Series L-BG Linear Bar Grilles and Registers are PERFORMANCE: Multiple applications of series
engineered for supply and return air distribution in L-BG including sidewall, sill floor, and ceiling
heating, and ventilating applications, and are installations make separate performance data
designed for sidewall, floor, sill, and ceiling necessary.
installation.
SIZE AVAILABILITY: L-B6 Bar Grilles are
MATERIAL: Linear Bar Grilles are made available in different widths ranging from inches,
exclusively of high grade aluminum extrusions with floor mounted units limited to a maximum
(6063-T5 alloy) for maximum strength, corrosion width of 12 inches. Stand to a maximum width of
resistance, and dimensional stability. Floor grilles 12 inches. Standard widths include: 2”, 2 ½”, 3”, 3
are additionally reinforced. ½”, 4”, 5”, 6”, 8”, 10”, 12”, Bar grilles are available
in virtually any length above a minimum length of
CONSTRUCTION: Face bars of natural anodized 6 inches, but one place lengths are limited to 6
extruded aluminum are mechanically interlocked feet. Longer Series L-BG, are formed by butting
into heavy gauge cross bars to produce straight, multiple grille sections together with alignment
rigid, and blemish free core sections. Placed on strips at the frame borders, resulting in hairline
½ inch centers, the bars, which measure 7/32 inch joints and a smooth unbroken face appearance.
by ¾ inch, are available in three angles of
deflection: 0°, 15°, 30° Floor and sill cores are FINISH: Standard finish for all L-BG Bar Grilles
removable, and are secured by coated steel and Registers are Natural Anodized or powder
retaining clips. Wall and ceiling cores are coating paint white.
permanently attached to their frames.
Bar grille frames are made of extruded aluminum
and are available in two border widths: 1 inch and
¾ inch.
Steel snap-in friction springs are used as the
standard mounting method for floor, sill and
sidewall applications, especially where
specifications call for concealed installation.

5 6
LAMINAIRE LAMINAIRE
L-BG
HOW TO SELECT PERFORMANCE DATA L-BG

HOW TO SELECT NOISE CRITERIA RECOMMENDATION CHART Linear bar grilles & REGISTERS
Table 1 Supply Air Performance 0’ and 15’ Deflection
SERIES ROUND DIFFUSERS

SERIES ROUND DIFFUSERS


STEP 1. The grilles selected should deliver the Listed Outlet Velocity (vk) 500 700 900 1000 1100 1200 1300
APPLICATION COMMENTS N.C.RANGE
Width
necessary CFM for the area to be conditioned. Total Pressure (pl) ,016 ,031 ,051 ,062 ,075 ,090 ,105
(in inches)
Broadcast studios extremely quiet, Static Pressure (ps) ,012 ,024 ,040 ,050 ,060 ,072 ,084
STEP 2. The throw (in feet) should extend at Below And AK Area
suitable to pick up Per foot NC - 15 20 23 26 29 31
least 75% of the distance from the face of the Concert halls low
25
1½ Flow CFM/Ft. 31 44 56 63 69 75 81
grille to the wall opposite the outlet. The throw Music rooms sound levels.
Throw, Sill of Floor 6 9 9 13 10 14 11 16 13 18 13 19 14 20
contained in the performance data is based on
a terminal velocity of 50 feet per minute. See ,062 ft. Side Wall 8 11 11 16 13 18 14 20 15 22 17 24 17 25
Residences Very quiet 30 2 Flow CFM/Ft. 43 60 77 10285 111 94
performance data notes for further application
details regarding throws, pressure, noise, etc. Theaters Throw, Sill of Floor 5 8 8 12 10 14 11 16 13 18 13 19 14 20
Libraries ,086 ft. Side Wall 7 10 10 15 13 18 14 20 15 22 17 24 17 25
STEP 3. The velocity at the neck shall be based Executive offices 2½ Flow CFM/Ft. 55 77 99 110 121 132 143
upon the recommended N.C. values in the
Throw, Sill of Floor 6 9 9 13 11 16 13 18 13 19 15 21 15 22
chart (at right).
Private offices quiet office 35 ,110 ft. Side Wall 8 11 11 16 14 20 16 23 17 24 18 26 20 28
HOW TO SPECIFY Hotel rooms Voice level will 3 Flow CFM/Ft. 65 91 117 130 43 156 169
Courtrooms Throw, Sill of Floor 7 10 10 14 13 18 14 20 15 21 15 22 17 24
be heard up to
All L –BG grilles/diffusers shall be L –BG Grille ,130 ft. Side Wall 8 12 13 18 15 22 17 25 18 26 20 28 21 30
Churches 30 feet
and damper constructed entirely of tempered 3½ Flow CFM/Ft. 76 107 137 153 168 183 198
extruded aluminum, using mechanically – Hospital rooms
Throw, Sill of Floor 7 10 10 15 13 18 15 21 15 22 17 24 18 26
joined comers on the frame and a Schools
,152 ft. Side Wall 9 13 13 19 16 23 18 26 20 28 21 30 22 32
mechanically–swedged blade-to-mullion moderately quiet 4 Flow CFM/Ft. 88 123 158 175 193 210 228
construction for the core.
Dining rooms voice level will 40 Throw, Sill of Floor 8 11 13 18 14 20 16 23 18 26 19 27 20 29
Labs be heard up to ,176 ft. Side Wall 10 14 15 22 17 25 20 29 22 32 24 34 25 26
General Offices 12 feet 5 Flow CFM/Ft. 110 154 198 220 242 264 286
Lounges Throw, Sill of Floor 8 12 13 18 15 21 17 24 18 26 19 27 21 30
,220 ft. Side Wall 10 15 15 22 18 26 21 30 22 32 24 34 26 37
Retail stores allows isolation 45 6 Flow CFM/Ft. 133 186 239 265 292 318 345
Lobbies of conversation Throw, Sill of Floor 8 12 13 18 15 22 17 25 18 26 20 28 21 30
Reception areas voice level will ,265 ft. Side Wall 10 15 15 22 19 27 22 31 23 33 24 35 27 38
8 Flow CFM/Ft. 178 249 320 355 391
Drafting- engineering be heard up to
Throw, Sill of Floor 10 14 13 19 15 22 18 26 19 27
Offices 6 feet
,356 ft. Side Wall 12 17 17 24 20 28 23 33 24 34
10 Flow CFM/Ft. 223 312 401 445
Machinery rooms high background 50 Throw, Sill of Floor 10 15 15 22 18 26 21 30
sound, voice level
Computer rooms ,446 ft. Side Wall 13 19 20 28 23 33 26 37
will be heard up to
Factories 3 feet, phone 12 Flow CFM/Ft. 268 375 482
conversation Throw, Sill of Floor 12 17 22 31 21 30
difficult ,536 ft. Side Wall 15 21 24 35 27 38
For application of performance data shown in table 1, please refer to the Engineering Notes, Throw and NC values in Table 1 are based on a 4 foot active Grille length. For
Grille lengths other than 4 feet.

7 8
LAMINAIRE LAMINAIRE
L-BG L-BG
PERFORMANCE DATA L-BG LINEAR BAR GRILLES & REGISTERS
Linear bar grilles & REGISTERS
Table 2 Supply Air Performance 30’ Deflection Table 3 Return Air Performance 0" and 15" Deflection
SERIES ROUND DIFFUSERS

SERIES ROUND DIFFUSERS


Listed Outlet Velocity (vk) 570 805 1035 1140 1265 1380 1495
Width NC
Total Pressure (pl) 0,020 0,040 0,067 0,081 0,100 0,119 0,139
(in inches) Listed Width Ak Effective Area 10 15 20 25 28 31 35 45
And AK Area Static Pressure (ps) 0,017 0,034 0,056 0,070 0,084 0,100 0,118
in inches Per Linear Foot Ps Static Pressure Inches H2O
Per foot NC - 20 25 28 31 34 36
1½ Flow CFM/Ft. 36 50 65 71 79 86 94 0,02 0,03 0,04 0,06 0,08 0,10 0,12 0,15
Throw, Sill of Floor 6 9 9 13 10 14 11 16 13 18 13 19 14 20 1 1/2 0,13 20 25 30 35 40 45 50 55
0,063 ft. Side Wall 8 11 11 16 13 18 14 20 15 22 17 24 17 25 2 0,18 30 40 45 55 65 70 80 90
2 Flow CFM/Ft. 48 68 88 108 11797 127 2 1/2 0,23 45 55 60 75 85 95 105 115
Throw, Sill of Floor 5 8 8 12 10 14 11 16 13 18 13 19 14 20 3 0,27 55 70 80 90 110 125 135 150
0,084 ft. Side Wall 7 10 10 15 13 18 14 20 15 22 17 24 17 25 3 1/2 0,30 65 80 90 110 125 140 155 170
2½ Flow CFM/Ft. 63 89 114 125 139 152 164 4 0,34 80 100 110 130 150 170 185 205
Throw, Sill of Floor 6 9 9 13 11 16 13 18 13 19 15 21 15 22 5 0,41 100 125 140 175 200 225 245 275
0,110 ft. Side Wall 8 11 11 16 14 20 16 23 17 24 18 26 20 28 6 0,46 120 150 175 215 245 275 305 340
3 Flow CFM/Ft. 74 105 135 148 164 179 194 8 0,57 165 200 235 290 330 380
Throw, Sill of Floor 7 10 10 14 13 18 14 20 15 21 15 22 17 24 10 0,68 215 260 315 375 430 495
0,130 ft. Side Wall 8 12 13 18 15 22 17 25 18 26 20 28 21 30 12 0,76 265 325 375 455 525
3½ Flow CFM/Ft. 87 123 156 174 193 211 228
Throw, Sill of Floor 7 10 10 15 13 18 15 21 15 22 17 24 18 26
0,153 ft. Side Wall 9 13 13 19 16 23 18 26 20 28 21 30 22 32
Flow CFM/Ft. 100 141 181 200 221 242 262 Table 3 Return Air Performance 0" and 15" Deflection
4
Throw, Sill of Floor 8 11 13 18 14 20 16 23 18 26 19 27 20 29 NC
0,175 ft. Side Wall 10 14 15 22 17 25 20 29 22 32 24 34 25 26 Listed Width Ak Effective Area 10 15 20 25 28 31 35 45
5 Flow CFM/Ft. 125 177 228 251 278 304 329 in inches Per Linear Foot Ps Static Pressure Inches H?O
Throw, Sill of Floor 8 12 13 18 15 21 17 24 18 26 19 27 21 30 0,02 0,03 0,04 0,06 0,08 0,10 0,16 0,20
0,219 ft. Side Wall 10 15 15 22 18 26 21 30 22 32 24 34 26 37 1 1/2 0,12 15 20 25 30 35 40 50 55
6 Flow CFM/Ft. 157 213 274 302 335 366 396 2 0,17 25 35 40 48 55 63 78 88
Throw, Sill of Floor 8 12 13 18 15 22 17 25 18 26 20 28 21 30 2 1/2 0,22 35 45 50 60 70 80 100 110
0,265 ft. Side Wall 10 15 15 22 19 27 22 31 23 33 24 35 27 38 3 0,25 45 55 65 75 90 100 130 145
8 Flow CFM/Ft. 202 286 367 405 449
3 1/2 0,29 50 65 75 90 105 120 150 165
Throw, Sill of Floor 10 14 13 19 15 22 18 26 19 27
4 0,33 60 75 90 110 125 140 175 200
0,354 ft. Side Wall 12 17 17 24 20 28 23 33 24 34
5 0,39 80 100 120 140 160 180 225 255
10 Flow CFM/Ft. 254 358 461 507
6 0,44 100 120 140 170 200 220 280 315
Throw, Sill of Floor 10 15 15 22 18 26 21 30
8 0,54 135 165 200 240 270 305 380
0,446 ft. Side Wall 13 19 20 28 23 33 26 37
10 0,64 175 215 250 300 350 390 500
12 Flow CFM/Ft. 305 431 554
12 0,72 210 260 300 380 425 475
Throw, Sill of Floor 12 17 22 31 21 30
0,535 ft. Side Wall 15 21 24 35 27 38 For application of performance data shown in table 1, please refer to the Engineering Notes, Throw and NC values in Table 1 are based on a 4 foot active Grille length. For
For application of performance data shown in table 1, please refer to the Engineering Notes, Throw and NC values in Table 1 are based on a 4 foot active Grille length. For Grille lengths other than 4 feet.
Grille lengths other than 4 feet.

9 10
LAMINAIRE LAMINAIRE
L-BG L-BG
PERFORMANCE DATA L-BG LINEAR BAR GRILLES & REGISTERS
Sill/floor Throw: Sill and floor throw given in the When outlet is located in floor, be sure that throw
data charts are the sum of the vertical and at least equals ceiling height. It is a known
SERIES ROUND DIFFUSERS

SERIES ROUND DIFFUSERS


horizontal projection from the outlet (based on the condition that the area beyond the horizontal
9’high test chamber). Al test data is for units throw area (in above figures) of up to 20’ (Throw
NUMBER OF BLADES PER LISTED SIZE The length of tested diffusers was 4’
mounted adjacent to the wall or ceiling to create plus 20’) will be conditioned satisfactorily.
listed size. When other lengths are
the COANDA (ceiling effect and/or wall effect)
Listed size (inches) 2 2½ 3 3½ 4 5 6 8 10 12 required, use the following correction
EFFECT See Diagrams.
Number of Bars 2 3 4 5 6 8 10 14 18 22 factors:

THROW CORRECTION FOR VARIOUS


PRESSURE: CONTINUOUS LENGTHS Throw horizontal

Total pressure readings are in inches water gauge at the Active up to +20°
1" 4" 6" 8" 10" 15" 20"
horizontal air pattern. This pressure refers to any length of length 100"
diffuser rather than a per-foot basis when product is used in
a return application, the – P, Negative Static Pressure Will Sidewall
,8 1,0 1,0 1,1 1,1 1,15 1,15 1,20
throw x 50 fpmVt
be 0.80 x the P, shown. Downward Throw
Throw vertical Isovel
Sill-floor
,8 1,0 1,0 1,1 1,1 1,15 1,15 1,20 15° Sill-Floor
THROW: throw x Isovel

Throws indicated are based on total number of feet of


-20°
projected air when a terminal velocity of 50 feet per minute
is reached. Throws are based on a 9’ ceiling height. For THROW TEMPERATURE CORRECTION FACTORS For 15° deflection

each additional foot in ceiling height, reduce the throw T°F -20°F T 0 F T +20°F T 6" max
rating by approximately one foot (for horizontal air flow
Throw corrections correct as shown x 11 x 12
patterns). The throw ratings at 100 and 150 feet per minute Ceiling Downward Throw: This technique has
are approximately as follows. certain drawbacks to consider. Cold ?T primary
Throw horizontal
air will tend to have a further downward projection
CORRECTION FACTOR FOR THROW DATA @ 50 FPM than would a warm ?T. Drafts may occur at the
V, AS SHOWN IN CHARTS FOR O-DEGREE DE more vulnerable “ankle level” of the occupied
F L E C T I O N U N I T S H O R I Z O N TA L T H R O W zone. The following data will determine proper
CORRECTION ONLY selection.
50 fpmVt
CEILING DOWNWARD VERTICAL THROW
When P?= ,040 ,060 ,120 ,180 ,200 CORRECTION FACTORS TO USE ON THE
Throw vertical

Throw @ 0° Sill-Floor SIDEWALL THROW VALUES


5’less 6’less 6’less 8’less 8’less Isovel
100fmp V?

Throw @
8’less 10’less 12’less 15’less 15’ less
150fpm Vt For 0° deflection 5’ or more from
Location 6” From Sidewall
sidewall
6" max
-20°F T x 1.00 x 0.70
0°F T x 0-90 x 0.60
+ 25°F T x 0.60 x 0.40

11 12
LAMINAIRE LAMINAIRE
L-BG
LINEAR BAR GRILLES & REGISTERS

DROP: Drop of a horizontal air stream is N.C. CORRECTION CHART


SERIES ROUND DIFFUSERS

SERIES ROUND DIFFUSERS


dependent primarily on the CFM and its ?T. The
larger the CFM delivered, the greater the drop Active length 1" 2" 3" 4" 6" 8" 10" 15" 20" 25" 30"
from the ceiling. Also. The cooler the air, the Db. CORRECTION -10 -7 -5 -4 -2 -1 0 +2 +3 +4 +5
greater the drop. Drop can be reduced by
Return applications have an increased N.C. of + 4 Db.
dividing the CFM total into multiple outlets with
smaller quantities of air. In linear bar-tipe grilles, Thermal expansion: Installation of continuous
this may be accomplished by dividing the linear runs should allow 1/32” space between 6’
diffuser into active and inactive sections. Typical segments for systems using a + 40° F?T. Add an
drop at - 20°F?T is shown in the ISOVEL extra 1/64” for every additional + 20° F?T to the
DIAGRAM. When dividing these sections, a space. This allows for expansion of the metal
certain number of inactive sections in- between when heated, and avoids possible ceiling
should be used. damage.

Dampering correction factors.


Nº of inactive 4’ to 6’ sections 1 5 10 up Data shown is or non- dampered units. To
Nº of inactive 4’ to 6’ sections determine the changes for adding an opposed-
1 2 3 blade damper, use the following chart:
Needed to effect separation
THROW TOTAL PRESSURE N.C.
Drop may also be reduced by using a greater
X 92 X 1.05 + 2 Db.
degree of deflection (such as 30° upward),
locating bar grille further down the wall, and
arching the throw in upward plane angle.

Outlet velocity: The outlet velocity is based


upon the total pressure and is the measurement
at face of the grille.

TOTAL PRESSURE P?
,02 ,02 ,03 ,04 ,05 ,06 ,09 ,12 ,16 ,20 ,25
OUTLET VELOCITY (Feet per minute)
500 600 700 800 900 1000 1200 1400 1600 1800 2000

Sound data: The N.C. Values are based upon


room absorption of 8Db re 10-¹² watts, The
symbol “ – “ indicates less than 20 Db. N.C. rating
Dampering for “fine balancing” up to 25% of the
cfm volume will result in an increase in N.C. of 6
Db. Greater dampering will result in increased
noise levels, and millaire recommends remote –
located balancing dampers upstream from the
branch duct. Data shown is for 10- foot active
length. Correct as follows for other lengths: