Installation
Automatic Transfer Switching Equipment
NZ7 Series
ZHEJIANG CHINT ELECTRICS CO.,LTD
Add: No. 1, CHINT Road, CHINT Industrial Zone, North Baixiang,
Yueqing, Zhejiang Province, P.R.China 325603
Tel: +86-577-62877777
Fax: +86-577-62775769 62871811
E-mail: global-sales@chint.com
Website: w w w .chint.com
CHINT Electric All Rights Reserved Recycle Paper Printed Specifications and technical data are subject to change without notice.
Please contact us to confirm relevant information on ordering
Warning

This equipment should only be mounted by professionals. The manufacturer shall not be held responsible
for any failure to comply with the instruction given in this manual. The expression right of the instruction is owned by CHINT.

The device should only be installed and serviced by professionals.


Switch off the general power supply to the device to confirm the absence of voltage.
Always use an appropriate voltage detection device to confirm the absence of voltage.
Handle operation, you must first disconnect the power supply controller or the controller set to manual.
The phase sequence of the input terminals of two breakers shall be consistent, and the Line N of two-way power
cannot be wrongly connected.
In conducting insulation test for the product, please remove the sampling line of the controller at the end of incoming
line of the product for controlling loop signal, which must be reconnected after the test. The insulation resistance
must not be less than 10MΩ.
Do not open the product by yourself; otherwise, the user should be liable for the consequence.
Do not change any internal wirings of this device; otherwise, the user should be liable for the consequence.
The grounding protection should be reliable so as to ensure the safety.
The automatic control function should be disabled during the regular or failure inspection of loading lines.
Notice
This product has been designed for environment A. Use of this product in environment B may cause
unwanted electromagnetic disturbances in which case the user may be required to take adequate mitigation measure.

Catalog

B Preparations 2

C Storage 4

D The necessary tools 6

E Installation 8
Preparations

Test
1. Manual test
2. Power test

2 2

1 2 OFF QN QR

3 QN: ON QN QR 4 QR: ON QN QR
Manual test

Preparations

Failure alarm Setting mode Manual mode Stop mode

Auto mode Automatic Transfer, Automatic Transfer, Automatic Transfer,


operating transfer delay time return transfer delay time Alternative position

Power test
Operational details of the reference P8 ~ P15

3
Storage

,51ņ

.6ņ

,3111n

Pollution degree 3

Storage

41 61 81
21 :1
,51ņ
&SI

41 61 81 ჸ
21 :1
.6ņ &SI

OFF

5
The necessary tools

Hex key
Screw-driver

4 6 18 10

3N.m 6N.m 8N.m 16N.m 18N.m

The necessary tools

Standard accessories

Optional

7
Installation

Connecting bus-bar type

Normal power bus-bar Alternative power bus-bar

Line voltage signal sampling

Power bus-bar

1 Load bus-bar

Vertical installation& horizontal installation

Installation

Wiring

UN UR
UN N pole UR N pole

NN NR
Wiring terminal of zero line
Wiring terminal
of zero line

Wiring, the voltage signal sampling line in order as shown


3 pole
Main circuit Line voltage signal sampling

UN UR

Main circuit bus-bar

Power phase sequence must be consistent

2 4 pole UN : Normal power supply UR : Alternative power supply

9
Installation

Wiring diagram of external terminals of the controller


Indication of UN status Indication of UR status

Tripping signal

Tripping signal
Power signal

Power signal
On signal

On signal
Zero line

Zero line

Output is AC230V/0.5A

Auxiliary power Stop signal


Passive contact point

Feedback signal

Passive contact point

DC24V/0.5A

Start control of generator

3 Note: the hidden line is the internal wiring of the controller.

Installation

Controller installed in the cabinet split on the panel


1 2

3 4 5

CLACK!

21
Installation

Display and operation interface

1 2 3

4
5 9

6 10

7 11
12
8 13
19

14 18

15 17

16

22

Installation

Display and operation interface

1. Indication of automatic working mode; 15. Button for compulsorily turn off the normal power
2. Indication of manual working mode; Under the manual control mode, if this button is pressed, it can
3. Failure indication compulsorily switch to the normal power; if it is setting condition, this
When the breaker is disengaged due to the failure or short-circuit button is the “scroll up” button of setting programs;
of the switch, this lamp will be on; 16. Button for compulsorily turn off the alternative power
4. Display area of normal power voltage parameters Under the manual control mode, if this button is pressed, it can
It displays normal power voltage parameters and changeover compulsorily switch to the alternative power; if it is setting condition, this
delay time under the working condition, and setting items under button is the “scroll up” button of setting programs;
the setting condition; 17. Off button
5. Indication of the on or off of breaker on the normal power side Under the manual control mode, if either line of both power lines are
6. Indication of setting condition normal and this button is pressed, it will switch to the disengagement
7. Indication of the on or off of breaker on the alternative power side position; this button is the minus button for setting parameters when it is
8. Indication of the start of stop function; under setting condition;
9. Units of voltage, time, and frequency of the normal power; 18. Failure inquiry button
10. Phases A, B, and C; When the switch fails and malfunction lamp on the failure screen is
11. Units of voltage, time, and frequency of the alternative power; on, the detail malfunction code can be inquired if it is pressed; this
12. Display area of alternative power voltage parameters; button is the plus button if it is under the setting condition;
It displays alternative power voltage parameters and transfer 19. Setting button
delay time under the working condition, and setting items under When this button is pressed, it may enter into the parameter setting
the setting condition; menu of the controller.
13. Indication of the start signal of generator
14. Selection button of automatic/manual transfer
When it is regularly used, it can be used for selecting the automatic
or manual mode; it saves and exits the functions when it is under
the setting condition;
5

23
Installation

Operation Description on Parameter Setting

Press the Setting Button when the controller is working, LED will display
to increase and ▼ to decrease. 0s to 180s .
Set return delay time, press ▲ to increase

if the automatic/ manual button is pressed, it will exit the setting menu;
Set start delay time of generator, press ▲
increase and ▼ to decrease. 0s to 180s .

press ▲ to increase and ▼ to decrease.

change the mode (when the last digit is 0, it

the parameter setting menu interface displayed in Figure ; press “ ”


when the value is 1, it is mutual alternative
is grid-grid self-throw and self-reset mode;
Set shut-down delay time of generator,
alternative power, press ▲ to increase

alternative power, press ▲ to increase

Set transfer mode, press ▲ ▼ button to

and “ ” buttons in the setting menu to scroll up the setting options;


Set transfer value of under-voltage of

Set transfer value of under-voltage of


Set transfer value of over-voltage of

Set transfer value of over-voltage of

mode, when it is 2, it is grid-generator.


normal power, press ▲ to increase

normal power, press ▲ to increase

Set transfer delay time, press ▲ to

and ▼ to decrease. 160V to 200V.


and ▼ to decrease.160V to 200V.

and ▼ to decrease.240V to 290V.

and ▼ to decrease. 240V to 290V

and ▼ to decrease. 0s to 180s .

self-throw and self-reset mode.)


0s to 180s .

press “ ” or “ ” to change parameters.


Button Description:
AUTO

OFF

SET

S ET

SE T

SET

S ET

SET

SET

SET

SET
N ON

24

Installation

The working processes of Type A controller


Grid – Grid Grid – Grid Grid-Power Generation
self-throw and self-reset operation mutual alternative operation self-throw and self-reset operation

QN QR QN QR QN QR
UN is normal UN is normal UN is normal
UN fails UN fails UN fails
T1 can be adjusted from 0s to 180s T1 can be adjusted from 0s to 180s T3 can be adjusted from 0s to 180s

UN is QN QR
UN is QN QR

disconnected disconnected Generator starts


UR is put into use UR is put into use Output of generator reaches set value
T1 can be adjusted from 0s to 180s

UR supplies
QN QR
UR supplies
QN QR UN is QN QR

disconnected
UN resumes to normal UN resumes to normal UR is put into use
T2 can be adjusted from 0s to 180s
QN QR
UR is UR supplies QN QR QN QR
disconnected UR supplies
UN is put into use UR fails UN resumes to normal
T1 can be adjusted from 0s to 180s T2 can be adjusted from 0s to 180s
QN QR UR is QN QR
UR is QN QR
UN supplies disconnected disconnected
UN is put into use
UN is put into use
QN QR QN QR
UN supplies UN supplies
UN is put into use
T4 can be adjusted from 0s to 180s
Generator shuts down
7 T1: Transfer delay can be adjusted from 0s to 180s T4: Delay time in shutting-down generator can be adjusted from 0s to 180s
Failure of UN , time before disconnecting QN QN: Operating breaker on the frequently used side
T2: Return delay time can be adjusted from 0s to 180s QR: Operating breaker on the stand-by side
Normal of UN , time before disconnecting QR UN : Normal power supply
T3: Delay time in starting generator can be adjusted from 0s to 180s UR : Alternative power supply
25
Installation

Application Terminals 401 and 402 can only connect to


passive signal; otherwise, the controller will
be burnt! Passive signals may be inputted
through relay. Product after receiving the
stop signal off, 403 and 404 will be connected.
After removing stop signals, this product will
restore to normal working status by pressing
any key of the controller.

UN normal
To control center
 
  UN

terminal of the
Internal contact
controller
  QN on
  QN tripped
To the remote port of the generator
 
  UR
  QR on
 QR tripped

This terminal is used under the  


Grid-Power Generation; it must DC24V
 
be connected to the generator
if required; and it does not affect
its use if it is not connected. It is used under the Grid-Power
When the UN fails  Generation mode and it is allowed
 not to connect it, but the default
 start delay of the generator is 0 second.

26

Installation

Wire connection

NZ7-400 connecting plate


assembled by the factory

27
Installation

Phase barrier

+NZ7-63 phase barrier assembled by the factory

28

Installation

Outline dimension & Installation dimension


1 Outline dimension
2 Installation dimension

Wiring terminal of zero line


(Only three pole products)

1 Outline dimension

29
Installation

2 Installation dimension

2:

Installation

Controller Module

84 42 14 nstallation dimension of the controller


when it is installed by split type
144

140

140
50

80

31