Sunteți pe pagina 1din 18

Air System Sizing Summary for for-food-tennant

Project Name: aircon design qloads 07 19 2019


Prepared by: addu 02:50AM

Air System Information


Air System Name .............................. for-food-tennant Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ............................................................... 2114.8 m²
Air System Type ................................................ SZCAV Location ............................................ Manila, Philippines

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 690.8 kW Load occurs at ................................................... Aug 1600
Sensible coil load ................................................. 666.6 kW OA DB / WB ...................................................... 34.7 / 27.2 °C
Coil L/s at Aug 1600 ............................................ 60045 L/s Entering DB / WB ............................................. 24.4 / 17.9 °C
Max block L/s ...................................................... 60045 L/s Leaving DB / WB .............................................. 15.2 / 14.5 °C
Sum of peak zone L/s ......................................... 60045 L/s Coil ADP ..................................................................... 14.1 °C
Sensible heat ratio ............................................... 0.965 Bypass Factor .......................................................... 0.102
m²/kW ....................................................................... 3.1 Resulting RH ................................................................. 54 %
W/m² ..................................................................... 326.6 Design supply temp. ................................................... 14.4 °C
Water flow @ 5.6 °K rise ...................................... 29.76 L/s Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 °K

Supply Fan Sizing Data

Actual max L/s ..................................................... 60045 L/s Fan motor BHP ........................................................... 0.00 BHP
Standard L/s ........................................................ 59897 L/s Fan motor kW ............................................................. 0.00 kW
Actual max L/(s-m²) .............................................. 28.39 L/(s-m²) Fan static ......................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ........................................................ 0 L/s L/s/person ................................................................... 0.00 L/s/person
L/(s-m²) ................................................................... 0.00 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 18


Zone Sizing Summary for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

Air System Information


Air System Name .............................. for-food-tennant Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ............................................................... 2114.8 m²
Air System Type ................................................ SZCAV Location ............................................ Manila, Philippines

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 670.5 60045 60045 Jul 1600 5.8 2114.8 28.39

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
Army Navy 1 41.2 Sep 1600 3620 0.3 97.6 37.09
BreadTalk 1 23.5 Sep 1600 2064 0.2 48.8 42.29
Bulgogi 1 19.1 Jul 1600 1683 0.2 48.8 34.49
Choobi 1 19.1 Jul 1600 1683 0.2 48.8 34.49
Chowking 1 19.1 Jul 1600 1683 0.2 48.8 34.49
Food Court 1 71.6 Aug 2100 6299 0.3 447.4 14.08
FrenchBaker 1 19.1 Jul 1600 1683 0.2 48.8 34.48
Gangnam 1 28.1 Sep 1600 2469 0.3 97.6 25.30
Gerrys 1 19.1 Jul 1600 1683 0.2 48.8 34.49
GongCha 1 18.7 Oct 1500 1648 0.2 48.8 33.78
Hukad 1 18.8 Oct 1500 1649 0.2 48.8 33.79
JCO 1 35.7 Jul 1600 3140 0.3 97.6 32.18
Jollibee 1 35.7 Jul 1600 3141 0.3 97.6 32.18
KFC 1 28.1 Sep 1600 2470 0.3 97.6 25.31
Krispy Kreme 1 35.5 Jul 1600 3119 0.3 97.6 31.96
Mandarin 1 19.1 Jul 1600 1683 0.2 48.8 34.49
Pancake House 1 18.7 Oct 1500 1648 0.2 48.8 33.78
Penongs 1 35.5 Jul 1600 3119 0.3 97.6 31.96
Shakeys 1 19.1 Jul 1600 1683 0.2 48.8 34.49
SNR 1 60.7 Aug 1600 5334 0.4 154.6 34.50
Starbucks 1 35.7 Jul 1600 3141 0.3 97.6 32.18
TGIF 1 28.1 Sep 1600 2469 0.3 97.6 25.30
Yakimix 1 33.4 Dec 1400 2933 0.3 97.6 30.05

Hourly Analysis Program v4.90 Page 2 of 18


Air System Design Load Summary for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.7 °C / 27.2 °C HEATING OA DB / WB 20.6 °C / 14.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 1399 m² 187270 - 1399 m² - -
Wall Transmission 2871 m² 59898 - 2871 m² 2738 -
Roof Transmission 2115 m² 9144 - 2115 m² 446 -
Window Transmission 1399 m² 44199 - 1399 m² 2595 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 634 m² 0 - 634 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 2221 W 2221 - 0 0 -
Task Lighting 1692 W 1692 - 0 0 -
Electric Equipment 269637 W 269625 - 0 0 -
People 2350 14859 22898 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 18468 0 - 0 0
Safety Factor 10% / 5% 60737 1145 0% 0 0
>> Total Zone Loads - 668112 24043 - 5779 0
Zone Conditioning - 666649 24043 - 130 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 60045 L/s 0 - 60045 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 60045 L/s 0 - 60045 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 666649 24043 - 130 0
Central Cooling Coil - 666648 24135 - 0 0
>> Total Conditioning - 666648 24135 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

DESIGN MONTH: JANUARY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 22.2 60045 458.7 482.7 0.0 0.0 0.0 0.0 0.0 0.0
0100 21.8 60045 462.1 486.2 0.0 0.0 0.0 0.0 0.0 0.0
0200 21.4 60045 437.0 460.9 0.0 0.0 0.0 0.0 0.0 0.0
0300 21.0 60045 440.4 464.5 0.0 0.0 0.0 0.0 0.0 0.0
0400 20.8 60045 424.6 448.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 20.7 60045 407.7 431.8 0.0 0.0 0.0 0.0 0.0 0.0
0600 20.8 60045 416.8 440.9 0.0 0.0 0.0 0.0 0.0 0.0
0700 21.3 60045 460.4 484.5 0.0 0.0 0.0 0.0 0.0 0.0
0800 22.1 60045 493.3 517.4 0.0 0.0 0.0 0.0 0.0 0.0
0900 23.2 60045 505.8 529.8 0.0 0.0 0.0 0.0 0.0 0.0
1000 24.5 60045 531.1 555.2 0.0 0.0 0.0 0.0 0.0 0.0
1100 26.0 60045 540.5 564.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 27.4 60045 544.5 568.5 0.0 0.0 0.0 0.0 0.0 0.0
1300 28.5 60045 556.2 580.3 0.0 0.0 0.0 0.0 0.0 0.0
1400 29.2 60045 560.6 584.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 29.4 60045 589.5 613.6 0.0 0.0 0.0 0.0 0.0 0.0
1600 29.2 60045 584.5 608.3 0.0 0.0 0.0 0.0 0.0 0.0
1700 28.6 60045 562.9 587.1 0.0 0.0 0.0 0.0 0.0 0.0
1800 27.6 60045 542.0 565.9 0.0 0.0 0.0 0.0 0.0 0.0
1900 26.5 60045 529.4 553.3 0.0 0.0 0.0 0.0 0.0 0.0
2000 25.3 60045 508.5 532.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 24.4 60045 498.6 522.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 23.5 60045 489.6 513.6 0.0 0.0 0.0 0.0 0.0 0.0
2300 22.8 60045 473.3 497.3 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: FEBRUARY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23.4 60045 475.5 499.4 0.0 0.0 0.0 0.0 0.0 0.0
0100 22.9 60045 466.4 490.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 22.5 60045 466.6 490.7 0.0 0.0 0.0 0.0 0.0 0.0
0300 22.1 60045 462.1 486.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 21.9 60045 436.0 460.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 21.8 60045 428.6 451.5 0.0 0.0 0.0 0.0 0.0 0.0
0600 22.0 60045 420.9 444.9 0.0 0.0 0.0 0.0 0.0 0.0
0700 22.4 60045 486.2 510.4 0.0 0.0 0.0 0.0 0.0 0.0
0800 23.2 60045 506.1 530.3 0.0 0.0 0.0 0.0 0.0 0.0
0900 24.3 60045 529.8 553.9 0.0 0.0 0.0 0.0 0.0 0.0
1000 25.6 60045 530.0 553.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 27.1 60045 543.3 567.4 0.0 0.0 0.0 0.0 0.0 0.0
1200 28.5 60045 558.8 582.9 0.0 0.0 0.0 0.0 0.0 0.0
1300 29.6 60045 555.5 579.5 0.0 0.0 0.0 0.0 0.0 0.0
1400 30.3 60045 584.6 608.7 0.0 0.0 0.0 0.0 0.0 0.0
1500 30.6 60045 603.1 627.1 0.0 0.0 0.0 0.0 0.0 0.0
1600 30.3 60045 611.9 636.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 29.7 60045 588.0 611.8 0.0 0.0 0.0 0.0 0.0 0.0
1800 28.7 60045 549.5 573.5 0.0 0.0 0.0 0.0 0.0 0.0
1900 27.6 60045 552.1 576.2 0.0 0.0 0.0 0.0 0.0 0.0
2000 26.4 60045 526.6 550.7 0.0 0.0 0.0 0.0 0.0 0.0
2100 25.5 60045 515.1 537.2 0.0 0.0 0.0 0.0 0.0 0.0
2200 24.6 60045 508.0 532.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 23.9 60045 487.6 511.6 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 4 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

DESIGN MONTH: MARCH


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 25.0 60045 500.4 524.5 0.0 0.0 0.0 0.0 0.0 0.0
0100 24.6 60045 487.8 511.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 24.1 60045 486.2 510.3 0.0 0.0 0.0 0.0 0.0 0.0
0300 23.8 60045 471.5 495.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 23.5 60045 467.2 491.3 0.0 0.0 0.0 0.0 0.0 0.0
0500 23.4 60045 446.3 470.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 23.6 60045 474.6 498.8 0.0 0.0 0.0 0.0 0.0 0.0
0700 24.1 60045 500.0 524.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 24.8 60045 522.5 547.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 26.0 60045 551.3 575.5 0.0 0.0 0.0 0.0 0.0 0.0
1000 27.3 60045 554.0 578.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 28.8 60045 543.7 567.7 0.0 0.0 0.0 0.0 0.0 0.0
1200 30.2 60045 552.2 576.3 0.0 0.0 0.0 0.0 0.0 0.0
1300 31.3 60045 580.8 605.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 32.0 60045 596.4 620.4 0.0 0.0 0.0 0.0 0.0 0.0
1500 32.2 60045 622.8 646.9 0.0 0.0 0.0 0.0 0.0 0.0
1600 32.0 60045 623.2 647.1 0.0 0.0 0.0 0.0 0.0 0.0
1700 31.3 60045 610.9 635.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 30.4 60045 583.9 607.8 0.0 0.0 0.0 0.0 0.0 0.0
1900 29.2 60045 569.2 593.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 28.1 60045 554.4 578.4 0.0 0.0 0.0 0.0 0.0 0.0
2100 27.1 60045 538.8 562.6 0.0 0.0 0.0 0.0 0.0 0.0
2200 26.3 60045 538.1 562.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 25.6 60045 514.8 538.7 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: APRIL


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 25.6 60045 503.8 527.6 0.0 0.0 0.0 0.0 0.0 0.0
0100 25.1 60045 498.9 523.1 0.0 0.0 0.0 0.0 0.0 0.0
0200 24.7 60045 481.9 505.8 0.0 0.0 0.0 0.0 0.0 0.0
0300 24.4 60045 476.2 500.3 0.0 0.0 0.0 0.0 0.0 0.0
0400 24.1 60045 473.5 497.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 24.0 60045 460.6 484.5 0.0 0.0 0.0 0.0 0.0 0.0
0600 24.2 60045 480.4 504.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 24.6 60045 512.1 536.2 0.0 0.0 0.0 0.0 0.0 0.0
0800 25.4 60045 528.4 552.7 0.0 0.0 0.0 0.0 0.0 0.0
0900 26.5 60045 538.2 564.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 27.9 60045 541.0 565.5 0.0 0.0 0.0 0.0 0.0 0.0
1100 29.4 60045 547.4 571.4 0.0 0.0 0.0 0.0 0.0 0.0
1200 30.8 60045 541.5 565.5 0.0 0.0 0.0 0.0 0.0 0.0
1300 31.8 60045 575.0 599.1 0.0 0.0 0.0 0.0 0.0 0.0
1400 32.5 60045 606.4 630.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 32.8 60045 624.7 648.8 0.0 0.0 0.0 0.0 0.0 0.0
1600 32.5 60045 628.7 652.6 0.0 0.0 0.0 0.0 0.0 0.0
1700 31.9 60045 621.1 645.2 0.0 0.0 0.0 0.0 0.0 0.0
1800 30.9 60045 578.4 602.3 0.0 0.0 0.0 0.0 0.0 0.0
1900 29.8 60045 568.0 590.3 0.0 0.0 0.0 0.0 0.0 0.0
2000 28.7 60045 562.7 586.9 0.0 0.0 0.0 0.0 0.0 0.0
2100 27.7 60045 543.9 567.9 0.0 0.0 0.0 0.0 0.0 0.0
2200 26.8 60045 531.7 553.7 0.0 0.0 0.0 0.0 0.0 0.0
2300 26.1 60045 524.1 548.2 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 5 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

DESIGN MONTH: MAY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 26.1 60045 515.8 539.8 0.0 0.0 0.0 0.0 0.0 0.0
0100 25.7 60045 503.7 527.5 0.0 0.0 0.0 0.0 0.0 0.0
0200 25.3 60045 497.3 521.4 0.0 0.0 0.0 0.0 0.0 0.0
0300 24.9 60045 480.5 504.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 24.6 60045 481.2 505.3 0.0 0.0 0.0 0.0 0.0 0.0
0500 24.6 60045 462.2 486.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 24.7 60045 494.9 519.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 25.2 60045 517.3 541.8 0.0 0.0 0.0 0.0 0.0 0.0
0800 26.0 60045 520.9 544.9 0.0 0.0 0.0 0.0 0.0 0.0
0900 27.1 60045 541.4 565.6 0.0 0.0 0.0 0.0 0.0 0.0
1000 28.4 60045 539.8 563.6 0.0 0.0 0.0 0.0 0.0 0.0
1100 29.9 60045 541.9 565.8 0.0 0.0 0.0 0.0 0.0 0.0
1200 31.3 60045 557.7 582.1 0.0 0.0 0.0 0.0 0.0 0.0
1300 32.4 60045 592.9 617.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 33.1 60045 611.3 635.4 0.0 0.0 0.0 0.0 0.0 0.0
1500 33.3 60045 628.0 652.1 0.0 0.0 0.0 0.0 0.0 0.0
1600 33.1 60045 633.6 657.6 0.0 0.0 0.0 0.0 0.0 0.0
1700 32.5 60045 625.6 649.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 31.5 60045 585.3 609.3 0.0 0.0 0.0 0.0 0.0 0.0
1900 30.3 60045 583.2 607.3 0.0 0.0 0.0 0.0 0.0 0.0
2000 29.2 60045 572.7 596.6 0.0 0.0 0.0 0.0 0.0 0.0
2100 28.2 60045 549.8 573.8 0.0 0.0 0.0 0.0 0.0 0.0
2200 27.4 60045 532.7 556.7 0.0 0.0 0.0 0.0 0.0 0.0
2300 26.7 60045 529.5 553.6 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: JUNE


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.2 60045 538.0 562.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 26.8 60045 516.0 539.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.4 60045 510.9 535.1 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.0 60045 502.2 526.2 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.8 60045 483.3 507.4 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.7 60045 481.6 505.7 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.8 60045 501.0 525.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.3 60045 515.9 540.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.1 60045 540.5 564.6 0.0 0.0 0.0 0.0 0.0 0.0
0900 28.2 60045 540.5 564.5 0.0 0.0 0.0 0.0 0.0 0.0
1000 29.5 60045 543.4 567.4 0.0 0.0 0.0 0.0 0.0 0.0
1100 31.0 60045 560.8 584.9 0.0 0.0 0.0 0.0 0.0 0.0
1200 32.4 60045 566.3 590.3 0.0 0.0 0.0 0.0 0.0 0.0
1300 33.5 60045 587.9 611.9 0.0 0.0 0.0 0.0 0.0 0.0
1400 34.2 60045 625.5 649.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 34.4 60045 638.5 662.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 34.2 60045 661.3 685.5 0.0 0.0 0.0 0.0 0.0 0.0
1700 33.6 60045 644.7 668.1 0.0 0.0 0.0 0.0 0.0 0.0
1800 32.6 60045 600.5 624.4 0.0 0.0 0.0 0.0 0.0 0.0
1900 31.5 60045 594.8 618.9 0.0 0.0 0.0 0.0 0.0 0.0
2000 30.3 60045 572.5 596.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 29.4 60045 570.6 594.7 0.0 0.0 0.0 0.0 0.0 0.0
2200 28.5 60045 544.4 568.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 27.8 60045 535.6 559.6 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 6 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.8 60045 543.7 567.8 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.4 60045 530.7 554.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.9 60045 502.7 526.7 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.6 60045 495.7 519.8 0.0 0.0 0.0 0.0 0.0 0.0
0400 26.3 60045 488.5 512.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 26.2 60045 484.8 509.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 26.4 60045 499.4 523.4 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.8 60045 531.1 555.2 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.6 60045 533.6 557.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 28.8 60045 549.4 573.5 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.1 60045 564.8 588.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 31.6 60045 557.7 581.7 0.0 0.0 0.0 0.0 0.0 0.0
1200 33.0 60045 566.8 590.8 0.0 0.0 0.0 0.0 0.0 0.0
1300 34.0 60045 604.4 628.6 0.0 0.0 0.0 0.0 0.0 0.0
1400 34.7 60045 621.6 645.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 35.0 60045 650.7 674.8 0.0 0.0 0.0 0.0 0.0 0.0
1600 34.7 60045 664.1 688.2 0.0 0.0 0.0 0.0 0.0 0.0
1700 34.1 60045 642.5 666.4 0.0 0.0 0.0 0.0 0.0 0.0
1800 33.2 60045 595.9 619.8 0.0 0.0 0.0 0.0 0.0 0.0
1900 32.0 60045 601.4 625.5 0.0 0.0 0.0 0.0 0.0 0.0
2000 30.9 60045 580.9 604.8 0.0 0.0 0.0 0.0 0.0 0.0
2100 29.9 60045 562.9 586.8 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.0 60045 553.4 577.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.3 60045 543.5 567.5 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: AUGUST


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 27.8 60045 534.5 558.7 0.0 0.0 0.0 0.0 0.0 0.0
0100 27.4 60045 514.2 538.2 0.0 0.0 0.0 0.0 0.0 0.0
0200 26.9 60045 504.0 526.2 0.0 0.0 0.0 0.0 0.0 0.0
0300 26.6 60045 494.9 518.9 0.0 0.0 0.0 0.0 0.0 0.0
0400 26.3 60045 490.7 514.9 0.0 0.0 0.0 0.0 0.0 0.0
0500 26.2 60045 476.1 500.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 26.4 60045 510.2 534.3 0.0 0.0 0.0 0.0 0.0 0.0
0700 26.8 60045 527.2 551.1 0.0 0.0 0.0 0.0 0.0 0.0
0800 27.6 60045 550.0 574.1 0.0 0.0 0.0 0.0 0.0 0.0
0900 28.8 60045 567.0 591.1 0.0 0.0 0.0 0.0 0.0 0.0
1000 30.1 60045 564.2 588.2 0.0 0.0 0.0 0.0 0.0 0.0
1100 31.6 60045 573.9 598.0 0.0 0.0 0.0 0.0 0.0 0.0
1200 33.0 60045 574.1 598.1 0.0 0.0 0.0 0.0 0.0 0.0
1300 34.0 60045 592.9 617.1 0.0 0.0 0.0 0.0 0.0 0.0
1400 34.7 60045 627.5 651.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 35.0 60045 641.9 665.9 0.0 0.0 0.0 0.0 0.0 0.0
1600 34.7 60045 666.6 690.8 0.0 0.0 0.0 0.0 0.0 0.0
1700 34.1 60045 634.7 658.7 0.0 0.0 0.0 0.0 0.0 0.0
1800 33.2 60045 596.4 620.3 0.0 0.0 0.0 0.0 0.0 0.0
1900 32.0 60045 598.7 622.8 0.0 0.0 0.0 0.0 0.0 0.0
2000 30.9 60045 572.5 596.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 29.9 60045 562.2 586.1 0.0 0.0 0.0 0.0 0.0 0.0
2200 29.0 60045 550.6 574.5 0.0 0.0 0.0 0.0 0.0 0.0
2300 28.3 60045 550.4 574.5 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 7 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

DESIGN MONTH: SEPTEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 26.7 60045 513.0 537.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 26.3 60045 509.3 533.5 0.0 0.0 0.0 0.0 0.0 0.0
0200 25.8 60045 491.8 515.7 0.0 0.0 0.0 0.0 0.0 0.0
0300 25.5 60045 482.0 504.2 0.0 0.0 0.0 0.0 0.0 0.0
0400 25.2 60045 479.1 503.3 0.0 0.0 0.0 0.0 0.0 0.0
0500 25.1 60045 461.1 485.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 25.3 60045 502.6 526.7 0.0 0.0 0.0 0.0 0.0 0.0
0700 25.7 60045 525.0 549.1 0.0 0.0 0.0 0.0 0.0 0.0
0800 26.5 60045 544.3 568.7 0.0 0.0 0.0 0.0 0.0 0.0
0900 27.7 60045 556.3 580.5 0.0 0.0 0.0 0.0 0.0 0.0
1000 29.0 60045 561.9 586.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 30.5 60045 565.8 590.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 31.9 60045 573.4 598.5 0.0 0.0 0.0 0.0 0.0 0.0
1300 32.9 60045 598.5 622.6 0.0 0.0 0.0 0.0 0.0 0.0
1400 33.6 60045 617.4 641.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 33.9 60045 631.9 656.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 33.6 60045 632.5 656.4 0.0 0.0 0.0 0.0 0.0 0.0
1700 33.0 60045 605.0 629.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 32.0 60045 590.6 614.5 0.0 0.0 0.0 0.0 0.0 0.0
1900 30.9 60045 568.5 592.4 0.0 0.0 0.0 0.0 0.0 0.0
2000 29.8 60045 562.6 586.7 0.0 0.0 0.0 0.0 0.0 0.0
2100 28.8 60045 544.3 568.3 0.0 0.0 0.0 0.0 0.0 0.0
2200 27.9 60045 534.5 558.5 0.0 0.0 0.0 0.0 0.0 0.0
2300 27.2 60045 526.0 550.0 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: OCTOBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 25.6 60045 504.5 528.5 0.0 0.0 0.0 0.0 0.0 0.0
0100 25.1 60045 481.9 505.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 24.7 60045 477.3 501.4 0.0 0.0 0.0 0.0 0.0 0.0
0300 24.4 60045 474.2 498.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 24.1 60045 460.0 483.8 0.0 0.0 0.0 0.0 0.0 0.0
0500 24.0 60045 463.8 487.9 0.0 0.0 0.0 0.0 0.0 0.0
0600 24.2 60045 477.1 501.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 24.6 60045 520.8 545.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 25.4 60045 544.4 568.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 26.5 60045 546.1 569.9 0.0 0.0 0.0 0.0 0.0 0.0
1000 27.9 60045 563.4 587.5 0.0 0.0 0.0 0.0 0.0 0.0
1100 29.4 60045 565.5 589.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 30.8 60045 583.0 607.1 0.0 0.0 0.0 0.0 0.0 0.0
1300 31.8 60045 587.9 611.8 0.0 0.0 0.0 0.0 0.0 0.0
1400 32.5 60045 616.9 641.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 32.8 60045 628.5 652.6 0.0 0.0 0.0 0.0 0.0 0.0
1600 32.5 60045 625.0 648.9 0.0 0.0 0.0 0.0 0.0 0.0
1700 31.9 60045 587.2 611.1 0.0 0.0 0.0 0.0 0.0 0.0
1800 30.9 60045 566.6 590.5 0.0 0.0 0.0 0.0 0.0 0.0
1900 29.8 60045 562.4 586.6 0.0 0.0 0.0 0.0 0.0 0.0
2000 28.7 60045 549.3 573.1 0.0 0.0 0.0 0.0 0.0 0.0
2100 27.7 60045 533.0 556.9 0.0 0.0 0.0 0.0 0.0 0.0
2200 26.8 60045 524.5 548.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 26.1 60045 506.8 530.8 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 8 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

DESIGN MONTH: NOVEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 23.9 60045 485.7 509.8 0.0 0.0 0.0 0.0 0.0 0.0
0100 23.5 60045 470.7 494.5 0.0 0.0 0.0 0.0 0.0 0.0
0200 23.0 60045 454.9 478.9 0.0 0.0 0.0 0.0 0.0 0.0
0300 22.7 60045 450.1 474.3 0.0 0.0 0.0 0.0 0.0 0.0
0400 22.4 60045 451.2 475.3 0.0 0.0 0.0 0.0 0.0 0.0
0500 22.3 60045 433.0 457.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 22.5 60045 450.9 475.3 0.0 0.0 0.0 0.0 0.0 0.0
0700 22.9 60045 487.7 511.8 0.0 0.0 0.0 0.0 0.0 0.0
0800 23.7 60045 522.7 546.9 0.0 0.0 0.0 0.0 0.0 0.0
0900 24.9 60045 527.4 551.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 26.2 60045 555.8 580.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 27.7 60045 553.5 577.3 0.0 0.0 0.0 0.0 0.0 0.0
1200 29.1 60045 573.9 598.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 30.1 60045 587.6 611.7 0.0 0.0 0.0 0.0 0.0 0.0
1400 30.8 60045 598.2 622.4 0.0 0.0 0.0 0.0 0.0 0.0
1500 31.1 60045 608.2 632.3 0.0 0.0 0.0 0.0 0.0 0.0
1600 30.8 60045 599.3 623.2 0.0 0.0 0.0 0.0 0.0 0.0
1700 30.2 60045 573.5 597.4 0.0 0.0 0.0 0.0 0.0 0.0
1800 29.3 60045 547.2 571.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 28.1 60045 545.3 569.4 0.0 0.0 0.0 0.0 0.0 0.0
2000 27.0 60045 535.9 560.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 26.0 60045 515.9 539.8 0.0 0.0 0.0 0.0 0.0 0.0
2200 25.1 60045 498.7 522.7 0.0 0.0 0.0 0.0 0.0 0.0
2300 24.4 60045 484.9 508.8 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: DECEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 22.8 60045 461.0 484.8 0.0 0.0 0.0 0.0 0.0 0.0
0100 22.4 60045 460.8 484.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 21.9 60045 444.5 468.5 0.0 0.0 0.0 0.0 0.0 0.0
0300 21.6 60045 431.7 455.6 0.0 0.0 0.0 0.0 0.0 0.0
0400 21.3 60045 428.0 452.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 21.2 60045 419.5 441.9 0.0 0.0 0.0 0.0 0.0 0.0
0600 21.4 60045 414.5 437.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 21.8 60045 469.4 493.5 0.0 0.0 0.0 0.0 0.0 0.0
0800 22.6 60045 494.6 518.7 0.0 0.0 0.0 0.0 0.0 0.0
0900 23.8 60045 521.2 545.4 0.0 0.0 0.0 0.0 0.0 0.0
1000 25.1 60045 529.3 553.3 0.0 0.0 0.0 0.0 0.0 0.0
1100 26.6 60045 542.4 566.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 28.0 60045 557.9 582.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 29.0 60045 568.6 592.7 0.0 0.0 0.0 0.0 0.0 0.0
1400 29.7 60045 586.5 610.6 0.0 0.0 0.0 0.0 0.0 0.0
1500 30.0 60045 585.0 609.1 0.0 0.0 0.0 0.0 0.0 0.0
1600 29.7 60045 576.6 600.6 0.0 0.0 0.0 0.0 0.0 0.0
1700 29.1 60045 546.1 570.1 0.0 0.0 0.0 0.0 0.0 0.0
1800 28.2 60045 537.3 560.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 27.0 60045 523.5 547.4 0.0 0.0 0.0 0.0 0.0 0.0
2000 25.9 60045 513.0 536.9 0.0 0.0 0.0 0.0 0.0 0.0
2100 24.9 60045 508.8 532.9 0.0 0.0 0.0 0.0 0.0 0.0
2200 24.0 60045 500.1 524.3 0.0 0.0 0.0 0.0 0.0 0.0
2300 23.3 60045 479.2 503.2 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 9 of 18


System Psychrometrics for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

August DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 34.7 0.01972 0 400 0 0
Vent - Return Mixing Outlet 24.4 0.01022 60045 1340 - -
Central Cooling Coil Outlet 15.2 0.01008 60045 1340 666648 24135
Supply Fan Outlet 15.2 0.01008 60045 1340 0 -
Cold Supply Duct Outlet 15.2 0.01008 60045 1340 - -
Zone Air - 24.4 0.01022 60045 1340 666649 24043
Return Plenum Outlet 24.4 0.01022 60045 1340 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2940.3 W/(L/s)
Site Altitude = 20.7 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 668112 Cooling 666649 24.4 60045 1340 0 0

Hourly Analysis Program v4.90 Page 10 of 18


System Psychrometrics for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 20.6 0.00752 0 400 0 0
Vent - Return Mixing Outlet 20.7 0.01235 60045 800 - -
Central Cooling Coil Outlet 20.7 0.01235 60045 800 0 0
Supply Fan Outlet 20.7 0.01235 60045 800 0 -
Cold Supply Duct Outlet 20.7 0.01235 60045 800 - -
Zone Air - 20.7 0.01235 60045 800 -130 0
Return Plenum Outlet 20.7 0.01235 60045 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.204 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2940.3 W/(L/s)
Site Altitude = 20.7 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -5779 Deadband -130 20.7 60045 800 0 0

Hourly Analysis Program v4.90 Page 11 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

Data for January

Total Cooling Total Heating


600
550
500
450
400
Load ( kW )

350
300
250
200
150
100
50
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for February

Total Cooling Total Heating


650
600
550
500
450
Load ( kW )

400
350
300
250
200
150
100
50
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 12 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

Data for March

Total Cooling Total Heating


650
600
550
500
450
Load ( kW )

400
350
300
250
200
150
100
50
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for April

Total Cooling Total Heating


650
600
550
500
450
Load ( kW )

400
350
300
250
200
150
100
50
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 13 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

Data for May

Total Cooling Total Heating


650
600
550
500
450
Load ( kW )

400
350
300
250
200
150
100
50
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for June

Total Cooling Total Heating


700

600

500
Load ( kW )

400

300

200

100

0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 14 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

Data for July

Total Cooling Total Heating


700

600

500
Load ( kW )

400

300

200

100

0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for August

Total Cooling Total Heating


700

600

500
Load ( kW )

400

300

200

100

0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 15 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

Data for September

Total Cooling Total Heating


650
600
550
500
450
Load ( kW )

400
350
300
250
200
150
100
50
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for October

Total Cooling Total Heating


650
600
550
500
450
Load ( kW )

400
350
300
250
200
150
100
50
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 16 of 18


Hourly Air System Design Day Loads for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

Data for November

Total Cooling Total Heating


650
600
550
500
450
Load ( kW )

400
350
300
250
200
150
100
50
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for December

Total Cooling Total Heating


600
550
500
450
400
Load ( kW )

350
300
250
200
150
100
50
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program v4.90 Page 17 of 18


Psychrometric Analysis for for-food-tennant
Project Name: aircon design qloads 07 19 2019
Prepared by: addu 02:50AM

Location: Manila, Philippines


Altitude: 20.7 m.
Data for: August DESIGN COOLING DAY, 1600
0.020
1. Central Cooling Coil Outlet
2. Supply Fan Outlet
3. Room Air
0.018

0.016

Specific Humidity ( kg/kg )


0.014

0.012
12 3
0.010

0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 18 of 18