Sunteți pe pagina 1din 10

Midos Type MVAJ

Tripping and Control Relays

Features
● High speed operation
● High and low burden alternatives
● Low burden models suitable for ac
and dc operation
● Models surge proof against high
capacitance discharge currents in
the dc supply system, are available
● Control relays immune to ac can be
supplied

Figure 1: Type MVAJ relay withdrawn from case

Models Available zero, whilst others incorporate a time burden which is either cut off at
delay to enable to series elements to operation or economised to a low
Type MVAJ relays may broadly be operate. This time delay is 40ms to figure, either instantaneously or after
divided into three groups: 60ms in all cases except that of the a time delay.
● High burden tripping relays types MVAJ 26 and 56 in which the The high burden provides immunity to
complying with ESI 48-4 Class EB2 delay is 2s. All low burden relays are capacitance discharge currents, which
● Low burden tripping relays which suitable for ac or dc operation. All can result at the inception of an earth
comply with ESI 48-4 Class EB1 high burden relays are for dc fault on battery wiring and immunity
operation only. to the subsequent leakage current.
● Control relays which meet the
requirements of National Grid Application The high burden also permits the use
Company SPEC.NGTS 2.19:1996 of supervision relays such as type
Table 1 lists the general High Burden Tripping Relays Types MVAX where the wiring is at risk and
characteristics and includes MVAJ 21, 23, 24, 25, 26, 27, 28, 29, provides reliable operation of series
information on how the relay burden 51, 53, 54, 55, 56, 57, 58 and 59 elements such as repeat relays
is modified at, or just after operation. These relays are suitable for use in type MCAA. For the latter purpose
‘Economy’ indicates that the burden is high security circuit breaker tripping type MVAJ relays can be provided
reduced to a low value. circuits. In particular they can be used with a time delayed economising
in distributed tripping or control relay feature.
Instantaneous cut off is a feature of
some hand and electrically reset contact logic schemes, where the
elements and reduces the burden to initiating contact may be remote from
the relay. The relays have a high

2
Relay Contact Operation Cut off Specifications Group Outgoing contacts Case size
type mechanism indicator single double single double
stack stack stack stack
MVAJ 11 SR H/R Economy ESI48-4 EB1 Low burden 5 10 4 4
MVAJ 13 HR H/R Instantaneous ESI48-4EB1 Low burden 5 10 2 4
MVAJ 14 ER H/SR Instantaneous ESI48-4EB1 Low burden 5* 10* 2 4
MVAJ 15 H/ER H/R Instantaneous ESI48-4EB1 Low burden 5* 10* 2 4
MVAJ 17 SR H/R Economy NGC SPEC.
NGTS 3.6.3:1992 Low burden 5 – 4 –
MVAJ 21 SR H/R Economy ESI48-4EB2 High burden 5 10 4 4
MVAJ 23 HR H/R Instantaneous ESI48-4EB2 High burden 4 10 2 4
MVAJ 24 ER H/R Instantaneous ESI48-4EB2 High burden 4* 9 2 4
MVAJ 25 H/ER H/R Instantaneous ESI48-4EB2 High burden 4* 9 2 4
MVAJ 26 SR H/R Time delay ESI48-4EB2 High burden 5 10 4 4
Economy
MVAJ 27 HR H/R Time delay ESI48-4EB2 High burden 9 4
MVAJ 28 ER H.R Time delay ESI48-4EB2 High burden 8 4
MVAJ 29 H/ER H/R Time delay ESI48-4EB2 High burden 8 4
MVAJ 34 ER S/R Instantaneous NGC SPEC. Control 7 4
NGTS 2.19:1996 in/out
4 stacks
MVAJ 41 SR H/R Economy ESI48-4EB1 Lowburden 20 Contacts
MVAJ 43 HR H/R Instantaneous ESI48-4EB1 Low burden 20 Contacts
MVAJ 44 ER H/SR Instantaneous ESI48-4EB1 Lowburden * 18 Contacts All in
MVAJ 45 H/ER H/R Instantaneous ESI48-4EB1 Lowburden * 18 Contacts size 8
MVAJ 51 SR H/R Economy ESI48-4EB2 Highburden 20 Contacts cases
MVAJ 53 HR H/R Instantaneous ESI48-4EB2 High burden 20 Contacts
MVAJ 54 ER H/R Instantaneous ESI48-4EB2 High burden 18 Contacts
MVAJ 55 H/ER H/R Instantaneous ESI48-4EB2 High burden 18 Contacts
MVAJ 56 SR H/R Time delay ESI48-4EB High burden 20 Contacts
Economy
MVAJ 57 HR H/R Time delay ESI48-4EB2 High burden 18 Contacts
MVAJ 58 ER H/R Time delay ESI48-4EB2 High burden 16 Contacts
MVAJ 59 H/ER H/R Time delay ESI48-4EB2 High burden 16 Contacts
KEY SR - Self reset HR - Hand reset ER - Electrical reset H/ER - Hand/electrical reset H/SR - Hand/self reset
Note: Relay types indicated * do not have continuously rated reset coils or internally wired cut-off contacts. If required, one pair of outgoing contacts may
be wired externally for this duty; this will obviously reduce the number of available contacts.

Table 1: List of MVAJ types available

Low Burden Tripping Relays Types connected directly to the dc supply via Description
MVAJ 11, 13, 14, 15, 41, 43, 44, 45 case terminals.
These relays are suitable for Since this reduces the necessary break High Burden Tripping Relays Types
applications where immunity to duty on the associated protection MVAJ 21, 23, 24,25, 26, 27, 28, 29,
capacitance discharge and high output relay, this feature is particularly 51, 53, 54, 55, 56, 57, 58 and 59
minimum operation currents are not useful when several tripping relays All relays use common standardised
required. are operated in parallel. parts. Versions have one, two or four
contact stacks depending upon the
Low Burden Self-reset Tripping Relay Control Relay Type MVAJ 34 number of output contacts required.
Type MVAJ 17 This is a dual-rated electrically reset
The type MVAJ 17 is a low burden relay, the main function of which is to
self-resetting tripping relay which switch protection and auto-reclosing
complies with the provisions of NGC equipment in and out of service from
SPEC. NGTS.3.63:1992. Its main a remote point via pilot wires. It
feature is the facility which allows the complies with NGC. SPEC.
economising element circuit to be NGTS 2.19:1996.

3
Types MVAJ 21, 51 high burden completely operated. This reduces the cannot conveniently provide an
self-resetting relays relay burden to zero as soon as auxiliary contact with a dwell time
These relays use a contact on the mechanical latching of the contacts long enough to ensure correct tripping
main contact stack to energise a has occurred. of the lower voltage circuit breaker.
separate, rear-mounted economising Types MVAJ 23 and 53 hand reset Typically the relay is initiated by
element. After operation this reduces whilst the types MVAJ 24 and 54 transformer protection, such as overall
the burden by switching in resistance have a second coil which, when differential, restricted earth fault, and
in series with the main element and energised, unlatches the relay Buchholz relays, in arrangements
switching out shunt resistance. resetting mechanism. Types MVAJ 25 where both the HV and LV circuit
Figure 2 shows a typical circuit and 55 may be reset either by hand breakers are to be tripped
diagram for self-resetting relays of this or electrically, by means of the same simultaneously.
type with high speed economy. When design of mechanism. See Figure 3. The HV circuit breaker may be
the main attracted armature unit RL1 is expected to trip more quickly than the
Type MVAJ 26 and 56 time delay on
energised by the protection contact LV breaker. So the tripping signal is
drop-off relays
PR, a contact RL1-a energises auxiliary maintained by the delayed resetting,
element RL2. When contacts RL2-a The types MVAJ 26 and 56 relays to ensure complete clearance by the
and RL2-b open, resistor R4 is put in have been specially designed for LV circuit breaker, even though the
series with RL1 while the circuit to applications requiring a tripping relay fault may have been cleared largely
resistor R2 is broken. which is self-resetting after a nominal by the HV circuit breaker and the
delay of 2 seconds. protection has started to reset.
Types MVAJ 23, 24, 25, 53, 54, 55 This relay may be used, for example, The MVAJ 26 and 56 relays can
high burden tripping relays with for intertripping between the higher accept either a fleeting initiation or
Instantaneous cut-off voltage and lower voltage circuit persistent initiation. With the latter,
These relays incorporate a break breakers of a large three phase the relay will provide a tripping signal
contact in series with the operate coil. power transformer. This may become of corresponding duration plus the 2
Located on the main contact stack, it necessary when the higher voltage seconds delay.
is arranged to break the coil circuit circuit breaker is tripped after a heavy
The relay consists of a main attracted
once the relay mechanism has internal fault, by protection which

Combination of output contacts


Left hand Right hand Combination L. Hand R. Hand
Note 1 10M 7 1
14 13 2 1 9M 1B 7 2
(a) CT shorting links make 16 15 4 3
17 6 5 8M 2B 7 3
before (b) & (c) disconnect 19 8 7
A 7M 3B 7 4
21 10 9
(b) Short terminals break before (c) 23 12 11 6M 4B 7 5
5M 5B 7 6
(c) Long terminals 4M 6B 8 4
RL2-A R1 (OP) 3M 7B 8 5
RL1
10 2M 8B 8 6
R4 RL2-B R2
Case earth
1 2 Rear mounted facing rear Output contacts to module terminals
3 4 viewed from front
5 6
Contact Module terminals
7 8
stack
L. hand 13 17 21 14
9 10 A B 15 19 23 16
11 12
R. hand 1 5 9 2 6 10
13 14 3 7 11 4 8 12
15 16 RL1-A R3 1 M M M M M M
RL2
17 18
PR 27 2 M M M B M M
19 20 + 3 B M M B M M
21 22
4 B M M B B M
23 24
5 B B M B B M
25 26
6 B B M B B B
27 28 Vx
V 7 M M M M
8 B B M B
Module terminal block
viewed from rear _ 28 Contact Description
M : Make
B : Break

Figure 2: MVAJ 21 self-reset with instantaneous economy (high burden)

4
armature element with a hand reset copper slug fitted to the front of RL2(t).
operation indicator and one When RL2(t) resets, RL2-a opens,
electromagnet with two contact stacks. reducing the current through RL1
Types MVAJ 27, 28, 29, 57, 58, 59 (operate) coil to zero.
relays with time delayed drop-off. The relay is now latched mechanically
These relays are hand reset, into the operated state. It may now be
electrically reset and hand/electrically reset via an external contact or push-
reset respectively and all have time button which energises the RL1 (reset)
delayed cut-off circuits. The burden is coil via the closed contact RL1-c.
reduced to zero 40/60ms after
Low Burden Tripping Relays Types
energisation by the use of a second
MVAJ 11, 13, 14, 15, 41, 43, 44, 45
attracted armature element mounted in
the rear of the case. This time delay These are low burden versions of
allows ample time for any flagging or types MVAJ 21, 23, 24, 25, 51, 53,
auxiliary element in series with the 54 and 55 relays respectively. They
tripping relay to operate before cut-off. comply with the less onerous
requirements of ESI 48-4, Class EB1.
Figure 4 shows a typical circuit
diagram for an electrically reset trip Where self-reset reverse flags are
relay with time delayed cut-off feature. fitted, a maximum of 8 output contacts
is available. The operating time is not
When the contact PR is closed, relays
greater than 15ms
RL1 (operate) and RL2(t) operate.
After operation the current in the coil
of RL1 (operate) is maintained by
contact RL2-a; contacts RL1-a and
RL1-b open, whilst RL1-c closes. The
opening of RL1-a causes relay RL2(t)
to start to reset. This resetting is
delayed by 40-60ms by means of a

Table 1
Combination of output contacts
RL1 RL2
Combination R. L. R. L.
Case earth Front mounted facing front Front mounted facing front Hand Hand Hand Hand
viewed from front viewed from front 18M 1 2 1 2
1 2 29 30
Left hand Right hand Left hand Right hand
3 4 31 32
5 6 33 34 42 41 30 29 14 13 2 1 Table 2
7 8 35 36 44 43 32 31 16 15 4 3 Output module to module terminals
9 10
45 34 33 17 6 5
37 38 47 36 35 19 8 7
A A Contact Module terminals
11 12 39 40 38 37 10 9 stack
B 40 39 B 12 11
13 14 41 42
LH 41 45 42
15 16 43 44 43 47 44
RL1
17 18 45 46 Vx RH 29 33 37 30 34 38
31 35 39 32 36 40
19 20 47 48 + PR 27
RL1-A
R1 (OP) (OP) 28
– LH 13 17 14
21 22 49 50 RL1 RL2 RL2 15 19 16
23 24 51 52 9 9 RH 1 5 9 2 6 10
3 7 11 4 8 12
25 26 53 54
RL2-A 1 M M M M M M
27 28 55 56
2 M M M

Module terminal block Contact description


viewed from rear Reset 25 RL1-B (Reset) 26 M : Make
RL1 B : Break
RL2-B (Reset)
RL2 Note:
The numbers quoted in table 1
Note 1 are for L. hand and R. hand stacks on
(a) CT shorting links make RL1 and RL2. The code numbers used
before (b) & (c) disconnect are for cross references to module
terminals in table 2.
(b) Short terminals break before (c)

(c) Long terminals

Figure 3: MVAJ 55 hand and electrically reset (high burden)

5
Combination of output contacts
Front mounted facing front Combination L. Hand R. Hand
viewed from front 8M 8 1
Left hand Right hand 7M 1B 8 2
6M 2B 8 3
A 13 2 1
15 4 3 5M 3B 8 4
17 6 5 4M 4B 8 5
Case earth B 19 8 7
C
10 9 3M 5B 8 6
Vx 12 11
1 2 2M 6B 8 7
3 4 + – 1M 7B 9 6
5 6
8B 9 7
7 8 PR 27 RL1-B R1 RL1 (OP) 28
9 10 8
11 12
RL2-A R2
13 14
Output contacts to module terminals
15 16
17 18 Contact Module terminals
Reset 25 RL1-C RL1
(Reset) 26 stack
19 20
8 L. hand 13 17
21 22
15 19
23 24 Rear mounted facing rear
viewed from front R. hand 1 5 9 2 6 10
25 26 3 7 11 4 8 12
27 28 1 M M M M M M
A 2 M M M B M M
3 B M M B M M
Module terminal block RL1-A R3 (t)
viewed from rear 4 B M M B B M
RL2
5 B B M B B M
Note 1 6 B B M B B B
(a) CT shorting links make 7 B B B B B B
before (b) & (c) disconnect 8 M M
9 B B
(b) Short terminals break before (c)
Contact Description
(c) Long terminals
M : Make
B : Break

Figure 4: MVAJ 28 electrically reset with time delayed cut off (high burden)

Table 1
Front mounted facing front Combination of output contacts
viewed from front
Combination L. Hand R. Hand
Case earth Left hand Right hand
10M 7 1
1 2
14 13 2 1 9M 1B 7 2
3 4 16 15 4 3 8M 2B 7 3
5 6 17 6 5
19 8 7 7M 3B 7 4
7 8 A 21 10 9
9 10 23 12 11 6M 4B 7 5
11 12 5M 5B 7 6
13 14 4M 6B 8 4
15 16 RL1-A R1 (OP) 3M 7B 8 5
RL1
17 18 10 2M 8B 8 6
19 20 PR 27
21 22
23 24
Table 2
25 26
27 28 Output contacts to module terminals
Vx Contact
V Module terminals
stack
Module terminal block L. hand 13 17 21 14
viewed from rear 28 15 19 23 16
R. hand 1 5 9 2 6 10
3 7 11 4 8 12

Notes 1 M M M M M M
2 M M M B M M
1. (a) CT shorting links make 2. Resistor fitted on
3 B M M B M M
before (b) & (c) disconnect 220/250V versions only
4 B M M B B M
3. The numbers quoted for L. hand
(b) Short terminals break before (c) 5 B B M B B M
and R. hand stacks in table1 are
6 B B M B B B
code numbers used for cross
(c) Long terminals 7 M M M M
references to module terminals
in table 2 8 B B M B

Contact Description
M : Make
B : Break

Figure 5: MVAJ 13 hand reset (low burden)

6
Technical Data
Ratings
All relays except MVAJ 17. Rated Operative range
and MVAJ 34 voltage (V)
(Vx)
24/27 14.4 – 32.4
30/34* 18 – 40.8
48/54* 28.8 – 64.8
110/125* 66 – 150
220/250 122 – 300
MVAJ 17 110/125 66 –150
MVAJ 34 dual rated 0Ω pilot 200Ω pilot
48/54 37.5 – 60 46 – 56
110/125 87.5 –137.5 87.5 – 137.5
220/250 122 – 286 175 – 275
*These ranges only are applicable to ESI 48-4

Burdens
Burden (W)
To operate Operated To reset Minimum
Relay Single Double Single Double operating
type stack stack stack stack current (mA)
MVAJ 11 25 50 10 – – 25
MVAJ 13 25 50 – – – 25
MVAJ 14 25 50 – 15 25 25
MVAJ 15 25 50 – 15 25 25
MVAJ 17 25 (See Note 2 below) 25
MVAJ 21 150 150 10 – – 100
MVAJ 23 150 150 – – – 100
MVAJ 24 150 150 – 50 50 100
MVAJ 25 150 150 – 50 50 100
MVAJ 26 150 150 12.5 – – 100
MVAJ 27 – 150 – – – 100
MVAJ 28 – 150 – – 50 100
MVAJ 29 – 150 – – 50 100
MVAJ34 10 – 10 25
(See 25 – 25 25
Note 3 below) 50 – 25 25
MVAJ 41 50 12.5 – 25
MVAJ 43 50 – – 25
MVAJ 44 50 – 45 25
MVAJ 45 50 – 45 25
MVAJ 51 150 15 – 100
MVAJ 53 150 – – 100
MVAJ 54 150 – 70 100
MVAJ 55 150 – 70 100
MVAJ 56 150 12.5 – 100
MVAJ 57 150 – – 100
MVAJ 58 150 – 70 100
MVAJ 59 150 – 70 100
Note 1: Minimum operating current for relays specified in ESI 48-4 Class EB1 is
25mA and in EB2 is 50mA for 110V dc rating
Note 2: The burden of the relay before it economises is less than 25W,
reducing to 2.1W after. The auxiliary, which is fed from a separate
supply, remains at 3.85W.
Note 3: The 3 sets of burdens quoted for MVAJ 34 apply to the 48/54,
110/125 and 220/250V versions respectively.

7
Operating time
MVAJ 11–15 fitted with
self reset reverse flags 15ms
All other types Not greater than 10ms at rated
voltage

Operation indicator
MVAJ 34 The operation indicator follows the
relay operation.

Contacts The number of contacts available is


shown in Table 1. They may be any
combination of make type and break
type but with a maximum of 8 break.

Contact ratings
Make and carry for 3s ac 7500VA with maxima
of 30A or 300V
dc 7500W with maxima
of 30A or 300V
Make and carry continuously ac 1250VA with maxima
of 5A or 300V
dc 1250W with maxima
of 5A or 300V
Break ac 1250VA with maxima
of 5A or 300V
dc 100W resistive
50W inductive with maxima
of 5A or 300V

Withstand Ratings
MVAJ 17 The relay shall not operate when a
1µf capacitor charged to 150V is
discharged into its operate circuit.
The relay is continously rated
at 150V dc.
MVAJ 34 Operation/resetting does not occur
when 100V ac rms 50/60Hz is
applied to the respective coil circuits.
The relay (at 50V range or above)
will operate with pilot wires
having a resistance of 200Ω.
MVAJ 21 – 29 & 51– 59 These relays will withstand without
operating, the discharge into their
operate circuits of a 10µF capacitor
charged to a voltage equal to the
highest in the operative range for the
relay
All relays are continously rated with
the exceptions listed in Table 1.

Specifications
MVAJ 17 NGC SPEC.NGTS 3.6.3:1992
MVAJ 34 NGC SPEC.NGTS 2.19:1996
All other relays IEC 255

8
High Voltage withstand
Dielectric withstand
IEC 255-5:1977 2kV rms for 1 minute between all
terminals and case earth.
2kV rms for 1 minute between
terminals of independent circuits
including contact circuits,with
terminals on each independent circuit
connected together.
1kV rms for 1 minute across open
contacts of output relays.
High voltage impulse
IEC 255-5:1977 Three positive and three negative
impulses of 5kV peak, 1.2/50 µs,
0.5J between all terminals and all
terminals and case earth.
Electrical environment
High frequency disturbance
IEC 255-22-1:1988
Class III 2.5kV peak between independent
circuits and case.
1.0kV peak across terminals of the
same circuit.
EMC compliance
89/336/EEC Compliance to the European
Commission Directive on EMC
is claimed via the Technical
Construction File route.
EN 50081-2:1994
EN 50082-2:1995 Generic Standards were used to
establish conformity.
Product safety
72/23/EEC Compliance with European
Commission Low Voltage Directive
EN 61010-1:1993/A2:1995 Compliance is demonstrated by
EN 60950:1992/A3:1995 reference to generic safety standards.
Atmospheric environment
Temperature
IEC 255-6:1988 Storage and transit -25°C to +70°C
Operating -25°C to +55°C
IEC 68-2-1:1990 Cold
IEC 68-2-2:1974 Dry Heat
Humidity
IEC 68-2-3:1969 56 days at 93% RH and 40°C
Enclosure protection
IEC 529: 1989 IP50 (dust protected)
Mechanical environment
Vibration
IEC 255-21-1:1988 0.5g between 10Hz and 150Hz
Mechanical durability
Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum

9
13
4 holes 4.4 24
45

168 159

Push button 48
projection 10 max
Panel cut-out:
Flush mounting fixing details

32 212 25 min.

177 157 max.

Reset

51 Flush mounting
All dimensions in mm

Figure 6: Case outline size 2

52
4 holes 4.4 23.5
97

168 159

Push button 99
projection 10 max
Panel cut-out:
Flush mounting fixing details

32 212 25 min.

177 157 max.

Reset

103 Flush mounting 11


All dimensions in mm

Figure 7: Case outline size 4

10
155.4
4 holes 4.4 24
200

168 159

Push button 203


projection 10 max
Panel cut-out:
Flush mounting fixing details

32 212 25 min.

177 157 max.

Reset

206 Flush mounting 11


All dimensions in mm

Figure 8: Case outline size 8

Cases Information Required with


Order
MVAJ relays are housed in size 2, 4
or 8 cases as indicated in Relay type
Table 1. Dimensions for these cases Voltage rating
are shown in Figures 6, 7 and 8 Number and combination of contacts
respectively. for tripping duties
Hand reset operation indicator
required
Instantaneous or time delayed cut-off
contact

11

S-ar putea să vă placă și