Documente Academic
Documente Profesional
Documente Cultură
Abstract—This paper presents a systematic method for the de- are mainly based on their experience, and they usually follow
sign of robust and efficient underfrequency load-shedding (UFLS) typical design criteria on the number of steps, step size, fre-
schemes. UFLS schemes play an important role in protecting the quency thresholds, etc. [6]–[8].
system integrity. The systematic method consists first in selecting
representative operating and contingency (OC) scenarios by means Several methods have been reported in the literature to
of a clustering algorithm and subsequently, in tuning UFLS scheme design conventional UFLS schemes, i.e., to tune frequency and
parameters by dint of a simulated annealing optimization algo- ROCOF thresholds, intentional time delays, and step sizes.
rithm. The approach is applied to a small isolated Spanish power Some of these methods are based on iterative trial and error
system. The systematic method leads to a robust and efficient UFLS procedures [9]; others make use of a screening process among
scheme. The resulting design is also compared to a design based on
OC scenarios determined by the common practice of OC scenario
a host of candidate schemes [6], [7]. However, these methods
selection. The possibility of rearranging UFLS stages and the in- do not necessarily guarantee an efficient performance of the
fluence of minimum allowable frequency constraints is analyzed as scheme.
well. Finally, an analysis of the impact of increasing converter-con- Both deterministic and heuristic optimization algorithms
nected generation (CCG) is presented. have also been applied to the design of conventional UFLS
Index Terms—Design methodology, frequency stability, load schemes to minimize the amount of shed load [10]–[13]. In
shedding, power system protection. [12], frequency thresholds, intentional time delays, and step
sizes are optimized by means of a quasi-Newton method.
Deterministic optimization algorithms depend however on
I. INTRODUCTION the initial guess of the decision variables. Furthermore, the
objective function, which aims at minimizing the amount of
B. Tuning of UFLS Scheme Parameters category are 1) the minimum and 2) the maximum allowable fre-
Efficiency of the UFLS scheme depends on the tuning of its quency values ( and ). In general,
parameters, which is proposed to be carried out in function of the constraint of minimum allowable frequency is accompanied
the selected representative OC scenarios. The problem of UFLS by a maximum time delay, , during which fre-
tuning is formulated as an optimization problem (1). quency can stay below the minimum allowable frequency. Typ-
ical values for small isolated power systems are 47.5 Hz during
maximum 3 s [23]. The maximum allowable frequency varies
between 51.5 Hz and 52 Hz. Equation (4) implements these two
constraints for the considered OC scenarios:
(1)
(2) ..
.
The objective function complying with the main objective is
(3) .. (5)
.
TABLE I
OC scenarios. The energy function is evaluated by time-domain EXISTING (EXIST) AND SYSTEMATICALLY DESIGNED (SYST)
simulations using the power-system model in Fig. 1. These sim- UFLS SCHEME OF THE CONSIDERED POWER SYSTEM
ulations evaluate in turn the impact of the UFLS scheme defined
by on the representative OC scenarios in every iteration of the
SA algorithm. is varied according to a neighborhood function
and a cooling schedule as described in [16].
The tuning process of a UFLS scheme using SA optimiza-
tion algorithm and contemplating representative OC scenarios
is shown in Fig. 2.
TABLE III
COMPARISON OF DIFFERENT UFLS SCHEME DESIGNS
Fig. 4. (a) Comparison of the system responses of the existing and the sys-
tematically designed UFLS scheme. (b) Convergence characteristics of the op-
timization algorithm.
TABLE II
COMPARISON OF THE PERFORMANCE OF THE EXISTING
AND THE SYSTEMATICALLY DESIGNED UFLS SCHEME
cally designed UFLS scheme, frequency deviations are confined of steps by neglecting the priority constraint. The omission of
within the imposed values of maximum and minimum allowable the constraint on the priority should intuitively lead to more ef-
frequency. By contrast, the existing UFLS scheme causes low ficient UFLS scheme designs since this corresponds somehow
and high frequencies and frequency instabilities since genera- to a rough optimization of the step size.
tors cannot lower their output to the new load demand level. Table III shows the results of completely optimized UFLS
scheme (Complete optimization) and the one obtained by
B. Sensitivity Analysis With Respect to Design Conditions omitting priority (No priority). It can be readily deduced that
This subsection presents a sensitivity analysis of UFLS omitting priority reduces the amount of shed load with regard
scheme designs with respect to the imposed design conditions; to the base case design. In addition, it is noteworthy that the
in particular, four cases are analyzed: 1) the use of OC scenarios efficiency of the UFLS scheme designed without considering
selected according to the common practice, 2) the imposition priority constraints approaches the efficiency achieved by an
of a minimum allowable frequency constraint SA-based complete optimization of the UFLS scheme. This
of 47.5 Hz with of 3 s, 3) the neglect of the shows that for smaller isolated power systems, where complete
priority constraint, and 4) the use of a GA as in [13]. Case 3 optimization is theoretically feasible but less practical, relaxing
is also compared with a complete optimization, i.e., when step the constraint on priority leads to very efficient UFLS schemes
sizes are considered as decision variables as well. Anew, the with a performance similar to completely optimized UFLS
UFLS schemes resulting from the analyzed cases are applied scheme.
to all possible OC scenarios. Table III displays and compares 4) Use of Genetic Algorithm: SA optimization algorithm has
the four cases. been used so far. A GA optimization algorithm as proposed in
1) Common Practice of OC Scenario Selection: The prin- [13] is applied using the same genetic operators and param-
cipal idea of clustering-based OC scenario selection is to ob- eters. As shown in Table III, case 4 (GA) has a similar (al-
tain most appropriate OC scenarios. Fig. 3 showed that clus- though slightly worse) impact on all possible OC scenarios in
tering-selected OC scenarios cover a wider range of frequency terms of minimum frequency deviations, amount of shed load,
responses and therefore, a more robust UFLS scheme could be and the number of errors as the base case. These small dif-
expected. ferences are mainly due to the fact that the objective function
Three important characteristics with respect to the robust- has a step-like shape and that for the same final objective func-
ness of the systematic design can be deduced by comparing the tion value, slightly different decision variable values can be ob-
base case with case 1 (Common practice) in Table III. First, the tained. It seems that different heuristic optimization algorithms
number of errors (occasions of poor performance) is remarkably lead to similar results. Fig. 4(b) compares SA and GA conver-
reduced in the case of the base case scheme. Frequency devia- gence characteristics, and it can be seen that they are similar, al-
tions have also been reduced which is indicated by the lower though SA seems to be slightly faster in converging to the final
sum of maximum frequency deviations (corresponding to min- value.
imum frequencies). Finally, the amount of shed load has been
significantly reduced thanks to the base case design. Thus, the C. Analysis of the Impact of Increasing CCG
systematic design given by the base case guarantees a robust and The impact of CCG on the response of a simple power system
efficient UFLS scheme. in terms of frequency has been analyzed in [2]. Negligible pri-
2) Minimum Allowable Frequency of : Con- mary control and the absence of inertial response increase fre-
straints imposed on minimum allowable frequency are more re- quency deviations and the initial slope of frequency. Larger
strictive than the Spanish grid code [23], which leads to a more amounts of shed load could be therefore expected.
conservative scheme and gives therefore a certain safety margin. Two additional CCG penetration levels have been contem-
A relaxation on the minimum allowable frequency constraint by plated: 1) CCG covering up to 24% of total load demand and
permitting the frequency to stay below 47.5 Hz for maximum 3 2) CCG covering up to 34% of total load demand. Further and
s could result in a lower amount of shed load since the constraint in order to study the impact of increasing CCG on the design
is less restrictive. process, a UFLS scheme has been designed for the CCG level
By comparing the base case with case 2 (47.5 Hz-3 s) in of 24% using the proposed method. Table IV shows and com-
Table III, it can be readily deduced that a relaxation on the min- pares the impact of increasing CCG levels on the performance
imum allowable frequency constraint remarkably reduces the of the base case and the performance of the UFLS scheme de-
amount of shed load as expected, at the expense of increased signed for the CCG level of 24% (Increased CCG). Both UFLS
frequency deviations. By relaxing the constraint on allowable schemes are applied to all possible OC scenarios of the initial
minimum frequency by applying the 47.5 Hz–3 s constraint, and the two additional levels of CCG (12%, 24%, and 34%, re-
one accepts very low minimum frequencies (e.g., 46 Hz or less) spectively).
although power-system responses finally comply with the im- It can be deduced from Table IV that the total amount of shed
posed constraint. This enhances the risk of tripping generating load and the number of error increase with the increasing level
units by their underfrequency protection. of CCG. Note that most errors are due to low frequency and
3) Neglect of Priority Constraint: Step sizes have not been overshedding. It can be also seen that for CCG levels of 24%
considered as a decision variables, since for rather small power and 34%, the UFLS scheme designed for the CCG level of 24%
systems, it does not make sense to adjust the step size. An at- sheds less load than the base case (designed for a CCG level of
tractive alternative consists in rearranging the established order 12%) and reduces frequency deviations. Further, the number of
SIGRIST et al.: A METHOD FOR THE DESIGN OF UFLS SCHEMES OF SMALL ISOLATED POWER SYSTEMS 957
TABLE IV TABLE VI
IMPACT OF INCREASING LEVELS OF CCG IN SOC ON UFLS SCHEME DESIGNS SYSTEM OPERATION CONDITIONS (SOC)
TABLE V
PARAMETERS OF THE TURBINE-GOVERNOR SYSTEM MODEL
ACKNOWLEDGMENT
The authors would like to thank S. Marín, J. Ruperez, A. Ro-
errors is slightly larger in the case of the base case. It seems that dríguez, and C. Castro for providing valuable comments and dis-
contemplating higher levels of CCG during the design process cussions throughout the collaboration.
improves the UFLS scheme performance. However, the UFLS
scheme designed for the CCG level of 24% exhibits a slightly
worse performance in terms of shed load and number of errors REFERENCES
than the base case for a CCG level of 12%. Similar to the find- [1] IEEE C37.106, Guide for Abnormal Frequency Protection for Power
ings of Section IV-B1, the selection of SOC with different levels Generating Plant, IEEE Standards, IEEE, 2004.
[2] L. Rouco et al., Impact of Wind Power Generators on the Frequency
of CCG penetration and the selection of OC scenarios seem to Stability of Synchronous Generators. Paris, France: Cigré Session
influence both the UFLS scheme design and its performance. 2008.
Thus, a representative CCG penetration level should be used [3] R. M. Maliszewski, R. D. Dunlop, and G. L. Wilson, “Frequency actu-
ated load shedding and restoration. Part I—Philosophy,” in Proc. IEEE
during UFLS scheme design process. Summer Power Meeting and EHV Conf., Los Angeles, CA, Jul. 12–17,
1970, pp. 1452–1459.
[4] IEEE C37.117, IEEE Guide for the Application of Protective Relays
V. CONCLUSIONS Used for Abnormal Frequency Load Shedding and Restoration, IEEE
Standards, IEEE, 2007.
This paper presents a systematic method for the design of ro- [5] UFLS Regional Reliability Standard Characteristics. Washington,
DC: NERC, 2008.
bust and efficient UFLS schemes. The proposed method consists [6] E. J. Thalassinakis and E. N. Dialynas, “A Monte-Carlo simulation
of two tasks: first, representative OC scenarios are selected by method for setting the underfrequency load shedding relays and se-
means of the K-Means clustering algorithm and subsequently, lecting the spinning reserve policy in autonomous power systems,”
IEEE Trans. Power Syst., vol. 19, no. 4, pp. 2044–2052, Nov. 2004.
UFLS scheme parameters are tuned by dint of the simulated an- [7] C. Concordia, L. H. Fink, and G. Poullikas, “Load shedding on an iso-
nealing optimization algorithm lated system,” IEEE Trans. Power Syst., vol. 10, no. 3, pp. 1467–1472,
The approach has been successfully applied to a small iso- Aug. 1995.
[8] B. Delfino et al., “Implementation and comparison of different under
lated Spanish power system. The systematically designed UFLS frequency load-shedding schemes,” in Proc. 2001 IEEE Power Eng.
scheme outperformed the existing scheme. Further, it has been Soc. Summer Meeting, Piscataway, NJ.
shown that the systematic design is more robust than a design [9] H. E. Lokay and V. Burtnyk, “Application of underfrequency relays for
automatic load shedding,” IEEE Trans. Power App. Syst., vol. PAS-87,
based on OC scenarios selected according to the common prac- no. 3, pp. 720–726, Mar. 1968.
tice, emphasizing the importance of an adequate selection of [10] L. Jenkins, “Optimal load shedding algorithm for power system emer-
OC scenarios. It has been also shown that the choice of min- gency control,” in Proc. 1983 IEEE Int. Conf. Systems, Man and Cy-
bernetics., Bombay and New Delhi, India.
imum allowable frequency constraints significantly influences [11] Y. Halevi and D. Kottick, “Optimization of load shedding system,”
the UFLS scheme performance and that by rearranging UFLS IEEE Trans. Energy Convers., vol. 8, no. 2, pp. 207–213, Jun. 1993.
stages, a similar performance can be obtained as by optimizing [12] A. D. L. Hau, “A general-order system frequency response model in-
corporating load shedding: Analytic modeling and applications,” IEEE
step sizes. Finally, the impact of increasing converter-connected Trans. Power Syst., vol. 21, no. 2, pp. 709–717, May 2006.
generation on the design of UFLS schemes has been analyzed. [13] J. A. P. Lopes et al., “Optimum determination of underfrequency load
shedding strategies using a genetic algorithm approach,” in Proc. 32nd
Annu. North American Power Symp., Waterloo, ON, Canada, 2000.
APPENDIX [14] J. G. Thompson and B. Fox, “Adaptive load shedding for isolated power
systems,” Proc. Inst. Elect. Eng., Gen., Transm., Distrib., vol. 141, no.
Table V lists the parameters of the turbine-governor system 5, pp. 491–496, Sep. 1994.
[15] L. Sigrist et al., “Representative operating and contingency scenarios
model, and Table VI lists the system operation conditions for the design of UFLS schemes,” IEEE Trans. Power Syst., vol. 25, no.
(SOC). 2, pp. 906–913, May 2010.
958 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO. 2, MAY 2012
[16] L. Ingber, “Simulated annealing: Practice versus theory,” J. Math. Ignacio Egido was born in Arévalo (Ávila), Spain, in 1976. He received the
Comput. Model., pp. 29–57, 1993. M.S. and Ph.D. degrees in electrical engineering from the Universidad Pontificia
[17] Genetic Algorithm and Direct Search Toolbox User’s Guide. Natick, Comillas, Madrid, Spain, in 2000 and 2005, respectively.
MA: MathWorks, 2007. He is currently an Assistant Professor in the Department of Electrical Engi-
[18] J. Zhu et al., “Phase balancing using simulated annealing,” IEEE Trans. neering of the School of Engineering of Universidad Pontificia Comillas. He de-
Power Syst., vol. 14, no. 4, pp. 1508–1513, Nov. 1999. velops his research activities at the Instituto de Investigación Tecnológica (IIT)
[19] D. N. Simopoulos, S. D. Kavatza, and C. D. Vournas, “Reliability of the same university, where he has been involved in a number of research
constrained unit commitment using simulated annealing,” IEEE Trans. projects related to AGC and power system stability. His interests include con-
Power Syst., vol. 21, no. 4, pp. 1699–1706, Nov. 2006. trol system design and power systems stability and control.
[20] M. A. Abido, “Robust design of multimachine power system stabilizers
using simulated annealing,” IEEE Trans. Energy Convers., vol. 15, no.
3, pp. 297–304, Sep. 2000.
[21] P. M. Anderson, Power System Protection. Piscataway, NJ: IEEE Luis Rouco (M’91) received the Ingeniero Industrial and Doctor Ingeniero In-
Press, 1999. dustrial degrees from Universidad Politécnica de Madrid, Madrid, Spain, in
[22] J. Abonyi and B. Feil, Cluster Analysis for Data Mining and System 1985 and 1990, respectively.
Identification. Basel, Switzerland: Birkhäuser, 2007. He is a Professor of electrical engineering in the School of Engineering of
[23] Ministry of Industry Tourism and Commerce of Spain, Resolution 9613 Universidad Pontificia Comillas, Madrid, attached to the Department of Elec-
of 26 April 2006 Establishing the Operation Procedures for Insular and trical Engineering. He served as Director of the Department of Electrical En-
Extra Peninsular Power Systems, Official Bulletin of the State no 219 gineering from 1999 to 2005. He develops his research activities at Instituto
of 31 May 2006. [Online]. Available: http://www.ree.es. de Investigación Tecnologica (IIT) of the same university, where he has super-
vised more than 100 research and consultancy projects for Spanish and foreign
Lukas Sigrist (S’08) received the M.Sc. degree in electrical and electronics companies. He has published more than 70 papers in conferences and journals.
engineering from École Polytechnique Fédérale de Lausanne (EPFL), Lau- He has been a visiting researcher at Ontario Hydro, Toronto, ON, Canada; the
sanne, Switzerland, in 2007 and the Ph.D. degree from Universidad Pontificia Massachusetts Institute of Technology, Cambridge; and ABB Power Systems,
Comillas, Madrid, Spain, in 2010. Vasteras, Sweden. His areas of interest are modeling, analysis, simulation, and
He is a researcher at Instituto de Investigación Tecnológica (IIT) of Univer- identification of electric power systems.
sidad Pontificia Comillas, where he has been involved in a number of research Prof. Rouco is a member of Cigré, the Vice-President of the Spanish Chapter
projects related to power-system stability. His areas of interest are modeling, of the IEEE Power Engineering Society, and a member of the Executive Com-
analysis, simulation, and identification of electric power systems. mittee of the Spanish National Committee of Cigré.