Air System Sizing Summary for Fan Coil

Project Name: Untitled 09/23/2019


Prepared by: Sabro Technologies 12:10PM

Air System Information


Air System Name ............................................ Fan Coil Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ............................................................. 11025.0 ft²
Air System Type ................................................ SZCAV Location ................................................. New Delhi, India

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ............................................ User-Modified Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load .......................................................... 38.1 Tons Load occurs at ................................................... Jun 1700
Total coil load ........................................................ 456.6 MBH OA DB / WB .................................................... 103.8 / 71.4 °F
Sensible coil load ................................................. 439.0 MBH Entering DB / WB ............................................. 77.7 / 64.4 °F
Coil CFM at Jun 1700 ......................................... 22068 CFM Leaving DB / WB .............................................. 58.8 / 57.5 °F
Max block CFM ................................................... 22068 CFM Coil ADP ..................................................................... 56.7 °F
Sum of peak zone CFM ...................................... 22068 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio ............................................... 0.961 Resulting RH ................................................................. 52 %
ft²/Ton ................................................................... 289.7 Design supply temp. ................................................... 58.0 °F
BTU/(hr-ft²) ............................................................. 41.4 Zone T-stat Check .................................................... 1 of 1 OK
Water flow @ 10.0 °F rise .................................... 91.37 gpm Max zone temperature deviation .................................. 0.0 °F

Central Heating Coil Sizing Data

Max coil load ........................................................ 194.8 MBH Load occurs at ..................................................... Des Htg
Coil CFM at Des Htg ........................................... 22068 CFM BTU/(hr-ft²) ................................................................. 17.7
Max coil CFM ...................................................... 22068 CFM Ent. DB / Lvg DB .............................................. 67.2 / 75.6 °F
Water flow @ 20.0 °F drop ................................... 19.49 gpm

Supply Fan Sizing Data

Actual max CFM .................................................. 22068 CFM Fan motor BHP ........................................................... 0.00 BHP
Standard CFM ..................................................... 21509 CFM Fan motor kW ............................................................. 0.00 kW
Actual max CFM/ft² ................................................ 2.00 CFM/ft² Fan static .................................................................... 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................... 2206 CFM CFM/person .............................................................. 20.05 CFM/person
CFM/ft² ................................................................... 0.20 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for Fan Coil
Project Name: Untitled 09/23/2019
Prepared by: Sabro Technologies 12:10PM

Air System Information


Air System Name ............................................ Fan Coil Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ............................................................. 11025.0 ft²
Air System Type ................................................ SZCAV Location ................................................. New Delhi, India

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data ............................................ User-Modified Space CFM Sizing ............. Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 375.2 20964 20964 Jul 1700 133.5 11025.0 1.90

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
lowe Ground Floor 1 375.2 Jul 1700 20964 133.5 11025.0 1.90

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for Fan Coil
Project Name: Untitled 09/23/2019
Prepared by: Sabro Technologies 12:10PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 103.8 °F / 71.4 °F HEATING OA DB / WB 44.0 °F / 36.9 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 4200 ft² 33396 - 4200 ft² 27083 -
Roof Transmission 11025 ft² 203446 - 11025 ft² 94237 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 11025 ft² 0 - 11025 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 11025 W 37617 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 11025 W 37617 - 0 0 -
People 110 26950 22550 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 33903 2255 10% 12132 0
>> Total Zone Loads - 372928 24805 - 133452 0
Zone Conditioning - 364255 24805 - 128139 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 22068 CFM 0 - 22068 CFM 0 -
Ventilation Load 1864 CFM 56097 -7203 2206 CFM 59940 0
Supply Fan Load 22068 CFM 0 - 22068 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 5% 18646 - 5% 6673 -
>> Total System Loads - 438998 17603 - 194752 0
Central Cooling Coil - 438998 17621 - 0 0
Central Heating Coil - 0 - - 194752 -
>> Total Conditioning - 438998 17621 - 194752 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for Fan Coil
Project Name: Untitled 09/23/2019
Prepared by: Sabro Technologies 12:10PM

June DESIGN COOLING DAY, 1700

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 103.8 0.00946 1864 400 56097 -7203
Vent - Return Mixing Outlet 77.7 0.01022 22068 945 - -
Central Cooling Coil Outlet 58.8 0.01005 22068 945 438998 17621
Central Heating Coil Outlet 58.8 0.01005 22068 945 0 -
Supply Fan Outlet 58.8 0.01005 22068 945 0 -
Cold Supply Duct Outlet 59.6 0.01005 20964 945 - -
Zone Air - 76.1 0.01031 20964 999 364255 24805
Return Plenum Outlet 76.1 0.01031 20964 999 0 -
Duct Leakage Air Outlet 58.8 0.01005 1103 945 - -
Return Duct Outlet 75.3 0.01029 22068 996 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.053 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4626.4 BTU/(hr-CFM)
Site Altitude = 708.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 372928 Cooling 364255 76.1 20964 999 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for Fan Coil
Project Name: Untitled 09/23/2019
Prepared by: Sabro Technologies 12:10PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 44.0 0.00312 2206 400 -59940 0
Vent - Return Mixing Outlet 67.2 0.00312 22068 482 - -
Central Cooling Coil Outlet 67.2 0.00312 22068 482 0 0
Central Heating Coil Outlet 75.6 0.00312 22068 482 194752 -
Supply Fan Outlet 75.6 0.00312 22068 482 0 -
Cold Supply Duct Outlet 75.3 0.00312 20964 482 - -
Zone Air - 69.5 0.00312 20964 492 -128139 0
Return Plenum Outlet 69.5 0.00312 20964 492 0 -
Duct Leakage Air Outlet 75.6 0.00312 1103 482 - -
Return Duct Outlet 69.8 0.00312 22068 492 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.053 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4626.4 BTU/(hr-CFM)
Site Altitude = 708.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -133452 Heating -128139 69.5 20964 492 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for Fan Coil
Project Name: Untitled 09/23/2019
Prepared by: Sabro Technologies 12:11PM

Location: New Delhi, India


Altitude: 708.0 ft.
Data for: June DESIGN COOLING DAY, 1700
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Duct Heat
6. Room Air
7. Return Duct Outlet
0.016

Specific Humidity ( lb/lb )


0.014

0.012
35 76 2
4 1 0.010

0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )