REV615 is a dedicated capacitor bank protection and REV615 is equipped with a large graphical display which
control relay for protection, control, measurement and can show customizable single-line diagrams (SLD) with
supervision of capacitor banks used for compensation of position indication for the circuit breaker, disconnectors and
reactive power in utility and industrial power distribution the earthing switch. Also measured values provided by the
systems. chosen standard configuration can be displayed. The SLDs
are customized using PCM600 and can have multiple pages
Application for easy access to selected information. The SLDs can be
REV615 has been designed to be the main protection for accessed not only locally but also via the web browser-based
H-bridge, double Y and single Y-connected capacitor banks HMI that has now been enriched with a number of usability
and feeder cables. Additionally, REV615 can be used to enhancing features.
protect harmonic filter circuits when no significant harmonic
component is higher than the 11th. Standardized communication and redundancy
REV615 fully supports the IEC 61850 standard for
REV615 is available in two standard configurations, both communication and interoperability of substation automation
of which offer three-phase overload protection, current- devices, including fast GOOSE messaging and IEC 61850-
based unbalance protection with compensation for natural 9-2 LE, and can now also benefit from the extended
unbalance, and current-based switching resonance protection interoperability provided by Edition 2. The capacitor bank
for capacitor banks. The overload protection includes an relay further supports both the parallel redundancy protocol
integrated undercurrent function which detects disconnection (PRP) and the high-availability seamless redundancy (HSR)
of a capacitor bank and inhibits the closing of the circuit protocol, together with the DNP3, IEC 60870-5-103 and
breaker for as long as the capacitor bank is partially charged. Modbus® protocols. With the protocol adapter SPA-ZC 302,
The three-phase thermal overload protection can be used for Profibus DVP1 can also be used. REV615 is able to use two
reactors and resistors in harmonic filter circuits. REV615 also communication protocols simultaneously.
offers non-directional overcurrent and earth-fault protection
for capacitor banks and their feeder cables. The other of the For redundant Ethernet communication, REV615 offers either
two standard configurations additionally offers directional two optical or two galvanic Ethernet network interfaces. A
earth-fault, residual voltage, voltage-based unbalance, and third port with a galvanic Ethernet network interface provides
over- and undervoltage protection. connectivity of any other Ethernet device to an IEC 61850
station bus inside a switchgear bay. The redundant Ethernet
One has been preconfigured for H-bridge connected solution can be built on the Ethernet-based IEC 61850,
capacitor banks and has a three-phase unbalance protection, Modbus ® and DNP3 protocols.
whereas the other has been preconfigured for double
Y-connected capacitor banks and has a single-current The implementation of the IEC 61850 standard in REV615
unbalance protection. covers both vertical and horizontal communication, including
GOOSE messaging with both binary and analog signals as
The standard configurations can be tailored to well as parameter setting according to IEC 61850-8-1. Also
meet application-specific requirements using the IEC 61850-9-2 LE process bus with sending sampled values
IEC 61850-compliant Protection and Control IED Manager of not only analog voltages but now also currents, in addition
PCM600. to receiving sampled values of voltages, is supported. For
process bus applications, which require high-accuracy time
Human-machine interface synchronization, IEEE 1588 V2 is used, with a time stamp
As a member of the Relion® product family, REV615 shares resolution of not more than four microseconds. IEEE 1588
the same human-machine interface (HMI) look and feel as the V2 is supported in all variants with a redundant Ethernet
other Relion protection and control relays and IEDs. The same communication module. In addition, REF615 supports
look and feel includes the location of a push button with a synchronization over Ethernet using SNTP or over a separate
certain function and the menu structure. bus using IRIG-B.
UL1UL2UL3 REV615 B
CAPACITOR BANK PROTECTION AND CONTROL RELAY STANDARD
CONFIGURATION
- Web HMI
I ESC Clear
3I 2× AND
I2> 3Ith>T/G/C 3I>>> O R
L
OR
46 49T/G/C 50P/51P
3× 3×
ARC 3I>/Io>BF
50L/50NL CONDITION MONITORING COMMUNICATION
51BF/51NBF
3I AND SUPERVISION
Protocols:
IEC 61850-8-1/-9-2LE
3I>3I< dI>C 3dI>C 3I> FUSEF CBCM MCS 3I Modbus®
51C 51NC-1 51NC-2 51P-1 60 CBCM MCS 3I IEC 60870-5-103
DNP3
2× 2× Interfaces:
3I>> TD> OPTS TCS Ethernet: TX (RJ45), FX (LC)
51P-2 55TD OPTM TCM Serial: Serial glass fiber (ST),
Io RS-485, RS-232
Redundant protocols:
HSR
Io PRP
RSTP
2)
Control and indication function for
2× 2× primary object Voltage transformer 5
3U< U2> U1< 3U> 3)
Status indication function for
27 47O- 47U+ 59 1)
Conventional transformer inputs
UL1UL2UL3 primary object
PQUUB
PQVUB
REMARKS
18× 2× Optional 3× No. of Calculated OR Alternative
MAP Uo> function instances value function to be
Uo MAP 59G Io/Uo defined when
2xRTD ordering
1xmA
Iunb
Standard configurations
Standard
Description
configuration
Capacitor bank overload and unbalance protection, non-directional overcurrent and earth-fault protection
A
and circuit breaker condition monitoring
Capacitor bank overload and unbalance protection, non-directional overcurrent and directional
earth-fault protection, voltage and frequence based protection and measurements, B
cicuit breaker condition monitoring
Three-phase current unbalance protection for H-bridge SCB HCUBPTOC 3dI>C 51NC-2 1 4)
1 4)
Capacitor bank switching resonance protection, current based SRCPTOC TD> 55TD 1 1
Power Quality
Current total demand distortion CMHAI PQM3I PQM3I (1) 5)
(1) 6)