PVUMFU NBZ CF CMPDLFE CZ TOPX
VBM *OTUBMM UIF VOJU PO UIF CBTF TP 1SPWJEF B TOPX IPPE UP UIF PVUEPPS *OTUBMM UIF VOJU VOEFS FBWFT
*OTUBMMBUJPO
UIBU UIF CPUUPN JT IJHIFS UIBO VOJU PO TJUF PS QSPWJEF UIF SPPG PO TJUF
TOPX DPWFS TVSGBDF 3FHBSEJOH PVUMJOF PG B TOPX IPPE
① "ODIPSCPMUmYFEQPTJUJPO ② /PUBCJMJBGPSJOTUBMMBUJPO
SFGFS UP PVS UFDIOJDBM NBOVBM
*OUBLF 'BTUFOXJUICPMUT
.
4JODF ESBJO XBUFS HFOFSBUFE CZ EFGSPTU DPOUSPM NBZ GSFF[F
GPMMPXJOH NFBTVSFT BSF SFRVJSFE 0VUMFU
6TFBUIJDLFSCMPDLUP
● %POUFYFDVUFESBJOQJQJOHXPSLCZVTJOHBESBJOFMCPXBOEESBJOHSPNNFUT PQUJPOBMQBSUT
<3FGFSUP%SBJOQJQJOHXPSL> 6TFBMPOHCMPDLUP
FYUFOEUIFXJEUI BODIPSEFFQFS
● 3FDPNNFOETFUUJOH%FGSPTU$POUSPM 48
BOE4OPX(VBSE'BO$POUSPM 48
<3FGFSUP4FUUJOH48
48>
*G UIF VOJU DBO CF BGGFDUFE CZ TUSPOH XJOE
GPMMPXJOH NFBTVSFT BSF SFRVJSFE "ODIPSCPMUQPTJUJPO
-
GSJHFSBOUDJSDVJU ● 5IFQSPUSVTJPOPGBOBODIPSCPMUPOUIFGSPOUTJEFNVTUCFLFQUXJUIJONN
*OTUBMM UIF PVUMFU BJS CMPX TJEF PG UIF *OTUBMM UIF PVUMFU BJS CMPX TJEF PG 5IF VOJU TIPVME CF JOTUBMMFE PO ● 4FDVSFMZJOTUBMMUIFVOJUTPUIBUJUEPFTOPUGBMMPWFSEVSJOHFBSUIRVBLFTPSTUSPOHXJOET
FUD
E #F TVSF OPU UP
VOJU UP GBDF B XBMM PG CVJMEJOH
PS UIF VOJU JO B QPTJUJPO QFSQFOEJDVMBS UIF TUBCMF BOE MFWFM GPVOEBUJPO ● 3FGFSUPUIFBCPWFJMMVTUSBUJPOTGPSJOGPSNBUJPOSFHBSEJOHDPODSFUFGPVOEBUJPOT
HFSBOUMFBLTXIJDI QSPWJEF B GFODF PS B XJOECSFBL TDSFFO UP UIF EJSFDUJPO PG XJOE *G UIF GPVOEBUJPO JT OPU MFWFM
● *OTUBMMUIFVOJUJOBMFWFMBSFB 8JUIBHSBEJFOUPGNNPSMFTT
QFDUFETUBSUPGGBO
3&'3*(&3"/51*1*/(803,
3FTUSJDUJPOT PO VOJU JOTUBMMBUJPO BOE VTF 4JOHMFUZQF *OEPPSVOJU
PQFSBUJPO ● $IFDL UIF GPMMPXJOH QPJOUT JO MJHIU PG UIF JOEPPS VOJU TQFDJmDBUJPOT BOE UIF JOTUBMMBUJPO TJUF
JODVS GSPTU CJUF PS
EVFUPBOPNBMPVTMZ ● 0CTFSWF UIF GPMMPXJOH SFTUSJDUJPOT PO VOJU JOTUBMMBUJPO BOE VTF *NQSPQFS JOTUBMMBUJPO DBO SFTVMU JO B DPNQSFTTPS GBJMVSF PS QFSGPSNBODF EFHSBEBUJPO )
%JNFOTJPOBM .BSLTBQQFBSJOHJOUIFESBXJOHPOUIFSJHIU
3FTUSJDUJPOT
O DBVTF CVSTU BOE SFTUSJDUJPOT 4JOHMFUZQF 5XJOUZQF
-
'10 • PAC-DB-142
0OFXBZQJQFMFOHUIPGSFGSJHFSBOUQJQJOH - -+-+-
.PEFM7 NPSMFTT 0VUEPPSVOJU
FOU
CVSOPSFMFDUSJD .BJOQJQFMFOHUI - -
0OFXBZQJQFMFOHUIBGUFSUIFmSTUCSBODIJOHQPJOU NPSMFTT − -,- 5XJOUZQF
*OEPPSVOJU 5IFVOJUPGXIJDIFMFWBUJPOEJGGFSFODFGSPNUIFPVUEPPSVOJUJTUIFMBSHFTU
%FUFSNJOBUJPO PG QJQF TJ[F 0VUEPPSVOJU - SJTFS
● %FUFSNJOF SFGSJHFSBOU QJQF TJ[F QVSTVBOU UP UIF GPMMPXJOH HVJEFMJOFT CBTFE PO UIF JOEPPS VOJU TQFDJmDBUJPOT
"CPVUCSB[JOH
.PEFM7
(BTQJQF -JRVJEQJQF #SB[JOH NVTU CF QFSGPSNFE VOEFS B OJUSPHFO HBT nPX
φ φ 8JUIPVU OJUSPHFO HBT
B MBSHF RVBOUJUZ PG GPSFJHO NBUUFST PYJEJ[FE mMN
BSF DSFBUFE
0VUEPPSVOJUDPOOFDUFE 'MBSF 'MBSF DBVTJOH B DSJUJDBM GBJMVSF GSPN DBQJMMBSZ UVCF PS FYQBOTJPO WBMWF DMPHHJOH
3FGSJHFSBOUQJQJOH CSBODIQJQF-
φ φ
1SJNBSZTJEF 4FDPOEBSZTJEF
φ φ 1MVHUIFFOEPGUIFQJQFXJUIUBQF
PSPUIFS
*OEPPSVOJUDPOOFDUFE 4UBUJPOWBMWF
*O UIF DBTF PG B TJOHMF UZQF NBUFSJBM
BOEmMMUIFQJQFXJUIOJUSPHFOHBT
.1B
$BQBDJUZPGJOEPPSVOJU .PEFM7
</> )BOE
5BQJOH
#SBODIJOHQJQFTFU %*48"
/JUSPHFO
3FGSJHFSBOUQJQJOH CSBODIQJQF-
-
φ φ /JUSPHFO
*O UIF DBTF PG B UXJO UZQF 3FMJFGWBMWF
HBT
*OEPPSVOJUDPOOFDUFE φ φ 0OMZVTFOJUSPHFO #SB[JOH
ESPPN
HBT /
$BQBDJUZPGJOEPPSVOJU .PEFM7×
3FGSJHFSBOU QJQF XBMM UIJDLOFTT BOE NBUFSJBM 1JQFEJBNFUFS<NN> /05& ● 4FMFDU QJQFT IBWJOH B XBMM UIJDLOFTT MBSHFS
.JOJNVNQJQFXBMMUIJDLOFTT<NN> UIBO UIF TQFDJmFE NJOJNVN QJQF UIJDLOFTT
● 4FMFDU SFGSJHFSBOU QJQFT PG UIF UBCMF TIPXO PO UIF SJHIU XBMM UIJDLOFTT
BOE NBUFSJBM BT TQFDJmFE GPS FBDI QJQF TJ[F 1JQFNBUFSJBM 0UZQFQJQF 0UZQFQJQF 0UZQFQJQF 0UZQFQJQF 1IPTQIPSVTEFPYJEJ[FETFBNMFTTDPQQFSQJQF$5
+*4)
0OTJUFQJQJOHXPSL 'MBSFE QJQF FOE" NN
$PQQFS
● 5BLF DBSF TP UIBU JOTUBMMFE QJQFT NBZ OPU UPVDI DPNQPOFOUT XJUIJO B VOJU
" QJQF PVUFS A
ー
*.1035"/5 *G UPVDIJOH XJUI BO JOUFSOBM DPNQPOFOU
JU XJMM HFOFSBUF BCOPSNBM TPVOET BOEPS WJCSBUJPOT
EJBNFUFS
UPPMT φ
)PXUPSFNPWFUIFTJEFDPWFS 1MFBTF SFNPWF UIF TDSFX PG B TJEF DPWFS BOE SFNPWF UP UIF GSPOU φ
φ
BOU DIBSHJOH ● $BSSZ PVU UIF PO TJUF QJQJOH XPSL XJUI UIF PQFSBUJPO WBMWF GVMMZ DMPTFE φ
● (JWF TVGmDJFOU QSPUFDUJPO UP B QJQF FOE DPNQSFTTFE BOE CMB[FE
PS XJUI BO BEIFTJWF UBQF
TP UIBU
$PQQFS QJQF QSPUSVTJPO GPS nBSJOH # NN
JQF HBVHF
SFGFS UP PVS UFDIOJDBM NBOVBM
*OUBLF 'BTUFOXJUICPMUT
.
4JODF ESBJO XBUFS HFOFSBUFE CZ EFGSPTU DPOUSPM NBZ GSFF[F
GPMMPXJOH NFBTVSFT BSF SFRVJSFE 0VUMFU
6TFBUIJDLFSCMPDLUP
● %POUFYFDVUFESBJOQJQJOHXPSLCZVTJOHBESBJOFMCPXBOEESBJOHSPNNFUT PQUJPOBMQBSUT
<3FGFSUP%SBJOQJQJOHXPSL> 6TFBMPOHCMPDLUP
FYUFOEUIFXJEUI BODIPSEFFQFS
● 3FDPNNFOETFUUJOH%FGSPTU$POUSPM 48
BOE4OPX(VBSE'BO$POUSPM 48
<3FGFSUP4FUUJOH48
48>
*G UIF VOJU DBO CF BGGFDUFE CZ TUSPOH XJOE
GPMMPXJOH NFBTVSFT BSF SFRVJSFE "ODIPSCPMUQPTJUJPO
4USPOH XJOE DBO DBVTF EBNBHF PG GBO GBO NPUPS
PS DBO DBVTF QFSGPSNBODF EFHSBEBUJPO
PS DBO USJHHFS BOPNBMPVT TUPQ
PG UIF VOJU EVF UP SJTJOH PG IJHI QSFTTVSF ● *OJOTUBMMJOHUIFVOJU
mYUIFVOJUTMFHTXJUICPMUTTQFDJmFEPOUIFBCPWF
GSJHFSBOUDJSDVJU ● 5IFQSPUSVTJPOPGBOBODIPSCPMUPOUIFGSPOUTJEFNVTUCFLFQUXJUIJONN
*OTUBMM UIF PVUMFU BJS CMPX TJEF PG UIF *OTUBMM UIF PVUMFU BJS CMPX TJEF PG 5IF VOJU TIPVME CF JOTUBMMFE PO ● 4FDVSFMZJOTUBMMUIFVOJUTPUIBUJUEPFTOPUGBMMPWFSEVSJOHFBSUIRVBLFTPSTUSPOHXJOET
FUD
E #F TVSF OPU UP
VOJU UP GBDF B XBMM PG CVJMEJOH
PS UIF VOJU JO B QPTJUJPO QFSQFOEJDVMBS UIF TUBCMF BOE MFWFM GPVOEBUJPO ● 3FGFSUPUIFBCPWFJMMVTUSBUJPOTGPSJOGPSNBUJPOSFHBSEJOHDPODSFUFGPVOEBUJPOT
HFSBOUMFBLTXIJDI QSPWJEF B GFODF PS B XJOECSFBL TDSFFO UP UIF EJSFDUJPO PG XJOE *G UIF GPVOEBUJPO JT OPU MFWFM
● *OTUBMMUIFVOJUJOBMFWFMBSFB 8JUIBHSBEJFOUPGNNPSMFTT
QFDUFETUBSUPGGBO
3&'3*(&3"/51*1*/(803,
3FTUSJDUJPOT PO VOJU JOTUBMMBUJPO BOE VTF 4JOHMFUZQF *OEPPSVOJU
PQFSBUJPO ● $IFDL UIF GPMMPXJOH QPJOUT JO MJHIU PG UIF JOEPPS VOJU TQFDJmDBUJPOT BOE UIF JOTUBMMBUJPO TJUF
JODVS GSPTU CJUF PS
VFUPBOPNBMPVTMZ ● 0CTFSWF UIF GPMMPXJOH SFTUSJDUJPOT PO VOJU JOTUBMMBUJPO BOE VTF *NQSPQFS JOTUBMMBUJPO DBO SFTVMU JO B DPNQSFTTPS GBJMVSF PS QFSGPSNBODF EFHSBEBUJPO )
%JNFOTJPOBM .BSLTBQQFBSJOHJOUIFESBXJOHPOUIFSJHIU
3FTUSJDUJPOT
O DBVTF CVSTU BOE SFTUSJDUJPOT 4JOHMFUZQF 5XJOUZQF
-
0OFXBZQJQFMFOHUIPGSFGSJHFSBOUQJQJOH - -+-+-
.PEFM7 NPSMFTT 0VUEPPSVOJU
OU
CVSOPSFMFDUSJD .BJOQJQFMFOHUI - -
0OFXBZQJQFMFOHUIBGUFSUIFmSTUCSBODIJOHQPJOU NPSMFTT − -,- 5XJOUZQF
*OEPPSVOJU 5IFVOJUPGXIJDIFMFWBUJPOEJGGFSFODFGSPNUIFPVUEPPSVOJUJTUIFMBSHFTU
%FUFSNJOBUJPO PG QJQF TJ[F 0VUEPPSVOJU - SJTFS
● %FUFSNJOF SFGSJHFSBOU QJQF TJ[F QVSTVBOU UP UIF GPMMPXJOH HVJEFMJOFT CBTFE PO UIF JOEPPS VOJU TQFDJmDBUJPOT
"CPVUCSB[JOH
.PEFM7
(BTQJQF -JRVJEQJQF #SB[JOH NVTU CF QFSGPSNFE VOEFS B OJUSPHFO HBT nPX
φ φ 8JUIPVU OJUSPHFO HBT
B MBSHF RVBOUJUZ PG GPSFJHO NBUUFST PYJEJ[FE mMN
BSF DSFBUFE
0VUEPPSVOJUDPOOFDUFE 'MBSF 'MBSF DBVTJOH B DSJUJDBM GBJMVSF GSPN DBQJMMBSZ UVCF PS FYQBOTJPO WBMWF DMPHHJOH
3FGSJHFSBOUQJQJOH CSBODIQJQF-
φ φ
1SJNBSZTJEF 4FDPOEBSZTJEF
φ φ 1MVHUIFFOEPGUIFQJQFXJUIUBQF
PSPUIFS
*OEPPSVOJUDPOOFDUFE 4UBUJPOWBMWF
*O UIF DBTF PG B TJOHMF UZQF NBUFSJBM
BOEmMMUIFQJQFXJUIOJUSPHFOHBT
.1B
$BQBDJUZPGJOEPPSVOJU .PEFM7
</> )BOE
5BQJOH
#SBODIJOHQJQFTFU %*48"
/JUSPHFO
3FGSJHFSBOUQJQJOH CSBODIQJQF-
-
φ φ /JUSPHFO
*O UIF DBTF PG B UXJO UZQF 3FMJFGWBMWF
HBT
*OEPPSVOJUDPOOFDUFE φ φ 0OMZVTFOJUSPHFO #SB[JOH
ESPPN
HBT /
$BQBDJUZPGJOEPPSVOJU .PEFM7×
3FGSJHFSBOU QJQF XBMM UIJDLOFTT BOE NBUFSJBM 1JQFEJBNFUFS<NN> /05& ● 4FMFDU QJQFT IBWJOH B XBMM UIJDLOFTT MBSHFS
UIBO UIF TQFDJmFE NJOJNVN QJQF UIJDLOFTT
216 -
● 4FMFDU SFGSJHFSBOU QJQFT PG UIF UBCMF TIPXO PO UIF SJHIU XBMM UIJDLOFTT .JOJNVNQJQFXBMMUIJDLOFTT<NN>
BOE NBUFSJBM BT TQFDJmFE GPS FBDI QJQF TJ[F 1JQFNBUFSJBM 0UZQFQJQF 0UZQFQJQF 0UZQFQJQF 0UZQFQJQF 1IPTQIPSVTEFPYJEJ[FETFBNMFTTDPQQFSQJQF$5
+*4)
0OTJUFQJQJOHXPSL 'MBSFE QJQF FOE" NN
$PQQFS
● 5BLF DBSF TP UIBU JOTUBMMFE QJQFT NBZ OPU UPVDI DPNQPOFOUT XJUIJO B VOJU
" QJQF PVUFS A
ー
*.1035"/5 *G UPVDIJOH XJUI BO JOUFSOBM DPNQPOFOU
JU XJMM HFOFSBUF BCOPSNBM TPVOET BOEPS WJCSBUJPOT
EJBNFUFS
UPPMT φ
)PXUPSFNPWFUIFTJEFDPWFS 1MFBTF SFNPWF UIF TDSFX PG B TJEF DPWFS BOE SFNPWF UP UIF GSPOU φ
φ
BOU DIBSHJOH ● $BSSZ PVU UIF PO TJUF QJQJOH XPSL XJUI UIF PQFSBUJPO WBMWF GVMMZ DMPTFE φ
● (JWF TVGmDJFOU QSPUFDUJPO UP B QJQF FOE DPNQSFTTFE BOE CMB[FE
PS XJUI BO BEIFTJWF UBQF
TP UIBU
$PQQFS QJQF QSPUSVTJPO GPS nBSJOH # NN
QF HBVHF JUT GPSN EJBNFUFS 8JUI BO 3" UPPM 8JUI B DPOWFOUJPOBM UPPM
● 'MBSF DPOOFDUJPO JT VTFE CFUXFFO UIF VOJU BOE SFGSJHFSBOU QJQF 'MBSF B QJQF BGUFS FOHBHJOH B nBSF
φ
OVU POUP JU 'MBSF EJNFOTJPOT GPS 3" BSF EJGGFSFOU GSPN UIPTF GPS DPOWFOUJPOBM 3$ "MUIPVHI 4DSFX φ
XF SFDPNNFOE UIF VTF PG nBSJOH UPPMT EFTJHOFE TQFDJmDBMMZ GPS 3"
DPOWFOUJPOBM nBSJOH UPPMT DBO ∼ ∼
BMTP CF VTFE CZ BEKVTUJOH UIF NFBTVSFNFOU PG QSPUSVTJPO # XJUI B QSPUSVTJPO DPOUSPM HBVHF φ
● 5IF QJQF TIPVME CF BODIPSFE FWFSZ N PS MFTT UP JTPMBUF UIF WJCSBUJPO 4JEF DPWFS φ
●5JHIUFOBnBSFKPJOUTFDVSFMZXJUIBEPVCMFTQBOOFS
%P OPU BQQMZ GPSDF CFZPOE QSPQFS GBTUFOJOH UPSRVF JO UJHIUFOJOH UIF nBSF OVU
$"65*0/ 'JYCPUIMJRVJEBOEHBTTFSWJDFWBMWFTBUUIFWBMWFNBJOCPEJFTBTJMMVTUSBUFEPOUIFSJHIU
BOEUIFOGBTUFOUIFN
BQQMZJOHBQQSPQSJBUFGBTUFOJOHUPSRVF
'10 • PAC-DB-142
)FBWZ
0QFSBUJPOWBMWFTJ[F 5JHIUFOJOHUPSRVF 5JHIUFOJOHBOHMF 3FDPNNFOEFEMFOHUI
NN
/N
°
PGBUPPMIBOEMF
NN
$MPTF
BMTPGBMMBQQSPYJNBUFMZ.1B5IFQSFTTVSF
JGDIBOHFE
TIPVMECFDPNQFOTBUFEGPS
F
*GBQSFTTVSFESPQJTPCTFSWFEJODIFDLJOHF
BOEB
oE
BMFBLFYJTUTTPNFXIFSF'JOEBMFBLCZBQQMZJOHCVCCMFUFTUMJRVJEUPXFMEFEQBSUTBOEnBSFKPJOUTBOESFQBJSJU"GUFSSFQBJS
DPOEVDUBOBJSUJHIUOFTTUFTUBHBJO $"65*0/
② *O DPOEVDUJOH BO BJSUJHIUOFTT UFTU
VTF OJUSPHFO HBT BOE QSFTTVSJ[F UIF TZTUFN XJUI OJUSPHFO HBT GSPN UIF HBT TJEF %P OPU VTF B NFEJVN PUIFS UIBO OJUSPHFO HBT VOEFS BOZ
DJSDVNTUBODFT
&WBDVBUJPO "JSUJHIUFOFTTUFTUDPNQMFUFE 1BZ BUUFOUJPO UP UIF GPMMPXJOH QPJOUT JO BEEJUJPO UP UIF
"CPVUJOTV
BCPWFGPSUIF3"BOEDPNQBUJCMFNBDIJOFT
<8PSLnPX> 7BDVVNJOHCFHJOT ● "OJOTVMBUJPOSFT
3VO UIF WBDVVN QVNQ GPS BU MFBTU POF IPVS BGUFS UIF WBDVVN HBVHF TIPXT L1B PS MPXFS NN)H PS MPXFS
○5P QSFWFOU B EJGGFSFOU PJM GSPN FOUFSJOH
BTTJHO EFEJDBUFE SFTJTUBODF
QMFBT
8IFO UIF TZTUFN IBT SFNBJOJOH NPJTUVSF UPPMT
FUD UP FBDI SFGSJHFSBOU UZQF 6OEFS OP DJSDVNTUBODFT
JOTJEF PS B MFBLZ QPJOU
UIF WBDVVN HBVHF 7BDVVNJOHDPNQMFUFE
$IFDLXIFUIFSB
JOEJDBUPS XJMM SJTF $POmSNUIBUUIFWBDVVNHBVHFJOEJDBUPSEPFTOPUSJTFFWFOJGUIFTZTUFNJTMFGUGPSPOFIPVSPSNPSF NVTU B HBVHF NBOJGPME BOE B DIBSHF IPTF JO QBSUJDVMBS CF
$IFDLXIFUIFSU
7BDVVNHBVHFDIFDL TIBSFE XJUI PUIFS SFGSJHFSBOU UZQFT 3
3$
FUD
5IJTVOJUJTFRVJQ
$IFDL UIF TZTUFN GPS B MFBLZ QPJOU BOE
UIFO ESBX BJS UP DSFBUF B WBDVVN BHBJO ○6TF B DPVOUFSnPX QSFWFOUJPO BEBQUFS UP QSFWFOU WBDVVN
QVNQ PJM GSPN FOUFSJOH UIF SFGSJHFSBOU TZTUFN
'JMMSFGSJHFSBOU
5FTU SVO N
"EEJUJPOBM SFGSJHFSBOU DIBSHF 1MFBTFSFNPW
" UFTU SVO DB
$BMDVMBUF B SFRVJSFE SFGSJHFSBOU DIBSHF WPMVNF GSPN UIF GPMMPXJOH UBCMF 48 BOE 48
4UBOEBSESFGSJHFSBOU 1JQFMFOHUIGPS "EEJUJPOBMDIBSHFWPMVNF LH
*OTUBMMBUJPOTQJQFMFOHUI N
4XJUDIJOH 48
TUBOEBSESFGSJHFSBOU QFSNFUFSPGSFGSJHFSBOUQJQJOH 3FGSJHFSBOUWPMVNFDIBSHFE DPWFSFEXJUIPVUBEEJUJPOBM
DIBSHFWPMVNF LH
GPSTIJQNFOUBUUIFGBDUPSZ LH
5IF VOJU XJMM TUB
DIBSHFWPMVNF N
MJRVJEQJQFφ
SFGSJHFSBOUDIBSHF
%P OPU GBJM UP
.PEFM7 ※ *ODBTFPGUIF
-
¡$PSMPXFS
JU
● 5IJT VOJU DPOUBJOT GBDUPSZ DIBSHFE SFGSJHFSBOU DPWFSJOH N PG SFGSJHFSBOU QJQJOH BOE BEEJUJPOBM SFGSJHFSBOU DIBSHF PO UIF JOTUBMMBUJPO TJUF JT OPU SFRVJSFE GPS BO JOTUBMMBUJPO XJUI VQ UP N SFGSJHFSBOU QJQJOH
217 -
8IFO SFGSJHFSBOU QJQJOH FYDFFET N
BEEJUJPOBMMZ DIBSHF BO BNPVOU DBMDVMBUFE GSPN UIF QJQF MFOHUI BOE UIF BCPWF UBCMF GPS UIF QPSUJPO JO FYDFTT PG N
● 8IFO SFGSJHFSBOU QJQJOH JT TIPSUFS UIBO N
SFEVDF SFGSJHFSBOU CZ LH GSPN UIF GBDUPSZ DIBSHFE WPMVNF BOE BEKVTU UP LH
$IFDLJOH
● *G BO FYJTUJOH QJQF TZTUFN JT VTFE
B SFRVJSFE SFGSJHFSBOU DIBSHF WPMVNF XJMM WBSZ EFQFOEJOH PO UIF MJRVJE QJQF TJ[F 'PS GVSUIFS JOGPSNBUJPO
QMFBTF TFFi 65*-*;"5*0/ 0' &9*45*/( 1*1*/(w 1MFBTFSFNPW
'PSNVMBUPDBMDVMBUFUIFWPMVNFPGBEEJUJPOBMSFGSJHFSBOUSFRVJSFE 6TF DIFDL KPJOUT
8IFO BO BEEJUJPOBM DIBSHF WPMVNF DBMDVMBUJPO SFTVMU GPVSXBZ WBMWF J
"EEJUJPOBMDIBSHFWPMVNF LH
\.BJOQJQFMFOHUI N
o-FOHUIDPWFSFEXJUIPVUBEEJUJPOBMDIBSHF N
^Y LHN
5PUBMMFOHUIPGCSBODIQJQFT N
Y LHN
JT OFHBUJWF
JU JT OPU OFDFTTBSZ UP DIBSHF SFGSJHFSBOU EJTDIBSHF QSFTTVS
● 'PSBOJOTUBMMBUJPONFBTVSJOHNPSMPOHFS
CVUOPUNPSFUIBON
JOQJQFMFOHUI
QMFBTFDIBSHFUIFTUBOEBSESFGSJHFSBOUDIBSHFWPMVNF
XIFOZPVSFDIBSHFSFGSJHFSBOUBGUFSTFSWJDJOHFUD BEEJUJPOBMMZ "TJOEJDBUFEJOUI
● 8IFOSFGSJHFSBOUQJQJOHJTTIPSUFSUIBON
SFDIBSHFLHPGSFGSJHFSBOU BUFBDIQPJOUXJMM
&Y
'PSBNJOTUBMMBUJPO
DIBSHFLHPGSFGSJHFSBOU IFBUJOHPQFSBUJPO
'PSBNJOTUBMMBUJPO
DIBSHFi
YLHw
$IBSHJOHSFGSJHFSBOU
4FUUJOH 4
● 4JODF 3" SFGSJHFSBOU NVTU CF DIBSHFE JO UIF MJRVJE QIBTF
ZPV TIPVME DIBSHF JU
LFFQJOH UIF DPOUBJOFS DZMJOEFS VQTJEF EPXO PS VTJOH B SFGSJHFSBOU DZMJOEFS FRVJQQFE XJUI B TJQIPO UVCF 1MFBTFSFNPW
● $IBSHF SFGSJHFSBOU BMXBZT GSPN UIF MJRVJE TJEF TFSWJDF QPSU XJUI UIF PQFSBUJPO WBMWF TIVU 8IFO ZPV mOE JU EJGmDVMU UP DIBSHF B SFRVJSFE BNPVOU
GVMMZ PQFO UIF PVUEPPS VOJU WBMWFT PO CPUI MJRVJE BOE HBT TJEFT BOE DIBSHF SFGSJHFSBOU GSPN
%FGSPTU DPOUS
UIF HBT TVDUJPO
TJEF TFSWJDF QPSU
XIJMF SVOOJOH UIF VOJU JO UIF DPPMJOH NPEF *O EPJOH TP
DBSF NVTU CF UBLFO TP UIBU SFGSJHFSBOU NBZ CF EJTDIBSHFE GSPN UIF DZMJOEFS JO UIF MJRVJE QIBTF BMM UIF UJNF 8IFO UIF DZMJOEFS WBMWF JT ・8IFO UIJT T
UISPUUMFE EPXO PS B EFEJDBUFE DPOWFSTJPO UPPM UP DIBOHF MJRVJEQIBTF SFGSJHFSBOU JOUP NJTU JT VTFE UP QSPUFDU UIF DPNQSFTTPS
IPXFWFS
BEKVTU DIBSHF DPOEJUJPOT TP UIBU SFGSJHFSBOU XJMM HBTJGZ VQPO FOUFSJOH UIF VOJU ・4FU UIJT TXJ
● *O DIBSHJOH SFGSJHFSBOU
BMXBZT DIBSHF B DBMDVMBUFE WPMVNF CZ VTJOH B TDBMF UP NFBTVSF UIF DIBSHF WPMVNF IFBUJOH PQF
● 8IFO SFGSJHFSBOU JT DIBSHFE XJUI UIF VOJU CFJOH SVO
DPNQMFUF B DIBSHF PQFSBUJPO XJUIJO NJOVUFT 3VOOJOH UIF VOJU XJUI BO JOTVGmDJFOU RVBOUJUZ PG SFGSJHFSBOU GPS B MPOH UJNF DBO DBVTF B DPNQSFTTPS GBJMVSF
4OPX HVBSE
/05& 1VU EPXO UIF SFGSJHFSBOU WPMVNF DBMDVMBUFE GSPN UIF QJQF MFOHUI POUP UIF DBVUJPO MBCFM BUUBDIFE PO UIF CBDL TJEF PG UIF TFSWJDF QBOFM ・8IFO UIJT T
℃ PS MPXF
・8IFO UIF VO
)FBUJOHBOEDPOEFOTBUJPOQSFWFOUJPO #BOE BDDFTTPSZ
1JQFDPWFS BDDFTTPSZ
'BJMVSF EJ
'10 • PAC-DB-142
%SFTTSFGSJHFSBOUQJQFT CPUIHBTBOEMJRVJEQJQFT
GPSIFBUJOTVMBUJPOBOEQSFWFOUJPOPGEFXDPOEFOTBUJPO
*NQSPQFS IFBU JOTVMBUJPOBOUJEFX ESFTTJOH DBO SFTVMU JO B XBUFS MFBL PS ESJQQJOH DBVTJOH EBNBHF UP IPVTFIPME FGGFDUT
FUD &SSPSJOEJDBUFEPOUIF
SFNPUFDPOUSPMVOJU
6TFBIFBUJOTVMBUJOHNBUFSJBMUIBUDBOXJUITUBOE℃PSBIJHIFSUFNQFSBUVSF1PPSIFBUJOTVMBUJOHDBQBDJUZDBODBVTFIFBUJOTVMBUJPOQSPCMFNTPSDBCMFEFUFSJPSBUJPO
"MM HBT QJQFT NVTU CF TFDVSFMZ IFBU JOTVMBUFE JO PSEFS UP QSFWFOU EBNBHF GSPN ESJQQJOH XBUFS UIBU DPNFT GSPN UIF DPOEFOTBUJPO GPSNFE PO UIFN EVSJOH B DPPMJOH PQFSBUJPO PS QFSTPOBM &
JOKVSZ GSPN CVSOT CFDBVTF UIFJS TVSGBDF DBO SFBDI RVJUF B IJHI UFNQFSBUVSF EVF UP EJTDIBSHFE HBT nPXJOH JOTJEF EVSJOH B IFBUJOH PQFSBUJPO 8JSFTGPSDPOOFDUJOHJOEPPS &
8SBQ JOEPPS VOJUT nBSF KPJOUT XJUI IFBU JOTVMBUJOH QBSUT QJQF DPWFS
GPS IFBU JOTVMBUJPO CPUI HBT BOE MJRVJE QJQFT
&YUFSJPSUBQF
BOEPVUEPPSVOJUT
(JWF IFBU JOTVMBUJPO UP CPUI HBT BOE MJRVJE TJEF QJQFT #VOEMF B IFBU JOTVMBUJOH NBUFSJBM BOE B QJQF UJHIUMZ UPHFUIFS TP UIBU OP HBQT NBZ CF MFGU CFUXFFO UIFN BOE XSBQ UIFN UPHFUIFS &
(BTQJQJOH
XJUI B DPOOFDUJOH DBCMF CZ B ESFTTJOH UBQF -JRVJEQJQJOH ● *GBOFSSPSDPE
"MUIPVHI JU JT WFSJmFE JO B UFTU UIBU UIJT BJS DPOEJUJPOJOH VOJU TIPXT TBUJTGBDUPSZ QFSGPSNBODF VOEFS +*4 DPOEFOTBUJPO UFTU DPOEJUJPOT
CPUI HBT BOE MJRVJE QJQFT OFFE UP CF ESFTTFE XJUI
NN PS UIJDLFS IFBU JOTVMBUJPO NBUFSJBMT BCPWF UIF DFJMJOH XIFSF SFMBUJWF IVNJEJUZ FYDFFET JOTVMBUJPO
5IFTUBUFP
5IF GPMMPXJOH UBCM
%3"*/1*1*/(803,
7BMWFGPSBDPPMJOHP
● &YFDVUFESBJOQJQJOHCZVTJOHBESBJOFMCPXBOEESBJOHSPNNFUTTVQQMJFETFQBSBUFMZBT ○ 5IFSF BSF ESBJO IPMFT QSPWJEFE PO UIF CPUUPN QMBUF PG BO PVUEPPS VOJU UP EJTDIBSHF 7BMWFGPSBIFBUJOHP
PQUJPOBMQBSUT
XIFSFXBUFSESBJOFEGSPNUIFPVUEPPSVOJUJTBQSPCMFN DPOEFOTFEXBUFS
○ 8IFO DPOEFOTFE XBUFS OFFET UP CF MFE UP B ESBJO
FUD
JOTUBMM UIF VOJU PO B nBU CBTF
)FFEUIFGP
TVQQMJFETFQBSBUFMZBTBOPQUJPOBMQBSU
PSDPODSFUFCMPDLT 5IJTPVUEPPSVOJU
○ $POOFDUBESBJOFMCPXBTTIPXOJOUIFJMMVTUSBUJPOBOEDMPTFUIFPUIFSUXPESBJOIPMFTXJUI
DPNQSFTTPSGSPNM
HSPNNFUT
%SBJOFMCPX QF
65*-*;"5*
)BSEWJOZMDIMPSJEFQJQFGPSHFOFSBMQVSQPTF 71
%SBJOHSPNNFU
QFT
$IFDLXIFUIFSBO
○ ×
&MFDUSJDBMJOTUBMMBUJPOXPSLNVTUCFQFSGPSNFECZBOFMFDUSJDBMJOTUBMMBUJPOTFSWJDFQSPWJEFSRVBMJmFECZBQPXFSQSPWJEFSPGUIFDPVOUSZ
&MFDUSJDBMJOTUBMMBUJPOXPSLNVTUCFFYFDVUFEBDDPSEJOHUPUIFUFDIOJDBMTUBOEBSETBOEPUIFSSFHVMBUJPOTBQQMJDBCMFUPFMFDUSJDBMJOTUBMMBUJPOTJOUIFDPVOUSZ
●
%POPUVTFBOZTVQQMZDPSEMJHIUFSUIBOPOFTQFDJmFEJOQBSFOUIFTFTGPSFBDIUZQFCFMPX
CSBJEFEDPSE DPEFEFTJHOBUJPO*&$
PSEJOBSZUPVHISVCCFSTIFBUIFEDPSE DPEFEFTJHOBUJPO*&$
%PFTUI
nBUUXJOUJOTFMDPSE DPEFEFTJHOBUJPO*&$
5IFQ
5IFQ
%POPUVTFBOZUIJOHMJHIUFSUIBOQPMZDIMPSPQSFOFTIFBUIFEnFYJCMFDPSE DPEFEFTJHOBUJPO*&$
GPSTVQQMZDPSETPGQBSUTPGBQQMJBODFTGPSPVUEPPSVTF 7$5DBCUZSFDBCMF 77'nBUDBCMF DPSFDBCMF 4IJFMEDBCMF
5IFF
●
(SPVOEUIFVOJU%POPUDPOOFDUUIFHSPVOEJOHXJSFUPBHBTQJQF
XBUFSQJQF
MJHIUOJOHSPEPSUFMFQIPOFHSPVOEJOHXJSF DPO
8I
*GJNQSPQFSZHSPVOEFE
BOFMFDUSJDTIPDLPSNBMGVODUJPONBZSFTVMU 8I
●
"HSPVOEJOHXJSFNVTUCFDPOOFDUFECFGPSFDPOOFDUJOHUIFQPXFSDBCMF1SPWJEFBHSPVOEJOHXJSFMPOHFSUIBOUIFQPXFSDBCMF ● $POOFDUBQBJSCFBSJOHBDPNNPOUFSNJOBMOVNCFSXJUIBOJOEPPSPVUEPPSDPOOFDUJOHXJSF
●
5IFJOTUBMMBUJPOPGBOJNQVMTFXJUITUBOEJOHUZQFFBSUIMFBLBHFCSFBLFSJTOFDFTTBSZ"GBJMVSFUPJOTUBMMBOFBSUIMFBLBHFCSFBLFSDBOSFTVMUJOBOBDDDJEFOUTVDIBT ● *ODBCMJOH
GBTUFODBCMFTTFDVSFMZXJUIDBCMFDMBNQTTPUIBUOPFYUFSOBMGPSDFNBZXPSLPO
BOFMFDUSJDTIPDLPSBmSF UFSNJOBMDPOOFDUJPOT
●
%POPUUVSOPOUIFQPXFSVOUJMUIFFMFDUSJDBMXPSLJTDPNQMFUFUFE ● (SPVOEJOHUFSNJOBMTBSFQSPWJEFEJOUIFDPOUSPMCPY
●
%POPUVTFBDPOEFOTJWFDBQBDJUPSGPSQPXFSGBDUPSJNQSPWFNFOUVOEFSBOZDJSDVNTUBODFT *UEPTFOPUJNQSPWFQPXFSGBDUPS
XIJMFJUDBODBVTFBOBCOPSNBM *TUIFFY
PWFSIFBUBDDJEFOU
●
'PSQPXFSTVQQMZDBCMFT
VTFDPOEVJUT
*TUIFF
●
%P OPU MBZ FMFDUSPOJD DPOUSPM DBCMFT SFNPUF DPOUSPM BOE TJHOBMJOH XJSFT
BOE PUIFS DBCMFT UPHFUIFS PVUTJEF UIF VOJU -BZJOH UIFN UPHFUIFS DBO SFTVMU JO UIF $IFDL
NBMGVODUJPOJOHPSBGBJMVSFPGUIFVOJUEVFUPFMFDUSJDOPJTFT TZTUFN
●
'BTUFODBCMFTTPUIBUNBZOPUUPVDIUIFQJQJOH
FUD 1PXFSTPVSDF
TJHOBMMJOFBOEHSPVOEUFSNJOBMCMPDL
●
8IFO DBCMFT BSF DPOOFDUFE
NBLF TVSF UIBU BMM FMFDUSJDBM DPNQPOFOUT XJUIJO UIF FMFDUSJDBM DPNQPOFOU CPY BSF GSFF PG MPPTF DPOOFDUPS DPVQMJOH PS UFSNJOBM "SFU
DPOOFDUJPOBOEUIFOBUUBDIUIFDPWFSTFDVSFMZ *NQSPQFSDPWFSBUUBDINFOUDBOSFTVMUJONBMGVODUJPOJOHPSBGBJMVSFPGUIFVOJU
JGXBUFSQFOFUSBUFTJOUPUIFCPY
●
"MXBZTVTFBUISFFDPSFDBCMFGPSBOJOEPPSPVUEPPSDPOOFDUJOHDBCMF/FWFSVTFBTIJFMEDBCMF (SPVOEJOHUFSNJOBM "SFIFB
Downloaded from www.Manualslib.com manuals search engine ○ %POPUDPOOFDUUPUIFHSPVOEJOHXJSFGSPNBOPUIFSVOJU
GSFFPG
)FBUJO
QVNQ PJM GSPN FOUFSJOH UIF SFGSJHFSBOU TZTUFN
'JMMSFGSJHFSBOU
5FTU SVO N
"EEJUJPOBM SFGSJHFSBOU DIBSHF 1MFBTFSFNPW
" UFTU SVO DB
$BMDVMBUF B SFRVJSFE SFGSJHFSBOU DIBSHF WPMVNF GSPN UIF GPMMPXJOH UBCMF 48 BOE 48
4UBOEBSESFGSJHFSBOU 1JQFMFOHUIGPS "EEJUJPOBMDIBSHFWPMVNF LH
*OTUBMMBUJPOTQJQFMFOHUI N
4XJUDIJOH 48
TUBOEBSESFGSJHFSBOU QFSNFUFSPGSFGSJHFSBOUQJQJOH 3FGSJHFSBOUWPMVNFDIBSHFE DPWFSFEXJUIPVUBEEJUJPOBM
DIBSHFWPMVNF LH
GPSTIJQNFOUBUUIFGBDUPSZ LH
5IF VOJU XJMM TUB
DIBSHFWPMVNF N
MJRVJEQJQFφ
SFGSJHFSBOUDIBSHF
%P OPU GBJM UP
.PEFM7 ※ *ODBTFPGUIF
¡$PSMPXFS
JU
● 5IJT VOJU DPOUBJOT GBDUPSZ DIBSHFE SFGSJHFSBOU DPWFSJOH N PG SFGSJHFSBOU QJQJOH BOE BEEJUJPOBM SFGSJHFSBOU DIBSHF PO UIF JOTUBMMBUJPO TJUF JT OPU SFRVJSFE GPS BO JOTUBMMBUJPO XJUI VQ UP N SFGSJHFSBOU QJQJOH
8IFO SFGSJHFSBOU QJQJOH FYDFFET N
BEEJUJPOBMMZ DIBSHF BO BNPVOU DBMDVMBUFE GSPN UIF QJQF MFOHUI BOE UIF BCPWF UBCMF GPS UIF QPSUJPO JO FYDFTT PG N
● 8IFO SFGSJHFSBOU QJQJOH JT TIPSUFS UIBO N
SFEVDF SFGSJHFSBOU CZ LH GSPN UIF GBDUPSZ DIBSHFE WPMVNF BOE BEKVTU UP LH
$IFDLJOH
● *G BO FYJTUJOH QJQF TZTUFN JT VTFE
B SFRVJSFE SFGSJHFSBOU DIBSHF WPMVNF XJMM WBSZ EFQFOEJOH PO UIF MJRVJE QJQF TJ[F 'PS GVSUIFS JOGPSNBUJPO
QMFBTF TFFi 65*-*;"5*0/ 0' &9*45*/( 1*1*/(w 1MFBTFSFNPW
'PSNVMBUPDBMDVMBUFUIFWPMVNFPGBEEJUJPOBMSFGSJHFSBOUSFRVJSFE 6TF DIFDL KPJOUT
8IFO BO BEEJUJPOBM DIBSHF WPMVNF DBMDVMBUJPO SFTVMU GPVSXBZ WBMWF J
"EEJUJPOBMDIBSHFWPMVNF LH
\.BJOQJQFMFOHUI N
o-FOHUIDPWFSFEXJUIPVUBEEJUJPOBMDIBSHF N
^Y LHN
5PUBMMFOHUIPGCSBODIQJQFT N
Y LHN
JT OFHBUJWF
JU JT OPU OFDFTTBSZ UP DIBSHF SFGSJHFSBOU EJTDIBSHF QSFTTVS
● 'PSBOJOTUBMMBUJPONFBTVSJOHNPSMPOHFS
CVUOPUNPSFUIBON
JOQJQFMFOHUI
QMFBTFDIBSHFUIFTUBOEBSESFGSJHFSBOUDIBSHFWPMVNF
XIFOZPVSFDIBSHFSFGSJHFSBOUBGUFSTFSWJDJOHFUD BEEJUJPOBMMZ "TJOEJDBUFEJOUI
● 8IFOSFGSJHFSBOUQJQJOHJTTIPSUFSUIBON
SFDIBSHFLHPGSFGSJHFSBOU BUFBDIQPJOUXJMM
&Y
'PSBNJOTUBMMBUJPO
DIBSHFLHPGSFGSJHFSBOU IFBUJOHPQFSBUJPO
'PSBNJOTUBMMBUJPO
DIBSHFi
YLHw
$IBSHJOHSFGSJHFSBOU
4FUUJOH 4
● 4JODF 3" SFGSJHFSBOU NVTU CF DIBSHFE JO UIF MJRVJE QIBTF
ZPV TIPVME DIBSHF JU
LFFQJOH UIF DPOUBJOFS DZMJOEFS VQTJEF EPXO PS VTJOH B SFGSJHFSBOU DZMJOEFS FRVJQQFE XJUI B TJQIPO UVCF 1MFBTFSFNPW
● $IBSHF SFGSJHFSBOU BMXBZT GSPN UIF MJRVJE TJEF TFSWJDF QPSU XJUI UIF PQFSBUJPO WBMWF TIVU 8IFO ZPV mOE JU EJGmDVMU UP DIBSHF B SFRVJSFE BNPVOU
GVMMZ PQFO UIF PVUEPPS VOJU WBMWFT PO CPUI MJRVJE BOE HBT TJEFT BOE DIBSHF SFGSJHFSBOU GSPN
%FGSPTU DPOUS
UIF HBT TVDUJPO
TJEF TFSWJDF QPSU
XIJMF SVOOJOH UIF VOJU JO UIF DPPMJOH NPEF *O EPJOH TP
DBSF NVTU CF UBLFO TP UIBU SFGSJHFSBOU NBZ CF EJTDIBSHFE GSPN UIF DZMJOEFS JO UIF MJRVJE QIBTF BMM UIF UJNF 8IFO UIF DZMJOEFS WBMWF JT ・8IFO UIJT T
UISPUUMFE EPXO PS B EFEJDBUFE DPOWFSTJPO UPPM UP DIBOHF MJRVJEQIBTF SFGSJHFSBOU JOUP NJTU JT VTFE UP QSPUFDU UIF DPNQSFTTPS
IPXFWFS
BEKVTU DIBSHF DPOEJUJPOT TP UIBU SFGSJHFSBOU XJMM HBTJGZ VQPO FOUFSJOH UIF VOJU ・4FU UIJT TXJ
● *O DIBSHJOH SFGSJHFSBOU
BMXBZT DIBSHF B DBMDVMBUFE WPMVNF CZ VTJOH B TDBMF UP NFBTVSF UIF DIBSHF WPMVNF IFBUJOH PQF
● 8IFO SFGSJHFSBOU JT DIBSHFE XJUI UIF VOJU CFJOH SVO
DPNQMFUF B DIBSHF PQFSBUJPO XJUIJO NJOVUFT 3VOOJOH UIF VOJU XJUI BO JOTVGmDJFOU RVBOUJUZ PG SFGSJHFSBOU GPS B MPOH UJNF DBO DBVTF B DPNQSFTTPS GBJMVSF
4OPX HVBSE
/05& 1VU EPXO UIF SFGSJHFSBOU WPMVNF DBMDVMBUFE GSPN UIF QJQF MFOHUI POUP UIF DBVUJPO MBCFM BUUBDIFE PO UIF CBDL TJEF PG UIF TFSWJDF QBOFM ・8IFO UIJT T
℃ PS MPXF
・8IFO UIF VO
)FBUJOHBOEDPOEFOTBUJPOQSFWFOUJPO #BOE BDDFTTPSZ
1JQFDPWFS BDDFTTPSZ
'BJMVSF EJ
%SFTTSFGSJHFSBOUQJQFT CPUIHBTBOEMJRVJEQJQFT
GPSIFBUJOTVMBUJPOBOEQSFWFOUJPOPGEFXDPOEFOTBUJPO
*NQSPQFS IFBU JOTVMBUJPOBOUJEFX ESFTTJOH DBO SFTVMU JO B XBUFS MFBL PS ESJQQJOH DBVTJOH EBNBHF UP IPVTFIPME FGGFDUT
FUD &SSPSJOEJDBUFEPOUIF
SFNPUFDPOUSPMVOJU
6TFBIFBUJOTVMBUJOHNBUFSJBMUIBUDBOXJUITUBOE℃PSBIJHIFSUFNQFSBUVSF1PPSIFBUJOTVMBUJOHDBQBDJUZDBODBVTFIFBUJOTVMBUJPOQSPCMFNTPSDBCMFEFUFSJPSBUJPO
"MM HBT QJQFT NVTU CF TFDVSFMZ IFBU JOTVMBUFE JO PSEFS UP QSFWFOU EBNBHF GSPN ESJQQJOH XBUFS UIBU DPNFT GSPN UIF DPOEFOTBUJPO GPSNFE PO UIFN EVSJOH B DPPMJOH PQFSBUJPO PS QFSTPOBM &
JOKVSZ GSPN CVSOT CFDBVTF UIFJS TVSGBDF DBO SFBDI RVJUF B IJHI UFNQFSBUVSF EVF UP EJTDIBSHFE HBT nPXJOH JOTJEF EVSJOH B IFBUJOH PQFSBUJPO 8JSFTGPSDPOOFDUJOHJOEPPS &
8SBQ JOEPPS VOJUT nBSF KPJOUT XJUI IFBU JOTVMBUJOH QBSUT QJQF DPWFS
GPS IFBU JOTVMBUJPO CPUI HBT BOE MJRVJE QJQFT
&YUFSJPSUBQF
BOEPVUEPPSVOJUT
(JWF IFBU JOTVMBUJPO UP CPUI HBT BOE MJRVJE TJEF QJQFT #VOEMF B IFBU JOTVMBUJOH NBUFSJBM BOE B QJQF UJHIUMZ UPHFUIFS TP UIBU OP HBQT NBZ CF MFGU CFUXFFO UIFN BOE XSBQ UIFN UPHFUIFS &
(BTQJQJOH
XJUI B DPOOFDUJOH DBCMF CZ B ESFTTJOH UBQF -JRVJEQJQJOH ● *GBOFSSPSDPE
"MUIPVHI JU JT WFSJmFE JO B UFTU UIBU UIJT BJS DPOEJUJPOJOH VOJU TIPXT TBUJTGBDUPSZ QFSGPSNBODF VOEFS +*4 DPOEFOTBUJPO UFTU DPOEJUJPOT
CPUI HBT BOE MJRVJE QJQFT OFFE UP CF ESFTTFE XJUI
NN PS UIJDLFS IFBU JOTVMBUJPO NBUFSJBMT BCPWF UIF DFJMJOH XIFSF SFMBUJWF IVNJEJUZ FYDFFET JOTVMBUJPO
5IFTUBUFP
5IF GPMMPXJOH UBCM
%3"*/1*1*/(803,
7BMWFGPSBDPPMJOHP
● &YFDVUFESBJOQJQJOHCZVTJOHBESBJOFMCPXBOEESBJOHSPNNFUTTVQQMJFETFQBSBUFMZBT ○ 5IFSF BSF ESBJO IPMFT QSPWJEFE PO UIF CPUUPN QMBUF PG BO PVUEPPS VOJU UP EJTDIBSHF 7BMWFGPSBIFBUJOHP
PQUJPOBMQBSUT
XIFSFXBUFSESBJOFEGSPNUIFPVUEPPSVOJUJTBQSPCMFN DPOEFOTFEXBUFS
○ 8IFO DPOEFOTFE XBUFS OFFET UP CF MFE UP B ESBJO
FUD
JOTUBMM UIF VOJU PO B nBU CBTF
)FFEUIFGP
TVQQMJFETFQBSBUFMZBTBOPQUJPOBMQBSU
PSDPODSFUFCMPDLT 5IJTPVUEPPSVOJU
○ $POOFDUBESBJOFMCPXBTTIPXOJOUIFJMMVTUSBUJPOBOEDMPTFUIFPUIFSUXPESBJOIPMFTXJUI
DPNQSFTTPSGSPNM
HSPNNFUT
%SBJOFMCPX QF
65*-*;"5*
)BSEWJOZMDIMPSJEFQJQFGPSHFOFSBMQVSQPTF 71
%SBJOHSPNNFU
QFT
$IFDLXIFUIFSBO
○ ×
&MFDUSJDBMJOTUBMMBUJPOXPSLNVTUCFQFSGPSNFECZBOFMFDUSJDBMJOTUBMMBUJPOTFSWJDFQSPWJEFSRVBMJmFECZBQPXFSQSPWJEFSPGUIFDPVOUSZ
&MFDUSJDBMJOTUBMMBUJPOXPSLNVTUCFFYFDVUFEBDDPSEJOHUPUIFUFDIOJDBMTUBOEBSETBOEPUIFSSFHVMBUJPOTBQQMJDBCMFUPFMFDUSJDBMJOTUBMMBUJPOTJOUIFDPVOUSZ
●
%POPUVTFBOZTVQQMZDPSEMJHIUFSUIBOPOFTQFDJmFEJOQBSFOUIFTFTGPSFBDIUZQFCFMPX
CSBJEFEDPSE DPEFEFTJHOBUJPO*&$
PSEJOBSZUPVHISVCCFSTIFBUIFEDPSE DPEFEFTJHOBUJPO*&$
%PFTUI
nBUUXJOUJOTFMDPSE DPEFEFTJHOBUJPO*&$
5IFQ
5IFQ
%POPUVTFBOZUIJOHMJHIUFSUIBOQPMZDIMPSPQSFOFTIFBUIFEnFYJCMFDPSE DPEFEFTJHOBUJPO*&$
GPSTVQQMZDPSETPGQBSUTPGBQQMJBODFTGPSPVUEPPSVTF 7$5DBCUZSFDBCMF 77'nBUDBCMF DPSFDBCMF 4IJFMEDBCMF
5IFF
●
(SPVOEUIFVOJU%POPUDPOOFDUUIFHSPVOEJOHXJSFUPBHBTQJQF
XBUFSQJQF
MJHIUOJOHSPEPSUFMFQIPOFHSPVOEJOHXJSF DPO
8I
*GJNQSPQFSZHSPVOEFE
BOFMFDUSJDTIPDLPSNBMGVODUJPONBZSFTVMU 8I
●
"HSPVOEJOHXJSFNVTUCFDPOOFDUFECFGPSFDPOOFDUJOHUIFQPXFSDBCMF1SPWJEFBHSPVOEJOHXJSFMPOHFSUIBOUIFQPXFSDBCMF ● $POOFDUBQBJSCFBSJOHBDPNNPOUFSNJOBMOVNCFSXJUIBOJOEPPSPVUEPPSDPOOFDUJOHXJSF
-
●
5IFJOTUBMMBUJPOPGBOJNQVMTFXJUITUBOEJOHUZQFFBSUIMFBLBHFCSFBLFSJTOFDFTTBSZ"GBJMVSFUPJOTUBMMBOFBSUIMFBLBHFCSFBLFSDBOSFTVMUJOBOBDDDJEFOUTVDIBT ● *ODBCMJOH
GBTUFODBCMFTTFDVSFMZXJUIDBCMFDMBNQTTPUIBUOPFYUFSOBMGPSDFNBZXPSLPO
218 -
BOFMFDUSJDTIPDLPSBmSF UFSNJOBMDPOOFDUJPOT
●
%POPUUVSOPOUIFQPXFSVOUJMUIFFMFDUSJDBMXPSLJTDPNQMFUFUFE ● (SPVOEJOHUFSNJOBMTBSFQSPWJEFEJOUIFDPOUSPMCPY
●
%POPUVTFBDPOEFOTJWFDBQBDJUPSGPSQPXFSGBDUPSJNQSPWFNFOUVOEFSBOZDJSDVNTUBODFT *UEPTFOPUJNQSPWFQPXFSGBDUPS
XIJMFJUDBODBVTFBOBCOPSNBM *TUIFFY
PWFSIFBUBDDJEFOU
●
'PSQPXFSTVQQMZDBCMFT
VTFDPOEVJUT
*TUIFF
●
%P OPU MBZ FMFDUSPOJD DPOUSPM DBCMFT SFNPUF DPOUSPM BOE TJHOBMJOH XJSFT
BOE PUIFS DBCMFT UPHFUIFS PVUTJEF UIF VOJU -BZJOH UIFN UPHFUIFS DBO SFTVMU JO UIF $IFDL
NBMGVODUJPOJOHPSBGBJMVSFPGUIFVOJUEVFUPFMFDUSJDOPJTFT TZTUFN
●
'BTUFODBCMFTTPUIBUNBZOPUUPVDIUIFQJQJOH
FUD 1PXFSTPVSDF
TJHOBMMJOFBOEHSPVOEUFSNJOBMCMPDL
●
8IFO DBCMFT BSF DPOOFDUFE
NBLF TVSF UIBU BMM FMFDUSJDBM DPNQPOFOUT XJUIJO UIF FMFDUSJDBM DPNQPOFOU CPY BSF GSFF PG MPPTF DPOOFDUPS DPVQMJOH PS UFSNJOBM "SFU
DPOOFDUJPOBOEUIFOBUUBDIUIFDPWFSTFDVSFMZ *NQSPQFSDPWFSBUUBDINFOUDBOSFTVMUJONBMGVODUJPOJOHPSBGBJMVSFPGUIFVOJU
JGXBUFSQFOFUSBUFTJOUPUIFCPY
●
"MXBZTVTFBUISFFDPSFDBCMFGPSBOJOEPPSPVUEPPSDPOOFDUJOHDBCMF/FWFSVTFBTIJFMEDBCMF (SPVOEJOHUFSNJOBM "SFIFB
GSFFPG
○ %POPUDPOOFDUUPUIFHSPVOEJOHXJSFGSPNBOPUIFSVOJU
)FBUJO
1PXFSDBCMF
JOEPPSPVUEPPSDPOOFDUJOHXJSFT CVUJOTUBMMBEFEJDBUFEXJSFVQUPUIFHSPVOEJOHXJSFGSPN
● "MXBZTQFSGPSNHSPVOEJOHTZTUFNJOTUBMMBUJPOXPSLXJUIUIFQPXFSDPSEVOQMVHHFE
UIFEJTUSJCVUJPOCPBSE
"MXBZTVTFBOFBSUIMFBLBHFDJSDVJUCSFBLFSEFTJHOFEGPSJOWFSUFSDJSDVJUTUPQSFWFOUBGBVMUZPQFSBUJPO 8JSJOHDMBNQ
$"65*0/ 5I
○ 'BTUFODBCMFTBOEQSPUFDUUIFUFSNJOBMDPOOFDUJPOTGSPN
&BSUIMFBLBHFCSFBLFS 1PXFSDBCMF *OEPPSPVUEPPS FYUFSOBMGPSDF
."9PWFS $BCMFMFOHUI (SPVOEJOHXJSF
)BSNPOJDSFTJTUBOUUZQF
1PXFSTPVSDF UIJDLOFTT XJSFUIJDLOFTT
.PEFM
NN
DVSSFOU N
UIJDLOFTT Y 8"3/*/(
"
OVNCFS 8JSJOHEJBHSBN
4XJUDIHFBSPS$JSDVJUCSFBLFS $
4JOHMFQIBTFXJSF ○ *UJTBUUBDIFEPOUIFCBDLTJEFPGUIFTFSWJDFQBOFM
- / 7 7 φNN φNNY
'10 • PAC-DB-142
0VUEPPSVOJU )[
/
●5IFTQFDJmDBUJPOTTIPXOJOUIFBCPWFUBCMFBSFGPSVOJUTXJUIPVUIFBUFST'PSVOJUTXJUIIFBUFST
SFGFSUPUIFJOTUBMMBUJPOJOTUSVDUJPOTPSUIFDPOTUSVDUJPO
/ JOTUSVDUJPOTPGUIFJOEPPSVOJU
*OEPPSVOJU ●4XJUDIHFBSPS$JSDVJUCSFBLFSDBQBDJUZXIJDIJTDBMDVMBUFEGSPN."9PWFSDVSSFOUTIPVMECFDIPTFOBMPOHUIFSFHVMBUJPOTJOFBDIDPVOUSZ
9 : ; ●5IFDBCMFTQFDJmDBUJPOTBSFCBTFEPOUIFBTTVNQUJPOUIBUBNFUBMPSQMBTUJDDPOEVJUJTVTFEXJUIOPNPSFUIBOUISFFDBCMFTDPOUBJOFEJOBDPOEVJUBOEB
9 : ; WPMUBHFESPQJT'PSBOJOTUBMMBUJPOGBMMJOHPVUTJEFPGUIFTFDPOEJUJPOT
GPMMPXUIFJOUFSOBMDBCMJOHSFHVMBUJPOT"EBQUJUUPUIFSFHVMBUJPOJOFGGFDUJOFBDI
3FNPUFDPOUSPMMFS DPVOUSZ
$IFDLJOHUIFTUBUFPGUIFVOJUJOPQFSBUJPO &MFDUSJD
XJSJOH
%PJOEPPSPVUEPPSDPOOFDUJOHDBCMFTDPOOFDUCFUXFFOUIFTBNFUFSNJOBMOVNCFST
"SFFJUIFS7$5DBCUZSFDBCMFTPS8'GMBUDBCMFTVTFEGPSJOEPPSPVUEPPSDPOOFDUJOHDBCMFT
1MFBTFSFNPWFBTFSWJDFQBOFM %PFTHSPVOEJOHTBUJTGZUIF%UZQFHSPVOEJOH UZQF***HSPVOEJOH
SFRVJSFNFOUT
-
*TUIFVOJUHSPVOEFEXJUIBEFEJDBUFEHSPVOEJOHXJSFOPUDPOOFDUFEUPBOPUIFSVOJUTHSPVOEJOHXJSF
6TF DIFDL KPJOUT QSPWJEFE PO UIF QJQJOH CFGPSF BOE BGUFS UIF $IBSHFQPSUPGUIF "SFDBCMFTGSFFPGMPPTFTDSFXTBUUIFJSDPOOFDUJPOQPJOUT
MDVMBUJPO SFTVMU $IFDLKPJOUPGUIFQJQF
219 -
GPVSXBZ WBMWF JOTUBMMFE JOTJEF UIF PVUEPPS VOJU GPS DIFDLJOH HBTPQFSBUJPOWBMWF "SFDBCMFTIFMEEPXOXJUIDBCMFDMBNQTTPUIBUOPFYUFSOBMGPSDFXPSLTPOUPUFSNJOBMDPOOFDUJPOT
BSHF SFGSJHFSBOU EJTDIBSHF QSFTTVSF BOE TVDUJPO QSFTTVSF %JTDIBSHFQSFTTVSF 4VDUJPOQSFTTVSF *TJOEPPSVOJUJOTUBMMBUJPOXPSLDPNQMFUFE
$PPMJOHPQFSBUJPO ー *OEPPS VOJU
"TJOEJDBUFEJOUIFUBCMFTIPXOPOUIFSJHIU
QSFTTVSFEFUFDUFE )JHIQSFTTVSF
-PXQSFTTVSF
8IFSFBGBDFDPWFSTIPVMECFBUUBDIFEPOUPBOJOEPPSVOJU
JTUIFGBDFDPWFSBUUBDIFEUPUIFJOEPPSVOJU
BUFBDIQPJOUXJMMWBSZEFQFOEJOHPOXIFUIFSBDPPMJOHPS 4VDUJPOQSFTTVSF %JTDIBSHFQSFTTVSF
)FBUJOHPQFSBUJPO 5FTU SVO QSPDFEVSF ● "MXBZTDBSSZPVUBUFTUSVOBOEDIFDLUIFGPMMPXJOHJOPSEFSBTMJTUFE
IFBUJOHPQFSBUJPOIBTCFFOTFMFDUFE -PXQSFTTVSF
)JHIQSFTTVSF
1MFBTFSFNPWFBTFSWJDFQBOFM ②
③
0QFOUIFMJRVJETJEFPQFSBUJPOWBMWFGVMMZ
$MPTFUIFQBOFM
SFGSJHFSBOU GSPN
%FGSPTU DPOUSPM TXJUDIJOH 48
④ 8IFSFBSFNPUFDPOUSPMVOJUJTVTFEGPSVOJUTFUVQPOUIFJOTUBMMBUJPOTJUF
GPMMPXJOTUSVDUJPOTGPSVOJUTFUVQPOUIFJOTUBMMBUJPOTJUFXJUIBSFNPUFDPOUSPMVOJU
ZMJOEFS WBMWF JT ・8IFO UIJT TXJUDI JT UVSOFE 0/
UIF VOJU XJMM SVO JO UIF EFGSPTU NPEF NPSF GSFRVFOUMZ ⑤
48480''UIFVOJUXJMMTUBSUBDPPMJOHPQFSBUJPO
・4FU UIJT TXJUDI UP 0/
XIFO JOTUBMMFE JO B SFHJPO XIFSF PVUEPPS UFNQFSBUVSF GBMMT CFMPX [FSP EVSJOH UIF TFBTPO UIF VOJU JT SVO GPS B 48480/UIFVOJUXJMMTUBSUBIFBUJOHPQFSBUJPO
⑥ 8IFOUIFVOJUTUBSUTPQFSBUJPO
QSFTTUIFXJOEEJSFDUJPOCVUUPOQSPWJEFEPOUIFSFNPUFDPOUSPMVOJUUPDIFDLJUTPQFSBUJPO
IFBUJOH PQFSBUJPO
⑦ 1MBDFZPVSIBOECFGPSFUIFJOEPPSVOJUTEJGGVTFSUPDIFDLXIFUIFSDPME XBSN
XJOETDPNFPVUJOBDPPMJOH IFBUJOH
PQFSBUJPO
4OPX HVBSE GBO DPOUSPM 48
⑧ .BLFTVSFUIBUBSFE-&%JTOPUCMJOLJOH
・8IFO UIJT TXJUDI JT UVSOFE PO
UIF PVUEPPS VOJU GBO XJMM SVO GPS TFDPOET JO FWFSZ NJOVUFT
XIFO PVUEPPS UFNQFSBUVSF GBMMT UP ⑨ 8IFOZPVDPNQMFUFUIFUFTUSVO
QMFBTFUVSOPO48GPSTFDPOEBOECFTVSFUPFOEBUFTUSVO
℃ PS MPXFS BOE UIF DPNQSFTTPS JT OPU SVOOJOH ⑩ 8IFSFPQUJPOTBSFVTFE
DIFDLUIFJSPQFSBUJPOBDDPSEJOHUPUIFSFTQFDUJWFJOTUSVDUJPONBOVBMT
・8IFO UIF VOJU JT VTFE JO B WFSZ TOPXZ DPVOUSZ
TFU UIJT TXJUDI UP 0/
4XJUDIFT GPS POTJUF TFUUJOH
WFS BDDFTTPSZ
'BJMVSF EJBHOPTJT JO B UFTU SVO 0/
48 48
'10 • PAC-DB-142
& #MJOLJOHPODF #MJOLJOHDPOUJOVPVTMZ )BDUVBUJPOPSPQFSBUJPOXJUIPQFSBUJPOWBMWFTTIVU $IFDLXIFUIFSUIFPQFSBUJPOWBMWFTBSFPQFO 48
&YUFSJPSUBQF PDDVSTNBJOMZEVSJOHBIFBUJOHPQFSBUJPO
*GBOFSSPSIBTCFFODBODFMFEXIFONJOVUFTIBWFFMBQTFETJODF
-PXQSFTTVSFFSSPSPSPQFSBUJPOXJUIPQFSBUJPOWBMWFTTIVU BDPNQSFTTPSTUPQ
ZPVDBOSFTUBSUUIFVOJUCZFGGFDUJOH$IFDL
& #MJOLJOHPODF #MJOLJOHDPOUJOVPVTMZ 3FTFUGSPNUIFSFNPUFDPOUSPMVOJU
PDDVSTNBJOMZEVSJOHBDPPMJOHPQFSBUJPO
48
(BTQJQJOH
● *GBOFSSPSDPEFPUIFSUIBOUIPTFMJTUFEBCPWFJTJOEJDBUFE
SFGFSUPUIFXJSJOHEJBHSBNPGUIFPVUEPPSVOJUBOEUIFJOEPPSVOJU
JOTVMBUJPO
5IFTUBUFPGUIFFMFDUSPOJDFYQBOTJPOWBMWF
5IF GPMMPXJOH UBCMF JMMVTUSBUFT UIF TUFBEZ TUBUFT PG UIF FMFDUSPOJD FYQBOTJPO WBMWF 48
8IFOUIFVOJUDPNFTUPBOPSNBMTUPQ 8IFOUIFVOJUDPNFTUPBOBCOPSNBMTUPQ
8IFOQPXFSJTUVSOFEPO
%VSJOHBDPPMJOHPQFSBUJPO %VSJOHBIFBUJOHPQFSBUJPO %VSJOHBDPPMJOHPQFSBUJPO %VSJOHBIFBUJOHPQFSBUJPO
7BMWFGPSBDPPMJOHPQFSBUJPO $PNQMFUFTIVUQPTJUJPO $PNQMFUFTIVUQPTJUJPO 'VMMPQFOQPTJUJPO 'VMMPQFOQPTJUJPO 'VMMPQFOQPTJUJPO
U UP EJTDIBSHF 7BMWFGPSBIFBUJOHPQFSBUJPO 'VMMPQFOQPTJUJPO 'VMMPQFOQPTJUJPO $PNQMFUFTIVUQPTJUJPO 'VMMPQFOQPTJUJPO 'VMMPQFOQPTJUJPO
0/
5IJTPVUEPPSVOJUNBZTUBSUJOUIFTUBOECZNPEF XBJUJOHGPSBDPNQSFTTPSTUBSUVQ
XIJDIDBODPOUJOVFVQUPNJOVUFT
UPQSFWFOUUIFPJMMFWFMJOUIF ※ %P OPU PQFSBUF 48
48
48
48
DPNQSFTTPSGSPNMPXFSJOHPOUIFmSTUPQFSBUJPOBGUFSUVSOJOHPOUIFDJSDVJUCSFBLFS*GUIBUJTUIFDBTF
EPOPUTVTQFDUBVOJUGBJMVSF ※ 3FGFS UP 5&$)/*$"- ."/6"- BCPVU 48 1VNQ EPXO 48
SBJOIPMFTXJUI
65*-*;"5*0/0'&9*45*/(1*1*/(
$IFDLXIFUIFSBOFYJTUJOHQJQFTZTUFNJTSFVTBCMFPSOPUCZVTJOHUIFGPMMPXJOHnPXDIBSU
45"35 5BCMF PG QJQF TJ[F SFTUSJDUJPOT
◎:4UBOEBSE QJQF TJ[F ○:6TBCMF △:3FTUSJDUFE UP TIPSUFS QJQF MFOHUI MJNJUT $PPM↓ $PPMJOH DBQBDJUZ ESPQ
"SFBOPVUEPPSVOJUBOEBOJOEPPSVOJUDPOOFDUFEUPUIF /0
FYJTUJOHQJQFTZTUFNUPSFVTF
"EEJUJPOBMDIBSHFWPMVNFQFSNFUFSPGQJQF LHN LHN
:&4
/0 8IJDIPGUIFGPMMPXJOHSFGSJHFSBUJPOPJMT $BOAU
-JRVJEQJQF φ φ φ
"SFUIFFYJTUJOHVOJUTPVSQSPEVDUT EPFTUIFFYJTUJOHVOJUVTF /0 .BLFBOJORVJSZ 6TF 1JQF TJ[F
:&4 :&4
4VOJTP
.4
#BSSFM'SFF[F
)"#
'SFPM
GPSSFVTBCJMJUZ (BTQJQF φ φ φ
FUIFSPJM
FTUFSPJM
$BO6TF 6TBCJMJUZ $PPM↓ ◎ △
%PFTUIFFYJTUJOHQJQFTZTUFNUPSFVTFTBUJTGZBMMPGUIFGPMMPXJOH 7 .BYJNVNPOFXBZQJQFMFOHUI
5IFQJQFMFOHUIJTNPSMFTT
5IFQJQFTJ[FDPOGPSNTUPUIFUBCMFPGQJQFTJ[FSFTUSJDUJPOT -FOHUIDPWFSFEXJUIPVUBEEJUJPOBMDIBSHF
EDBCMF
5IFFMFWBUJPOEJGGFSFODFCFUXFFOUIFJOEPPSBOEPVUEPPSVOJUT /0
DPOGPSNTUPUIFGPMMPXJOHSFTUSJDUJPOT
8IFSFUIFPVUEPPSVOJUJTBCPWFNPSMFTT ● 5IF QJQF MFOHUI TIPVME CF BU MFBTU N *G UIF QJQF MFOHUI JT TIPSUFS UIBO N
UIF RVBOUJUZ PG SFGSJHFSBOU OFFET UP CF
8IFSFUIFPVUEPPSVOJUJTCFMPXNPSMFTT ※$IFDLXJUIUIFGMPXDIBSUEFWFMPQFEGPSBDBTFXIFSF
BOFYJTUJOHQJQFTZTUFNJTSFVTFEGPSB SFEVDFE 1MFBTF DPOTVMU XJUI PVS EJTUSJCVUPS JO UIF BSFB
JG ZPV OFFE UP SFDPWFS SFGSJHFSBOU BOE DIBSHF JU BHBJO
DUJOHXJSF :&4 UXJOUSJQMFEPVCMFUXJONPEFMQVCMJTIFEBTBUFDIOJDBM
EBUBTIFFU ● "OZ DPNCJOBUJPOT PG QJQF TJ[FT OPU MJTUFE JO UIF UBCMF BSF OPU VTBCMF
BZXPSLPO *TUIFVOJUUPJOTUBMMJOUIFFYJTUJOHQJQFTZTUFNB :&4
$IBOHFUIFCSBODIJOHQJQFUPBTQFDJGJFEUZQF
$IBOHFJTJNQPTTJCMF
UXJOUSJQMFEPVCMFUXJONPEFM
/0 $IBOHF
:&4 3FQBJSJTJNQPTTJCMF
1JQF TZTUFN BGUFS UIF CSBODIJOH QJQF
3FQBJSUIFEBNBHFEQBSUT
*TUIFFYJTUJOHQJQFTZTUFNUPSFVTFGSFFPGDPSSPTJPO
nBXTPSEFOUT
◎:4UBOEBSE QJQF TJ[F ○:6TBCMF
/0 3FQBJS
"JSUJHIUOFTTJT "EEJUJPOBMDIBSHJOHBNPVOUPGSFGSJHFSBOUQFSN LHN ● "OZ DPNCJOBUJPOT PG QJQF TJ[FT OPU MJTUFE JO
*TUIFFYJTUJOHQJQFTZTUFNUPSFVTFGSFFPGHBTMFBLT JNQPTTJCMF
$IFDLXIFUIFSSFGSJHFSBOUDIBSHFXBTSFRVJSFEGSFRVFOUMZGPSUIF $IFDLUIFQJQFTZTUFNGPSBJSUJHIUOFTTPOUIFTJUF -JRVJEQJQF φ UIF UBCMFBSF OPU VTBCMF
TZTUFNCFGPSF
1JQF TJ[F
/0
"JSUJHIUOFTTJT0,
3FNPWFJT
(BTQJQF φ φ
PDL JNQPTTJCMF .PEFM $PNCJOBUJPOUZQF $PNCJOBUJPOPGDBQBDJUZ
"SFUIFSFBOZCSBODIQJQFTXJUIOPJOEPPSVOJUDPOOFDUFE 3FNPWFUIPTFCSBODIFT
/0 3FNPWF '%$ 5XJO ◎ ○
"SFIFBUJOTVMBUJPONBUFSJBMTPGUIFFYJTUJOHQJQFTZTUFNUPSFVTF 3FQBJSJTJNQPTTJCMF
BOPUIFSVOJU
GSFFPGQFFMPGGTPSEFUFSJPSBUJPO
)FBUJOTVMBUJPOJTOFDFTTBSZGPSCPUIHBTBOEMJRVJEQJQFT
3FQBJSUIFEBNBHFEQBSUT
5IF NPEFM UZQFT PG FYJTUJOH VOJUT PG XIJDI CSBODIJOH QJQFT BSF SFVTBCMF
3FQBJS
OEJOHXJSFGSPN /0 5IF CSBODIJOH QJQFT VTFE XJUI NPEFMT PUIFS UIBO UIPTF MJTUFE BCPWF BSF OPU SFVTBCMF
"SFOUUIFSFBOZMPPTFQJQFTVQQPSUT 3FQBJSUIFEBNBHFEQBSUT
6TF PVS HFOVJOF CSBODIJOH QJQFT GPS 3"
/PMPPTFQJQFTVQQPSUT 4PNFMPPTFQJQFTVQQPSUT 3FQBJS
Downloaded from www.Manualslib.com manuals search5IFFYJTUJOHQJQFTZTUFNJTOPUSFVTBCMF
engine 'PSNVMB UP DBMDVMBUF BEEJUJPOBM DIBSHF WPMVNF
4XJUDIJOH 48 UP 0/ XJMM TUBSU UIF DPNQSFTTPS QMVNCJOH "SFIFBUJOTVMBUJPONBUFSJBMTJOTUBMMFEPOCPUIMJRVJEBOEHBTQJQFT
5IF VOJU XJMM TUBSU B DPPMJOH PQFSBUJPO
XIFO 48 JT 0''
PS B IFBUJOH PQFSBUJPO
XIFO 48 JT 0/ "SFPQFSBUJPOWBMWFTTVSFMZPQFOFEGPSCPUIMJRVJEBOEHBTTZTUFNT
%P OPU GBJM UP TXJUDI 48 UP 0'' XIFO B UFTU SVO JT DPNQMFUFE )BWFZPVSFDPSEFEUIFBEEJUJPOBMSFGSJHFSBOUDIBSHFWPMVNFBOESFGSJHFSBOUQJQFMFOHUIPOUIFQBOFMTMBCFM
*TUIFVOJUGSFFPGDBCMJOHFSSPSTTVDIBTVODPNQMFUFEDPOOFDUJPO
BOBCTFOUPSSFWFSTFEQIBTF
※ *ODBTFPGUIFmSTUPQFSBUJPOBGUFSUVSOJOHPOUIFQPXFSTVQQMZ
XIFOUIFVOJUSVOTJOUIFDPPMJOHNPEFBUPVUTJEFUFNQFSBUVSF "SFQSPQFSMZSBUFEFMFDUSJDBMFRVJQNFOUTVTFEGPSDJSDVJUCSFBLFSTBOEDBCMFT
¡$PSMPXFS
JUBVUPNBUJDBMMZDIBOHFTJOUPUIFDPPMJOHNPEFBGUFSJUSVOTJOUIFIFBUJOHNPEFGPSNJOVUFT %PFTOUDBCMJOHDSPTTDPOOFDUCFUXFFOVOJUT
XIFSFNPSFUIBOPOFVOJUBSFJOTUBMMFE
"SFOUJOEPPSPVUEPPSTJHOBMXJSFTDPOOFDUFEUPSFNPUFDPOUSPMXJSFT
$IFDLJOHUIFTUBUFPGUIFVOJUJOPQFSBUJPO &MFDUSJD
XJSJOH
%PJOEPPSPVUEPPSDPOOFDUJOHDBCMFTDPOOFDUCFUXFFOUIFTBNFUFSNJOBMOVNCFST
"SFFJUIFS7$5DBCUZSFDBCMFTPS8'GMBUDBCMFTVTFEGPSJOEPPSPVUEPPSDPOOFDUJOHDBCMFT
1MFBTFSFNPWFBTFSWJDFQBOFM %PFTHSPVOEJOHTBUJTGZUIF%UZQFHSPVOEJOH UZQF***HSPVOEJOH
SFRVJSFNFOUT
*TUIFVOJUHSPVOEFEXJUIBEFEJDBUFEHSPVOEJOHXJSFOPUDPOOFDUFEUPBOPUIFSVOJUTHSPVOEJOHXJSF
6TF DIFDL KPJOUT QSPWJEFE PO UIF QJQJOH CFGPSF BOE BGUFS UIF $IBSHFQPSUPGUIF "SFDBCMFTGSFFPGMPPTFTDSFXTBUUIFJSDPOOFDUJPOQPJOUT
DVMBUJPO SFTVMU GPVSXBZ WBMWF JOTUBMMFE JOTJEF UIF PVUEPPS VOJU GPS DIFDLJOH $IFDLKPJOUPGUIFQJQF HBTPQFSBUJPOWBMWF "SFDBCMFTIFMEEPXOXJUIDBCMFDMBNQTTPUIBUOPFYUFSOBMGPSDFXPSLTPOUPUFSNJOBMDPOOFDUJPOT
SHF SFGSJHFSBOU EJTDIBSHF QSFTTVSF BOE TVDUJPO QSFTTVSF %JTDIBSHFQSFTTVSF 4VDUJPOQSFTTVSF *TJOEPPSVOJUJOTUBMMBUJPOXPSLDPNQMFUFE
$PPMJOHPQFSBUJPO ー *OEPPS VOJU
"TJOEJDBUFEJOUIFUBCMFTIPXOPOUIFSJHIU
QSFTTVSFEFUFDUFE )JHIQSFTTVSF
-PXQSFTTVSF
8IFSFBGBDFDPWFSTIPVMECFBUUBDIFEPOUPBOJOEPPSVOJU
JTUIFGBDFDPWFSBUUBDIFEUPUIFJOEPPSVOJU
BUFBDIQPJOUXJMMWBSZEFQFOEJOHPOXIFUIFSBDPPMJOHPS 4VDUJPOQSFTTVSF %JTDIBSHFQSFTTVSF
)FBUJOHPQFSBUJPO 5FTU SVO QSPDFEVSF ● "MXBZTDBSSZPVUBUFTUSVOBOEDIFDLUIFGPMMPXJOHJOPSEFSBTMJTUFE
IFBUJOHPQFSBUJPOIBTCFFOTFMFDUFE -PXQSFTTVSF
)JHIQSFTTVSF
1MFBTFSFNPWFBTFSWJDFQBOFM ②
③
0QFOUIFMJRVJETJEFPQFSBUJPOWBMWFGVMMZ
$MPTFUIFQBOFM
FGSJHFSBOU GSPN
%FGSPTU DPOUSPM TXJUDIJOH 48
④ 8IFSFBSFNPUFDPOUSPMVOJUJTVTFEGPSVOJUTFUVQPOUIFJOTUBMMBUJPOTJUF
GPMMPXJOTUSVDUJPOTGPSVOJUTFUVQPOUIFJOTUBMMBUJPOTJUFXJUIBSFNPUFDPOUSPMVOJU
ZMJOEFS WBMWF JT ・8IFO UIJT TXJUDI JT UVSOFE 0/
UIF VOJU XJMM SVO JO UIF EFGSPTU NPEF NPSF GSFRVFOUMZ ⑤
48480''UIFVOJUXJMMTUBSUBDPPMJOHPQFSBUJPO
・4FU UIJT TXJUDI UP 0/
XIFO JOTUBMMFE JO B SFHJPO XIFSF PVUEPPS UFNQFSBUVSF GBMMT CFMPX [FSP EVSJOH UIF TFBTPO UIF VOJU JT SVO GPS B 48480/UIFVOJUXJMMTUBSUBIFBUJOHPQFSBUJPO
⑥ 8IFOUIFVOJUTUBSUTPQFSBUJPO
QSFTTUIFXJOEEJSFDUJPOCVUUPOQSPWJEFEPOUIFSFNPUFDPOUSPMVOJUUPDIFDLJUTPQFSBUJPO
IFBUJOH PQFSBUJPO
⑦ 1MBDFZPVSIBOECFGPSFUIFJOEPPSVOJUTEJGGVTFSUPDIFDLXIFUIFSDPME XBSN
XJOETDPNFPVUJOBDPPMJOH IFBUJOH
PQFSBUJPO
4OPX HVBSE GBO DPOUSPM 48
⑧ .BLFTVSFUIBUBSFE-&%JTOPUCMJOLJOH
・8IFO UIJT TXJUDI JT UVSOFE PO
UIF PVUEPPS VOJU GBO XJMM SVO GPS TFDPOET JO FWFSZ NJOVUFT
XIFO PVUEPPS UFNQFSBUVSF GBMMT UP ⑨ 8IFOZPVDPNQMFUFUIFUFTUSVO
QMFBTFUVSOPO48GPSTFDPOEBOECFTVSFUPFOEBUFTUSVO
℃ PS MPXFS BOE UIF DPNQSFTTPS JT OPU SVOOJOH ⑩ 8IFSFPQUJPOTBSFVTFE
DIFDLUIFJSPQFSBUJPOBDDPSEJOHUPUIFSFTQFDUJWFJOTUSVDUJPONBOVBMT
・8IFO UIF VOJU JT VTFE JO B WFSZ TOPXZ DPVOUSZ
TFU UIJT TXJUDI UP 0/
4XJUDIFT GPS POTJUF TFUUJOH
FS BDDFTTPSZ
'BJMVSF EJBHOPTJT JO B UFTU SVO 0/
48 48
O B nBU CBTF
)FFEUIFGPMMPXJOHPOUIFmSTUPQFSBUJPOBGUFSUVSOJOHPOUIFDJSDVJUCSFBLFS "MMTFUUP0''GPSTIJQNFOU
5IJTPVUEPPSVOJUNBZTUBSUJOUIFTUBOECZNPEF XBJUJOHGPSBDPNQSFTTPSTUBSUVQ
XIJDIDBODPOUJOVFVQUPNJOVUFT
UPQSFWFOUUIFPJMMFWFMJOUIF ※ %P OPU PQFSBUF 48
48
48
48
DPNQSFTTPSGSPNMPXFSJOHPOUIFmSTUPQFSBUJPOBGUFSUVSOJOHPOUIFDJSDVJUCSFBLFS*GUIBUJTUIFDBTF
EPOPUTVTQFDUBVOJUGBJMVSF ※ 3FGFS UP 5&$)/*$"- ."/6"- BCPVU 48 1VNQ EPXO 48
BJOIPMFTXJUI
65*-*;"5*0/0'&9*45*/(1*1*/(
$IFDLXIFUIFSBOFYJTUJOHQJQFTZTUFNJTSFVTBCMFPSOPUCZVTJOHUIFGPMMPXJOHnPXDIBSU
45"35 5BCMF PG QJQF TJ[F SFTUSJDUJPOT
◎:4UBOEBSE QJQF TJ[F ○:6TBCMF △:3FTUSJDUFE UP TIPSUFS QJQF MFOHUI MJNJUT $PPM↓ $PPMJOH DBQBDJUZ ESPQ
"SFBOPVUEPPSVOJUBOEBOJOEPPSVOJUDPOOFDUFEUPUIF /0
FYJTUJOHQJQFTZTUFNUPSFVTF
"EEJUJPOBMDIBSHFWPMVNFQFSNFUFSPGQJQF LHN LHN
:&4
/0 8IJDIPGUIFGPMMPXJOHSFGSJHFSBUJPOPJMT $BOAU
-JRVJEQJQF φ φ φ
"SFUIFFYJTUJOHVOJUTPVSQSPEVDUT EPFTUIFFYJTUJOHVOJUVTF /0 .BLFBOJORVJSZ 6TF 1JQF TJ[F
:&4 :&4
4VOJTP
.4
#BSSFM'SFF[F
)"#
'SFPM
GPSSFVTBCJMJUZ (BTQJQF φ φ φ
FUIFSPJM
FTUFSPJM
$BO6TF 6TBCJMJUZ $PPM↓ ◎ △
%PFTUIFFYJTUJOHQJQFTZTUFNUPSFVTFTBUJTGZBMMPGUIFGPMMPXJOH 7 .BYJNVNPOFXBZQJQFMFOHUI
5IFQJQFMFOHUIJTNPSMFTT
5IFQJQFTJ[FDPOGPSNTUPUIFUBCMFPGQJQFTJ[FSFTUSJDUJPOT -FOHUIDPWFSFEXJUIPVUBEEJUJPOBMDIBSHF
EDBCMF
5IFFMFWBUJPOEJGGFSFODFCFUXFFOUIFJOEPPSBOEPVUEPPSVOJUT /0
DPOGPSNTUPUIFGPMMPXJOHSFTUSJDUJPOT
8IFSFUIFPVUEPPSVOJUJTBCPWFNPSMFTT ● 5IF QJQF MFOHUI TIPVME CF BU MFBTU N *G UIF QJQF MFOHUI JT TIPSUFS UIBO N
UIF RVBOUJUZ PG SFGSJHFSBOU OFFET UP CF
8IFSFUIFPVUEPPSVOJUJTCFMPXNPSMFTT ※$IFDLXJUIUIFGMPXDIBSUEFWFMPQFEGPSBDBTFXIFSF
BOFYJTUJOHQJQFTZTUFNJTSFVTFEGPSB SFEVDFE 1MFBTF DPOTVMU XJUI PVS EJTUSJCVUPS JO UIF BSFB
JG ZPV OFFE UP SFDPWFS SFGSJHFSBOU BOE DIBSHF JU BHBJO
UJOHXJSF :&4 UXJOUSJQMFEPVCMFUXJONPEFMQVCMJTIFEBTBUFDIOJDBM
EBUBTIFFU ● "OZ DPNCJOBUJPOT PG QJQF TJ[FT OPU MJTUFE JO UIF UBCMF BSF OPU VTBCMF
ZXPSLPO *TUIFVOJUUPJOTUBMMJOUIFFYJTUJOHQJQFTZTUFNB :&4
$IBOHFUIFCSBODIJOHQJQFUPBTQFDJGJFEUZQF
$IBOHFJTJNQPTTJCMF
UXJOUSJQMFEPVCMFUXJONPEFM
/0 $IBOHF
:&4 3FQBJSJTJNQPTTJCMF
1JQF TZTUFN BGUFS UIF CSBODIJOH QJQF
3FQBJSUIFEBNBHFEQBSUT
*TUIFFYJTUJOHQJQFTZTUFNUPSFVTFGSFFPGDPSSPTJPO
nBXTPSEFOUT
◎:4UBOEBSE QJQF TJ[F ○:6TBCMF
/0 3FQBJS
● "OZ DPNCJOBUJPOT PG QJQF TJ[FT OPU MJTUFE JO
-
*TUIFFYJTUJOHQJQFTZTUFNUPSFVTFGSFFPGHBTMFBLT
"JSUJHIUOFTTJT "EEJUJPOBMDIBSHJOHBNPVOUPGSFGSJHFSBOUQFSN LHN
JNQPTTJCMF
$IFDLXIFUIFSSFGSJHFSBOUDIBSHFXBTSFRVJSFEGSFRVFOUMZGPSUIF -JRVJEQJQF φ UIF UBCMFBSF OPU VTBCMF
220 -
$IFDLUIFQJQFTZTUFNGPSBJSUJHIUOFTTPOUIFTJUF
TZTUFNCFGPSF
1JQF TJ[F
/0
"JSUJHIUOFTTJT0,
3FNPWFJT
(BTQJQF φ φ
PDL JNQPTTJCMF .PEFM $PNCJOBUJPOUZQF $PNCJOBUJPOPGDBQBDJUZ
"SFUIFSFBOZCSBODIQJQFTXJUIOPJOEPPSVOJUDPOOFDUFE 3FNPWFUIPTFCSBODIFT
/0 3FNPWF '%$ 5XJO ◎ ○
"SFIFBUJOTVMBUJPONBUFSJBMTPGUIFFYJTUJOHQJQFTZTUFNUPSFVTF 3FQBJSJTJNQPTTJCMF
BOPUIFSVOJU
GSFFPGQFFMPGGTPSEFUFSJPSBUJPO
)FBUJOTVMBUJPOJTOFDFTTBSZGPSCPUIHBTBOEMJRVJEQJQFT
3FQBJSUIFEBNBHFEQBSUT
5IF NPEFM UZQFT PG FYJTUJOH VOJUT PG XIJDI CSBODIJOH QJQFT BSF SFVTBCMF
3FQBJS
EJOHXJSFGSPN /0 5IF CSBODIJOH QJQFT VTFE XJUI NPEFMT PUIFS UIBO UIPTF MJTUFE BCPWF BSF OPU SFVTBCMF
"SFOUUIFSFBOZMPPTFQJQFTVQQPSUT 3FQBJSUIFEBNBHFEQBSUT
6TF PVS HFOVJOF CSBODIJOH QJQFT GPS 3"
/PMPPTFQJQFTVQQPSUT 4PNFMPPTFQJQFTVQQPSUT 3FQBJS
'PSNVMB UP DBMDVMBUF BEEJUJPOBM DIBSHF WPMVNF
5IFFYJTUJOHQJQFTZTUFNJTOPUSFVTBCMF
OFDUJPOTGSPN 5IFFYJTUJOHQJQFTZTUFNJTSFVTBCMF *OTUBMMBOFXQJQFTZTUFN "EEJUJPOBM DIBSHF WPMVNF LH
\.BJO QJQF MFOHUI N
o -FOHUI DPWFSFE XJUIPVU BEEJUJPOBM DIBSHF TIPXO JO UIF UBCMF N
^ ×
"EEJUJPOBM DIBSHF WPMVNF QFS NFUFS PG QJQF TIPXO JO UIF UBCMF LHN
+
5PUBM MFOHUI PG CSBODI QJQFT N
×"EEJUJPOBM DIBSHF WPMVNF QFS NFUFS PG QJQF TIPXO JO UIF UBCMF LHN
8"3/*/( 8IFSF UIF FYJTUJOH VOJU DBO CF SVO GPS B DPPMJOH PQFSBUJPO ※ *G ZPV PCUBJO B OFHBUJWF GJHVSF BT B SFTVMU PG DBMDVMBUJPO
OP BEEJUJPOBM SFGSJHFSBOU OFFET UP CF DIBSHFE
$BSSZ PVU UIF GPMMPXJOH TUFQT XJUI UIF FYDJTJOH VOJU JO UIF PSEFS PG
BOE
&YBNQMF
8IFO BO 7 TJOHMF JOTUBMMBUJPO
JT JOTUBMMFE JO B N MPOH FYJTUJOH QJQF TZTUFN MJRVJE φ
HBT φ
DFQBOFM UIF RVBOUJUZ PG SFGSJHFSBOU UP DIBSHF BEEJUJPOBMMZ TIPVME CF NN
Y LHN LH
3VO UIF VOJU GPS NJOVUFT GPS B DPPMJOH PQFSBUJPO
4UPQ UIF JOEPPS GBO BOE SVO UIF VOJU GPS NJOVUFT GPS B DPPMJOH PQFSBUJPO SFUVSOJOH MJRVJE
&YBNQMF
8IFO BO 7 UXJO JOTUBMMBUJPO
JT JOTUBMMFE JO B N MPOH FYJTUJOH QJQF TZTUFN
NBJO QJQF MFOHUI N
MJRVJE φ
HBT φ QJQF MFOHUI BGUFS CSBODIJOH QJQF N Y
MJRVJE φ
HBT φ
$MPTF UIF MJRVJE TJEF PQFSBUJPO WBMWF PG UIF PVUEPPS VOJU BOE QVNQ EPXO SFGSJHFSBOU SFDPWFSZ
UIF RVBOUJUZ PG SFGSJHFSBOU UP DIBSHF BEEJUJPOBMMZ TIPVME CF NN
Y LHN N Y Y LHN LH
#MPX XJUI OJUSPHFO HBT ※ *G EJTDPMPSFE SFGSJHFSBUJPO PJM PS BOZ GPSFJHO NBUUFST JT EJTDIBSHFE CZ
UIF CMPX
XBTI UIF QJQF TZTUFN PS JOTUBMM B OFX QJQF TZTUFN
8IFSF UIF FYJTUJOH VOJU DBOOPU CF SVO GPS B DPPMJOH PQFSBUJPO
● 'PS UIF GMBSF OVU
EP OPU VTF UIF PME POF
CVU VTF UIF POF TVQQMJFE XJUI UIF PVUEPPS VOJU
'10 • PAC-DB-142
1SPDFTT B GMBSF UP UIF EJNFOTJPOT TQFDJGJFE GPS 3" 8BTI UIF QJQF TZTUFN PS JOTUBMM B OFX QJQF TZTUFN
● 5VSO POTJUF TFUUJOH TXJUDI 48 UP UIF 0/ QPTJUJPO 8IFSF UIF HBT QJQF TJ[F JT φ
● *G ZPV DIPPTF UP XBTI UIF QJQF TZTUFN
DPOUBDU PVS EJTUSJCVUPS JO UIF BSFB
'10 • PAC-DB-142
'10 • PAC-DB-142
'10 • PAC-DB-142
'10 • PAC-DB-142
7BDVVNJOHCFHJOT 1BZBUUFOUJPOUPUIFGPMMPXJOHQPJOUTJOBEEJUJPOUPUIFBCPWFGPSUIF
<8PSLnPX> 8IFO UIF TZTUFN IBT SFNBJOJOH NPJTUVSF 3VO UIF WBDVVN QVNQ GPS BU MFBTU POF IPVS BGUFS UIF WBDVVN
JOTJEF PS B MFBLZ QPJOU
UIF WBDVVN HBVHF HBVHF TIPXT L1B PS MPXFS NN)H PS MPXFS
3"BOEDPNQBUJCMFNBDIJOFT
JOEJDBUPS XJMM SJTF 7BDVVNJOHDPNQMFUFE ○5P QSFWFOU B EJGGFSFOU PJM GSPN FOUFSJOH
BTTJHO EFEJDBUFE UPPMT
FUD UP FBDI 8"3/*/(
$IFDL UIF TZTUFN GPS B MFBLZ QPJOU BOE $POmSNUIBUUIFWBDVVNHBVHFJOEJDBUPSEPFTOPUSJTFFWFOJG
UIFTZTUFNJTMFGUGPSPOFIPVSPSNPSF SFGSJHFSBOU UZQF 6OEFS OP DJSDVNTUBODFT NVTU B HBVHF NBOJGPME BOE B DIBSHF
UIFO ESBX BJS UP DSFBUF B WBDVVN BHBJO
7BDVVNHBVHFDIFDL IPTF JO QBSUJDVMBS CF TIBSFE XJUI PUIFS SFGSJHFSBOU UZQFT 3
3$
FUD
○6TF B DPVOUFSnPX QSFWFOUJPO BEBQUFS UP QSFWFOU WBDVVN QVNQ PJM GSPN
'JMMSFGSJHFSBOU FOUFSJOH UIF SFGSJHFSBOU TZTUFN
"EEJUJPOBM SFGSJHFSBOU DIBSHF
$BMDVMBUF B SFRVJSFE SFGSJHFSBOU DIBSHF WPMVNF GSPN UIF GPMMPXJOH UBCMF 5XJO
USJQMF
8UXJOUZQF
4JOHMFUZQF "EEJUJPOBMDIBSHFWPMVNF LH
$"65*0/
*UFN
"EEJUJPOBMDIBSHFWPMVNF LH
3FGSJHFSBOUWPMVNF *OTUBMMBUJPOTQJQFMFOHUI N
4UBOEBSESFGSJHFSBOU 1JQFMFOHUIGPS QFSNFUFSPGSFGSJHFSBOUQJQJOH 3FGSJHFSBOUWPMVNF *OTUBMMBUJPOTQJQFMFOHUI N
1JQFMFOHUIGPS DIBSHFEGPSTIJQNFOU DPWFSFEXJUIPVUBEEJUJPOBM
*UFN 4UBOEBSESFGSJHFSBOU
TUBOEBSESFGSJHFSBOU QFSNFUFSPGSFGSJHFSBOUQJQJOH DIBSHFEGPSTIJQNFOU DPWFSFEXJUIPVUBEEJUJPOBM DIBSHFWPMVNF LH
TUBOEBSESFGSJHFSBOU MJRVJEQJQF
DIBSHFWPMVNF LH
DIBSHFWPMVNF N
MJRVJEQJQF
DIBSHFWPMVNF N
BUUIFGBDUPSZ LH
SFGSJHFSBOUDIBSHF
$BQBDJUZ BUUIFGBDUPSZ LH
SFGSJHFSBOUDIBSHF $BQBDJUZ .BJOQJQF #SBODIQJQF
.PEFM7 .PEFM7
.PEFM7 .PEFM7
5FTU SV
" UFTU SVO
.PEFM7 .PEFM7 48 GP
4XJUDIJOH
● " TUBOEBSE SFGSJHFSBOU DIBSHF WPMVNF NFBOT B SFGSJHFSBOU DIBSHF WPMVNF GPS BO JOTUBMMBUJPO XJUI N MPOH SFGSJHFSBOU QJQJOH
5IF VOJU X
● 5IJT VOJU DPOUBJOT GBDUPSZ DIBSHFE SFGSJHFSBOU DPWFSJOH N PG SFGSJHFSBOU QJQJOH BOE BEEJUJPOBM SFGSJHFSBOU DIBSHF PO UIF JOTUBMMBUJPO TJUF JT OPU SFRVJSFE GPS BO JOTUBMMBUJPO XJUI VQ UP N SFGSJHFSBOU QJQJOH PQFSBUJPO
8IFO SFGSJHFSBOU QJQJOH FYDFFET N
BEEJUJPOBMMZ DIBSHF BO BNPVOU DBMDVMBUFE GSPN UIF QJQF MFOHUI BOE UIF BCPWF UBCMF GPS UIF QPSUJPO JO FYDFTT PG N
%P OPU GB
● 8IFO SFGSJHFSBOU QJQJOH JT TIPSUFS UIBO N
SFEVDF SFGSJHFSBOU CZ LH GSPN UIF GBDUPSZ DIBSHFE WPMVNF BOE BEKVTU UP LH
● *G BO FYJTUJOH QJQF TZTUFN JT VTFE
B SFRVJSFE SFGSJHFSBOU DIBSHF WPMVNF XJMM WBSZ EFQFOEJOH PO UIF MJRVJE QJQF TJ[F 'PS GVSUIFS JOGPSNBUJPO
TFFi 65*-*;"5*0/ 0' &9*45*/( 1*1*/(w
$IFDL
6TF DIFDL KP
'PSNVMBUPDBMDVMBUFUIFWPMVNFPGBEEJUJPOBMSFGSJHFSBOUSFRVJSFE JOTJEF UIF PV
8IFO BO BEEJUJPOBM DIBSHF WPMVNF DBMDVMBUJPO SFTVMU JT OFHBUJWF
"TJOEJDBUFE
.PEFM∼7 "EEJUJPOBMDIBSHFWPMVNF LH
\.BJOQJQFMFOHUI N
o-FOHUIDPWFSFEXJUIPVUBEEJUJPOBMDIBSHF N
^Y LHN
5PUBMMFOHUIPGCSBODIQJQFT N
Y LHN
● 5P DIBSHF SFGSJHFSBOU BHBJO SFDPWFS SFGSJHFSBOU GSPN UIF TZTUFN mSTU BOE UIFO DIBSHF UIF WPMVNF DBMDVMBUFE GSPN UIF BCPWF UBCMF 4UBOEBSE SFGSJHFSBOU DIBSHF WPMVNF CSBODI QJQFT DIBSHF WPMVNF
4FUUJOH
-
%FGSPTU D
225 -
・8IFO UI
$IBSHJOHSFGSJHFSBOU ・4FU UIJT
● 4JODF 3" SFGSJHFSBOU NVTU CF DIBSHFE JO UIF MJRVJE QIBTF
ZPV TIPVME DIBSHF JU
LFFQJOH UIF DPOUBJOFS DZMJOEFS VQTJEF EPXO PS VTJOH B SFGSJHFSBOU DZMJOEFS FRVJQQFE XJUI B TJQIPO UVCF UIF TFB
● $IBSHF SFGSJHFSBOU BMXBZT GSPN UIF MJRVJE TJEF TFSWJDF QPSU XJUI UIF PQFSBUJPO WBMWF TIVU 8IFO ZPV mOE JU EJGmDVMU UP DIBSHF B SFRVJSFE BNPVOU
GVMMZ PQFO UIF PVUEPPS VOJU WBMWFT PO CPUI MJRVJE BOE HBT TJEFT BOE DIBSHF SFGSJHFSBOU GSPN UIF
4OPX HV
HBT TVDUJPO
TJEF TFSWJDF QPSU
XIJMF SVOOJOH UIF VOJU JO UIF DPPMJOH NPEF *O EPJOH TP
DBSF NVTU CF UBLFO TP UIBU SFGSJHFSBOU NBZ CF EJTDIBSHFE GSPN UIF DZMJOEFS JO UIF MJRVJE QIBTF BMM UIF UJNF 8IFO UIF DZMJOEFS WBMWF JT UISPUUMFE EPXO ・8IFO UI
PS B EFEJDBUFE DPOWFSTJPO UPPM UP DIBOHF MJRVJEQIBTF SFGSJHFSBOU JOUP NJTU JT VTFE UP QSPUFDU UIF DPNQSFTTPS
IPXFWFS
BEKVTU DIBSHF DPOEJUJPOT TP UIBU SFGSJHFSBOU XJMM HBTJGZ VQPO FOUFSJOH UIF VOJU PVUEPPS
● *O DIBSHJOH SFGSJHFSBOU
BMXBZT DIBSHF B DBMDVMBUFE WPMVNF CZ VTJOH B TDBMF UP NFBTVSF UIF DIBSHF WPMVNF ・8IFO UI
● 8IFO SFGSJHFSBOU JT DIBSHFE XJUI UIF VOJU CFJOH SVO
DPNQMFUF B DIBSHF PQFSBUJPO XJUIJO NJOVUFT 3VOOJOH UIF VOJU XJUI BO JOTVGmDJFOU RVBOUJUZ PG SFGSJHFSBOU GPS B MPOH UJNF DBO DBVTF B DPNQSFTTPS GBJMVSF
/05& 1VU EPXO UIF SFGSJHFSBOU WPMVNF DBMDVMBUFE GSPN UIF QJQF MFOHUI POUP UIF DBVUJPO MBCFM BUUBDIFE PO UIF CBDL TJEF PG UIF TFSWJDF QBOFM
#BOE BDDFTTPSZ
1JQFDPWFS BDDFTTPSZ
'BJMVSF
)FBUJOHBOEDPOEFOTBUJPOQSFWFOUJPO &SSPSJOEJDBUFEPO
SFNPUFDPOUSPMV
%SFTTSFGSJHFSBOUQJQFT CPUIHBTBOEMJRVJEQJQFT
GPSIFBUJOTVMBUJPOBOEQSFWFOUJPOPGEFXDPOEFOTBUJPO
&
6TFBIFBUJOTVMBUJOHNBUFSJBMUIBUDBOXJUITUBOE℃PSBIJHIFSUFNQFSBUVSF1PPSIFBUJOTVMBUJOHDBQBDJUZDBODBVTFIFBUJOTVMBUJPOQSPCMFNTPSDBCMFEFUFSJPSBUJPO
*NQSPQFS IFBU JOTVMBUJPOBOUJEFX ESFTTJOH DBO SFTVMU JO B XBUFS MFBL PS ESJQQJOH DBVTJOH EBNBHF UP IPVTFIPME FGGFDUT
FUD &
"MM HBT QJQFT NVTU CF TFDVSFMZ IFBU JOTVMBUFE JO PSEFS UP QSFWFOU EBNBHF GSPN ESJQQJOH XBUFS UIBU DPNFT GSPN UIF DPOEFOTBUJPO GPSNFE PO UIFN EVSJOH B DPPMJOH PQFSBUJPO PS QFSTPOBM
JOKVSZ GSPN CVSOT CFDBVTF UIFJS TVSGBDF DBO SFBDI RVJUF B IJHI UFNQFSBUVSF EVF UP EJTDIBSHFE HBT nPXJOH JOTJEF EVSJOH B IFBUJOH PQFSBUJPO 8JSFTGPSDPOOFDUJOHJOEPPS &
&YUFSJPSUBQF
8SBQ JOEPPS VOJUT nBSF KPJOUT XJUI IFBU JOTVMBUJOH QBSUT QJQF DPWFS
GPS IFBU JOTVMBUJPO CPUI HBT BOE MJRVJE QJQFT
BOEPVUEPPSVOJUT
● *GBOFSSPS
(JWF IFBU JOTVMBUJPO UP CPUI HBT BOE MJRVJE TJEF QJQFT #VOEMF B IFBU JOTVMBUJOH NBUFSJBM BOE B QJQF UJHIUMZ UPHFUIFS TP UIBU OP HBQT NBZ CF MFGU CFUXFFO UIFN BOE XSBQ UIFN UPHFUIFS (BTQJQJOH
XJUI B DPOOFDUJOH DBCMF CZ B ESFTTJOH UBQF
"MUIPVHI JU JT WFSJmFE JO B UFTU UIBU UIJT BJS DPOEJUJPOJOH VOJU TIPXT TBUJTGBDUPSZ QFSGPSNBODF VOEFS +*4 DPOEFOTBUJPO UFTU DPOEJUJPOT
CPUI HBT BOE MJRVJE QJQFT OFFE UP CF ESFTTFE
-JRVJEQJQJOH
5IFTUB
XJUI NN PS UIJDLFS IFBU JOTVMBUJPO NBUFSJBMT BCPWF UIF DFJMJOH XIFSF SFMBUJWF IVNJEJUZ FYDFFET JOTVMBUJPO 5IF GPMMPXJO
'10 • PAC-DB-142
%3"*/1*1*/(803, 7BMWFGPSBDP
7BMWFGPSBIF
● &YFDVUFESBJOQJQJOHCZVTJOHBESBJOFMCPXBOEESBJOHSPNNFUTTVQQMJFETFQBSBUFMZBT ○ 5IFSFBSFESBJOIPMFTQSPWJEFEPOUIFCPUUPNQMBUFPGBOPVUEPPSVOJUUPEJTDIBSHF
PQUJPOBMQBSUT
XIFSFXBUFSESBJOFEGSPNUIFPVUEPPSVOJUJTBQSPCMFN DPOEFOTFEXBUFS
)FFEUI
○ 8IFODPOEFOTFEXBUFSOFFETUPCFMFEUPBESBJO
FUD
JOTUBMMUIFVOJUPOBnBUCBTF 5IJTPVUEPPS
JOUIFDPNQSF
TVQQMJFETFQBSBUFMZBTBOPQUJPOBMQBSU
PSDPODSFUFCMPDLT
%SBJOFMCPX QF
○ $POOFDUBESBJOFMCPXBTTIPXOJOUIFJMMVTUSBUJPOBOEDMPTFUIFPUIFSUXPESBJOIPMFT
%SBJOHSPNNFU XJUIHSPNNFUT
)BSEWJOZMDIMPSJEFQJQFGPSHFOFSBMQVSQPTF 71
QFT
65*-*;
&-&$53*$"-8*3*/(803, 'PSEFUBJMTPGFMFDUSJDBMDBCMJOH
SFGFSUPUIFJOEPPSVOJUJOTUBMMBUJPONBOVBM $IFDLXIFUIFSBO
&MFDUSJDBMJOTUBMMBUJPOXPSLNVTUCFQFSGPSNFECZBOFMFDUSJDBMJOTUBMMBUJPOTFSWJDFQSPWJEFSRVBMJmFECZBQPXFSQSPWJEFSPGUIFDPVOUSZ ● $POOFDUBQBJSCFBSJOHBDPNNPOUFSNJOBMOVNCFSXJUIBOJOEPPSPVUEPPSDPOOFDUJOHXJSF
&MFDUSJDBMJOTUBMMBUJPOXPSLNVTUCFFYFDVUFEBDDPSEJOHUPUIFUFDIOJDBMTUBOEBSETBOEPUIFSSFHVMBUJPOTBQQMJDBCMFUPFMFDUSJDBM ● *ODBCMJOH
GBTUFODBCMFTTFDVSFMZXJUIDBCMFDMBNQTTPUIBUOPFYUFSOBMGPSDFNBZXPSLPOUFSNJOBMDPOOFDUJPOT
"SFBOPVUEPPSV
JOTUBMMBUJPOTJOUIFDPVOUSZ ● (SPVOEJOHUFSNJOBMTBSFQSPWJEFEJOUIFDPOUSPMCPY FYJTUJOHQJQFTZT
%POPUVTFBOZTVQQMZDPSEMJHIUFSUIBOPOFTQFDJmFEJOQBSFOUIFTFTGPSFBDIUZQFCFMPX
●
CSBJEFEDPSE DPEFEFTJHOBUJPO*&$
PSEJOBSZUPVHISVCCFSTIFBUIFEDPSE DPEFEFTJHOBUJPO*&$
1PXFSTPVSDF
TJHOBMMJOFBOEHSPVOEUFSNJOBMCMPDL
"SFUIF
nBUUXJOUJOTFMDPSE DPEFEFTJHOBUJPO*&$
%POPUVTFBOZUIJOHMJHIUFSUIBOQPMZDIMPSPQSFOFTIFBUIFEnFYJCMFDPSE DPEFEFTJHOBUJPO*&$
GPSTVQQMZDPSETPG (SPVOEJOHUFSNJOBM
QBSUTPGBQQMJBODFTGPSPVUEPPSVTF ○%POPUDPOOFDUUPUIFHSPVOEJOHXJSFGSPNBOPUIFSVOJU
CVUJOTUBMMBEFEJDBUFEXJSFVQUPUIF
(SPVOEUIFVOJU%POPUDPOOFDUUIFHSPVOEJOHXJSFUPBHBTQJQF
XBUFSQJQF
MJHIUOJOHSPEPSUFMFQIPOFHSPVOEJOHXJSF
●
HSPVOEJOHXJSFGSPNUIFEJTUSJCVUJPOCPBSE
*GJNQSPQFSZHSPVOEFE
BOFMFDUSJDTIPDLPSNBMGVODUJPONBZSFTVMU %PFTUIFFYJTUJOHQ
"HSPVOEJOHXJSFNVTUCFDPOOFDUFECFGPSFDPOOFDUJOHUIFQPXFSDBCMF1SPWJEFBHSPVOEJOHXJSFMPOHFSUIBOUIFQPXFSDBCMF
●
8JSJOHDMBNQ
5IFQJQFMFOHUI
5IFQJQFTJ[FD
5IFJOTUBMMBUJPOPGBOJNQVMTFXJUITUBOEJOHUZQFFBSUIMFBLBHFCSFBLFSJTOFDFTTBSZ"GBJMVSFUPJOTUBMMBOFBSUIMFBLBHFCSFBLFS
●
○'BTUFODBCMFTBOEQSPUFDUUIFUFSNJOBMDPOOFDUJPOGSPNFYUFSOBMGPSDF
5IFFMFWBUJPOE
DBOSFTVMUJOBOBDDDJEFOUTVDIBTBOFMFDUSJDTIPDLPSBmSF DPOGPSNTUPUI
%POPUUVSOPOUIFQPXFSVOUJMUIFFMFDUSJDBMXPSLJTDPNQMFUFUFE
● 8IFSFUIFPV
8JSJOHEJBHSBN 8IFSFUIFPV
%POPUVTFBDPOEFOTJWFDBQBDJUPSGPSQPXFSGBDUPSJNQSPWFNFOUVOEFSBOZDJSDVNTUBODFT *UEPTFOPUJNQSPWFQPXFSGBDUPS
●
○*UJTBUUBDIFEPOUIFCBDLTJEFPGUIFTFSWJDFQBOFM
XIJMFJUDBODBVTFBOBCOPSNBMPWFSIFBUBDDJEFOU
'PSQPXFSTVQQMZDBCMFT
VTFDPOEVJUT
● .4DSFX
0VUHPJOHDBCMFEJSFDUJPO *TUIFVOJUUPJOTU
%POPUMBZFMFDUSPOJDDPOUSPMDBCMFT SFNPUFDPOUSPMBOETJHOBMJOHXJSFT
BOEPUIFSDBCMFTUPHFUIFSPVUTJEFUIFVOJU-BZJOHUIFN
●
UXJOUSJQMFEPVC
UPHFUIFSDBOSFTVMUJOUIFNBMGVODUJPOJOHPSBGBJMVSFPGUIFVOJUEVFUPFMFDUSJDOPJTFT ○"TMJLFUIFSFGSJHFSBOUQJQF
JUDBOCFMFUPVUJOBOZPGUIFGPMMPXJOHEJSFDUJPOTTJEFSJHIU
GSPOU
'BTUFODBCMFTTPUIBUNBZOPUUPVDIUIFQJQJOH
FUD
● .PEFM SFBSBOEEPXOXBSE
8IFODBCMFTBSFDPOOFDUFE
NBLFTVSFUIBUBMMFMFDUSJDBMDPNQPOFOUTXJUIJOUIFFMFDUSJDBMDPNQPOFOUCPYBSFGSFFPGMPPTF
● 7∼7
*TUIFFYJTUJOHQJQF
DPOOFDUPS DPVQMJOH PS UFSNJOBM DPOOFDUJPO BOE UIFO BUUBDI UIF DPWFS TFDVSFMZ *NQSPQFS DPWFS BUUBDINFOU DBO SFTVMU JO
NBMGVODUJPOJOHPSBGBJMVSFPGUIFVOJU
JGXBUFSQFOFUSBUFTJOUPUIFCPY
×
"MXBZTVTFBUISFFDPSFDBCMFGPSBOJOEPPSPVUEPPSDPOOFDUJOHDBCMF/FWFSVTFBTIJFMEDBCMF
●
○
*TUIFFYJTUJOHQJQ
$IFDLXIFUIFSS
UIFTZTUFNCFGPSF
● "MXBZT QFSGPSN HSPVOEJOH TZTUFN JOTUBMMBUJPO XPSL
1PXFSDBCMF
JOEPPSPVUEPPSDPOOFDUJOHXJSFT XJUIUIFQPXFSDPSEVOQMVHHFE
"SFUIFSFBOZCSB
7$5DBCUZSFDBCMF 77'nBUDBCMF DPSFDBCMF 4IJFMEDBCMF
"MXBZTVTFBOFBSUIMFBLBHFDJSDVJUCSFBLFSEFTJHOFEGPS
$"65*0/ JOWFSUFSDJSDVJUTUPQSFWFOUBGBVMUZPQFSBUJPO "SFIFBUJOTVMBUJP
SFVTFGSFFPGQFFM
.PEFM 1PXFSTPVSDF 1PXFSDBCMFUIJDLOFTT NN
."9PWFSDVSSFOU "
$BCMFMFOHUI N
(SPVOEJOHXJSFUIJDLOFTT *OEPPSPVUEPPSXJSFUIJDLOFTT×OVNCFS )FBUJOTVMBUJPOJT
7/ 4JOHMFQIBTFXJSF
&BSUIMFBLBHFCSFBLFS &BSUIMFBLBHFCSFBLFS 7/ 7)[
)BSNPOJDSFTJTUBOUUZQF
)BSNPOJDSFTJTUBOUUZQF
7)[ "SFOUUIFSFBOZM
7/
φNN φNNY
Downloaded from www.Manualslib.com
4XJUDIHFBSPS$JSDVJUCSFBLFS
manuals search engine
4XJUDIHFBSPS$JSDVJUCSFBLFS 74 QIBTFXJSF
/PMPPTF
8IFO SFGSJHFSBOU QJQJOH FYDFFET N
BEEJUJPOBMMZ DIBSHF BO BNPVOU DBMDVMBUFE GSPN UIF QJQF MFOHUI BOE UIF BCPWF UBCMF GPS UIF QPSUJPO JO FYDFTT PG N
%P OPU GB
● 8IFO SFGSJHFSBOU QJQJOH JT TIPSUFS UIBO N
SFEVDF SFGSJHFSBOU CZ LH GSPN UIF GBDUPSZ DIBSHFE WPMVNF BOE BEKVTU UP LH
● *G BO FYJTUJOH QJQF TZTUFN JT VTFE
B SFRVJSFE SFGSJHFSBOU DIBSHF WPMVNF XJMM WBSZ EFQFOEJOH PO UIF MJRVJE QJQF TJ[F 'PS GVSUIFS JOGPSNBUJPO
TFFi 65*-*;"5*0/ 0' &9*45*/( 1*1*/(w
$IFDLJ
6TF DIFDL KPJO
'PSNVMBUPDBMDVMBUFUIFWPMVNFPGBEEJUJPOBMSFGSJHFSBOUSFRVJSFE JOTJEF UIF PVU
8IFO BO BEEJUJPOBM DIBSHF WPMVNF DBMDVMBUJPO SFTVMU JT OFHBUJWF
"TJOEJDBUFE
.PEFM∼7 "EEJUJPOBMDIBSHFWPMVNF LH
\.BJOQJQFMFOHUI N
o-FOHUIDPWFSFEXJUIPVUBEEJUJPOBMDIBSHF N
^Y LHN
5PUBMMFOHUIPGCSBODIQJQFT N
Y LHN
● 5P DIBSHF SFGSJHFSBOU BHBJO SFDPWFS SFGSJHFSBOU GSPN UIF TZTUFN mSTU BOE UIFO DIBSHF UIF WPMVNF DBMDVMBUFE GSPN UIF BCPWF UBCMF 4UBOEBSE SFGSJHFSBOU DIBSHF WPMVNF CSBODI QJQFT DIBSHF WPMVNF
4FUUJOH
%FGSPTU DP
・8IFO UI
$IBSHJOHSFGSJHFSBOU ・4FU UIJT
● 4JODF 3" SFGSJHFSBOU NVTU CF DIBSHFE JO UIF MJRVJE QIBTF
ZPV TIPVME DIBSHF JU
LFFQJOH UIF DPOUBJOFS DZMJOEFS VQTJEF EPXO PS VTJOH B SFGSJHFSBOU DZMJOEFS FRVJQQFE XJUI B TJQIPO UVCF UIF TFBT
● $IBSHF SFGSJHFSBOU BMXBZT GSPN UIF MJRVJE TJEF TFSWJDF QPSU XJUI UIF PQFSBUJPO WBMWF TIVU 8IFO ZPV mOE JU EJGmDVMU UP DIBSHF B SFRVJSFE BNPVOU
GVMMZ PQFO UIF PVUEPPS VOJU WBMWFT PO CPUI MJRVJE BOE HBT TJEFT BOE DIBSHF SFGSJHFSBOU GSPN UIF
4OPX HVB
HBT TVDUJPO
TJEF TFSWJDF QPSU
XIJMF SVOOJOH UIF VOJU JO UIF DPPMJOH NPEF *O EPJOH TP
DBSF NVTU CF UBLFO TP UIBU SFGSJHFSBOU NBZ CF EJTDIBSHFE GSPN UIF DZMJOEFS JO UIF MJRVJE QIBTF BMM UIF UJNF 8IFO UIF DZMJOEFS WBMWF JT UISPUUMFE EPXO ・8IFO UIJ
PS B EFEJDBUFE DPOWFSTJPO UPPM UP DIBOHF MJRVJEQIBTF SFGSJHFSBOU JOUP NJTU JT VTFE UP QSPUFDU UIF DPNQSFTTPS
IPXFWFS
BEKVTU DIBSHF DPOEJUJPOT TP UIBU SFGSJHFSBOU XJMM HBTJGZ VQPO FOUFSJOH UIF VOJU PVUEPPS U
● *O DIBSHJOH SFGSJHFSBOU
BMXBZT DIBSHF B DBMDVMBUFE WPMVNF CZ VTJOH B TDBMF UP NFBTVSF UIF DIBSHF WPMVNF ・8IFO UIF
● 8IFO SFGSJHFSBOU JT DIBSHFE XJUI UIF VOJU CFJOH SVO
DPNQMFUF B DIBSHF PQFSBUJPO XJUIJO NJOVUFT 3VOOJOH UIF VOJU XJUI BO JOTVGmDJFOU RVBOUJUZ PG SFGSJHFSBOU GPS B MPOH UJNF DBO DBVTF B DPNQSFTTPS GBJMVSF
/05& 1VU EPXO UIF SFGSJHFSBOU WPMVNF DBMDVMBUFE GSPN UIF QJQF MFOHUI POUP UIF DBVUJPO MBCFM BUUBDIFE PO UIF CBDL TJEF PG UIF TFSWJDF QBOFM
#BOE BDDFTTPSZ
1JQFDPWFS BDDFTTPSZ
'BJMVSF
)FBUJOHBOEDPOEFOTBUJPOQSFWFOUJPO &SSPSJOEJDBUFEPOU
SFNPUFDPOUSPMVO
%SFTTSFGSJHFSBOUQJQFT CPUIHBTBOEMJRVJEQJQFT
GPSIFBUJOTVMBUJPOBOEQSFWFOUJPOPGEFXDPOEFOTBUJPO
&
6TFBIFBUJOTVMBUJOHNBUFSJBMUIBUDBOXJUITUBOE℃PSBIJHIFSUFNQFSBUVSF1PPSIFBUJOTVMBUJOHDBQBDJUZDBODBVTFIFBUJOTVMBUJPOQSPCMFNTPSDBCMFEFUFSJPSBUJPO
*NQSPQFS IFBU JOTVMBUJPOBOUJEFX ESFTTJOH DBO SFTVMU JO B XBUFS MFBL PS ESJQQJOH DBVTJOH EBNBHF UP IPVTFIPME FGGFDUT
FUD &
"MM HBT QJQFT NVTU CF TFDVSFMZ IFBU JOTVMBUFE JO PSEFS UP QSFWFOU EBNBHF GSPN ESJQQJOH XBUFS UIBU DPNFT GSPN UIF DPOEFOTBUJPO GPSNFE PO UIFN EVSJOH B DPPMJOH PQFSBUJPO PS QFSTPOBM
JOKVSZ GSPN CVSOT CFDBVTF UIFJS TVSGBDF DBO SFBDI RVJUF B IJHI UFNQFSBUVSF EVF UP EJTDIBSHFE HBT nPXJOH JOTJEF EVSJOH B IFBUJOH PQFSBUJPO 8JSFTGPSDPOOFDUJOHJOEPPS &
&YUFSJPSUBQF
8SBQ JOEPPS VOJUT nBSF KPJOUT XJUI IFBU JOTVMBUJOH QBSUT QJQF DPWFS
GPS IFBU JOTVMBUJPO CPUI HBT BOE MJRVJE QJQFT
BOEPVUEPPSVOJUT
● *GBOFSSPS
(JWF IFBU JOTVMBUJPO UP CPUI HBT BOE MJRVJE TJEF QJQFT #VOEMF B IFBU JOTVMBUJOH NBUFSJBM BOE B QJQF UJHIUMZ UPHFUIFS TP UIBU OP HBQT NBZ CF MFGU CFUXFFO UIFN BOE XSBQ UIFN UPHFUIFS (BTQJQJOH
XJUI B DPOOFDUJOH DBCMF CZ B ESFTTJOH UBQF
"MUIPVHI JU JT WFSJmFE JO B UFTU UIBU UIJT BJS DPOEJUJPOJOH VOJU TIPXT TBUJTGBDUPSZ QFSGPSNBODF VOEFS +*4 DPOEFOTBUJPO UFTU DPOEJUJPOT
CPUI HBT BOE MJRVJE QJQFT OFFE UP CF ESFTTFE
-JRVJEQJQJOH
5IFTUB
XJUI NN PS UIJDLFS IFBU JOTVMBUJPO NBUFSJBMT BCPWF UIF DFJMJOH XIFSF SFMBUJWF IVNJEJUZ FYDFFET JOTVMBUJPO 5IF GPMMPXJO
%3"*/1*1*/(803, 7BMWFGPSBDPP
7BMWFGPSBIFB
● &YFDVUFESBJOQJQJOHCZVTJOHBESBJOFMCPXBOEESBJOHSPNNFUTTVQQMJFETFQBSBUFMZBT ○ 5IFSFBSFESBJOIPMFTQSPWJEFEPOUIFCPUUPNQMBUFPGBOPVUEPPSVOJUUPEJTDIBSHF
PQUJPOBMQBSUT
XIFSFXBUFSESBJOFEGSPNUIFPVUEPPSVOJUJTBQSPCMFN DPOEFOTFEXBUFS
)FFEUIF
○ 8IFODPOEFOTFEXBUFSOFFETUPCFMFEUPBESBJO
FUD
JOTUBMMUIFVOJUPOBnBUCBTF 5IJTPVUEPPSV
JOUIFDPNQSFT
TVQQMJFETFQBSBUFMZBTBOPQUJPOBMQBSU
PSDPODSFUFCMPDLT
%SBJOFMCPX QF
○ $POOFDUBESBJOFMCPXBTTIPXOJOUIFJMMVTUSBUJPOBOEDMPTFUIFPUIFSUXPESBJOIPMFT
%SBJOHSPNNFU XJUIHSPNNFUT
)BSEWJOZMDIMPSJEFQJQFGPSHFOFSBMQVSQPTF 71
QFT
65*-*;"
&-&$53*$"-8*3*/(803, 'PSEFUBJMTPGFMFDUSJDBMDBCMJOH
SFGFSUPUIFJOEPPSVOJUJOTUBMMBUJPONBOVBM $IFDLXIFUIFSBO
&MFDUSJDBMJOTUBMMBUJPOXPSLNVTUCFQFSGPSNFECZBOFMFDUSJDBMJOTUBMMBUJPOTFSWJDFQSPWJEFSRVBMJmFECZBQPXFSQSPWJEFSPGUIFDPVOUSZ ● $POOFDUBQBJSCFBSJOHBDPNNPOUFSNJOBMOVNCFSXJUIBOJOEPPSPVUEPPSDPOOFDUJOHXJSF
&MFDUSJDBMJOTUBMMBUJPOXPSLNVTUCFFYFDVUFEBDDPSEJOHUPUIFUFDIOJDBMTUBOEBSETBOEPUIFSSFHVMBUJPOTBQQMJDBCMFUPFMFDUSJDBM ● *ODBCMJOH
GBTUFODBCMFTTFDVSFMZXJUIDBCMFDMBNQTTPUIBUOPFYUFSOBMGPSDFNBZXPSLPOUFSNJOBMDPOOFDUJPOT
"SFBOPVUEPPSVO
JOTUBMMBUJPOTJOUIFDPVOUSZ ● (SPVOEJOHUFSNJOBMTBSFQSPWJEFEJOUIFDPOUSPMCPY FYJTUJOHQJQFTZTUF
%POPUVTFBOZTVQQMZDPSEMJHIUFSUIBOPOFTQFDJmFEJOQBSFOUIFTFTGPSFBDIUZQFCFMPX
●
CSBJEFEDPSE DPEFEFTJHOBUJPO*&$
PSEJOBSZUPVHISVCCFSTIFBUIFEDPSE DPEFEFTJHOBUJPO*&$
1PXFSTPVSDF
TJHOBMMJOFBOEHSPVOEUFSNJOBMCMPDL
"SFUIFF
nBUUXJOUJOTFMDPSE DPEFEFTJHOBUJPO*&$
%POPUVTFBOZUIJOHMJHIUFSUIBOQPMZDIMPSPQSFOFTIFBUIFEnFYJCMFDPSE DPEFEFTJHOBUJPO*&$
GPSTVQQMZDPSETPG (SPVOEJOHUFSNJOBM
QBSUTPGBQQMJBODFTGPSPVUEPPSVTF ○%POPUDPOOFDUUPUIFHSPVOEJOHXJSFGSPNBOPUIFSVOJU
CVUJOTUBMMBEFEJDBUFEXJSFVQUPUIF
(SPVOEUIFVOJU%POPUDPOOFDUUIFHSPVOEJOHXJSFUPBHBTQJQF
XBUFSQJQF
MJHIUOJOHSPEPSUFMFQIPOFHSPVOEJOHXJSF
●
HSPVOEJOHXJSFGSPNUIFEJTUSJCVUJPOCPBSE
*GJNQSPQFSZHSPVOEFE
BOFMFDUSJDTIPDLPSNBMGVODUJPONBZSFTVMU %PFTUIFFYJTUJOHQJ
"HSPVOEJOHXJSFNVTUCFDPOOFDUFECFGPSFDPOOFDUJOHUIFQPXFSDBCMF1SPWJEFBHSPVOEJOHXJSFMPOHFSUIBOUIFQPXFSDBCMF
●
8JSJOHDMBNQ
5IFQJQFMFOHUIJ
5IFQJQFTJ[FDP
5IFJOTUBMMBUJPOPGBOJNQVMTFXJUITUBOEJOHUZQFFBSUIMFBLBHFCSFBLFSJTOFDFTTBSZ"GBJMVSFUPJOTUBMMBOFBSUIMFBLBHFCSFBLFS
●
○'BTUFODBCMFTBOEQSPUFDUUIFUFSNJOBMDPOOFDUJPOGSPNFYUFSOBMGPSDF
5IFFMFWBUJPOEJG
DBOSFTVMUJOBOBDDDJEFOUTVDIBTBOFMFDUSJDTIPDLPSBmSF DPOGPSNTUPUIF
%POPUUVSOPOUIFQPXFSVOUJMUIFFMFDUSJDBMXPSLJTDPNQMFUFUFE
● 8IFSFUIFPVUE
8JSJOHEJBHSBN 8IFSFUIFPVUE
%POPUVTFBDPOEFOTJWFDBQBDJUPSGPSQPXFSGBDUPSJNQSPWFNFOUVOEFSBOZDJSDVNTUBODFT *UEPTFOPUJNQSPWFQPXFSGBDUPS
●
○*UJTBUUBDIFEPOUIFCBDLTJEFPGUIFTFSWJDFQBOFM
XIJMFJUDBODBVTFBOBCOPSNBMPWFSIFBUBDDJEFOU
'PSQPXFSTVQQMZDBCMFT
VTFDPOEVJUT
● .4DSFX
0VUHPJOHDBCMFEJSFDUJPO *TUIFVOJUUPJOTUB
%POPUMBZFMFDUSPOJDDPOUSPMDBCMFT SFNPUFDPOUSPMBOETJHOBMJOHXJSFT
BOEPUIFSDBCMFTUPHFUIFSPVUTJEFUIFVOJU-BZJOHUIFN
●
UXJOUSJQMFEPVCMF
UPHFUIFSDBOSFTVMUJOUIFNBMGVODUJPOJOHPSBGBJMVSFPGUIFVOJUEVFUPFMFDUSJDOPJTFT ○"TMJLFUIFSFGSJHFSBOUQJQF
JUDBOCFMFUPVUJOBOZPGUIFGPMMPXJOHEJSFDUJPOTTJEFSJHIU
GSPOU
'BTUFODBCMFTTPUIBUNBZOPUUPVDIUIFQJQJOH
FUD
● .PEFM SFBSBOEEPXOXBSE
8IFODBCMFTBSFDPOOFDUFE
NBLFTVSFUIBUBMMFMFDUSJDBMDPNQPOFOUTXJUIJOUIFFMFDUSJDBMDPNQPOFOUCPYBSFGSFFPGMPPTF
● 7∼7
*TUIFFYJTUJOHQJQFT
DPOOFDUPS DPVQMJOH PS UFSNJOBM DPOOFDUJPO BOE UIFO BUUBDI UIF DPWFS TFDVSFMZ *NQSPQFS DPWFS BUUBDINFOU DBO SFTVMU JO
NBMGVODUJPOJOHPSBGBJMVSFPGUIFVOJU
JGXBUFSQFOFUSBUFTJOUPUIFCPY
×
"MXBZTVTFBUISFFDPSFDBCMFGPSBOJOEPPSPVUEPPSDPOOFDUJOHDBCMF/FWFSVTFBTIJFMEDBCMF
●
○
*TUIFFYJTUJOHQJQF
$IFDLXIFUIFSSFG
-
UIFTZTUFNCFGPSF
XJUIUIFQPXFSDPSEVOQMVHHFE
"SFUIFSFBOZCSBO
7$5DBCUZSFDBCMF 77'nBUDBCMF DPSFDBCMF 4IJFMEDBCMF
"MXBZTVTFBOFBSUIMFBLBHFDJSDVJUCSFBLFSEFTJHOFEGPS
$"65*0/ JOWFSUFSDJSDVJUTUPQSFWFOUBGBVMUZPQFSBUJPO "SFIFBUJOTVMBUJPO
SFVTFGSFFPGQFFM
.PEFM 1PXFSTPVSDF 1PXFSDBCMFUIJDLOFTT NN
."9PWFSDVSSFOU "
$BCMFMFOHUI N
(SPVOEJOHXJSFUIJDLOFTT *OEPPSPVUEPPSXJSFUIJDLOFTT×OVNCFS )FBUJOTVMBUJPOJT
7/ 4JOHMFQIBTFXJSF
&BSUIMFBLBHFCSFBLFS &BSUIMFBLBHFCSFBLFS 7/ 7)[
)BSNPOJDSFTJTUBOUUZQF
)BSNPOJDSFTJTUBOUUZQF
7)[ "SFOUUIFSFBOZMP
7/
φNN φNNY /PMPPTFQ
4XJUDIHFBSPS$JSDVJUCSFBLFS 4XJUDIHFBSPS$JSDVJUCSFBLFS 74 QIBTFXJSF
74 7)[
- / - - - / 7)[ 5IFFYJTUJO
74
0VUEPPSVOJU 0VUEPPSVOJU
/ /
※"UUIFDPOOFDUJPOXJUIUIFEVDUUZQFJOEPPSVOJU
/ /
.PEFM 1PXFSTPVSDF 1PXFSDBCMFUIJDLOFTT NN
."9PWFSDVSSFOU "
$BCMFMFOHUI N
(SPVOEJOHXJSFUIJDLOFTT *OEPPSPVUEPPSXJSFUIJDLOFTT×OVNCFS 8"3/*/(
*OEPPSVOJU *OEPPSVOJU
9 : ; 9 : ; 7/ 4JOHMFQIBTFXJSF
7/ 7)[
9 : ; 9 : ; 7)[
3FNPUFDPOUSPMMFS 3FNPUFDPOUSPMMFS 7/
φNN φNNY
74 QIBTFXJSF
.PEFM7/_7/ .PEFM74_74
'10 • PAC-DB-142
74 7)[
7)[
74
●5IF TQFDJmDBUJPOT TIPXO JO UIF BCPWF UBCMF BSF GPS VOJUT XJUIPVU IFBUFST 'PS VOJUT XJUI IFBUFST
SFGFS UP UIF JOTUBMMBUJPO JOTUSVDUJPOT PS UIF DPOTUSVDUJPO
JOTUSVDUJPOTPGUIFJOEPPSVOJU
●4XJUDIHFBSPS$JSDVJUCSFBLFSDBQBDJUZXIJDIJTDBMDVMBUFEGSPN."9PWFSDVSSFOUTIPVMECFDIPTFOBMPOHUIFSFHVMBUJPOTJOFBDIDPVOUSZ
●5IFDBCMFTQFDJmDBUJPOTBSFCBTFEPOUIFBTTVNQUJPOUIBUBNFUBMPSQMBTUJDDPOEVJUJTVTFEXJUIOPNPSFUIBOUISFFDBCMFTDPOUBJOFEJOBDPOEVJUBOEBWPMUBHF
ESPQJT'PSBOJOTUBMMBUJPOGBMMJOHPVUTJEFPGUIFTFDPOEJUJPOT
GPMMPXUIFJOUFSOBMDBCMJOHSFHVMBUJPOT"EBQUJUUPUIFSFHVMBUJPOJOFGGFDUJOFBDIDPVOUSZ
5FTU SVO NFUIPE "SFQSPQFSMZSBUFEFMFDUSJDBMFRVJQNFOUTVTFEGPSDJSDVJUCSFBLFSTBOEDBCMFT
%PFTOUDBCMJOHDSPTTDPOOFDUCFUXFFOVOJUT
XIFSFNPSFUIBOPOFVOJUBSFJOTUBMMFE
" UFTU SVO DBO CF JOJUJBUFE GSPN BO PVUEPPS VOJU CZ VTJOH 48 BOE 48 48 "SFOUJOEPPSPVUEPPSTJHOBMXJSFTDPOOFDUFEUPSFNPUFDPOUSPMXJSFT
48 GPS POTJUF TFUUJOH 0'' &MFDUSJD %PJOEPPSPVUEPPSDPOOFDUJOHDBCMFTDPOOFDUCFUXFFOUIFTBNFUFSNJOBMOVNCFST
$PPMJOH EVSJOH B UFTU SVO
4XJUDIJOH 48 UP 0/ XJMM TUBSU UIF DPNQSFTTPS 0/ XJSJOH "SFFJUIFS7$5DBCUZSFDBCMFTPS8'GMBUDBCMFTVTFEGPSJOEPPSPVUEPPSDPOOFDUJOHDBCMFT
5IF VOJU XJMM TUBSU B DPPMJOH PQFSBUJPO
XIFO 48 JT 0''
PS B IFBUJOH 0/ )FBUJOH EVSJOH B UFTU SVO
%PFTHSPVOEJOHTBUJTGZUIF%UZQFHSPVOEJOH UZQF***HSPVOEJOH
SFRVJSFNFOUT
PQFSBUJPO
XIFO 48 JT 0/ 0'' /PSNBM PS"GUFS UIF UFTU PQFSBUJPO
*TUIFVOJUHSPVOEFEXJUIBEFEJDBUFEHSPVOEJOHXJSFOPUDPOOFDUFEUPBOPUIFSVOJUTHSPVOEJOHXJSF
%P OPU GBJM UP TXJUDI 48 UP 0'' XIFO B UFTU SVO JT DPNQMFUFE
"SFDBCMFTGSFFPGMPPTFTDSFXTBUUIFJSDPOOFDUJPOQPJOUT
$IFDLJOH UIF TUBUF PG UIF VOJU JO PQFSBUJPO $IFDLKPJOUPGUIFQJQF
$IBSHFQPSUPGUIF
HBTPQFSBUJPOWBMWF
"SFDBCMFTIFMEEPXOXJUIDBCMFDMBNQTTPUIBUOPFYUFSOBMGPSDFXPSLTPOUPUFSNJOBMDPOOFDUJPOT
*TJOEPPSVOJUJOTUBMMBUJPOXPSLDPNQMFUFE
6TF DIFDL KPJOUT QSPWJEFE PO UIF QJQJOH CFGPSF BOE BGUFS UIF GPVSXBZ WBMWF JOTUBMMFE ー *OEPPS VOJU
$PPMJOH %JTDIBSHFQSFTTVSF 4VDUJPOQSFTTVSF 8IFSFBGBDFDPWFSTIPVMECFBUUBDIFEPOUPBOJOEPPSVOJU
JTUIFGBDFDPWFSBUUBDIFEUPUIFJOEPPSVOJU
JOTJEF UIF PVUEPPS VOJU GPS DIFDLJOH EJTDIBSHF QSFTTVSF BOE TVDUJPO QSFTTVSF PQFSBUJPO )JHIQSFTTVSF
-PXQSFTTVSF
FHBUJWF
"TJOEJDBUFEJOUIFUBCMFTIPXOPOUIFSJHIU
QSFTTVSFEFUFDUFEBUFBDIQPJOUXJMM )FBUJOH 4VDUJPOQSFTTVSF %JTDIBSHFQSFTTVSF 5FTU SVO QSPDFEVSF ● "MXBZTDBSSZPVUBUFTUSVOBOEDIFDLUIFGPMMPXJOHJOPSEFSBTMJTUFE
WBSZEFQFOEJOHPOXIFUIFSBDPPMJOHPSIFBUJOHPQFSBUJPOIBTCFFOTFMFDUFE PQFSBUJPO -PXQSFTTVSF
)JHIQSFTTVSF
① 0QFOUIFHBTTJEFPQFSBUJPOWBMWFGVMMZ
%FGSPTU DPOUSPM TXJUDIJOH 48
② 0QFOUIFMJRVJETJEFPQFSBUJPOWBMWFGVMMZ
・8IFO UIJT TXJUDI JT UVSOFE 0/
UIF VOJU XJMM SVO JO UIF EFGSPTU NPEF NPSF GSFRVFOUMZ ③ $MPTFUIFQBOFM
・4FU UIJT TXJUDI UP 0/
XIFO JOTUBMMFE JO B SFHJPO XIFSF PVUEPPS UFNQFSBUVSF GBMMT CFMPX [FSP EVSJOH ④ 8IFSFBSFNPUFDPOUSPMVOJUJTVTFEGPSVOJUTFUVQPOUIFJOTUBMMBUJPOTJUF
GPMMPXJOTUSVDUJPOTGPSVOJUTFUVQPOUIFJOTUBMMBUJPOTJUFXJUIBSFNPUFDPOUSPMVOJU
UIF TFBTPO UIF VOJU JT SVO GPS B IFBUJOH PQFSBUJPO 480/480''UIFVOJUXJMMTUBSUBDPPMJOHPQFSBUJPO
⑤
FGSJHFSBOU GSPN UIF
4OPX HVBSE GBO DPOUSPM 48
480/480/UIFVOJUXJMMTUBSUBIFBUJOHPQFSBUJPO
JT UISPUUMFE EPXO ・8IFO UIJT TXJUDI JT UVSOFE PO
UIF PVUEPPS VOJU GBO XJMM SVO GPS TFDPOET JO FWFSZ NJOVUFT
XIFO ⑥ 8IFOUIFVOJUTUBSUTPQFSBUJPO
QSFTTUIFXJOEEJSFDUJPOCVUUPOQSPWJEFEPOUIFSFNPUFDPOUSPMVOJUUPDIFDLJUTPQFSBUJPO
PVUEPPS UFNQFSBUVSF GBMMT UP ℃ PS MPXFS BOE UIF DPNQSFTTPS JT OPU SVOOJOH ⑦ 1MBDFZPVSIBOECFGPSFUIFJOEPPSVOJUTEJGGVTFSUPDIFDLXIFUIFSDPME XBSN
XJOETDPNFPVUJOBDPPMJOH IFBUJOH
PQFSBUJPO
・8IFO UIF VOJU JT VTFE JO B WFSZ TOPXZ DPVOUSZ
TFU UIJT TXJUDI UP 0/ ⑧ .BLFTVSFUIBUBSFE-&%JTOPUCMJOLJOH
⑨ 8IFOZPVDPNQMFUFUIFUFTUSVO
EPOPUGPSHFUUPUVSO48UPUIF0''QPTJUJPO
⑩
DPWFS BDDFTTPSZ
'BJMVSF EJBHOPTJT JO B UFTU SVO 8IFSFPQUJPOTBSFVTFE
DIFDLUIFJSPQFSBUJPOBDDPSEJOHUPUIFSFTQFDUJWFJOTUSVDUJPONBOVBMT
JOTVMBUJPO 5IF GPMMPXJOH UBCMF JMMVTUSBUFT UIF TUFBEZ TUBUFT PG UIF FMFDUSPOJD FYQBOTJPO WBMWF
'10 • PAC-DB-142
OJUUPEJTDIBSHF
)FFEUIFGPMMPXJOHPOUIFmSTUPQFSBUJPOBGUFSUVSOJOHPOUIFDJSDVJUCSFBLFS
UPOBnBUCBTF 5IJTPVUEPPSVOJUNBZTUBSUJOUIFTUBOECZNPEF XBJUJOHGPSBDPNQSFTTPSTUBSUVQ
XIJDIDBODPOUJOVFVQUPNJOVUFT
UPQSFWFOUUIFPJMMFWFM
JOUIFDPNQSFTTPSGSPNMPXFSJOHPOUIFmSTUPQFSBUJPOBGUFSUVSOJOHPOUIFDJSDVJUCSFBLFS*GUIBUJTUIFDBTF
EPOPUTVTQFDUBVOJUGBJMVSF
UXPESBJOIPMFT
65*-*;"5*0/0'&9*45*/(1*1*/(
$IFDLXIFUIFSBOFYJTUJOHQJQFTZTUFNJTSFVTBCMFPSOPUCZVTJOHUIFGPMMPXJOHnPXDIBSU
$IFDLJOH UIF TUBUF PG UIF VOJU JO PQFSBUJPO $IFDLKPJOUPGUIFQJQF
$IBSHFQPSUPGUIF
HBTPQFSBUJPOWBMWF
"SFDBCMFTIFMEEPXOXJUIDBCMFDMBNQTTPUIBUOPFYUFSOBMGPSDFXPSLTPOUPUFSNJOBMDPOOFDUJPOT
*TJOEPPSVOJUJOTUBMMBUJPOXPSLDPNQMFUFE
6TF DIFDL KPJOUT QSPWJEFE PO UIF QJQJOH CFGPSF BOE BGUFS UIF GPVSXBZ WBMWF JOTUBMMFE ー *OEPPS VOJU
$PPMJOH %JTDIBSHFQSFTTVSF 4VDUJPOQSFTTVSF 8IFSFBGBDFDPWFSTIPVMECFBUUBDIFEPOUPBOJOEPPSVOJU
JTUIFGBDFDPWFSBUUBDIFEUPUIFJOEPPSVOJU
JOTJEF UIF PVUEPPS VOJU GPS DIFDLJOH EJTDIBSHF QSFTTVSF BOE TVDUJPO QSFTTVSF PQFSBUJPO )JHIQSFTTVSF
-PXQSFTTVSF
UJWF
"TJOEJDBUFEJOUIFUBCMFTIPXOPOUIFSJHIU
QSFTTVSFEFUFDUFEBUFBDIQPJOUXJMM )FBUJOH 4VDUJPOQSFTTVSF %JTDIBSHFQSFTTVSF 5FTU SVO QSPDFEVSF ● "MXBZTDBSSZPVUBUFTUSVOBOEDIFDLUIFGPMMPXJOHJOPSEFSBTMJTUFE
WBSZEFQFOEJOHPOXIFUIFSBDPPMJOHPSIFBUJOHPQFSBUJPOIBTCFFOTFMFDUFE PQFSBUJPO -PXQSFTTVSF
)JHIQSFTTVSF
'BJMVSF EJBHOPTJT JO B UFTU SVO 8IFSFPQUJPOTBSFVTFE
DIFDLUIFJSPQFSBUJPOBDDPSEJOHUPUIFSFTQFDUJWFJOTUSVDUJPONBOVBMT
JOTVMBUJPO 5IF GPMMPXJOH UBCMF JMMVTUSBUFT UIF TUFBEZ TUBUFT PG UIF FMFDUSPOJD FYQBOTJPO WBMWF
PEJTDIBSHF
)FFEUIFGPMMPXJOHPOUIFmSTUPQFSBUJPOBGUFSUVSOJOHPOUIFDJSDVJUCSFBLFS
OBnBUCBTF 5IJTPVUEPPSVOJUNBZTUBSUJOUIFTUBOECZNPEF XBJUJOHGPSBDPNQSFTTPSTUBSUVQ
XIJDIDBODPOUJOVFVQUPNJOVUFT
UPQSFWFOUUIFPJMMFWFM
JOUIFDPNQSFTTPSGSPNMPXFSJOHPOUIFmSTUPQFSBUJPOBGUFSUVSOJOHPOUIFDJSDVJUCSFBLFS*GUIBUJTUIFDBTF
EPOPUTVTQFDUBVOJUGBJMVSF
ESBJOIPMFT
65*-*;"5*0/0'&9*45*/(1*1*/(
$IFDLXIFUIFSBOFYJTUJOHQJQFTZTUFNJTSFVTBCMFPSOPUCZVTJOHUIFGPMMPXJOHnPXDIBSU
/PMPPTFQJQFTVQQPSUT 4PNFMPPTFQJQFTVQQPSUT 3FQBJS 5IF NPEFM UZQFT PG FYJTUJOH VOJUT PG XIJDI CSBODIJOH QJQFT BSF SFVTBCMF
.PEFMT MBUFS UIBO5ZQF
5IFFYJTUJOHQJQFTZTUFNJTOPUSFVTBCMF ● ' % $ * * * □ □ □
5IFFYJTUJOHQJQFTZTUFNJTSFVTBCMF
*OTUBMMBOFXQJQFTZTUFN ● ' % $ 1 * * * □ □ □
5IF CSBODIJOH QJQFT VTFE XJUI NPEFMT PUIFS UIBO UIPTF MJTUFE BCPWF BSF OPU SFVTBCMF CFDBVTF PG UIFJS JOTVGGJDJFOU
OVNCFS 8"3/*/( 8IFSF UIF FYJTUJOH VOJU DBO CF SVO GPS B DPPMJOH PQFSBUJPO QSFTTVSF SFTJTUBODF 1MFBTF VTF PVS HFOVJOF CSBODIJOH QJQFT GPS 3"
●* * * BSF OVNCFST SFQSFTFOUJOH IPSTFQPXFS □ □ □ JT BO BMQIBOVNFSJD MFUUFS
$BSSZ PVU UIF GPMMPXJOH TUFQT XJUI UIF FYDJTJOH VOJU JO UIF PSEFS PG
BOE
3VO UIF VOJU GPS NJOVUFT GPS B DPPMJOH PQFSBUJPO 'PSNVMB UP DBMDVMBUF BEEJUJPOBM DIBSHF WPMVNF
4UPQ UIF JOEPPS GBO BOE SVO UIF VOJU GPS NJOVUFT GPS B DPPMJOH PQFSBUJPO SFUVSOJOH MJRVJE
"EEJUJPOBM DIBSHF WPMVNF LH
\.BJO QJQF MFOHUI N
o -FOHUI DPWFSFE XJUIPVU BEEJUJPOBM DIBSHF TIPXO JO UIF UBCMF N
^ ×
$MPTF UIF MJRVJE TJEF PQFSBUJPO WBMWF PG UIF PVUEPPS VOJU BOE QVNQ EPXO SFGSJHFSBOU SFDPWFSZ
"EEJUJPOBM DIBSHF WPMVNF QFS NFUFS PG QJQF TIPXO JO UIF UBCMF LHN
+
#MPX XJUI OJUSPHFO HBT ※ *G EJTDPMPSFE SFGSJHFSBUJPO PJM PS BOZ GPSFJHO NBUUFST JT EJTDIBSHFE CZ
'10 • PAC-DB-142
5PUBM MFOHUI PG CSBODI QJQFT N
×"EEJUJPOBM DIBSHF WPMVNF QFS NFUFS PG QJQF TIPXO JO UIF UBCMF LHN
UIF CMPX
XBTI UIF QJQF TZTUFN PS JOTUBMM B OFX QJQF TZTUFN
● 'PS UIF GMBSF OVU
EP OPU VTF UIF PME POF
CVU VTF UIF POF TVQQMJFE XJUI UIF PVUEPPS VOJU ※ *G ZPV PCUBJO B OFHBUJWF GJHVSF BT B SFTVMU PG DBMDVMBUJPO
OP BEEJUJPOBM SFGSJHFSBOU OFFET UP CF DIBSHFE
1SPDFTT B GMBSF UP UIF EJNFOTJPOT TQFDJGJFE GPS 3" &YBNQMF
8IFO BO 7 TJOHMF JOTUBMMBUJPO
JT JOTUBMMFE JO B N MPOH FYJTUJOH QJQF TZTUFN MJRVJE φ
HBT φ
DPOTUSVDUJPO
● 5VSO POTJUF TFUUJOH TXJUDI 48 UP UIF 0/ QPTJUJPO 8IFSF UIF HBT QJQF TJ[F JT φ
UIF RVBOUJUZ PG SFGSJHFSBOU UP DIBSHF BEEJUJPOBMMZ TIPVME CF NN
Y LHN LH
OEBWPMUBHF 8IFSF UIF FYJTUJOH VOJU DBOOPU CF SVO GPS B DPPMJOH PQFSBUJPO
VOUSZ 8BTI UIF QJQF TZTUFN PS JOTUBMM B OFX QJQF TZTUFN
● *G ZPV DIPPTF UP XBTI UIF QJQF TZTUFN
DPOUBDU PVS EJTUSJCVUPS JO UIF BSFB
4FMFDUJPO
14#%-K
PSB012D923L
#F TVSF UP TFMFD
(4) Models FDC200, 250VS 〇" QMBDF XIFS
*/45"--"5*0/."/6"-'03065%0036/*5
*OWFSUFSESJWFOTJOHMFTQMJU1"$ 〇" QMBDF XIFS
〇" QMBDF XIFS
7 r 7 〇" QMBDF XIFS
〇" QMBDF XIFS
%FTJHOFEGPS3"SFGSJHFSBOU 〇" QMBDF XIFS
◎5IJT JOTUBMMBUJPO NBOVBM EFBMT XJUI PVUEPPS VOJUT BOE HFOFSBM JOTUBMMBUJPO TQFDJmDBUJPOT POMZ 'PS JOEPPS VOJUT
SFGFS UP UIF SFTQFDUJWF 〇" QMBDF XIFS
JOTUBMMBUJPO NBOVBMT TVQQMJFE XJUI UIF VOJUT 〇" QMBDF XIFSF
〇" QMBDF XIFSF
◎8IFO JOTUBMM UIF VOJU
CF TVSF UP DIFDL XIFUIFS UIF TFMFDUJPO PG JOTUBMMBUJPO QMBDF
QPXFS TVQQMZ TQFDJmDBUJPOT
VTBHF MJNJUBUJPO $IFDLCFGPSFJOTUBMMBUJPOXPSL 〇" QMBDF XIFSF
QJQJOH MFOHUI
IFJHIU EJGGFSFODFT CFUXFFO JOEPPS BOE PVUEPPS VOJUT
QPXFS TVQQMZ WPMUBHF BOE FUD
BOE JOTUBMMBUJPO TQBDFT 〇" QMBDF XIFS
<"DDFTTPSZ> VOJU
XJMM OPU
〇" QMBDF XIFS
4"'&5: 13&$"65*0/4 &EHJOH "DDFTTPSZQJQF
● 8F SFDPNNFOE ZPV UP SFBE UIJTi4"'&5: 13&$"65*0/4w DBSFGVMMZ CFGPSF UIF JOTUBMMBUJPO XPSL JO PSEFS UP HBJO GVMM BEWBOUBHF PG UIF GVODUJPOT PG UIF VOJU BOE UP
QJFDF QJFDF QJFDF
0%
$BVUJPO B
BWPJE NBMGVODUJPO EVF UP NJTIBOEMJOH
*G UIF VOJU JT
*% 5IF CPUUPN Q
*%
● 5IF QSFDBVUJPOT EFTDSJCFE CFMPX BSF EJWJEFE JOUP 8"3/*/(
BOE $"65*0/
5IF NBUUFST XJUI QPTTJCJMJUJFT MFBEJOH UP TFSJPVT DPOTFRVFODFT TVDI BT LOPDLPVUIPMF
QSPUFDUJPO "DDFTTPSZQJQF" "DDFTTPSZQJQF# *OTUBMM UIF V
EFBUI PS TFSJPVT QFSTPOBM JOKVSZ EVF UP FSSPOFPVT IBOEMJOH BSF MJTUFE JO UIF 8"3/*/(
BOE UIF NBUUFST XJUI QPTTJCJMJUJFT MFBEJOH UP QFSTPOBM JOKVSZ PS UIBU UIF CPU
EBNBHF PG UIF VOJU EVF UP FSSPOFPVT IBOEMJOH JODMVEJOH QSPCBCJMJUZ MFBEJOH UP TFSJPVT DPOTFRVFODFT JO TPNF DBTFT BSF MJTUFE JO $"65*0/ 5IFTF BSF ● .PEFMOBNFBOEQPXFSTPVSDF TOPX DPWFS
WFSZ JNQPSUBOU QSFDBVUJPOT GPS TBGFUZ #F TVSF UP PCTFSWF BMM PG UIFN XJUIPVU GBJM ● 3FGSJHFSBOUQJQJOHMFOHUI
● 5IF NFBOJOH PG .BSLT VTFE IFSF BSF BT TIPXO CFMPX ● 1JQJOH
XJSJOHBOENJTDFMMBOFPVTTNBMMQBSUT
● *OEPPSVOJUJOTUBMMBUJPONBOVBM
/FWFS EP JU VOEFS BOZ DJSDVNTUBODF "MXBZT EP JU BDDPSEJOH UP UIF JOTUSVDUJPO
● 'PS UIJT PVUEPPS VOJU
&/ JT OPU BQQMJDBCMF JG DPOTFOU CZ UIF VUJMJUZ DPNQBOZ PS OPSUJmDBUJPO UP UIF VUJMJUZ DPNQBOZ JT HJWFO CFGPSF VTBHF
● #F TVSF UP DPOmSN OP BOPNBMZ PO UIF FRVJQNFOU CZ DPNNJTTJPOJOH BGUFS DPNQMFUFE JOTUBMMBUJPO BOE FYQMBJO UIF PQFSBUJOH NFUIPET BT XFMM BT UIF NBJOUFOBODF
NFUIPET PG UIJT FRVJQNFOU UP UIF VTFS BDDPSEJOH UP UIF PXOFShT NBOVBM
● ,FFQ UIF JOTUBMMBUJPO NBOVBM UPHFUIFS XJUI PXOFShT NBOVBM BU B QMBDF XIFSF BOZ VTFS DBO SFBE BU BOZ UJNF .PSFPWFS JG OFDFTTBSZ
BTL UP IBOE UIFN UP B OFX VTFS 4JODFESBJOXB
● %POUFYFDV
-
● 3FDPNNFOE
8"3/*/(
*G UIF VOJU DB
229 -
4USPOH XJOE
PG UIF VOJU EV
● *OTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEJOTUBMMFS ● %POPUQFSGPSNCSB[JOHXPSLJOUIFBJSUJHIUSPPN
*GZPVJOTUBMMUIFTZTUFNCZZPVSTFMG
JUNBZDBVTFTFSJPVTUSPVCMFTVDIBTXBUFSMFBLT
FMFDUSJDTIPDLT
mSFBOEQFSTPOBMJOKVSZ
BTBSFTVMUPGBTZTUFN *UDBODBVTFMBDLPGPYZHFO *OTUBMM UIF P
NBMGVODUJPO VOJU UP GBDF
● 6TFUIFQSFTDSJCFEQJQFT
nBSFOVUTBOEUPPMTGPS3"
QSPWJEF B G
● *OTUBMMUIFTZTUFNJOGVMMBDDPSEBODFXJUIUIFJOTUSVDUJPONBOVBM 6TJOHFYJTUJOHQBSUT GPS3PS3$
DBODBVTFUIFVOJUGBJMVSFBOETFSJPVTBDDJEFOUTEVFUPCVSTUPGUIFSFGSJHFSBOUDJSDVJU
*ODPSSFDUJOTUBMMBUJPONBZDBVTFCVSTUT
QFSTPOBMJOKVSZ
XBUFSMFBLT
FMFDUSJDTIPDLTBOEmSF TDSFFO
● 5JHIUFO UIF nBSF OVU CZ VTJOH EPVCMF TQBOOFST BOE UPSRVF XSFODI BDDPSEJOH UP QSFTDSJCFE NFUIPE #F TVSF OPU UP
● 6TFUIFPSJHJOBMBDDFTTPSJFTBOEUIFTQFDJmFEDPNQPOFOUTGPSJOTUBMMBUJPO UJHIUFOUIFnBSFOVUUPPNVDI
*G QBSUT PUIFS UIBO UIPTF QSFTDSJCFE CZ VT BSF VTFE
*U NBZ DBVTF GBMM PG UIF VOJU
XBUFS MFBLT
FMFDUSJD TIPDLT
mSF
SFGSJHFSBOU MFBL
TVCTUBOEBSE -PPTFnBSFDPOOFDUJPOPSEBNBHFPOUIFnBSFQBSUCZUJHIUFOJOHXJUIFYDFTTUPSRVFDBODBVTFCVSTUPSSFGSJHFSBOUMFBLTXIJDI
QFSGPSNBODF
DPOUSPMGBJMVSFBOEQFSTPOBMJOKVSZ NBZSFTVMUJOMBDLPGPYZHFO
● 8IFO JOTUBMMJOH JO TNBMM SPPNT
UBLF QSFWFOUJPO NFBTVSFT OPU UP FYDFFE UIF EFOTJUZ MJNJU PG SFGSJHFSBOU JO UIF FWFOU PG MFBLBHF ● %POPUPQFOUIFTFSWJDFWBMWFTGPSMJRVJEMJOFBOEHBTMJOFVOUJMDPNQMFUFESFGSJHFSBOUQJQJOHXPSL
BJSUJHIUOFTTUFTU
BDDPSEBODFXJUI*40 BOEFWBDVBUJPO 0WFS
$POTVMUUIFFYQFSUBCPVUQSFWFOUJPONFBTVSFT*GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJUJOUIFFWFOUPGMFBLBHF
MBDLPGPYZHFODBOPDDVS
XIJDI *GUIFDPNQSFTTPSJTPQFSBUFEJOTUBUFPGPQFOJOH TFSWJDFWBMWFTCFGPSFDPNQMFUFEDPOOFDUJPOPGSFGSJHFSBOU QJQJOH XPSL
ZPV
DBODBVTFTFSJPVTBDDJEFOUT NBZJODVSGSPTUCJUFPSJOKVSZGSPNBOBCSVQUSFGSJHFSBOUPVUnPXBOEBJSDBOCFTVDLFEJOUPSFGSJHFSBOUDJSDVJU
XIJDIDBODBVTF
● 7FOUJMBUFUIFXPSLJOHBSFBXFMMJOUIFFWFOUPGSFGSJHFSBOUMFBLBHFEVSJOHJOTUBMMBUJPO CVSTUPSQFSTPOBMJOKVSZEVFUPBOPNBMPVTMZIJHIQSFTTVSFJOUIFSFGSJHFSBOU
3&'3*(&
*GUIFSFGSJHFSBOUDPNFTJOUPDPOUBDUXJUIOBLFEnBNFT
QPJTPOPVTHBTJTQSPEVDFE ● 0OMZVTFQSFTDSJCFEPQUJPOBMQBSUT5IFJOTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEJOTUBMMFS
● "GUFSDPNQMFUFEJOTUBMMBUJPO
DIFDLUIBUOPSFGSJHFSBOUMFBLTGSPNUIFTZTUFN *GZPVJOTUBMMUIFTZTUFNCZZPVSTFMG
JUDBODBVTFTFSJPVTUSPVCMFTVDIBTXBUFSMFBLT
FMFDUSJDTIPDLT
mSF
*GSFGSJHFSBOUMFBLTJOUPUIFSPPNBOEDPNFTJOUPDPOUBDUXJUIBOPWFOPSPUIFSIPUTVSGBDF
QPJTPOPVTHBTJTQSPEVDFE ● %POPUQFSGPSNBOZDIBOHFPGQSPUFDUJWFEFWJDFJUTFMGPSJUTTFUVQDPOEJUJPO
● )BOHVQUIFVOJUBUUIFTQFDJmFEQPJOUTXJUISPQFTXIJDIDBOTVQQPSUUIFXFJHIUJOMJGUJOHGPSQPSUBHF"OEUPBWPJEKPMUJOHPVUPGBMJHONFOU
5IF GPSDFE PQFSBUJPO CZ TIPSUDJSDVJUJOH QSPUFDUJWF EFWJDF PG QSFTTVSF TXJUDI BOE UFNQFSBUVSF DPOUSPMMFS PS UIF VTF PG OPO
TQFDJmFEDPNQPOFOUDBODBVTFmSFPSCVSTU
CFTVSFUPIBOHVQUIFVOJUBUQPJOUTVQQPSU
"OJNQSPQFSNBOOFSPGQPSUBHFTVDIBTQPJOUTVQQPSUDBODBVTFEFBUIPSTFSJPVTQFSTPOBMJOKVSZEVFUPGBMMJOHPGUIFVOJU ● #FTVSFUPTXJUDIPGGUIFQPXFSTVQQMZJOUIFFWFOUPGJOTUBMMBUJPO
JOTQFDUJPOPSTFSWJDJOH
3FTUSJDUJP
● *OTUBMMUIFVOJUJOBMPDBUJPOXJUIHPPETVQQPSU *GUIFQPXFSTVQQMZJTOPUTIVUPGG
UIFSFJTBSJTLPGFMFDUSJDTIPDLT
VOJUGBJMVSFPSQFSTPOBMJOKVSZEVFUPUIFVOFYQFDUFETUBSUPGGBO ● $IFDL UIF GPMMP
6OTVJUBCMFJOTUBMMBUJPOMPDBUJPOTDBODBVTFUIFVOJUUPGBMMBOEDBVTFNBUFSJBMEBNBHFBOEQFSTPOBMJOKVSZ ● $POTVMUUIFEFBMFSPSBOFYQFSUSFHBSEJOHSFNPWBMPGUIFVOJU ● 0CTFSWF UIF GPM
● &OTVSFUIFVOJUJTTUBCMFXIFOJOTUBMMFE
TPUIBUJUDBOXJUITUBOEFBSUIRVBLFTBOETUSPOHXJOET *ODPSSFDUJOTUBMMBUJPODBODBVTFXBUFSMFBLT
FMFDUSJDTIPDLTPSmSF
6OTVJUBCMFJOTUBMMBUJPOMPDBUJPOTDBODBVTFUIFVOJUUPGBMMBOEDBVTFNBUFSJBMEBNBHFBOEQFSTPOBMJOKVSZ ● 4UPQUIFDPNQSFTTPSCFGPSFDMPTJOHWBMWFBOEEJTDPOOFDUJOHSFGSJHFSBOUQJQFTJODBTFPGQVNQEPXOPQFSBUJPO
'10 • PAC-DB-142
● 5IFFMFDUSJDBMJOTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEFMFDUSJDJBOJOBDDPSEBODFXJUIiUIFOPSNGPSFMFDUSJDBMXPSLwBOEiOBUJPOBM *G EJTDPOOFDUJOH SFGSJHFSBOU QJQFT JO TUBUF PG PQFOJOH TFSWJDF WBMWFT CFGPSF DPNQSFTTPS TUPQQJOH
ZPV NBZ JODVS GSPTU CJUF PS 3FTUSJDUJ
$"65*0/ 0OFXBZQJQFMFOHUIEJGGFS
● $BSSZPVUUIFFMFDUSJDBMXPSLGPSHSPVOEMFBEXJUIDBSF ● %POPUVTFUIFCBTFnBNFGPSPVUEPPSVOJUXIJDIJTDPSSPEFEPSEBNBHFEEVFUPMPOHQFSJPETPGPQFSBUJPO CSBODIJOHQPJOUUPUIFJOEP
%POPUDPOOFDUUIFHSPVOEMFBEUPUIFHBTMJOF
XBUFSMJOF
MJHIUOJOHDPOEVDUPSPSUFMFQIPOFMJOFhTHSPVOEMFBE*ODPSSFDUHSPVOEJOHDBODBVTFVOJUGBVMUTTVDIBT 6TJOHBOPMEBOEEBNBHFCBTFnBNFDBODBVTFUIFVOJUGBMMJOHEPXOBOEDBVTFQFSTPOBMJOKVSZ
FMFDUSJDTIPDLTEVFUPTIPSUDJSDVJUJOH/FWFSDPOOFDUUIFHSPVOEJOHXJSFUPBHBTQJQFCFDBVTFJGHBTMFBLT
JUDPVMEDBVTFFYQMPTJPOPSJHOJUJPO ● %POPUJOTUBMMUIFVOJUJOUIFMPDBUJPOTMJTUFECFMPX
● 6TFUIFDJSDVJUCSFBLFSGPSBMMQPMFXJUIDPSSFDUDBQBDJUZ ・-PDBUJPOTXIFSFDBSCPOmCFS
NFUBMQPXEFSPSBOZQPXEFSJTnPBUJOH 0OFXBZQJQFMFOHUIEJGGFS
TFDPOECSBODIJOHQPJOUUP
6TJOHUIFJODPSSFDUDJSDVJUCSFBLFS
JUDBODBVTFUIFVOJUNBMGVODUJPOBOEmSF ・-PDBUJPOTXIFSFBOZTVCTUBODFTUIBUDBOBGGFDUUIFVOJUTVDIBTTVMQIJEFHBT
DIMPSJEFHBT
BDJEBOEBMLBMJOFDBOPDDVS
5PUBMQJQFMFOHUIBGUFSUIFT
● *OTUBMMJTPMBUPSPSEJTDPOOFDUTXJUDIPOUIFQPXFSTVQQMZXJSJOHJOBDDPSEBODFXJUIUIFMPDBMDPEFTBOESFHVMBUJPOT ・7FIJDMFTBOETIJQT
5IFJTPMBUPSTIPVMECFMPDLFEJOBDDPSEBODFEXJUI&/ ・-PDBUJPOTXIFSFDPTNFUJDPSTQFDJBMTQSBZTBSFPGUFOVTFE &MFWBUJPOEJGGFSFODFCFUXF
VOJUT
● 5BLFDBSFXIFODBSSZJOHUIFVOJUCZIBOE ・-PDBUJPOTXJUIEJSFDUFYQPTVSFPGPJMNJTUBOETUFBNTVDIBTLJUDIFOBOENBDIJOFQMBOU
・-PDBUJPOTXIFSFBOZNBDIJOFTXIJDIHFOFSBUFIJHIGSFRVFODZIBSNPOJDTBSFVTFE &MFWBUJPOEJGGFSFODFCFUXF
*GUIFVOJUXFJHIUTNPSFUIBOLH
JUNVTUCFDBSSJFECZUXPPSNPSFQFSTPOT%POPUDBSSZCZUIFQMBTUJDTUSBQT
BMXBZTVTFUIFDBSSZIBOEMFXIFODBSSZJOHUIF
VOJUCZIBOE6TFHMPWFTUPNJOJNJ[FUIFSJTLPGDVUTCZUIFBMVNJOVNmOT ・-PDBUJPOTXJUITBMUZBUNPTQIFSFTTVDIBTDPBTUMJOFT
● %JTQPTFPGBOZQBDLJOHNBUFSJBMTDPSSFDUMZ
・-PDBUJPOTXJUIIFBWZTOPX *GJOTUBMMFE
CFTVSFUPQSPWJEFCBTFnBNFBOETOPXIPPENFOUJPOFEJOUIFNBOVBM
・-PDBUJPOTXIFSFUIFVOJUJTFYQPTFEUPDIJNOFZTNPLF
$"65*0/
"OZSFNBJOJOHQBDLJOHNBUFSJBMTDBODBVTFQFSTPOBMJOKVSZBTJUDPOUBJOTOBJMTBOEXPPE"OEUPBWPJEEBOHFSPGTVGGPDBUJPO
CFTVSFUPLFFQUIFQMBTUJD ・-PDBUJPOTBUIJHIBMUJUVEF NPSFUIBONIJHI
XSBQQFSBXBZGSPNDIJMESFOBOEUPEJTQPTFBGUFSUFBSJUVQ ・-PDBUJPOTXJUIBNNPOJDBUNPTQIFSFT
● 1BZBUUFOUJPOOPUUPEBNBHFUIFESBJOQBOCZXFMETQBUUFSXIFOXFMEJOHXPSLJTEPOFOFBSUIFJOEPPSVOJU ・-PDBUJPOTXIFSFIFBUSBEJBUJPOGSPNPUIFSIFBUTPVSDFDBOBGGFDUUIFVOJU
*GXFMETQBUUFSFOUFSFEJOUPUIFJOEPPSVOJUEVSJOHXFMEJOHXPSL
JUDBODBVTFQJOIPMFJOESBJOQBOBOESFTVMUJOXBUFSMFBLBHF5PQSFWFOUTVDIEBNBHF
LFFQUIFJOEPPSVOJUJOJUTQBDLJOHPSDPWFSJU ・-PDBUJPOTXJUIPVUHPPEBJSDJSDVMBUJPO
● #FTVSFUPJOTVMBUFUIFSFGSJHFSBOUQJQFTTPBTOPUUPDPOEFOTFUIFBNCJFOUBJSNPJTUVSFPOUIFN ・-PDBUJPOTXJUIBOZPCTUBDMFTXIJDIDBOQSFWFOUJOMFUBOEPVUMFUBJSPGUIFVOJU
*OTVGmDJFOUJOTVMBUJPODBODBVTFDPOEFOTBUJPO
XIJDIDBOMFBEUPNPJTUVSFEBNBHFPOUIFDFJMJOH
nPPS
GVSOJUVSFBOEBOZPUIFSWBMVBCMFT ・-PDBUJPOTXIFSFTIPSUDJSDVJUPGBJSDBOPDDVS JODBTFPGNVMUJQMFVOJUTJOTUBMMBUJPO
・-PDBUJPOTXIFSFTUSPOHBJSCMPXTBHBJOTUUIFBJSPVUMFUPGPVUEPPSVOJU
%FUFSNJO
● #FTVSFUPQFSGPSNBJSUJHIUOFTTUFTUCZQSFTTVSJ[JOHXJUIOJUSPHFOHBTBGUFSDPNQMFUFESFGSJHFSBOUQJQJOHXPSL *UDBODBVTFSFNBSLBCMFEFDSFBTFJOQFSGPSNBODF
DPSSPTJPOBOEEBNBHFPGDPNQPOFOUT
NBMGVODUJPOBOEmSF ● %FUFSNJOF SFGSJ
*GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJUJOUIFFWFOUPGSFGSJHFSBOUMFBLBHFJOUIFTNBMMSPPN
MBDLPGPYZHFODBOPDDVS
XIJDIDBODBVTFTFSJPVTBDDJEFOUT
● %POPUJOTUBMMUIFPVUEPPSVOJUJOUIFMPDBUJPOTMJTUFECFMPX
● 1FSGPSNJOTUBMMBUJPOXPSLQSPQFSMZBDDPSEJOHUPUIJTJOTUBMMBUJPONBOVBM
・-PDBUJPOTXIFSFEJTDIBSHFEIPUBJSPSPQFSBUJOHTPVOEPGUIFPVUEPPSVOJUDBOCPUIFSOFJHICPSIPPE
*NQSPQFSJOTUBMMBUJPODBODBVTFBCOPSNBMWJCSBUJPOTPSJODSFBTFEOPJTFHFOFSBUJPO
・-PDBUJPOTXIFSFPVUMFUBJSPGUIFPVUEPPSVOJUCMPXTEJSFDUMZUPBOBOJNBMPSQMBOUT5IFPVUMFUBJSDBOBGGFDUBEWFSTFMZUPUIFQMBOUFUD
● &BSUIMFBLBHFCSFBLFSNVTUCFJOTUBMMFE ・-PDBUJPOTXIFSFWJCSBUJPODBOCFBNQMJmFEBOEUSBOTNJUUFEEVFUPJOTVGmDJFOUTUSFOHUIPGTUSVDUVSF
*GUIFFBSUIMFBLBHFCSFBLFSJTOPUJOTUBMMFE
JUDBODBVTFmSFPSFMFDUSJDTIPDLT ・-PDBUJPOTXIFSFWJCSBUJPOBOEPQFSBUJPOTPVOEHFOFSBUFECZUIFPVUEPPSVOJUDBOBGGFDUTFSJPVTMZ POUIFXBMMPSBUUIFQMBDFOFBSCFESPPN
● %P OPU JOTUBMM UIF VOJU XIFSF DPSSPTJWF HBT TVDI BT TVMGVSPVT BDJE HBT FUD
PS DPNCVTUJCMF HBT TVDI BT UIJOOFS BOE QFUSPMFVN HBTFT
DBO *UDBODBVTFUIFEBNBHFPGUIFJUFNT
BDDVNVMBUFPSDPMMFDU
PSXIFSFWPMBUJMFDPNCVTUJCMFTVCTUBODFTBSFIBOEMFE ● %POPUUPVDIBOZCVUUPOTXJUIXFUIBOET
$PSSPTJWFHBTDBODBVTFDPSSPTJPOPGIFBUFYDIBOHFS
CSFBLBHFPGQMBTUJDQBSUTBOEFUD"OEDPNCVTUJCMFHBTDBODBVTFmSF *UDBODBVTFFMFDUSJDTIPDLT *OUIFDBTFPGBUSJQMFUZQ
● 4FDVSFBTQBDFGPSJOTUBMMBUJPO
JOTQFDUJPOBOENBJOUFOBODFTQFDJmFEJOUIFNBOVBM ● %POPUUPVDIBOZSFGSJHFSBOUQJQFTXJUIZPVSIBOETXIFOUIFTZTUFNJTJOPQFSBUJPO
*OTVGmDJFOUTQBDFDBOSFTVMUJOBDDJEFOUTVDIBTQFSTPOBMJOKVSZEVFUPGBMMJOHGSPNUIFJOTUBMMBUJPOQMBDF %VSJOHPQFSBUJPOUIFSFGSJHFSBOUQJQFTCFDPNFFYUSFNFMZIPUPSFYUSFNFMZDPMEEFQFOEJOHUIFPQFSBUJOHDPOEJUJPO
BOEJUDBODBVTFCVSOJOKVSZPSGSPTUJOKVSZ
● 8IFOUIFPVUEPPSVOJUJTJOTUBMMFEPOBSPPGPSBIJHIQMBDF
QSPWJEFQFSNBOFOUMBEEFSTBOEIBOESBJMTBMPOHUIFBDDFTTSPVUFBOEGFODFTBOEIBOESBJMTBSPVOEUIFPVUEPPSVOJU
● %POPUDMFBOVQUIFVOJUXJUIXBUFS
*GTBGFUZGBDJMJUJFTBSFOPUQSPWJEFE
JUDBODBVTFQFSTPOBMJOKVSZEVFUPGBMMJOHGSPNUIFJOTUBMMBUJPOQMBDF
*UDBODBVTFFMFDUSJDTIPDLT *OUIFDBTFPGBUSJQMFUZQ
● %POPUJOTUBMMOPSVTFUIFTZTUFNDMPTFUPUIFFRVJQNFOUUIBUHFOFSBUFTFMFDUSPNBHOFUJDmFMETPSIJHIGSFRVFODZIBSNPOJDT
&RVJQNFOUTVDIBTJOWFSUFST
TUBOECZHFOFSBUPST
NFEJDBMIJHIGSFRVFODZFRVJQNFOUTBOEUFMFDPNNVOJDBUJPOFRVJQNFOUTDBOBGGFDUUIFTZTUFN
BOEDBVTF ● %POPUPQFSBUFUIFPVUEPPSVOJUXJUIBOZBSUJDMFQMBDFEPOJU
NBMGVODUJPOTBOECSFBLEPXOT5IFTZTUFNDBOBMTPBGGFDUNFEJDBMFRVJQNFOUBOEUFMFDPNNVOJDBUJPOFRVJQNFOU
BOEPCTUSVDUJUTGVODUJPOPSDBVTFKBNNJOH :PVNBZJODVSQSPQFSUZEBNBHFPSQFSTPOBMJOKVSFGSPNBGBMMPGUIFBSUJDMF
● %POPUJOTUBMMUIFPVUEPPSVOJUJOBMPDBUJPOXIFSFJOTFDUTBOETNBMMBOJNBMTDBOJOIBCJU ● %POPUTUFQPOUPUIFPVUEPPSVOJU
*OTFDUTBOETNBMMBOJNBMTDBOFOUFSUIFFMFDUSJDQBSUTBOEDBVTFEBNBHFPSmSF*OTUSVDUUIFVTFSUPLFFQUIFTVSSPVOEJOHTDMFBO :PVNBZJODVSJOKVSZGSPNBESPQPSGBMM
*OUIFDBTFPGB8UXJOUZ
$"65*0/ 0OFXBZQJQFMFOHUIEJGG
● $BSSZPVUUIFFMFDUSJDBMXPSLGPSHSPVOEMFBEXJUIDBSF ● %POPUVTFUIFCBTFnBNFGPSPVUEPPSVOJUXIJDIJTDPSSPEFEPSEBNBHFEEVFUPMPOHQFSJPETPGPQFSBUJPO CSBODIJOHQPJOUUPUIFJOE
%POPUDPOOFDUUIFHSPVOEMFBEUPUIFHBTMJOF
XBUFSMJOF
MJHIUOJOHDPOEVDUPSPSUFMFQIPOFMJOFhTHSPVOEMFBE*ODPSSFDUHSPVOEJOHDBODBVTFVOJUGBVMUTTVDIBT 6TJOHBOPMEBOEEBNBHFCBTFnBNFDBODBVTFUIFVOJUGBMMJOHEPXOBOEDBVTFQFSTPOBMJOKVSZ
FMFDUSJDTIPDLTEVFUPTIPSUDJSDVJUJOH/FWFSDPOOFDUUIFHSPVOEJOHXJSFUPBHBTQJQFCFDBVTFJGHBTMFBLT
JUDPVMEDBVTFFYQMPTJPOPSJHOJUJPO ● %POPUJOTUBMMUIFVOJUJOUIFMPDBUJPOTMJTUFECFMPX
● 6TFUIFDJSDVJUCSFBLFSGPSBMMQPMFXJUIDPSSFDUDBQBDJUZ ・-PDBUJPOTXIFSFDBSCPOmCFS
NFUBMQPXEFSPSBOZQPXEFSJTnPBUJOH 0OFXBZQJQFMFOHUIEJGG
TFDPOECSBODIJOHQPJOUU
6TJOHUIFJODPSSFDUDJSDVJUCSFBLFS
JUDBODBVTFUIFVOJUNBMGVODUJPOBOEmSF ・-PDBUJPOTXIFSFBOZTVCTUBODFTUIBUDBOBGGFDUUIFVOJUTVDIBTTVMQIJEFHBT
DIMPSJEFHBT
BDJEBOEBMLBMJOFDBOPDDVS
5PUBMQJQFMFOHUIBGUFSUIF
● *OTUBMMJTPMBUPSPSEJTDPOOFDUTXJUDIPOUIFQPXFSTVQQMZXJSJOHJOBDDPSEBODFXJUIUIFMPDBMDPEFTBOESFHVMBUJPOT ・7FIJDMFTBOETIJQT
5IFJTPMBUPSTIPVMECFMPDLFEJOBDDPSEBODFEXJUI&/ ・-PDBUJPOTXIFSFDPTNFUJDPSTQFDJBMTQSBZTBSFPGUFOVTFE &MFWBUJPOEJGGFSFODFCFUX
VOJUT
● 5BLFDBSFXIFODBSSZJOHUIFVOJUCZIBOE ・-PDBUJPOTXJUIEJSFDUFYQPTVSFPGPJMNJTUBOETUFBNTVDIBTLJUDIFOBOENBDIJOFQMBOU
・-PDBUJPOTXIFSFBOZNBDIJOFTXIJDIHFOFSBUFIJHIGSFRVFODZIBSNPOJDTBSFVTFE &MFWBUJPOEJGGFSFODFCFUX
*GUIFVOJUXFJHIUTNPSFUIBOLH
JUNVTUCFDBSSJFECZUXPPSNPSFQFSTPOT%POPUDBSSZCZUIFQMBTUJDTUSBQT
BMXBZTVTFUIFDBSSZIBOEMFXIFODBSSZJOHUIF
VOJUCZIBOE6TFHMPWFTUPNJOJNJ[FUIFSJTLPGDVUTCZUIFBMVNJOVNmOT ・-PDBUJPOTXJUITBMUZBUNPTQIFSFTTVDIBTDPBTUMJOFT
● %JTQPTFPGBOZQBDLJOHNBUFSJBMTDPSSFDUMZ
・-PDBUJPOTXJUIIFBWZTOPX *GJOTUBMMFE
CFTVSFUPQSPWJEFCBTFnBNFBOETOPXIPPENFOUJPOFEJOUIFNBOVBM
・-PDBUJPOTXIFSFUIFVOJUJTFYQPTFEUPDIJNOFZTNPLF
$"65*0
"OZSFNBJOJOHQBDLJOHNBUFSJBMTDBODBVTFQFSTPOBMJOKVSZBTJUDPOUBJOTOBJMTBOEXPPE"OEUPBWPJEEBOHFSPGTVGGPDBUJPO
CFTVSFUPLFFQUIFQMBTUJD ・-PDBUJPOTBUIJHIBMUJUVEF NPSFUIBONIJHI
XSBQQFSBXBZGSPNDIJMESFOBOEUPEJTQPTFBGUFSUFBSJUVQ ・-PDBUJPOTXJUIBNNPOJDBUNPTQIFSFT
● 1BZBUUFOUJPOOPUUPEBNBHFUIFESBJOQBOCZXFMETQBUUFSXIFOXFMEJOHXPSLJTEPOFOFBSUIFJOEPPSVOJU ・-PDBUJPOTXIFSFIFBUSBEJBUJPOGSPNPUIFSIFBUTPVSDFDBOBGGFDUUIFVOJU
*GXFMETQBUUFSFOUFSFEJOUPUIFJOEPPSVOJUEVSJOHXFMEJOHXPSL
JUDBODBVTFQJOIPMFJOESBJOQBOBOESFTVMUJOXBUFSMFBLBHF5PQSFWFOUTVDIEBNBHF
LFFQUIFJOEPPSVOJUJOJUTQBDLJOHPSDPWFSJU ・-PDBUJPOTXJUIPVUHPPEBJSDJSDVMBUJPO
● #FTVSFUPJOTVMBUFUIFSFGSJHFSBOUQJQFTTPBTOPUUPDPOEFOTFUIFBNCJFOUBJSNPJTUVSFPOUIFN ・-PDBUJPOTXJUIBOZPCTUBDMFTXIJDIDBOQSFWFOUJOMFUBOEPVUMFUBJSPGUIFVOJU
*OTVGmDJFOUJOTVMBUJPODBODBVTFDPOEFOTBUJPO
XIJDIDBOMFBEUPNPJTUVSFEBNBHFPOUIFDFJMJOH
nPPS
GVSOJUVSFBOEBOZPUIFSWBMVBCMFT ・-PDBUJPOTXIFSFTIPSUDJSDVJUPGBJSDBOPDDVS JODBTFPGNVMUJQMFVOJUTJOTUBMMBUJPO
・-PDBUJPOTXIFSFTUSPOHBJSCMPXTBHBJOTUUIFBJSPVUMFUPGPVUEPPSVOJU
%FUFSNJO
● #FTVSFUPQFSGPSNBJSUJHIUOFTTUFTUCZQSFTTVSJ[JOHXJUIOJUSPHFOHBTBGUFSDPNQMFUFESFGSJHFSBOUQJQJOHXPSL *UDBODBVTFSFNBSLBCMFEFDSFBTFJOQFSGPSNBODF
DPSSPTJPOBOEEBNBHFPGDPNQPOFOUT
NBMGVODUJPOBOEmSF ● %FUFSNJOF SFGS
*GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJUJOUIFFWFOUPGSFGSJHFSBOUMFBLBHFJOUIFTNBMMSPPN
MBDLPGPYZHFODBOPDDVS
XIJDIDBODBVTFTFSJPVTBDDJEFOUT
● %POPUJOTUBMMUIFPVUEPPSVOJUJOUIFMPDBUJPOTMJTUFECFMPX
● 1FSGPSNJOTUBMMBUJPOXPSLQSPQFSMZBDDPSEJOHUPUIJTJOTUBMMBUJPONBOVBM
・-PDBUJPOTXIFSFEJTDIBSHFEIPUBJSPSPQFSBUJOHTPVOEPGUIFPVUEPPSVOJUDBOCPUIFSOFJHICPSIPPE
*NQSPQFSJOTUBMMBUJPODBODBVTFBCOPSNBMWJCSBUJPOTPSJODSFBTFEOPJTFHFOFSBUJPO
・-PDBUJPOTXIFSFPVUMFUBJSPGUIFPVUEPPSVOJUCMPXTEJSFDUMZUPBOBOJNBMPSQMBOUT5IFPVUMFUBJSDBOBGGFDUBEWFSTFMZUPUIFQMBOUFUD
● &BSUIMFBLBHFCSFBLFSNVTUCFJOTUBMMFE ・-PDBUJPOTXIFSFWJCSBUJPODBOCFBNQMJmFEBOEUSBOTNJUUFEEVFUPJOTVGmDJFOUTUSFOHUIPGTUSVDUVSF
*GUIFFBSUIMFBLBHFCSFBLFSJTOPUJOTUBMMFE
JUDBODBVTFmSFPSFMFDUSJDTIPDLT ・-PDBUJPOTXIFSFWJCSBUJPOBOEPQFSBUJPOTPVOEHFOFSBUFECZUIFPVUEPPSVOJUDBOBGGFDUTFSJPVTMZ POUIFXBMMPSBUUIFQMBDFOFBSCFESPPN
● %P OPU JOTUBMM UIF VOJU XIFSF DPSSPTJWF HBT TVDI BT TVMGVSPVT BDJE HBT FUD
PS DPNCVTUJCMF HBT TVDI BT UIJOOFS BOE QFUSPMFVN HBTFT
DBO *UDBODBVTFUIFEBNBHFPGUIFJUFNT
BDDVNVMBUFPSDPMMFDU
PSXIFSFWPMBUJMFDPNCVTUJCMFTVCTUBODFTBSFIBOEMFE ● %POPUUPVDIBOZCVUUPOTXJUIXFUIBOET
$PSSPTJWFHBTDBODBVTFDPSSPTJPOPGIFBUFYDIBOHFS
CSFBLBHFPGQMBTUJDQBSUTBOEFUD"OEDPNCVTUJCMFHBTDBODBVTFmSF *UDBODBVTFFMFDUSJDTIPDLT *OUIFDBTFPGBUSJQMFUZ
● 4FDVSFBTQBDFGPSJOTUBMMBUJPO
JOTQFDUJPOBOENBJOUFOBODFTQFDJmFEJOUIFNBOVBM ● %POPUUPVDIBOZSFGSJHFSBOUQJQFTXJUIZPVSIBOETXIFOUIFTZTUFNJTJOPQFSBUJPO
*OTVGmDJFOUTQBDFDBOSFTVMUJOBDDJEFOUTVDIBTQFSTPOBMJOKVSZEVFUPGBMMJOHGSPNUIFJOTUBMMBUJPOQMBDF %VSJOHPQFSBUJPOUIFSFGSJHFSBOUQJQFTCFDPNFFYUSFNFMZIPUPSFYUSFNFMZDPMEEFQFOEJOHUIFPQFSBUJOHDPOEJUJPO
BOEJUDBODBVTFCVSOJOKVSZPSGSPTUJOKVSZ
● 8IFOUIFPVUEPPSVOJUJTJOTUBMMFEPOBSPPGPSBIJHIQMBDF
QSPWJEFQFSNBOFOUMBEEFSTBOEIBOESBJMTBMPOHUIFBDDFTTSPVUFBOEGFODFTBOEIBOESBJMTBSPVOEUIFPVUEPPSVOJU
● %POPUDMFBOVQUIFVOJUXJUIXBUFS
*GTBGFUZGBDJMJUJFTBSFOPUQSPWJEFE
JUDBODBVTFQFSTPOBMJOKVSZEVFUPGBMMJOHGSPNUIFJOTUBMMBUJPOQMBDF
*UDBODBVTFFMFDUSJDTIPDLT *OUIFDBTFPGBUSJQMFUZ
● %POPUJOTUBMMOPSVTFUIFTZTUFNDMPTFUPUIFFRVJQNFOUUIBUHFOFSBUFTFMFDUSPNBHOFUJDmFMETPSIJHIGSFRVFODZIBSNPOJDT
&RVJQNFOUTVDIBTJOWFSUFST
TUBOECZHFOFSBUPST
NFEJDBMIJHIGSFRVFODZFRVJQNFOUTBOEUFMFDPNNVOJDBUJPOFRVJQNFOUTDBOBGGFDUUIFTZTUFN
BOEDBVTF ● %POPUPQFSBUFUIFPVUEPPSVOJUXJUIBOZBSUJDMFQMBDFEPOJU
NBMGVODUJPOTBOECSFBLEPXOT5IFTZTUFNDBOBMTPBGGFDUNFEJDBMFRVJQNFOUBOEUFMFDPNNVOJDBUJPOFRVJQNFOU
BOEPCTUSVDUJUTGVODUJPOPSDBVTFKBNNJOH :PVNBZJODVSQSPQFSUZEBNBHFPSQFSTPOBMJOKVSFGSPNBGBMMPGUIFBSUJDMF
● %POPUJOTUBMMUIFPVUEPPSVOJUJOBMPDBUJPOXIFSFJOTFDUTBOETNBMMBOJNBMTDBOJOIBCJU ● %POPUTUFQPOUPUIFPVUEPPSVOJU
*OTFDUTBOETNBMMBOJNBMTDBOFOUFSUIFFMFDUSJDQBSUTBOEDBVTFEBNBHFPSmSF*OTUSVDUUIFVTFSUPLFFQUIFTVSSPVOEJOHTDMFBO :PVNBZJODVSJOKVSZGSPNBESPQPSGBMM
*OUIFDBTFPGB8UXJO
"DDFTTPSZQ
)"6-"(&"/%*/45"--"5*0/
φ *%
5BLFQBSUJDVMBSDBSFJODBSSZJOHJOPSNPWJOHUIFVOJU BOEBMXBZTQFSGPSNTVDIBOPQFSBUJPOXJUIUXPPSNPSFQFSTPOT
8IFO B VOJU JT IPJTUFE XJUI TMJOHT GPS IBVMBHF
UBLF JOUP DPOTJEFSBUJPO UIF PGGTFU PG JUT HSBWJUZ DFOUFS QPTJUJPO 1BE
$"65*0/ *G OPU QSPQFSMZ CBMBODFE
UIF VOJU DBO CF UISPXO PGGCBMBODF BOE GBMM
%FMJWFSZ
1PSUBHF )FBWZ
● %FMJWFS UIF VOJU BT DMPTF BT QPTTJCMF UP UIF JOTUBMMBUJPO TJUF CFGPSF SFNPWJOH JU GSPN UIF QBDLBHJOH ● 5IF SJHIU IBOE TJEF PG UIF VOJU BT WJFXFE GSPN UIF GSPOU EJGGVTFS TJEF
JT IFBWJFS " QFSTPO
3FGSJHFSB
● 8IFO TPNF DPNQFMMJOH SFBTPO OFDFTTJUBUFT UIF VOQBDLJOH PG UIF VOJU CFGPSF JU JT DBSSJFE JO
VTF OZMPO DBSSZJOH UIF SJHIU IBOE TJEF NVTU UBLF IFFE PG UIJT GBDU " QFSTPO DBSSZJOH UIF MFGU IBOE TJEF ● 4FMFDU SFGSJHFS
TMJOHT PS QSPUFDUJWF XPPE QJFDFT TP BT OPU UP EBNBHF UIF VOJU CZ SPQFT MJGUJOH JU NVTU IPME XJUI IJT SJHIU IBOE UIF IBOEMF QSPWJEFE PO UIF GSPOU QBOFM PG UIF VOJU BOE XJUI IJT MFGU TJ[F
IBOE UIF DPSOFS DPMVNO TFDUJPO ● 5IJT VOJU VTFT
8PPEFO QBMMFU CFDBVTF0UZQ
4#%-
4FMFDUJPO PG JOTUBMMBUJPO MPDBUJPO GPS UIF PVUEPPS VOJU
*OTUBMMBUJPO TQBDF
#F TVSF UP TFMFDU B TVJUBCMF JOTUBMMBUJPO QMBDF JO DPOTJEFSBUJPO PG GPMMPXJOH DPOEJUJPOT ● 8BMMTTVSSPVOEJOHUIFVOJUJOUIFGPVSTJEFTBSFOPUBDDFQUBCMF
● 5IFSFNVTUCFBNFUFSPSMBSHFSTQBDFJOUIFBCPWF
〇" QMBDF XIFSF JU JT IPSJ[POUBM
TUBCMF BOE DBO FOEVSF UIF VOJU XFJHIU BOE XJMM OPU BMMPX WJCSBUJPO USBOTNJUUBODF PG UIF VOJU
MFTQMJU1"$ 〇" QMBDF XIFSF JU DBO CF GSFF GSPN QPTTJCJMJUZ PG CPUIFSJOH OFJHICPST EVF UP OPJTF PS FYIBVTU BJS GSPN UIF VOJU ● 8IFSFBEBOHFSPGTIPSUDJSDVJUJOHFYJTUT
JOTUBMMHVJEFMPVWFST
● 8IFONPSFUIBOPOFVOJUBSFJOTUBMMFE
QSPWJEFTVGmDJFOUJOUBLFTQBDFDPOTDJPVTMZTPUIBUTIPSUDJSDVJUJOHNBZOPUPDDVS
〇" QMBDF XIFSF UIF VOJU JT OPU FYQPTFE UP PJM TQMBTIFT
7 〇" QMBDF XIFSF JU DBO CF GSFF GSPN EBOHFS PG nBNNBCMF HBT MFBLBHF ● 8IFSF QJMJOH TOPX DBO CVSZ UIF PVUEPPS VOJU
QSPWJEF QSPQFS TOPX HVBSET
● " CBSSJFS XBMM QMBDFE JO GSPOU PG UIF FYIBVTU EJGGVTFS NVTU OPU CF IJHIFS UIBO UIF VOJU
〇" QMBDF XIFSF ESBJO XBUFS DBO CF EJTQPTFE XJUIPVU BOZ USPVCMF
"SFGSJHFSBOU 〇" QMBDF XIFSF UIF VOJU XJMM OPU CF BGGFDUFE CZ IFBU SBEJBUJPO GSPN PUIFS IFBU TPVSDF
-
(mm)
〇" QMBDF XIFSF TOPX XJMM OPU BDDVNVMBUF
〇" QMBDF XIFSF UIF VOJU DBO CF LFQU BXBZ N PS NPSF GSPN57 TFU BOEPS SBEJP SFDFJWFS JO PSEFS UP BWPJE BOZ SBEJP PS57 JOUFSGFSFODF 7, 7 -
230 -
*OUBLF
〇" QMBDF XIFSF HPPE BJS DJSDVMBUJPO DBO CF TFDVSFE
BOE FOPVHI TFSWJDF TQBDF DBO CF TFDVSFE GPS NBJOUFOBODF BOE TFSWJDF PG UIF VOJU TBGFMZ -
PSL
&YBNQMFJOTUBMMBUJPO Ⅱ Ⅲ
4J[F Ⅰ
〇" QMBDF XIFSF UIF VOJU XJMM OPU CF BGGFDUFE CZ FMFDUSPNBHOFUJD XBWFT BOEPS IJHIIBSNPOJD XBWFT HFOFSBUFE CZ PUIFS FRVJQNFOU 0QFO 0QFO
-
-
〇" QMBDF XIFSF DIFNJDBM TVCTUBODFT MJLF TVMGVSJD HBT
DIMPSJD HBT
BDJE BOE BMLBMJ JODMVEJOH BNNPOJB
XIJDI DBO IBSN UIF *OUBLF
- 0QFO
VOJU
XJMM OPU CF HFOFSBUFE BOE OPU SFNBJO TFSWJDF
QF
〇" QMBDF XIFSF TUSPOH XJOE XJMM OPU CMPX BHBJOTU UIF PVUMFU BJS CMPX PG UIF VOJU - 0VUMFU
TQBDF
-
-
FDF
0%
$BVUJPO BCPVU TFMFDUJPO PG JOTUBMMBUJPO MPDBUJPO
*G UIF VOJU JT JOTUBMMFE JO UIF BSFB XIFSF UIF TOPX XJMM BDDVNVMBUF
GPMMPXJOH NFBTVSFT BSF SFRVJSFE
5IF CPUUPN QMBUF PG VOJU BOE JOUBLF
PVUMFU NBZ CF CMPDLFE CZ TOPX
"DDFTTPSZQJQF# *OTUBMM UIF VOJU PO UIF CBTF TP 1SPWJEF B TOPX IPPE UP *OTUBMM UIF VOJU VOEFS FBWFT
*OTUBMMBUJPO
UIBU UIF CPUUPN JT IJHIFS UIBO UIF PVUEPPS VOJU PO TJUF PS QSPWJEF UIF SPPG PO TJUF
TOPX DPWFS TVSGBDF 3FHBSEJOH PVUMJOF PG B TOPX ① "ODIPSCPMUmYFEQPTJUJPO ② /PUBCJMJBGPSJOTUBMMBUJPO
IPPE
SFGFS UP PVS UFDIOJDBM *OUBLF
NBOVBM 'BTUFOXJUICPMUT
.
0VUMFU
'10 • PAC-DB-142
*G UIF VOJU DBO CF BGGFDUFE CZ TUSPOH XJOE
GPMMPXJOH NFBTVSFT BSF SFRVJSFE ● 4FDVSFMZJOTUBMMUIFVOJUTPUIBUJUEPFTOPUGBMMPWFSEVSJOHFBSUIRVBLFTPSTUSPOHXJOET
FUD
4USPOH XJOE DBO DBVTF EBNBHF PG GBO GBO NPUPS
PS DBO DBVTF QFSGPSNBODF EFHSBEBUJPO
PS DBO USJHHFS BOPNBMPVT TUPQ ● 3FGFSUPUIFMFGUJMMVTUSBUJPOTGPSJOGPSNBUJPOSFHBSEJOHDPODSFUFGPVOEBUJPOT
PG UIF VOJU EVF UP SJTJOH PG IJHI QSFTTVSF ● *OTUBMMUIFVOJUJOBMFWFMBSFB 8JUIBHSBEJFOUPGNNPSMFTT
*NQSPQFSJOTUBMMBUJPODBOSFTVMUJOBDPNQSFTTPSGBJMVSF
CSPLFOQJQJOHXJUIJOUIFVOJUBOEBCOPSNBMOPJTFHFOFSBUJPO
*OTUBMM UIF PVUMFU BJS CMPX TJEF PG UIF *OTUBMM UIF PVUMFU BJS CMPX TJEF PG 5IF VOJU TIPVME CF JOTUBMMFE PO
VOJU UP GBDF B XBMM PG CVJMEJOH
PS UIF VOJU JO B QPTJUJPO UIF TUBCMF BOE MFWFM GPVOEBUJPO
QSPWJEF B GFODF PS B XJOECSFBL QFSQFOEJDVMBS UP UIF EJSFDUJPO PG *G UIF GPVOEBUJPO JT OPU MFWFM
SFGSJHFSBOUDJSDVJU
TDSFFO XJOE UJF EPXO UIF VOJU XJUI XJSFT
IPE #F TVSF OPU UP
5P SVO UIF VOJU GPS B DPPMJOH PQFSBUJPO
XIFO UIF PVUEPPS UFNQFSBUVSF
FGSJHFSBOUMFBLTXIJDI
8JOE EJSFDUJPO
JT o¡$ PS MPXFS
● 8IFO UIF PVUEPPS BJS UFNQFSBUVSF JT ¡$ PS MPXFS
QSPWJEF B TOPX IPPE UP UIF PVUEPPS VOJU PO TJUF
SL
BJSUJHIUOFTTUFTU
4P UIBU TUSPOH XJOE XJMM OPU CMPX BHBJOTU UIF PVUEPPS IFBU FYDIBOHFS EJSFDUMZ 3FHBSEJOH PVUMJOF PG B TOPX IPPE
0WFS NN
SBOU QJQJOH XPSL
ZPV SFGFS UP PVS UFDIOJDBM NBOVBM
DVJU
XIJDIDBODBVTF 8JOE EJSFDUJPO
3&'3*(&3"/51*1*/(803,
FS PS UIF VTF PG OPO
3FTUSJDUJPOT PO VOJU JOTUBMMBUJPO BOE VTF
OFYQFDUFETUBSUPGGBO ● $IFDL UIF GPMMPXJOH QPJOUT JO MJHIU PG UIF JOEPPS VOJU TQFDJmDBUJPOT BOE UIF JOTUBMMBUJPO TJUF 4JOHMFUZQF *OEPPSVOJU
● 0CTFSWF UIF GPMMPXJOH SFTUSJDUJPOT PO VOJU JOTUBMMBUJPO BOE VTF *NQSPQFS JOTUBMMBUJPO DBO SFTVMU JO B DPNQSFTTPS GBJMVSF PS QFSGPSNBODF EFHSBEBUJPO
.BSLTBQQFBSUJOHJOUIFESBXJOH
OPQFSBUJPO 0OFXBZQJQFMFOHUIEJGGFSFODFGSPNUIFmSTUCSBODIJOHQPJOUUPUIFJOEPPSVOJU N ≧N )
NBZ JODVS GSPTU CJUF PS 3FTUSJDUJPOT
%JNFOTJPOBM 8UXJOUZQF
.PEFMGPSPVUEPPSVOJUT 4JOHMFUZQF 5XJOUZQF 5SJQMFUZQF" 5SJQMFUZQF#
ZEVFUPBOPNBMPVTMZ SFTUSJDUJPOT
φ ≦N -
7 -JRVJE1JQJOH -+-
-+-
-+- -+-
0VUEPPSVOJU
φ -+- -+-B+-, -+-B+-
0OFXBZQJQFMFOHUIPGSFGSJHFSBOUQJQJOH ≦N -
φPSφ -+- -+-C+-, -+-C+-
DBO DBVTF CVSTU BOE 7ï (BTQJQJOH -+-
-+-B+-
-+-B+-
UZQF#
1SPIJCJUBUJPOPGUIFVTF
7 φ ≦N 5XJOUZQF
φ ≦N *OEPPSVOJU
7 -JRVJE1JQJOH -+-
5IFVOJUPGXIJDIFMFWBUJPOEJGGFSFODFGSPNUIFPVUEPPSVOJUJTUIFMBSHFTU
φ
NFOU
CVSOPSFMFDUSJD .BJOQJQFMFOHUI ≦N − - - -
7ï (BTQJQJOH φPSφ
1SPIJCJUBUJPOPGUIFVTF
7 φ ≦N *OEPPSVOJU I
0OFXBZQJQFMFOHUICFUXFFOUIFmSTUCSBODIJOH 7 − -B
QPJOUGSPNUPUIFTFDPOECSBODIJOHQPJOU ≦N − − −
7 -B 1SPIJCJUBUJPOPGUIFVTF
)
JS 0OFXBZQJQFMFOHUIBGUFSUIFmSTUCSBODIJOH 7 -
-
- -
-B+L, -+-B+- -
QPJOU ≦N − − -C+-, -C+- -
7 -
-B+-
-+-B+-
UZQF#
1SPIJCJUBUJPOPGUIFVTF
0OFXBZQJQFMFOHUIBGUFSUIFmSTUCSBODIJOH ≦N − − − −
QPJOUBOETFDPOECSBODIJOHQPJOU 7 -B+-, -B+-
−
- SJTFS
5XJOUZQF ≦N
− 0VUEPPSVOJU
≦N |-−-|
|-−-|
|-−-|
7 −
5SJQMFUZQF ≦N − -− -B+-
-− -B+-
5SJQMFUZQF
0OFXBZQJQFMFOHUIEJGGFSFODFGSPNUIFmSTU − |-−-|
CSBODIJOHQPJOUUPUIFJOEPPSVOJU 7 ≦N |-− -B+-
|
|-− -B+-
|
|-−-|
UZQF#
1SPIJCJUBUJPOPGUIFVTF 5ZQF"
|-−-|
|-−-|
8UXJOUZQF 77 ≦N − − | -+-B
− -+-C
|
| -+-B
− -+-C
| *OEPPSVOJU
| -+-B
− -+-C
|
| -+-B
− -+-C
|
5IFVOJUPGXIJDIFMFWBUJPOEJGGFSFODFGSPNUIFPVUEPPSVOJUJTUIFMBSHFTU
0OFXBZQJQFMFOHUIEJGGFSFODFGSPNUIF
TFDPOECSBODIJOHQPJOUUPUIFJOEPPSVOJU 7 ≦N − − − |-−-| |-−-|, |-−-|
*OEPPSVOJU I
5PUBMQJQFMFOHUIBGUFSUIFTFDPOECSBODIJOHQPJOU ≦N − − − − -+-, -+- I
*OEPPSVOJU
&MFWBUJPOEJGGFSFODFCFUXFFOJOEPPSBOEPVUEPPS 8IFOUIFPVUEPPSVOJUJTQPTJUJPOFEIJHIFS
≦N I
) ) ) ) )
VOJUT 8IFOUIFPVUEPPSVOJUJTQPTJUJPOFEMPXFS
≦N -
)
&MFWBUJPOEJGGFSFODFCFUXFFOJOEPPSVOJUT ≦N − I I
I
I I
I
I I
I
I
I
I
I -
● 'PSNPEFM7
BMXBZTVTFφNNMJRVJEQJQFT
XIFOUIFMFOHUIPGUIFNBJOi-wFYDFFETN*GφNNQJQFTBSFVTFEJOBOJOTUBMMBUJPOIBWJOHPWFSNQJQJOH
UIFZDBODBVTF -
$"65*0/ QFSGPSNBODFEFHSBEBUJPOBOEPSXBUFSMFBLTGSPNBOJOEPPSVOJU
● 5IFVTFSFTUSJDUJPOTBQQFBSJOHJOUIFUBCMFBCPWFBSFBQQMJDBCMFUPUIFTUBOEBSEQJQFTJ[FDPNCJOBUJPOTTIPXOJOUIFUBCMFCFMPX8IFSFBOFYJTUJOHQJQFTZTUFNJTVUJMJ[FE
EJGGFSFOUPOFXBZQJQFMFOHUI
- SJTFS
SFTUSJDUJPOTTIPVMEBQQMZEFQFOEJOHPOJUTQJQFTJ[F'PSNPSFJOGPSNBUJPO
TFFi65*-*;"5*0/0'&9*45*/(1*1*/(w
● 8JUIUIFUSJQMFQJQFDPOOFDUJPO
UIFXBZPGVTFJTEJGGFSFOUXIFOUIFEJGGFSFODFPGPOFXBZQJQFMFOHUIBGUFSUIFmSTUCSBODIJOHQPJOUJTNUPN'PSEFUBJMT
SFGFSUPUIFBCPWFUBCMFBOESJHIUmHVSF
0VUEPPSVOJU
/PUF
*OTUBMMUIFJOEPPSVOJUTTPUIBU--CFDPNFTUIFMPOHFTUPOFXBZQJQF
,FFQUIFQJQFMFOHUIEJGGFSFODFCFUXFFO-BOE -B-
PS -B-
XJUIJON
/PUF
$POOFDUUIFVOJUUIBUJTUIFNBYJNVNDBQBDJUZXJUI- 5SJQMFUZQF
5ZQF#
%FUFSNJOBUJPO PGmanuals
Downloaded from www.Manualslib.com QJQF TJ[Fsearch engine *OEPPSVOJU
● %FUFSNJOF SFGSJHFSBOU QJQF TJ[F QVSTVBOU UP UIF GPMMPXJOH HVJEFMJOFT CBTFE PO UIF JOEPPS VOJU TQFDJmDBUJPOT 5IFVOJUPGXIJDIFMFWBUJPOEJGGFSFODFGSPNUIFPVUEPPSVOJUJTUIFMBSHFTU
7 〇" QMBDF XIFSF JU DBO CF GSFF GSPN EBOHFS PG nBNNBCMF HBT MFBLBHF
● " CBSSJFS XBMM QMBDFE JO GSPOU PG UIF FYIBVTU EJGGVTFS NVTU OPU CF IJHIFS UIBO UIF VOJU
〇" QMBDF XIFSF ESBJO XBUFS DBO CF EJTQPTFE XJUIPVU BOZ USPVCMF
"SFGSJHFSBOU 〇" QMBDF XIFSF UIF VOJU XJMM OPU CF BGGFDUFE CZ IFBU SBEJBUJPO GSPN PUIFS IFBU TPVSDF
(mm)
〇" QMBDF XIFSF TOPX XJMM OPU BDDVNVMBUF
〇" QMBDF XIFSF UIF VOJU DBO CF LFQU BXBZ N PS NPSF GSPN57 TFU BOEPS SBEJP SFDFJWFS JO PSEFS UP BWPJE BOZ SBEJP PS57 JOUFSGFSFODF 7, 7 *OUBLF -
〇" QMBDF XIFSF HPPE BJS DJSDVMBUJPO DBO CF TFDVSFE
BOE FOPVHI TFSWJDF TQBDF DBO CF TFDVSFE GPS NBJOUFOBODF BOE TFSWJDF PG UIF VOJU TBGFMZ -
XPSL
&YBNQMFJOTUBMMBUJPO Ⅱ Ⅲ
4J[F Ⅰ
〇" QMBDF XIFSF UIF VOJU XJMM OPU CF BGGFDUFE CZ FMFDUSPNBHOFUJD XBWFT BOEPS IJHIIBSNPOJD XBWFT HFOFSBUFE CZ PUIFS FRVJQNFOU 0QFO 0QFO
-
-
〇" QMBDF XIFSF DIFNJDBM TVCTUBODFT MJLF TVMGVSJD HBT
DIMPSJD HBT
BDJE BOE BMLBMJ JODMVEJOH BNNPOJB
XIJDI DBO IBSN UIF *OUBLF
- 0QFO
VOJU
XJMM OPU CF HFOFSBUFE BOE OPU SFNBJO TFSWJDF
QJQF
〇" QMBDF XIFSF TUSPOH XJOE XJMM OPU CMPX BHBJOTU UIF PVUMFU BJS CMPX PG UIF VOJU - 0VUMFU
TQBDF
-
-
QJFDF
0%
$BVUJPO BCPVU TFMFDUJPO PG JOTUBMMBUJPO MPDBUJPO
*G UIF VOJU JT JOTUBMMFE JO UIF BSFB XIFSF UIF TOPX XJMM BDDVNVMBUF
GPMMPXJOH NFBTVSFT BSF SFRVJSFE
5IF CPUUPN QMBUF PG VOJU BOE JOUBLF
PVUMFU NBZ CF CMPDLFE CZ TOPX
"DDFTTPSZQJQF# *OTUBMM UIF VOJU PO UIF CBTF TP 1SPWJEF B TOPX IPPE UP *OTUBMM UIF VOJU VOEFS FBWFT
*OTUBMMBUJPO
UIBU UIF CPUUPN JT IJHIFS UIBO UIF PVUEPPS VOJU PO TJUF PS QSPWJEF UIF SPPG PO TJUF
TOPX DPWFS TVSGBDF 3FHBSEJOH PVUMJOF PG B TOPX ① "ODIPSCPMUmYFEQPTJUJPO ② /PUBCJMJBGPSJOTUBMMBUJPO
IPPE
SFGFS UP PVS UFDIOJDBM *OUBLF
NBOVBM 'BTUFOXJUICPMUT
.
0VUMFU
6TFBUIJDLFSCMPDLUP BODIPSEFFQFS
6TFBMPOHCMPDLUPFYUFOEUIFXJEUI
4JODFESBJOXBUFSHFOFSBUFECZEFGSPTUDPOUSPMNBZGSFF[F
GPMMPXJOHNFBTVSFTBSFSFRVJSFE
● %POUFYFDVUFESBJOQJQJOHXPSLCZVTJOHBESBJOFMCPXBOEESBJOHSPNNFUT PQUJPOBMQBSUT
<3FGFSUP%SBJOQJQJOHXPSL>
● *OJOTUBMMJOHUIFVOJU
mYUIFVOJUTMFHTXJUICPMUTTQFDJmFEPOUIFMFGU
● 3FDPNNFOETFUUJOH%FGSPTU$POUSPM 48
BOE4OPX(VBSE'BO$POUSPM 48
<3FGFSUP4FUUJOH48
48>
● 5IFQSPUSVTJPOPGBOBODIPSCPMUPOUIFGSPOUTJEFNVTUCFLFQUXJUIJONN
*G UIF VOJU DBO CF BGGFDUFE CZ TUSPOH XJOE
GPMMPXJOH NFBTVSFT BSF SFRVJSFE ● 4FDVSFMZJOTUBMMUIFVOJUTPUIBUJUEPFTOPUGBMMPWFSEVSJOHFBSUIRVBLFTPSTUSPOHXJOET
FUD
4USPOH XJOE DBO DBVTF EBNBHF PG GBO GBO NPUPS
PS DBO DBVTF QFSGPSNBODF EFHSBEBUJPO
PS DBO USJHHFS BOPNBMPVT TUPQ ● 3FGFSUPUIFMFGUJMMVTUSBUJPOTGPSJOGPSNBUJPOSFHBSEJOHDPODSFUFGPVOEBUJPOT
PG UIF VOJU EVF UP SJTJOH PG IJHI QSFTTVSF ● *OTUBMMUIFVOJUJOBMFWFMBSFB 8JUIBHSBEJFOUPGNNPSMFTT
*NQSPQFSJOTUBMMBUJPODBOSFTVMUJOBDPNQSFTTPSGBJMVSF
CSPLFOQJQJOHXJUIJOUIFVOJUBOEBCOPSNBMOPJTFHFOFSBUJPO
*OTUBMM UIF PVUMFU BJS CMPX TJEF PG UIF *OTUBMM UIF PVUMFU BJS CMPX TJEF PG 5IF VOJU TIPVME CF JOTUBMMFE PO
VOJU UP GBDF B XBMM PG CVJMEJOH
PS UIF VOJU JO B QPTJUJPO UIF TUBCMF BOE MFWFM GPVOEBUJPO
QSPWJEF B GFODF PS B XJOECSFBL QFSQFOEJDVMBS UP UIF EJSFDUJPO PG *G UIF GPVOEBUJPO JT OPU MFWFM
IFSFGSJHFSBOUDJSDVJU
TDSFFO XJOE UJF EPXO UIF VOJU XJUI XJSFT
FUIPE #F TVSF OPU UP
5P SVO UIF VOJU GPS B DPPMJOH PQFSBUJPO
XIFO UIF PVUEPPS UFNQFSBUVSF
SFGSJHFSBOUMFBLTXIJDI
8JOE EJSFDUJPO
JT o¡$ PS MPXFS
● 8IFO UIF PVUEPPS BJS UFNQFSBUVSF JT ¡$ PS MPXFS
QSPWJEF B TOPX IPPE UP UIF PVUEPPS VOJU PO TJUF
PSL
BJSUJHIUOFTTUFTU
4P UIBU TUSPOH XJOE XJMM OPU CMPX BHBJOTU UIF PVUEPPS IFBU FYDIBOHFS EJSFDUMZ 3FHBSEJOH PVUMJOF PG B TOPX IPPE
0WFS NN
HFSBOU QJQJOH XPSL
ZPV SFGFS UP PVS UFDIOJDBM NBOVBM
JSDVJU
XIJDIDBODBVTF 8JOE EJSFDUJPO
F 3&'3*(&3"/51*1*/(803,
PMMFS PS UIF VTF PG OPO
3FTUSJDUJPOT PO VOJU JOTUBMMBUJPO BOE VTF
VOFYQFDUFETUBSUPGGBO ● $IFDL UIF GPMMPXJOH QPJOUT JO MJHIU PG UIF JOEPPS VOJU TQFDJmDBUJPOT BOE UIF JOTUBMMBUJPO TJUF 4JOHMFUZQF *OEPPSVOJU
● 0CTFSWF UIF GPMMPXJOH SFTUSJDUJPOT PO VOJU JOTUBMMBUJPO BOE VTF *NQSPQFS JOTUBMMBUJPO DBO SFTVMU JO B DPNQSFTTPS GBJMVSF PS QFSGPSNBODF EFHSBEBUJPO
.BSLTBQQFBSUJOHJOUIFESBXJOH
XOPQFSBUJPO 0OFXBZQJQFMFOHUIEJGGFSFODFGSPNUIFmSTUCSBODIJOHQPJOUUPUIFJOEPPSVOJU N ≧N )
NBZ JODVS GSPTU CJUF PS 3FTUSJDUJPOT
%JNFOTJPOBM 8UXJOUZQF
.PEFMGPSPVUEPPSVOJUT 4JOHMFUZQF 5XJOUZQF 5SJQMFUZQF" 5SJQMFUZQF#
VSZEVFUPBOPNBMPVTMZ SFTUSJDUJPOT
φ ≦N -
7 -JRVJE1JQJOH -+-
-+-
-+- -+-
0VUEPPSVOJU
φ -+- -+-B+-, -+-B+-
0OFXBZQJQFMFOHUIPGSFGSJHFSBOUQJQJOH ≦N -
φPSφ -+- -+-C+-, -+-C+-
I DBO DBVTF CVSTU BOE 7ï (BTQJQJOH -+-
-+-B+-
-+-B+-
UZQF#
1SPIJCJUBUJPOPGUIFVTF
7 φ ≦N 5XJOUZQF
φ ≦N *OEPPSVOJU
7 -JRVJE1JQJOH -+-
5IFVOJUPGXIJDIFMFWBUJPOEJGGFSFODFGSPNUIFPVUEPPSVOJUJTUIFMBSHFTU
φ
BQNFOU
CVSOPSFMFDUSJD .BJOQJQFMFOHUI ≦N − - - -
7ï (BTQJQJOH φPSφ
1SPIJCJUBUJPOPGUIFVTF
7 φ ≦N *OEPPSVOJU I
0OFXBZQJQFMFOHUICFUXFFOUIFmSTUCSBODIJOH 7 − -B
QPJOUGSPNUPUIFTFDPOECSBODIJOHQPJOU ≦N − − −
7 -B 1SPIJCJUBUJPOPGUIFVTF
)
QBJS 0OFXBZQJQFMFOHUIBGUFSUIFmSTUCSBODIJOH 7 -
-
- -
-B+L, -+-B+- -
QPJOU ≦N − − -C+-, -C+- -
7 -
-B+-
-+-B+-
UZQF#
1SPIJCJUBUJPOPGUIFVTF
0OFXBZQJQFMFOHUIBGUFSUIFmSTUCSBODIJOH ≦N − − − −
QPJOUBOETFDPOECSBODIJOHQPJOU 7 -B+-, -B+-
−
- SJTFS
5XJOUZQF ≦N
− 0VUEPPSVOJU
≦N |-−-|
|-−-|
|-−-|
7 −
5SJQMFUZQF ≦N − -− -B+-
-− -B+-
5SJQMFUZQF
0OFXBZQJQFMFOHUIEJGGFSFODFGSPNUIFmSTU − |-−-|
CSBODIJOHQPJOUUPUIFJOEPPSVOJU 7 ≦N |-− -B+-
|
|-− -B+-
|
|-−-|
UZQF#
1SPIJCJUBUJPOPGUIFVTF 5ZQF"
|-−-|
|-−-|
8UXJOUZQF 77 ≦N − − | -+-B
− -+-C
|
| -+-B
− -+-C
| *OEPPSVOJU
| -+-B
− -+-C
|
| -+-B
− -+-C
|
5IFVOJUPGXIJDIFMFWBUJPOEJGGFSFODFGSPNUIFPVUEPPSVOJUJTUIFMBSHFTU
0OFXBZQJQFMFOHUIEJGGFSFODFGSPNUIF
TFDPOECSBODIJOHQPJOUUPUIFJOEPPSVOJU 7 ≦N − − − |-−-| |-−-|, |-−-|
*OEPPSVOJU I
5PUBMQJQFMFOHUIBGUFSUIFTFDPOECSBODIJOHQPJOU ≦N − − − − -+-, -+- I
*OEPPSVOJU
&MFWBUJPOEJGGFSFODFCFUXFFOJOEPPSBOEPVUEPPS 8IFOUIFPVUEPPSVOJUJTQPTJUJPOFEIJHIFS
≦N I
) ) ) ) )
VOJUT 8IFOUIFPVUEPPSVOJUJTQPTJUJPOFEMPXFS
≦N -
)
&MFWBUJPOEJGGFSFODFCFUXFFOJOEPPSVOJUT ≦N − I I
I
I I
I
I I
I
I
I
I
I -
● 'PSNPEFM7
BMXBZTVTFφNNMJRVJEQJQFT
XIFOUIFMFOHUIPGUIFNBJOi-wFYDFFETN*GφNNQJQFTBSFVTFEJOBOJOTUBMMBUJPOIBWJOHPWFSNQJQJOH
UIFZDBODBVTF -
$"65*0/ QFSGPSNBODFEFHSBEBUJPOBOEPSXBUFSMFBLTGSPNBOJOEPPSVOJU
● 5IFVTFSFTUSJDUJPOTBQQFBSJOHJOUIFUBCMFBCPWFBSFBQQMJDBCMFUPUIFTUBOEBSEQJQFTJ[FDPNCJOBUJPOTTIPXOJOUIFUBCMFCFMPX8IFSFBOFYJTUJOHQJQFTZTUFNJTVUJMJ[FE
EJGGFSFOUPOFXBZQJQFMFOHUI
- SJTFS
SFTUSJDUJPOTTIPVMEBQQMZEFQFOEJOHPOJUTQJQFTJ[F'PSNPSFJOGPSNBUJPO
TFFi65*-*;"5*0/0'&9*45*/(1*1*/(w
● 8JUIUIFUSJQMFQJQFDPOOFDUJPO
UIFXBZPGVTFJTEJGGFSFOUXIFOUIFEJGGFSFODFPGPOFXBZQJQFMFOHUIBGUFSUIFmSTUCSBODIJOHQPJOUJTNUPN'PSEFUBJMT
SFGFSUPUIFBCPWFUBCMFBOESJHIUmHVSF
0VUEPPSVOJU
/PUF
*OTUBMMUIFJOEPPSVOJUTTPUIBU--CFDPNFTUIFMPOHFTUPOFXBZQJQF
,FFQUIFQJQFMFOHUIEJGGFSFODFCFUXFFO-BOE -B-
PS -B-
XJUIJON
5SJQMFUZQF
-
/PUF
$POOFDUUIFVOJUUIBUJTUIFNBYJNVNDBQBDJUZXJUI-
5ZQF#
%FUFSNJOBUJPO PG QJQF TJ[F
231 -
*OEPPSVOJU
● %FUFSNJOF SFGSJHFSBOU QJQF TJ[F QVSTVBOU UP UIF GPMMPXJOH HVJEFMJOFT CBTFE PO UIF JOEPPS VOJU TQFDJmDBUJPOT 5IFVOJUPGXIJDIFMFWBUJPOEJGGFSFODFGSPNUIFPVUEPPSVOJUJTUIFMBSHFTU
0VUEPPSVOJU
3FGSJHFSBOUQJQJOH CSBODIQJQF-
-
-
φ φ
*OUIFDBTFPGBUSJQMFUZQF" *OEPPSVOJUDPOOFDUFE φ φ − − −
$BQBDJUZPGJOEPPSVOJU .PEFM7×
.PEFM7"× 8UXJOUZQF
FCVSOJOKVSZPSGSPTUJOKVSZ #SBODIJOHQJQFTFU %*48# %*48# %*48# %*48#
*OEPPSVOJU
3FGSJHFSBOUQJQJOH CSBODIQJQF-B
-
φ φ φ φ φ φ φ φ 5IFVOJUPGXIJDIFMFWBUJPOEJGGFSFODFGSPNUIFPVUEPPSVOJUJTUIFMBSHFTU
'10 • PAC-DB-142
- SJTFS
● " SJTFS QJQF NVTU CF B QBSU PG UIF NBJO " CSBODIJOH QJQF TFU TIPVME CF JOTUBMMFE IPSJ[POUBMMZ BU B QPJOU BT DMPTF UP BO JOEPPS VOJU BT QPTTJCMF
FGSJHFSBOU DIBSHJOH " CSBODIJOH QBSU NVTU CF ESFTTFE XJUI B IFBUJOTVMBUJPO NBUFSJBM TVQQMJFE BT BO BDDFTTPSZ 0VUEPPSVOJU
● 'PSUIFEFUBJMTPGJOTUBMMBUJPOXPSLSFRVJSFEBUBOEOFBSBCSBODIJOHBSFB
TFFUIFJOTUBMMBUJPONBOVBMTVQQMJFEXJUIZPVSCSBODIJOHQJQFTFU
"CPVUCSB[JOH
φ *%
φ *%
+PJOUQJQF% NBUFSJBM
BOEmMMUIFQJQFXJUIOJUSPHFOHBT 4UBUJPOWBMWF
φ *%
.1B
POT
5BQJOH </> )BOE
/JUSPHFO
/JUSPHFO 3FMJFGWBMWF
'JFMEQJQJOH φ *%
+PJOUQJQF$ φ *%
+PJOUQJQF$ φ *%
HBT
0OMZVTFOJUSPHFO #SB[JOH
φ 0%
#SBODIJOHQJQFTFU #SBODIJOHQJQFTFU #SBODIJOHQJQFTFU
HBT /
%*48#
%*45#
%*48#
%*45#
%*48#
%*45#
)FBWZ
3FGSJHFSBOUQJQFXBMMUIJDLOFTTBOENBUFSJBM 1JQFEJBNFUFS<NN> /05&
● 4FMFDU SFGSJHFSBOU QJQFT PG UIF UBCMF TIPXO PO UIF SJHIU XBMM UIJDLOFTT BOE NBUFSJBM BT TQFDJmFE GPS FBDI QJQF .JOJNVNQJQFXBMMUIJDLOFTT<NN> ● 4FMFDUQJQFTIBWJOHBXBMMUIJDLOFTTMBSHFS
TJ[F 1JQFNBUFSJBM 0UZQFQJQF 0UZQFQJQF 0UZQFQJQF 0UZQFQJQF )UZQFQJQF )UZQFQJQF )UZQFQJQF UIBOUIFTQFDJmFENJOJNVNQJQFUIJDLOFTT
● 5IJT VOJU VTFT 3" "MXBZT VTF ) QJQFT IBWJOH B NN PS UIJDLFS XBMM GPS φ PS MBSHFS QJQFT
CFDBVTF0UZQFQJQFTEPOPUNFFUUIFQSFTTVSFSFTJTUBODFSFRVJSFNFOU 1IPTQIPSVTEFPYJEJ[FETFBNMFTTDPQQFSQJQF$5
+*4)
0VUEPPSVOJU
3FGSJHFSBOUQJQJOH CSBODIQJQF-
-
-
φ φ
*OUIFDBTFPGBUSJQMFUZQF" *OEPPSVOJUDPOOFDUFE φ φ − − −
$BQBDJUZPGJOEPPSVOJU .PEFM7×
.PEFM7"× 8UXJOUZQF
CVSOJOKVSZPSGSPTUJOKVSZ #SBODIJOHQJQFTFU %*48# %*48# %*48# %*48#
*OEPPSVOJU
3FGSJHFSBOUQJQJOH CSBODIQJQF-B
-
φ φ φ φ φ φ φ φ 5IFVOJUPGXIJDIFMFWBUJPOEJGGFSFODFGSPNUIFPVUEPPSVOJUJTUIFMBSHFTU
● " SJTFS QJQF NVTU CF B QBSU PG UIF NBJO " CSBODIJOH QJQF TFU TIPVME CF JOTUBMMFE IPSJ[POUBMMZ BU B QPJOU BT DMPTF UP BO JOEPPS VOJU BT QPTTJCMF
FGSJHFSBOU DIBSHJOH " CSBODIJOH QBSU NVTU CF ESFTTFE XJUI B IFBUJOTVMBUJPO NBUFSJBM TVQQMJFE BT BO BDDFTTPSZ 0VUEPPSVOJU
● 'PSUIFEFUBJMTPGJOTUBMMBUJPOXPSLSFRVJSFEBUBOEOFBSBCSBODIJOHBSFB
TFFUIFJOTUBMMBUJPONBOVBMTVQQMJFEXJUIZPVSCSBODIJOHQJQFTFU
"CPVUCSB[JOH
φ *%
φ *%
+PJOUQJQF% NBUFSJBM
BOEmMMUIFQJQFXJUIOJUSPHFOHBT 4UBUJPOWBMWF
φ *%
.1B
POT
5BQJOH </> )BOE
/JUSPHFO
/JUSPHFO 3FMJFGWBMWF
'JFMEQJQJOH φ *%
+PJOUQJQF$ φ *%
+PJOUQJQF$ φ *%
HBT
0OMZVTFOJUSPHFO #SB[JOH
φ 0%
#SBODIJOHQJQFTFU #SBODIJOHQJQFTFU #SBODIJOHQJQFTFU
HBT /
%*48#
%*45#
%*48#
%*45#
%*48#
%*45#
)FBWZ
3FGSJHFSBOUQJQFXBMMUIJDLOFTTBOENBUFSJBM 1JQFEJBNFUFS<NN> /05&
● 4FMFDU SFGSJHFSBOU QJQFT PG UIF UBCMF TIPXO PO UIF SJHIU XBMM UIJDLOFTT BOE NBUFSJBM BT TQFDJmFE GPS FBDI QJQF .JOJNVNQJQFXBMMUIJDLOFTT<NN> ● 4FMFDUQJQFTIBWJOHBXBMMUIJDLOFTTMBSHFS
TJ[F 1JQFNBUFSJBM 0UZQFQJQF 0UZQFQJQF 0UZQFQJQF 0UZQFQJQF )UZQFQJQF )UZQFQJQF )UZQFQJQF UIBOUIFTQFDJmFENJOJNVNQJQFUIJDLOFTT
● 5IJT VOJU VTFT 3" "MXBZT VTF ) QJQFT IBWJOH B NN PS UIJDLFS XBMM GPS φ PS MBSHFS QJQFT
CFDBVTF0UZQFQJQFTEPOPUNFFUUIFQSFTTVSFSFTJTUBODFSFRVJSFNFOU 1IPTQIPSVTEFPYJEJ[FETFBNMFTTDPQQFSQJQF$5
+*4)
-
232 -
'10 • PAC-DB-142
'10 • PAC-DB-142
'10 • PAC-DB-142
'10 • PAC-DB-142
PSB012D917C F
PSB012D917C F
(5) Method for connecting the accessory pipe (Models FDC200,250 only)
Be sure to use the accessory pipe to connect the operation valve on the gas
A B
side with the field pipe.
① Referring to Table ① and Table ②, prepare the straight pipe and the elbow in the field,
ID22.22
which are used in the construction examples A ~ D applicable to the connecting direction.
② Firstly, use the accessory pipe to assemble the connecting pipe assembly outside the
outdoor unit.
As shown in the figures of construction examples A ~ D applicable to the connecting
direction(chain double dashed line), braze the accessory pipe and the parts prepared OD25.4
in the above ①. ID22.22 1 pc
1 pc
③ After assembly of the connecting pipe, connect it to the service valve on the
gas side inside the outdoor unit.
Tighten the flare nut with appropriate torque. Appropriate torque
④ After connection of the connecting pipe assembly to the service valve on the
φ19.05 100~120N·m
gas side, braze the connecting pipe assembly and the field pipe.
(47)
1 Accessory pipe A 1 Accessories
2 Straight pipe ① 1 Procured in the field
3 Straight pipe ② 1 or 0 Procured in the field (Not required for downward direction) Inner face of
the base
4 Elbow 1 or 0 Procured in the field (Not required for downward direction)
Inner face of
Position for the
the base
accessory pipe
Table ② Length of the straight pipe (prepared in the field) (44)
Pipe size Downward Forward Rightward Backward
Straight
pipe① φ22.22×t1.6 above 415mm 185~235mm 185~235mm 185~235mm
Straight
pipe②
φ22.22×t1.6 - above 125mm above 125mm above 405mm
● Be sure to use pipes of 1/2H material, and wall thickness above 1mm. (Pressure resistance of O-type pipe is not enough)
● Switch ON SW5-1 on the control PCB, if O-type pipe must be used and bent with the bender.
During heating operation, the high-pressure protection may be actuated under the condition lower than the normal pressure,
and the heating capacity may decrease.
About brazing
Be sure to braze while supplying nitrogen gas.
If no nitrogen gas is supplied, a large amount of impurity
(oxidized fi lm) will be generated, which may clog the capillary
tube and the expansion valve, resulting in fatal malfunction.
Accessory pipe A
- 236 -
Straight pipe ①
(Procured in the field
Straight pipe ① 185~235mm)
(Procured in the field
above 415mm)
Straight pipe ②
(Procured in the field
above 125mm)
Accessory pipe A
Accessory pipe A
Straight pipe ①
Straight pipe ① (Procured in the field
(Procured in the field 185~235mm)
185~235mm)
Straight pipe ②
Straight pipe ② (Procured in the field
(Procured in the field above 405mm)
above 125mm)
- 237 -
- 238 -
- 239 -
- 240 -
- 241 -
- 242 -
2-1 DIS-WA1
INSTRUCTIONS FOR BRANCHING PIPE SET INSTALLATION FOR TWIN/TRIPLE/ W-TWIN CONFIGURATION SYSTEMS
1.10.5 Instructions for branching pipe set (DIS-WA1, WB1, TA1, TB1)
Supported combinati
Outdoor unit model Indoor u
WARNING / CAUTION
● This set is for R410A refrigerant.
2HP+
● Select a branching pipe set correctly rated for the combined total capacity of connected indoor units and install it according to this manual.
An improperly installed branching pipe set can cause degraded performance or an abnormal unit stop.
● Provide good heat insulation to the pipes by following instructions contained in this manual.
Improper heat insulation can result in degraded performance or a water leak accident from condensation.
4HP
● Please make sure that only parts supplied as accessories or the manufacturer's approved parts are used in installing the unit, because a leak of refrigerant can
result in a lack-of-oxygen accident, if it reaches a concentration beyond the tolerable limit.
This manual explains how to use a branching pipe set that is indispensable in connecting pipes for a twin/triple/W-twin configuration installation (system). For the 1.5HP+
details of piping work, unit installation work and electrical installation work, please refer to the installation manuals and installation guides supplied with your outdoor
and indoor units.
Three-way branching
In connecting an indoor unit of which capacity is 1.5HP, 2HP or 2.5HP, always use a φ9.52 liquid pipe to connect to the branching
CAUTION
pipe (branching pipe – indoor unit).
In connecting to an indoor unit (liquid pipe side:φ6.35), use the different diameter pipe joint A supplied with the set and follow the
procedure set out below.
Flarenutφ6.35
Brazing
Liquid connecting pipe (φ9.52) Joint A To indoor unit liquid pipe connection port
- 243 -
2-1 DIS-WA1 2-2 DIS-WB1
ID9.52
Gas branching pipe
ID15.88
ID12.7
3HP+5HP ② ②
12D865 F 3HP 1.5HP+1.5HP
Joint B 8HP ID9.52 ID25.4
①
② ①
③ ③
① 4HP+4HP Joint C ID9.52
ID15.88 ID15.88
③
Joint B ID9.52 ID15.88
2HP+2HP Flare joint ② ②
ID12.7 ①
(φ6.35) ①
10HP 5HP+5HP ID12.7 ID25.4
Joint A
A ③ ③
Connecting pipe ID12.7 ID9.52 ID15.88
4HP (φ9.52)
of refrigerant can Joint B
ID12.7
① ② ② Joint B
ID9.52 ① ②
③ ID15.88 ①
ID15.88 Applicable to the difference in length of pipes after the branch being less than 3 m
(system). For the 1.5HP+2.5HP
CAUTION ③ ③
2-3 DIS-TA1
Joint B * Connection is not allowed when the difference in length of pipes is larger than 3 m.
with your outdoor Reference ID15.88
ID12.7 Supported combinations
Joint A Outdoor unit model Indoor unit model Liquid branching pipe Gas branching pipe
Flare joint A
(φ6.35) ID12.7
Connecting pipe Joint A
Joint B ID15.88 (φ9.52)
② ② ID12.7
elow. ① ① ②
ID15.88 ID15.88 ③ Flare
from indoor units to 6HP 2HP+2HP+2HP ID9.52 joint
2.5HP+2.5HP ③ ③ ① ④ (φ6.35) ① ② ③ ④
Joint B ID15.88 ID15.88
Joint A
ID12.7
CAUTION Reference
Flare joint
t insulation material 5HP (φ6.35) ID12.7
Joint A
Joint B
②
2HP+3HP
Connecting pipe
(φ9.52) ① 2-4 DIS-TB1 Applicable to the difference in length of pipes after the branch being less than 3 m
ID15.88 * Connection is not allowed when the difference in length of pipes is larger than 3 m.
②
①
ID9.52 ③ Supported combinations
Liquid branching pipe Gas branching pipe
③ CAUTION ID15.88 Outdoor unit model Indoor unit model
ID9.52 Reference
h for liquid and gas ID9.52 ID15.88
ID9.52 ID15.88 ②
② ② 8HP 3HP+3HP+3HP ① ③
① ① ID9.52 ① ② ③ ④
ID9.52 ID15.88 ④ ID25.4
3HP+3HP
③ ③
ID9.52 ID15.88
Flare joint OLD Model list
6HP (φ6.35) ID12.7
Joint A model name
h for liquid and gas Joint B
Connecting pipe
② FDTA251R
2HP+4HP (φ9.52) ① FDENA251R
② ID15.88
① FDKNA251R
ID9.52 ③
③ CAUTION ID15.88
FDURA251R
ID9.52 Reference FDUMA252R
h for liquid and gas Note When connect the indoor unit of an old model that is shown in the model list,
use the joint supplied with the branch piping set like A
2-5. Triple type for same model/same capacity or different model/same capacity
When the difference in length of pipes after the branch is longer than 3 m and shorter than 10 m
Outdoor unit model Indoor unit model Branching pipe Branching pipe set type Liquid branching pipe Gas branching pipe
h for liquid and gas
Flare joint
(φ6.35)
and OD, outer diameter. ID12.7
Outdoor unit Joint A
Indoor unit Joint B
Connecting pipe ②
a (φ9.52) ①
② ID15.88
a ①
ID9.52 ③
③ CAUTION ID15.88
b ID9.52 Reference
Flare joint
6HP 2HP+2HP+2HP DIS-WA1 (φ6.35)
Floor surface ID12.7
Joint A
t Joint B
Connecting pipe ②
(φ9.52)
①
① ② ID15.88
ID9.52
b ③ ③
CAUTION Joint B
Reference
Floor surface ID12.7
Joint A
Flare joint
(φ6.35)
- 244 -
2-6. Triple type for same model/different capacity or different model/different capacity
Applicable to the difference in length of pipes after the branch being less than 3 m
* Connection is not allowed when the difference in length of pipes is larger than 3 m.
Outdoor unit Outdoor unit model Indoor unit model Branching pipe Branching pipe set type Liquid branching pipe Gas branching pipe
Indoor unit
ID9.52 ID15.88
A ② ②
① ①
a a DIS-WB1 ID12.7 ID25.4
B
b ③ ③
ID9.52 ID15.88
10HP 2.5HP+2.5HP+5HP
C Flare joint (φ6.35) ID12.7 A
Connecting pipe Joint A ID15.88
(φ9.52) Joint B
② ②
② ① ①
b DIS-WA1 ID9.52 ID15.88
① ③ ③
ID15.88
CAUTION Joint B ③
Reference Joint A
Connecting position Flare joint (φ6.35) ID12.7 ID15.88
Note When connect the indoor unit of an old model that is shown in the model list, use the joint supplied with the branch piping set like A.
2-7. Double
W-twinTwin
typetype
Pipes should be connected as follows for a Double
W-twin Twin installation
installation (4 connected
(4 connected indoor
indoor units.
units. TheThecapacity
capacityofofananoutdoor
outdoorunit
unit available
available for this configuration
configuration
is either 8HP or 10HP only):
Branching pipe Branching pipe set type Outdoor unit model Liquid branching pipe Gas branching pipe
Outdoor unit capacity Indoor unit capacity
ID9.52
8HP 2HP×4 units ②
①
8HP ID9.52
10HP 2.5HP×4 units
Joint C ③ ID15.88
ID9.52 ②
①
a DIS-WB1 ID25.4
ID9.52
③
②
① ID15.88
10HP ID12.7
Outdoor unit Indoor unit
b ③
ID9.52
a
ID12.7
b Joint B
②
①
8HP Flare joint (φ6.35) ID15.88
Joint A ③
Connecting pipe
(φ9.52) Joint B
② ID12.7
b DIS-WA1 ID9.52
① ③ A ID12.7
CAUTION Joint B
Reference ID15.88
Joint A ② ②
①
10HP Flare joint (φ6.35) ① ID15.88
ID15.88 ③
③ Joint B
ID15.88 ID12.7
Note When connect the indoor unit of an old model that is shown in the model list, use the joint supplied with the branch piping set like A.
2. Apply a heat insulation material (to be procured locally) to the joint between the
branching pipe’s heat insulation and the heat insulation material covering
1. It has an adhesive layer on the entire inner face. the installation’s piping as described above and wrap a tape over the gap
Remove a separator and wrap it around the branching pipe. shown as a hatched (///) area to complete dressing of the piping.
- 245 -
2. V MULTI SYSTEM
CONTENTS
Series code
Product capacity
Model name FDT : Ceiling cassette-4way type
FDEN : Ceiling suspended type
- 246 -
FDC71VN 40+40
FDC100VN
Twin 50+50
FDC100VS
DIS-WA1
FDC125VN 60+60
FDC125VS 50+71
Twin 71+71
FDC140VN
FDC140VS
Triple 50+50+50 DIS-TA1
100+100
Twin DIS-WB1
71+125
FDC200VS
Triple 71+71+71 DIS-TB1
DIS-WA1 x 2set
Double Twin 50+50+50+50
DIS-WB1 x 1set
60+60+125
Triple DIS-TB1
FDC250VS
71+71+100
- 247 -
2.2 SPECIFICATIONS
(1) Indoor units
(a) Ceiling Cassette-4way type (FDT) Adapted to RoHS directive
Model
FDT40VD
PJF000Z188 A
- 248 -
Model
FDT50VD
PJF000Z188 A
- 249 -
Model
FDT60VD
PJF000Z188 A
- 250 -
Model
FDT71VD
PJF000Z188 A
- 251 -
Model
FDT100VD
PJF000Z188 A
- 252 -
Model
FDT125VD
PJF000Z188 A
- 253 -
Model
FDEN40VD
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 4.0 4.5
Power factor % 97 / 98
Sound Pressure Level dB(A) P-Hi : 46 Hi : 39 Me : 38 Lo : 37
Exterior dimensions
mm 210 × 1,070 × 690
Height x Width x Depth
Exterior appearance Plaster White
(Munsell color) (6.8Y8.9/0.2) near equivalent
Net weight kg 28
Heat exchanger Louver fin & inner grooved tubing
Air handling equipment
Centrifugal fan × 2
Fan type & Q'ty
Motor <Starting method> W 25 < Direct line start >
Air flow (Standard) CMM P-Hi : 13 Hi : 11 Me : 9 Lo : 7
Available static pressure Pa 0
Outdoor air intake Not possible
Air filter, Q'ty Pocket plastic net × 2 (Washable)
Shock & vibration absorber Rubber sleeve (for fan motor)
Insulation (noise & heat) Polyurethane form
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics
Internal thermostat for fan motor
Safety equipment
Frost protection thermostat
Installation data Liquid line :φ6.35 (1/4")
mm
Refrigerant piping size Gas line :φ12.7 (1/2")
Connecting method Flare piping
Drain pump —
Drain Hose Connectable with VP20
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 254 -
Model
FDEN50VD
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 5.0 5.4
Sound Pressure Level dB(A) P-Hi : 46 Hi : 39 Me : 38 Lo : 37
Exterior dimensions
mm 210 × 1,070 × 690
Height x Width x Depth
Exterior appearance Plaster White
(Munsell color) (6.8Y8.9/0.2) near equivalent
Net weight kg 28
Heat exchanger Louver fin & inner grooved tubing
Refrigerant control —
Air handling equipment
Centrifugal fan × 2
Fan type & Q'ty
Motor <Starting method> W 25 < Direct line start >
Air flow (Standard) CMM P-Hi : 13 Hi : 11 Me : 9 Lo : 7
Available static pressure Pa 0
Outdoor air intake Not possible
Air filter, Q'ty Pocket plastic net × 2 (Washable)
Shock & vibration absorber Rubber sleeve (for fan motor)
Insulation (noise & heat) Polyurethane form
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics
Internal thermostat for fan motor
Safety equipment
Frost protection thermostat
Installation data Liquid line :φ6.35 (1/4")
mm
Refrigerant piping size Gas line :φ12.7 (1/2")
Connecting method Flare piping
Drain pump —
Drain Hose Connectable with VP20
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 255 -
Model
FDEN60VD
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 5.6 6.7
Sound Pressure Level dB(A) P-Hi : 50 Hi : 41 Me : 39 Lo : 38
Exterior dimensions
mm 210 × 1,320 × 690
Height x Width x Depth
Exterior appearance Plaster White
(Munsell color) (6.8Y8.9/0.2) near equivalent
Net weight kg 37
Heat exchanger Louver fin & inner grooved tubing
Air handling equipment
Centrifugal fan × 4
Fan type & Q'ty
Motor <Starting method> W 20 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 22 Hi : 18 Me : 14 Lo : 12
Available static pressure Pa 0
Outdoor air intake Not possible
Air filter, Q'ty Pocket plastic net × 2 (Washable)
Shock & vibration absorber Rubber sleeve (for fan motor)
Insulation (noise & heat) Polyurethane form
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics
Internal thermostat for fan motor
Safety equipment
Frost protection thermostat
Installation data Liquid line :φ6.35 (1/4")
mm
Refrigerant piping size Gas line :φ12.7 (1/2")
Connecting method Flare piping
Drain pump —
Drain Hose Connectable with VP20
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 256 -
Model
FDEN71VD
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 7.1 8.0
Sound Pressure Level dB(A) P-Hi : 50 Hi : 41 Me : 39 Lo : 38
Exterior dimensions
mm 210 × 1,320 × 690
Height x Width x Depth
Exterior appearance Plaster White
(Munsell color) (6.8Y8.9/0.2) near equivalent
Net weight kg 37
Heat exchanger Louver fin & inner grooved tubing
Air handling equipment
Centrifugal fan × 4
Fan type & Q'ty
Motor <Starting method> W 20 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 22 Hi : 18 Me : 14 Lo : 12
Available static pressure Pa 0
Outdoor air intake Not possible
Air filter, Q'ty Pocket plastic net × 2 (Washable)
Shock & vibration absorber Rubber sleeve (for fan motor)
Insulation (noise & heat) Polyurethane form
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics
Internal thermostat for fan motor
Safety equipment
Frost protection thermostat
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ15.88 (5/8")
Connecting method Flare piping
Drain pump —
Drain Hose Connectable with VP20
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 257 -
Model
FDEN100VD
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 11.2
Sound Pressure Level dB(A) P-Hi : 46 Hi : 44 Me : 41 Lo : 39
Exterior dimensions
mm 250 × 1,620 × 690
Height x Width x Depth
Exterior appearance Plaster White
(Munsell color) (6.8Y8.9/0.2) near equivalent
Net weight kg 49
Heat exchanger Louver fin & inner grooved tubing
Air handling equipment
Centrifugal fan × 4
Fan type & Q'ty
Motor <Starting method> W 30 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 28 Hi : 26 Me : 23 Lo : 21
Available static pressure Pa 0
Outdoor air intake Not possible
Air filter, Q'ty Pocket plastic net × 2 (Washable)
Shock & vibration absorber Rubber sleeve (for fan motor)
Insulation (noise & heat) Polyurethane form
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics
Internal thermostat for fan motor
Safety equipment
Frost protection thermostat
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ15.88 (5/8")
Connecting method Flare piping
Drain pump —
Drain Hose Connectable with VP20
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 258 -
Model
FDEN125VD
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 14.0
Sound Pressure Level dB(A) P-Hi : 50 Hi : 46 Me : 44 Lo : 43
Exterior dimensions
mm 250 × 1,620 × 690
Height x Width x Depth
Exterior appearance Plaster White
(Munsell color) (6.8Y8.9/0.2) near equivalent
Net weight kg 49
Heat exchanger Louver fin & inner grooved tubing
Refrigerant control —
Air handling equipment
Centrifugal fan × 4
Fan type & Q'ty
Motor <Starting method> W 40 × 2 < Direct line start >
Air flow (Standard) CMM P-Hi : 32 Hi : 29 Me : 26 Lo : 23
Available static pressure Pa 0
Outdoor air intake Not possible
Air filter, Q'ty Pocket plastic net × 2 (Washable)
Shock & vibration absorber Rubber sleeve (for fan motor)
Insulation (noise & heat) Polyurethane form
Remote controller wired : RC-E4 (option) wireless : RCN-E1R (option)
Room temperature control Thermostat by electronics
Internal thermostat for fan motor
Safety equipment
Frost protection thermostat
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ15.88 (5/8")
Connecting method Flare piping
Drain pump —
Drain Hose Connectable with VP20
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit, Drain hose
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
PFA003Z900 A
- 259 -
Model
FDC71VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 7.1 [ 3.2 (Min.)~8.0 (Max.)] 8.0 [ 3.6 (Min.)~9.0 (Max.)]
Sound Pressure Level dB(A) 48
Exterior dimensions
mm 750 × 968 × 340
Height x Width x Depth
Exterior appearance Stucco White
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 60
Refrigerant equipment
2YC45DXD × 1
Compressor type & Q'ty
Starting method Direct line start
Refrigerant oil 0.65 FVC50K
Heat exchanger Straight fin & inner grooved tubing
Refrigerant control Electronic expansion valve
Air handling equipment
Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 86 < Direct line start >
Air flow (Standard) CMM Cooling : 60 , Heating : 50
Shock & vibration absorber Rubber sleeve (for Compressor )
Electric heater W 20 (Crank case heater)
Internal thermostat for fan motor
Safety equipment
Abnormal discharge temperature protection.
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ15.88 (5/8")
Connecting method Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 2.95kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories —
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
PJF000Z188 A
- 260 -
Model
FDC100VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Sound Pressure Level dB(A) 49
Exterior dimensions
mm 845×970×370
Height x Width x Depth
Exterior appearance Stucco White
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 81
Refrigerant equipment
RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method Direct line start
Refrigerant oil 0.9 M-MA68
Heat exchanger Straight fin & inner grooved tubing
Refrigerant control Electronic expansion valve
Air handling equipment
Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 86 < Direct line start >
Air flow (Standard) CMM Cooling : 75, Heating : 73
Shock & vibration absorber Rubber sleeve (for Compressor )
Electric heater W 20 (Crank case heater)
Internal thermostat for fan motor
Safety equipment
Abnormal discharge temperature protection.
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ15.88 (5/8")
Connecting method Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
PJF000Z188 A
- 261 -
Model
FDC100VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 10.0 [ 4.0 (Min.)~11.2 (Max.)] 11.2 [ 4.0 (Min.)~12.5 (Max.)]
Sound Pressure Level dB(A) 49
Exterior dimensions
mm 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 83
Refrigerant equipment
RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method Direct line start
Refrigerant oil 0.9 M-MA68
Heat exchanger Straight fin & inner grooved tubing
Refrigerant control Electronic expansion valve
Air handling equipment
Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 86 < Direct line start >
Air flow (Standard) CMM Cooling : 75, Heating : 73
Shock & vibration absorber Rubber sleeve (for Compressor )
Electric heater W 20 (Crank case heater)
Internal thermostat for fan motor
Safety equipment
Abnormal discharge temperature protection.
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ15.88 (5/8")
Connecting method Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
PJF000Z188 A
- 262 -
Model
FDC125VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Sound Pressure Level dB(A) Cooling : 50 Heating : 51
Exterior dimensions
mm 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 81
Refrigerant equipment
RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method Direct line start
Refrigerant oil 0.9 M-MA68
Heat exchanger Straight fin & inner grooved tubing
Refrigerant control Electronic expansion valve
Air handling equipment
Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 86 < Direct line start >
Air flow (Standard) CMM Cooling : 75, Heating : 73
Shock & vibration absorber Rubber sleeve (for Compressor )
Electric heater W 20 (Crank case heater)
Internal thermostat for fan motor
Safety equipment
Abnormal discharge temperature protection.
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ15.88 (5/8")
Connecting method Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
PJF000Z188 A
- 263 -
Model
FDC125VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 12.5 [ 5.0 (Min.)~14.0 (Max.)] 14.0 [ 4.0 (Min.)~16.0 (Max.)]
Sound Pressure Level dB(A) Cooling : 50 Heating : 51
Exterior dimensions
mm 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 83
Refrigerant equipment
RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method Direct line start
Refrigerant oil 0.9 M-MA68
Heat exchanger Straight fin & inner grooved tubing
Refrigerant control Electronic expansion valve
Air handling equipment
Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 86 < Direct line start >
Air flow (Standard) CMM Cooling : 75, Heating : 73
Shock & vibration absorber Rubber sleeve (for Compressor )
Electric heater W 20 (Crank case heater)
Internal thermostat for fan motor
Safety equipment
Abnormal discharge temperature protection.
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ15.88 (5/8")
Connecting method Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
PJF000Z188 A
- 264 -
Model
FDC140VN
Item
Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Sound Pressure Level dB(A) 51
Exterior dimensions
mm 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 81
Refrigerant equipment
RMT5126MDE2 × 1
Compressor type & Q'ty
Starting method Direct line start
Refrigerant oil 0.9 M-MA68
Heat exchanger Straight fin & inner grooved tubing
Refrigerant control Electronic expansion valve
Air handling equipment
Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 86 < Direct line start >
Air flow (Standard) CMM Cooling : 75, Heating : 73
Shock & vibration absorber Rubber sleeve (for Compressor )
Electric heater W 20 (Crank case heater)
Internal thermostat for fan motor
Safety equipment
Abnormal discharge temperature protection.
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ15.88 (5/8")
Connecting method Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154 and 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
PJF000Z188 A
- 265 -
Model
FDC140VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.)~14.5 (Max.)] 16.0 [ 4.0 (Min.)~16.5 (Max.)]
Sound Pressure Level dB(A) 51
Exterior dimensions
mm 845 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 83
Refrigerant equipment
RMT5126MDE3 × 1
Compressor type & Q'ty
Starting method Direct line start
Refrigerant oil 0.9 M-MA68
Heat exchanger Straight fin & inner grooved tubing
Refrigerant control Electronic expansion valve
Air handling equipment
Propeller fan × 1
Fan type & Q'ty
Motor <Starting method> W 86 < Direct line start >
Air flow (Standard) CMM Cooling : 75, Heating : 73
Shock & vibration absorber Rubber sleeve (for Compressor )
Electric heater W 20 (Crank case heater)
Internal thermostat for fan motor
Safety equipment
Abnormal discharge temperature protection.
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ15.88 (5/8")
Connecting method Flare piping
Refrigerant line (one way) length Max.50m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154 and 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Drain Holes sizeφ20 x 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
PJF000Z188 A
- 266 -
Model
FDC200VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 20.0 [ 7.0 (Min.)~22.4 (Max.)] 22.4 [ 7.6 (Min.)~25.0 (Max.)]
Sound Pressure Level dB(A) 57
Exterior dimensions
mm 1,300 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 122
Refrigerant equipment
GTC5150ND70K × 1
Compressor type & Q'ty
Starting method Direct line start
Refrigerant oil 1.45 M-MA32R
Heat exchanger Straight fin & inner grooved tubing
Refrigerant control Electronic expansion valve
Air handling equipment
Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 86 × 2 < Direct line start >
Air flow (Standard) CMM Cooling : 150, Heating : 145
Shock & vibration absorber Rubber sleeve (for Compressor )
Electric heater W 33 (Crank case heater)
Internal thermostat for fan motor
Safety equipment
Abnormal discharge temperature protection.
Installation data Liquid line :φ9.52 (3/8")
mm
Refrigerant piping size Gas line :φ22.22 (7/8")
Connecting method Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154 and 155
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 5.4kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
PJF000Z188 A
- 267 -
Model
FDC250VS
Item
Power source 380-415V 3N~50Hz / 380V 3N~60Hz
Operation data Cooling Heating
Nominal capacity kW 25.0 [ 10.0 (Min.)~28.0 (Max.)] 28.0 [ 9.5 (Min.)~31.5 (Max.)]
Sound Pressure Level dB(A) Cooling : 57 Heating : 58
Exterior dimensions
mm 1,505 × 970 × 370
Height x Width x Depth
Exterior appearance Stucco White
(Munsell color) (4.2Y7.5/1.1) near equivalent
Net weight kg 140
Refrigerant equipment
GTC5150ND70K × 1
Compressor type & Q'ty
Starting method Direct line start
Refrigerant oil 1.45 M-MA32R
Heat exchanger Straight fin & inner grooved tubing
Refrigerant control Electronic expansion valve
Air handling equipment
Propeller fan × 2
Fan type & Q'ty
Motor <Starting method> W 86 × 2 < Direct line start >
Air flow (Standard) CMM Cooling : 150, Heating : 145
Shock & vibration absorber Rubber sleeve (for Compressor )
Electric heater W 33 (Crank case heater)
Internal thermostat for fan motor
Safety equipment
Abnormal discharge temperature protection.
Installation data Liquid line :φ12.7 (1/2")
mm
Refrigerant piping size Gas line :φ22.22 (7/8")
Connecting method Liquid : Flare / Gas : Brazing
Refrigerant line (one way) length Max.70m
Vertical height difference between Max.30m (Outdoor unit is higher) 1.See page 154
outdoor unit and indoor unit Max.15m (Outdoor unit is lower)
Refrigerant Quantity R410A 7.2kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain Holes size φ20 × 3pcs
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Connecting pipe, Edging
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
PJF000Z188 A
- 268 -
- 269 -
[Example]
(Conditions) Operation Voltage ········ Indoor unit: 220 V, 50 Hz
Outdoor unit: 220 V, 50 Hz
Operation mode ··········· Cooling and Heating
Unit······························· Outdoor unit: FDC140VN × 1 unit
Indoor unit: FDT71VD × 2 units
4.71 × 1000
(Cooling) × 100 .=. 99 %
21.0 × 220
4.60 × 1000
(Heating) × 100 .=. 99 %
20.1 × 220
2) 3 Phase models
a) Total power consumption
Total power consumption (kW) = Power consumption of outdoor unit + ¤ (Power consumption of indoor unit)
b) Total running current
Total running current (A) = Running current of outdoor unit + [¤ (Running current of indoor unit) × 1/3]
c) Total power factor
Total power factor (%) = [Total power consumption (W) / √3 × Total running current (A) × Power source] × 100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
- 270 -
[Example]
(Conditions) Operation Voltage ········ Indoor unit: 220 V, 50 Hz
Outdoor unit: 380 V, 50 Hz
Operation mode ··········· Cooling and Heating
Unit······························· Outdoor unit: FDC200VS × 1 unit
Indoor unit: FDT71VD × 1 unit, FDT125VD × 1 unit
[
(Cooling) 9.1 + (0.30 + 0.45) × )] =. 9.6 (A)
1 .
3
(Heating) 9.0 + [(0.30 + 0.45) × )] =. 9.5 (A)
1 .
3
6.58 × 1000
(Cooling) × 100 .=. 99 %
3 × 9.6 × 380
6.44 × 1000
(Heating) × 100 .=. 99 %
3 × 9.5 × 380
- 271 -
3. OPTION PARTS
CONTENTS
- 273 -
WARNING
Fasten the wiring to the terminal securely and hold the cable securely so as not to apply <To change the settings>
unexpected stress on the terminal. 2 Remove the cover by unscrewing two screws from the back of receiver.
Loose connection or hold will cause abnormal heat generation or fire. 3 Change the setting by the switch on PCB.
Make sure the power supply is turned off when electric wiring work.
Otherwise, electric shock, malfunction and improper running may occur.
Default settings
CAUTION Screws
DO NOT install the wireless kit at the following places in order to avoid malfunction.
(1) Places exposed to direct sunlight (8) Places where the receiver is influenced by
(2) Places near heat devices the fluorescent lamp (especially inverter
(3) High humidity places type) or sunlight.
(4) Hot surface or cold surface enough to (9) Places where the receiver is affected by
generate condensation infrared rays of any other communication
(5) Places exposed to oil mist or steam directly devices
(6) Uneven surface (10)Places where some object may obstruct the
(7) Places affected by the direct airflow of the communication with the remote controller Receiver Backside Cover Backside
AC unit.
Note
When the batteries are removed, the setting will return
to the default setting.
Accessories Please make sure to reset it when the batteries are
replaced.
Please make sure that you have all of the following accessories.
Caution
Receiver Remote controller Instruct the customer to set the mentioned above when
holder replacing the batteries.
(How to set is also mentioned in the user’s manual
Wireless
remote Wood screw for holder attached on the air conditioner.)
controller
Drain plug
Control box
Drain pipe Refrigerant pipes
Setting on site
1 PCB on the receiver has the following switches to set the functions. Default setting is shown Terminal block ( X,Y ) in the indoor
with mark. unit control box
Customized signal setting to avoid Normal
mixed communication Remote
Master
Receiver master/slave setting
Slave Wiring 2,6 4Terminal block(X,Y) 3 5Clamp
Valid
Buzzer valid/Invalid
Invalid
Valid
Auto restart
Invalid
- 274 -
PJA012D758
1.4m
2. Places near heat devices 5. Places exposed to oil mist or steam directly.
2.4m
3. High humidity places 6. Uneven surface Reachable area of the signal
1m
4m 3m 2m 1m 0 1m 2m 3m 4m
Note
When the batteries are removed, the setting will return to the
default setting (Auto mode is valid).
Caution
Instruct the customer to set the mentioned above when
replacing the batteries. (How to set is also mentioned in
Control plural indoor units with one remote controller the user’s manual attached on the air conditioner.)
Auto mode operation setting
Up to 16 indoor units can be connected.
1 Connect the XY terminal with 2-core wire. As for the size, refer to the following note.
2 For Single packaged air conditioner series, set the indoor unit address with SW2 on the indoor
unit PCB from [0] to [F] so as not to duplicate. Backup button
A Backup button is provided on the receiver. Backup button
Restrictions on the thickness and length of wire Even when the operation from the wireless
(Maximun total extension 600m.) remote controller is not possible (due to flat
Standard Within 100m x 0.3 mm2 batteries, controller lost, or controller failure),
2
Within 200m x 0.5 mm still it possible to operate as temporary means.
Within 300m x 0.75mm2 Press the button directly when operating it.
Within 400m x 1.25mm2 (1) The air conditioner starts the operation with
Within 600m x 2.0 mm2 the condition of Auto mode, 23˚C of set
point, High fan speed and horizontal louver
position.
(2) The air conditioner stops the operation when
the button is pressed when in operation.
Terminal block
- 275 -
● DO NOT install the wireless kit at the following places in order to avoid malfunction.
(1) Places exposed to direct sunlight (8) Places where the receiver is influenced by Switch
(2) Places near heat devices the fluorescent lamp (especially inverter
(3) High humidity places type) or sunlight.
(4) Hot surface or cold surface enough to (9) Places where the receiver is affected by
generate condensation infrared rays of any other communication
(5) Places exposed to oil mist or steam directly devices
(6) Uneven surface (10)Places where some object may obstruct the Receiver Backside Cover Backside
(7) Places affected by the direct airflow of the communication with the remote controller
AC unit.
Note
Installation tips for th
※ When the batteries are removed, the setting will return
Adjust and keep th
to the default setting.
Accessories Please make sure to reset it when the batteries are
Tighten the screw
DO NOT attach th
replaced.
Please make sure that you have all of the following accessories.
Caution
Receiver Remote controller Instruct the customer to set the mentioned above when
holder replacing the batteries. How to insert
(How to set is also mentioned in the user’s manual
Wireless
remote Wood screw for holder attached on the air conditioner.)
① Detach the back lid.
controller
② Insert the batteries.
AAA dry cell battery ③ Reattach the back li
Parts set (RO3) Radio interference prevention mode
Restrictions on th
(Maximun total e
Standar
Terminal block
① PCB on the receiver has the following switches to set the functions. Default setting is shown Terminal block in the indoor
with mark. unit control box
Customized signal setting to avoid Normal
mixed communication Remote Master/Slave
Master
Receiver master/slave setting Up to two receivers ca
Slave
When two receivers ar
Valid to set it as slave.
Buzzer valid/Invalid
Invalid
(For the method of swi
Valid
Auto restart ② How to install the
Invalid
- 276 -
2.5
3. High humidity places 6. Uneven surface
1.1
② Correlation between illuminance at the receiver
and reachable area of the signal in a plain view.
The drawing in the right shows the The receivable area of the
correlation between the reachable area signal when the illuminance
de of the signal and illuminance at the at the receiver is 300lux
receiver when the remote controller is
operated at 1.1m high under the
condition of ceiling height of 2.5m.
When the illuminance becomes double,
Wood screw the area is narrowed down to two
thirds.
ontroller setting as
polarized)
Caution
control box’s metal sheet. Instruct the customer to set the mentioned above when
replacing the batteries. (How to set is also mentioned in
Terminal block
- 277 -
8*3&-&443&.05&$0/530--&3*/45"--"5*0/."/6"-
3.1.3 FDEN Series (RCN-E1R)
1'"%
4FUUJO
3 1$#
'
TXJU
8"3/*/(
8*3&-&443&.05&$0/530--&3*/45"--"5*0/."/6"-
'BTUFOUIFXJSJOHUPUIFUFSNJOBMTFDVSFMZBOEIPMEUIFDBCMFTFDVSFMZTPBTOPUUPBQQMZVOFYQFDUFETUSFTTPOUIFUFSNJOBM
-PPTFDPOOFDUJPOPSIPMEXJMMDBVTFBCOPSNBMIFBUHFOFSBUJPOPSàSF
%FGB
4FUUJO
48
1$#
.BLFTVSFUIFQPXFSTVQQMZJTUVSOFEPGGXIFOFMFDUSJDXJSJOHXPSL TXJUD
8"3/*/(
0UIFSXJTF
FMFDUSJDTIPDL
NBMGVODUJPOBOEJNQSPQFSSVOOJOHNBZPDDVS
48
%FGB
'BTUFOUIFXJSJOHUPUIFUFSNJOBMTFDVSFMZBOEIPMEUIFDBCMFTFDVSFMZTPBTOPUUPBQQMZVOFYQFDUFETUSFTTPOUIFUFSNJOBM 48
$"65*0/
-PPTFDPOOFDUJPOPSIPMEXJMMDBVTFBCOPSNBMIFBUHFOFSBUJPOPSàSF 48
48
*OTUBMMBSFDFJWFSVOJUXIFSFJUJTOPUFYQPTFEUPEJSFDUTVOSBZTPSJOUFOTFMJHIUGSPNMJHIUJOHàYUVSFT
.BLFTVSFUIFQPXFSTVQQMZJTUVSOFEPGGXIFOFMFDUSJDXJSJOHXPSL 48
0UIFSXJTF
FMFDUSJDTIPDL
NBMGVODUJPOBOEJNQSPQFSSVOOJOHNBZPDDVS
48
$"65*0/
1 "DDFTTPSJFT
*OTUBMMBSFDFJWFSVOJUXIFSFJUJTOPUFYQPTFEUPEJSFDUTVOSBZTPSJOUFOTFMJHIUGSPNMJHIUJOHàYUVSFT
48
1MFBTFNBLFTVSFUIBUZPVIBWFBMMPGUIFGPMMPXJOHBDDFTTPSJFT
.BTU
3FNPUPDPOUSPMMFSIPMEFS """ESZDFMMCBUUFSZ 30
8PPETDSFXGPSIPMEFS 8JSFMFTTSFNPUFDPOUSPMMFS
1 "DDFTTPSJFT 6Q
8I
1MFBTFNBLFTVSFUIBUZPVIBWFBMMPGUIFGPMMPXJOHBDDFTTPSJFT
TMBW
.BTUF
3FNPUPDPOUSPMMFSIPMEFS """ESZDFMMCBUUFSZ 30
8PPETDSFXGPSIPMEFS 8JSFMFTTSFNPUFDPOUSPMMFS
$POUS
6QU
8IF
6Q
TMBW
1$
2 *OTUBMMBUJPOPGUIFDPOUSPMMFSIPMEFS
25
$POUSP
$"65*0/%0/05JOTUBMMJUPOUIFGPMMPXJOHQMBDFT 34
6QU
1$
1MBDFTFYQPTFEUPEJSFDUTVOMJHIU )PUTVSGBDFPSDPMETVSGBDFFOPVHIUPHFOFSBUFDPOEFOTBUJPO
*OTUBMMBUJPOPGUIFDPOUSPMMFSIPMEFS
21MBDFTOFBSIFBUEFWJDFT 1MBDFTFYQPTFEUPPJMNJTUPSTUFBNEJSFDUMZ
25
D
)JHIIVNJEJUZQMBDFT 6OFWFOTVSGBDF
$"65*0/%0/05JOTUBMMJUPOUIFGPMMPXJOHQMBDFT 34
1MBDFTFYQPTFEUPEJSFDUTVOMJHIU )PUTVSGBDFPSDPMETVSGBDFFOPVHIUPHFOFSBUFDPOEFOTBUJPO
1MBDFTOFBSIFBUEFWJDFT 1MBDFTFYQPTFEUPPJMNJTUPSTUFBNEJSFDUMZ
*OTUBMMBUJPOUJQTGPSUIFSFNPUFDPOUSPMMFSIPMEFS
)JHIIVNJEJUZQMBDFT 6OFWFOTVSGBDF
r"EKVTUBOELFFQUIFIPMEFSVQSJHIU
r5JHIUFOUIFTDSFXUPUIFFOEUPBWPJETDSBUDIJOHUIF
SFNPUFDPOUSPMMFS
*OTUBMMBUJPOUJQTGPSUIFSFNPUFDPOUSPMMFSIPMEFS 8PPETDSFX
r%0/05BUUBDIUIFIPMEFSPOQMBTUFSXBMM
r"EKVTUBOELFFQUIFIPMEFSVQSJHIU
)PMEFSGPS
r5JHIUFOUIFTDSFXUPUIFFOEUPBWPJETDSBUDIJOHUIF SFNPUFDPOUSPMMFS
SFNPUFDPOUSPMMFS
r%0/05BUUBDIUIFIPMEFSPOQMBTUFSXBMM 8PPETDSFX
)PXUPJOTFSUCBUUFSJFT
)PMEFSGPS
1%FUBDIUIFCBDLMJE SFNPUFDPOUSPMMFS
2*OTFSUUIFCBUUFSJFT UXP"""CBUUFSJFT
&OTVSFUIFDPSSFDU
QPMBSJUZXIFO "55
33FBUUBDIUIFCBDLMJE JOTFSUJOH
)PXUPJOTFSUCBUUFSJFT *O B
1%FUBDIUIFCBDLMJE OFD
2*OTFSUUIFCBUUFSJFT UXP"""CBUUFSJFT
&OTVSFUIFDPSSFDU 4FUU
QPMBSJUZXIFO "55&
33FBUUBDIUIFCBDLMJE JOTFSUJOH DPO
*O B
OFDF
4FUUJ
DPOO
- 278 -
% 3 '%&/
/6"- 4FUUJOHPOTJUF
1$# PO UIF SFDFJWFS IBT UIF GPMMPXJOH
5PDIBOHFTFUUJOH
3FNPWFUIFGSPOUQBOFM
TXJUDIFTUPTFUUIFGVODUJPO 3FNPWFGPVSTDSFXTMPDBUFEPOUIFCBDLPGUIFSFDFJWFSBOE
%FGBVMUTFUUJOHJTTIPXOXJUINBSL EFUBDIUIFCPBSE
$IBOHFUIFTFUUJOHCZUIFTXJUDIPO1$#
1SFWFOUTJOUFSGFSFODF 0//PSNBM DI
48
EVSJOHQMVSBMTFUUJOH 0''$VTUPNJ[FE DI
48
0/ .BTUFS 0/
48 3FDFJWFSNBTUFSTMBWF 0''
TFUUJOH 0'' 4MBWF
0/ 7BMJE 4XJUDI
48 #V[[FSWBMJE*OWBMJE %FGBVMUTFUUJOHT
0'' *OWBMJE
0/ 7BMJE
48 "VUPSFTUBSU
0'' *OWBMJE 3FDFJWFS#BDLTJEF
8IFOTXJUDIJTUVSOFEUPPGGQPTJUJPO
DIBOHFUIFXJSFMFTTSFNPUFDPOUSPMMFSTFUUJOH
'PSUIFNFUIPEPGDIBOHJOHUIFTFUUJOH
SFGFSUP4FUUJOHUPBWPJENJYFEDPNNVOJDBUJPO
POQBHF
3FGFSUP8JSFMFTTSFNPUFDPOUSPMMFSVOJUPQFSBUJPOEJTUBODFPG5'%&/JODBTFPGQMVSBMTFUUJOH
.BTUFS4MBWFTFUUJOHXIFOVTJOHQMVSBMSFNPUFDPOUSPMMFST
6QUPUXPSFDFJWFSPSXJSFESFNPUFDPOUSPMMFSDBOCFJOTUBMMFEJOPOFJOEPPSVOJUHSPVQ
8IFOUXPSFDFJWFSTPSXJSFESFNPUFDPOUSPMMFSBSFVTFE
JUJTOFDFTTBSZUPDIBOHF48POUIF1$#UPTFUJUBT
TMBWF
$POUSPMQMVSBMJOEPPSVOJUTXJUIPOFSFNPUFDPOUSPMMFS
6QUPJOEPPSVOJUTDBOCFDPOOFDUFE
1$POOFDUJOEPPSVOJUTXJUIFBDIPUIFSXJUIDPSFXJSFT"TGPSTJ[F
SFGFSUPUIFGPMMPXJOHOPUF
25IFSFDFJWFSXJSFTNVTUCFDPOOFDUFEPOMZXJUIUIFJOEPPSVOJUUIBUXJMMCFPQFSBUFECZUIFSFNPUF
DPOUSPMMFSEJSFDUMZ
34FUUIFJOEPPSVOJUBEESFTTXJUI48POUIFJOEPPSVOJU1$#GSPN<>UP<'>TPBTOPUUPEVQMJDBUF
UJPO 3FTUSJDUJPOTPOUIFUIJDLOFTTBOEMFOHUIPGXJSF
.BYJNVOUPUBMFYUFOTJPON
4UBOEBSE 8JUIJONY NN
8JUIJONY NN
8JUIJONYNN
8JUIJONYNN
8JUIJONY NN
5FSNJOBMCMPDL
*OEPPSVOJU
*OEPPSVOJU
*OEPPSVOJU
"EESFTT
3FDFJWFS "EESFTT
3FDFJWFS "EESFTT '
3FDFJWFS
S
3FDFJWFSXJSFTNVTUCFDPOOFDUFEGPSPOFVOJU
8JSFMFTT POMZBOEMFBWFPUIFSJOEPPSVOJUTXJUIPQFO
SFNPUFDPOUSPMVOJU DPOOFDUPST
"55&/5*0/
*O B TZTUFN DPOàHVSFE BT TIPXO BCPWF
VQ UP UXP SFDFJWFST BSF VTBCMF *G UXP SFDFJWFST BSF VTFE
JU JT
OFDFTTBSZUPEFTJHOBUFPOFPGUIFNBTBTMBWFCZTFUUJOH48 'PSUIFNFUIPEPGDIBOHJOHUIFTFUUJOH
SFGFSUP
4FUUJOH PO TJUF
4JODF PUIFS SFDFJWFST BSF OPU VTBCMF
EP OPU DPVQMF UIF DPOOFDUPST GPS UIFN 6OMFTT UIF
DPOOFDUPSJTDPVQMFEGPSBSFDFJWFS
UIF-&%XJMMOPUCFBCMFUPNBLFBOZJOEJDBUJPO
$POUJOVBUJPOPOOFYUQBHF
- 279 -
3 '%&/ DPOUJOVFE
3 '
8JSFMFTTSFNPUFDPOUSPMMFSVOJUPQFSBUJPOEJTUBODF )PXU
14UBOEBSETJHOBMSFDFJWJOHSBOHF 21PJOUTGPSBUUFOUJPOJODPOOFDUJOHBQMVSBM "UX
<$POEJUJPO> OVNCFSPGJOEPPSVOJUT
"
*MMVNJOBODFBUUIFSFDFJWFSBSFBMVY <$POEJUJPO>
"
8IFOOPMJHIUJOHàYUVSFJTMPDBUFEXJUIJONPG *MMVNJOBODFBUUIFSFDFJWFSBSFBMVY V
JOEPPSVOJUJOBOPSEJOBSZPGàDF
8IFOOPMJHIUJOHàYUVSFJTMPDBUFEXJUIJONPG
"
JOEPPSVOJUJOBOPSEJOBSZPGàDF
8
$FJMJOHTVSGBDF 8IFOUIFSFNPUFDPOUSPMVOJUJTVTFEXJUIUIF
8
BGPSFNFOUJPOFEJOUFSGFSFODFQSFWFOUJPOTFUUJOH
N
&
N
BNJOJNVNEJTUBODFHVBSBOUFFJOHUIF U
8JSFMFTTSFNPUF QSFWFOUJPOPGVOJOUFOEFEVOJUSFTQPOTFTJTN
DPOUSPMVOJU 'MPPSTVSGBDF N
8JUIJON 5PQWJFX
4 3
N N
4FUUJO
3FDFJWBCMFSBOHF 3FDFJWBCMFSBOHF 1SFT
5PQWJFX
CVUU
N
4FUUJO
3FDFJWBCMFSBOHF
1MFBTFPQFSBUFSFNPUFDPOUSPMVOJUTXJUDIFTXJUIUIFVOJUGBDFEDPSSFDUMZ 73'
UPXBSEUIFJOEPPSVOJUhTSFDFJWFSTFDUJPO DBOO
.BL
&GGFDUJWFPQFSBUJPOEJTUBODFDBOWBSZXJUIUIFMVNJOBODFBSPVOEUIF
SFDFJWFSBOEUIFSFáFDUJPOGSPNXBMMTPGUIFSPPN TPB
8IFOUIFSFDFJWFSJTFYQPTFEUPJOUFOTJWFMJHIUTVDIBTGSPNUIFEJSFDU
TVOPSBTUSPOHMJHIU
JUNBZCFDPNFPQFSBCMFPOMZGSPNBTIPSUEJTUBODF 1VTI
PSVOBCMFUPSFDFJWFTJHOBMTBUBMM JOTF
XJMMN
#BDLVQCVUUPO
"CBDLVQTXJUDIJTQSPWJEFEPOUIFSFDFJWFSTFDUJPOPGUIFQBOFMTVSGBDF
8IFOPQFSBUJPOGSPNUIFXJSFMFTTSFNPUFDPOUSPMVOJUJTOPUQPTTJCMF EVFUPáBUCBUUFSJFT
BNJTMBJEVOJU
BVOJU
GBJMVSF
ZPVDBOVTFJUBTBOFNFSHFODZNFBOT:PVTIPVMEPQFSBUFUIJTTXJUDINBOVBMMZ
*GQSFTTFEXIJMFUIFBJSDPOEJUJPOFSJTJOBIBMU
JUXJMMDBVTFUIFBJSDPOEJUJPOFSUPTUBSUPQFSBUJPOJOUIF
BVUPNBUJDNPEF
8JOETQFFE)JGBO
5FNQFSBUVSFTFUUJOH$
-PVWFSIPSJ[POUBM
*GQSFTTFEXIJMFUIFBJSDPOEJUJPOFSJTJOPQFSBUJPO
JUXJMMTUPQUIFBJSDPOEJUJPOFS
-JHIUSFDFJWJOHTFDUJPO
"55&
8IF
5*.&3
$)&$,36/
1MFB
#BDLVQTXJUDI
$BV
TFHNFOUJOEJDBUPS
*OTUS
)PX
$PPMJOHUFTUSVOPQFSBUJPO
r"GUFSTBGFUZDPOàSNBUJPO
UVSOPOUIFQPXFS
r5SBOTNJUBDPPMJOHPQFSBUJPODPNNBOEXJUIUIFXJSFMFTTSFNPUFDPOUSPMVOJU
XIJMFUIFCBDLVQTXJUDIPOUIF
SFDFJWFSJTEFQSFTTFE
r*GUIFCBDLVQTXJUDIPOUIFSFDFJWFSJTQSFTTFEEVSJOHBUFTUSVO
JUXJMMFOEUIFUFTUSVO
*GZPVDBOOPUPQFSBUFUIFVOJUQSPQFSMZEVSJOHBUFTUSVO
QMFBTFDIFDLXJSJOHCZDPOTVMUJOHXJUIJOTQFDUJPO
HVJEFT
- 280 -
3 '%&/ DPOUJOVFE
)PXUPSFBEUIFUXPEJHJUEJTQMBZ
"UXPEJHJUJOEJDBUPS TFHNFOUJOEJDBUPS
JTQSPWJEFEPOUIFSFDFJWFSTFDUJPO
"OJOEJDBUJPOXJMMCFEJTQMBZFEGPSPOFIPVSBGUFSQPXFSPO
"OJOEJDBUJPOBQQFBSTGPSTFDPOETXIFOBi4UPQuDPNNBOEJTTFOUGSPNUIFXJSFMFTTSFNPUFDPOUSPM
VOJUXIJMFUIFBJSDPOEJUJPOFSJTOPUSVOOJOH
NPG
"OJOEJDBUJPOBQQFBSJOHJO
PS
BCPWFXJMMHPPGGBTTPPOBTUIFVOJUTUBSUTPQFSBUJPO
8IFOUIFSFBSFOPFSSPSSFDPSETUPJOEJDBUF
BEESFTTFTBSFEJTQMBZFEGPSBMMPGUIFDPOOFDUFEVOJUT
UIF
8IFOUIFSFBSFTPNFFSSPSSFDPSETSFNBJOJOH
UIFFSSPSSFDPSETBSFEJTQMBZFE
UUJOH
&SSPSSFDPSETDBOCFDMFBSFECZUSBOTNJUUJOHBi4UPQuDPNNBOEGSPNUIFXJSFMFTTSFNPUFDPOUSPMVOJU
XIJMF
UIFCBDLVQTXJUDIJTEFQSFTTFE
N
4 3FNPUFDPOUSPMMFS
4FUUJOHUPBWPJENJYFEDPNNVOJDBUJPO
1SFTTJOH"$-BOE"*3'-08CVUUPOBUUIFTBNFUJNFPSJOTFSUJOHUIFCBUUFSJFTXJUIQSFTTJOH"*3'-08
CVUUPOXJMMDVTUPNJ[FUIFTJHOBM
4FUUJOHUPEJTBCMFUIF"VUPNPEFPQFSBUJPO
3BEJPQSFWFOUJPONPEF
FDUMZ 73'TZTUFN FYDFQUIFBUSFDPWFSZQJQFTZTUFN
DBOOPUCFPQFSBUFEJO"VUPNPEF
.BLFTVSFUPTFUUIFSFNPUFDPOUSPMMFSGPSUIFNPEFMT
TPBTOPUUPCFBCMFUPDIPPTF"VUPNPEF
FDU
BODF 1VTIJOH"$-BOE.0%&CVUUPOBUUIFTBNFUJNFPS
JOTFSUJOHUIFCBUUFSJFTXJUIQSFTTJOH.0%&CVUUPO
XJMMNBLFBVUPNPEFPQFSBUJPO
BVOJU
"VUPNPEFPQFSBUJPOTFUUJOH
"55&/5*0/
8IFOUIFCBUUFSJFTBSFSFNPWFE
UIFTFUUJOHXJMMSFUVSOUPUIFEFGBVMUTFUUJOH
1MFBTFNBLFTVSFUPSFTFUJUXIFOUIFCBUUFSJFTBSFSFQMBDFE
$BVUJPO
*OTUSVDUUIFDVTUPNFSUPTFUUIFNFOUJPOFEBCPWFXIFOSFQMBDJOHUIFCBUUFSJFT
)PXUPTFUJTBMTPNFOUJPOFEJOUIFVTFSTNBOVBMBUUBDIFEPOUIFBJSDPOEJUJPOFS
POUIF
UJPO
1'"%
- 281 -
WARNING
(1) Drilling of the ceiling (ceiling opening)
Fasten the wiring to the terminal securely and hold the cable securely so as not to
apply unexpected stress on the terminal. Drill the receiver installation holes with the following dimensions at the ceiling position where
Loose connection or hold will cause abnormal heat generation or fire. wires can be connected.
Make sure the power supply is turned off when electric wiring work.
Otherwise, electric shock, malfunction and improper running may occur. (A) Direct installation onto the ceiling with
88mm(H)×101mm(W)
wood screws.
CAUTION (B) Installation with enclosed bracket. 108mm(H)×108mm(W)
DO NOT install the wireless kit at the following places in order to avoid malfunction.
(1)Places exposed to direct sunlight (8)Places where the receiver is influenced by
(2)Places near heat devices the fluorescent lamp (especially in verter
(3)High humidity places type) or sunlight.
(2) Wiring connection of receiver
(4)Hot surface or cold surface enough to (9)Places where the receiver is affected by Indoor unit terminal block
generate condensation infrared rays of any other communication
(5)Places exposed to oil mist or steam directly devices. Caution
(6)Uneven surface (10)Places where some object may obstruct the
Do not connect the wiring to the
(7)Places affected by the direct airflow of the communication with the remote controller
AC unit. power source of the terminal block.
If it is connected, printed board will (non-polarized) Wiring
DO NOT leave the wireless kit without the cover.
be damaged.
In case the cover needs to be detached, protect the receiver with a packaging box or
bag in order to keep it away from water and dust. Reciever
Attention
(3) Installation of the receiver
• Instruct the customer how to operate it correctly referring to the instruction manual.
• User’s manual of a wireless remote controller is attached to a indoor unit or a outside unit. Remove the screw on the side of the receiver and sprit it into the upper case and lower
• Read this together with a manual attached to this kit. case.Install the receiver with one of the two installation methods (A) or (B) shown below.
① Accessories Please make sure that you have all of the following accessories. (A) Direct installation onto the ceiling with screws
Use this installation method when the ceiling is wooden, and there is no problem for
1 Remote controller
1 Receiver 1 1
holder strength in installing directly with wood screws.
2 Screw for holder 2 Wall opening Lower case
2 Wiring (3m) 1 Installation hole
AAA dry cell Hole
3 battery (R03) 2 Opening
3 Parts set (A) 1
Wiring
1 Screw for receiver 2 Hole
4 Parts set (B) 1
2 Fixing band 1
5 Parts set (C) 1 Lower case
3 Clamp 5
6 Wireless remote 1 Installation hole
controller 4 Screw for clamp 5
7 User’s manual 1 Wiring
1 Receiver installation
1
bracket
2 Screw for the bracket 2 Upper case
3 Installation fitting 2
Protrusion
Receivable area Installation fitting (right side of center)
of the signal
Hole Bracket
(ø10)
Hole (ø10)
Floor
[Bottom]
② Correlation between illuminance at the receiver and reachable area of the signal in a plain Bracket
view. Protrusion (left side of center)
condition Correlation between the reachable area of the signal and illuminance at
the receiver when the remote controller is operated at 1.1m high under Protrusion
(right side of center)
the condition of ceiling height of 2.5m. Lower case
[Top] Installation hole
When the illuminance becomes double, the area is narrowed down to two third. Hole
③Pass the wiring from the rear side through the hole on the lower case.
or
④Fit the lower case onto the bracket, and fix the lower case to the bracket using the
les
30° °
or less 30r less
s
Wireless
remote controller
o two installation holes shown above. (The other four holes are not used.)
Floor
5m or less 60° or less ⑤Follow step ① to ⑥ for (A) to complete the installation.
- 282 -
④ Remotecontroller (B) Control plural indoor units with one remote controller
Up to 16 indoor units can be connected.
Installation of the controller holder ①Connect the XY terminal with 2-core wire.
Restrictions on the thickness and length of wire
As for the size, refer to the following note. (Maximun total extension 600m.)
Caution ②For Packaged air conditioner series, set the Standard Within 100m x 0.3 mm2
Within 200m x 0.5 mm2
DO NOT install it on the following places indoor unit address with SW2 on the indoor Within 300m x 0.75mm2
Holder for
1) Places exposed to direct sunlight remote unit PCB from [0] to [F] so as not to duplicate. Within 400m x 1.25mm2
controller Within 600m x 2.0 mm2
2) Places near heat devices
3) High humidity places
4) Hot surface or cold surface enough to generate Terminal block
condensation
5) Places exposed to oil mist or steam directly Wood screw
6) Uneven surface Indoor unit (1) Indoor unit (2) Indoor unit (16)
Address (0) Address (1) Address (F)
KIT
Installation tips for the remote controller holder
• Adjust and keep the holder upright.
• Tighten the screw to the end to avoid scratching
the remote controller. Remote controller
• DO NOT attach the holder to plaster wall.
How to insert batteries ③For VRF series, set the indoor unit address with SW1, SW2 and SW5-2 on the
① Detach the back lid. indoor unit PCB from [000] to [127] so as not to duplicate.
② Insert the batteries. (two AAA batteries)
③ Reattach the back lid. (C) Master/Slave setting when using plural remote controller
Up to two receivers can be installed in one indoor unit group.
Setting to
avoid mixed
communication. SW1-1
(Customized signal
SW1-4 setting to avoid
(Auto restart) mixed communication)
SW1-2
(Receiver master/slave
setting)
Customized signal setting to ON : Nor mal
SW1-1
avoid mixed communication OFF : Remot e
ON : Mast er
SW1-2 Receiver master/slave setting
OFF : Slave
ON : Val id
SW1-4 Auto restart
OFF : I nval id
: Default setting
- 283 -
MODE button
Use to select the mode.
FAN SPEED button
Button to set the fan speed
In
TEMP button
Use to raise the setting temperature. 0.
Operation mode display Indoor unit No. display VRF series outdoor unit No. display
: Cooling
: Drying
: Fan operation
: Heating
: Auto mode Fan speed display
Wiring
83.5
117
16
33.5
ditioner
In case of exposing wiring The remote controller wiring can be extracted from the upper center.
After the thin part in the upper side of the remote controller upper
case is scraped with a nipper or knife, remove burr with a file.
0.3mm2×2 cores. Thin part
Upper case
LCD
er
Sheath
120
y Upper case
XY
X, Y Terminal block
70 wiring
Attach M3 screw
play with washer The peeling length of each wiring is as follows:
X wiring : 160mm
Y wiring : 150mm Sheath
Peeling length
Wiring specifications
play (1) Wiring of remote controller should use 0.3mm2 × 2 core wires or cables. (on-site configuration)
(2) Maximum prolongation of remote controller wiring is 600m.
entilation If the prolongation is over 100m, change to the size below.
But, the wiring in the remote controller case should be 0.3mm2 (recommended) to 0.5mm2. Unit:mm
Change the wire size outside of the case according to wire connecting. Waterproof treatment is
necessary at the wire
connecting section. Be careful about contact failure.
splay Length Wiring thickness
play 100 to 200m 0.5mm2×2 cores Adapted to RoHS directive
Under 300m 0.75mm2×2 cores
Under 400m 1.25mm2×2 cores
Under 600m 2.0mm2×2 cores
- 285 -
WARNING ⑴
● Fasten the wiring to the terminal securely and hold the cable securely so as not to apply Screw
unexpected stress on the terminal. ⑵ Remove the upper case of the remote controller.
Loose connection or hold will cause abnormal heat generation or fire. Insert a flat-blade screwdriver to a concave portion of
● Make sure the power supply is turned off when electric wiring work. the bottom surface of the remote control and slightly
Otherwise, electric shock, malfunction and improper running may occur. twist it, and the case is removed. ⑵ Se
Upper case (Note) •
CAUTION •
⑵ •
● DO NOT install the remote controller at the following places in order to avoid malfunction.
(1) Places exposed to direct sunlight (4) Hot surface or cold surface enough to generate condensation
(2) Places near heat devices (5) Places exposed to oil mist or steam directly ⑶ The remote controller cord can be extracted from the
(3) High humidity places (6) Uneven surface upper center.
● DO NOT leave the remote controller without the upper case. After the thin part in the upper side of the remote
Thin part
In case the upper cace needs to be detached, protect the remote controller with a packaging box controller upper case is scraped with a nipper or knife,
or bag in order to keep it away from water and dust. remove burr with a file.
⑶ 4. T
Accessories Remote controller, wood screw (φ3.5×16) 2 pieces
⑴ At
Prepare on site Remote controller cord (2 cores) (Refer to [2. Installation and wiring of remote controller]) be
[In case of embedding cord] Electrical box, M4 screw (2 pieces) Th
[In case of exposing cord] Cord clamp (if needed) ⑷ The lower case of the remote controller is mounted to
an
a flat wall with two accessory wood screws.
1. Installation procedure
Lower case
In case of embedding cord
⑴ Make certain to remove the screw on the bottom Wall
surface ⑵ Th
surface of the remote controller. co
⑸ Connect the remote controller cord to the terminal block. ⑷ ⑶ In
Connect the terminals (X and Y) of the remote controller and ce
⑴ If
Screw the terminals (X and Y) of the indoor unit. (No polarity of X and
Y) es
⑵ Remove the upper case of the remote controller. ⑷ If
The wiring route is as shown in the right.
Insert a flat-blade screwdriver to a concave portion of the bottom co
surface of the remote controller and slightly twist it, and the case is ab
removed. th
XY th
Upper case
⑸
5. C
⑵ 2 2 Return
The wiring in the remote controller case should be 0.3 mm (recommended) to 0.5 mm at
maximum. ⑴ Pr
⑶ Pre-bury the electrical box and remote controller cord. Further, peel off the sheath. “8
The peeling length of each wiring is as follows: (“
Remote controller cord X wiring : 160mm Sheath Th
Electrical box Peeling length (E
Y wiring : 150mm
Prepare on site (N
⑶ ⑹ Mount the upper case for restoring to its former state so as not to
crimp the remote controller cord, and secure with the removed screw.
⑷ Prepare two M4 screws (recommended length: 12 – 16mm), and install the lower case to the electrical box. ⑵ Pr
Do not use a screw whose screw head is larger than the height of the wall around the screw hole. ⑺ In the case of exposing installation, secure the remote controller cord to the wall surface with a En
cord clamp so as not to loosen the remote controller cord. [In the c
remote
⑴ Pr
Lower case 2. Installation and wiring of remote controller in
(A
⑴ Wiring of remote controller should use 0.3mm × 2 core wires or cables. (on-site configuration)
2
⑷ nu
⑵ Maximum prolongation of remote controller wiring is 600 m.
Wiring outlet ⑵ Pr
If the prolongation is over 100m, change to the size below.
Two M4 screws (head: ø8 or less) (prepare on site) Se
But, the wiring in the remote controller case should be 0.3mm2 (recommended) to 0.5mm2.
⑶ Pr
Change the wire size outside of the case according to wire connecting. Waterproof treatment is De
⑸ Connect the remote controller cord to the terminal block. necessary at the wire (E
Connect the terminals (X and Y) of the remote controller and the terminals (X and Y) of the indoor connecting section. Be careful about contact failure. “8
unit. (No polarity of X and Y) 100 - 200m・・・・・・・・・・・・・・・・・0.5mm2 × 2 cores da
Under 300m・・・・・・・・・・・・・・・・・0.75mm2 × 2 cores to
⑹ Mount the upper case for restoring to its former state so as not to crimp the remote controller cord, Under 400m・・・・・・・・・・・・・・・・・1.25mm2 × 2 cores ⑷ Pr
and secure with the removed screw. Under 600m・・・・・・・・・・・・・・・・・2.0mm2 × 2 cores En
- 286 -
6. Function setting 7. How to set functions by button op
Each function of the remote controller and the indoor unit is automatically set to the initial setting, which is the standard use, on the occasion of connecting the remote controller with the indoor unit. In the case of the standard ⑴ Stop air-conditioning, and simultaneously pre
use, the setting change is unnecessary. However, if you whould like to change the initial setting “ ○ ”, change the setting for only the item of the function number. Record the setting contents and stored them. at the same time for over three seconds.
Downloaded from www.Manualslib.com manuals search engine The function number “01” blinks in the upper righ
'10 • PAC-DB-142
3. Master/ slave setting when more than one remote controller are used
surface of the ⑴ Up to two remote controllers can be connected to one unit (or one group) of indoor unit.
Switch Setting Function detail
indoor unit ON Slave remote controller
SW1-1
OFF Master remote controller
X○
○ Y
⑴ Remote controller line (nonpolarity)
Screw
. ○X○ Y ○X○ Y
ion of Remote controller “Master” Remote controller “Slave”
ghtly SW1-1 “OFF” SW1-1 “ON”
⑵ Set the switch SW1-1 of the slave remote controller is “Slave” (ON). The factory default is set as “Master” (OFF).
Upper case (Note) • The remote controller thermistor enabled setting can be set only to the master remote controller.
• Install the master remote controller at the position to detect room temperature.
⑵ • The air conditioner operation follows the last operation of the remote controller in case of the
master / slave setting.
SW1
m the ON
OFF
1 2 3 4 5 6 7 8 9 0
e SW1-1:ON (Slave remote controller)
Thin part SW1-1:OFF(Master remote controller)
r knife,
- 287 -
7. How to set functions by button operation
standard ⑴ Stop air-conditioning, and simultaneously press AIR CON NO. and MODE buttons
at the same time for over three seconds.
Downloaded from The function number “01”manuals
www.Manualslib.com blinks in the search
upper right.
engine
connecting section. Be careful about contact failure.
unit. (No polarity of X and Y) 100 - 200m・・・・・・・・・・・・・・・・・0.5mm2 × 2 cores
Under 300m・・・・・・・・・・・・・・・・・0.75mm2 × 2 cores
⑹ Mount the upper case for restoring to its former state so as not to crimp the remote controller cord, Under 400m・・・・・・・・・・・・・・・・・1.25mm2 × 2 cores
and secure with the removed screw. '10 • PAC-DB-142
Under 600m・・・・・・・・・・・・・・・・・2.0mm 2
× 2 cores
Note 1: The symbol “ ※ ” in the initial setting varies depending upon the indoor unit and the outdoor unit to be connected, and this is Note 2: Fan speed of “High speed” setting
automatically determined as follows: Indoor unit fan speed setting
Fan speed setting
Swith No. - - - -
Function Setting Product model
Function No. Standard Hi − Mid − Lo Hi − Lo Hi − Mid
“FAN SPEED” button prohibited Product model whose indoor fan speed is only one step High speed 1・2 UHi − Hi − Mid UHi − Mid UHi − Hi ⑸ Press
“FAN SPEED”
SW1-6
button “FAN SPEED” button enabled
Product model whose indoor fan speed is two steps or three
Initial setting of some indoor unit is “High speed”.
The sett
steps
Fan speed: three steps Product model whose indoor unit fan speed is three steps Note 3: As for plural indoor unit, set indoor functions to each master and slave indoor unit.
Indoor unit fan Fan speed: two steps (Hi-Lo) Product model whose indoor unit fan speed is two steps ・Even if
Remote controller function 01 But only master indoor unit is received the setting change of indoor unit function “07 Operation permission/
speed Fan speed: two steps (Hi-Me) ・The se
Fan: one step Product model whose indoor unit fan speed is only one step prohibition” and “08 External input”.
“Auto” operation “Auto” operation enabled Product model where “Auto” mode is selectable
Remote controller function 06
setting “Auto” operation disabled Product model without “Auto” mode
[Confirmat
Heating fan Low fan speed Product model except FDUS Accordin
Indoor unit function 13
control Intermittent operation FDUS (Howeve
- 288 -
PJZ012D069.indd 1
Function number
5 6 7 8 9 0
End button
⑷ [In the case of selecting the remote controller function (01-06)] [In the case of selecting the indoor unit function (07-14)]
① The current setting number of the selected function number blinks ① “88” blinks on the temperature setting indicators.
(Example) (blinking for approximately 2 to 10 seconds while data is read)
Function number: “01” (lighting) ↓
Setting number: “01” (blinking) After that, the current setting number of the selected function number blinks.
erature at +3.0°C.
(Example)
erature at +2.0°C.
erature at +1.0°C.
Function number Function number: “07” (lighting)
erature at -1.0°C. Setting number: “01” (blinking)
erature at -2.0°C.
Setting number Function number
erature at -3.0°C.
Setting number
Then, the screen goes back to the function number blinking b. Press TEMP△ or TEMP▽ button.
indication ⑴ , if the setting is sequentially conducted, continue Select the indoor unit No. to be set.
with the same procedures. If the setting is finished, proceed to ⑸ . If “U ALL” is selected, the same setting can be set to all units.
c. Press MODE button.
Decide the indoor unit No.
“88” blinks on the temperature setting indicators. (blinking for 2 to 10 seconds while data
is read)
hours
ours
When AIR CON NO. button is pressed, go back to the indoor unit selection display (for
example, “U 000” blinking).
ours
- 289 -
2008/11/13 11:42:01
This manual instructs the way of installing the optional fan controller for high static <Precautions for wiring>
pressure ducts. Install the controller in accordance with the following procedure. ○ Connect wires correctly as shown by the electric wiring diagram. Be sure to
tighten set screws firmly to prevent them generating heat or causing other
WARNING troubles after becoming loose.
○ Number of wires connected to the terminal block must be 2 wires or less.
(1)Consult your dealer for the installation of the controller.
Never connect 3 more wires in any event.
(2)Only qualified electrician must install the controller.
(3)Remove the control box before the installation. 4. Installation procedure
Before installing the product,take it out from the package and place it on the floor. (1) Remove the lid from the control box.
(4)Be sure to turn off the power supply during installation. (2) Remove the wiring (fuse~CNF2,3) and wiring(TB X Y ~CNB).
Unless the above precautions are observed,it could cause electrical shocks or fire.
CAUTION Confirm that electricity has been dischaged before touching
the capacitor terminals.There is risk of electric shocks.
1.Applicable models and corresponding fan controller kit
Standard type FDU200VD,250VD (3) Install the fan controller.
U-FCRA (4) Referring to “3.Electric circuit diagram”,connect wires as illustrated and fix
Fan controller kit
(PJZ006A102A) with bands a .
(5) Reinstall the removed lid on the control box.
2.Component parts list
Fan controller Band Tapping Screw
Old
3
4 5
6
(M3:2 pcs.)
2 7
CNR CNJ2 CNM3 CNW1
8
a (L=92):5 pieces
1
2 pieces
CNJ
1 piece
CNO
Wiring A
CNQ
CNE
CNT
F1
F2 52FL,4 52FL,6
CNI
FL
52FH,4 52FH,6 FH
CNWO
CNS
F(3.15A) CNF3
<FMI-2>
CNG
FH2 2
CNV
CFI2 2
CFI1
CNT2
52FL,3 52FL,5 FL
52FH,3 52FH,5 FH
CNF2
FH1
F(3.15A)
1
<FMI-1> Remove
CNF CFI1
CNN
1
<FC>
52FL
CNH
CNF
Wiring B CNZ
TB2,X
(AK4)
TB2,Y
CNB
(R9)
Remove
(A4) CNA CND CNK2 CNK1 CNB CNW2 52FH
CFI2
3.Electric circuit diagram (Change the sections indicated with bald lines.) Fan controller F1 (6.3A)
Old F2 (6.3A)
1 L Red
2 N White 1 2 3
X Y A B
1 2 3 X Y
White Red
Standard type
F F
Multi type (6.3A) (6.3A)
2 1 CNB White
Red 1 3
White Black
1~ 1~
Orange Orange Orange Orange Orange
White White
CNE
CNF2 CNF5
CNT
White White
White
CNF3
CNI
White White
White
CNWO
White
CNS
CNG
CNV
CFI1
CNT2
52FL
CNH
White Red
Standard type
CNF
CNZ
F F
Multi type (6.3A) (6.3A)
2 1 CNB White
Red 1 3 CNA CND CNK2 CNK1 CNB CNW2 52FH
White Black Wiring B
CFI2
Pink Pink Pink Pink X Y TB2
CNF
52FL 52FH 52FL 52FH
X Y F1 (6.3A)
White F(3.15A)
White Regarding the Characteristics fan please see to page 135
White Black
Red Black
Blue Black
FC - 290 -
CNF White
� Follow the instruction and installation manual for outdoor unit when � Follow the law or regulation of the country where it is installed.
installing the heater. � Do not alter the heater.
� This heater must be installed by authorized personnel. � Lay down the heater so that the edge of the sheet metal does not
� Turn off the power supply when the kit is installed. damage the heater.
Failure to follow the above will result in serious accident like electrical � Bending radius must be bigger than 25mm.
shock or fire. � Do not use the heater near flammable substances.
� Be sure to check the electrical insulation before use.
� Be sure to check the drain is not trapped by the heater.
AREAS TO BE APPLIED � Do not leave refrigerant oil on the base.
This kit is to be used in an area where the lowest temperature drops below
zero.
Caution: In case the heater is not applied on the unit which is installed in an Step 4
area mentioned above, it may be regarded as installation failure
and warranty may not be given. 4. Remove the fan
<Note>
Components Heater Bracket Tapping screw Do not rotate the a
fan blade.
Plastic band with clip It may cause malfu
Plastic band without clip
� Heater : 1pc
� Bracket : 4pcs
� Tapping screw : 4pcs
� Plastic band with clip : 2pcs
� Plastic band : 5pcs
Installation procedure
Step 1 Step 5
1. Remove the top panel of the outdoor unit 5. Lay down the dr
(11 pcs of tapping screws).
Step 2 Step 6
2. Remove the service panel 6. Put the heater u
(4 pcs of tapping screws). and align the en
of heat exchang
- 291 -
PCZ012D007 Step 3
3. Remove the front panel
(11 pcs of tapping screws).
Pull the panel straightforward so that the panel
doesn’t touch the fan blade.
stalled.
Step 4
4. Remove the fan blade if necessary.
<Note>
Do not rotate the axis of fan motor when removing the
fan blade.
It may cause malfunction of the fan motor.
ut clip
Step 5 Heater
Heater
Step 6
End of Heater
End plate of Heat
6. Put the heater underneath the heat exchanger exchanger
and align the end of heater with the end plate
of heat exchanger.
- 292 -
Step 7 Step 11
7. Fix the heater with 4 brackets. 11. Reassemble th
<Note> Take care to a
1) Fix the heater so that the bracket 3) In bending position, twist the heater to ▼ mark on the
doesn’t pinch the heater as figure make it easier to bend, and get back
shows. to be able to fix it with bracket. <Note>
Bracket 1. Tightening torq
Heater
2. Do not rotate t
It may cause m
Base
✕ ✕ ✓
2) Place the heater so as to touch the
base completely.
Heater
✕
Step 8 Step 12
8. Insert the plastic band with clip on the designated <Note> 12. Reassemble th
place (2 places), and fix the heater. 1) Do not fasten the heating part with 2) When the heater is laid down correctly, 1) Front panel
the plastic band. the end of heating part comes to the
There is a marking on the end of corner of the base. Use screw B
heating part.
Marking Marking
✕ ✓ 2) Service pane
Use screw B
Step 9 Step 10
9. Lay down the wiring on the same route of fan motor wiring, 10. Insert the connector to the port CnF (Black) on the top right
and fix the wire with attached plastic band (2 places) at the of the PCB, and fix the wire with bands (3 places). Excess
same place where the fan motor wiring is banded. part of the wire should be dropped naturally.
Connector CnF
Band (Black)
Fan motor wiring
Heater
<Note>
Be sure to cut the excess
<Note> part of plastic band.
Fan motor wiring is banded on It may cause abnormal
the bracket so that it doesn’t noise when hit by fan blade
loosen. or misassembling of <Note>
Do not loose the band for the panels. ● This heater should
motor wiring to band the heater Do not bundle excess part disconnection of th
wire together but use the of the wire. It may damage Drop the cable
● Be sure to prevent
attached plastic band. the heater. naturally
Especially, pay clo
- 293 -
Step 11
11. Reassemble the fan blade.
Take care to align the D-cut of motor shaft and the fan blade.
n, twist the heater to ▼ mark on the center of the fan shows the position of D-cut.
end, and get back
with bracket. <Note>
1. Tightening torque of the nut is 4.0-4.9 N·m.
2. Do not rotate the axis of fan motor when tightening the nut.
It may cause malfunction of the fan motor.
e injured by
n fixing the heater
Step 12
12. Reassemble the panels.
laid down correctly, 1) Front panel 3) Top panel
part comes to the
. Use screw B for all places.
A
A B
B
A
A
A
A A
A
A
✓ 2) Service panel
Use screw B for all places.
<Note>
1) When reassembling the service panel, take care
not to damage the front panel with the edge.
2) There are two different length of screws.
Be sure to use correct screw.
Long screw A: used for Top panel other than
fixing fan bracket. A B
Short screw B: other place than A.
B
B
<Note>
● This heater should have bending radius of at least 25mm including non-heating part. Do not bundle the excess part of the wire. It may cause
disconnection of the heater or insufficient capacity.
Drop the cable
● Be sure to prevent the heater from touching any refrigerant piping.
naturally
Especially, pay close attention not to make it touch with pipes which are close to the wiring route such as suction pipe, check valve and check joint.
- 294 -
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.
C Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.