6 FIRST AID FIRE FIGHTING EQUIPMENT

4.6.1 Portable Fire Extinguishers

Portable extinguishers shall be located at convenient locations and shall at all times be
readily accessible and clearly visible. The maximum running distance to locate an
extinguisher shall not exceed 15 mtrs. The extinguishers should be provided at various
locations as below. The portable extinguisher should be installed in such a way that the top
of extinguisher is not more than 1.5 mtrs. above the floor level.

The quantities mentioned below are minimum.

Petroleum Depots & Terminals :

Type of Area Portable Extinguishers

(i)Lube godown 1 no. 10 Kg DCP for 200 m2 floor area.

(ii)Lube filling shed 1 no. 10 Kg DCP for 200 M2

(iii)Storage of class-A/B 1 no. 10 Kg DCP for 100M2


products in packed
containers and stored
in open/closed area.

(iv)Pump House upto 50 HP :


(Class A & B) 1 no. 10 Kg DCP for 2 pumps
Above 50-100 HP : 1 no. 10 Kg DCP for each pump.
Beyond 100 HP : 2nos of 10 kg or 1 no.
of 25 kg DCP for each pump.

Pump House upto 50 HP :


(Class C) 1 no. 10Kg DCP for
every 4 pumps Upto 50 HP :
Above 50 HP : 2 nos. 10 Kg DCP or 1x25 kg DCP for 4 pumps.

(v)Tank Truck loading 1 no. 10 Kg DCP for


and unloading for every 2 Bays. and
POL/speciality products 1 no. 75 Kg DCP mobile unit for each gantry.

(vi)Tank Wagon loading 1 no. 10 Kg DCP for


and unloading every 50 mtrs. length
gantry (siding) and 1 no. 75 Kg DCP mobile unit in each siding.

(vii)Above Ground Minimum 2 nos. 10 kg.


Tank DCP or 1x25 kg. DCP per tank and 4 x 75 Kg or 6 X 50 Kg
DCP mobile unit per installation
U/G Tank farms 2 nos. 10 Kg DCP or 1x25 kg DCP
(viii)Fire pump house: 1 no. 10 Kg DCP for every 2 pumps

(ix)Admin. building/ 1 no. 10 Kg DCP for 200 M2


(Store House) (minimum 1x10 Kg DCP on each floor)

(x) Generator room


upto 250 KVA : 1 no. of 10 Kg DCP and 1 no. 4.5 KG CO2 for every generator.
Above 250 KVA : 2 nos of 4.5 kg & 1 no of 10 Kg DCP

(xi)Main switch room 1 no. 4.5 Kg CO2 for every 25 M2

(xii)Computer Room/ Halon/Its Proven equivalent- 2 nos.


cabin 0.6/1 Kg for 50 M2 or 1 No per cabin whichever is higher

(xiii)Security Cabin 1 no. 10 Kg DCP

(xiv)Canteen 1 no. 10 Kg DCP for 100 M2

(xv)Laboratory 1x10 Kg DCP & 1x4.5 Kg CO2.

(xvi)Effluent Treatment 1 nos. 75 Kg. & 2 nos.


Plant 10 Kg. DCP Extinguisher.

(xvii)Workshop 1 no. 10 Kg. DCP & 1 no. 2 Kg. CO2 Extinguisher.

(xviii)Transformer 1 no. 6.8 Kg. CO2 Extinguisher.

(xix)UPS / Charger 1 no. 2 Kg. CO2


Room Extinguisher.

NOTE: ALL FIRE EXTINGUISHERS SHALL BEAR ISI MARK.

PIPELINE INSTALLATION :

For pipeline installations, the portable extinguisher shall be provided as per the above list
(4.6.1) suitably amended along with following additions :

(xx)Main line pump shed 1 no. each 75 Kg DCP, 10 Kg DCP & 6.8 Kg CO2
(Engine Driven) extinguishers per two pumps upto a maximum of 4 nos.

(xxi)Main Line Pump Shed 1 no each 10 Kg DCP & 6.8 Kg CO2


(Motor Driven) extinguishers per two pumps upto a maximum of 4 nos.
and 1 no 75 Kg DCP per 4 pumps

(xxii)Booster Pump 1 no 10 Kg DCP per two pumps upto a maximum of 3.


1 no 6.8 Kg CO2 extinguisher

(xxiii)Sump Pump 1 no 10 Kg DCP


Transmix Pump extinguisher
& Oil Water
Separator Pump
(xxiv)Scrapper Barrel 1 no 10 Kg DCP Extinguisher

(xxv)Control Room 2nos 2.5 Kg Halon/Its proven equivalent and 4.5 Kg CO2
extinguisher

(xxvi)UHF / Radio Room 2nos 2.5 Kg.Halon/Its proven equivalent and 4.5 Kg CO2
extinguisher.

(xxvii)Metre Prover, 1 no 10 Kg DCP


Separator Filter extinguisher

(xxviii)Repeator Station 1 no 10 Kg DCP & 1 no 2 Kg CO2 extinguisher.

(xxix)Mainline Emergency 4 nos 10 Kg DCP &


Equipment Centre 2 nos 2 Kg CO2 extinguisher

(xxx)Air Compressor 1 no of 2 Kg CO2 type 1 no. 5 Kg DCP Fire extinguisher

4.6.2 WHEELED FIRE FIGHTING


EQUIPMENT

(i)For Installations having tanks of dia large than 9 mtrs, following. Fire Fighting equipments
shall be provided:

For installation having aggr- Nil


egate capacity of 1000 KL

For installation having aggr- 1 No. of


egate capacity upto 10,000 KL 1600 LPM

For installation having aggr- 1 No. of


egate capacity upto 25,000 KL 2400 LPM

For installation having aggr- 2 No. of


egate capacity more than 2400 LPM
25,000 KL

(ii)Foam compound trolley 200/210 litres : 1 No. upto 24 mtrs dia tanks, 2 Nos. for 24 to 30 mtrs
dia and 3 Nos. for 30 to 40 mtrs or above dia tanks.