3.

General Inspection : OK

4. Insulation Resistance Test: (Measured Values in GΩ)

Applied Voltage: 5000 V DC Duration: 1 Min.

Condition Equipment Status R–R’ Y–Y’ B-B’

CB is ON & LBS 2 is OFF 15.1 17.8 18.5

OPEN CB is ON & LBS 1 is OFF 14.5 21.6 20.5

LBS 1 is ON & LBS 2 is OFF 25.1 15.2 16.2

Condition Equipment Status R-E Y-E B-E R-Y Y-B B-R


LBS 1, LBS 2 & CB are
CLOSE 13.8 19.0 18.6 34.5 39.1 21.3
ON

5. Contact Resistance Test: Injected Current -200A DC

Measured Values in Micro Ohm


Equipment Status CRM Between
R Phase Y Phase B Phase
LBS 1 to LBS 2 487 450 407

LBS 1, LBS 2 & CB are ON LBS 1 to CB 478 473 473

LBS 2 to CB 490 614 405

TEST REPORT FOR LBS 1 CT

1. Name Plate Details:

2. Winding Resistance Test:

Measured Values in Ω
Ratio Ref.
R ph Y ph B ph
50/1 A 0.5 0.5 0.5
100/1A 0.7 0.7 0.8
200/1A 1.6 1.6 1.7

3. Ratio Test:

RATIO Measured current in Secondary (A)


Injected current
R Phase Y Phase B Phase
in Primary (A)
10 0.202 0.205 0.204
20 0.400 0.401 0.403
50/1A 30 0.603 0.602 0.602
40 0.803 0.806 0.804
50 0.991 1.002 1.005
100/1A 25 0.257 0.254 0.256
50 0.503 0.503 0.502
75 0.746 0.745 0.749
Fault Ref. Phase Ref. Set Current(A) Pick Up Current(A)
100 0.993 1.005 1.001
RY 100 109
200/1AOC 50 YB 0.256 100 0.252 1040.254
100 R 0.503 20 0.502 220.503
E/F 150 Y 0.748 20 0.745 210.752
200 B 0.998 20 0.999 241.005

4. Fault Passage Indicator Test (FPI):

4.1 Name Plate Details of FPI Sensor:

4.2 Service Settings:

Phase OC 100 A
Earth Fault OC 20 A

4.3 Primary Injection Test:

TEST REPORT FOR LBS 2 CT

1. Name Plate Details:

2. Winding Resistance Test:

3. Ratio Test:

RATIO Measured current in Secondary (A)


Injected current
R Phase Y Phase B Phase
in Primary (A)
10 0.204 0.203 0.204
20 0.405 0.402 0.403
50/1A 30 0.602 0.605 0.603
40 0.803 0.804 0.805
50 1.005 1.003 1.002
100/1A 25 0.252 0.247 0.252
50 0.506 0.503 0.512
75 0.751 0.749 0.748
Fault Ref. Phase Ref. Set Current(A) Pick Up Current(A)
100 0.999 0.995 0.995
RY 100 104
200/1AOC 50 YB 0.253 100 0.206 106 0.258
100 R 0.504 20 0.502 23 0.503
E/F 150 Y 0.752 20 0.759 21 0.751
200 B 1.005 20 1.003 26 0.995

4. Fault Passage Indicator Test (FPI):

4.1 Name Plate Details of FPI Sensor:

4.2 Service Settings:

Phase OC 100 A
Earth Fault OC 20 A
4.3 Primary Injection Test:

TEST REPORT FOR CIRCUIT BREAKER CT


1. Name Plate Details:

2. Winding Resistance Test:

Measured Values in Ω
Terminal Ref.
R ph Y ph B ph
1S1 – 1S2 0.4 0.4 0.4
1S1 – 1S3 0.6 0.6 0.5
1S1 – 1S4 1.0 1.0 1.2
Measured Values in Ω
Ref.
R ph Y ph B ph
2S1 – 2S2 0.5 0.4 0.4
2S1 – 2S3 0.9 0.8 0.9
2S1 – 2S4 1.6 1.6 1.5

3. Ratio Test:

Measured current in Secondary (A)


Injected
RATIO current in R Phase Y Phase B Phase
Primary (A)
Meter Protn. Meter Protn. Meter Protn.
10 0.205 0.208 0.206 0.205 0.208 0.207
20 0.402 0.418 0.413 0.411 0.412 0.404
50/1A 30 0.603 0.605 0.605 0.604 0.610 0.603
40 0.805 0.802 0.806 0.804 0.815 0.806
50 1.006 1.004 1.005 1.007 1.006 1.004
25 0.253 0.270 0.259 0.254 0.256 0.275
50 0.502 0.519 0.514 0.504 0.518 0.517
100/1A
75 0.756 0.757 0.756 0.753 0.755 0.754
100 0.998 1.004 0.999 1.003 1.006 1.006
50 0.256 0.256 0.253 0.257 0.254 0.259
100 0.506 0.504 0.502 0.504 0.505 0.502
200/1A
150 0.753 0.754 0.756 0.756 0.759 0.759
200 1.005 1.002 1.006 1.005 1.002 1.007

TEST REPORT FOR POTENTIAL TRANSFORMER

1. Name Plate Details:

2. Winding Resistance Test: (Measured Values in Ω)

Terminal Ref. R Y B
1a – 1n 0.5 0.5 0.5

3. Ratio Test:

Ratio: 11000 / √3 / 110 / √3 V


Measured Secondary Voltage (V)
Applied Primary Voltage (V)
R Y B
1000 10.22 10.21 10.22
2000 20.40 20.42 20.41
3000 30.25 30.26 30.25
4000 40.0 40.2 40.1

TEST REPORT FOR AUXILIARY TRANSFORMER

1. Name Plate Details:

2. Winding Resistance Test:

Terminal Ref. Measured Value in Ω


H1– H2 1.2

3. Ratio Test:

Ratio: 11000 / 230 V

Applied Primary Voltage (V) Measured Secondary Voltage (V)


1000 21.8
2000 42.5
3000 64.0
4000 86.5

TEST REPORT FOR FEEDER PROTECTION RELAY

1. Name plate Details:

2. Service Settings:

3. Secondary Injection Test:


Phase OC (I>):

Phase Ref Set Current(A) Pick Up Current(A) Set Time(S) Operated Time(S)
RY 0.3 0.306 1.00 1.069
YB 0.3 0.308 1.00 1.023
BR 0.3 0.305 1.00 1.032
Earth Fault OC (Ie>):

Phase Operated
Set Current(A) Pick Up Current(A) Set Time(S)
Ref Time(S)
R 0.2 0.205 1.00 1.032

Y 0.2 0.208 1.00 1.025


B 0.2 0.209 1.00 1.026
4. Functional Check:

1 LBS 1,2 and Circuit Breaker’s Earth Switch mechanical operation check OK
2 LBS 1,2 Load Break Switch mechanical and Electrical operation check OK
3 Circuit Breaker Disconnector Mechanical operation check OK
4 Circuit Breaker Electrical and Mechanical ON& OFF operation check OK
5 Circuit Breaker trip check through feeder Protection Relay OK
5. Remarks : Test results of Ring Main Unit are found satisfactory.