CONTENTS
1. CHECKING POINTS BEFORE POWER ON........................................................................................................................................................................ 3
1.1. BOARD QUANTITY CHECK ..........................................................................................................................................................................................................................................3
1.2. ROM MOUNTING STATUS CHECK ...............................................................................................................................................................................................................................3
1.3. SWITCH SETTING STATUS CHECK................................................................................................................................................................................................................................4
1.3.1. DOC-200 PCB Switch Setting Status Check .......................................................................................................................................................................................................4
1.3.2. DOL – 200 & DOL – 210 Switch Setting Status Check.......................................................................................................................................................................................5
1.4. OTHER STATUS CHECK ...............................................................................................................................................................................................................................................8
4. EASY FUNCTIONS................................................................................................................................................................................................................. 14
4.1. VIRTUAL SWITCH INPUT FUNCTION ..........................................................................................................................................................................................................................14
4.2. DATA SETTING (INCLUDING SPEC) AND INQUIRY FUNCTION .....................................................................................................................................................................................15
4.3. TIME CHANGE FUNCTION OF GROUP MANAGEMENT SYSTEM ..................................................................................................................................................................................17
4.4. CHECK FUNCTION OF INDICATOR MOUNTED TO PLATFORM .....................................................................................................................................................................................18
4.5. TO MOUNT LCD .......................................................................................................................................................................................................................................................20
5. TROUBLE SHOOTING.......................................................................................................................................................................................................... 21
5.1. WHEN ELEVATOR INDICATOR FLICKERS....................................................................................................................................................................................................................21
5.2. WHEN ELEVATOR INDICATOR DOES NOT INDICATE FOR ALL FLOORS.......................................................................................................................................................................21
5.3. WHEN LIGHT DOES NOT TURN ON BY PRESSING HALL BUTTON .............................................................................................................................................................................22
5.4. WHEN HALL BUTTON FLICKERS ...............................................................................................................................................................................................................................22
-1-
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
APPENDICES .............................................................................................................................................................................................................................. 27
APPENDIX 1. LAYOUT OF DIP S/W AND LEDS OF DOL – 200 AND DOL – 210................................................................................................................................................................27
APPENDIX 2. SYSTEM STATUS FLAG CONFIGURATION .....................................................................................................................................................................................................28
APPENDIX 3. EXTERNAL DEVICE CONNECTION STATUS FLAG CONFIGURATION ..............................................................................................................................................................28
-2-
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
2) DOL-200 PCB
Note: Refer to ‘Appendix 1. Layout of DIP S/W and LEDs of DOL – 200 and DOL – 210’ for positions.
Hall Row DOL-200-A DOL-200-A DOL-210-B DOL-210-B
E2-27C256 E5-27C256 D9-27C256 D7-27C256
Number A1-27C256 A2-27C256 A1-27C256 A2-27C256
Main GNET 1st hall line 2nd hall line 3rd hall line 4th hall line 5th hall line 6th hall line
Secondary GNET
Description communication communication communication communication communication communication communication
ROM
ROM ROM ROM ROM ROM ROM ROM
1 Yes No Yes No No No No No
2 Yes No Yes Yes No No No No
3 Yes No Yes Yes Yes No No No
4 Yes No Yes Yes Yes Yes No No
5 Yes No Yes Yes Yes Yes Yes No
6 Yes No Yes Yes Yes Yes Yes Yes
-3-
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
SW7 Upper right Flash Write suppression Standard Set Pin1 and Pin2 to OFF
center
SW7 Upper right Flash Write suppression Standard Set Pin1 and Pin2 to OFF
center
-4-
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
1.3.2. DOL – 200 & DOL – 210 Switch Setting Status Check
-5-
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
2) DIP S/W Setting Examples
Example 1: When there are four elevators and four Hall Lines, Indicator of each elevator is connected to the left of each Hall Line.
In other words, car No. 1 is connected to the left of 1st Hall Line, car No. 2 to the left of 2nd Hall Line, car No. 3 to the left of 3rd Hall Line and car No. 4 to the left of 4th Hall
Line.
left left
Car No. 1 Car No. 2
left left
Car No. 3 Car No. 4
-6-
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
Example 2: When eight elevators are installed in six Hall Lines
Connections are applied as shown in the figure below (pay attention to the difference between 2nd Hall Line and 5th Hall Line)
-7-
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
1) Wiring Check
(1) Check management panel wiring status on the basis of provided management panel wiring diagram.
4) Make sure that ANN (LCD) is mounted to the ANN (lower right) of DOC-200 PCB.
-8-
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
-9-
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
SGWDT Slave CPU WDT status of GNET LON of DOL ON Error ⌦ LED status does not influence on the system (negligible)
OFF Normal
st
HGWDT1 Status of LON CPU controlling 1 Hall Line Flickering Normal ⌦ OFF status : Communication error between management panel & hall
PCB Abnormal operation status of LON controlling hall communication.
OFF Error
⌦ When all the LEDs are off: Check group management operation
ON Unused
If group management is operated, replace ROM (including GNET ROM)
HGWDT2 Status of LON CPU controlling 2nd Hall Line Flickering Normal If there are no improvements after ROM is changed, replace the board.
OFF Error ⌦ When a few LEDs are off: Failures in the ROM of LON controlling HNET
ON Unused or in the board. (Replace DOL-200 board or DOL-210 board.)
HGWDT3 Status of LON CPU controlling 3rd Hall Line Flickering Normal
OFF Error
ON Unused
th
HGWDT4 Status of LON CPU controlling 4 Hall Line Flickering Normal
OFF Error
ON Unused
th
HGWDT5 Status of LON CPU controlling 5 Hall Line Flickering Normal
OFF Error
ON Unused
th
HGWDT6 Status of LON CPU controlling 6 Hall Line Flickering Normal
OFF Error
ON Unused
- 10 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
5 A11A12 Bit information of incorporated elevator (hexadecimal) Ex) 03 Car No.1,2 07 Car No. 1,2,3 0F Car No.1,2,3,4
6 A14A15A16 Total floor (decimal) ⌦ Is the number of floors for which system can provide service complied with
installation spec?
7 B01~B06 Time recognized by the system (year, month, day) ⌦ Set the time of group management system to be coincident with present time when
8 B07B08 Time recognized by the system the time is not correspondent to the present time by using time setting function
[day of the week : 0(Sunday) ~ 6(Saturday)] ex) 2(Tuesday) provided by LCD.
9 B09~B14 Time recognized by the system (hour, minute, second)
10 C01~C08 Refer to the ‘Appendix 2. System Status Flag Configuration’.
11 C10~C13 Refer to the ‘Appendix 3. External Device Connection Status
Flag Configuration’.
12 D10~D12 OpCode in process OpCode in process
(Refer to the LCD manual for OpCode configuration) (Refer to the LCD manual for OpCode configuration)
13 D14~D16 Displaying the number of screens registered in the OpCode Displaying the number of screens registered in the OpCode in process
in process
A 01 : A 03 : A 05 : A 07 : A 09 : A 11 A 12 : A 14 A 15 A 16
B 01 B 02 B 03 B 04 B 05 B 06 B 07 B 08 B 09 B 10 B 11 B 12 B 13 B 14
C 01 C 02 C 03 C 04 C 05 C 06 C 07 C 08 : C 10 C 11 C 12 C 13
LCD Display
O p C o d e : D 10 D 11 D 12 / D 14 D 15 D 16
- 11 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
- 12 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
#8 #1
#8 #1
- 13 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
4. Easy Functions
1) Virtual switches are set by using LCD. The switches set by LCD are reflected in setting switch input status and provide the same environment as switches are actually input.
- 14 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
- 15 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
Start
Yes
Is data input finished? End
No
Note 1: Before key or Next key is recommended in
Address input
case of adjacent address.
A1
Yes
Check Pin3 of SW5 Check Pin2 of SW4 Error message output?
No
Note 2 : Address is input in eight-digit hexadecimal.
Note 3 : Data is input in four-digit hexadecimal.
No Check present data
Data change needed?
Yes
Data input
Set
- 16 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
A01 A02 A03 A04 A05 A06 A07 A08 A09 A10 A11 A12 A13 A14
Y Y M M D D W W H H M M S S
C01 C02 C03 C04 C05 C06 C07 C08 C09 C10 C11 C12 C13 C14
1 . I n 2 . S e t
- 17 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
- 18 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
9) Get on the elevator and set the Independent operation switch of OPB to On. From this time maintenance operation starts.
10) Register the Car Call of the floor press Close button until the elevator starts.
When the elevator arrives at the target floor, all devices (Indicator, Lantern, Hall Button etc.) mounted to the hall operate in a cyclical way.
12) If there is another floor subject to check, repeat the process from 10) to 11).
- 19 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
Start
No
Is it normal condition?
Yes
Power On
Replace LCD
Yes
End
- 20 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
5. Trouble Diagnosis
2) Measures
Step 1: Check all control panel spec to see whether same car ID is set or not.
Step 2: Check that DIP/SW of DOL-200 or DOL-210 is set correctly.
2) Measures
Step 1: Check the operating status of group management system and interface board (DOL-200).
Step 2: Check the starting status of control panel connected to the corresponding row.
Step 3: Check that button is registered by pressing Hall button.
Step 1-1: If Hall button is registered
Step 1-1-1: Check the connection between Indicator and Hall board.
If there is no problem in the connection, Hard Ware of Indicator is in failure.
Step 1-2: If Hall button is not registered
Step 1-2: Check the status of communication between Hall board and interface board(DOL-100) of corresponding floor by using the LCD of group management
system.
1) Diagnose the failure of communication with corresponding OpCode by using LCD OpCode 943(line 1 and 2), 944(line 3 and 4) and 945(line 5 and 6).
2) If communication is in failure, check the wiring of communication line and power line of Hall board.
3) If wiring is not in failure, Hard Ware of Hall board is in failure.
3) Ex: In the building where four elevators with four Hall rows are installed, one elevator with one indicator is placed on the left of each Hall Line. Car No. 1 is installed on the
left of row 1, car No. 2 on the left of line 2, car No. 3 on the left of line 3 and car No. 4 on the left of line 4.
- 21 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
The method of check when the indicator of car No. 1 does not show any information
(1) Change the setting of SW2-IO S/W1 from [PIN8]00000001[PIN1] to [PIN8][00000010[PIN1] to make sure the information of car No. 2 is displayed in the indicator of car
No. 1.
(2) If the information of car No. 2 is shown in the indicator of car No. 1 after performing (1), car No. 1 is in trouble or communication with car No. 1 does not work.
(3) If Indicator information is not shown even after the car information shown in the indicator of car No. 1 is changed by performing (1), DOL-200 board or DOL-210 board
may have problem. Check the communication by using the group management annunciator.
2) Measures
Step 1: If Hall buttons of other rows can not be registered
Step 1-1: Check that elevator is incorporated into group management panel. (Use LCD OpCode 750.)
Step 1-2: Check that service enable elevator is in the troubled button. (Select one among OpCode 610 to OpCode 647 of LCD)
Step 2: Check the power input status of group management panel and interface board (DOL-200).
Step 4: Check the connection status of Hall board. (Diagnose the failure of communication with corresponding OpCode by using LCD OpCode 943(line 1 and 2),
944 (line 3 and 4) and 945(line 5 and 6).)
Step 5: Check the call type setting status of Hall board. (Check the call type is set to one (K, L, M, N) not applied to the proper building.)
2) Measures
Step 1: Replace it with the button in other row not flickering and do the test. (Wait for three minutes.)
If it continues flickering: Button signal is being input continuously due to the error in the wiring of Hall button.
Step 1-1: Check Hall button and Hall board wiring.
- 22 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
2) Expected Causes
(1) Car ID is overwritten to cause the repeated cycle of incorporation and incorporation release. It brings about a repetition in which the ID is indicated when incorporated and
the ID is not indicated when incorporation is released.
(2) The conditions where incorporation and incorporation release shown in the above (1) are done repeatedly.
The above problem occurs if car ID is overwritten and any of the overwritten cars is not incorporated.
3) Measures
(1) Input OpCode 750 in the LCD.
Line Data Description
1 A/B/C/D/E/FF/GGG A: operating system/stand-by system (1: stand-by system) B: Operating MICOM down C: Stand-by MICOM down
2 HHIIJJKKMMNNOO (down when set to 1) D: operation mode E: Write Protection status (released when set to 1) FF: incorporated elevator
3 PPPPPPPP/QQQQ bit information GGG: running floor number HH~OO: present time(year, month, day, one of weekday, hour, minutes,
second) PP~PP: system status flag QQQQ: H/W connection status
(2) Check whether the data of FF changes repeatedly. For example, $01=>$00=>$01=>$00
(3) If the data changes repeatedly, Check the car ID.
- 23 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
- 24 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
5.7. When The LED For Communication With Monitor Panel Does Not Flicker
Measure 1: Check that the supervisory panel line is connected to the MD connector of DOC-200 board.
Measure 2: Check that the supervisory panel ID set in the SW6 of DOC-200 board is within 65 ~ 80.
Measure 3: Check that the group management ID set in the supervisory panel is equal to the value set in the SW6 of DOC-200 board.
Measure 2: Check auto parking status. (Elevator under automatic parking is excluded from parking)
(1) Check auto parking status by using LCD OpCode 105.
(2) Identify which elevator is under auto parking: ($1A1562)
5.10. When The Door Does Not Close Even Though Close Button Is Pressed
Measure 1: Check Close Button Suppression Status
(1) Check Close button suppression status by using LCD OpCode 120.
(2) Check Car Status→Close Button Cut($1B5D2A)
- 25 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
Symptoms Countermeasures
Car Call is changed but Hall Call is not changed when service floor is changed ⌦ Check that NonStop→Spec.CarSvcSpecCheck($199700) is not 0. It is normal when
in the monitor panel. it is not 0.
Stand-by system does not operate even though operation system is down. ⌦ Check that MB connector of operation system is wired to MB connector of wait system.
- 26 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
Appendices
Appendix 1. Layout of DIP S/W and LEDs of DOL – 200 and DOL – 210
TERM S/W
SW 2
SW 1
SW 2
D9-27C256
D7-27C256
E5-27C256
E2-27C256
ROM
ROM
ROM
ROM
A2-27C256 A1-27C256 A2-27C256 A1-27C256
ROM ROM ROM ROM
ZS6
2405
DC-DC CONV HGWDT6
HGWDT5
HGWDT4
HGWDT3
HGWDT2
HGWDT1
SGWDT MGWDT
- 27 -
DI Group Management, Installation and Document No: BS692EY -
Target Model: DGS-700 Preparation Date: April 01, 1998
Maintenance Manual Revision No: 0
- 28 -