Sunteți pe pagina 1din 10

20-11-2018

Phasor diagram for a loaded transformer (with losses and no • A single-phase transformer with a ratio of 440/110-V takes a no-
leakage ,R-L Load)
load current of 5A at 0.2 power factor lagging. If the secondary
supplies a current of 120 A at a p.f. of 0.8 lagging, estimate the
𝐼1 current taken by the primary.
𝑉1 , 𝐸1
𝐼′2 Solution.
Φ1 Cos2 =0.8, 2 = 36°54´
~ LO
AD
Cos0 = 0.2 0 = 78°30´
Now K = 𝑉2 /𝑉1 = 110/440 = 1/4
Φ0 𝐼0
 𝐼2 ´ = K𝐼2 =120×1/4=30 A
Φ
𝐼0 = 5 A
• V2=E2 and V1=E1
𝐼2 Φ2 Angle between 𝐼0 𝑎𝑛𝑑 𝐼2 ´ = 78°30´- 36°54´= 41°36´
• Since N1=N2
𝑰𝟏 = (𝟓𝟐 + 𝟑𝟎𝟐 + 𝟐 × 𝟓 × 𝟑𝟎 × 𝒄𝒐𝒔41°36´ = 34.45 A
E 1 = E2
𝑉2 , 𝐸2

20-11-2018 Transformers by Dr. Paresh Kale 36 20-11-2018 Transformers by Dr. Paresh Kale 37

Why Transformer Rating in kVA ?

I hope you remember • Cu loss of a transformer depends on current


Power Triangle
• Iron loss depends on voltage.

• Hence, total transformer loss depends on volt-ampere (VA) and


not on phase angle between voltage and current

• i.e. it is independent of load power factor.


Disclaimer
• Thus, Rating of transformers is in kVA and not in kW
I neither drink nor support
drinking alcohol. Eating
Lays is long gone then.

20-11-2018 Transformers by Dr. Paresh Kale 42 20-11-2018 Transformers by Dr. Paresh Kale 43

• A 25-kVA transformer has 500 turns on the primary • A 5 kVA single-phase transformer has a turns ratio of 10:1 and is fed
and 50 turns on the secondary winding. The primary is from a 2.5 kV supply. Neglecting losses, determine
connected to 3000-V, 50-Hz supply. • (a) the full-load secondary current,
• (b) the minimum load resistance which can be connected across the
• Find the full-load primary and secondary currents, the secondary winding to give full load kVA,
secondary e.m.f. and the maximum flux in the core. • (c) the primary current at full load kVA.
• Neglect leakage drops and no-load primary current.

• Ans: (a) 𝑁1/𝑁2 = 10/1 and 𝑉1 = 2500 V.


• K = N2/N1 = 50/500 = 1/10 𝑁 𝑉
• Now, full-load I1 = 25,000/3000 = 8.33 A. Since ( 𝑁1 ) = ( 𝑉1 ), secondary voltage 𝑉2 = 250 V
2 2
• At FL, I2 = I1/K = 10 × 8.33 = 83.3 A
The transformer rating in volt –amperes = 𝑉2 𝐼2 (at FL) i.e. 5000 = 250𝐼2
• E2 = K E1 = 3000 × 1/10 =300 V
Hence full load secondary current
• E1 = 4.44 f N1Φm; 3000 = 4.44 × 50 × 500 × Φm
𝐼2 = ( 5000/250) = 20 A
• ∴ Φm = 27 mWb
20-11-2018 Transformers by Dr. Paresh Kale 44 20-11-2018 Transformers by Dr. Paresh Kale 45

1
20-11-2018

A 2,200/200-V transformer draws a no-load primary current


of 0.6 A and absorbs 400 watts. Find the magnetising and
(b) Minimum value of load resistance, iron loss currents.

𝑉2 250
𝑅𝐿 = ( )=( ), = 12.5 Ω. • Iron-loss current
𝐼2 20
• = no-load input in watts/ primary voltage
• = 400 /2, 200
• = =0.182 A
𝑁1 𝐼2
(c) ( )=( ) from which primary current
𝑁2 𝐼1
𝐼02 =𝐼𝑤
2
+ 𝐼𝜇2
𝑁1 1
𝐼1 =𝐼2 ( ) = 20 ( )=2A
𝑁2 10 𝐼𝜇 = 0. 62 - 0182)2 = 0.572 𝐴

20-11-2018 Transformers by Dr. Paresh Kale 46 20-11-2018 Transformers by Dr. Paresh Kale 47

• A single-phase transformer has 1000 turns on the primary and


A 2,200/250-V transformer takes 0.5 A at a p.f. of 0.3 on open 200 turns on the secondary.
circuit. Find magnetising and working components of no-load • The no load current is 3 amp. at a p.f. of 0.2 lagging.
primary current. • Calculate the primary current and power-factor when the
secondary current is 280 Amp at a p.f. of 0.80 lagging.
• I0 = 0.5 A, cos φ0 = 0.3
• V2 is taken as reference. cos−1(0.80) = 36.87°
• ∴ Iw = I0 cos φ0 = 0.5 × 0.3 = 0.15 A • I2 = 280 ∠−36.87º amp
• I’2 = (280/5) ∠−36.87º amp

• φ0 = cos−1 0.20 = 78.5°, sin φ0 = 0.98

• I1 = I0 + I’2
• I1 = 3(0.20 − j 0.98) + 56 (0.80 − j 0.60)
• I1 = 45.4 − j 36.54 = 58.3 ∠-38.86º
20-11-2018 Transformers by Dr. Paresh Kale 48 20-11-2018 Transformers by Dr. Paresh Kale 49

Transformer with Winding Resistance, Transformer with Winding Resistance,


No Magnetic Leakage No Magnetic Leakage
• Due to some resistance of the primary and secondary windings,
there is some voltage drop in two windings.

• The secondary terminal voltage V2 is vectorially less than the


secondary induced e.m.f. E2 by an amount I2 R2
• where R2 is the resistance of the secondary winding.
• Hence, V2 is equal to the vector difference of E2 and resistive voltage
drop I2 R2
• ∴ V2 = E2 − I2 R2 ...vector difference

• Similarly, primary induced e.m.f. E1 is equal to the vector


difference of V1 and I1 R1 where R1 is the resistance of the
primary winding.
• E1 = V1 − I1 R1

20-11-2018 Transformers by Dr. Paresh Kale 50 20-11-2018 Transformers by Dr. Paresh Kale 51

2
20-11-2018

Magnetic leakage Magnetic leakage


• At no load and light loads, the primary and secondary ampere-turns are
• Assumption: all the flux linked with small, hence leakage fluxes are negligible.
primary winding also links the secondary
winding.
• But when load is increased, both primary and secondary windings carry
huge currents. Hence, large m.m.f.s are set up which, while acting on
• But, in practice, it is impossible to realize leakage paths, increase the leakage flux.

• i.e.ΦL1 completes its magnetic circuit by • A transformer with magnetic leakage is equivalent to an ideal
passing through air rather than around the transformer with inductive coils connected in both primary and
core
secondary circuits

• leakage flux is produced when the m.m.f. due to N0I1 acts along the • The terms X1 and X2 are known as primary and secondary leakage
leakage paths. Hence, this flux is known as primary leakage flux reactance resp.

• It is proportional to the primary ampere-turns alone because the


secondary turns do not link the magnetic circuit of ΦL1

• The flux ΦL1 is in time phase with I1. It induces an e.m.f. EL1 in
primary but not in secondary.

20-11-2018 Transformers by Dr. Paresh Kale 52 20-11-2018 Transformers by Dr. Paresh Kale 53

Transformer with Resistance and Leakage


Important points regarding magnetic flux
Reactance
• The leakage flux links one or the other winding but not both,
hence it in no way contributes to the transfer of energy from
the primary to the secondary winding.

• The primary voltage V1 will have to supply reactive drop I1X1


in addition to I1R1. Similarly E2 will have to supply I2 R2 and I2
X2.

• In an actual transformer, the primary and secondary windings


are not placed on separate legs or limbs, as it causes large
primary and secondary leakage fluxes would result.

• These leakage fluxes are minimised by sectionalizing and


interleaving the primary and secondary windings

20-11-2018 Transformers by Dr. Paresh Kale 54 20-11-2018 Transformers by Dr. Paresh Kale 56

Review Transformer with Resistance and Leakage Reactance

𝑉1 , 𝐸1 𝑉1 , 𝐸1 𝑉1 , 𝐸1 𝐼1
𝑉1 , 𝐸1
𝐼′2
𝐼′2 𝐼1 𝐼𝑤 𝐼0
Φ1
Φ0

Φ0 𝐼0
𝐼0 Φ 𝐼0 Φ 𝐼𝑚 Φ Φ • 𝑍1 = 𝑅21 + 𝑋 21
𝐼2 Φ2 • 𝑍2 = 𝑅2 2 + 𝑋 2 2
𝐼2

𝐸2 𝐸2 𝐸2 All vectorial additions


𝑉2 , 𝐸2 • 𝑉1 = 𝐸1 + 𝐼1 𝑅1 + 𝑗 𝑋1 = 𝐸1 + 𝐼1 𝑍1

• 𝐸2 = 𝑉2 + 𝐼2 𝑅2 + 𝑗 𝑋2 = 𝑉2 + 𝐼2 𝑍2

20-11-2018 Transformers by Dr. Paresh Kale 57 20-11-2018 Transformers by Dr. Paresh Kale 58

3
20-11-2018

Equivalent parameters Equivalent parameters


𝑹𝟐
𝑹𝒆 = 𝑹𝟎𝟏 = 𝑹𝟏 + 𝑹′𝟐 = 𝑹𝟏 +
𝑲𝟐

𝑹𝒆 = 𝑹𝟎𝟐 = 𝑹𝟐 + 𝑹′𝟏 = 𝑹𝟐 + 𝑲𝟐 𝑹𝟏

• R01 and R02 = Equivalent effective resistance of the transformer


as referred to primary and secondary resp.
Referred to primary Referred to Secondary
𝑋2
𝑋𝑒 = 𝑋01 = 𝑋1 + 𝑋′2 = 𝑋1 + 2
𝐾
𝑍𝑒 = 𝑍01 = 𝑅2 01 + 𝑋 2 01
𝑋02 = 𝑋2 + 𝑋′1 = 𝑋2 + 𝐾 2 𝑋1

• X01 and X02 = Equivalent effective reactance of the transformer 𝑍02 = 𝑅2 02 + 𝑋 2 02


as referred to primary and secondary resp.
20-11-2018 Transformers by Dr. Paresh Kale 59 20-11-2018 Transformers by Dr. Paresh Kale 60

Important to remember

• (a) when shifting any primary resistance / reactance /


impedance to the secondary,
multiply it by K2 i.e. (transformation ratio)2

• (b) when shifting secondary resistance / reactance /


impedance to the primary, EQUIVALENT CIRCUIT AND
divide it by K2
PERFORMANCE OF T/F
• (c) however, when shifting any voltage from one
winding to another only K is used.

20-11-2018 Transformers by Dr. Paresh Kale 63 20-11-2018 Transformers by Dr. Paresh Kale 67

Equivalent Circuit Exact equivalent circuit

• R0 = E1/Iw • To make transformer calculations simpler, it is preferable to transfer


voltage, current and impedance either to the primary or to the
secondary
• X0 = E1/I0

20-11-2018 Transformers by Dr. Paresh Kale 68 20-11-2018 Transformers by Dr. Paresh Kale 69

4
20-11-2018

Exact equivalent circuit Simplification of exact eqv. circuit


‘ ‘
‘ ‘ ‘




‘ ‘

20-11-2018 Transformers by Dr. Paresh Kale 70 20-11-2018 Transformers by Dr. Paresh Kale 71

Approximate equivalent circuit


• A 30 kVA, 2400/120-V, 50-Hz transformer has a
high voltage winding resistance of 0.1 Ω and a
leakage reactance of 0.22Ω.

• The low voltage winding resistance is 0.035 Ω
and the leakage reactance is 0.012 Ω.

‘ • Find the equivalent winding resistance,
reactance and impedance referred to the
• (i) high voltage side and
‘ • (ii) the low-voltage side.

20-11-2018 Transformers by Dr. Paresh Kale 72 20-11-2018 Transformers by Dr. Paresh Kale 73

• The output stage of an amplifier has an output


• R1 = 0.1 Ω, X1 = 0.22 Ω,
resistance of 112. Calculate the optimum turns ratio of
• R2 = 0.035 Ω and X2 = 0.012 Ω
a transformer which would match a load resistance of 7
• K = 120/2400 = 1/20; to the output resistance of the amplifier.

• R01 = R1 + R2′ = R1 + R2/K2 = 0.1 + 0.035/(1/20)2 = 14.1 Ω The equivalent input resistance 𝑅1
• X01 = X1 + X2′ = X1 + X2/K2 = 0.22 + 0.12/(1/20)2 =5Ω of the T/F needs to be 112 Ω for
maximum power transfer.
Z01 = 14.1 + j5 Ω
𝑁
𝑅1 =( 1 )2 𝑅𝐿
• R02 = R2 + R1′ = R2 + K2R1 = 0.035 + (1/20)2 × 0.1 = 0.03525 Ω 𝑁2
• X02 = X2 + X1′ = X2 + K2X1 = 0.012 + (1/20)2 × 0.22 = 0.01255 Ω
𝑁 𝑅1 112
Hence ( 1 )2 = = = 16
𝑁2 𝑅𝐿 7
Z02 = 0.03525 + j 0.01255 Ω
Hence the optimum
𝑁1
i.e. = 16 = 4 turns ratio is 4:1
𝑁2

20-11-2018 Transformers by Dr. Paresh Kale 74 20-11-2018 Transformers by Dr. Paresh Kale 75

5
20-11-2018

The voltage regulation of a transformer Efficiency of transformer

• Variation of the secondary voltage between no load and full load, 𝑂𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟 𝑂𝑢𝑡𝑝𝑢𝑡 𝑝𝑜𝑤𝑒𝑟
expressed as either a per-unit or a percentage of the no-load • 𝐸𝑓𝑓𝑖𝑐𝑖𝑛𝑒𝑐𝑦 𝜂 = =
𝐼𝑛𝑝𝑢𝑡 𝑃𝑜𝑤𝑒𝑟 𝑂𝑢𝑡𝑝𝑢𝑡 𝑃𝑜𝑤𝑒𝑟+𝐿𝑜𝑠𝑠𝑒𝑠
voltage, the primary voltage being assumed constant, i.e.

𝑁𝐿 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 −𝐹𝐿 𝑣𝑜𝑙𝑡𝑎𝑔𝑒


• 𝑉𝑜𝑙𝑡𝑎𝑔𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 = • Losses in Transformer
𝑁𝐿 𝑉𝑜𝑙𝑡𝑎𝑔𝑒
• Winding resistance
𝑉1 −𝑉′2 • Core loss (Due to Hysteresis and Eddy current)
• 𝑃𝑒𝑟 − 𝑢𝑛𝑖𝑡 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 =
𝑉1
𝑁1
• Where, 𝑉′2 = 𝑉2 𝑉2 𝐼2 𝑐𝑜𝑠𝜙2
𝑁2 • 𝐸𝑓𝑓𝑖𝑐𝑖𝑛𝑒𝑐𝑦 𝜂 =
𝑉2 𝐼2 𝑐𝑜𝑠𝜙2 + 𝑃𝑐 +𝐼21 𝑅1 +𝐼22 𝑅2
𝐼1 (𝑅01 𝑐𝑜𝑠𝜑2 +𝑋01 𝑠𝑖𝑛𝜑2 )
• 𝑃𝑒𝑟 − 𝑢𝑛𝑖𝑡 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 𝑟𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 = 𝑉1

20-11-2018 Transformers by Dr. Paresh Kale 79 20-11-2018 Transformers by Dr. Paresh Kale 80

Condition for maximum efficiency Condition for maximum efficiency

• 𝑅02 = 𝑅2 + 𝑅′1 = 𝑅2 + 𝐾 2 𝑅1 𝑉2 𝑐𝑜𝑠𝜙2


• 𝐸𝑓𝑓𝑖𝑐𝑖𝑛𝑒𝑐𝑦 𝜂 =
𝑉2 𝑐𝑜𝑠𝜙2+ (𝑷𝒄 /𝑰𝟐)+𝐼2 𝑅02

• For any load current I2


• For transformer, V2 is constant.
• 𝑇𝑜𝑡𝑎𝑙 𝐼2 𝑅 𝑙𝑜𝑠𝑠𝑒𝑠 = 𝐼2 2 𝑅02
• For a load of given power the efficiency is a maximum when the
𝑉2 𝐼2 𝑐𝑜𝑠𝜙2 denominator of above equation is minimum
• 𝐸𝑓𝑓𝑖𝑐𝑖𝑛𝑒𝑐𝑦 𝜂 = 𝟐 𝟐
𝑉2 𝐼2 𝑐𝑜𝑠𝜙2 + 𝑃𝑐 +𝑰 𝟏 𝑹𝟏 +𝑰 𝟐 𝑹𝟐

• Differentiating wrt I2, condition we get


𝑉2 𝐼2 𝑐𝑜𝑠𝜙2
=
𝑉2 𝐼2 𝑐𝑜𝑠𝜙2 + 𝑃𝑐 + 𝑰𝟐 𝟐 𝑹𝟎𝟐
• 𝑰𝟐 𝟐 𝑹𝟎𝟐 = 𝑷𝒄
𝑉2 𝑐𝑜𝑠𝜙2
= • Variable losses = constant losses
𝑉2 𝑐𝑜𝑠𝜙2 + (𝑷𝒄 /𝑰𝟐 ) + 𝐼2 𝑅02

20-11-2018 Transformers by Dr. Paresh Kale 81 20-11-2018 Transformers by Dr. Paresh Kale 82

• I 2 2 R 02 = Pc
𝐶𝑜𝑟𝑒 𝑙𝑜𝑠𝑠𝑒𝑠
• Current at maximum efficiency =
𝑅02

• In a 25-kVA, 2000/200 V, single-phase


transformer, the iron and full-load copper losses
• If iron loss and FL Cu loss is given, are 350 and 400 W respectively. Calculate the
• then load at which Core loss = Copper loss (i.e. corresponding to efficiency at unity power factor on
maximum efficiency) is given by

• (i) full load


𝐼𝑟𝑜𝑛 𝐿𝑜𝑠𝑠
= 𝐹𝑢𝑙𝑙 𝐿𝑜𝑎𝑑 ∗
𝐹𝐿 𝐶𝑜𝑝𝑝𝑒𝑟 𝐿𝑜𝑠𝑠
• (ii) half full-load.

𝑥 ∗𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝐾𝑉𝐴 ∗𝑝𝑜𝑤𝑒𝑟 𝑓𝑎𝑐𝑡𝑜𝑟


Efficiency at any load = ∗ 100
𝑥 ∗𝐹𝑢𝑙𝑙 𝑙𝑜𝑎𝑑 𝐾𝑉𝐴 ∗𝑝𝑜𝑤𝑒𝑟 𝑓𝑎𝑐𝑡𝑜𝑟+𝐶𝑜𝑝𝑝𝑒𝑟 𝐿𝑜𝑠𝑠+𝐼𝑟𝑜𝑛 𝐿𝑜𝑠𝑠

• Where x = ratio of actual to FL KVA

20-11-2018 Transformers by Dr. Paresh Kale 83 20-11-2018 Transformers by Dr. Paresh Kale 84

6
20-11-2018

• (i) Full-load Unity p.f.


Total loss = 350 + 400 = 750 W
F.L. output at u.p.f. = 25 × 1 = 25 kW
Efficiency η = 25/25.75 = 0.97 or 97%

• (ii) Half F.L. Unity p.f.


• Cu loss = 400 × (1/2)2 = 100 W.
• Iron loss remains constant at 350 W
• Total loss = 100 + 350 = 450 W. TESTING OF T/F
• Half-load output at u.p.f. = 12.5 kW

• ∴ η = 12.5/(12.5 + 0.45) = 96.52%

20-11-2018 Transformers by Dr. Paresh Kale 85 20-11-2018 Transformers by Dr. Paresh Kale 86

Open-circuit (OC) test Open-circuit (OC) test

• With normal voltage applied to primary, normal flux will be set up in core
• Hence normal iron losses will occur which are recorded by the wattmeter.

• The purpose of this test is to determine NL loss or core loss


• Also, NL current which is helpful in finding X0 and R0.

• Usually high voltage winding – is left open and the other is connected
to its supply of normal voltage

20-11-2018 Transformers by Dr. Paresh Kale 87 20-11-2018 Transformers by Dr. Paresh Kale 88

Short-circuit (SC) test Short-circuit (SC) test

• It is used to determine:

• Equivalent impedance (Z01 or Z02), leakage reactance (X01 or


X02) and total resistance (R01 or R02) of the transformer as
referred to the winding in which the measuring instruments
are placed.
• One winding, usually the low-voltage winding, is solidly short-circuited by
• Cu loss at any load: Used to calculate efficiency of the T/F. a thick conductor

• or through an ammeter which may serve the additional purpose of


• Knowing Z01 or Z02, the total voltage drop in the transformer indicating rated load current
as referred to primary or secondary can be calculated
• A low voltage (usually 5 to 10% of normal primary voltage) is applied to
the primary
• Regulation of the transformer
• It is cautiously increased till full-load currents are flowing both in primary
and secondary
20-11-2018 Transformers by Dr. Paresh Kale 89 20-11-2018 Transformers by Dr. Paresh Kale 90

7
20-11-2018

Short-circuit (SC) test

• Applied voltage is a small % of the normal voltage • Obtain the equivalent circuit of a 200/400-V, 50-Hz, 1-
• Mutual flux Φ produced is also a small % of its normal value. phase transformer from the following test data :
• Hence, core losses are very small
• O.C test : 200 V, 0.7 A, 70 W – on L.V. side
• If Vsc is the voltage required to circulate rated load currents, then
• Z01 = Vsc / I1 • S.C. test : 15 V, 10 A, 85 W – on H.V. side

W= 𝑰𝟐𝟏 𝑹𝟎𝟏 • Calculate the secondary voltage when delivering 5 kW


at 0.8 p.f. lagging, the primary voltage being 200V.
𝑹𝟎𝟏 =w/𝑰𝟏

𝑿𝟎𝟏 = (𝒁𝟐𝟎𝟏 −𝑹𝟐𝟎𝟏 )

20-11-2018 Transformers by Dr. Paresh Kale 91 20-11-2018 Transformers by Dr. Paresh Kale 92

• Instruments are placed in the secondary i.e. high-voltage winding


• From O.C. Test • whereas the low-voltage winding i.e. primary has been short-
circuited

• V1 I0 cos φ0 = W0 • Z02 = Vsc/I2 = 15/10 = 1.5 Ω ;


• ∴ 200 × 0.7 × cos φ0 = 70
• cos φ0 = 0.5 and sin φ0 = 0.866 • K = 400/200 = 2
• Z01 = Z02/K2 = 1.5/4 = 0.375 Ω

• Iw = I0 cos φ0 = 0.7 × 0.5 = 0.35 A • Also I22R02 = W ;


• Iμ = I0 sin φ0 = 0.7 × 0.866 = 0.606 A • R02 = 85/100 = 0.85 Ω

• R01 = R02/K2 = 0.85/4 = 0.21 Ω


• R0 = V1/Iw = 200/0.35 = 571.4 Ω
• X0 = V1/Iμ = 200/0.606 = 330 Ω • X01 = 𝑍012 − 𝑅012
= 0.3752 − 0.212 = 0.31Ω
• These values refer to primary i.e. low-voltage side.
Z02 = 1.5 Ω, R02 = 0.85 Ω ∴ X02 = 1.24 Ω

20-11-2018 Transformers by Dr. Paresh Kale 93 20-11-2018 Transformers by Dr. Paresh Kale 94

• Output kVA = 5000/0.8 ; • The following data refer to a 1-phase transformer :


• Output current I2 = 5000/0.8 × 400 = 15.6 A
• Turn ratio 19.5 : 1
• This value of I2 is approximate because V2 (which is to be
calculated as yet) has been taken equal to 400 V (which, in • R1 = 25 Ω ; X1 = 100 Ω ;
fact, is equal to E2) • R2 = 0.06 Ω ; X2 = 0.25 Ω.
• No-load current = 1.25 A leading the flux by 30°
• Total transformer drop as referred to secondary
= I2 (R02 cos φ2 + X02 sin φ2)
• The secondary delivers 200 A at a terminal voltage
= 15.6 (0.85 × 0.8 + 1.24 × 0.6)
of 500 V and p.f. of 0.8 lagging.
= 22.2 V

• ∴ V2 = 400 − 22.2 = 377.8 V • Determine by the aid of a vector diagram, the


primary applied voltage, the primary p.f. and the
efficiency.

20-11-2018 Transformers by Dr. Paresh Kale 95 20-11-2018 Transformers by Dr. Paresh Kale 98

8
20-11-2018

• K = 1/19.5
• Taking V2 as ref vector
• E1 = E2/K = 10520+ j 640 V
• V2 = 500 ∠0° = 500 + j0
• -E1 = -10520 – j 640 = 10540 ∠ 183.5 V
• I2 = 200 (0.8 − j 0.6) = 160 − j 120
• I2’= I2K = (-160+ j120)/19.5 = -8.21+j 6.16 A
• Z2 = (0.06 + j 0.25)
• I0 leds V2 by an angle = 3.5 + 90 + 30 = 123.5
• E2 = V2 + I2 Z2
• = (500 + j 0) + (160 − j 120) (0.06 + j 0.25) • I0= 1.25 ∠ 123.5 = -0.69 + j 1.04 A
• = 500 + (39.6 + j 32.8)
• = 539.6 + j 32.8 • I1 = I2’ +I0 = -8.9 + j 7.2 = 11.45 ∠ 141 A
• = 541 ∠3.5°

20-11-2018 Transformers by Dr. Paresh Kale 99 20-11-2018 Transformers by Dr. Paresh Kale 100

NL primary input power • The low voltage winding of a 300-kVA, 11,000/2500-V, 50-
= V1I0sinΦ0 Hz transformer has 190 turns and a resistance of 0.06. The
• V1 = - E1 + I1Z1
= 11540*1.25*cos60 high-voltage winding has 910 turns and a resistance of 1.6
• = -11462 – j 1350 V
= 7210 W Ω.
• = 11540 ∠ 186.7 V R02 = R2 + K2R1
=0.1257 Ohm • When the LV winding is short-circuited, the full-load current
• Phase angle between V1 is obtained with 550-V applied to the HV winding.
Total Cu loss as referred to secondary
and I1
= 186.7 -141 = I22R02 • Calculate
= 5030W
= 45.7 • (i) the equivalent resistance and leakage reactance as
Output = V2I2cosΦ2 referred to HV side
• Primary pf = 0.7 (lag) = 80000W • (ii) the leakage reactance of each winding.
Total losses = 5030 + 7210
= 12240 W • Assume efficiency = 98.5 %
Efficiency = 86.74 % • each winding the ratio (reactance/resistance) is the same

20-11-2018 Transformers by Dr. Paresh Kale 101 20-11-2018 Transformers by Dr. Paresh Kale 102

• FL primary current • Calculate the regulation of a transformer in which the


• = 300,000/0.985 × 11,000 = 27.7A percentage resistance drops is 1.0% and percentage
• K = 190/910 reactance drop is 5.0% when the power factor is
• Z01 = 550/27.7 = 19.8 Ω (a) 0.8 lagging (b) unity (c) 0.8 leading.
• R′2 = R2/K2 = = 1.38 Ω
• R01 = R1 + R′2 = 1.6 + 1.38 = 2.98 Ω %R = vr cos φ + vx sin φ
• X01 = 19.5 Ω

• each winding the ratio (reactance/resistance) is the same a) p.f. = 0.8 lag % R = 1 × 0.8 + 5 × 0.6 = 3.8%
𝑹𝟎𝟏 𝑹𝟏
• =
𝑿𝟎𝟏 𝑿𝟏 b) p.f. = 1 % R = 1 × 1 + 5 × 0 = 1%
• X1 = 1.6 * 19.5 /2.98 = 10.5 Ω
• X′2 = 19.5 × 1.38/2.98 = 9.0 Ω ; c) p.f. = 0.8 lead % R = 1 × 0.8 − 5 × 0.6 = − 2.2%
• X2 = 0.39 Ω
20-11-2018 Transformers by Dr. Paresh Kale 103 20-11-2018 Transformers by Dr. Paresh Kale 104

9
20-11-2018

Auto transformer • A single phase auto transformer has a voltage ratio


320V:250V and supplies a load of 20 KVA at 250 V.
Assuming ideal transformer, determine the current in each
• Electrical T/F where section of the winding.
primary and secondary
Rating = 20 kVA =𝑉1 𝐼2
shares same common
single winding.
Hence primary current,
20×103 20×103
𝐼1 = = = 62.5 A
• often used to step up or 𝑉1 320
step down voltages in
And secondary current,
• 110-115-120 V range 20×103 20×103
• 220-230-240 V range 𝐼2 = = = 80 A
𝑉2 250

Hence current in common part of the


winding = 80 – 62.5 = 17.5 A
20-11-2018 Transformers by Dr. Paresh Kale 105 20-11-2018 Transformers by Dr. Paresh Kale 107

Advantages of Auto transformer Disadvantages of Auto transformer

• Saving in cost since less copper is needed


• Primary and secondary windings are not
• Less volume, hence less weight electrically separate

• A higher efficiency, resulting from lower I2R losses • If open circuit occurs in the secondary winding the
full primary voltage appears across the secondary
• A continuously variable output voltage is
achievable if a sliding contact is used

• A smaller percentage voltage regulation

20-11-2018 Transformers by Dr. Paresh Kale 108 20-11-2018 Transformers by Dr. Paresh Kale 109

20-11-2018 Transformers by Dr. Paresh Kale 114

10

S-ar putea să vă placă și