07.94 Supply Infeed (NE)
2 Service and Diagnostics
1 2
3 4
5 6
Effects:
1 LED red bright: Pulses are deleted for the complete drive group
2 LED red bright: Pulses are deleted for the complete drive group
4 LED yellow dark: Pulses are deleted for the complete drive group
5 LED red bright: Only the I/O module pulses are deleted (regenerative feed
back no longer possible. Axes initially continue to run,
ready relay drops–out)
6 LED red bright: Pulses are deleted for the complete drive group
S Terminal 48 Start
– has the highest priority for enabling the pulses for all of the modules
– acts instantaneously
S Terminal 64 Drive enable
Caution
! Induction motors can reach high speeds even at low VDC link!
S Terminal 19 FR–
– For this mode, terminals 2U1, 2V1 and 2W1 of the power supply
must be supplied with the line supply voltage between the series reactor and
I/R, as otherwise the power supply will be destroyed. The also applies to the
montioring modules!
Note
This is guaranteed by the jumpers inserted in the factory at connector X181.
S Monitoring module with connection to the line supply and additional power
supply connection at the DC link :
– For this mode, terminals 2U1, 2V1 and 2W1 of the power supply
must be supplied with the line supply voltage between the series reactor and
I/R, as otherwise, the power supply will be destroyed!
– Terminal 63 may only be energized (enabled) after the NE module has run–up
(ready). (Interrogation “ready” or terminal 111 – 113 – 213).
Diagnostics The overvoltage limiting module must be checked if a line supply fault is
displayed or the yellow LED is dark.
Procedure:
1. Power–down the unit so that it is in a no–voltage condition
2. Remove the overvoltage limiting module and insert connector X181 on the NE
NE module. If the NE module functions, then the overvoltage limiting module
is defective and must be replaced. Otherwise, check the line supply and if
necessary check the NE module/group.
Note
In this way, continued operation is possible, without overvoltage protection.
Note
Operation without overvoltage limiting module is not in conformance with UL!
NE