PROJECT: FFA restaurant

FAHU WITH HORSE SHOE HEAT PIPE

HORSE SHOE HEAT PIPE DETAILS COOLING COIL DETAILS DIMENSIONAL DETAILS

TOTAL FLUID
SUPPLY AIR SUPPLY AIR TOTAL STATIC MOTOR RATING AIR ON PRE- AIR OFF PRE- AIR ON RE- AIR OFF RE- COOLING COIL SENSIBLE AIR ON COIL AIR OFF COIL PRESSURE LENGTH WIDTH HEIGHT QUANTI
AHU REFERENCE MODEL NO FLOW RATE FLOW RATE ESP (Pa) PRESSURE (Pa) (kW) COOL TEMP - COOL TEMP - HEAT TEMP - HEAT TEMP - CAPACITY COOLING COIL TEMP - DB / TEMP - DB / WB DROP (mm) (mm) (mm) TY
(CFM) (LPS) DB / WB (°C) DB / WB(°C) DB / WB(°C) DB / WB (°C) (kW) CAPACITY (kW) WB (°C) (°C) (KPa)

FAHU - 01 TAH 1130 / 1040 3360 1586 500 1149 4.0 34.0/32.0 30.3/29.6 14.0/13.6 20.9/16.1 114.76 31.85 30.3/29.6 13.9/13.9 18.40 2630 1240 1250 1

1. Units shall be factory assembled and Eurovent certified for the following :
a) D1 class for mechanical strength
b) L1 class for negative (-400Pa) and positive (-700Pa) casing leakage
c) T2 class for thermal transmittance
d) TB2 class for thermal bridging using polyamide profiles
e) F9 class for filter bypass leakage.
2.Units shall be built with pentapost extruded aluminium profiles for rigid construction
3. Panels shall be of 50mm thickness with inner / outer skin of 1.0mm GI /1.0mm PPGI.
4. Roof exposed units to be provided with weather proof canopy.
5. Contractor shall provide static pressure calculations for all units and obtain approval before ordering the units.
6.Equipment selection based on trosten
7. Units shall be installed to manufacturer's installation instructions.

CONDENSING UNIT

INPUT POWER INPUTAT POWER


TOTAL
COOLING AT SELECTED TOTAL INPUT TOTAL POWER
AHU REFERENCE MODEL REFRIGERANT CAPACITY - MAX.AMBIENT
CONDITION IN CONDITION NO. OF CIRCUITS WIDTH (mm) DEPTH (mm) HEIGHT (mm) QUANTITY PER COOLING IN (KW)- TOTAL NO. OF
(KW) (KW) PER UNIT (KW) IN FAHU CAPACITY - POWER
FOR CDU CIRCUITS FAHU+CDU IN
KW
PER UNIT (KW)-PER AHU
-* - **

FAHU-01 TAC-G420D7N5 R-407 C 117.67 41.92 51.63 2 2050 2000 1675 1 117.7 51.6 2 55.63

Note : Condensing units shall be of air cooled type, R 407 C refrigerant, hermetic scroll compressors.