NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS OTHERWISE NOTED.

2. THE ARCHITECTURAL BACKGROUNDS ARE DRAWN TO SCALE HOWEVER MEP SYMBOLS


& DATA ARE NOT NECESSARILY DRAWN TO SCALE. IF IN DOUBT, REQUEST FURTHER
SUPPORT TO CABLE TRAY
INFORMATION.
WITHIN 300mm EACH
SIDE
3. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH THE MAIN CONTRACT
CONDITIONS, THE BUILDING SERVICES SPECIFICATIONS AND SCHEDULES, AND ALL

OF
OTHER CONTRACT DOCUMENTATION.

CONSENT
4. REFER TO THE ARCHITECT’S DRAWINGS FOR DETAILS OF ALL SETTING OUT
INFORMATION. NO DIMENSIONS SHALL BE MEASURED FROM THIS DRAWING.
TYPE CC LINDAPTOR OR EQUAL 500mm 500mm

5. REFER TO THE ARCHITECT’S REFLECTED CEILING PLANS (HA-161617-083 TO 155 &


161633-001, 002, 003 & 005) FOR THE SETTING OUT OF ALL SOFFIT MOUNTED
STEEL GIRDER SERVICES COMPONENTS.
AND BEAM FLAMEMASTIC COATING ON CABLES

TTEN
AND TRAY 500mm EITHER SIDE 6. REFER TO THE ARCHITECT’S DRAWINGS FOR DETAILS OF ALL BUILDING
3 No.LAYERS MINERAL WOOD OF WALL AS BERGER K.BS COMPARTMENTATION. ALL SERVICES SHALL BE FIRE STOPPED USING THE APPROVED
SLAB PANELS TO MAKE UP PENETRATION SEAL F.P.S.2.

WRI
MORTAR INFILL TO FOAM CURB PENETRATION DETAILS, FULLY IN ACCORDANCE WITH THE COMPARTMENT RATING.
WALL THICKNESS SPIKED
TOGETHER & FIXED BY CHANNEL
7. THE CONSTRUCTION CONTRACTOR SHALL PROVIDE CO-ORDINATED INSTALLATION
AT TOP & BOTTOM & COATED
DRAWINGS FOR REVIEW AND PRIOR TO INSTALLATION ON SITE AS DEFINED IN

THE
WITH FLAMEMASTIC COATING
26x3mm TINNED COPPER TAPE CONTRACT PRELIMS. THE CONSTRUCTION CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING ALL ROUTES SHOWN AND MODIFY WHERE NECESSARY ON THE
INSTALLATION DRAWINGS PRIOR TO COMMENCING INSTALLATION ON SITE. ALL
MINERAL WOOL SLAB PANELS TO INFILL

THOUT
INFORMATION SHALL BE ISSUED IN A TIMELY MANNER TO ALLOW THE REVIEW AND
HOLE AROUND CABLE TRAY SPIKED
APPROVAL PROCESS WITHOUT AFFECTING THE CONSTRUCTION SCHEDULE.
TOGETHER & FIXED BY CHANNEL

8. THE CONTRACTOR SHALL CARRY OUT ALL WORKS, SYSTEMS, ETC. TO A METHOD,

WI
STANDARD AND SCHEDULE APPROVED BY THE COMPANY.

ELECTRICAL SERVICES CABLE THROUGH WALL 9. THESE GENERAL NOTES SHALL BE READ IN CONJUNCTION WITH ALL RELEVANT SAUDI

NG
ELECTRICAL SERVICES TYPICAL STEELWORK EARTH CONNECTION ELEC
ELEC ARAMCO STANDARDS. PLEASE REFER TO DRAWINGS HA-162371-001,

DRAWI
103 SCALE: N.T.S.
102 SCALE: N.T.S.
HA-162372-001 & 002 & HA-162373-001 AND ALL MEP SPECIFICATIONS WHICH
DETAILS THE SPECIFIC SAUDI ARAMCO STANDARDS APPLICABLE TO EACH MEP
CABLE TRAY & CABLES WITH
DISCIPLINE.
FLAMEMASTIC COATING AS BERGER
K.B.S. PENETRATING SEAL F.P.S2
10. THE DESIGN DRAWINGS DO NOT NECESSARILY SHOW ALL COMPONENTS WHICH MAY

S
THI
BE REQUIRED TO FORM A COMPLETE INSTALLATION. THE CONTRACTOR SHALL PROVIDE
ALL ACCESSORIES AND FITTINGS AS NECESSARY FOR A COMPLETE INSTALLATION IN
ACCORDANCE WITH THE MEP SPECIFICATIONS.

FROM
11. REFER TO DRAWING HA-162371-001 FOR ALL HVAC SYMBOLS, ABBREVIATIONS AND
STANDARD HVAC NOTES.

12. REFER TO DRAWINGS HA-162372-001 & 002 FOR ALL ELECTRICAL SYMBOLS,

NED
ABBREVIATIONS AND STANDARD ELECTRICAL NOTES.
ELEC CABLE TRAY FIRE STOPPING DETAIL THROUGH FLOOR SLAB
SCALE: N.T.S.
101

OBTAI
13. REFER TO DRAWING HA-162373-001 FOR ALL PLUMBING & FIRE PROTECTION
SYMBOLS, ABBREVIATIONS & STANDARD PLUMBING & FIRE PROTECTION NOTES.

BE
PART,SHALL
POKE-THRU
RECEPTACLE

FIRE RATED CONCRETE WALL

FLOOR SLAB FLOOR SLAB


GALVANIZED STANDARD WEIGHT STEEL
FINISH FLOOR
PIPE SLEEVE WITH 1/4" STEEL PLATE
WATER STOP AND ANCHOR COLLAR SLAB

N
I
STEEL ZINC DICHROMATE BOLTS, EARTH
NOLTS AND WASHERS

FULL,OR
DIAMETER AS PVC CONDUIT

RECOMMENDED J-BOX(TYP)
BY SEAL
MANUFACTURER
CEILING REFERENCE DRAWINGS

N
BELOW

I
DWG. CONTROL FOR J.O. 10-07575-0001 HD 161614 001
RESILIENT WATERPROOF METAL PIPE OR CONDUIT

ON
STEEL ELBOW ELECTRICAL STANDARD SYMBOL SHEET HA 162372 001
CAULKING (TYP)

REPRODUCTI
(PVC COATED
ELECTRICAL SPECIFICATION HE 162356 001
MODULAR TYPE WALL PENETRATION PVC SLIP/THREAD FOR CORROSION
SEAL (LINK-SEAL LS SERIES OR FITTING PROTECTION) ELECTRICAL SCHEDULES HA 162467 001 - 019
EQUAL)

INTERIOR SIDE OF WALL

SAUDIARAMCO.NO
CONDUIT PENETRATION THROUGH CONCRETE WALL POKE-THRU’ RECEPTACLE WITH WIRING IN CEILING BELOW STEEL ELBOW THRU FLOOR DETAIL
ELEC ELEC ELEC
N
104 SCALE: N.T.S.
105 SCALE: N.T.S.
106 SCALE: N.T.S.

MAKKAH

S65^45W’

OF
PROPERTY
3M FIRE FIRE RATED
1-2 HOUR FIRE
BARRIER CP CONCRETE
RATED GYPSUM FIRE RATED
25 CAULK FLOOR SLAB
WALLBOARD CONCRETE WALL
1 HOUR GYPSUM
WALLBOARD

SOLE
ASSEMBLY
3M FIRE BARRIER
FS-195
1" MINERAL WOOL WRAP/STRIP
1/4" BEAD
PACKING
3M FIREDAM 150 CAULK

THE
DAMMING 3M FIRE BARRIER
3/4" DEPTH MATERIAL FS-195 WRAP/STRIP
3M FIREDAM 150

ARE
CAULK
METAL PIPE OR
CONDUIT
TABLE 1

N
HEREI
WRAP CAULK INSULATION
0 1.0 2.0 3.0 4.0 5.0 10.0
1 WRAP 1" DEPTH 1" THICK
UL SYSTEM #CAJ 5001
2 WRAP 2" DEPTH 2" THICK METAL PIPE OR
1" MAXIMUM UL SYSTEM #CAJ 5002 TABLE 1
3 WRAP 3" DEPTH 3" THICK CONDUIT METERS
ANNULAR UL SYSTEM #CAJ 5003
WRAP CAULK INSULATION
6" MAXIMUM SPACE UL SYSTEM #CBJ 5002 3M FIRE

NED
DIAMETER STEEL 1 WRAP 1" DEPTH 1" THICK BARRIER CP N.T.S.
UL SYSTEM #CBJ 5003
2 WRAP 2" DEPTH 2" THICK 150 CAULK SCALE:
CONDUIT
3 WRAP 3" DEPTH 3" THICK

CONTAI
NOTES
MINIMUM 28
WOOD OR STEEL STUD
GAUGE STEEL UL SYSTEM #CAJ 1017
1. THE MAXIMUM ANNULAR SPACE TO BE FILLED IN THE REVISION VALIDATION
SLEEVE
WALL IS 3", AND THE MINIMUM ANNULAR SPACE IS
NOTES THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
3/4".
REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
2. FS-195 WRAP/STRIPS ARE FRICTION FIT INTO THE 1. WALL PENETRATION FIRE STOPS MUST BE INSTALLED ON

ON
OPENING OR SECURED WITH 16 GAUGE STEEL TIE WIRE BOTH SIDES OF THE WALL. 10-07575-0001-001

NFORMATI
OR ALUMINUM FOIL TAPE AND SLID INTO THE OPENING
2. THE MAXIMUM ANNULAR SPACE TO BE FILLED IN THE
WITH A MINIMUM 1/4" BEAD OF CP 25 CAULK. DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
UL SYSTEM #WL5001
WALL IS 3", AND THE MINIMUM ANNULAR SPACE IS (DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)
3. THE MINIMUM ANNULAR SPACE MUST ACCOMADATE THE 3/4". ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE
MINIMUM NUMBER OF FS-195 WRAP/STRIPS REQUIRED PER SGC GRH NAH FFT
3. FS-195 WRAP/STRIPS ARE FRICTION FIT INTO THE
INSULATION THICKNESS. SEE TABLE 1 BELOW. 04/15/10 04/15/10 04/15/10 04/15/10
OPENING OR SECURED WITH 16 GAUGE STEEL TIE WIRE
OR ALUMINUM FOIL TAPE AND SLID INTO THE OPENING REV.NO. DATE REVISION DESCRIPTION

I
WITH A MINIMUM 1/4" BEAD OF CP 25 CAULK. 00 04/15/10 IFC
ELEC PENETRATION FIRESTOP FOR CONDUIT THROUGH GYPSUM WALLBOARD ELEC PENETRATION FIRESTOP FOR CONDUIT THROUGH FLOOR SLAB

THE
4. THE MINIMUM ANNULAR SPACE MUST ACCOMADATE THE
107 SCALE: N.T.S.
108 SCALE: N.T.S. JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
MINIMUM NUMBER OF FS-195 WRAP/STRIPS REQUIRED PER
INSULATION THICKNESS. SEE TABLE 1 ABOVE.
10-07575-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
ELEC PENETRATION FIRESTOP FOR CONDUIT THROUGH CONCRETE WALL DRAWING TYPE

109 SCALE: N.T.S. ELECTRICAL PLAN/LAYOUT/DETAIL EDT

NG
ELEC STANDARD DETAILS SHEET 1

DRAWI
K.A.C.K.C (ITHRA)

DHAHRAN SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
H75 P HA-162461 001 00
Saudi Aramco 2615 ENG. (05/05)

CONFIDENTIAL VECTOR CADD-01