Sunteți pe pagina 1din 19

TABLA No.

DIMENSIONES DE LOS CONDUCTORES ELECTRICOS DESNUDOS

CALIBRE SECCIÓN DIÁMETRO


AWG o MCM CIRCULAR MIL Mm2 PULGADAS MILIMETROS
20 1 022 0.518 0.032 0.812
18 1 824 0.823 0.040 1.024
16 2 583 1.309 0.051 1.291
14 4 107 2.080 0.064 1.628
12 6 530 3.310 0.081 2.053

10 10 380 5.260 0.102 2.588


8 16 510 8.370 0.129 3.264
6 26 250 13.300 0.162 4.115
4 41 740 21.150 0.204 5.189
2 66 370 33.630 0.258 6.543

1/0 105 400 53.480 0.325 8.252


2/0 133 100 67.420 0.365 9.266
3/0 167 800 85.030 0.410 10.403
4/0 211 600 107.230 0.460 11.684

250 250 000 126.640 0.575 14.605


300 300 000 152.000 0.630 16.000
350 350 000 177.350 0.681 17.300
400 400 000 202.710 0.728 18.490
500 500 000 253.350 0.814 20.680

600 600 000 304.000 0.893 22.680


700 700 000 354.710 0.964 24.690
750 750 000 379.840 0.998 25.350
800 800 000 405.160 1.031 26.190
900 900 000 455.810 1.093 27.760

1000 1 000 000 506.450 1.152 29.260


1250 1 250 000 633.060 1.289 32.740
1500 1 500 000 759.680 1.412 35.870
1750 1 750 000 886.290 1.526 38.760
2000 2 000 000 1 012.900 1.631 41.420
TABLA No. 6

CAPACIDAD DE CORRIENTE EN AMPERES PARA CONDUCTORES DE COBRE,


AISLADOS Y, PARA UNA TEMPERATURA AMBIENTE DE 30º C.

CALIBRE TIPOS T, TW, UF (60º C) THW, THWN, RHW, XHW (75º C)


AWG o MCM TUBO o DUCTO EN AIRE TUBO o DUCTO EN AIRE
14 15 20 15 20
12 20 25 20 25
10 30 30 30 40
8 40 60 50 70
6 55 80 65 95
4 70 105 85 125
2 95 140 115 170
1/0 125 195 150 230
2/0 145 225 175 265
3/0 165 260 200 310
4/0 195 300 230 360
250 215 340 255 405
300 240 375 285 445
350 260 420 310 505
400 280 455 335 545
500 320 515 380 620
600 355 575 420 690
700 385 630 460 755
750 400 655 475 785
800 410 680 490 815
900 435 730 520 870
1000 455 780 545 935
FACTORES DE CORRECCIÓN PARA TEMPERATURAS AMBIENTES
MAYORES DE 30º C
31 A 35º C 0.91 0.91 0.94 0.94
36 A 40º C 0.82 0.82 0.88 0.88
41 A 45º C 0.71 0.71 0.82 0.82
46 A 50º C 0.58 0.58 0.75 0.75
51 A 55º C 0.41 0.41 0.67 0.67
56 A 60º C 0.58 0.58
61 A 79º C 0.41 0.41

NOTAS: Para 4 a 6 conductores en un tubo, la ampacidad se reduce al 80% de las cifras


dadas, de 7 a 9 conductores, la ampacidad se reduce al 70% ; al 50% si hay de 10 a 20
conductores y, al 45% si hay de 21 a 30 conductores en un tubo. En un sistema balanceado,
el neutro no cuenta como conductor para los efectos de esta nota.
TABLA No. 7

CAPACIDAD DE CORRIENTE EN AMPERES PARA CONDUCTORES DE COBRE,


AISLADOS Y, PARA UNA TEMPERATURA AMBIENTE DE 30° C

CALIBRE THHW, RHH, THHN, XHHW (90º C) VINICON, AVA, AVL (110º C)
AWG o MCM TUBO o DUCTO EN AIRE TUBO o DUCTO EN AIRE
14 25 35 30 40
12 30 40 35 50
10 40 55 45 65
8 55 80 60 85
6 75 105 80 120
4 95 140 105 160
2 130 190 135 210
1/0 170 260 190 285
2/0 195 300 215 330
3/0 225 350 245 380
4/0 260 405 275 445
250 290 455 315 495
300 320 505 345 555
350 350 570 390 610
400 380 615 420 665
500 430 700 470 765
600 475 780 525 855
700 500 850 560 940
750 535 885 580 980
800 550 900 600 1 020
1000 615 1 055 680 1 165
FACTORES DE CORRECCION PARA TEMPERATURAS AMBIENTES
MAYORES DE 30º C
31 A 35º C 0.96 0.96 0.97 0.97
36 A 40º C 0.91 0.91 0.94 0.94
41 A 45º C 0.87 0.87 0.90 0.90
46 A 50º C 0.82 0.82 0.87 0.87
51 A 55º C 0.76 0.76 0.83 0.83
56 A 60º C 0.71 0.71 0.79 0.79

NOTAS: Para 4 a 6 conductores en un tubo, la ampacidad se reduce al 80% de las cifras


dadas. De 7 a 9 conductores, la ampacidad se reduce al 70% ; de 10 a 20 al 50% y de 21 a
30 al 45%. En un sistema balanceado, el neutro no cuenta como conductor para los efectos
de esta nota.
TABLA No. 8

NUMERO MAXIMO DE CONDUCTORES TIPO T, TW, THW, THHW, XHHW QUE PUEDEN
INSTALARSE EN UN TUBO CONDUIT DE ACUERDO CON LOS FACTORES DE
RELLENO AUTORIZADOS POR LAS NORMAS OFICIALES NOM-001-SEDE.

CALIBRE DIAMETRO NOMINAL DEL TUBO EN MILÍMETROS


CONDUCTOR 13 19 25 32 38 51 63 76 89 102 127 152

14 9 15 25 44 60 99 142
12 7 12 19 35 47 78 111 171
10 5 9 15 26 36 60 85 111 176
8 2 4 7 12 17 28 40 62 84 108

6 1 2 4 7 10 16 23 36 48 62 97 141
4 1 1 3 5 7 12 17 27 36 47 73 106
2 1 1 2 4 5 9 13 20 27 34 54 78

1/0 - 1 1 2 3 5 8 12 16 21 33 49
2/0 - 1 1 1 3 5 7 10 14 18 29 41
3/0 - 1 1 1 2 4 6 9 12 15 24 35
4/0 - - 1 1 1 3 5 7 10 13 20 29

250 1 1 1 2 4 6 8 10 16 23
300 1 1 1 2 3 5 7 9 14 20
350 1 1 1 3 4 6 8 12 18
400 1 1 1 2 4 5 7 11 16
500 1 1 1 1 3 4 6 9 14

600 1 1 1 3 3 5 7 11
750 1 1 1 2 3 4 6 9
800 1 1 1 1 3 4 6 8
900 1 1 1 3 3 5 8
1000 1 1 1 2 3 5 7
TABLA No. 9

NUMERO MAXIMO DE CONDUCTORES TIPO THWN Y THHN QUE PUEDEN


INSTALARSE EN UN TUBO CONDUIT DE ACUERDO CON LOS FACTORES DE
RELLENO AUTORIZADOS POR LAS NORMAS OFICIALES NOM-001-SEDE.

CALIBRE DIÁMETRO NOMINAL DEL TUBO EN MILÍMETROS


CONDUCTOR 13 19 25 32 38 51 63 76 89 102 127 152

14 13 24 39 69 94 154
12 10 18 29 51 70 114 164
10 6 11 18 32 44 73 104 160
8 3 5 9 16 22 36 51 79 106 136

6 1 4 6 11 15 26 37 57 76 98 154
4 1 2 4 7 9 16 22 35 47 60 94 137
2 1 1 3 5 7 11 16 25 33 43 67 97

1/0 1 1 3 4 7 10 15 21 27 42 61
2/0 1 1 2 3 6 8 13 17 22 35 51
3/0 1 1 1 3 5 7 11 14 18 29 42
4/0 1 1 1 2 4 6 9 12 15 24 35

250 1 1 1 3 4 7 10 12 20 28
300 1 1 1 3 4 6 8 11 17 24
350 1 1 2 3 5 7 9 15 21

400 1 1 1 3 5 6 8 13 19
500 1 1 1 2 4 5 7 11 16
750 1 1 1 2 3 4 7 11
TABLA No. 10

CANTIDAD DE CONDUCTORES QUE PUEDEN ALOJARSE EN UN DUCTO DE LÁMINA

SECCIÓN CONDUCTOR DUCTOS DE LÁMINA


CALIBRE CON AISLAMIENTO mm2 SECCION TRANSVER. mm2
CONDUCTOR THWN, TW, THW MEDIDAS TOTAL 20% TOTAL
AWG o MCM THHN XHW EN mm

14 5.80 8.30 60 x 60 3 600 720


12 7.90 10.64 100 x 100 10 000 2 000
10 12.30 13.99 150 x 150 22 500 4 500
8 21.10 26.70 200 x 200 40 000 8 000

6 34.20 49.29
4 55.15 65.61
2 77.00 89.42 PARA USAR ESTA TABLA:
1.- Determinar cantidad, tipo y calibre de
conductores a canalizar.
1/0 123.50 143.99
2.- Sumar sus secciones transversales.
2/0 147.60 169.72 3.- Escoger el ducto adecuado, utilizando
3/0 176.70 201.06 la columna del 20% de su sección - -
4/0 211.20 239.98 transversal.

250 261.30 298.65


300 302.60 343.07
350 346.19 386.88
400 384.30 430.05

500 463.00 514.72


600 572.27 628.70
750 673.91 735.04
1000 813.92 934.35
TABLA No. 11

RESISTENCIA DE CONDUCTORES CON CORRIENTE DIRECTA, FACTORES DE


CORRECCION AL OPERARLOS CON CORRIENTE ALTERNA POR EL EFECTO PIEL Y,
REACTANCIA AL NEUTRO PARA UNA FRECUENCIA DE 60 HERTZ.

CALIBRE RESISTENCIA FACTOR DE CORRECCIÓN REACTANCIA EN


CONDUCTOR C. DIRECTA POR EFECTO PIEL OHMS / 1000 PIES
AWG o MCM OHMS / 1000’ (1) (2) MÍNIMA MÁXIMA
14 3.0000 1.000 1.000
12 1.8700 1.000 1.000
10 1.1800 1.000 1.000
8 0.7400 1.000 1.000 0.041 0.045
6 0.4650 1.000 1.000 0.040 0.045
4 0.2920 1.000 1.000 0.037 0.050
2 0.1850 1.000 1.010 0.035 0.048
1/0 0.1600 1.000 1.020 0.034 0.048
2/0 0.0920 1.000 1.030 0.032 0.044
3/0 0.0730 1.000 1.040 0.031 0.044
4/0 0.0580 1.000 1.050 0.030 0.045
250 0.0490 1.005 1.060 0.030 0.044
300 0.0408 1.006 1.070 0.029 0.045
350 0.0350 1.009 1.080 0.029 0.044
400 0.0306 1.011 1.100 0.029 0.043
500 0.0245 1.018 1.130 0.028 0.038
600 0.0204 1.025 1.160 0.028 0.038
750 0.0163 1.039 1.210 0.028 0.035
1000 0.0123 1.067 1.300 0.028 0.038
1250 0.0098 1.102 1.410 0.028 0.038
1500 0.0082 1.142 1.530 0.028 0.038
1750 0.0070 1.185 1.659 0.027 0.037
2000 0.0061 1.233 1.800 0.027 0.038

NOTAS: ( 1 ) Conductor en aire o en tubo no magnético.


( 2 ) Conductor en tubo de acero.
♦ Los valores de la reactancia mínima se aplican para conductores juntos dentro de un tubo
o de un ducto.
♦ Los valores de la reactancia máxima se aplican para conductores separados en
instalaciones aéreas o en ménsulas en galerías de conductores.
♦ Para conductores en ductos o tubos de acero o, con armadura de acero, la reactancia
aumenta en un 25%. Por lo tanto, multiplíquense los valores por 1.25.
TABLA No. 12

CAPACIDADES Y DIMENSIONES DE CARTUCHOS FUSIBLES

CAPACIDAD EN 250 VOLTS 600 VOLTS


AMPERES LARGO (mm) DIÁMETRO(mm) LARGO (mm) DIÁMETRO(mm)
FUSIBLES TIPO TAPÓN
10, 15, 20, 25 Y
30 --- --- --- ---
FUSIBLES TIPO CASQUILLO
3, 5, 6, 10, 15,
20, 25 Y 30 53 14 125 19
35, 40, 45, 50 Y
60 76 21 139 26
FUSIBLES TIPO NAVAJA
75, 90, 100 151 30 200 35
125, 150, 175,
200 181 42 244 47
225, 250, 300 219 56 295 65
500, 600 263 67 340 76
TABLA No. 13

CAPACIDAD Y DIMENSIONES DE LOS INTERRUPTORES TERMOMAGNETICOS

CAPACIDAD No. DIMENSIONES EN


MARCO CAPACIDAD EN INTERRUPTIVA DE CENTIMETROS
AMPERES 240V 480V 600V POLOS ALTO ANCHO FONDO
15, 20, 30, 40, 50, 1 7.5 2.5 7.3
QL 70, 100 10000 --- --- 2 7.5 5.0 7.3
3 7.5 7.5 7.3
15, 20, 30, 40, 50, 1 15.3 3.5 8.6
FA 70, 100 10000 --- --- 2 15.3 7.0 8.6
3 15.3 10.5 8.6
15, 20, 30, 40, 50,
FB 70, 100, 125, 150 18000 14000 14000 2 15.3 7.0 8.6
3 15.3 10.5 8.6
15, 20, 30, 40, 50,
HFB 70, 100, 125, 150 65000 25000 18000 2 15.3 7.0 8.6
3 15.3 10.5 8.6
LB 125, 150, 175,
200, 225 25000 22000 22000 3 25.7 14.0 10.3
LB 250, 300, 350,
400 42000 30000 22000 3 25.7 14.0 10.3
125, 150, 175,
HLB 200, 225, 250, 65000 35000 25000 3 25.7 14.0 10.3
300, 350, 400
LA 500, 600 42000 30000 22000 3 27.6 21.0 10.3
NB 700, 800, 1000,
1200 42000 30000 22000 3 41.2 21.0 14.0
PB 1400, 1600, 1800
2000, 2500, 3000 125000 100000 100000 3 56.2 30.5 22.9
NC (+) 800, 900, 1000,
1200 42000 30000 22000 3
1000, 1200, 1400
PC (+) 1600, 1800, 2000 125000 100000 100000 3
2500, 3000
MPC 3, 7, 15, 30, 50,
100, 150 25000 22000 22000 3 15.3 10.5 8.6

NOTAS: (+) Interruptores con protección electrónica.


MPC: Interruptor magnético instantáneo.
TABLA No. 14

CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE DIRECTA

POTENCIA EN VOLTAJE
HP 115 VOLTS 230 VOLTS 550 VOLTS

0.50 4.6 2.3 --


0.75 6.6 3.3 1.4
1.00 8.6 4.3 1.8
1.50 12.6 6.3 2.5
2.00 16.4 8.2 3.4
3.00 24.0 12.0 5.0

5.0 40.0 20.0 8.3


7.5 58.0 29.0 12.0
10.0 76.0 38.0 16.0
15.0 112.0 56.0 23.0
20.0 148.0 74.0 31.0

25.0 184.0 92.0 38.0


30.0 220.0 110.0 46.0
40.0 292.0 146.0 61.0
50.0 360.0 180.0 75.0
60.0 430.0 215.0 90.0

75.0 536.0 268.0 111.0


100.0 --- 355.0 148.0
125.0 --- 443.0 184.0
150.0 --- 534.0 220.0
200.0 --- 712.0 295.0
TABLA No. 15

CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE ALTERNA


MONOFASICOS

POTENCIA EN VOLTAJES
HP 115 VOLTS 230 VOLTS 440 VOLTS

1/6 3.2 1.6 ---


¼ 4.6 2.3 ---
½ 7.4 3.7 ---
¾ 10.2 5.1 ---
1.0 13.0 6.5 ---

1.5 18.4 9.2 ---


2.0 24.0 12.0 ---
3.0 34.0 17.0 ---
5.0 56.0 28.0 ---
7.5 80.0 40.0 21.0
10.0 100.0 50.0 26.0
TABLA No. 16

CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE ALTERNA TRIFASICOS

POTENCIA MOTORES DE INDUCCIÓN MOTORES SÍNCRONOS


HP 220 V 440 V 550 V 2400 V 220 V 440 V 550 V 2300 V

1/2 2.0 1.0 0.8 --- --- --- --- ---


3/4 2.8 1.4 1.1 --- --- --- --- ---
1.0 3.5 1.8 1.4 --- --- --- --- ---
1.5 5.0 2.5 2.0 --- --- --- --- ---
2.0 6.5 3.3 2.6 --- --- --- --- ---

3.0 9.0 4.5 4.0 --- --- --- --- ---


5.0 15.0 7.5 6.0 --- --- --- --- ---
7.5 22.0 11.0 9.0 --- --- --- --- ---
10.0 27.0 14.0 11.0 --- --- --- --- ---
15.0 40.0 20.0 16.0 --- --- --- --- ---

20.0 52.0 26.0 21.0 --- --- --- --- ---


25.0 64.0 32.0 26.0 7.0 54.0 27.0 22.0 5.4
30.0 78.0 39.0 31.0 8.5 65.0 33.0 26.0 6.5
40.0 104.0 52.0 41.0 10.5 86.0 43.0 35.0 8.0
50.0 125.0 63.0 50.0 13.0 108.0 54.0 44.0 10.0

60.0 150.0 75.0 60.0 16.9 128.0 64.0 51.0 12.0


75.0 185.0 93.0 74.0 19.0 161.0 81.0 65.0 15.0
100.0 246.0 123.0 98.0 25.0 211.0 106.0 85.0 20.0
125.0 310.0 155.0 124.0 31.0 264.0 132.0 106.0 25.0
150.0 360.0 180.0 144.0 37.0 --- 158.0 127.0 30.0

200.0 480.0 240.0 192.0 48.0 --- 210.0 168.0 40.0


250.0 --- 300.0
300.0 --- 345.0
350.0 --- 406.0
400.0 --- 475.0
TABLA No. 17

CAPACIDAD O AJUSTE MAXIMO DEL DISPOSITIVO DE PROTECCION PARA LOS


CIRCUITOS DERIVADOS DE LOS MOTORES

POR CIENTO DE LA CORRIENTE A PLENA CARGA


TIPO DE MOTOR FUSIBLES INT. TERMOMAGNÉTICO
NORMAL ACC. RET. INSTANT. TIEMPO INV.

Todos los motores monofásicos o


trifásicos, jaula de ardilla, con
arranque a tensión plena o con
resistencias o reactancias:
LETRA DE CÓDIGO “A” 150 150 700 150
LETRA DE CÓDIGO “B a E” 250 175 700 200
LETRA DE CÓDIGO “F a V” 300 175 700 250
SIN LETRA CÓDIGO 300 175 700 250

Todos los motores jaula de ardilla y


síncronos con arranque por
autotransformador:
LETRA DE CÓDIGO “A” 150 150 700 150
LETRA DE CÓDIGO “B a E” 200 175 700 200
LETRA DE CÓDIGO “F a V” 250 175 700 200
SIN LETRA DE CÓDIGO 250 175 700 200

Motores jaula de ardilla de alta


reactancia y no mayores de 30 A. 250 175 700 250

Motores jaula de ardilla de alta


reactancia y mayores de 30 A. 200 175 700 200

Motores de rotor devanado 150 150 700 150


TABLA No. 18

RELACION QUE MUESTRA ALGUNAS DE LAS CAPACIDADES DE LOS ELEMENTOS


TERMICOS UTILIZADOS PARA LA PROTECCION CONTRA SOBRECARGA DE LOS
MOTORES

CAPACIDAD EN AMPERES CAPACIDAD EN AMPERES CAPACIDAD EN AMPERES

TAMAÑOS 0 Y 1 TAMAÑOS 0 Y 1 TAMAÑOS 2 A 8

0.167 - 0.187 5.040 - 5.590 91.80 - 105.0


0.188 - 0.210 5.600 - 6.250 106.0 - 121.0
0.211 - 0.237 6.260 - 6.920 122.0 - 135.0
0.238 - 0.266 6.930 - 7.750 126.0 - 139.0
0.267 - 0.298 7.760 - 8.630 140.0 - 157.0
0.299 - 0.334 8.640 - 9.590 158.0 - 175.0
0.335 - 0.376 9.600 - 10.60 176.0 - 196.0
0.377 - 0.422 10.70 - 11.90 197.0 - 218.0
0.423 - 0.474 12.00 - 13.30 219.0 - 243.0
0.475 - 0.532 13.40 - 14.70 244.0 - 270.0
0.533 - 0.598 14.80 - 16.60 264.0 - 295.0
0.599 - 0.672 16.70 - 18.80 296.0 - 330.0
0.673 - 0.757 18.90 - 21.20 331.0 - 369.0
0.758 - 0.855 21.30 - 23.90 370.0 - 410.0
0.856 - 0.959 24.00 - 27.00 411.0 - 458.0
0.969 - 1.070 459.0 - 512.0
1.080 - 1.210 TAMAÑOS 2 A 8 513.0 - 574.0
1.220 - 1.350 550.0 - 607.0
1.360 - 1.520 24.60 - 27.90 608.0 - 685.0
1.530 - 1.700 28.00 - 32.00 686.0 - 763.0
1.710 - 1.900 32.10 - 36.60 764.0 - 855.0
1.910 - 2.100 36.70 - 41.80 828.0 - 924.0
2.110 - 2.330 41.90 - 45.00 925.0 - 1 027
2.340 - 2.620 42.90 - 48.50 1 028 - 1 147
2.630 - 2.930 48.60 - 55.10 1 148 - 1 285
2.940 - 3.270 55.20 - 62.30
3.280 - 3.640 62.40 - 69.50
3.650 - 4.060 69.60 - 79.10
4.070 - 4.550 79.20 - 90.00
4.560 - 5.030 80.00 - 91.70
TABLA 19

POTENCIA MAXIMA DEL BANCO DE CAPACITORES PARA COMPENSAR FACTORES


DE POTENCIA DE MOTORES TRIFASICOS DE INDUCCION, LIMITANDO EL
FENOMENO DE AUTOINDUCCION.

POTENCIA VELOCIDAD DE SINCRONISMO DEL MOTOR EN R. P. M.


MOTOR EN HP 3 600 1 800 1 200 900 720 600

10 2.5 4.0 4.0 5.0 5.0 6.5


15 2.5 5.0 5.0 7.5 7.5 10.0
20 5.0 5.0 5.0 7.5 10.0 12.5
25 5.0 7.5 7.5 10.0 10.0 15.0

30 7.5 10.0 10.0 10.0 12.5 15.0


40 10.0 10.0 10.0 12.5 15.0 17.5
50 12.5 12.5 12.5 15.0 20.0 22.5
60 15.0 15.0 15.0 17.5 22.5 25.0
75 17.5 17.5 17.5 20.0 27.5 30.0

100 22.5 22.5 22.5 25.0 35.0 37.5


125 25.0 27.5 27.5 30.0 40.0 47.5
150 32.5 32.5 35.0 37.5 47.5 55.0
200 42.5 42.5 42.5 45.0 60.0 67.5
TABLA No. 20

MULTIPLICADORES DE KW PARA DETERMINAR LOS KVAR EN CAPACITORES, REQUERIDOS


PARA CORREGIR EL FACTOR DE POTENCIA

F. P. FACTOR DE POTENCIA CORREGIDO


ORIGINA 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.98 1.00
L

0.56 0.996 1.024 1.054 1.085 1.117 1.151 1.188 1.277 1.480
0.58 0.921 0.949 0.979 1.010 1.042 1.076 1.113 1.202 1.405
0.60 0.849 0.877 0.907 0.938 0.970 1.004 1.041 1.130 1.333
0.62 0.782 0.810 0.840 0.871 0.903 0.937 0.974 1.063 1.266
0.64 0.717 0.745 0.775 0.806 0.838 0.872 0.909 0.998 1.201
0.66 0.654 0.682 0.712 0.743 0.775 0.809 0.846 0.935 1.138
0.68 0.594 0.622 0.652 0.683 0.715 0.749 0.786 0.875 1.078
0.70 0.536 0.564 0.594 0.625 0.657 0.691 0.728 0.817 1.020

0.72 0.480 0.508 0.538 0.569 0.601 0.635 0.672 0.761 0.964
0.74 0.425 0.453 0.483 0.514 0.546 0.580 0.617 0.706 0.909
0.76 0.371 0.399 0.429 0.460 0.492 0.526 0.563 0.652 0.855
0.78 0.318 0.346 0.376 0.407 0.439 0.473 0.510 0.599 0.802
0.80 0.266 0.294 0.324 0.355 0.387 0.421 0.458 0.547 0.750
0.81 0.240 0.268 0.298 0.329 0.361 0.395 0.432 0.521 0.724
0.82 0.214 0.242 0.272 0.303 0.335 0.369 0.406 0.495 0.698
0.83 0.188 0.216 0.246 0.277 0.309 0.343 0.380 0.469 0.672
0.84 0.162 0.190 0.220 0.251 0.283 0.317 0.354 0.443 0.646
0.85 0.136 0.164 0.194 0.225 0.257 0.291 0.328 0.417 0.620

0.86 0.109 0.137 0.167 0.198 0.230 0.264 0.301 0.390 0.593
0.87 0.083 0.111 0.141 0.172 0.204 0.238 0.275 0.364 0.567
0.88 0.056 0.084 0.114 0.145 0.177 0.211 0.248 0.337 0.540
0.89 0.028 0.056 0.086 0.117 0.149 0.183 0.220 0.309 0.512
0.90 0.028 0.058 0.089 0.121 0.155 0.192 0.281 0.484

0.91 0.030 0.061 0.093 0.127 0.164 0.253 0.456


0.92 0.031 0.063 0.097 0.134 0.223 0.426
0.93 0.032 0.066 0.103 0.192 0.395
0.94 0.034 0.071 0.160 0.363
0.95 0.037 0.126 0.329

0.96 0.089 0.292


0.97 0.048 0.251
0.98 0.203
0.99 0.143
EJEMPLO:

Se tiene una carga de 600 kilowatts con un factor de potencia de 0.80, que se desea corregir
a 0.92. Se entra a la columna de “factor de potencia original” con el dato de 0.80 y, en el
mismo renglón , se busca la constante para corregir el factor de potencia a 0.92,
encontrándose que es 0.324, el cual se multiplica por los 600 kilowatts de demanda. Se
tendrá así:

600 * 0.324 = 194.4

siendo el resultado así obtenido, la capacidad del banco de capacitores en KVAR.


TABLA No. 21

FACTORES DE DEMANDA PROMEDIO

TIPO DE SERVICIO F. DEMANDA TIPO DE SERVICIO F. DEMANDA

Alumbrado público 1.00 Fábricas de cigarros 0.60


Apartamentos 0.35 Fábricas de dulces 0.45
Bancos 0.70 Talleres de fundición 0.70
Bodegas 0.50 Fábricas de galletas 0.55
Casinos 0.85 Fábricas de hielo 0.90
Correos 0.30 Talleres de herrería 0.50
Escuelas 0.70 Imprentas 0.60
Garages 0.60 Fábricas de jabón 0.60
Hospitales 0.40 Fáb. artículos de lámina 0.70
Hoteles chicos 0.50 Talleres de niquelado 0.75
Hoteles grandes 0.40 Madererías 0.65
Iglesias 0.60 Talleres de marmolería 0.70
Mercados 0.80 Talleres mecánicos 0.75
Multifamiliares 0.25 Fábricas de muebles 0.65
Oficinas 0.65 Fábricas de pan 0.55
Restaurantes 0.65 Fábricas de papel 0.75
Teatros 0.60 Periódicos 0.75
Tiendas 0.65 Fábricas de pinturas 0.70
Fábricas de acetileno 0.70 Industria química 0.50
Industria automotriz 0.70 Refinerías 0.60
Talleres de carpintería 0.65 Fábricas de refrescos 0.55
Empacadoras de carne 0.80 Industria textil 0.65
Fábricas de cartón 0.50 Fábricas de ropa 0.45
Fábricas de cemento 0.65 Fábricas de zapatos 0.45
TABLA NO. 22

TABLA 250-95 SECCIÓN TRANSVERSAL MÍNIMA DE LOS CONDUCTORES DE PUESTA


A TIERRA PARA CANALIZACIONES Y EQUIPOS

CAPACIDAD DEL DISPOSITIVO SECCIÓN TRANSVERSAL SECCIÓN TRANSVERSAL


AUTOMÁTICO DE SOBRE COBRE ALUMINIO
CORRIENTE ANTES DEL EQUIPO mm2 AWG mm2 AWG
15 2.082 14 3.307 12
20 3.307 12 5.260 10
30 5.260 10 8.367 8
40 5.260 10 8.367 8
60 5.260 10 8.367 8
100 8.367 8 13.300 6
200 13.300 6 21.150 4
300 21.150 4 33.620 2
400 27.670 3 42.410 1
500 33.620 2 53.480 1/0
600 42.410 1 67.430 2/0
800 53.480 1/0 85.010 3/0
1000 67.430 2/0 107.200 4/0

S-ar putea să vă placă și