TEST MODE MODBUS NO DESCRIPTIONS COMM Tx Rx REMARKS GATEWAY 000012-Tx:02 03 00 00 00 0A C5 FE 1. Online with EMH software and found the 000013-Rx:02 03 14 3D 23 D7 0B 3C F5 C2 91 3D 23 D7 0B 42 14 CC CD 42 0F 99 9A 66 33 device read well 000014-Tx:02 03 00 00 00 0A C5 FE 2. Online with Laptop and Modbus scan 000015-Tx:02 03 00 00 00 0A C5 FE The indication show the use RTU serial line for LGONE Gateway 000016-Tx:02 03 00 00 00 0A C5 FE Modbus scan send transmit 1 Modbus Gateway LG ONE G1 directly and after moment of counting 000017-Tx:02 03 00 00 00 0A C5 FE but not receive in four transmit, we are found request time out 000018-Tx:02 03 00 00 00 0A C5 FE counting time from the LG for counting four time (4 time) Tx after 000019-Rx:02 03 14 3D 23 D7 0B 3C F5 C2 91 3D 23 D7 0B 42 14 CC CD 42 0F 99 9A 66 33 ONE Gateway G1 Rx Receive during reading Modbus 000020-Tx:02 03 00 00 00 0A C5 FE FC03 000021-Rx:D7 0B 42 14 CC CD 42 0F 99 9A 66 33 02 03 14 3D 23 D7 0B 3C F5 C2 91 3D 23 000022-Tx:02 03 00 00 00 0A C5 FE 000014-Tx:03 03 00 00 00 02 C5 E9 000015-Rx:03 03 04 3C F5 C2 91 55 5D 000016-Tx:03 03 00 00 00 02 C5 E9 3. Online with EMH software and found the 000017-Rx:03 03 04 3C F5 C2 91 55 5D device read well 000018-Tx:03 03 00 00 00 02 C5 E9 4. Online with Laptop and Modbus scan The indication show the 000019-Rx:03 03 04 3C F5 C2 91 55 5D use RTU serial line for LGONE Gateway Modbus scan send transmit 000020-Tx:03 03 00 00 00 02 C5 E9 2 Modbus Gateway LG ONE G2 directly and after moment of counting but not receive in one 000021-Tx:03 03 00 00 00 02 C5 E9 transmit, we are found request time out counting time from the LG 000022-Rx:03 03 04 3C F5 C2 91 55 5D for counting one time (4 time) Tx after ONE Gateway G2 000023-Tx:03 03 00 00 00 02 C5 E9 Rx Receive during reading Modbus 000024-Rx:03 03 04 3C F5 C2 91 55 5D FC03 000025-Tx:03 03 00 00 00 02 C5 E9 000026-Rx:03 03 04 3C F5 C2 91 55 5D 000027-Tx:03 03 00 00 00 02 C5 E9