Documente Academic
Documente Profesional
Documente Cultură
OPERATIONAL MEMORANDUM
1.0 INTRODUCTION
Oil filled transformers in power plant application are used for variety of
applications staring from most critical application for generator transformers
to unit auxiliary transformers, station transformers, inter connecting
transformers, tie transformers to service transformers for feeding power
supply to different category of equipment. Availability of all these transformers
is essential for smooth functioning of power plant.
Major components and activities which need to be assessed for residual life
of transformers are as follows:
The second method of finding the insulation quality or to be more precise, the
residual life of transformer insulation is by way of determining the furfural content
from the transformer oil. Since it is very easy to draw oil sample from a
transformer for furfural content test and also this test can be done without de-
energizing the transformer unlike DP test, this method has become more
acceptable. Chemical experts have found out that furfural content in oil does not
change even if the oil is degassed or filtered during routine maintenance of
transformer.
where
(Fur) = 2-furfuraldehyde concentration in oil in ppm
DP = Degree of polymerization of insulation paper
where
(Fur) = 2-furfuraldehyde concentration in oil in ppm
T = Operating times in years
With above conversion equations we can find out DP from furfural content test of
oil and thus the residual life of insulation paper can be found.
The norms for residual life assessment were studied and given by Paul J Griffin
during his presentation on Assessment of paper insulation and other cellulose
materials in service - aged transformers at the Southeastern Electric Exchange
on 24-06-1999 as per the following values:
The life of the transformer is actually the life of the internal insulation system.
The most widely used systems are liquid insulation (transformer oil) and solid
insulation (Kraft paper, pressboard, seasoned wood i.e. cellulose products). The
insulating oil provides approximately 80% of the dielectric strength of a trans-
former. Transformer oil is a good insulating medium and when impregnated in
paper, press board and cloth, increases the dielectric strength of it further. The
low viscosity of oil also allows it to penetrate the solid insulation setting up
convection currents for conveying the heat from the core materials to the
radiators. The liquid insulation therefore also serves as a coolant and its oxidation
stability allows it to operate at high temperatures for long periods. Therefore, it is
essential that the insulating oil inside the transformer is having good dielectric
strength and stability so as to ensure overall adequacy of required dielectric
strength and residual life. The residual life of insulating oil can be determined by
three properties namely specific resistivity, tan delta and acidity. By periodic
monitoring of the trend the requirement of replacement can be estimated and
accordingly the program is to be made to avoid any emergency on account of
aged oil.
2.3 HEALTH OF ACCESSORIES
The transformer is capital equipment and no utility can afford to loose the
transformer since these are very costly. Therefore, a number of protection
devices are used to protect the transformer from damage. It is therefore
necessary to ensure that these protection devices are healthy and do the
necessary function as and when required. Buchholz relay, pressure relief device,
sudden pressure relay, OTI / WTI, MOG etc. are such devices which trip the
transformer in case of internal fault. Current transformers are also provided to
protect the transformer and trip it in case of internal as well as external fault.
Being low cost items, complete replacement is a better option for these
accessories rather than carrying out any residual life assessment. The
replacement decision can be based on the past performance of these
accessories.
In transformers, the main flux is by and large axial (this is so, as the design of
transformer is such as to minimize the leakage flux in the transformer, which
introduces the radial component in the total flux) and the currents in the HV and
LV coils are circulating in the opposite direction. The electromagnetic forces
acting on coils thus are radial in nature and tend to repel the windings from each
other. Hence, the outer winding experience bursting forces and inner winding
experience compressive forces.
The magnitude of axial force which is due to radial leakage flux is generally small.
Theoretically axial forces shall be zero if the coils on a core limb are concentric,
but due to manufacturing process and tolerances, it is not possible to achieve
this. Above can be attributed either due to inadequate skills in shop floor during
assembly or due to the slackness in the coils because of shrinkage of insulating
material of coils etc.
The magnitude of the current during the period when it is feeding the external
fault is very high and the forces that the windings are subjected to because of the
rush of fault current also are quite enormous and cause distortion of transformer
windings. The windings inside a transformer are tightly pressed and securely
clamped in place in order to prevent distortion / deformation. The supporting
system is designed with adequate safety margins to take care of any such
eventuality.
During service life of a transformer, it feeds system faults some of which are very
close to the transformer. Thus the faults inside the switchyard create maximum
short circuit forces because of low impedance and some distant faults on
transmission line create relatively lesser short circuit forces. It is therefore
essential to assess the movement of transformer internals due to each external
fault. The frequency response analysis (FRA) gives the relative movement of
windings with respect to each other and also with respect to magnetic core. The
trend observed during periodic FRA testing can be a good tool to find out the
movement of transformer internals as compared to previous test history.
Effectively, we can assess the degree of susceptibility of the transformer to fail
during next short circuit in the system.
3.0 With above background, the proposed test schedule along with test
frequency and acceptance limits for residual life assessment for aging
transformers is as per Table-1 below:
TABLE-1
RLA TEST SCHEDULE FOR AGING TRANSFORMERS
1 BDV
2 Moisture
3 Tan Delta
4 Specific Resistivity
5 Acidity
6 IFT
7 DGA
(Prakash Hirani)
AGM (COS)
AGM (COS-Elec)
GM (COS)