TRANSFORMERS

EA 2616 CLIENT:- M/S CavinKare Pvt. Ltd., Test Report


Durga No. 12, Poonamalle Road,
Ekkaduthangal, Page No: 1a
Switchgears Chennai – 600 097.
Date of Test: 08th May 2016.

S.NO DESCRIPTION DETAILS

1. Equipment Description TRANSFORMER

2. Location OUTDOOR

3. Name plate data

Transformer Phases: 3PHASE


HV / LV: 11000 / 433 volts
Make: INDO TECH TRANSFORMERS
Serial No: IT 5755
Capacity: 500 KVA
Impedance Voltage: .4.75 %
Rated Voltage
Primary : 11000 VOLTS Maximum Temperature Rise
Secondary: 433 VOLTS In Oil: 50 C
In Winding: 55 C
Rated Current
Primary : 26.24 Amps Year Of Manufacture: 2004
Secondary: 666.71 Amps

Frequency: 50 HZ Oil Quantity: 520 litres

Voltage Group: Dyn 11


Type of Cooling: ONAN
No. of Taps : 9

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – FAULT LEVEL CALCULATION


NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051. PHONE : 9884320732
EA 2616 CLIENT:- M/S CavinKare Pvt. Ltd., Test Report
Durga No. 12, Poonamalle Road,
Ekkaduthangal, Page No: 1b
Switchgears Chennai – 600 097.

TEST REPORT FOR TRANSFORMER

Date of Test: 08th May 2016.


1. INSULATION RESISTANCE TEST

REFERENCE IR VALUES IN MEGA


OHMS
HV – EARTH 2000
LV – EARTH 400
HV - LV 2000

TESTED WITH 5 KV IR VALUE TESTER


MAKE : WACO
SL. NO. : 231937

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – FAULT LEVEL CALCULATION


NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051. PHONE : 9884320732
EA 2616 CLIENT:- M/S CavinKare Pvt. Ltd., Test Report
Durga No. 12, Poonamalle Road,
Ekkaduthangal, Page No: 1c
Switchgears Chennai – 600 097.
Date of Test: 08th May 2016.

TEST REPORT FOR TRANSFORMER


3.
RATIO TEST

VOLTAGE APPLIED ACROSS VOLTAGE MEASURED AT SECONDARY TERMINALS IN


TAP IN AC VOLTS AC VOLTS
POSITION 2r -2n 2y -2n 2b -2n 2r -2y 2y – 2b 2b -2r
1R-1Y 1Y – 1B 1B –1R

1 9.04 9.02 9.03 15.63 15.63 15.63


2 9.24 9.26 9.24 16.04 15.99 16.01
3 9.49 9.50 9.49 16.46 16.41 16.41
4 9.74 9.70 9.73 16.83 16.85 16.85
5 10.00 9.97 10.00 17.26 17.24 17.29
416 418 417
6 10.26 10.26 10.25 17.70 17.75 17.77
7 10.54 10.51 10.52 18.21 18.24 18.26
8 10.84 10.82 10.85 18.76 18.74 18.80
9 11.16 11.14 11.17 19.22 19.23 19.21

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – FAULT LEVEL CALCULATION


NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051. PHONE : 9884320732
EA 2616 CLIENT:- M/S CavinKare Pvt. Ltd., Test Report
Durga No. 12, Poonamalle Road,
Ekkaduthangal, Page No: 1d
Switchgears Chennai – 600 097.

TEST REPORT FOR TRANSFORMER

Date of Test: 08th May 2016.

3. SHORT-CIRCUIT TEST

VOLTAGE APPLIED IN AC
TAP VOLTS SHORT CIRCUIT CURRENT
POSITION ACROSS MEASURED IN AC AMPS
AT LV SIDE

1R-1Y 1Y-1B 1B-1R r y b n

1 470 462 464 19.0

4 418 417 416 499 492 483 18.9

9 501 505 494 19.2

4 . MAGNETIC BALANCE TEST

SINGLE PHASE
TAP POSITION VOLTAGE VOLTAGE MEASURED IN AC VOLTS
APPLIED
ACROSS 2r – 2n 2y – 2n 2b – 2n
2r -2n 221 122 86

4 2y -2n 100 218 108

2b – 2n 80 131 222

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – FAULT LEVEL CALCULATION


NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051. PHONE : 9884320732
EA 2616 CLIENT:- M/S CavinKare Pvt. Ltd., Test Report
Durga No. 12, Poonamalle Road,
Ekkaduthangal, Page No: 1e
Switchgears Chennai – 600 097.

TEST REPORT FOR TRANSFORMER

Date of Test: 21st April 2013

5. MAGNETISING CURRENT TEST:-

VOLTAGE APPLIED IN AC
TAP VOLTS MAGNETISING CURRENT
POSITION ACROSS MEASURED IN AC MILLIAMPS
1R-1Y 1Y-1B 1B-1R R Y B

4 421 424 422 22 mA 22 mA 22 mA

6. VECTOR GROUP TEST:-

STEP 1 - 1R AND 2r ARE SHORTED

STEP 2 - 3 PHASE VOLTAGE APPLIED ACROSS 1R – 1Y – 1B


1R-1Y 1Y-1B 1B-1R

424 421 423

STEP 3 - VOLTAGE MEASURED ACROSS


1Y – 2y ----- 428 VOLTS

1Y- 2b ------ 428 VOLTS

1B – 2y ------ 435 VOLTS

TO CONFIRM VECTOR GROUP Dyn 11 (1B -2y ) > (1Y – 2y)

AND POLARITY ( 1Y – 2y) = ( 1Y -2b)

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – FAULT LEVEL CALCULATION