Sunteți pe pagina 1din 8

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO.

2, MAY 2012 951

A Method for the Design of UFLS Schemes


of Small Isolated Power Systems
Lukas Sigrist, Student Member, IEEE, Ignacio Egido, and Luis Rouco, Member, IEEE

Abstract—This paper presents a systematic method for the de- are mainly based on their experience, and they usually follow
sign of robust and efficient underfrequency load-shedding (UFLS) typical design criteria on the number of steps, step size, fre-
schemes. UFLS schemes play an important role in protecting the quency thresholds, etc. [6]–[8].
system integrity. The systematic method consists first in selecting
representative operating and contingency (OC) scenarios by means Several methods have been reported in the literature to
of a clustering algorithm and subsequently, in tuning UFLS scheme design conventional UFLS schemes, i.e., to tune frequency and
parameters by dint of a simulated annealing optimization algo- ROCOF thresholds, intentional time delays, and step sizes.
rithm. The approach is applied to a small isolated Spanish power Some of these methods are based on iterative trial and error
system. The systematic method leads to a robust and efficient UFLS procedures [9]; others make use of a screening process among
scheme. The resulting design is also compared to a design based on
OC scenarios determined by the common practice of OC scenario
a host of candidate schemes [6], [7]. However, these methods
selection. The possibility of rearranging UFLS stages and the in- do not necessarily guarantee an efficient performance of the
fluence of minimum allowable frequency constraints is analyzed as scheme.
well. Finally, an analysis of the impact of increasing converter-con- Both deterministic and heuristic optimization algorithms
nected generation (CCG) is presented. have also been applied to the design of conventional UFLS
Index Terms—Design methodology, frequency stability, load schemes to minimize the amount of shed load [10]–[13]. In
shedding, power system protection. [12], frequency thresholds, intentional time delays, and step
sizes are optimized by means of a quasi-Newton method.
Deterministic optimization algorithms depend however on
I. INTRODUCTION the initial guess of the decision variables. Furthermore, the
objective function, which aims at minimizing the amount of

F REQUENCY stability of power systems is concerned with


the ability of generators to supply their loads at an accept-
able frequency after generator and load imbalances. Small iso-
shed load, becomes discontinuous and shows a step-like shape
if step sizes are not considered as decision variables (which is
usually not possible in small isolated power systems), impeding
lated power systems are especially sensitive to real-power im- the use of gradient-based methods.
balances. It is crucial to avoid the frequency falling below a cer- Heuristic algorithms seem to be an appropriate alternative
tain value, since low frequency may severely harm power plants [13]. A genetic algorithm (GA) has been used to optimize
and load-side equipment and hence, the system integrity [1]. In- the step size of a very simple single-stage UFLS scheme of
creasing integration of converter-connected generation (CCG) a test system, maintaining constant frequency threshold and
(e.g., photovoltaics or full-converter wind generators) enhances intentional time delay [13]. However, for small isolated power
the risk of frequency instability due to the negligible primary systems, it is difficult to realize the optimized step size by
control and inertia [2]. rearranging available feeder load-blocks.
Underfrequency load-shedding (UFLS) schemes are a last-re- Irrespective of the design method applied, the adequate
sort tool to protect the power system in case of a severe distur- selection of hypothetical contingencies the system should be
bance [3]. In small isolated power systems, UFLS schemes play protected for is crucial to design robust UFLS schemes [9].
an important role in protecting the system integrity. Most of Different contingencies could be initially considered (line
the UFLS schemes implemented today are conventional static tripping, generation outages, sudden load increase, etc.), but
and semi-adaptive schemes [4], [5]. These schemes continu- only generation outages are contemplated here, since they lead
ously measure frequency and optionally the rate of change of to pronounced frequency deviations [7]. The common prac-
frequency (ROCOF) by means of type 81 relays and shed a tice of contingency selection consists in determining system
predefined amount of load in case frequency and/or the rate of operation conditions corresponding to different load-demand
change of frequency fall below a certain threshold. Electric utili- levels (e.g., minimum and maximum) and to design the UFLS
ties adopt different approaches to design UFLS schemes, which scheme taking into account the outages of the largest and the
smallest generating unit for each of these system conditions
Manuscript received May 04, 2011; revised July 21, 2011 and September 14, [7], [14]. In [15], clustering techniques have been applied to
2011; accepted October 28, 2011. Date of publication December 05, 2011; date
of current version April 18, 2012. This work was supported by Red Eléctrica de
select representative OC scenarios for subsequent design of
España, Madrid, Spain. Paper no. TPWRS-00410-2011. UFLS schemes, but the design itself has not been addressed.
The authors are with the School of Engineering ICAI, Universidad Pontificia Similarly, most design methods did not consider the selection
Comillas, 28015 Madrid, Spain (e-mail: Lukas.Sigrist@iit.upcomillas.es).
Color versions of one or more of the figures in this paper are available online
of OC scenarios [9]–[13].
at http://ieeexplore.ieee.org. This paper proposes a method for the design of robust and
Digital Object Identifier 10.1109/TPWRS.2011.2174448 efficient UFLS schemes. To guarantee a robust UFLS scheme,
0885-8950/$26.00 © 2011 IEEE
952 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO. 2, MAY 2012

representative OC scenarios are selected by means of clustering


techniques. Efficiency of the UFLS scheme can be achieved by
applying an optimization algorithm such as simulated annealing
(SA) to adjust the UFLS scheme parameters by minimizing the
amount of shed load. SA is a heuristic method suited to solve
complex optimization problems [16], [17], and it has been suc-
cessfully applied to problems related to power-system stability,
operation, and planning [18]–[20].
The proposed method makes use of a simplified power-
system model, taking into account power output limitations.
This model allows simulating and evaluating the behavior
of a small isolated power system following a disturbance. In
[10] and [12], linear power-system models have been sup-
posed, neglecting power output limitations, and intentional
Fig. 1. System-frequency dynamics model of the power system.
time delays have been modeled as simple delays, omitting
their frequency-dependent characteristics. Finally and unlike
other design methods, step sizes are a priori not considered as
decision variables and only frequency and ROCOF thresholds output limitations and are also modeled. The
as well as intentional time delays are optimized. In very small inclusion of CCG can be easily realized if inertia and parameters
power systems, it is difficult to realize a desired step size by of the second-order generating unit model were known.
rearranging available feeder load-blocks. However, the pos- Nonlinearities introduced by both power output limitations
sibility exists to rearrange UFLS stages, corresponding to a and the step-like behavior of the UFLS scheme in Fig. 1 require
somehow rough step-size optimization. simulating the response of the power system to a disturbance.
Section II describes the simplified power system model the These responses in terms of frequency and shed load
time-domain simulations are based on; in Section III, the sys- are subsequently used within the systematic method for the de-
tematic method for the design of robust and efficient UFLS sign of UFLS schemes.
scheme is presented; in Section IV, the developed method is
applied to the design of the UFLS scheme of a small isolated III. METHOD FOR THE DESIGN OF UFLS SCHEMES
Spanish power system. A sensitivity analysis with respect to de-
sign conditions and an analysis of the impact of increasing CCG In this section, the systematic method for the design of ro-
on the design of UFLS schemes are presented as well. Section V bust and efficient UFLS schemes is presented, covering both
concludes the paper. selection of OC scenarios and optimal tuning of UFLS scheme
parameters. This method comprises two tasks: the selection of
representative OC scenarios and the application of the SA opti-
mization algorithm.
II. SYSTEM MODELING
A. Selection of Operating and Contingency Scenarios
This section outlines the model used to represent and simulate
small isolated power systems. This model is widely used for It is crucial to select adequate OC scenarios to design robust
the analysis and design of UFLS schemes and is able to reflect UFLS schemes. Not only N-1 outages have to be considered, but
short-term frequency dynamics of small isolated power systems also multiple generation outages could occur. OC scenarios are
[21]. then defined as the outage of a single generating unit or as the
Fig. 1 details the power-system model used to design UFLS simultaneous outage of multiple generating units for a particular
schemes of a small isolated power system, consisting of gen- system operating condition (SOC).
erating units. Each generating unit is represented by a second- The clustering-based method proposed in [15] is used here
order model approximation of its turbine-governor system. In to identify representative OC scenarios, i.e., to find those sce-
fact, frequency dynamics are dominated by rotor and turbine- narios which represent all other possible scenarios best. Clus-
governor system dynamics. Excitation and generator transients tering is carried out with regard to system responses in terms of
can be neglected for being much faster than the turbine-governor frequency to all possible OC scenarios. Note also that the
dynamics. Steam turbines can be usually represented by first- UFLS scheme does not intervene during the OC scenario selec-
order models as in [12], but generation mix also contains gas- tion process.
driven and Diesel-driven turbines, which might require higher The quality of the OC scenario selection can be evaluated by
order models. Since frequency can be considered uniform [21], statistical measurements such as principal component analysis
an equivalent system inertia can be defined. The overall re- (PCA), etc. [22]. PCA is mathematically defined as an orthog-
sponse of loads can be taken into account by means of a load- onal linear transformation that transforms the data to a new co-
damping factor if its value is known. ordinate system such that the greatest variance by any projec-
The gain and parameters , , , and , of each tion of the data comes to lie on the first coordinate (called the
generating unit , can be deduced from more accurate models first principal component), the second greatest variance on the
or field tests. Since primary spinning reserve is finite, power second coordinate, and so on.
SIGRIST et al.: A METHOD FOR THE DESIGN OF UFLS SCHEMES OF SMALL ISOLATED POWER SYSTEMS 953

B. Tuning of UFLS Scheme Parameters category are 1) the minimum and 2) the maximum allowable fre-
Efficiency of the UFLS scheme depends on the tuning of its quency values ( and ). In general,
parameters, which is proposed to be carried out in function of the constraint of minimum allowable frequency is accompanied
the selected representative OC scenarios. The problem of UFLS by a maximum time delay, , during which fre-
tuning is formulated as an optimization problem (1). quency can stay below the minimum allowable frequency. Typ-
ical values for small isolated power systems are 47.5 Hz during
maximum 3 s [23]. The maximum allowable frequency varies
between 51.5 Hz and 52 Hz. Equation (4) implements these two
constraints for the considered OC scenarios:
(1)

The main objective of a UFLS scheme is to protect a power ..


system against instability by curtailing a minimum amount of .
load; therefore, the objective function aims at minimizing
the amount of shed load, whereas stability is guaranteed by im-
posing appropriate inequality constraint functions . and ..
. (4)
are the lower and upper bounds of the decision variables .
In its most generic formulation, decision variables of the
optimization problem correspond to the frequency and ROCOF The constraint requires that the time frequency that is below
thresholds, the intentional time delays, and the step sizes of is smaller than . The constraint
underfrequency and ROCOF stages. However, for rather small requires that the maximum frequency, , is always smaller
power systems, it does not make sense to adjust the step size. than or equal to .
In fact, the step size is usually defined by the utility and also The constraints with respect to the performance of the UFLS
depends on the feeders connected to the relays defined by a par- scheme are 3) the UFLS scheme does not act once the frequency
ticular stage and on the priority of the associated loads; there- has passed its minimum value since frequency is returning to-
fore, in smaller power systems, it will be difficult to find feeder wards its nominal value (instant of shedding), 4) the amount of
blocks which finally sum up to the desired step size. In addi- shed load, , is smaller than or at most equal to the amount
tion, implemented step size usually differs from real step size of lost real power, (amount of shed load), and 5) the UFLS
due to feeder-load variation, feeder outages, or breaker failures. scheme respects the priority of loads (priority). The constraint
Thus, type 81 (underfrequency and ROCOF) relay parameters, in (5) requires that the instant of last shedding, , is prior
i.e., frequency and ROCOF thresholds ( , , and ) to the instant of minimum frequency, , whereas the con-
as well as intentional time delays ( and ) are a straint requires that is smaller than or at most equal to
priori considered here as decision variables as shown in (2). This . The constraint on priority is implemented such that its as-
corresponds to a more practical, industry-oriented optimization sociated constraint function is positive whenever a UFLS stage
strategy. The settings of the existing UFLS scheme can be used actuates without that its preceding stage has actuated:
as initial values for the decision variables:

(2) ..
.
The objective function complying with the main objective is

(3) .. (5)
.

where is a weighting factor, the amount of shed load


in pu for the th representative OC scenario, the vector of The SA optimization algorithm [17] is applied to solve the
decision variables, and is the number of representative OC optimization problem (1). The objective function is translated
scenarios. Other objective function formulations also include an into an energy function, which also takes into account the con-
additional term related to frequency deviations (see, e.g., [11]), straints by means of a penalty function. This energy function is
but it seems more intuitive to include restrictions on frequency given by (6):
deviation as constraints. The weighting factor is set to unity
here as in [12], attaching equal importance to the amount of (6)
shed load in each OC scenario. Another possibility could be to
make inversely proportional to the amount of lost generation
in pu. This way, load shedding for smaller outages outweighs where indicates whether the constraint is active (i.e., 1)
load shedding for larger outages. or not (i.e., 0), whereas and are a penalty constants
Constraints can be divided into two categories. The first one taking distinct values for different constraints and is the th
contains the constraints imposed by the power system, whereas constraint function. In fact, these two penalty constants ensure
the second category covers the constraints with respect to the that the importance of the constraint is taken into account.
performance of the UFLS scheme. The constraints of the first is the number of constraints and is the number of considered
954 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO. 2, MAY 2012

Fig. 3. Comparison of OC scenarios determined by the common practice and


Fig. 2. Flow chart of the UFLS scheme tuning process based on the SA opti- by the K-Means clustering algorithm. (a) Time domain. (b) Principal component
mization algorithm. analysis.

TABLE I
OC scenarios. The energy function is evaluated by time-domain EXISTING (EXIST) AND SYSTEMATICALLY DESIGNED (SYST)
simulations using the power-system model in Fig. 1. These sim- UFLS SCHEME OF THE CONSIDERED POWER SYSTEM
ulations evaluate in turn the impact of the UFLS scheme defined
by on the representative OC scenarios in every iteration of the
SA algorithm. is varied according to a neighborhood function
and a cooling schedule as described in [16].
The tuning process of a UFLS scheme using SA optimiza-
tion algorithm and contemplating representative OC scenarios
is shown in Fig. 2.

IV. APPLICATION TO AN ISOLATED SPANISH POWER SYSTEM


The systematic method for the design of UFLS schemes is
applied to a small isolated Spanish power system. This power
system consists of eleven generators and its peak load demand
is around 35 MW. The parameters of the generating unit models
and the different system operation conditions (SOC) are given in
the Appendix. The SOC include CCG which covers up to 12%
of total load demand and which corresponds to the average con-
tribution of CCG in supplying load demand of the considered representative scenarios are superposed to the principal com-
isolated Spanish power system. ponents of all OC scenarios and the principal components of
At first, the systematic method is applied step by step to the the common practice. For example, the first three OC scenarios
existing UFLS scheme of the considered power system. The re- of the common practice seem to be very close, whereas the
sulting UFLS scheme will be referred to as base case. Subse- clustering-based scenarios are rather widespread, thus better
quently, a sensitivity analysis with respect to design conditions covering the variance within all the possible OC scenarios.
is presented. Finally, the impact of increasing CCG on the de- The existing UFLS scheme, which is currently used by the
sign of UFLS schemes is discussed. system operator of the contemplated Spanish isolated power
system, is shown in Table I. After large disturbances and in order
A. Base Case
to enable the power system to withstand the same disturbances
In a first step, the representative operating and contingency next time, this UFLS scheme has been revised and manually
scenarios are determined by means of K-Means algorithm. It readjusted by the system utility using OC scenarios selected ac-
has been found by applying the K-Means algorithm iteratively cording to the common practice. The existing UFLS scheme will
that four clusters are sufficient to represent all possible 164 OC be redesigned using the proposed method for the design of ro-
scenarios. N-1 outages have been considered since they include bust and efficient UFLS scheme outlined in Section III.
generation loss of over 50% of the total demand. Fig. 3(a) shows Decision variables are the frequency thresholds and
the representative OC scenarios determined by the K-Means , the ROCOF thresholds , and the intentional time
algorithm and compares them to the OC scenarios given by delays . The UFLS scheme parameters are bounded above
the common practice, i.e., the OC scenarios corresponding to and below as follows: 1) , 2)
the outages of the largest and smallest generating unit for the , 3) , and
maximum and minimum load-demand level. Note that during 4) . Step sizes of the underfrequency and
the process of OC scenarios selection, the UFLS scheme does ROCOF stages have not been considered as a decision variable
not intervene and that the worst OC scenarios are in both cases and therefore, the step sizes of the existing UFLS scheme have
nearly the same. According to Fig. 3(a), the clustering-based been used. accounts for measurement and tripping delays.
method covers a wider range of possible system responses. The optimization constraints for the base case design are: the
In Fig. 3(b), first and second principal components of the minimum and maximum allowable frequencies, the instant of
SIGRIST et al.: A METHOD FOR THE DESIGN OF UFLS SCHEMES OF SMALL ISOLATED POWER SYSTEMS 955

TABLE III
COMPARISON OF DIFFERENT UFLS SCHEME DESIGNS

Fig. 4. (a) Comparison of the system responses of the existing and the sys-
tematically designed UFLS scheme. (b) Convergence characteristics of the op-
timization algorithm.

TABLE II
COMPARISON OF THE PERFORMANCE OF THE EXISTING
AND THE SYSTEMATICALLY DESIGNED UFLS SCHEME

Fig. 5. Comparison of the system responses in terms of frequency. (a) Existing


UFLS scheme. (b) Systematically designed UFLS scheme.

the minimum and maximum allowable frequency deviations


shedding, the amount of shed load, and the priority. In partic- in case of the existing UFLS scheme. Frequency overshoot
ular and taking into account (4), minimum allowable frequen- also indicates overshedding. In the case of the systematically
cies of 48 Hz and 47 Hz with corresponding designed UFLS scheme, frequency is confined within the
of 2 s and 0 s, respectively, have been imposed. allowable frequency range. Fig. 4(b) shows the systematic
The maximum allowable frequency is set to 52 method’s convergence characteristics (see also Section IV-B4).
Hz. Table II provides some additional information on the perfor-
Constraints imposed on minimum allowable frequency mance of both the existing and the optimized UFLS scheme.
are more restrictive than those described in Section III (e.g., Table II indicates whether the UFLS scheme satisfies the con-
for maximum 3 s). This leads to a straints on its performance (state) and in addition, provides a
more conservative scheme and gives therefore a certain safety cause in case of constraint violation. It can be inferred that the
margin. Further, more restrictive constraints might also benefit existing UFLS scheme sheds too much load for the first two
UFLS scheme performance in the case of assumed step sizes do contingencies (cause a). Furthermore, load is shed after the fre-
not correspond with real step sizes due to feeder-load variation, quency has passed its minimum (cause b). Overshedding is also
feeder outages, or breaker failures. the reason for the large frequency overshoot and the resulting
Table I shows the systematically designed UFLS scheme. The frequency instability since generators cannot lower their output
number of stages adjusted depends on the maximum amount of to the new demand level. Finally, it can be seen from Table II that
lost power generation in the contemplated OC scenarios. For ex- the systematically designed UFLS scheme sheds less amount of
ample, the worst OC scenario in Fig. 3 corresponds to the outage load than the existing UFLS scheme (Pshed) and that no con-
of generator G17 of the SOC 4, implying a loss of about 50% of straint on its performance is violated. Thus, the existing UFLS
power generation. Thus, using the first six stages of the UFLS scheme has been successfully optimized with respect to the con-
scheme, the system can be stabilized. Remaining steps (7 to 10) sidered representative OC scenarios.
could be used as backup steps in case of step-size variations To come full circle, both the existing and the systematically
or non-responding turbine-governor systems. Backup steps sup- designed UFLS scheme are applied to all possible 164 N-1
port the UFLS scheme during such events and guarantee system OC scenarios. The first two lines in Table III compare the
integrity, and minimizing the amount of shed load is not para- performance of both UFLS schemes. According to Table III,
mount anymore when tuning their settings. In comparison to the amount of shed load has been remarkably reduced after
the existing UFLS scheme, frequency thresholds and inten- implementing the systematically designed UFLS scheme. This
tional time delays of the underfrequency relays have been is also reflected in the lower number of relays which tripped. In
lowered, whereas frequency thresholds and of the addition, fewer errors (e.g., overshedding, low frequency, etc.)
ROCOF relays have been increased. The latter allows a faster occurred thanks to the systematically designed UFLS scheme.
UFLS scheme intervention in case of severe disturbances. Total frequency deviations have also been slightly
Fig. 4(a) and Table II compare the two UFLS schemes. reduced.
Fig. 4(a) shows the system responses in terms of frequency to Fig. 5 finally shows and compares the system responses in
the four representative OC scenarios. It can be inferred that the terms of frequency of the existing and the systematically de-
minimum and maximum frequency deviations clearly exceed signed UFLS scheme. It can be seen that in case of the systemati-
956 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO. 2, MAY 2012

cally designed UFLS scheme, frequency deviations are confined of steps by neglecting the priority constraint. The omission of
within the imposed values of maximum and minimum allowable the constraint on the priority should intuitively lead to more ef-
frequency. By contrast, the existing UFLS scheme causes low ficient UFLS scheme designs since this corresponds somehow
and high frequencies and frequency instabilities since genera- to a rough optimization of the step size.
tors cannot lower their output to the new load demand level. Table III shows the results of completely optimized UFLS
scheme (Complete optimization) and the one obtained by
B. Sensitivity Analysis With Respect to Design Conditions omitting priority (No priority). It can be readily deduced that
This subsection presents a sensitivity analysis of UFLS omitting priority reduces the amount of shed load with regard
scheme designs with respect to the imposed design conditions; to the base case design. In addition, it is noteworthy that the
in particular, four cases are analyzed: 1) the use of OC scenarios efficiency of the UFLS scheme designed without considering
selected according to the common practice, 2) the imposition priority constraints approaches the efficiency achieved by an
of a minimum allowable frequency constraint SA-based complete optimization of the UFLS scheme. This
of 47.5 Hz with of 3 s, 3) the neglect of the shows that for smaller isolated power systems, where complete
priority constraint, and 4) the use of a GA as in [13]. Case 3 optimization is theoretically feasible but less practical, relaxing
is also compared with a complete optimization, i.e., when step the constraint on priority leads to very efficient UFLS schemes
sizes are considered as decision variables as well. Anew, the with a performance similar to completely optimized UFLS
UFLS schemes resulting from the analyzed cases are applied scheme.
to all possible OC scenarios. Table III displays and compares 4) Use of Genetic Algorithm: SA optimization algorithm has
the four cases. been used so far. A GA optimization algorithm as proposed in
1) Common Practice of OC Scenario Selection: The prin- [13] is applied using the same genetic operators and param-
cipal idea of clustering-based OC scenario selection is to ob- eters. As shown in Table III, case 4 (GA) has a similar (al-
tain most appropriate OC scenarios. Fig. 3 showed that clus- though slightly worse) impact on all possible OC scenarios in
tering-selected OC scenarios cover a wider range of frequency terms of minimum frequency deviations, amount of shed load,
responses and therefore, a more robust UFLS scheme could be and the number of errors as the base case. These small dif-
expected. ferences are mainly due to the fact that the objective function
Three important characteristics with respect to the robust- has a step-like shape and that for the same final objective func-
ness of the systematic design can be deduced by comparing the tion value, slightly different decision variable values can be ob-
base case with case 1 (Common practice) in Table III. First, the tained. It seems that different heuristic optimization algorithms
number of errors (occasions of poor performance) is remarkably lead to similar results. Fig. 4(b) compares SA and GA conver-
reduced in the case of the base case scheme. Frequency devia- gence characteristics, and it can be seen that they are similar, al-
tions have also been reduced which is indicated by the lower though SA seems to be slightly faster in converging to the final
sum of maximum frequency deviations (corresponding to min- value.
imum frequencies). Finally, the amount of shed load has been
significantly reduced thanks to the base case design. Thus, the C. Analysis of the Impact of Increasing CCG
systematic design given by the base case guarantees a robust and The impact of CCG on the response of a simple power system
efficient UFLS scheme. in terms of frequency has been analyzed in [2]. Negligible pri-
2) Minimum Allowable Frequency of : Con- mary control and the absence of inertial response increase fre-
straints imposed on minimum allowable frequency are more re- quency deviations and the initial slope of frequency. Larger
strictive than the Spanish grid code [23], which leads to a more amounts of shed load could be therefore expected.
conservative scheme and gives therefore a certain safety margin. Two additional CCG penetration levels have been contem-
A relaxation on the minimum allowable frequency constraint by plated: 1) CCG covering up to 24% of total load demand and
permitting the frequency to stay below 47.5 Hz for maximum 3 2) CCG covering up to 34% of total load demand. Further and
s could result in a lower amount of shed load since the constraint in order to study the impact of increasing CCG on the design
is less restrictive. process, a UFLS scheme has been designed for the CCG level
By comparing the base case with case 2 (47.5 Hz-3 s) in of 24% using the proposed method. Table IV shows and com-
Table III, it can be readily deduced that a relaxation on the min- pares the impact of increasing CCG levels on the performance
imum allowable frequency constraint remarkably reduces the of the base case and the performance of the UFLS scheme de-
amount of shed load as expected, at the expense of increased signed for the CCG level of 24% (Increased CCG). Both UFLS
frequency deviations. By relaxing the constraint on allowable schemes are applied to all possible OC scenarios of the initial
minimum frequency by applying the 47.5 Hz–3 s constraint, and the two additional levels of CCG (12%, 24%, and 34%, re-
one accepts very low minimum frequencies (e.g., 46 Hz or less) spectively).
although power-system responses finally comply with the im- It can be deduced from Table IV that the total amount of shed
posed constraint. This enhances the risk of tripping generating load and the number of error increase with the increasing level
units by their underfrequency protection. of CCG. Note that most errors are due to low frequency and
3) Neglect of Priority Constraint: Step sizes have not been overshedding. It can be also seen that for CCG levels of 24%
considered as a decision variables, since for rather small power and 34%, the UFLS scheme designed for the CCG level of 24%
systems, it does not make sense to adjust the step size. An at- sheds less load than the base case (designed for a CCG level of
tractive alternative consists in rearranging the established order 12%) and reduces frequency deviations. Further, the number of
SIGRIST et al.: A METHOD FOR THE DESIGN OF UFLS SCHEMES OF SMALL ISOLATED POWER SYSTEMS 957

TABLE IV TABLE VI
IMPACT OF INCREASING LEVELS OF CCG IN SOC ON UFLS SCHEME DESIGNS SYSTEM OPERATION CONDITIONS (SOC)

TABLE V
PARAMETERS OF THE TURBINE-GOVERNOR SYSTEM MODEL

ACKNOWLEDGMENT
The authors would like to thank S. Marín, J. Ruperez, A. Ro-
errors is slightly larger in the case of the base case. It seems that dríguez, and C. Castro for providing valuable comments and dis-
contemplating higher levels of CCG during the design process cussions throughout the collaboration.
improves the UFLS scheme performance. However, the UFLS
scheme designed for the CCG level of 24% exhibits a slightly
worse performance in terms of shed load and number of errors REFERENCES
than the base case for a CCG level of 12%. Similar to the find- [1] IEEE C37.106, Guide for Abnormal Frequency Protection for Power
ings of Section IV-B1, the selection of SOC with different levels Generating Plant, IEEE Standards, IEEE, 2004.
[2] L. Rouco et al., Impact of Wind Power Generators on the Frequency
of CCG penetration and the selection of OC scenarios seem to Stability of Synchronous Generators. Paris, France: Cigré Session
influence both the UFLS scheme design and its performance. 2008.
Thus, a representative CCG penetration level should be used [3] R. M. Maliszewski, R. D. Dunlop, and G. L. Wilson, “Frequency actu-
ated load shedding and restoration. Part I—Philosophy,” in Proc. IEEE
during UFLS scheme design process. Summer Power Meeting and EHV Conf., Los Angeles, CA, Jul. 12–17,
1970, pp. 1452–1459.
[4] IEEE C37.117, IEEE Guide for the Application of Protective Relays
V. CONCLUSIONS Used for Abnormal Frequency Load Shedding and Restoration, IEEE
Standards, IEEE, 2007.
This paper presents a systematic method for the design of ro- [5] UFLS Regional Reliability Standard Characteristics. Washington,
DC: NERC, 2008.
bust and efficient UFLS schemes. The proposed method consists [6] E. J. Thalassinakis and E. N. Dialynas, “A Monte-Carlo simulation
of two tasks: first, representative OC scenarios are selected by method for setting the underfrequency load shedding relays and se-
means of the K-Means clustering algorithm and subsequently, lecting the spinning reserve policy in autonomous power systems,”
IEEE Trans. Power Syst., vol. 19, no. 4, pp. 2044–2052, Nov. 2004.
UFLS scheme parameters are tuned by dint of the simulated an- [7] C. Concordia, L. H. Fink, and G. Poullikas, “Load shedding on an iso-
nealing optimization algorithm lated system,” IEEE Trans. Power Syst., vol. 10, no. 3, pp. 1467–1472,
The approach has been successfully applied to a small iso- Aug. 1995.
[8] B. Delfino et al., “Implementation and comparison of different under
lated Spanish power system. The systematically designed UFLS frequency load-shedding schemes,” in Proc. 2001 IEEE Power Eng.
scheme outperformed the existing scheme. Further, it has been Soc. Summer Meeting, Piscataway, NJ.
shown that the systematic design is more robust than a design [9] H. E. Lokay and V. Burtnyk, “Application of underfrequency relays for
automatic load shedding,” IEEE Trans. Power App. Syst., vol. PAS-87,
based on OC scenarios selected according to the common prac- no. 3, pp. 720–726, Mar. 1968.
tice, emphasizing the importance of an adequate selection of [10] L. Jenkins, “Optimal load shedding algorithm for power system emer-
OC scenarios. It has been also shown that the choice of min- gency control,” in Proc. 1983 IEEE Int. Conf. Systems, Man and Cy-
bernetics., Bombay and New Delhi, India.
imum allowable frequency constraints significantly influences [11] Y. Halevi and D. Kottick, “Optimization of load shedding system,”
the UFLS scheme performance and that by rearranging UFLS IEEE Trans. Energy Convers., vol. 8, no. 2, pp. 207–213, Jun. 1993.
stages, a similar performance can be obtained as by optimizing [12] A. D. L. Hau, “A general-order system frequency response model in-
corporating load shedding: Analytic modeling and applications,” IEEE
step sizes. Finally, the impact of increasing converter-connected Trans. Power Syst., vol. 21, no. 2, pp. 709–717, May 2006.
generation on the design of UFLS schemes has been analyzed. [13] J. A. P. Lopes et al., “Optimum determination of underfrequency load
shedding strategies using a genetic algorithm approach,” in Proc. 32nd
Annu. North American Power Symp., Waterloo, ON, Canada, 2000.
APPENDIX [14] J. G. Thompson and B. Fox, “Adaptive load shedding for isolated power
systems,” Proc. Inst. Elect. Eng., Gen., Transm., Distrib., vol. 141, no.
Table V lists the parameters of the turbine-governor system 5, pp. 491–496, Sep. 1994.
[15] L. Sigrist et al., “Representative operating and contingency scenarios
model, and Table VI lists the system operation conditions for the design of UFLS schemes,” IEEE Trans. Power Syst., vol. 25, no.
(SOC). 2, pp. 906–913, May 2010.
958 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO. 2, MAY 2012

[16] L. Ingber, “Simulated annealing: Practice versus theory,” J. Math. Ignacio Egido was born in Arévalo (Ávila), Spain, in 1976. He received the
Comput. Model., pp. 29–57, 1993. M.S. and Ph.D. degrees in electrical engineering from the Universidad Pontificia
[17] Genetic Algorithm and Direct Search Toolbox User’s Guide. Natick, Comillas, Madrid, Spain, in 2000 and 2005, respectively.
MA: MathWorks, 2007. He is currently an Assistant Professor in the Department of Electrical Engi-
[18] J. Zhu et al., “Phase balancing using simulated annealing,” IEEE Trans. neering of the School of Engineering of Universidad Pontificia Comillas. He de-
Power Syst., vol. 14, no. 4, pp. 1508–1513, Nov. 1999. velops his research activities at the Instituto de Investigación Tecnológica (IIT)
[19] D. N. Simopoulos, S. D. Kavatza, and C. D. Vournas, “Reliability of the same university, where he has been involved in a number of research
constrained unit commitment using simulated annealing,” IEEE Trans. projects related to AGC and power system stability. His interests include con-
Power Syst., vol. 21, no. 4, pp. 1699–1706, Nov. 2006. trol system design and power systems stability and control.
[20] M. A. Abido, “Robust design of multimachine power system stabilizers
using simulated annealing,” IEEE Trans. Energy Convers., vol. 15, no.
3, pp. 297–304, Sep. 2000.
[21] P. M. Anderson, Power System Protection. Piscataway, NJ: IEEE Luis Rouco (M’91) received the Ingeniero Industrial and Doctor Ingeniero In-
Press, 1999. dustrial degrees from Universidad Politécnica de Madrid, Madrid, Spain, in
[22] J. Abonyi and B. Feil, Cluster Analysis for Data Mining and System 1985 and 1990, respectively.
Identification. Basel, Switzerland: Birkhäuser, 2007. He is a Professor of electrical engineering in the School of Engineering of
[23] Ministry of Industry Tourism and Commerce of Spain, Resolution 9613 Universidad Pontificia Comillas, Madrid, attached to the Department of Elec-
of 26 April 2006 Establishing the Operation Procedures for Insular and trical Engineering. He served as Director of the Department of Electrical En-
Extra Peninsular Power Systems, Official Bulletin of the State no 219 gineering from 1999 to 2005. He develops his research activities at Instituto
of 31 May 2006. [Online]. Available: http://www.ree.es. de Investigación Tecnologica (IIT) of the same university, where he has super-
vised more than 100 research and consultancy projects for Spanish and foreign
Lukas Sigrist (S’08) received the M.Sc. degree in electrical and electronics companies. He has published more than 70 papers in conferences and journals.
engineering from École Polytechnique Fédérale de Lausanne (EPFL), Lau- He has been a visiting researcher at Ontario Hydro, Toronto, ON, Canada; the
sanne, Switzerland, in 2007 and the Ph.D. degree from Universidad Pontificia Massachusetts Institute of Technology, Cambridge; and ABB Power Systems,
Comillas, Madrid, Spain, in 2010. Vasteras, Sweden. His areas of interest are modeling, analysis, simulation, and
He is a researcher at Instituto de Investigación Tecnológica (IIT) of Univer- identification of electric power systems.
sidad Pontificia Comillas, where he has been involved in a number of research Prof. Rouco is a member of Cigré, the Vice-President of the Spanish Chapter
projects related to power-system stability. His areas of interest are modeling, of the IEEE Power Engineering Society, and a member of the Executive Com-
analysis, simulation, and identification of electric power systems. mittee of the Spanish National Committee of Cigré.

S-ar putea să vă placă și