Sunteți pe pagina 1din 8

Regression

Multivariate
Modeling
An empirical or regression modeling approach is simple to develop and easy to use
compared to detailed hourly simulations of energy use in commercial buildings.
S. Katipamula Therefore, regression models developed from measured energy data are becoming
P a c i { iNc o r t h w eNs ta t i o n aL la b an increasingly popular method for determining retrofit savings or identifiing opera-
R i c h l a nWd , A9 9 3 5 2 tional and maintenance (O&M) problems. Because energy consumption in large
commercial buildings is a complex function of climatic conditions, building character-
istics, building urolr, system chaiacteristici and type of heating, ventilation, and air
T. A. Reddy conditioning (HVAC) equipment used, a multiple linear regression (MLR) model
D re x e provides better accuracy than a single-variable model for modeling energy consump'
Uln i v e rs i ty -tion.
D e p t.o f C i v ial n d AIso, when hourly monitored data are available, an issue which arises is what
A r c h i te c tu Eran gl i n e e ri n g time resolution to adopt for regression models to be most accurate. This paper
P h i l a d e l pPhA i1a9
, 104 addresses both these topics. This paper reviews the literature on MLR models of
buitding energy use, describes the methodology to develop MLR models, and high'
tights the usefulness of MLR models as baseline models and in detecting deviations
D. E.Claridge ii energy consumption resulting from major operational changes. The paper first
T e x a s A & M U n i v e r s i t ydevelops the functional basis of cooling energy use for two commonly used HVAC
Energy System Lab systems: dual-duct constant volume (DDCV) and dual-duct variable air volume
Col l e gSeta ti oTnX , 77843 (DDVAV). {lsing ihesefunctional forms, the cooling energy consumption in five large
commercial buitdings located in central Texas were modeled at monthly, daily, hourly,
and hour-of-day (HOD) time scales. Compared to the single-variable model (two'
parameter model with outdoor dry.bulb as the only variable), MLR models showed
a decrease in coefficient of variation (CV) between I0 percent to 60 percent, with
an average decrease of about 33 percent, thus clearly indicating the superioriry of
MLR models. Although the models at the monthly time scale had higher cofficient
of determination (R2) and lower CV than'daily, hourly, and HOD models, the daily
and HOD models proved more accurate at predicting cooling energy use.

I Introduction and Review of Literature ter change point model (piecewise linear model) to model elec-
tricity use of a grocery store. The basis of using a four-parameter
Regression analysis of measured data is becoming increas- change point model to model the energy consumption in a gro-
ingly popular as a means of developing baseline models of cery store is that below a certain To there is no cooling load,
energy consumption in commercial buildings, both for de- but there is still a refrigeration load and thus the change in the
termining retrofit savings and for identifying O&M problems. slope.
They are simple to develop and easy to use compared to other The single-variable regression models (based on just the I,)
modeling approaches, such as calibrated DOE-2.1 (Diamond, can adequately model energy consumption in residential build-
and Hunn, 1981; Copeland, 1983; Bronson et al., 1992; and ings (Fels, 1986) and, in some cases, commercial buildings
Kaplan et al., 1992) or simplified systems modeling (Katipa- (Kissock et al., 1993). However, the energy consumption in
mula and Claridge, 1993). large commercial buildings is a complex function of climatic
Regression models can be based on monthly (Fels, 1986), conditions (dry-bulb and dew-point temperatures, solar, . .),
daily (Kissock et al.,1992; Ruch and Claridge,1992), or hourly building characteristics (loss coeffi cients, heat capacity, internal
energy consumption data (Seem and Braun, 1991; Dhar et al., loads, .), building usage (l2-hour, or 24-hour, amount of
1994). A two-parameter linear model (E, : a * bT,,) is often fresh air intake, . .), system characteristics (total mass flow,
used to regress the daily or the monthly energy consumption hot and cold deck supply temperatures,economizer cycle,. '),
as a function of the outdoor dry-bulb temperature (2,) (Kissock and type of HVAC equipment used. Because some of these
et al., 1992), because significant variation in the energy con- parameters are difficult to estimate or monitor in an actual build-
sumption in buildings is due to the variations in the envelope ing, they cannot be used explicitly as variables in the regression
and ventilation loads, which are a strong function of I,. The models. Although the building use and operational parameters
Princeton Scorekeeping'Method (PRISM) uses a three-parame- (e.g., supply temperatures, fresh air intake) change from hour
ter model to model residential energy consumption (Fels, 1986). to hour, they are effectively constant from day to day. Therefore,
This model is based on the physical observation that the gains their contributions are minimal for models with monthly and
in a building preclude the necessity for heating until the outdoor daily time scales. The daily models are reasonable and reliable
temperature drops below a "balance temperature," which is if several months (six months or more) of data are used. lJnfor-
lower than the thermostat set point by an amount equal to the tunately, if only fewer than three months of data are available.
ratio of the gains to the loss coefficient of the building. Schrock the daily regression models may lead to significant errors in
and Claridge (1989) and Ruch et al. (1992) used a four-parame- prediction of the annual energy consumption (Rachlin et al.,
1986; Kissock et al., 1993: and Katipamula et al.' 1995a).
A number of researchers have shown the benefits of MLR
Contributed by the Solar Energy Division of The American Society of Mechani- analysis (Boonyatikarn, 1982: Sullivan and Nozaki, 1984; Les-
cal Engineers for publication in the ASME JounNa.l op Solen ENencv ENct-
NEERINc.Manuscript received by the ASME Solar Energy Division, June 1997;
lie et al.. 1986; Mazzucchi, 1986; Haberl and Claridge, 1987:
tinal revision, Apr. 1998. Associate Technical Editor: G. Vliet MacDonald, 1988; and Abushakra et al.. 1995). Boonyatikarn

'120 177
Journal of Solar Energy Engineering Copyright O 1998 by ASME A U GU S T ' 1998,V ol. |
(1982) used MLR model to analyze energy use of 50 commer- large commercial buildings: 2.t applying rhe MLR moclels to
cial buildings in Michigan. The MLR model using 10 indepen- severallarge commercial buildings; and 3) selectionof suitable
dent variables (system type, refrigeration type, fuel type, num- time resolution for regression models.
ber of hours equipment was used, exhaust air, supply air, cool-
ing degree-days, percent opaque surface, average shading in
2 Methodology of MLR Model Development
winter, and average shading in summer) explained 93 percent
of the variation in the energy consumption. The development of regression moders is often based on both
Sullivan and Nozaki (1984) used the MLR approach to ana- theory and experience. In this section, the theoretical basis of
lyzethe effects of various fenestration parameterson the heating MLR model developmenris presenred.To simplify the analysis
and cooling requirements of commercial buildings. The input the buildings are assumed to be conditioned 24 hours u duy;
databasefor the MLR analysis was created by a series of simula- therefore, the thermal storage effect is not significant. For details
tions using the DOE-2.1B energy simulation program. Leslie on the functional basis of thermal energy consumption, refer
et al. (1986) used MLR models with heating degree-days, pro- to Katipamula et al. (1994), Reddy er al. (1995), ind Knebel
duction levels, and labor forces levels to model the monthlv (1983).
energy use for a military base. Mazzucchi (1986) applied MLR
2.1 Cooling Energy Consumption With DDCV Systems.
models with 4 and customer count to model energy use in
In a building with a DDCV system, the airflow rate is constant
restaurants. Haberl and Claridge (1987) used a daily MLR
and the comfort condition of each zone is met by mixing the
model to predict the energy consumption at a recreation center.
hot and cold air streams. Therefore, the energy use of a building
Abushakra et al. (1995) used a MLR model to model the electric
with a DDcv system is always greater than rhe building loadi
demand in a large commercial building. The MLR model used
(including ventilation loads) (Reddy er al., r995). In a multizone
ambient conditions (f", wind speed and direction, barometric
building, it is not unrealistic to have one zone calling for heating
pressure, and relative humidity) and electricity demand (chillers,
and another zone concurrently calling for cooring-. Therefore-,
pumps, fans, lights and receptacles).
the physical model should account for simultaneoui heating and
Although the investigators cited above have shown the bene-
cooling.
fits of MLR models, none of them developed the models based
Previous studiesby Knebel (1983), Katipamula and claridge
on engineering principles of the systems used in specific build-
(1993), and Liu and claridge (1995) have shown rhar buildings
ing. Models based on engineering principles capture the physi-
can be physically modeled as a two zone building, one exterior
cal interactions taking place between the HVAC system and the
(perimeter) zone and one interior (core) zone, with adequate
building. BecauseMLR models based on engineering principles
accuracy. Again, to simplify the analysis, both zones are as_
require knowledge of the HVAC system operation and its inter-
sumed to have same s€t point temperature, the total cooling
action with the other building systems, they are more difficult
energy consumption of the building with a DDCV system is
to develop. Another major disadvantage of any MLR model is
given by
the selection of independent variables. For the MLR analysis
to be robust, the variables should be independent of each other; E,: Irh{p(To - Tr) + (U"(7" - T,) * 4,or * 4,.,.") * e,,,,af
however, in reality, most variables used in modeling energy use
are correlated to some extent. -
Katipamula et al. (1994, 1995a, and 1995b) developed MLR :l - w,) (r)
* m,h.(w^
"\?(To - T,)
models of energy use from measured energy data based on
engineering principles. The major conclusions from those stud- The contribution of the individual components of i can be
ies are 1) the CV of the MLR decreasedbetween l0 percent to quantified by studying the functional relaiionship of each of the
66 percent when compared to the CV from a single variable major components of Eq. (1). Most commercial buildings in
model; and 2) models at the monthly time scale had higher R2 hot and humid climates reset the hot deck supply temperature
and lower CV than daily, hourly, and HOD models, but the (7'r') with ro and the cold deck temperature (2.) is a ionstant.
daily models and HOD models proved more accurate at pre- Because of the reset in 2,,. the E, may exhibit a piecewise linear
dicting cooling energy use. This paper summarizes those siud- relationship as a function of To (Katipamula et al., lgg4).
les. Equation (1) can be directly used in the regression analysis
The main objective of the paper is to provide a methodology if measured values of all the variables are avallable. However,
to develop MLR models based on engineering principles and Tn,7,, T^, T, w^, and lrc are seldom measured on a continuous
to highlight the effectiveness of MLR models as baseline models basis; therefore, an equation that is functionally equivalent to
and in detecting deviation in the energy consumption due to - Eq. (1) but with reduced variables is as follows:
major operational changes. The major sections in this paper are
E": q. * 0rT, + grl + p3IT,
l) methodology for developing MLR models based on engi-
neering principles for modeling cooling energy consumption in * jo(w^ - w,) * /sei * goQ"or Q)

- Nomenclature

co : specific heat of air qr,": internal sensible heat gains e: external zone
E: €Dergyuse qsor= total global horizontal solar radia- ft : heating
GJ : gigajoules : 10eJoules tion ln : mixed air
,d : mass flow rate Uo: overall heat transmission coeffi- min : minimum flow for a VAV system
h, : latent heat of vaporization cient o : outdoor dry-bulb
1= indicator variable w : specific humidity of air s: coil surface
I: dry-bulb temperature w. : specific humidity of air leaving / : total
7- : dry-bulb temperature at minimum cooling coil u: ventilation or outdoor air intake
flow condition z: zone
T. : cooling coil leaving air dry-bulb Subscripts
temperature c : cooling
Tr, : heating coil leaving air dry-bulb d = internal zone
temperature dp: autdoor dewpoint temperature

178 | Vol. 120, AUGUST 1998


Transactions of the ASME

h
: a * grTZ + 7rTi, * 1zQiT" * 0+q'orT,i
where d, gt,0z, gzi 00,0r, and P6 are regressioncoefficients
and / is the indicator variable introduced to model the change (7)
when T, > T'" at min. flow
point behavior. The value of 1 is set equal to I for To-greatet
ihan the change point temperature and is equal to zero otherwise
(Daniel et al., f-qgO).If the change point does not exist in the
3 Application of MLR Models
data, then the magnitude of the coefficients B2 and B3 will not
be statisticallY significant. In the previous section, a methodology was presented for
In most laige iommercial buildings, a major portion of the developing empirical models from the fundamental governing
- w,)
latent loads is due to ventilation; therefore, the term (w,, equationsTor cooling energy consumption in commercial build-
- ?.)*, where T7o is^the ings with DDCV oi UOV4V systems. This methodology can
in Eq. (2) can be replacedby (Tq
outdoor air dewpoinf temperature and Z, is the mean surface be adapted to other system typg-s (single-duct constant
temperature of the cooling coil. The term is set equal to zero volume with ieheat, single-duct variable air volume with re-
"uiity
when it is negative, as representedby the superscript "+"' heat), and other end uses (heating and electric energy use).
This is n"c".rary because when 7,1,is lower than I, there is no Relevant equations are presented in Reddy et al' (1995)'
latent cooling load even if the mixed air is saturated' In this section, summary results of modeling the cooling
energy consumption in five large commercial buildings at a
E, : d * 0rT" + gzl + P3IT, + goT\o * gsQ, * FeQ,or (3) dailfiime scale are presented. For detailed discussion on effect
2.2 Cooling Energy Consumption With DDVAV of time resolution on statistical modeling refer to Katipamula
systems. tn a uuitaing with a DDVAV system,.the airflow et al. (1995b). The physical characteristics and operational de-
rate is modulated to meet the comtort condition of each zone. tails oi the five buildings are given in the Appendix. Among
Therefore, the energy consumption closely parallels thebuilding the five buildings there are three buildings with -QpCV and
(EC)
loads (including ventilation loads) (Reddy et al., 1995). The three with DDVAV systems. One of the five buildings
was retrofitted from a DDCV system to a DDVAV system;
total cooling of a two-zone building with a DDVAV
"n".gy
system is given bY therefore, the building has data for both DDCV and DDVAV
system operation. Measured data over one entire year were used
E, : l(U"(T.
- Tr) + 4,or * 4t.,.")* q,.,.al to develop MLR models; the data included To, Too, QsosQi lrrd
E". The hourly values of E , qi and 4solwere summed over the
(T^ - T')
x * rn.h,.(w^ - w,) (4) day to get d;ily values. The independent variab.le.l' T, and
(T, - T,) *"r" averaged over the day to obtain average daily values.
fr'r,
""ftfln
analysis assumes that the regressor variables are inde-
This expression, unlike the one for DDCV, shows a second-
- T.) is a con- pendent of eich other. Multicollinearity betw-eenthe regressor
order reiationship with Z, because the term (7,
- T.) is a function of To (Katipamula et variables results in large uncertainty bounds for the regression
stant and the term (T^
of (T^ - T") will be significant if coefficients, leading to model uncertainty' A rule -of thumb
al.. 1994). The contribution
(Draper and Smith, teat; is that multicollinearity effects may
rhe amount of fresh air intake is high. In a DDVAV system,
U" lmportunt if the simple correlation between two variables is
the mass flow is modulated to meet the zone sensible cooling
largeithan the correlation of one or either variable with a depen-
load; however, there is a minimum flow rate below which there
deit variable. Earlier studies by Wu et al. (1992), Reddy and
is no modulation. Therefore, when the flow reaches the mini-
claridge (1994), and Katipamula et al. (1994) showed that col-
mum flow, the system essentially becomes a constant volume
lineariiy is not significanfbetwe"n To, fro and q; at a daily and
system and the energy consumption shows a change in slope.
hourly iime scale, but can be significant between 7o and q,or'
Again, due to lack of some measured values (such as occupancy,
In most commercial buildings, the cold deck supply tempera-
inftrnal gains, erc.) a functional form equivalent t9 Eq. (4) is
ture is held constant, at 12.8oC,throughout the year. Therefore,
needed fir regression. Also, if we assume that the outdoor
the average surface temperature of the coil, 4, for all buildings
air intake is small (less than 20 percent of the total rated air-
- T,) will be close to unity' analyzedlexcept EC wiih DDCV) is assumed to be 12.8"C. In
flow), then the term (I- - T,)l(7,
of Eq. (4) in terrns of measured the bC, a contlol problem (Katipamula, and Claridge' 199?
The functional equivalence
resulted in mean i values varying between 10'C and 21"C.
variables is
Therefore, for the EC with the DDCV system, the average coil
E, : d * 0rT, + 0rl + P3IT' + gqfio + 7sQ, * 1oQ'or (5) surface temperature was assumed to be 15.6"C'

The above equation is similar to Eq. (3) for the DDCV system. 3.1 DDCV Modeling. Daily cooling energy use in three
However. if itre outdoor air intake is high then the functional (3)' The
buitdings with DDCV systems was modeled using Eq'
equivalent of Eq. (4) is (Katipamula et al', 1994): ,u,,'rnufu of the "stepwiie" regression results is shown in Table
l. In a siepwise regression, the contribution of each individual
E, : d * grT. + 7zTXo* ?zQi * ?cQ'ori
variable to the model can be assessedby comparing the partial
when T, = T'" at min. flow (6) R2 values. A partial R2 of 87.1 percent for I, (Table l) means

Table 1 Summary of results for DDCV MLR models

EC WEL MSB
Partial .R' Model .R' Partial .R' Model .R' Partial Ii" Model f{'

Variable (To) (%) (To) (To) (%) (To)


To 87.1 87.1 6.6 6.6 4.5 4.5
ril 4.0 91.1 90.3 96.9 88.6 93.1
0.8 91.9 0.0 96.9 0.9 94.0
Qi
0.0 91.9 0.0 96.9 0.1 94.1
I
0.0 91.9 0.0 96.9 0.9 95.0
I *To
0.0 96.9 0.0 95.0
Qsol 0.0 91.9

A U GU S T 1998' V o l' 120 / 179


Journal of Solar Energy Engineering
-EC It
-.....wEL IE
l8 -_ MSB 16
l6

l4
l4
t2

s"
vlo
t2

10
S"
-lo l0

E OE
u8 6
6
6
4

0 0 gr ltro I
o ---;---a; qr r.To r qd To t*'
Addition of Independent Variables to the Model
Addition of IndependentYariablesto the Model
variableswith DDVAV
Fig.2 changein cv with additionof independent
with DDCV
Fig. 1 Ghange in cv with addition of independent variables system
sYstems

DDCV models, all three DDVAV models show a presence


that the outdoordry-bulb temperatureexplains87.1 percentof of a change point in the data (both 1 and IxTo ate statistically
the variation in the cooling energyuse. significant).
For the EC building, T,lxplains most of the variationin the "In
g"n"rul, the cooling energy consumption of a building with
cooling energyuse followed by fio and internal gaini' At EC'
a ndVRV system is pioportional to the thermal loads on the
the hoideckilmperature is constantand the ratio of the glazed building. tn i VRV system, the air flow rate is modulated to
surfaceto the totil surfaceis small (about 22percent);therefore, meet th-e comfort conditions in the zone' while the airflow is
there is no changepoint in the model, and the contributionof constant in the DDCV system. The modulation in the airflow
the solar variablJto the model is statisticallyinsignificant(i.e', reduces simultaneous heating and coolingi thus, the cooling
partial R2 : 0).
'- energy consumption is a stronger function of the thermal loads
A .nuior portion of the conditionedspacein both.WEL and tti" building. Therefore, the independent variables TXoand q,
MSB UuitOlngs is madeup of laboratories;therefore,the outdoor on
-rrigtr is much variation in cooling energy consumption
air intake is (>70 percent).unlike the EC building, the explain twice
wiih the DDVAV system as compared to the DDCV system.
Do explainr *&" variati-onin the cooling energyconsumption In case of DDVAV, the decrease in CV with the addition of
tdan i, in both WEL and MSB buildings for 1fr9 following
independent variables is greater than DDCV models (Fig. 2).
."u.onJ' 1) outdoorair intake is over 70 percent(laboratories),
2) thereis more day-to-dayvariation of frpthT &:jytd 3) there
is a correlationbetweenfio andTo.Also, in the WEL building, 4 Effect of Time Resolution on Statistical
Modeling
does not show a change point because the reset in the data are available,an
the data when hourlyor ls-minutemonitored
hot deck temperatureis not large. However, the data from the issue that arises is what time resolution to adopt for developing
MSB building showsthe presenceof a changepoint' . iegression models (Katipamula et al., 1995b). The operational
The generaitrendsac.ois the threebuildings are similar, with 'hout p#ameters (such as ?:, T;,, outdoor air intake, Qi)change from
T" or fioexplaining most of the variation and the other variables to hour but are effectively constant on a monthly or even
onfy .oit ibuting t'iigtttty. The contributionfor solar radiationis a daily basis. Therefore, monthly and daily energy consumption
statisticallyinsignificant in all three buildings for two reasons: when compared to the hourly consumption show much less
it rh. r1nuttfraJtion (lessthan 20 percent)of externalsurfaceis scatter. Diimond and Hunn (1981) compared simulated energy
giii"g, and2) to a lesserextent,the correlationbetween7" and consumption to the measured data and found that on a monthly
with the addition time scale the deviations were higher than on an annual time
[*, ry"anAonet al., 1991).The decreasein CV
variables to the model is shown in Fig' 1'
oi'ina"p.ndent scale. They concluded that some effects average out over the
reducing the deviations.
3.2 DDVAV Modeling. Daily cooling energy use in year, -
with DDvAV systems was modeled using One methol to account for the hour-to-hour variation in the
three buildings-summary by the daily operational
Eq- fSl The of the stepwiseregressionresults is internal gains (which are influenced
model schedulelf the building) is to sort the hourly data into several
stro*n'in Table 2. Ali variableswere selectedby the giouping would be first to sort the data
T, explains more variations in the subgroups. A logical
*iit ,tt" exceptionof g,or.
intJweekauys und weekends and then sort these into 24 hourly
c oolingene rg y c o n s u mp ti o n th a n a n y o thervari abl e.U nl i ke

Table 2 Summary of results for DDVAV MLR models


--pc BUR WIN
Model B' Partial fd" Model J(- ranlar f[
Partial It'
Variable (%\ (To) (To) (vo) (To) (To)
83.2 83.2 79.1 79.1 84.1 84.1
To
n1+ 7.2 90.4 8.1 87.2 D.O 89.6
tdo

4.L 94.5 2.3 89.5 0.6 90.2


Q;
1.1 95.6 2.3 91.8 0.2 90.4
I
I *To 0.8 96.4 0.8 92.6 0.9 91.3
0.0 96.4 0.0 92.6 0.0 91.3
Qsot

Transactions of the ASME


18OI Vol. 120, AUGUST 1998
20
- Monthly
l8
""' Daily
--- Hourly
l6
HOD
l4

S"
-lo E"
ur ur0
6

0
To Top* gi I*To I gsol To Top* gi I*To I gsol

(f)
(c)

20
Monthly It
Daily
Hourly l6
HOD
l4

E" Stt
-lo

ur0 ur
5

2
0

To Tap* gi I*To I 9sol To Tap* ft I*To I gsol

(e)

nl
- Monthly I
tr]
""' Daily
--- Hourly l6
t2
HOD
l4

xQ
i-'
l0

g
s"
-lo

u6 ur
6
4
4
2
0

To Top* gi I*To I gsol To Top* ei I*To I gsol


(d)
(a)

(b) WEL DDCV, (c) MSB DDCV'


Fig. 3 Ghange in CV with addition of independent variabtes to the model. (a) EC DDCV,
(df EC DDVAV, (e) BUR DDVAV and (4 wlN DDVAV

(lata sub-groups each. Monthly, daily, hourly and hour-of-day mula et al., 1995b).The general trends are similar to the results
rHOD) cooling energy use in three buildings (EC, MSB, and presented in the previous section. Also, the trends fbr models
\\'EL) with a DDCV system was modeled using Eq. ( I ) (Katipa- developed for the three buildings with DDVAV system (EC.

Journal of Solar Energy Engineering AUGUST 1998, Vol. 120 | 181


models
Table 3 Comparison of the predictive ability of different

--Todeling
Period
rr^-+iGnof inn I Prediction Indices MonthlY Daiiy Hourly HOD
site 'vo 4.8 5.8 5.1
'92 Jatr. - Lrec. CV 8.4
MSB Jan. - Dec. -2.2 ,0.6 -0.7 -0.9
(DDCV)
MBE
-Jan. '93 9.1 9.1
'92 - Dec. CV 9.9 I.O
BUR fan. - Dec. -8.2 -6.5 -6.4 -I.l

(vAV) MBE
- uec. 'YJ CV 15.3 L5.2 t5.7 ID.O
WIN F-Pec.'92 Jan.
-t2.6 -12.0 -10.7 - 1 1 . 8
(vAV) MBE

h"#*ii"rT5;,;:ff ji:"''#[*ii
ffi :ffi ;ffi;,+:-#"tr"#.ii'i;;fl:f
iit;ft' withonlv ls93'theuairfldoworate:il*:lliti.Y')tJleautv
r'i!r'., In60"tn: andlower-cVtt'-'otr'"' modeli' *tv tnevne
righ and
*;ilm:';;'ru.;;;e;ii"" ri'lher
i:1"+::':J*:'"'#ll'j;:;*"fl,k;::t6yT:,ffi1'Jiff
flt**"Xl"Li"J'THlilfi$.,"'^ffiF?'::l'ifl";
5 concrusions
;;#l,l*ti:;,lt;fr;TflS^""fi:'1""'$l'.1fJt#i
tt"k,l',il?'itl',llT[J1""#'?kmut
#J,p.'jn#t*;i\B,i-l*trr[-f$i
both-had.lower
ill',3]l,.a more wirhapiecewise
accurarery linear
muliiple
i;i:;*:*llll*:';lr":','".,";qi::il'ilx'*
efj*'.l5*9"$l*"ru.''t&lTiJ'il1'lll'ili interactions
ofrhi ohvsical rn
prace
takine
"f,ffi;1f"il."flr;t'r"i1*xil""fi; cv thandailv
lower
riiid'iil;l,ilr.,rl*:'r[k#,i11,"#
mlJr;."iii :',"','"n;;x;"::"11""'"x1,iH:"$f;i'"BB
use;a" rxi;r,l xin::':mm:'T:;lill';iiill'-Tf
en€rgv
:ir.utllll:;x*:":ilni"- rharroo,ins
l.i,lt"l.r":1;';*t*;r*l;'m6*;31ffi1d: i**p"t+i+***-**'1il"Ti1"tr
;lsJ1?H::::1":'il:t=.-[ll"#il'o;*f,, .#i:]: ""1 rhan
formore the
e0percen,.or '-.oaccounted
r. and

mav
il::il il;,h,;;;de,s no, ' $L:ffi$tr5r-;a1q1,'1
H,H.l*#nkfltl#+i.":,pifFilrL#!fi
i"T*li j'ffiiiill"*llilI -,'*;u,i.nio.m,r,
consumption accurately. Also, on fi;bj;lhifffi:iffi:',f,: A
, l3J,:.1,i{:{J""'Hi'*iif*.r
frri';';{1"ili1+$,","?,i}:Hlf""'.1}xl':Lt"#fi
#if;fu{iny;yl,m;tJ:,9:,ffiffT#,#i,;::'#: ' Xihdtg"tsf,"el"_.**.*,:*
nTj,,}".y
""T3'"ll"li*.0,*n,'",:.:"p,i-orli,J":r,f:rffiiI',i3;$ ru,ure
predic,ing f;#f,tlg*;.*:i;j;ffj:J",
ent time scales.the modelsidenti use(Katipamula ut ' 'nnll'au
wereusedto predict
' "n"'nu
"ooting"n"tgy-"ottt"totbrr
"t
f9:-:.-:"::11 -
,n- thehourly
:*i:ll*lt*:i*l."}"T;fii'lrffllffitli;.ff"[fi H:P"'H:::lil!,li'J5if,::+11!!lngef
.l
r*""fi;*'*{d;'t'1itt}r$fi.iffi". $1Tfi'iiqffigg*yr
II *T'J3;"3i*,1'"*""t1,'.?3,f";;;;;iu"",-,(Mse)on
*tTi'l$ll"t
i#:iiCiy|*"hh:[.";.1;'#""",Ti1
oneadditional
have
#';'it'u. oo,,u,nr. vearor :;il"f i;'ffiiliv-,noa'ii *u' u"*"'n l-2p"'""nt

Itl; i'*,,Hil*l*,m:'';lfrti{d',1,#'$ffi
ii3ii.*riun.
:1','rl{mflx*lf#jittt**'"
""4
ij*g-r"*':l"i:l;
Th' dailv.models
wN uuitalngr. !l',
b:::

llrll"l;3liJ,'illllt;fifliif!]1ilj rabre
hisherthanthatof theDDCVMLF
theadvantase
4 summarizes ofthe
anddisadvantages

ffi,l""Pl"t'3;li;;.i?'i:"#fi',i:i::t'6'*x"$;HtXxf effort
11":"f"T3'$""" 48
it involvesdeveloping
because
itr" .o_ntnty ,"qoii"" tt" ,ri*i-um
air. Because7,, andfi,-" i'igiiv "oil"iut"o'ui
f,""iiiip*aii,"a"*r',",r'Jii#fiii':*"1"H"**til: f,i'*".",1i,1,?"1'il,tfiiq;fi11:.: lifill,"i:ii;
[*l**t""'l*tff"Yi*:'S#i:".fJ*':];':fx ilTfi,",t"lX.*::.l*U*lf::"ffiff-#'n
of the ASME
Transactions
1g2t vol.12o, AUGUST1998
Table 4 Advantage and disadvantages of different models

Monthly Daily Hourly HOD


Modeling
Effort Minimum Minimum Moderate Difficult
Metering and
Monitoring Noner Required Required Required
Data Needed
for Robust 12 months $6 months &6 months &6 months
Modeling or more or more or more or more
Applicability
to Savings [n some In most AU All
Measurements cases cases cases cases
Prediction
Uncertainty High Low Moderate Low
o&M
Opportunities Most
Detection Limited Possible Appropriate appropriate
Dynamic
Control No Possible Yes Best

tion. An earlier study by Rachlin et al. (1986) suggestedthat Draper, N., and Smith, H., 1981, Applied Regression Analysis,2nd ed., John
Wiley and Sons. New York, NY.
eight months of monthly data are sufficient to model residential Fels, M. (Ed), 1986, "Special Issue Devoted to Measuring Energy Savings,
or small commercial energy consumption. However, to model The Princeton Scorekeeping Method (PRISM)," Energr* and Buildings, Vol. 9,
energy use in large commercial buildings on a monthly time No. I and 2.
scale requires 12 months or more of data. To accurately predict Haberl J. S., and Claridge, D. 8., 1987, "An Expert System for Building Energy
Consumption Analysis: Prototype Results," ASHPl/.E Transactions, Vol. 93. Part
annual energy use using daily regression models, at least three
I, pp. 979-998.
to six months of data are required (Kissock et al., 1993; Katipa- Kaplan, M., Jones, B., and Jansen, H., 1992, "DOE2.lC Model Calibration
mula et al., 1995).No analysishas yet been done to determine With Monitored End-Use Data," The ACEEE 1992 Summer Study on EnergT'
how much data are required for hourly or HOD regression Efficiency in Buildings, pp. l0.ll5-10.125.
models. Because the daily models require three to six months Katipamula, S., Reddy, T. A., and Claridge, D. E., 1995a, "Bias in Predicting
Annual Energy Use in Commercial Building With Regression Models Developed
of data. this period may be valid for hourly or HOD models as From Short Data Sets," Proceedings of the 1995 ASMilJSES/JSES International
well. Solar Energy Conference, Maui, Hawaii, pp. 99- I10.
Katipamula, S., Reddy, T. A., and Claridge, D. E.. 1995b, "Effect of Time
Resolution on Statistical Modeling of Cooling Energy Use in Large Commercial
6 Acknowledgments Buildings," ASHRAE Transactions, Vol. l0l, Pall.2.
Katipamula, S., Reddy, T. A., and Claridge, D.8., 1994, "Development and
This study was funded by ( I ) Pacific Northwest National Application of Regression Models to Predict Cooling Energy Consumption in
I-aboratory which is operated by Battelle Memorial Institute Large Commercial Buildings," Proceedings of the 1994 ASMAJSES/JSES Inter-
tbr the U.S. Department of Energy under Contract DE-AC06- national Solar Energy Conference, San Francisco, Meuch 27 -3O, pp. 307 -322.
76RLO 1830. and (2) by the Texas State Energy Conservation Katipamula, S., and Claridge, D.8., 1993, "Use of Simplified System Models
to Measure Retrofit Energy Savings," ASME JounNx- op Solnn ENEncv Excr-
Of'fice of the Intergovernmental Division of the General Ser-
NEERTNc, Vol. I16, No. 2, May, pp. 57-68.
vices Commission (State Agencies Program) as part of the Katipamula, S., and Claridge, D. E., 1992, "Monitored Air Handler Perfor-
LoanSTAR monitoring and Analvsis Program. mance and Comparison With A Simplified System Model." ASHP,/^E Transac-
rions, Vol. 98, Part 2. pp. 341-351.
Kissock, J. K., Haberl, J. S., Claridge, D. 8., and Reddy, T. A., 1992. "Measur-
7 References ing Retrofit Savings for the Texas LoanSTAR Program: Preliminary Methodology .
and Results," Proceedings of the ASME/JSES/KSES Internationul Solar Energy
Abushakra. B.. Zmeureanu. R., and Fazio. P., 1995, "Evaluation of Conven-
Conference, Maui, Hawaii, pp. 299-308.
tronal Inverse lvlodels For Predicting Electricity Demand of A Large Institutional
tluilding." Proceedings of the Second International Conftrence on lruloor Air Kissock, J. K., Reddy, T. A., Fletcher, D., and Claridge, D. E., 1993. "The
Effect of Short Data Periods on The Annual Prediction Accuracy of Temperatures-
Qttttlitt, Ventilation. and Energt Consen'utiotr in Buildings, May 9- 12, Montreal.
C a n a d a .p p . 5 5 9 - 5 6 6 . Dependent Regression Models of Commercial Buildings Energy Use." Proceed-
Boonyatikarn. S., 1982, "lmpact of Building Envelopes on Energy Consump- ings of the 1993 ASME/ASES/SED International Solar Energ;" Conference, Wash-
titrt and Energy Design Guidelines." Pntceedings of the ASHRAE/DOE ConJer- ington, D.C., April, pp.455-463.
(nt ( ()tt Thermal Pe(ornnnce o.f thc Exterior Ent'elope of Buildings II, pp.469. Knebel, D. E., 1983, "Simplified Energy Analysis Using the Modified Bin
l]ronson, D.. Hinchey. S.. Haberl. J. S., O'Neal. D. L.. and Claridge. D. E.. Method." American Society of Heating, Refrigerating. and Air-Conditioning En-
1991. "A Procedure tbr Calibrating the DOE-2 Simulation Program to Non- gineers. Inc., Atlanta, GA.
\\'cather Dependent Measured Loads," ASHRAE Tnuisttcttont Vol. 98. Part l, Leslie. N. P., Aveta, G. A., and Sliwinski. B. J.. 1986, "Regression Based
pp.636-652. Process Energy Analysis System," ASHRAE Transactions, Vol. 92, Part lA. pp.
(-opelandC.. 1983, "Retrofit Energy Studies Using the DOE-2 Computer Simu- 93-tOz.
lrttion Program." ASHRAE Trunsactions. Vol. 89, Part lA, pp. 3.11-351. Liu, M., and Claridge, D. E., 1995, "Application of Calibrated HVAC System
Daniet. C.. and Wood, F. S.. with assistanceof Gorman. J. M., 1980. Fitting Models to Identiff Component Malfunctions and to Optimize Operation and Control
I'.tluttriuts to Datu: Computer Arrailsls of Mult$actor Data,2nd ed., John Wiley Schedules." Proceedings of the 1995 ASMAJSMUJSES htenutional Solar Energt
runrlSons, New York. NY. Conference, Vol. I, Maui, Hawaii, March 19-24, 1995, pp. 209-217.
Dhar. A.. Reddy, T. A.. and Claridge. D. E., 1994, "lmproved Fourier Series MacDonald, M., 1988, "Power Signatures as Characteristicsof Commercial
'\pproach to NilodelingHourly Energy Use in Commercial Buildin g," Prcceedirtgs and Related Buildings," Fifth Annual Svmpositun on Improving Building Ettergv
,tl tlre 1994 AslvlE/JSES/JSES Internttrionul Solur Energy Conference, San Fran- Eficiencv in Hot and Humid Climates, Energy Systems Laboratory, Texas A&Nl
c i s c o .M a r c h ? 7 - 3 O , p p . 4 5 5 - 4 6 8 . University, College Station, Texas. pp. 80-87.
D i a m o n d . S . C . , a n d H u n n . B . D . , 1 9 8l . " C o m p a r i s o n o f D O E - 2 C o n r p u t e r Mazzucchi, R. P., 1986, "The Project ot RestaurantEnergy Perlormance End-
I)rogranrSimulations to Metered Data For Seven Comrnercial Buildings." ASH- Use Monitoring and Analysis." ASHRAE Trattsttt'tiotts,Vol. 92. Pan 28. pp.
l l . \ l i T r u n n t - t i o r r s ,V o l . 8 7 . P a r t l . p p . 1 2 2 2 - 1 2 3l . 328- 349.

Journal of Solar Energy Engineering A U GU S T 1998. V o l. 120 | 183


R a c h l i n . J . . F e l s . i \ ' 1 . .a n d S o c o l o u . R . . l 9 t i 6 . " T h e S t a b i l i t y o f P R I S M E s t i - S c h r o c k . D . W . , a n d C l a r i d g c . I ) . E . . l 9 t t 9 . " l ' r c d i c t i n g [ i n e r g v U s ; ' t g ci r t r t
mates." Energt and Buildings. Vol. 9. No. I and 2. Superrrrarket."Pnx'ceding.sol'tlrc Si.tth Atrttttul.5r'lt7ro.rittlt ttrt ltrtprttring Builtl-
Reddy. T. A.. Katipamula. S.. Kissock J. S.. and Claridge, D. E., 1995. "The lrrg Sls/t'nr.rin Hot and Humid Clirttate,s,Dallas. Texas. October 3-'1. 1989. pp.
Functional Basis of Steady-StateThermal Energy Use in Air-Side HVAC Equip- Ft9-F21.
ment," ASME JounNnl oF SoLAR ENencv ENGINEenI^-G. Vol. ll7, No. I' pp. Seem. J. E.. and Braun, J. E.. 199 l. "Adaptive Methods lbr Real-Time Fore-
3l -39. February.. casting of Building Electric Demand," ASHRAE Transactiotts,Vol. 97. Part l,
Reddy, T.A., and Claridge. D.E., 1994, "Using Synthetic Data to Evaluate pp.7lo-721.
Multiple Regressionand Principal Component Analysis for Statistical Models of Sullivan. R. T., and Nozaki. S. A., 1984. "Multiple Regression Techniques
Daily Energy Consumption." Energ,t'and Buildings, Vol. 21, pp. 35-44. Applied to Fenestration Effects On Commercial Building Energy Performance,"
Ruch, D., and Claridge, D. E.. 1992, "A Four Parameter Change-Point ASHRAE Transactions,Vol. 90. Part lA, pp. I l6- 123.
Model for Predicting Energy Consumption in Commercial Buildings"' Vandon, M., Kreider, J. S., and Norford. L. K.. 1991, "Improvement of the
A S M E J o u n N n l o F S o L A R E N e n c v E N c t N e E n t N cV , ol. l14, No.2,pp.77- Solar Calculations in the Modified Bin Method." ASHRAE Transacriotts, Yol-
8.1. Februarv. 97. Part 2.

APPENDIX

Table A Building characteristics (all buildings are institutional)

Supply Operation
Temp.(oC) People/
T"lMax. Tn HVAC (h/dav)

15.6/40.6

L2124

12124

L2.8120.4

10,310

1U I V ol. 120, A U GU ST 1 9 9 8 Transactions of the ASME

S-ar putea să vă placă și