Sunteți pe pagina 1din 1

E

cooling water - DN250 cooling water - DN250 cooling water - DN250 cooling water - DN250
(from the chiller 2) (to the chiller 2) (from the chiller 1) (to the chiller 1)

650 650 800

500
SKM 4 - chilled water supply - DN300

SKM 4 - chilled water return - DN300

SKM 3 - chilled water supply - DN300

SKM 3 - chilled water return - DN300

COOLING TOWER AREA


FL+13800
Cooling Tower 2 Cooling Tower 1
- NC 8409 - - NC 8409 -

Plan view - roof

A B C D F E
500 2054 3508 500

500

810
DN600
DN250 DN350 DN350 DN450
2100

2100
chilled water
from Chiller - DN250
pipe ring
MP-KF 170-273
pipe ring
MP-KF 170-273

-0.80

-0.80
-0.80
pressure gauge unit
-1 .... 9 bar
pressure gauge unit
-1 .... 9 bar
Fixpoint
KF-FP Set 273
Fixpoint
KF-FP Set 273 Gudang A-C
Chiller-Pump 2 ETANORM

-0.80

-0.80
with vacuum
ETN 100-080-250 GG SKM 4 SKM 3
supporting ring Omega
with vacuum ETANORM ETANORM
length: 130 mm
150-290 A GB G F supporting ring
Chiller-Pump 1 V= 90 m3/h;
length: 130 mm Omega head= 21 mWS ETN 200-150-250 GG ETN 200-150-250 GG
V= 305 m3/h;
150-290 A GB G F inlet: DN100/PN16 V= 500 m3/h; V= 500 m3/h;
head= 12 mWS
V= 310 m3/h; outlet: DN80/PN16 head= 19 mWS head= 19 mWS
inlet: DN200/PN10
head= 11 mWS motor power: 11 kW inlet: DN200/PN10 inlet: DN200/PN10
outlet: DN150/PN16
inlet: DN200/PN10 weight: 320 kg outlet: DN150/PN16 outlet: DN150/PN16
motor power: 18.5 kW
pipe ring outlet: DN150/PN16 motor power: 37 kW motor power: 37 kW
weight: 690 kg
MP-KF 170-273 pressure gauge unit motor power: 22 kW weight: 610 kg weight: 610 kg
pipe ring
0 - 10 bar MP-KF 170-273 weight: 690 kg
pressure gauge unit
temp. sensor
0 - 10 bar
TD2247 + ZT/E-Ms
Fixpoint
safety valve
652 mFK (1") without vacuum
supporting ring pressure gauge unit
pressure sensor length: 130 mm 0 - 10 bar

R. CHILLER
PE3004

temp. sensor
TD2247 + ZT/E-Ms
pressure gauge unit
Fixpoint 0 - 10 bar
KF-FP Set 273 temp. sensor
TD2247 + ZT/E-Ms
1175

Fixpoint
without vacuum safety valve
supporting ring 652 mFK (1") without vacuum
length: 130 mm supporting ring
pressure sensor length: 130 mm
PE3004
2871

temp. sensor
TD2247 + ZT/E-Ms

Fixpoint
KF-FP Set 273

without vacuum
supporting ring
length: 130 mm

4200x2000x500
switchboard
airinotec
Slooping 0,5%

Chiller 2
- CVHG 565 - Chiller 1
only the initiator is able to assign respectively sell the so-called right of use and realization completely or partly to third parties.

Gudang A-C -
in cases of breach the initiator is entitled amongst others to injunctive reliefs as well as claims for clearance and damages.

Gudang A-C -
- CVHE-500 AFD - chilled water supply - DN150
chilled water return - DN150
only the initiator is justified to undertake the utilization as well as the realization and to permit or forbid it.

preliminary copy
that means that he decides if by whom and in which form his creation is duplicated and used.
All documents contained in this documentation are property of airinotec gmbh.

A B C D F E
customer
PT GUDANG GARAM
titling

Unit V - Phase 2
b type Chiller 1 and Cooling tower 1 changed 06.03.'17 mm
a revised after visit June 2016 20.07.'16 mm Chiller-House
index revision date name
Plan view - ground floor plan view
date name
All ventings and drains shall be
loccated according to local requirements!
writer
check.
23-06-2016 mm
airinotec order № size drawing index scale
1:50
norm
industrial air solutions A-16-1-0028 K0 050 b
Kulmbacher Str. 127 ▪ 95445 Bayreuth / GERMANY ▪ +49 (0) 921-745 4439-0 ▪ info@airinotec.com