Sunteți pe pagina 1din 14

Technology Installation Review

A New Technology Demonstration Publication


DOE/GO-102007-2325

Federal Energy Management Program

Leading by example, Coolerado Cooler Helps to Save


saving energy and
taxpayers dollars in
Cooling Energy and Dollars
federal facilities New cooling technology targets peak load reduction

Executive Summary
A new evaporative cooling technology can deliver cooler supply air temperatures than
either direct or indirect evaporative cooling systems, without increasing humidity. The
technology, known as the Coolerado Cooler™, has been described as an “ultra cooler”
because of its performance capabilities relative to other evaporative cooling products.

The Coolerado Cooler evaporates water in a secondary (or working) airstream, which is
discharged in multiple stages. No water or humidity is added to the primary (or product)
airstream in the process. This approach takes advantage of the thermodynamic properties
of air, and it applies both direct and indirect cooling technologies in an innovative cooling
system that is drier than direct evaporative cooling and cooler than indirect cooling.
The technology also uses much less energy than conventional vapor compression air-
conditioning systems and therefore can be a cost- and energy-saving technology for
many Federal facilities in the United States.

Performance tests have shown that the efficiency of the Coolerado Cooler is 1.5 to 4 times
higher than that of conventional vapor compression cooling systems, while it provides the
same amount of cooling. It is suitable for climates having low to average humidity, as is
the case in much of the western half of the United States. This technology can also be used
to precool air in conventional heating, ventilating, and air-conditioning systems in more
humid climates because it can lower incoming air temperatures without adding moisture.

Introduction
Air-conditioning systems are a major contributor to summer peak electrical demands
in most of the United States. Both electric power generators and conventional vapor
compression electric air-conditioning systems operate at lower efficiencies when ambient
air temperatures are high, and this increases the peak demand on the grid even further.
Moreover, peak demand charges are often billed at a utility’s highest rates. Because a
significant portion of summer air-conditioning loads occur when electricity is the most
expensive, cooling is often more costly than other electrical loads. Therefore, reducing
cooling energy demand can offset energy costs at a proportionally greater rate than other
load-reduction strategies and yield greater cost savings for a given amount of energy
Bringing you a prosperous savings.
fuure where energy is
clean, abundant, reliable, This Technology Installation Review, prepared for the U.S. Department of Energy’s Federal
and affordable Energy Management Program, describes the operating principles, measured performance,

U.S. Department of Energy Internet: www.eere.energy.gov/femp/


No portion of this publication may be altered in any form without
Energy Efficiency prior written consent from the U.S. Department of Energy, Energy Efficiency
and Renewable Energy and Renewable Energy, and the authoring national laboratory.
Technology Installation Review

and energy savings potential of Types of Cooling Systems water vapor, the heat that goes into
the Coolerado Cooler technology. the evaporation process is removed
A wide variety of systems and
Because this technology signifi- from the air, resulting in a cooler
technologies are used for cooling
cantly reduces electric demand for air temperature.
commercial and residential build-
cooling over the course of a cooling
ings. The following short descrip- Evaporative coolers are effective in
season, it can provide energy and
tions of several system types average- to low-humidity climates,
cost savings and help Federal
provide a frame of reference for and they consume much less
energy managers meet the energy-
evaluating the Coolerado Cooler’s energy than other types of air-
reduction goals stated in the
performance. conditioning systems.
Energy Policy Act (EPAct) of 2005.1
It can also help to reduce expen- Conventional Systems. Evaporative coolers can be either
sive peak demand charges. Conventional HVAC systems direct or indirect. In direct evapo-
condition supply air year-round rative cooling, water evaporates
The technology uses a water-
to deliver fresh, comfortable air directly into the supply airstream,
fueled cooling system powered
to building occupants. In summer, reducing the dry-bulb temperature
solely with fan energy to provide
conventional air-conditioning of the air while raising its humid-
more cooling at a lower cost.
systems cool the air and often ity. The latent heat of the air is
Incorporating this concept with
remove the moisture in it simulta- used to evaporate the water.
multiple purges of moist second-
neously by passing the air over a Evaporation cools the air while
ary/working air creates a staged
cold surface. When warm, moist increasing its moisture content or
indirect evaporative cooling
“inside” air is blown across the relative humidity. No heat is
process. This process, known
surface of a unit’s cooling coil, added or taken out of the air; thus,
as the Maisotsenko Cycle, is
the air temperature drops and the it is an adiabatic process.
the innovation that led to the
water vapor in it condenses. The
Coolerado Cooler’s receipt of a In direct evaporative coolers, often
conditioned air is both cooler and
prestigious R&D 100 Award from called swamp coolers, the supply
drier and therefore more
R&D Magazine in 2004. airstream is in direct contact with
comfortable.
The Coolerado Cooler is modular water by means of an evaporative
Typically, conventional air- medium or wetted pad (such as
in design; thus, multiple units
conditioning systems depend on fiberglass, fabricated paper, or
can be stacked as high and wide
a vapor-compression cycle to aspen pad) or a series of spray
as needed to meet a building’s
provide cooling. Common types of misters. The supply airstream
cooling requirements. Capacity
conventional vapor-compression gains a lot of moisture in this
configurations range from 1-ton
systems are self-contained, factory- process, so cool, moist air must be
residential window units to 500-
assembled packaged units, split exhausted from the cooled space
ton commercial units. With modifi-
units with outdoor compressor and not reused or reconditioned.
cations, the Coolerado Cooler can
and condenser units and indoor
be integrated into a precooling Figure 1 illustrates a supply
air-handling units (AHUs), and
system for ventilation air in new airstream being blown across an
chiller systems. Chiller systems
or existing heating, ventilating, evaporative medium. Figure 2
use mechanical chillers to cool
and air-conditioning (HVAC) diagrams a psychrometric (see
water that is then distributed to
systems. When used for precool- Glossary of Terms for psychro­
coils located in AHUs. With each
ing, it is capable of providing metric terminology) analysis of
of these systems, the cooled air
energy and cost savings in virtu- this direct evaporative cooling
is delivered via terminal devices
ally any climate in the continental process. The entering dry-bulb air
(e.g., supply diffusers) to the space
United States. temperature (TDB) is 110°F (43.3°C),
to be cooled.
the relative humidity (RH) is 15%,
Evaporative Cooling. When liquid and the thermodynamic wet-bulb
water evaporates and becomes temperature (TWB) is 72°F (22.2°C).

________________
1 See www.eere.energy.gov/femp/about/legislation_epact_05.html, 2006.

 — FEDERAL ENERGY MANAGEMENT PROGRAM


Technology Installation Review

Figure 1. Direct evaporative cooling


through a wetted medium. Source:
www.energy.ca.gov/appliances/
2003rulemaking/documents/case_
studies/CASE_Evaporative_Cooler.pdf

Up to 38°F (21.1°C) of cooling can


theoretically be achieved (110°F Figure 2. Direct evaporative cooling process shown psychrometrically.
(43.3°C) – 72°F (22.2°C)) by simply Source: PsycPro software at www.Linric.com
adding water to the supply air-
stream. In this case, the supply
airstream was cooled to within
6°F (3.3°C) of the thermodynamic
wet-bulb limit, so it was 84%
effective as 32°F (17.8°C) of cooling
was achieved out of 38°F (21.1°C)
that was theoretically possible.
Achieving 90% to 95% of the wet-
bulb temperature is often the target
for direct cooling performance.

A psychrometric chart can show


why direct evaporative cooling
works well in dry climates and
not as well in humid ones. Using
Figure 3, if we start with 95°F
(35°C) TDB air (A) with relative
humidity of 70%, that air can be
directly cooled only 9°F (5°C)
before it reaches saturation at a
TWB of 86°F (30°C). Moving up
and to the left on the short red line
at A, the final air temperature can Figure 3. Comparison of the direct evaporative cooling possible when starting with
TDB of 95°F (35°C) at 70% RH vs. at 10% RH. Source: PsycPro software at www.
be read by following the vertical Linric.com
lines to the dry-bulb temperature.
Starting with 95°F (35°C) TDB air
(B) at 10% relative humidity, that

FEDERAL ENERGY MANAGEMENT PROGRAM — 


Technology Installation Review

Figure 4. In an indirect evaporative


cooling process, the primary airstream
flows in a different channel than the
secondary airstream. Source: Wang,
Shan K., Handbook of Air Conditioning
and Refrigeration (2nd Edition),
McGraw-Hill, p. 5, 2001; www.knovel. Figure 5. In the indirect evaporative cooling process, no water is shown being added
com/knovel2/Toc.jsp?BookID=568& to the primary airstream as it cools from A to B. Source: PsycPro software, www.
VerticalID=0 Linric.com

air can be cooled to 65°F (18.3°C) addition, the added moisture in • No chlorofluorocarbon (CFC)
before condensing, for about 35°F the air can be a bonus. usage
(19.4°C) of cooling. This is a • Reduced pollution-causing
Direct evaporative coolers have
significant increase in the amount emissions
several energy and cost advantages
of cooling that can be delivered The indirect evaporative cooling
over vapor compression systems.
than from humid air at the same process typically involves two
Typically, they have lower
temperature. It shows that there airstreams: one primary or product
installed costs and consume much
is greater cooling potential in air airstream and one secondary or
less energy than central air condi-
that is initially at a lower relative working airstream (Figure 4). The
tioners. These are some additional
humidity when a direct evapora- indirect cooling process evaporates
advantages:
tive cooling process is used. water and removes heat from the
• Lower initial cost than secondary/working airstream,
The cooling effect from direct
alternatives while not adding moisture to
evaporative coolers is a result of
the amount of moisture added to • Lower delivery temperature than the primary/product air. A heat
the air. Direct systems are not as indirect units exchange membrane is used
effective or efficient in climates • Less water use per cubic foot between the working airstream
in which the outside ambient air per minute (cfm) than that of and the supply airstream. The
is typically humid (such as the indirect evaporative coolers membrane’s ability to transfer heat
eastern half of the United States), • Substantial energy and energy out of the supply airstream and
because little moisture can be cost savings compared with the air flow rate determine the
added to the air and the cooling vapor compression systems effectiveness of the system.
effect is minimized. In very dry • Reduced peak power demand Psychrometrically, the indirect
climates (such as those in many • Wide variety of packaged cooling process moves left hori­
parts of New Mexico and Nevada), systems available zontally across the chart, since
direct cooling is quite effective no moisture is added (Figure 5).
• Easy integration into built-up
at cooling dry ambient air. In Theoretically, the air can be cooled
systems

 — FEDERAL ENERGY MANAGEMENT PROGRAM


Technology Installation Review

to the same wet-bulb temperature


through indirect evaporative
cooling as it can be through direct
evaporative cooling. In practice,
the direct evaporative cooling
process typically delivers cooler air
than the indirect process because
of heat exchanger inefficiencies in
the indirect process. Because the
secondary/working airstream has
added moisture, it is eventually
exhausted from the building and
no moisture is added to the pri-
mary/product airstream.
Figure 6. Two-stage indirect/direct evaporative cooling. Source:/www.energy.ca.gov/
The thermodynamic wet-bulb appliances/2003rulemaking/documents/case_studies/CASE_Evaporative_Cooler.pdf
temperature is often the target
temperature for both direct and
indirect evaporative cooling
technologies. It is considered to be
the lowest temperature attainable
through thermodynamic processes
without the need for additional
energy.

Combined Indirect/Direct
Evaporative Cooling. Both indirect
and direct cooling processes can
be combined into a single piece of
equipment in a two-stage process
(Figure 6). In typical indirect/
direct systems, the secondary
airstream sensibly cools the pri-
mary air in the first stage in an
indirect process. The air is then
directly cooled through evapora-
tion to lower the temperature
Figure 7. Two-stage indirect/direct evaporative cooling (indirect from A to B and then
further (Figure 7). The primary or direct from B to C) yields a lower TDB than does direct-only from A to D. Source:
supply air may actually exit below PsycPro software at www.Linric.com
the initial wet-bulb temperature.
This approach increases the
tional vapor compression air Cooler is one such ultracooler.
humidity of the primary or supply
conditioning. It differs markedly from conven-
air. However, it can operate
tional indirect/direct systems
effectively in a wider range of
climates than direct evaporative Ultracoolers because the direct evaporative
process does not involve the
cooling, and related energy costs Several coolers are able to cool air supply air; rather, it involves the
are lower than those of conven- below the thermodynamic wet- secondary or working airstream.
bulb temperature associated with As a result, no moisture is added
the dry-bulb temperature of the to the supply air throughout the
outside ambient air. The Coolerado entire cooling process, while the
________________
2 Source: www.oasysairconditioner.com, 2005.

FEDERAL ENERGY MANAGEMENT PROGRAM — 


Technology Installation Review

effectiveness of the evaporative


cooling process is notably
increased. The Coolerado Cooler
can cool below the wet-bulb
temperature; the dew-point
temperature is its cooling limit.

The OASys™ system2 is another


example of an innovative dual-
stream ultracooler that employs
both direct and indirect cooling
processes in a single unit. This
ultracooler can also add a con-
trolled amount of moisture to
the primary airstream.

The Coolerado Cooler uses both Figure 8. Supply air temperatures from several different cooling technologies.
Source: Don Cameron, NREL, 2005.
a direct and an indirect process
operating in parallel and in stages
to achieve cooler air than a direct
or indirect system alone would
achieve. Water is evaporated into
air in one chamber within the
cooler, and this cools the air
flowing in an adjacent chamber.
The cold air is used to cool the
building while the water vapor
holding the heat is exhausted.

Coolerado Cooler Basics


Figure 8 shows typical supply air
temperatures from several differ-
ent types of cooling technologies,
given ambient psychrometric Figure 9. Comparison of conventional indirect/direct air flow vs. the Maisotsenko
conditions of 96°F (35.6°C) TDB, Cycle air flow. OA is outside air; RA is return air.Source: Steve Slayzak, NREL.
71°F (26.7°C) TWB, 58°F (14.4°C)
dew point, and RH of 29% at effectiveness of both the direct M-Cycle), named for Dr. Valeriy
an elevation of 2500 ft (762 m). and indirect stages of its cooling Maisotsenko (see Figure 9). The
As shown, conventional air- process. The schematic in Figure 9 cycle works by cooling both the
conditioning delivers the lowest illustrates fluid movement through primary/product air and the
supply air temperature, but at a the patented Heat and Mass secondary/working air in stages—
significant cost in terms of energy Exchanger™ (HMX). The HMX is 20 stages in all. Each stage contrib-
and dollars. Indirect evaporative made of plastic-coated, cellulose utes to cooling by lowering the
coolers typically deliver air near blend fiber in a geometric design wet-bulb temperature. The cumu-
the comfort threshold—either that cools both the product and lative result is a lower primary/
slightly above or slightly below working airstreams without product air temperature than is
it, depending on ambient outside mixing them. possible with conventional evapo-
air conditions. rative cooling technology. The key
The development of a system of difference between this and other
How It Works. The Coolerado cascading incremental airflows direct/indirect processes is that
Cooler has a unique design creates a thermodynamic cycle the secondary/working air that
approach to maximizing the called the Maisotsenko Cycle (or is accumulating moisture is

 — FEDERAL ENERGY MANAGEMENT PROGRAM


Technology Installation Review

exhausted at each stage, enabling


more cooling to take place.

To better understand the process,


it can be helpful to examine what
happens in a single stage of the
20-stage process. In a typical
indirect/direct evaporative cooling
system, the working air is purged
once, at the end of the cycle, so the
limits of performance are based
on the thermodynamics of initial
conditions of relative humidity,
dry-bulb, wet-bulb, and dew-point
temperatures.

Here, the technology used for the


Coolerado Cooler enhances its
ability to further reduce primary/
product air temperatures. It does
so by taking the primary/product
air at the ending conditions and Figure 10. Conceptual psychrometric representation of the staged indirect cooling
process with continual purge of secondary/working air. Source: PsycPro software at
starting the process over. That www.Linric.com
product air is split into two air-
streams again—the primary/ purge process, so it will mix with of this purging, the Coolerado
product air and the secondary/ air at higher humidity but only in Cooler requires greater total
working air—but now at a lower the working airstream that is airflow than other types of cooling
dry-bulb temperature and a lower continuously exhausted. systems. However, because the
thermodynamic wet-bulb tempera- supply air temperature is lower
ture. The new starting point of the The advantage of the Maisotsenko than that possible with direct and
primary/product air is to the left Cycle is that the working air is indirect evaporative cooing sys-
of the original starting point on purged repeatedly so that the tems, less supply air is required
the psychrometric chart, so it has a initial conditions are essentially to meet space conditioning needs.
lower achievable thermodynamic reset, as lower dry-bulb and wet-
bulb temperatures are established Laboratory Testing Parameters.
wet-bulb temperature (Figure 10).
with each purge cycle. This allows Engineers at the National
No moisture is added at this point
the eventual supply air tempera- Renewable Energy Laboratory
to either the primary/product air
ture to be below what the original (NREL) in Golden, Colorado,
or this portion of the working/
initial conditions would indicate operated a Coolerado Cooler unit
secondary air, so significant
possible—below the thermodynamic in the NREL Thermal Test Facility
cooling capacity is available.
wet bulb temperature. This key (TTF) during the 2003-2004 time
In Figure 10, the red arrows cycling feature is essentially what frame (Figure 12). NREL put the
indicate the direct evaporative sets the Coolerado Cooler apart Coolerado Cooler through a range
cooling taking place in the process from other indirect/direct evapo- of tests to establish its performance
airstream exhausted at each of the rative cooling systems and enables capabilities and parameters. The
20 stages. The blue arrows repre- greater cooling performance. This system was equipped with a wide
sent indirect cooling through the cycling continues in all 20 stages, variety of sensors to measure
heat exchange membrane, which is and each contributes to lowering relative humidity, wet-bulb and
taking place in the process/supply the temperature of the primary/ dry-bulb temperatures, pressure
airstream with no moisture being product air. drops, and flow rates across the
added. Note that this portion of the HMX. Researchers measured the
working air does get mixed into Figures 10 and 11 illustrate the fan power directly from a power
the existing working air during the continuous purge process. Because transducer. These conditions were

FEDERAL ENERGY MANAGEMENT PROGRAM — 


Technology Installation Review

1 Outside air is pushed into the Coolerado


Cooler heat exchanger with a single fan. but under variable ambient condi-
10
10
tions determined by Colorado’s
2 Product Air Channels. 5
6 weather. Figure 13 shows the
3 Working Air Channels. 6 calculated EER for a variety of
4 Heat from the Product Air is transferred temperature differences between
through the thin plastic and into the Wet dry-bulb and wet-bulb
Channels below. 8
temperatures.
5 Working Air is blocked from entering 4 7
the building. The calculated EER values indi-
9
6 The Blocked Working Air is turned and cated a high degree of correlation
passed through small holes into Wet between the difference between the
Channels below the Product Air stream.
dry-bulb and wet-bulb tempera-
7 The Working Air is now moving through ture and the EER (i.e., the greater
Wet Channels perpendicular or cross 2
flow above and below the Dry Channels. the temperature difference, the
greater the calculated EER). The
8 The heat that is passed from the Dry 2
Channel is converted into water vapor. Coolerado Cooler unit operates
3
more efficiently when the weather
9 Heat from the Product Air has been
converted into water vapor and is now is both hot and dry.
rejected as exhaust to the outside air.
1 Given the operating characteristics
10 The Product Air which has now traveled
the length of the heat exchanger, enters of the Coolerado Cooler and its
the desired space, cold and dry. performance in Colorado, an
Figure 11. How the staged indirect/direct evaporative cooling process flows. Source: extrapolation was done to estimate
http://www.idalex.com/technology/how_it_works_-_technological_perspective.htm its potential performance in
various cities in the western United
measured in a real-world type ment states its EER under specific States. Along with the correlation
of environment with the unit test conditions (see Glossary of from the test data, an estimated
installed and providing cooling Terms for cooling terminology). EER value was calculated using
to the TTF, rather than in a At NREL, the first test involved 1% design wet-bulb and dry-bulb
controlled-test setup. determining how effective or temperatures from the American
efficient the Coolerado Cooler Society of Heating, Refrigerating,
The energy efficiency ratio (EER) was in providing cooling by and Air-Conditioning Engineers’
on the Energy Guide label found determining its EER. The EER (ASHRAE) design temperature
on new air-conditioning equip- calculation was done repeatedly, data for several locations through-
out the West.

Figure 13. Energy


efficiency rating versus
wet-bulb temperature
depression.
Note: Different colors
represent different air
mixtures and dates.
Source: Data collected
at NREL’s Thermal Test
Facility, 2003-2004.

Figure 12. Coolerado Cooler test unit at


NREL’s Thermal Test Facility. Source: NREL

 — FEDERAL ENERGY MANAGEMENT PROGRAM


Technology Installation Review

Table 1 shows the estimated EER


values for cooling from April State City April May June July August Sept.
through September, averaged over TX El Paso 13.6 13.7 12.4 9.1 8.8 7.7
both the month and the day. Peak
NM Albuquerque 15.7 13.7 13.0 12.7 11.1 10.0
temperature values with average
to low humidity would lead to CO Grand Junction 14.5 13.9 17.3 12.4 12.5 10.9
higher EERs when cooling WY Cheyenne 12.1 9.3 10.2 9.4 8.2 8.7
demands are the highest. MO Billings 14.6 12.8 13.9 12.8 15.8 14.2
Another analysis performed using ID Boise 11.2 15.2 17.0 16.8 17.3 14.6
the collected data was to determine
UT Salt Lake City 13.1 11.9 16.4 13.3 10.3 10.9
how effectively the system cooled
relative to the thermodynamic wet- AZ Phoenix 20.5 20.8 19.5 15.1 13.6 14.5
bulb temperature. This measure NV Las Vegas 20.0 18.5 24.0 16.8 15.1 13.0
of efficiency, known as wet-bulb CA Bakersfield 14.8 19.4 21.4 19.5 15.2 13.3
efficiency, is defined as follows:
WA Spokane 9.7 13.9 13.7 15.2 15.2 14.8
where OR Pendleton 9.9 11.9 15.4 19.2 19.4 15.8
TSI_DB – TSO_DB
ewet-bulb = _____________________ Table 1. Estimated average EER for the Coolerado Cooler based on test data correla-
tions. Calculated at NREL (2004) using 1% design wet-bulb temperatures from
TSI_DB – TSI_WB
ASHRAE 2001, Chapter 273.
where

TSI_DB = Drybulb_Temperature_Supply_Inlet

TSO_DB =
Drybulb_Temperature_Supply_Outlet

TSI_WB = Wetbulb_Temperature_Supply_Inlet

A value of 1.0, or 100%, indicates


that a cooling unit has achieved as
much cooling as is theoretically
possible, i.e., the thermodynamic
wet-bulb temperature. Because
the Coolerado Cooler efficiency
increases on these units when the
difference between dry- and wet-
bulb temperatures is greater, a
trend can be seen with the change
in temperature (Figure 14). As the
temperature differential increases
beyond 12°-13°C (21°-23°F),
efficiencies greater than 85% are
regularly achieved.
Figure 14. Wet-bulb efficiency rating versus wet-bulb temperature depressions.
Applications for the Note: Different colors represent different air mixtures and dates. Source: Data
collected at NREL’s Thermal Test Facility, 2003–2004.
Coolerado Cooler
The performance of the Coolerado
Cooler will vary, depending upon
average outside ambient condi-

________________
3 Table 1B Cooling and Dehumidification Design Conditions, Chapter 27.7 – Climatic Design Information, 2001 ASHRAE Handbook
Fundamentals.`
FEDERAL ENERGY MANAGEMENT PROGRAM — 
Technology Installation Review

a conventional air conditioner.


Reducing the amount of electrical
energy consumed for cooling can
thus also reduce the amount of
water consumed, from the power
plant to the cooled space.

The exact amount of water con-


sumed in generating electricity
varies, depending on the fossil fuel
used (natural gas-fired plants use
less water than coal-fired plants)
and the type of conversion tech­
nology employed (combined-cycle
power plants use less water than
steam plants do). Generating a
kilowatt-hour (kWh) of electricity
at a new coal plant in the
Southwest uses about 0.67 gallons
(gal) (2.5 liters [L]) of water, while
a new natural-gas-fired plant
Figure 15. Map of summer cooling load hours. Source: ARI Unitary Directory, August consumes about 0.33 gal (1.2 L)
1, 1992, to January 31, 1993, pp. 16-17; Air-Conditioning and Refrigeration Institute,
www.energyexperts.org/ac_calc/default.asp. of water per kWh generated.4 The
national weighted average for
tions during the cooling season. consumption if it is used to thermoelectric and hydroelectric
The map in Figure 15 provides a pre­cool the air entering conven- water use is 2.0 gal (7.6 L) of
color-coded graphical indication tional vapor compression systems. evaporated water per kWh of
of where and how a direct evapo- Direct evaporative systems cannot electricity consumed at the point
rative cooler will be most effective. be used in a similar manner in of use.5 The impact varies by the
The Coolerado Cooler will work these conditions because they source—either surface water or
as well or better as a direct evapo- provide little cooling to moist air. groundwater. Water diverted or
rative cooler does in the same The Coolerado Cooler is suitable withdrawn is water removed from
regions but also in other regions, for use throughout the country, streams, groundwater, or other
because it does not add moisture to though different configurations sources. Much of this water is
the supply air. The map also shows and energy savings are applicable consumed through use. The
the average number of summer in different climates. remainder returns to the local
cooling hours per year. surface or groundwater system
and is available for subsequent
The purple area indicates regions Water Use Issues use downstream of its discharge.6
in which this technology and direct Water is used in both evaporative
evaporative coolers should work A conventional residential air-
cooling and in ultracoolers such as
well in stand-alone applications. conditioning system does not
the Coolerado Cooler and OASys
The large green area indicates consume water at the place where
systems. A significant amount
regions in which the Coolerado it delivers conditioned air if it has
of water is also used in thermal
Cooler has the potential to signi­ an air-cooled condenser. Most
electric power plants to generate
ficantly reduce cooling energy commercial HVAC systems include
the electricity required to power
a wet cooling tower, which evapo-

________________
4 The New Mother Lode: The Potential for More Efficient Electricity Use in the Southwest, SWEEP, 2002.
5 Torcellini, P., Long, N., and Judkoff, R. Consumptive Water Use for U.S. Power Production, National Renewable Energy Laboratory, U.S.
Department of Energy, December 2003.
6 The Last Straw: Water Use by Power Plants in the Arid West, Clean Air Task Force, The Land and Water Fund of the Rockies, The Energy
Foundation, and The Hewlett Foundation, April 2003.

10 — FEDERAL ENERGY MANAGEMENT PROGRAM


Technology Installation Review

Cooling system Load determination Operating characteristics Cost parameters


Conventional air • Based on all building thermal • Supply air can be heated or cooled to remove or add • installed cost per ton
conditioning loads i.e., solar gains, moisture $900–$1,800/ton
systems building materials, internal • Supply air made very cool then mixed with return air • Power per ton
gains by people, machines, • Cycles on and off between set points 900–1,500 W/ton
appliances, etc.
• Low CFM
• High power consumption
Direct • Size to blow enough air • High CFM — delivers cool air with enough velocity to • Installed cost/ton
evaporative across wetted medium to provide sensible cooling to building occupants $280-$670/ton
coolers evaporate water into the air • Open system — windows or exhaust vents must be • Power per ton
thereby cooling it open 250–400 W/ton
• Based on square footage of • Runs continuously during occupied hours with a
building and air changes per cooling load
hour for occupancy type • Needs periodic bleed-off to avoid mineralization
• Low power consumption
Coolerado • Sized based on square • Delivers cool air at moderate CFM • Installed cost per ton
Coolers footage, thermal load, • High volume of moist air exhaust $900–$1,100/ton
ambient air conditions • Low power consumption • Power per ton
• Sized to about twice the CFM • Constant low volume bleed-off 220–260 W/ton
of air conditioning
• Secondary/working air moisture (water) is exhausted
from building

Table 2. Comparison of load, operating, and cost parameters for small office coolers.
Source: Compilation from R.S. Means Mechanical Cost Data 2005 and manufacturers’ data sheets

rates the water. However, water water through the evaporative Economic and
associated with the generation of medium, are often used to mini- Performance Data
electricity used for cooling also mize mineral build-up on the
needs to be accounted for in order medium. The Coolerado Cooler Conventional air-conditioning
to make a meaningful comparison employs a small continual flow, systems, direct evaporative cool-
of cooling methods. For both a rather than bleed-off cycles, to ers, and ultracoolers all have
direct evaporative cooler and prevent mineral build-up. It uses different sizing, operational, and
ultracoolers, the electricity con- about 10 gal/hr (37.9 L/hr) during cost parameters (Table 2).
sumed in providing cooled air peak operation and averages about Meaningful comparisons are
needs to be accounted for as well 3.5 gal/hr (13.2 L/hr) during the difficult to make, because of the
as on-site water consumed during entire cooling season.8 lack of conversion factors between
the evaporation process. systems designed to operate on
Chiller plants in larger commercial different principles and data. This
A study of 46 residences in HVAC systems use water to is especially true for a technology
Phoenix, Arizona, found that direct remove heat from air and equip- that is still fairly new
evaporative coolers consumed ment. A general rule of thumb for and deployed in relatively small
about 4.4 gallons per hour (gal/hr) water usage is 2 to 3 gal/ton (7.6 numbers in various locations
(16.7 L/hr) of water during to 11.4 L per ton) of cooling.9 with different environments. One
operation without bleed-off and cannot simply compare one system
about 10.4 gal/hr (39.4 L/hr) with with another in a different loca-
bleed-off7 for an average of about tion, or even in the same location
7.6 gal/hr (28.8 L/hr) for all sys- in different ambient conditions,
tems. Bleed-off cycles, which flush because the sizing and operating

________________
7 Evaporative cooler water use, Karpiscak, M.; Marion, M.; Arizona Cooperative Extension, http://ag.arizona.edu/pubs/consumer/az9145.pdf; 1994.
8 Telephone conversation with R. Gillan, February 2006.
9 Evaluating and Improving Chiller Plant Efficiency, Trane Corporation, www.trane.com/commercial/issues/environmental/short.asp, 2006.

FEDERAL ENERGY MANAGEMENT PROGRAM11 — 11


Technology Installation Review

parameters would yield different ants are used in the cooling change in water content [TDew
results. Unlike other building process. measured in F°].
energy systems, ultracoolers are
not yet readily modeled in terms The Coolerado Cooler can have the Dry-bulb temperature: The inside
of their energy use using currently greatest impact on demand charges air temperature measured by a
available tools. and cost and energy savings when thermometer. These temperatures
peak demand is greatest. During are shown as vertical lines on the
Because it is a relatively new the cooling season, these are the psychrometric chart [TDB measured
technology, the Coolerado Cooler hottest times of the day; they are in °F].
has not been the subject of a also times when air-conditioning
widespread study and has not loads are highest and power plant Humidity ratio: The ratio of the
undergone significant independent efficiencies are lowest. It performs mass of water vapor to the mass
review, except as discussed earlier best during those times and of dry air in a moist-air mixture
in this report. Consequently, the provides the benefits of cool, fresh, [W is the symbol used, measured
manufacturer has had to supply dry air at a much lower cost than as a decimal ratio].
some of the economic and perfor- that of a conventional air Psychrometrics is the study of the
mance data. conditioner. thermodynamic properties of
Both direct evaporative coolers moisture content in atmospheric
and the Coolerado Cooler consume Glossary of Terms air. It is used in the design and
25% to 40% as much power as vapor analysis of performance for a wide
compression air-conditioning
Psychrometric Terms variety of processes that involve
systems do. The installed cost for Dew-point temperature: The tem- warming or cooling air, which
the Coolerado Cooler can be 2 to perature at which moisture in the always contains some moisture.
3 times higher than that of direct air will condense on surfaces; The amount of this moisture has
evaporative coolers, but it is either HVAC designers work to avoid a direct effect on the health and
less expensive than most vapor condensation on building surfaces comfort of occupants. HVAC
compression air-conditioning and equipment. From a given system designers and operators use
systems or cost-competitive with dry- or wet-bulb temperature, psychrometric analysis techniques
them. move horizontally to the left on with thermodynamic properties and
the psychrometric chart to find principles to optimize health and
comfort levels within occupied
Summary and Conclusions the lower temperature at which
spaces.
condensation will occur with no
The Coolerado Cooler technology
can reduce cooling energy. Like
other energy efficiency strategies,
it can help Federal agencies, reach
the energy-use reduction goals of
EPAct 2005, particularly in the
western United States. This tech-
nology also has the potential to
have a significant impact on an
agency’s energy bills in terms of
reducing both energy and demand
costs. Widespread deployment of
this technology in average to dry
climates in the United States could
have a significant positive impact
on electric demand and ease the
burden on the utility grid. An
added benefit is that no refriger-
Figure G-1. Key properties measured in a psychrometric chart. Source: http://www.
sp.uconn.edu/~mdarre/NE-127/NewFiles/psychrometric_inset.html

12 — FEDERAL ENERGY MANAGEMENT PROGRAM


Technology Installation Review

Relative humidity: The measure of


the moisture content of a mixed Cooling calculation parameters:
airstream (dry air and water vapor) • A ton of refrigeration is defined as the cooling power of one
relative to the amount of moisture short ton (2000 lb or 907 kg) of ice melting in a 24-hour period.
in saturated air at the same tem-
perature. These curved lines are • 1 ton of cooling equals 12,000 Btu/hr, or 3510 W.
bounded by the dew-point curve, • It takes 1 Btu to raise the temperature of 1 lb of water 1°F.
which is also 100% relative humid-
• It takes approximately 1000 Btu to evaporate 1 lb of water and
ity [RH, often denoted by the
approximately 8700 Btu to evaporate 1 gal of water.
symbol φ, is measured in percent].
• It takes 0.24 Btu to raise the temperature of 1 lb of air 1°F.
Wet-bulb temperature: An interme-
diate quantity that informs the • 1 lb of air occupies 13.7 ft3 of space at sea level when the
HVAC designer about the mois- temperature is 75°F.
ture content in air, it is measured
with
50% RH by the power consumed consumed (kWh). The result,
a thermometer with a wetted wick
(in watts [W]) in order to meet in units of Btu/kWh, indicates
and a specified airflow over that
indoor requirements of 80°F and seasonal performance. Higher
wick. It represents the maximum
50% RH. The resulting unit for EER SEERs are more efficient. A SEER
thermodynamic cooling that can
is Btu/hr/W. Higher EERs are of 13.0 or greater is required for
be achieved before condensation.
more efficient. The EER indicates Energy Star qualification. SEERs
These are shown as diagonal lines
peak performance on the hottest will always be higher than EERs
moving up and to the left in a
days.10 The minimum required for a given piece of cooling equip-
psychrometric chart and decreas-
Energy Star® EER rating for a ment because they are tested at
ing in temperature (cooling) [TWB
room air conditioner is 9.4 or less extreme or less rigorous
measured in F°].
greater. For an 8,000 to 13,999 Btu/ conditions.11
hr capacity air conditioner without
Cooling Equipment Terms louvers, the Energy Star require- Acknowledgments
Cooling capacity: This is a measure ment specifies a minimum EER of
of the amount of air (mass) being 10.8. Energy Star EER require- This publication was written
cooled per unit time, its specific ments vary between 9.4 and 10.8 by Robi Robichaud of the NREL
heat capacity, and the change in for other configurations and FEMP Technical Assistance Team.
temperature achieved. Typical units capacity sizes. The author wishes to thank the
are in tons of cooling provided; following for their valuable
SEER (seasonal energy efficiency contributions: Ben Barnes, Mike
1 ton of cooling is equivalent to
ratio): This is a measure of the Brandemuehl, Sheila Hayter,
12,000 Btu/hr of heat removed
seasonal efficiency of an air condi- Erik Kozubal, Steve Slayzak, Vern
from a space.
tioner through the entire cooling Smith, Otto Van Geet, and Andy
EER (energy efficiency ratio): This season at a specific outdoor Walker. This analysis was funded
is a measure of the instantaneous temperature (82°F), accounting for by the U.S. Department of Energy,
efficiency of a room air conditioner seasonal temperature variations. Office of Energy Efficiency and
and is calculated by dividing the It is calculated by dividing the Renewable Energy, Federal Energy
cooling capacity (Btu/hr) at an seasonal cooling energy (Btu) by Management Program.
outdoor temperature of 95°F and the seasonal electrical energy

________________
10 Buying an Air Conditioner? Remember the EER. Pacific Gas and Electric, 2006,www.pge.com/docs/pdfs/res/rebates/central_air/
03eer_tech_v3.pdf.
11 Buying an Air Conditioner? Remember the EER. Pacific Gas and Electric, 2006, www.pge.com/docs/pdfs/res/rebates/central_air/
03eer_tech_v3.pdf.

FEDERAL ENERGY MANAGEMENT PROGRAM13 — 13


A Strong Energy Portfolio
for a Strong America
Energy efficiency and clean, renewable
Log on to FEMP’s Web site for information energy will mean a stronger economy, a
cleaner environment, and greater energy
about New Technology Demonstrations independence for America. Working with a
wide array of state, community, industry,
www.eere.energy.gov/femp/ and university partners, the U.S. Department
of Energy’s Office of Energy Efficiency and
You will find links to Renewable Energy invests in a diverse port-
folio of energy technologies.
• A New Technology Demonstration Overview
• Information on technology demonstrations For More Information
• Downloadable versions of publications in Adobe Portable
EERE Information Center
Document Format (pdf ) 1-877-EERE-INF or
• A list of new technology projects under way (877-337-3463)
• Electronic access to a regular mailing list for new products www.eere.energy.gov/femp
when they become available General Contacts
• How Federal agencies may submit requests to us to assess Will Lintner
new and emerging technologies Team Lead, RSTT
Federal Energy Management Program
U.S. Department of Energy
1000 Independence Ave, SW, EE
Washington, DC 20585
Phone: (202) 586-3120
Fax: (202) 586-3000
william.lintner@ee.doe.gov
Steven A. Parker
Pacific Northwest National Laboratory
P.O. Box 999, MSIN: K5-08
Richland, WA 99352
Phone: (509) 375-6366
Fax: (509) 375-3614
steven.parker@pnl.gov
Technical Contact
Robi Robichaud
National Renewable Energy Laboratory
Disclaimer MS 1534
This report was sponsored by the United States Department of Energy, Energy Efficiency and 1617 Cole Boulevard
Renewable Energy, Federal Energy Management Program. Neither the United States Government Golden, CO 80401
Phone: (303) 384-7553
nor any agency or contractor thereof, nor any of their employees, makes any warranty, express Fax: (303) 384-7411
or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or robi_robichaud@nrel.gov
usefulness of any information, apparatus, product, or process disclosed, or represents that its
use would not infringe privately owned rights. Reference herein to any specific commercial Produced for the U.S. Department
product, process, or service by trade name, trademark, manufacturer, or otherwise does not of Energy, Energy Efficiency and
necessarily constitute or imply its endorsement, recommendation, or favoring by the United Renewable Energy, by the National
States Government or any agency or contractor thereof. The views and opinions of authors Renewable Energy Laboratory
expressed herein do not necessarily state or reflect those of the United States Government or
any agency or contractor thereof. DOE/GO-102007-2325
June 2007

This publication is subject to Government rights. U.S. Department of Energy

Printed with a renewable-source ink on paper containing Energy Efficiency


at least 50% wastepaper, including 10% postconsumer waste. and Renewable Energy

S-ar putea să vă placă și