Documente Academic
Documente Profesional
Documente Cultură
CHAPTER 17
Air Coolers
Fin-Fan Coolers
A
ir coolers are twice as expensive to purchase and install as
water coolers. The great advantage of an air cooler is that it
does not need cooling water. The difficult aspect of air cooling
arises from the flow of air across the tubes.
Most air coolers are either induced-draft or forced-draft, as shown
in Fig. 17.1, the more common arrangement being forced draft. The
air is moved by rather large fans. The tubes are surrounded with foil-
type fins, typically 1 in high. The surface area of the fins as compared
to the surface area of the tubes is typically 12 to 1. That is why we call
an air cooler an extended-surface heat exchanger.
The heat-transfer coefficient of an air cooler (Btu, per hour, per
square foot of finned area, per degree Fahrenheit) is not particularly
good. It might be 3 to 4 for cooling a viscous liquid, or 10 to 12 for
condensing a clean vapor. The low heat-transfer coefficients are offset
by the large extended surface area.
193
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2009 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.
Air
Air
Forced draft induced draft
Outlet
Shroud
Screen
This is a long, wet, hot, and dirty job, but the results are sometimes
quite fantastic. Washing from the top down takes even longer, uses
10 times as much water, and never does as good a job. But it’s a lot
easier and drier.
The fan blades themselves may be adjusted to obtain more airflow.
This is done by increasing the fan blade pitch. The pitch can usually be
adjusted between 12° (for low airflow) to 24° (for high airflow). Any
increase in airflow has to increase the amp load on the fan motor
driver. The motor could then trip off.
Setting the blade pitch cannot be done with great precision, and
it’s not too critical. I once increased the blade pitch from 15º to about
22º. Airflow increased by only 5 percent measured by the increased
amperage load on the motor driver.
Cooler weather always increases the airflow produced by a fan.
This always increases the amp load on the fan’s motor driver. To
prevent the motor from tripping off, or simply to save electricity
during the winter, you might reduce the fan blade pitch.
One factor that does not reduce airflow is crushed fins at the top
of the tube bundle. Walking across a fin tube bundle will crush these
fins. It looks bad, but does not appear to affect cooling efficiency.
Take a close look at Fig. 17.2. Note that on the right side of the sketch
there is a small gap between the blade tip and the shroud. It is this
gap that accounts for the air recirculation previously described. The
bigger the gap, the greater the detrimental air recirculation. With age,
shrouds get out of round and the gap increases, but not uniformly.
The only way to seal off this gap is to use strips of plastic or Teflon
attached to the inner wall of the shroud. When the fan is turned on it
will cut through parts of the plastic strips and create its own seal.
Field results have been positive, and the strips can be purchased as a
retrofit kit from air cooler vendors.
of water by the dry air cools the surface of the fins; that is, the latent
heat of vaporization of the water robs sensible heat from the tubes.
Salts or other dissolved solids in the evaporating water will plate out
on the exterior of the tubes. With time, a serious loss in heat-transfer
efficiency results. Use of steam condensate can avoid this particular
difficulty.
Water sprays should be used only as a stopgap measure because
of the swell they cause in the plant’s effluent volume, and also their
tendency to create a safety hazard in the vicinity of the cooler.
One of my clients used fire water for a few hours to cool an air
cooler. The problem was the fire water was seawater. It proved
impossible to totally remove the salts from between the fins. The tube
bundles had to be replaced to restore efficiency.
Inlet Vent
Outlet Drain
Inlet
Fins
Pass partition
baffle
Threaded plug
Tubes
Outlet
25 psig
Out
145°F
25 psig
A B C D E
210°F 210°F
35 psig 35 psig
In
arrangement. Let’s assume that the inlet header is oversized and has
zero pressure drop. Let’s also assume that the outlet header is oversized
and also has no P. The pressure drop across the tube side of all such
air coolers arranged in parallel is then identical.
If one of the air coolers begins to experience tube-side fouling, the
fluid flow will be reduced. But the tube-side pressure drop will
remain the same. The pressure drop across all five air-cooler bundles,
shown in Fig. 17.6, is 10 psig.
Individual flows to parallel banks of air coolers are rarely—if
ever—measured. Regardless, we can gauge the approximate relative
flow to each bundle. This can be done by checking the outlet temperature
of the bundles or banks.
Let’s assume that the cooling airflow to all five banks is the same.
Banks A and B in Fig. 17.6 have low outlet temperatures. Banks C, D,
and E have much hotter outlets. Question: Which coolers are handling
most of the heat-transfer duty? Is it A and B or C, D, and E?
The correct answer is C, D, and E. Most of the flow is passing
through C, D, and E. Very little flow is passing through A and B.
Look at the combined outlet temperature from all five coolers. It is
145°F. This indicates that most of the total flow is coming from C, D,
and E—the banks with the higher outlet temperature. Very little of
the flow is coming from A and B—the banks with the lower outlet
temperature.
Why would the flow through A and B be so low? Apparently, their
tubes must be partly plugged. Corrosion products, gums, and dust are
common plugging agents. But when such exchangers foul, their
relative tube-side P, as compared to the other exchangers, remains
constant. But their relative tube-side flow, as compared to the other
parallel exchangers, decreases.
A: 105°F
B: 095°F
C: 170°F
D: 165°F
E: 180°F
If you are now willing to make the assumption that the airflow is
the same through the five coolers, we could calculate the process side
flow through each cooler. For example, percent flow through A =
20°F/290°F = 7 percent. This calculation assumes that the percent of
flow through the cooler is proportional to the air temperature rise
through the cooler divided by the total air temperature rise through all
five coolers.
It is not all that difficult to decide whether the airflow through
identical coolers is similar. I just wave a handkerchief in the breeze at
a few spots above the cooler.