Specification

ZISE##-TFI48GB-A
Safety Instructions (continue)

Installation & Maintenance Manual


• Insert a noise filter (line noise filter, ferrite element or other element)
Series ZSE 30 (Vacuum, Low Pressure) ISE 30 (Positive Pressure) ZSE 30 ISE 30
between the switching regulator and pressure switch when analog

Digital Pressure Switch


Rated Pressure Range -100.0 to 100.0kPa 0.000 to 1.000MPa 12 to 24VDC, ripple (p-p) 10% or less
output is used. Power Supply Voltage

Series ZSE30/ISE30
• Do not use with a corrosive or inflammable gas or liquid. Set Pressure Range -101.0 to 101.0kPa -0.100 to 1.000MPa (Protected against inverse connection)
• Do not press the setting buttons with a sharp pointed object. Withstand Pressure 500kPa 1.5MPa Current Consumption 45mA or less (With no load)
• Turn power on for 20 to 30 minutes before detecting fine pressure. Minimum Display Unit 0.2kPa 0.001MPa Switch Output (See NOTE 1) NPN or PNP open collector output. 1 output
Initial drift of about ±1% occurs immediately after turning the power on. Applicable Fluid Air, inert gases and Non-flammable gases Maximum Load Current 80mA

Safety Instructions
• The direct-current power supply to combine should be a UL Temperature Characteristic ±2%F.S. or less (25ÞC reference) Maximum Impressed Voltage 30V (During NPN output)
authorization class 2 power supply based on UL1310, or a power Enclosure IP40 (IEC60529) Residual Voltage 1V or less (at 80mA load current)
supply using a transformer which is class 2 based on UL1585. Ambient Operation: 0 to 50ÞC, Storage:-10 to 60ÞC 2.5ms or less (anti-chatter function working: 20, 160,
• Only a pressure switch with UL mark on the body is UL approved. Response Time
The Digital Pressure Switch and this manual contain essential Temperature Range (No condensation or freezing) 640 or 1280ms selectable)

Environmental Resisitance
information for the protection of users and others from possible • This pressure sensor is for use with air only. Please contact SMC if Ambient Humidity Operation·and Storage:35 to 85%RH Short Circuit Protection Provided
the switch is to be used with other fluids.
injury and property damage and to ensure correct handling. Range (No condensation) Repeatability ±0.2%F.S. ±2 digits or less ±0.2%F.S. ±1 digit or less
Please check that you fully understand the definition of the following 1000VAC ,1 minute Output Voltage:1 to 5V ±2.5%F.S. or less
Withstand Voltage Voltage
messages (signs) before going on to read the text, and always (between live parts and case) (within rated pressure range)
Output
follow the instructions. Insulation 50M or more (at 500VDC M) Linearity:±1.0%F.S. or less
(See NOTE 2)
Resistance (between live parts and case) Output impedance: about 1k

IMPORTANT MESSAGES For one-touch fitting type:


10 to 150Hz, 1.5mm or 20m/s2 double amplitude, Analog Output Current: 4 to 20mA ±2.5%F.S. or less
Vibration proof
2 hours each indirections of X, Y and Z Output (within rated pressure range)
Current
Read this manual and follow its instructions. Signal words such • Do not apply unnecessary forces such as twisting, pulling, moment 100m/s2, 3 times each in directions of Linearity:±1.0%F.S. or less
loads, etc. on fitting or tubing. Impact proof Output
X, Y and Z respectively Maximum Load Impedance: 300 at power supply
as WARNING and NOTE, will be followed by important safety • When using a brand of tubing other than SMC, be careful of the (See NOTE 3)
Standards CE Marked, UL/CSA(E216656) voltage of 12V, 600 at 24V
information that must be carefully reviewed. tolerance of the tube’s O.D. Minimum Load Impedance: 50
Indicates a potentially hazardous situation 1) Nylon tube ±0.1mm Hyste- Hysteresis Mode
which could result in death or serious injury 2) Soft nylon tube ±0.1m Variable(From 0)
Piping Type 01 T1 C4H C6H N7H C4L C6L N7L resis Window Comparator Mode
if you do not follow instructions. 3) Polyurethane tube +0.15mm, -0.2mm
R1/8 NPT1/8 3.5 digits 7-segment display, dual-color display
Port Size M5 0.8 M5 0.8
- - - - - - Display Method
(red/green) Sampling rate: 5 times/ 1s
Gives you helpful information. One-touch Fitting Display Accuracy (at 25oC) ±2%F.S. ±2 digits ±2%F.S. ±1 digit
4mm
- - 5/32inch
6mm 1/4inch - - -
Strait Type Indication Light Lit when ON (Green)
One-touch Fitting 4mm NOTE 1: Analog output cannot be selected when switch output is selected.
- - - - - 5/32inch
6mm 1/4inch
Elbow Type NOTE 2:Both switch output and current output cannot be selected simultaneously when
Oring:HNBR voltage output is selected.
Material for Fluid
Pressure sensing part: silicon, Piping port: C3602(Electroless nickel plated) NOTE 3:Both switch output and voltage output cannot be selected simultaneously when
Contact
O ring: NBR O ring: NBR, Fitting Part: PBT current output is selected.
Including lead wire 81g 76g 78g

Weight
with connector (2m)
Excluding lead wire 43g 38g 40g
with connector

Model Indication Method Names and Functions of Individual Parts


Do not disassemble, modify (including change of printed
circuit board) or repair.
Main Unit
An injury or failure can result.
30- - - Indication Light : Displays switch operation condition.
Pressure Range Option 2
Do not operate outside of the specification range.
(Green Light)

Option 1
LCD Display : Displays the current status of pressure, setting mode,
ISE For Positive Pressure No Symbol None
selected indication unit and error code. Four display
Fire, malfunction or switch damage can result.
Do not operate in atmosphere of inflammable, an
ZSE
Piping Specification
For Vacuum or Low Pressure No Lead Wire Bracket
modes can be selected: display always in red or green
explosive or corrosive gas.
No
A only, or changing from green to red linked to output.
01 R1/8 (M5 female thread)
Symbol Button : Selects the mode or increases ON/OFF set value.
Fire, an explosion and corrosion can result. Press this button to change to the peak display mode.
This pressure switch is not an explosion-proof type.
Do not use this product in a place where static electricity
Button : Selects the mode or decreases ON/OFF set value.
Output Specification
Panel Mount Adapter
T1 NPT1/8 (M5 female thread)

is a problem.
Press this button to change to the bottom display mode.
25 NPN Output Lead Wire with Button : Press this button to change to either mode and to set a
C4H One-touch fitting Ø4mm,Ø5/32inch Connector(Length: 2m)
Otherwise It can cause failure or malfunction of the system. 65 PNP Output B set value.
C6H One-touch fitting Ø6mm Straight Type 26 1-5V Output

NOTE
LCD Display
28 4-20mA Output
N7H One-touch fitting Ø1/4inch Indication Light
Panel Mount Adapter + Front Protection Cover
Follow the instructions given below when handling the pressure C4L One-touch fitting Ø4mm, Ø5/32inch Button
switch.
Units Specification
Button
Otherwise, the switch may be damaged or may fail, thereby C6L One-touch fitting Ø6mm
Elbow Type
resulting in malfunction. M SI Units Only (Note 1)
Button
• Do not drop, bring into collision with other objects or apply N7L One-touch fitting Ø1/4inch D
No Symbol With Unit Selection Function (Note 2)
excessive shock to the unit (100m/s2 or more).
• Do not pull the lead wire with force or lift the main unit by holding Set pressure range and Rated pressure range Note 1) Fixed Unit For Vacuum, Low Pressure: kPa
the lead wire. (Pulling strength less than 35N) Set the sensor pressure with the rated pressure range For Positive Pressure: MPa
Note 2) Product with unit selection function cannot be
• Do not insert wire or other articles into the pressure port. "Set pressure range " means the pressure range that can be set.
used in Japan due to new Measure Law issued.
• Connect wires and cables correctly. "Rated pressure range" means pressure range that satisfies the product
• Do not perform wiring while power is on. specifications (accuracy, linearity, etc.)
Setting outside of the Rated pressure range could be set if the setting is within the Use the following product codes when optional items are needed as
• Do not wire with power cable or high-voltage cable in the same wire separate products.
route. Withstand pressure range, but the specified performance is not always realized.
Pressure Range
• Connect Terminal FG to ground when using a switching regulator Switch
-100kPa 0 100kPa 500kPa 1MPa Lead Wire with Connector ZS-27-A Length: 2m L
For
obtained on the commercial market.
vacuum or
-100kPa 100kPa Bracket ZS-27-B Mounting Screw (M3x5L, 2 pcs) A
Low
ZSE30
Pressure
-101kPa 101kPa Panel Mount Adapter ZS-27-C M3x8L, 2 pcs attached B

For Positive
Panel mount Adapter + Front Protection Cover ZS-27-D M3x8L, 2 pcs attached D
Pressure
0 1MPa
ISE30 Front Protection Cover ZS-27-01 - -
-100kPa 1MPa
(-0.1MPa)
Rated Pressure Range of a Switch
Set Pressure Range of a Switch
Outline with Dimensions (in mm) Outline with Dimensions (continue) Installation(continue)
ZISE##-TFI48GB-A

Dimensions of Main Unit Panel mounting of adjacent switches • Mounting with Panel Mount Adapter and Front Connection
30 25 8 9.5
Lead wire with 2-M3 0.5 n : The number of switches Protection Cover • Make connection after turning the power off.
3.6 20 0.1 • Install the lead wire separately from the route for power cable or
Horizontal
connector Depth 4
Panel high-voltage cable. Otherwise, malfunction may potentially result

20 0.1
Front Protection Cover due to noise.
10

(ZS-27-01)
Pipe Port • Be sure to ground Terminal FG when using a switching regulator
obtained on the commercial market. If the analog output is
01:R1/8 Pipe Port
1.5 connected to a switching regulator obtained on the market, switching
T1:NPT1/8 M5 0.8 31 n+3.5 ( n-1)
noise will be superimposed and product specification can no longer

Details of Pipe Fitting Part


Refer to the following diagrams for pipe fitting part. be met. This can be prevented by inserting a noise filter, such as a

31 -0.4
line noise filter and a ferrite element, between the switching regulator

0
and the pressure switch, or by using a seriespower supply instead of
01 Type T1 Type
a switching regulator.

more than 24
Refer to the above Refer to the above
R1/8 pipe fitting part NPT/8 pipe fitting part
Panel Mount Adapter plus Front Protection Cover
14.4 20 (Article No.ZS-27-D)
C4H Type C4L Type

Notice when removing the switch Connector Connecting/Disconnecting


Ø4. Ø5/32[inch] Ø4. Ø5/32[inch]

• The Digital pressure switch with panel mount adapter


One-touch fitting One-touch fitting

can be removed from panel by releasing the hooks at


18
Vertical
elbow type
11.2

• When connecting the connector, insert it straight onto the pins and

the switch sides


10.4 lock the connector into the square groove in the housing unit

as illustrated.
C6H Type C6L Type
0
31 -0.4 more than 24 connector clicks.
14.4 22.4
• When disconnecting the connector, press the connector lever to
Pressure switch disengage the lever claw from the square groove. Then pull the
Ø6
Ø6 and Panel mount connector straight out.
One-touch fitting
One-touch fitting adapter may be
elbow type

31 n+3.5 ( n-1)
20

Housing
damaged if not
11.2

Square Groove
12.8 released correctly. Pin
Lever
N7H Type 14.4 N7L Type 22.8 DC Polarity Mark

Lead Wire (Brown)


Ø1/4[inch] Ø1/4[inch]
Hook
One-touch fitting One-touch fitting
20.5

Connector Lead Wire (Blue)


elbow type
11.2

13.2

Mounting hardware Installation Internal Circuit and Wiring


Bracket
30 View from Top • Mounting with Bracket Pipe Connection (One-touch Fitting Type) Output Specification
Caution :Tighten the pipe port to a torque of 7 to 9N·m.
20 1.Cut the tube perpendicularly. When the Lead wire with connector provided by SMC
2.Hold the tube, slowly push it into the one-touch fitting until it CORPORATION is used, the colors of wire (Brown, Black, Blue) will
Fasten the bracket mounting screws to a torque of 0.5
40

comes to a stop.
20

42.5

apply as shown on circuit diagram.


45

to 0.7N·m.
10
15
30

4.2

Brown DC (+)
1.8

3 Mount the bracket on the main unit using the two mounting screws -25
Tube Load

Main Circuit
22 M3 5L and install on NPN Open Collector Output + 12
35 to
the facility using Max. 30V, 80mA Black OUT
- 24VDC
hexagon socket head M3x5L
Residual Voltage not exceeding
cap screws. 1V
Panel mount adapter
Blue DC (-)
One-touch Fitting
Panel Cut Dimensions for Bracket
Panel Mounting (Article No. ZS-27-B)
34.5 7.2 17.8 8 9.5 Brown DC (+)
0
31 -0.4 -26

Main Circuit
Black OUT
M3x5L Analog Output Type (Analog Output) + 12
1 to 5V (±2.5% F.S.) - to

• Mounting with Panel Mount Adapter


Load Impedance : Approx. 1k Load 24VDC

8.75 Blue DC (-)


Panel Thickness
0.5 to 6mm
-28 Brown DC (+)
Analog Output Type
Panel mount adapter and Front protection cover

Main Circuit
Black OUT
4 to 20mA (±2.5% F.S.) (Analog Output) + 12
Maximum Load Impedance : to
-
Load 24VDC
11 17.8 8 9.5 300 at 12V power supply voltage
42.4
34.5 600 at 24V power supply voltage Blue DC (-)
Minimum Load Impedance : 50
Brown DC (+)
Panel mount -65

Main Circuit
adapter can be PNP Open Collector + 12
rotated 90 degrees Max. 80mA Black OUT to
- 24VDC
Panel Thickness: 0.5 to 6 mm Panel Mount Adapter to be attached.
(Article No. ZS-27-C) Load

Blue DC (-)
Setting Pressure Setting
ZISE##-TFI48GB-A

Setting Procedures If set to Manual Setting Window comparator mode setting


3.Output Mode Setting
Measurement Mode
The desired output mode can be set for switch output. flicker flashing
The output mode currently selected will be displayed.
Press the or button to switch to normal output “no” or
reverse output “nC”.

Initialize
no nC
Press the SET button while in Measurement mode to display set If the Window comparator mode is set, “P2” or “n2” and the current

(Normally open) (Normally closed)


Set output mode, response time and display color change. values. “P_1” or “n_1” and the current set value will display set value will be displayed alternately (after the setting for “P1” or
alternately. Press the button to move to the next set value, or “n1”). Press the button to move to the next set value.

Pressure Setting
Press the button to set and move to response time setting. Press the or button to enter into the Value Change mode. (Hysteresis : H)
(See “Value Setting” )

Hysteresis mode setting


flashing
Input a set value for pressure to perform switch output.

4.Response Time Setting


flashing
Measurement Mode
Press the or button to enter into the Value Change mode.
The response time for switch output can be set. (See “Value Setting” )
Detects pressure, displays values and performs switching. Setting of the response time prevents chattering of
If the Hysteresis mode is set, “H” and the set value of Hysteresis will be Next, “H” and the set value of Hysteresis will be displayed
Other functions such as zero clear can also be set if necessary. the output.
displayed alternately (after the setting for “P1” or “n1”). alternately. Press the button to return to the normal
The response time currently set will be displayed. Select the Measurement mode, or Press the or button to enter into the
Press the button to return to Measurement mode, or

Initialize
desired response time by pressing the or button.
2.5 20 160 640 1280
Press the or button to enter into the Value Change mode. Value Change mode. (See “Value Setting” )
(See “Value Setting” ) If the initialize setting is Normally Open mode, “P_1” will be
Press and hold the button for more than two If set to Normally Open Mode If set to Normally Closed Mode displayed. “n_1” will be displayed if it is Normally Closed mode.
seconds. The display shown at the lower right will If the operating mode is set to Hysteresis, press button to set The set pressure value can be checked without holding or stopping
Switch Output Set value of Hysteresis (H) Switch Output Set value of Hysteresis (H)
allow the setting of the display color. and move on to setting Auto Preset mode. ON ON switch output operation.

If set to Normally Open Mode If set to Normally Closed Mode


When the units specification of model indication is - If the operating mode is set to Window comparator, press OFF OFF
M, the SI units will be fixed. If no symbol is supplied, button to set and return to Measurement mode.
P1 High pressure n1 High pressure
see “Selecting Indication Unit”. Switch Output Set value of Hysteresis (H)
Set value of Hysteresis (H)
Switch Output
ON
ON
When the Hysteresis is set at less than or equal to 2 digits, the OFF
OFF
switch output may chatter if input pressure fluctuates near the P1 P2 High pressure n1 n2 High pressure
set point.

1.Display Color Setting 5.Auto Preset Setting Pressure Setting (continue)

Auto Preset Mode setting


Select a color for the LCD display.

Fine Adjustment Mode


This function is used to memorise a measurement
When changing the display color, press the or pressure as a reference value when Auto Preset input is set.

Sor (Red/ON) SoG (Green/ON) rEd (Red) Grn (Green) (Fine Adjustment Function of Display Value)
button to select a display color. The settings currently set will be displayed. Press the or Press the button while in Measurement mode to
button to set to Auto Preset mode. select the Auto Preset mode. “AP1” will be displayed. Prepare a
Press the Press the button and buttons switch unit for which pressure is to be set. Press the and
button to set the desired display color and to move on to setting a simultaneously for longer than two seconds while in
mAn AUt
buttons simultaneously while “AP1” is displayed to return to the
desired operation mode. Measurement mode. “FSt” and the current pressure
(Manual Setting) (Auto Preset)
Measurement mode.
If the mode is set to analog output, press the or button, Measurement value will be displayed. Press the or To execute Auto Preset, press the button and “A1L” will be
to select a desired display color from button to change the set value. If no operation is made for displayed. Perform adsorption and desorption operations.
“Grn” (Green) “rEd” (Red), then press the button to set. Press the button to set and return to Measurement mode. longer than two seconds or the button is pressed, the Detection will be made and a set value will be stored in the memory
The display will move to operation mode setting. display will return to the current pressure Measurement value automatically. Press the button while “A1L” is displayed to
which will then display alternately with “FSt”. finish setting and to return to the normal Measurement mode.
Press the button to display the adjusted amount

2.Operation Mode Setting Selecting Indication Unit


(percentage), which will then display flicker alternately with

Value Setting
“FSC”.
If the unit specification of the model indication Press the button to set and return to the Measurement
is without “-M”
The desired switch operation mode can be selected.
The operation mode currently selected will be displayed. Select mode. To input a value for pressure setting or other
the desired operation mode by pressing the or button. The indication unit can be selected freely. purposes:

HyS wnd
Pressing the or button will change the unit and will 1. Press the or button to enter the Set Value

(Hysteresis) (Window Comparator)


automatically convert set values. Change mode. The first digit will flash.
The units will change in the following order : 2. Press the or button to set the desired
Hysteresis Mode Window Comparator Mode PA GF bAr PSi inH mmH value.

For Vacuum and Low Pressure


(No operation within ten seconds after the Set
ON ON ON ON
Value Change mode was selected results in
Pa kgf/cm2 bar psi inchHg mmHg automatic setting of the value appearing in the
OFF OFF OFF OFF

P1 n1 P1 P2 n1 n2 display window and in charging of the mode to Set


For Positive Pressure
(Whe the product (Reverse) (Whe the product (Reverse)
is shipped) is shipped) Value Change mode to Set Value Indication mode.)
MPa kgf/cm2 bar psi
3. Press the button to make the next digit flash.
(If the highest digit is zero, “ ” or “ ” will flash.
Press the button to set and move to output mode setting. “ ” means “+zero”, “ ” means “-zero”.)
Press the button to set and to move on to setting the
(When the button is pressed at the third digit, the first
display color.
digit will flash).
4. Press the button continuously for longer than
one second to return to displaying set values.
Other Functions
ZISE##-TFI48GB-A

Peak and Bottom Hold Display Function


Maximum and minimum values are always detected and updated
during measurement. Displayed values can be held. For peak hold,
Press and hold the button for longer than one second to hold the
maximum pressure value. The display will flash.
To reset holding, press and hold the button for more than one
second. The display will return to measurement mode. For buttom
hold, press and hold the button for longer than one second to
hold the minimum pressure value. To display will flash
To reset holding, pressure and hold the button for more than
one second. The display will return to measurement mode.

Key Lock Function


This function prevents malfunction such as a set value being
changed by mistake. Press and hold the button for longer than
four seconds to display which of “Loc” or “UnL” is currently set.
Select by pressing the or button and set by presing the
button. If button operation is
not desired, set to “Loc” to set the Lock mode. To release key lock,
Press and hold the button for longer than four seconds to

Zero Clear Function


display the current setting and set to “UnL”.

The displayed value can be adjusted to zero when pressure to be


measured is within ±70digits of the atmospheric pressure.
(The range of ±10% F.S.setting is different depending on the
individual product difference)
This function is useful because it enables the detection of pressure
fluctuations larger than a certain value without being influenced by
fluctuations of source pressure. Press continuously the and
buttons simultaneously to reset to “0” on the display. and
return to the Measurement mode automatically.

Error Display Function


This function displays error location and nature when a problem or
an error occurs.

Error Name Error Display Error Nature Troubleshooting


Method

Overcurrent
Turn the power off and
A load current is flowig to
Error
remove the cause of the
the switch output of 80mA
output oovercurrent.
or more.
Then turn the power on.

Pressure more than ±0.071MPa


for 1MPa or more than ±7.1kPa
Perform zero-clear
Residual
for vacuum compared with the
atmospheric pressure is applied operation again after
Pressure during zero clear operation. restoring the applied
Error
In three seconds, the mode will pressure to an
reset to the Measurement mode. atmospheric pressure
±10% F.S. of the setting range

Contact
condition.
changes with individual product
differences.

Pressure outside of the high


AUSTRIA (43) 2262 62280 NETHERLANDS (31) 20 531 8888

Pressurizing
limit of the set pressure Reset applied
range is applied. BELGIUM (32) 3 355 1464 NORWAY (47) 67 12 90 20

Error
pressure to a level
CZECH REP. (420) 541 424 611 POLAND (48) 22 211 9600
Pressure outside of the low within the set
DENMARK (45) 7025 2900 PORTUGAL (351) 21 471 1880
limit of the set pressure pressure range.
FINLAND (358) 207 513513 SLOVAKIA (421) 2 444 56725
range is applied.
FRANCE (33) 1 6476 1000 SLOVENIA (386) 73 885 412
Displayed in the case of an GERMANY (49) 6103 4020 SPAIN (34) 945 184 100
internal data error. GREECE (30) 210 271 7265 SWEDEN (46) 8 603 1200
Turn the power off HUNGARY (36) 23 511 390 SWITZERLAND (41) 52 396 3131
Displayed in the case of an
System
and turn it on again. IRELAND (353) 1 403 9000 UNITED KINGDOM (44) 1908 563888
internal data error.
Error
If resetting fails, an ITALY (39) 02 92711
investigation by SMC
Displayed in the case of an
Corporation will be
internal data error.
required.
Displayed in the case of an
URL http://www.smcworld.com (Global) http://www.smceu.com (Europe)
internal data error.