Sunteți pe pagina 1din 6

NCMA TEK

National Concrete Masonry Association


an information series from the national authority on concrete masonry technology

POST-TENSIONED TEK 14-20A


Structural (2002)
CONCRETE MASONRY WALL DESIGN
Keywords: allowable stress design, design examples, flexural top and bottom of the masonry element (see Figure 1). Post-
strength, post-tensioned masonry, prestressed masonry, reinforcing
tensioning is the primary method of prestressing, where the
tendons, strength design
tendons are stressed after the masonry has been placed. This
TEK focuses on the design of concrete masonry walls con-
INTRODUCTION structed with vertical post-tensioned tendons.

The 1999 Building Code Requirements for Masonry Advantages—Prestressing has the potential to increase the
Structures, ACI 530/ASCE 5/TMS 402 (ref. 1), was the first flexural strength, shear strength and stiffness of a masonry
masonry code in the United States to include general design element. In addition to increasing the strength of an element,
provisions for prestressed masonry. Prestressing masonry is prestressing forces can also close or minimize the formation
a process whereby internal compressive stresses are intro- of some cracks. Further, while research (refs. 14, 15) indi-
duced to counteract tensile stresses resulting from applied cates that ductility and energy dissipation capacity are en-
loads. Compressive stresses are developed within the ma- hanced with prestressing, Building Code Requirements for
sonry by tensioning a steel tendon, which is anchored to the Masonry Structures (ref. 1) conservatively does not take
such performance into account.
Post-tensioned masonry can be an economical alterna-
Top anchorage
tive to conventionally reinforced masonry. One major advan-
tage of prestressing is that it allows a wall to be reinforced
without the need for grout. Also, the number of prestressing
Top anchorage tendons may be less than the number of reinforcing bars
block or bond required for the same flexural strength.
beam Post-tensioning masonry is primarily applicable to walls,
although it can also be used for beams, piers, and columns.
Concrete
Vertical post-tensioning is most effective for increasing the
masonry units
structural capacity of elements subjected to relatively low
(single wythe
axial loads. Structural applications include loadbearing, non-
Internal stresses shown) loadbearing and shear walls of tall warehouses and gymnasi-
ums, and commercial buildings, as well as retaining walls and
Coupler
sound barrier walls. Post-tensioning is also an option for
strengthening existing walls.
Prestressing
tendons (bonded MATERIALS
or unbonded;
restrained or Post-tensioned wall construction uses standard materi-
unrestrained) als: units, mortar, grout, and perhaps steel reinforcement. In
addition, post-tensioning requires tendons, which are steel
Footing wires, bars or strands with a higher tensile strength than
anchorage conventional reinforcement. Manufacturers of prestressing
tendons must supply stress relaxation characteristics for
Footing their material if it is to be used as a prestressing tendon.
Specifications for those materials used specifically for post-
tensioning are given in Table 1. Other material specifications
Figure 1—Schematic of Typical Post-Tensioned Wall are covered in references 9 through 12. Construction is

TEK 14-20A © 2002 National Concrete Masonry Association (replaces TEK 14-20)
be exceeded. Immediately after transfer of the post-tensioning
Table 1—Post-Tensioned Material Specifications
forces, the stresses in the steel are the largest because long-
term losses have not occurred. Further, because the masonry
Prestressing Tendons
has had little time to cure, the stresses in the masonry will be
ASTM A 416 Steel Strand, Uncoated Seven-Wire
closer to their capacity. Once long-term losses have tran-
ASTM A 421 Uncoated Steel Wire
spired, the stresses in both the masonry and the steel are
ASTM A 722 Uncoated High-Strength Steel Bar
reduced. The result is a coincidental reduction in the effec-
Accessories tive capacity due to the prestressing force and an increase in the
ASTM F 959 Washer-Type Direct Tension Indicators stresses the fully cured masonry can resist from external loads.

covered in Construction of Post-Tensioned Concrete Ma- Effective Prestress


sonry Walls, TEK 3-14 (ref. 3). Over time, the level of prestressing force decreases due
to creep and shrinkage of the masonry, relaxation of the
CORROSION PROTECTION prestressing tendons and potential decreases in the ambient
temperature. These prestressing losses are in addition to seat-
As with conventionally reinforced masonry structures, ing and elastic shortening losses witnessed during the pre-
Building Code Requirements for Masonry Structures (ref. stressing operation. In addition, the prestressing force of bonded
1) mandates that prestressing tendons for post-tensioned tendons will decrease along the length of the tendon due to
masonry structures be protected against corrosion. As a frictional losses. Since the effective prestressing force varies
minimum, the prestressing tendons, anchors, couplers and over time, the controlling stresses should be checked at several
end fittings in exterior walls exposed to earth or weather must stages and loading conditions over the life of the structure.
be protected. All other walls exposed to a mean relative The total prestress loss in concrete masonry can be
humidity exceeding 75% must also employ some method of assumed to be approximately 35%. At the time of transfer of
corrosion abatement. Unbonded tendons can be protected the prestressing force, typical losses include: 1% seating
with galvanizing, epoxy coating, sheathing or other alterna- loss + 1% elastic shortening = 2%. Additional losses at
tive method that provides an equivalent level of protection. service loads and moment strength include:
Bonded tendons are protected from corrosion by the corru- relaxation 3%
gated duct and prestressing grout in which they are encased. temperature 10%
creep 8%
DESIGN LOADS CMU shrinkage 7%
contingency 5%
As for other masonry structures, minimum required total 33%
design loads are included in Minimum Design Loads for Prestress losses need to be estimated accurately for a
Buildings and Other Structures, ASCE 7 (ref. 5), or the safe and economical structural design. Underestimating losses
governing building codes. If prestressing forces are intended will result in having less available strength than assumed.
to resist lateral loads from earthquake, a factor of 0.9 should Overestimating losses may result in overstressing the wall in
be applied to the strength level prestress forces (0.6 for compression.
allowable stress design) as is done with gravity loads.
Effective Width
STRUCTURAL DESIGN In theory, a post-tensioning force functions similarly to
a concentrated load applied to the top of a wall. Concentrated
The design of post-tensioned masonry is based on al- loads are distributed over an effective width as discussed in
lowable stress design procedures, except for laterally re- the commentary on Building Code Requirements for Ma-
strained tendons which use a strength design philosophy. sonry Structures (ref. 1). A general rule-of-thumb is to use
Building Code Requirements for Masonry Structures (ref. six times the wall thickness as the effective width.
1) prescribes allowable stresses for unreinforced masonry in Elastic shortening during post-tensioning can reduce
compression, tension and shear, which must be checked the stress in adjacent tendons that have already been stressed.
against the stresses resulting from applied loads. Spacing the tendons further apart than the effective width
The flexural strength of post-tensioned walls is gov- theoretically does not reduce the compressive stress in the
erned by either the flexural tensile stress of the masonry (the effective width due to the post-tensioning of subsequent
flexural stress minus the post-tensioning and dead load stress), tendons. The applied loads must also be consolidated into the
the masonry compressive stress, the tensile stress within the effective width so the masonry stresses can be determined.
tendon, the shear capacity of the masonry or the buckling These stresses must be checked in the design stage to avoid
capacity of the wall. overstressing the masonry.
Masonry stresses must be checked at the time of peak
loading (independently accounting for both short-term and Flexure
long-term losses), at the transfer of post-tensioning forces, Tensile and compressive stresses resulting from bend-
and during the jacking operation when bearing stresses may ing moments applied to a section are determined in accor-
dance with conventional elastic beam theory. This results in area of masonry, and the wall is sized such that the maximum
a triangular stress distribution for the masonry in both tension shear stress is less than the allowable stress. In addition, the
and compression. Maximum bending stress at the extreme compressive stress due to post-tensioning can be relied on to
fibers are determined by dividing the applied moment by the increase allowable shear stresses in some circumstances.
section modulus based on the minimum net section.
Post-Tensioning Tendons
Net Flexural Tensile Stress The stress in the tendons is limited (ref. 1) such that:
Sufficient post-tensioning force needs to be provided so (a) the stress due to the jacking force does not exceed
the net flexural tensile stress is less than the allowable values. 0.94fpy, 0.80fpu, nor that recommended by the manufac-
Flexural cracking should not occur if post-tensioning forces turer of the tendons or anchorages,
are kept within acceptable bounds. Flexural cracking due to (b) the stress immediately after transfer does not exceed
sustained post-tensioning forces is believed to be more 0.82fpy nor 0.74fpu, and
severe than cracking due to transient loading. Flexural cracks (c) the stress in the tendons at anchorages and couplers does
due to eccentric post-tensioning forces will remain open not exceed 0.78fpy nor 0.70fpu.
throughout the life of the wall, and may create problems
related to water penetration, freeze-thaw or corrosion. For DETERMINATION OF POST-TENSIONING FORCES
this reason, Building Code Requirements for Masonry Struc-
tures (ref. 1) requires that the net flexural tensile stress be Case (a) after prestress losses and at peak loading:
limited to zero at transfer of the post-tensioning force and for Assuming that the moment, M, due to wind or earthquake
service loadings with gravity loads only. loadings is large relative to the eccentric load moment, the
critical location will be at the mid-height of the wall for
Axial Compression simply-supported walls, and the following equations apply
Compressive stresses are determined by dividing the (bracketed numbers are the applicable Building Code Re-
sum of the post-tensioning and gravity forces by the net area quirements for Masonry Structures (ref. 1) equation or
of the section. They must be less than the code prescribed section numbers):
(ref. 1) allowable values of axial compressive stress. fa fb
Walls must also be checked for buckling due to gravity [2-10] + ≤ 1.33
Fa Fb
loads and post-tensioning forces from unrestrained tendons.
Laterally restrained tendons can not cause buckling; there- where:
Pd ed Pl el Ppf e p
fore only gravity compressive forces need to be checked for P + Pl + Ppf M+ + +
buckling in walls using laterally restrained tendons. Restrain- fa = d and fb = 2 2 2
ing the tendons also ensures that the tendons do not move An S
laterally in the wall when the masonry deflects. The maximum
compressive force that can be applied to the wall based upon The 1.33 factor in Equation [2-10] represents the one-
buckling is 1/4 Pe, per equation 2-11 of Building Code Re- third increase in allowable stress permitted for wind and
quirements for Masonry Structures (ref. 1). earthquake loadings. If the moment, M, is a result of soil
pressures (as is the case for retaining walls), the 1.33 factor
Combined Axial and Flexural Compressive Stress in Equation [2-10] must be replaced by 1.00.
Axial compressive stresses due to post-tensioning and
gravity forces combine with flexural compressive stresses at [2-11] Pd + Pl + Ppf < 1/4 Pe
the extreme fiber to result in maximum compressive stress. Note that if the tendons are laterally restrained, Ppf should not
Conversely, the axial compressive stresses combine with the be included in Equation [2-11].
flexural tensile stresses to reduce the absolute extreme fiber
stresses. To ensure the combination of these stresses does fb - fa < fbt
not exceed code prescribed allowable stresses, a unity equa- [4.5.1.3] fb - fa < 0 (under the load combination of
tion is checked to verify compliance. Employing this unity prestressing force and dead load only)
equation, the sum of the ratios of applied-to-allowable axial
and flexural stresses must be less than one. Unless standards Additional strength design requirements for laterally re-
(ref. 5) limit its use, an additional one-third increase in strained tendons:
allowable stresses is permitted for wind and earthquake load- [4-3] Mu < φMn = φ [Ppf + fyAs + Pdu + Plu] (d - a/2)
ings, as is customary with unreinforced and reinforced ma- Equation 4-3 above applies to members with uniform
sonry. Further, for the stress condition immediately after width, concentric reinforcement and prestressing tendons
transfer of the post-tensioning force, a 20% increase in and concentric axial load. The nominal moment strength for
allowable axial and bending stresses is permitted by Building other conditions should be determined based on static mo-
Code Requirements for Masonry Structures (ref. 1). ment equilibrium equations.
Ppf + f y As + Pdu + Plu
Shear [4-1] a=
As with all stresses, shear stresses are resisted by the net 0.85 f 'm b
a < tf Loads: M = wh2/8 = (15)(12)2/8 = 270 ft-lb (366 N-m)
[4.5.3.3.5] a/d < 0.425 Pd at mid-height = (39)(12)/2 = 234 lb/foot of wall (3,410
[4.5.3.3.2] φ = 0.80 N/m) (Pl = 0)

Case (b) at transfer of post-tensioning: Maximum tendon stresses:


Assuming that vertical live loads are not present during post- Determine governing stresses based on code limits (ref. 1):
tensioning, the following equations apply. The worst case is At jacking: 0.94 fpy = 94.0 ksi (648 MPa)
at the top of the wall where post-tensioning forces are 0.80 fpu = 97.6 ksi (673 MPa)
applied. At transfer: 0.82 fpy = 82.0 ksi (565 MPa)
f ai f bi 0.74 fpu = 90.3 ksi (623 MPa)
[2-10] + ≤ 1.2 At service loads: 0.78 fpy = 78.0 ksi (538 MPa) ⇒ governs
Fai Fbi
0.70 fpu = 85.4 ksi (589 MPa)
where:
Pd + Ppi Pd ed + Ppi e p + M Because the tendon's specified tensile strength is less than
f ai = f bi = 150 ksi (1,034 MPa), fps = fse (per ref. 1 section 4.5.3.3.4).
An S
and: Prestress losses: Assume 35% total loss (as described in the
fbi - fai < 0 Effective Prestress section above).

For cantilevered walls, these equations must be modi- Tendon forces:


fied to the base of the wall. Determine the maximum tendon force, based on the govern-
If the eccentricity of the live load, Pl, is small, neglect- ing tendon stress determined above for each case of jacking,
ing the live load in Equation [2-10] may also govern. transfer and service. At transfer, include 2% prestress losses.
At service, include the full 35% losses.
Case (c) bearing stresses at jacking: Tendon capacity at jacking = 0.94 fpy Aps = 13.3 kips (59
Bearing stresses at the prestressing anchorage should kN)
be checked at the time of jacking. The maximum allowable Tendon capacity at transfer = 0.82 fpy Aps x 0.98 = 11.4
bearing stress at jacking is 0.50f'mi per Building Code Re- kips (51 kN) (including transfer losses)
quirements for Masonry Structures (ref. 1) section 4.9.4.2. Tendon capacity at service = 0.78 fpy Aps x 0.65 = 7.2 kips
(32 kN) (including total losses)
DESIGN EXAMPLE
Try tendons at 48 in. (1,219 mm) on center (note that this
Design a simply-supported exterior wall 12 ft (3.7 m) tendon spacing also corresponds to the maximum effective
high for a wind load of 15 psf (0.72 kPa). The wall is prestressing width of six times the wall thickness).
constructed of concrete masonry units complying with ASTM Determine prestressing force, based on tendon capacity
C 90 (ref. 6). The units are laid in a full bed of Type S Portland determined above:
cement lime mortar complying with ASTM C 270 (ref. 7). at transfer: Ppi = 11.4 kips/4 ft = 2,850 lb/ft (41.6 kN/m)
The specified compressive strength of the masonry (f'm) is at service: Ppf = 7.2 kips/4 ft = 1,800 lb/ft (26.3 kN/m)
1,500 psi (10.3 MPa). The wall will be post-tensioned with
7/16 in. (11 mm) diameter laterally restrained tendons when the
Wall section properties: (ref. 8)
wall achieves a compressive strength of 1,250 psi (8.6 MPa). 8 in. (203 mm) CMU with full mortar bedding:
Axial load and prestress are concentric. An = 41.5 in.2/ft (87,900 mm2/m)
I = 334 in.4/ft (456 x 106 mm4/m)
Given: S = 87.6 in.3/ft (4.71 x 106 mm3/m)
8 in. (203 mm) CMU r = 2.84 in. (72.1 mm)
tf = 1.25 in. (32 mm)
f'm = 1,500 psi (10.3 MPa) At service loads:
f'mi = 1,250 psi (8.6 MPa) At service, the following are checked: combined axial com-
Fbt = 25 psi (0.17 MPa) (Type S Portland cement/lime mortar) pression and flexure using the unity equation (equation 2-
fpy = 100 ksi (690 MPa) (bars) 10); net tension in the wall; stability by ensuring the compres-
f pu = 122 ksi (840 MPa) sive load does not exceed one-fourth of the buckling load, Pe,
Aps = 0.14 in2 (92 mm2) and shear and moment strength.
Es = 29 x 106 psi (200 GPa)
Em = 900 f’m = 1.35 x 106 psi (9,300 MPa) Check combined axial compression and flexure:
n = Es/Em = 21.5
Pd + Ppf 234 + 1800
d = 7.625/2 in. = 3.81 in. (97 mm) (tendons placed in the fa = = = 49 psi (0.34 MPa)
center of the wall) An 41.5
unit weight of CMU wall = 39 psf (190 kg/m2) (ref. 13) h/r = (12 ft)(12 in./ft)/2.84 in. = 50.7 < 99
[2-12] Fa = 1/4 f'm [ 1- ( h/140r )2 ] Pd + Ppi 234 + 2,850
= 1/4 (1,500 psi) [1- ( 50.7/140)2 ] = 326 psi (2.2 MPa) f ai = = = 74 psi (0.51 MPa)
An 41.5
M + Pd ed + Ppf e p 270 + 0 + 0
fb = = x 12 in./ft h/r = (12 ft)(12 in./ft)/2.84 in. = 50.7
S 87.6 Fai = 1/4 f'mi [1- ( h/140r )2 ]
= 37 psi (0.26 MPa) = 1/4(1,250)[1 -(50.7/140)2] = 272 psi (1.9 MPa)
[2-14] Fb = 1/3 f'm = 500 psi (3.4 MPa)
M + Pd ed + Ppi e p 270 + 0 + 0
fa fb 49 37 f bi = = = 37 psi (0.26 MPa)
+ = + S 87.6
Fa Fb 326 500 = 0.22 < 1.33 OK
Fbi = 1/3 f'mi = 1/3(1,250) = 417 psi (2.9 MPa)
f ai f bi 74 37
Check tension for load combination of prestress force and + = +
dead load only (per ref. 1 section 4.5.1.3): Fai Fbi 272 417 = 0.36 < 1.2 OK
fb - fa = 37 - 49 = -12 psi (-0.08 MPa) < 0 OK
Check tension for load combination of prestress force and
Check stability: dead load only (per ref. 1 section 4.5.1.3):
Because the tendons are laterally restrained, the prestressing fbi - fai = 37 - 74 = -37 psi (-0.26 MPa) < 0 OK
force, Ppf, is not considered in the determination of axial load
( per ref. 1 section 4.5.3.2), and the wall is not subject to live Therefore, use 7/16 in. (11 mm) diameter tendons at 48 in.
load in this case, so equation 2-11 reduces to: (1,219 mm) o.c. Note that although wall design is seldom
P = Pd = 234 lb/ft (3,414 N/m) governed by out-of-plane shear, the shear capacity should
also be checked.
[2-15] 1/4 Pe = 1/4
π 2 Em I
h2
(1 − 0.577 e
r
)
3

NOTATIONS
π (1.35 × 10 )(334) 3
2 6 An net cross-sectional area of masonry section, in.2 (mm2)
(1) = 53,653 lb (239 kN)
= (12 × 12)2 Aps threaded area of post-tensioning tendon, in.2 (mm2)
As cross-sectional area of mild reinforcement, in.2 (mm2)
[2-11] P < 1/4 Pe OK a depth of an equivalent compression zone at nominal
strength, in. (mm)
Check moment strength: b width of section, in. (mm)
Building Code Requirements for Masonry Structures sec- d distance from extreme compression fiber to centroid of
tion 4.5.3.3 includes the following criteria for moment prestressing tendon, in. (mm)
strength of walls with laterally restrained tendons: Es modulus of elasticity of prestressing steel, psi (MPa)
a/d < 0.425 Em modulus of elasticity of masonry, psi (MPa)
Mu < φ Mn e d eccentricity of dead load, in. (mm)
where φ = 0.8 and el eccentricity of live load, in. (mm)
Mn = [Ppf + fyAs + Pdu] [d - a/2] e p eccentricity of post-tensioning load, in. (mm)
In addition, the compression zone must fall within the ma- Fa allowable masonry axial compressive stress, psi (MPa)
sonry, so a < tf . Fai allowable masonry axial compressive stress at transfer,
psi (MPa)
Mu = 1.3 M = 1.3 x 270 = 351 ft-lb (476 N.m) Fb allowable masonry flexural compressive stress, psi (MPa)
Pdu = 1.2 Pd = 1.2 x 234 = 281 lb (1.2 kN) Fbi allowable masonry flexural compressive stress at trans-
where 1.3 and 1.2 are load factors for wind and dead loads, fer, psi (MPa)
respectively. Fbt allowable flexural tensile strength of masonry, psi (MPa)
Ppf + Fy As + Pdu 1,800 + 0 + 281 f a axial stress after prestress loss, psi (MPa)
a= = f ai axial stress at transfer, psi (MPa)
0.85 f 'm b 0.85(1,500)(12 ) = 0.14 in. (3.6 mm) f b flexural stress after prestress loss, psi (MPa)
a < tf OK f bi flexural stress at transfer, psi (MPa)
a/d = 0.14/3.81 = 0.036 < 0.425 OK f'm specified compressive strength of masonry, psi (MPa)
Mu < φ Mn f'mi specified compressive strength of masonry at time of
φ Mn = 0.8 [Ppf + fyAs + Pdu] [d - a/2] transfer of prestress, psi (MPa)
= 0.8 [1,800 + 0 + 281] (3.81 - 0.14/2)/12 in./ft f ps stress in prestressing tendon at nominal strength, psi (MPa)
= 519 ft-lb (703 N.m) > Mu OK f pu specified tensile strength of prestressing tendon, ksi (MPa)
fpy specified yield strength of prestressing tendon, ksi (MPa)
At transfer: fse effective stress in prestressing tendon after all pre-
Check combined axial compression and flexure using the stress losses have occurred, psi (MPa)
unity equation (equation 2-10) and net tension in the wall. fy specified yield strength of steel for reinforcement and an-
chors, psi (MPa)
h masonry wall height, in. (mm) Materials, 2001.
I moment of inertia of net wall section of extreme fiber tension or 7. Standard Specification for Mortar for Unit Masonry, ASTM
compression, in.4/ft (mm4/m) C 270-01. American Society for Testing and Materials, 2001.
M moment due to lateral loads, ft-lb (N.m) 8. Section Properties of Concrete Masonry Walls, TEK 14-1.
Mn nominal moment strength, ft-lb (N.m) National Concrete Masonry Association, 1993.
Mu factored moment due to lateral loads, ft-lb (N.m) 9. ASTM Specifications for Concrete Masonry Units, TEK 1-
n modular ratio of prestressing steel and masonry (Es/Em) 1C. National Concrete Masonry Association, 2000.
Pd axial dead load, lb/ft (kN/m) 10. Mortars for Concrete Masonry, TEK 9-1A. National Con-
Pd u factored axial dead load, lb/ft (kN/m) crete Masonry Association, 2001.
Pe Euler buckling load, lb/ft (kN/m) 11. Grout for Concrete Masonry, TEK 9-4. National Concrete
Pl axial live load, lb/ft (kN/m) Masonry Association, 1998.
Pl u factored axial live load, lb/ft (kN/m) 12. Steel for Concrete Masonry Reinforcement, TEK 12-4B.
Pp i prestress force at transfer, lb/ft (kN/m) National Concrete Masonry Association, 1998.
Pp f prestress force including losses, lb/ft (kN/m) 13. Concrete Masonry Wall Weights, TEK 14-13A. National
r radius of gyration for net wall section, in. (mm) Concrete Masonry Association, 2002.
S section modulus of net cross-sectional area of the wall, in.3/ft 14. Schultz, A.E., and M.J. Scolforo, An Overview of Prestressed
(mm3/m) Masonry, TMS Journal, Vol. 10, No. 1, August 1991, pp. 6-21.
tf face shell thickness of concrete masonry, in. (mm) 15. Schultz,A.E.,andM.J.Scolforo,EngineeringDesignProvisionsfor
w applied wind pressure, psf (kPa) Prestressed Masonry, Part 1: Masonry Stresses, Part 2: Steel
φ strength reduction factor = 0.8 Stresses and Other Considerations, TMS Journal, Vol. 10, No. 2,
February 1992, pp. 29-64.
REFERENCES 16. Standard Specification for Steel Strand, Uncoated Seven-
1. Building Code Requirements for Masonry Structures, ACI Wire for Prestressed Concrete, ASTM A 416-99. American
530-02/ASCE 5-02/TMS 402-02. Reported by the Masonry Society for Testing and Materials, 1999.
Standards Joint Committee, 2002. 17. Standard Specification for Uncoated Stress-Relieved Steel
2. Building Code Requirements for Structural Concrete, ACI Wire for Prestressed Concrete, ASTM A 421-98a. American
318-99. Detroit, MI: American Concrete Institute, Revised 1999. Society for Testing and Materials, 1998.
3. Construction of Post-Tensioned Concrete Masonry Walls, 18. Standard Specification for Uncoated High-Strength Steel
TEK 3-14. National Concrete Masonry Association, 2002. Bar for Prestressed Concrete, ASTM A 722-98. American
4. International Building Code. International Code Council, 2000. Society for Testing and Materials, 1998.
5. Minimum Design Loads for Buildings and Other Structures, ASCE 19. Standard Specification for Compressible-Washer-Type Di-
7-98, American Society of Civil Engineers, 1998. rect Tension Indicators for Use with Structural Fasteners,
6. Standard Specification for Loadbearing Concrete Masonry ASTM F 959-01a. American Society for Testing and Materials,
Units, ASTM C 90-01a. American Society for Testing and 2001.

NATIONAL CONCRETE MASONRY ASSOCIATION To order a complete TEK Manual or TEK Index,
13750 Sunrise Valley Drive, Herndon, Virginia 20171 contact NCMA Publications (703) 713-1900
www.ncma.org

S-ar putea să vă placă și