Documente Academic
Documente Profesional
Documente Cultură
Training Manual
for the
REGENT Fault-Tolerant
Programmable Controller
Revision C
February 1995
P/N MD-622010
Catalog No. T3911
Disclaimer
Because of the variety of uses for this equipment, and
because of the differences between this equipment versus
electromechanical equipment, the user of and those
responsible for applying this equipment must satisfy
themselves as to the acceptability of each application and use
of the equipment. In no event will ICS be responsible or
liable for indirect, special or consequential damages
(including but not limited to lost profits) resulting from the
use or application of this manual or the equipment described
herein, even if ICS has been advised, or should have known
of the possibility of such damages.
i
Important Notice: Grounding
Requirements
The product described herein is equipped with grounding
lugs for the user's safety. They are to be used in conjunction
with a properly grounded receptacle to avoid electrical shock
and/or damage to the equipment.
Related Documents
User's Guide for the REGENT Fault-Tolerant
Programmable Controller. Catalog Number T3390.
Notice
The information contained in this document is subject to
change without notice. The reader should, in all cases,
consult ICS to determine whether any such changes have
been made.
ii
Table of
Contents
Section 1 Introduction ....................................................................... 1
Who this course is intended for......................................... 1-1
Recommended prerequisites ............................................. 1-1
Course goals .................................................................... 1-2
Other training courses ...................................................... 1-2
iii
Main & I/O Processors ....................................... 3-10
TRIOS Memory Usage ....................................... 3-12
Communication Modules................................................ 3-14
Controller Assembly Input Power Distribution ............... 3-16
iv
Section 7 Power Up & Troubleshooting .......................................... 7
Power Up ........................................................................ 7-2
Initializing the REGENT .................................................. 7-3
Connecting your PC to the REGENT ................... 7-3
Running WINTERPRET ...................................................... 7-4
Troublshooting ................................................................ 7-7
Fault Detection ..................................................... 7-7
Fault Annunciation ............................................... 7-8
Relay Fault Contacts ................................. 7-8
Module LEDs ........................................... 7-9
Fault Status Viewer ................................ 7-10
Fault History Window ............................. 7-11
ASCII Messages ..................................... 7-12
Clearing Faults (The Voted Reset Procedure)................. 7-13
Identifying Faults ........................................................... 7-16
Processor Module Faults .................................... 7-16
Communication Module Faults ........................... 7-18
I/O Transciever Module Faults ........................... 7-20
I/O Module Faults .............................................. 7-22
I/O Power Supply Module Faults ........................ 7-25
I/O Power Supply Cable Faults ........................... 7-25
I/O Safetybus Cable Faults.................................. 7-28
v
Section 1
Introduction
Recommended prerequisites
While experience with § Working experience with typical programmable
PLCs is helpful, the lack controllers (PLCs).
of it has not caused any
difficulty for students so § A background in troubleshooting industrial electronic
far. control equipment and field devices.
Introduction 1-1
Course goals
1-2 Introduction
Section 2
Purpose
Objectives
• To be familiar with the types and names of modules used
in the REGENT system.
• To be familiar with the overall operation of the system.
• To be familiar with the physical and environmental
requirements of the system.
• To be able to analyze interface requirements with other
systems.
Follow along with the The following list describes the chassis and modules in each
instructor and connect of the three REGENT assemblies.
the component names
with the associated items Controller Assembly
in the diagram. Controller Chassis
Processor Modules
Communication Modules (4 types)
Communication Module Blanks
I/O Assembly
There is space for up to I/O Chassis
10 I/O modules, of any I/O Transceiver Modules
mix and match, simplex Digital Input and Output Modules
or redundant, in each Analog Input and Output Modules
chassis. I/O Safetybus Cable
I/O Safetybus Terminators
I/O Power Cable
Each input module Process state data is buffered on each input module(s)
passes information to all and transmitted over three redundant data buses to the
three transceivers. three I/O transceiver modules in that rack.
Transceivers have a one The three I/O transceiver modules relay the process state
to one correspondence information to the triplicated processors over the
with the processors. triplicated I/O Safetybus. There is a direct one to one
correspondence between the transceivers and processors.
The processors share The processors read the process state information and
information with each perform control programs which have been stored in
other. memory. The three processors operate as a triplicated
set, sharing information with each other, and are held in
tight synchronization.
Each output module The output module(s) contains bus interface circuitry
receives information which receives the output commands from the triple data
from all three buses and majority-votes the data. Output circuits are
transceivers. driven by the majority-voted commands.
Memory Size
Systems running the Processors are available with either 128K or 512K byte
WINTERPRET operating RAM. (To equate memory size to a conventional PLC
system are normally (measured in 16 bit words), subtract 60K (used by the
supplied with 512K REGENT operating system) and divide by 10. A 512K
processors. REGENT, therefore, is equivalent to a 45K "word" PLC.)
I/O System
Any mix of digital or analog I/O modules.
The I/O Safetybus is a Each I/O slice must be daisy chained, with a maximum of
high speed parallel bus. 150 cable feet from the controller assembly to the last I/O
assembly.
Communications
Maximum of 3 communications modules, each with at least
2 ports.
Communication Standards
RS232C
RS422
RS485
Environmental
8 MB of RAM 16 MB of RAM
Printer
Controller Assembly
Purpose
Objectives
Controller Chassis
The controller chassis is a 19-inch rack in which the
processor and communication modules are installed. The
mounting brackets are removable and can be repositioned for
either front or rear mounting.
Each processor module There are three sets of primary power terminals in the lower
has it’s own dedicated right corner of the chassis for triplicated input power for the
power supply. processor module power supplies. Each set of terminals from
left to right connects power to the corresponding left to right
processor. Above each set of terminals is a fuse and metal
oxide varistor (MOV) for surge suppression and line
filtering. The specific fuses, MOVs and filter networks
characterize the controller chassis for a specific input voltage
type. Controller chassis are available for 110 VAC, 220
VAC or 24VDC input power. The processor modules must
be of the same input power type as the controller chassis.
On the front of each module (refer to Figure 3-3) are various LED
indicators with the following functions:
PROC
PROC Green Healthy
COMM
RESET Pushbutton
Pressing a reset button Used for manual initiation of a voted reset to clear errors and
causes the top 3 PROC, synchronize an uninitialized processor module with the two
COMM, and I/O LEDs operating processors. Buttons on at least two running
to go off on that processors must be pressed to generate a reset signal. The
processor, only as an buttons do not need to be pressed simultaneously. Pressing
acknowledgment. the button on a processor which is off will have no effect. If
two or more processors require resetting, such as at power-
up, the reset signal is automatically generated.
Main Processor
Application Programs
Function Blocks
* Ladder Logic
* Continuous Control (PID)
* Analog Scaling
* Floating Point Math
* Sequence of Events
* Process Historian
Communications
Background Tasks (Diagnostics)
I/O Processor
Write Outputs
Read Inputs
Background Tasks (Diagnostics)
Swap LRAM - SRAM
Controller Assembly 3 - 11
TRIOS Memory Usage
The operating system used by the REGENT is called TRIOS
(TRIplex Operating System). TRIOS is stored both in ROM
memory on board the processor and in RAM. The RAM
portion of TRIOS is loaded into the REGENT from the PDS
(Program Development Station). Since a portion of the RAM
memory of the processor module is used by TRIOS, the
available memory to the user is somewhat less than the
memory size indicated for the processor.
Controller Assembly 3 - 13
Communication Modules
The communication modules provide for serial
communication to external computer equipment. Up to three
communication modules may be installed in a controller
chassis. Each communication module has at least two
independent ports. A family of modules are available for
RS-232, 422, and 485 serial communications, parallel
interfacing for Centronics communications, and Ethernet
TCP/IP/802.3 communications.
Controller Assembly 3 - 15
Controller Assembly Power Distribution
Each of the three input power sources wired to the controller
chassis connects through the chassis to one of the processor
modules. Each processor module power supply converts the
input power to the regulated DC voltage required by the
processor module. The regulated DC voltage is sent back to
the controller chassis for use by the communication modules.
Power Sharing
Processor Processor Processor Circuitry
Primary
Power
I/O Assembly
Purpose
Objectives
• To be familiar with how the I/O interfaces with the
controller assembly.
• To be familiar with the two shutdown modes of the I/O
assembly.
• To be familiar with the types of I/O modules that are
available.
• To be familiar with the levels of I/O redundancy.
I/O Chassis
The I/O chassis is a 19-inch chassis in which the transceivers
and I/O modules are installed. Mounting brackets are
connected to the chassis for either front or rear mounting.
There are thirteen module slots in the I/O chassis. The three
slots on the left are for the transceiver modules. The
remaining ten slots on the right are available for I/O modules.
Digital Outputs
16 Outputs 24 VDC T3441A
16 Outputs 110 VAC T3444
8 Outputs, Form C Relay (1 amp) T3446L
8 Outputs, Form C Relay (2 amps) T3446H
Analog Inputs
Standard response T3420A
Fast response T3420AF
Thermocouple Inputs
24 Input, Type J, K, S, T T3431
RTD Input
16 Inputs T3432
Fire Input
16 Inputs T3419
Analog Output
8 Outputs, 4-20 mA T3470
Multiplexed I/O
512 Inputs, 256 Outputs T3491
I/O Assembly 4 - 11
Figure 4-9: Analog Input Modules
I/O Assembly 4 - 13
Simplex Input Modules
I/O Assembly 4 - 15
Simplex Output Modules
Simplex output modules have Safetybus interface circuits,
provide electro-optical isolation up to 2,500 volts, and
incorporate watchdog shutdown timers.
I/O Assembly 4 - 17
Multiplexed I/O Assembly
Each multiplexed I/O module has Safetybus interface
circuits, a microprocessor, and two isolated serial interfaces
to communicate with external remote myultiplexed I/O
equipment. Multiplexed I/O assemblies are used to provide
an economical serial interface for driving matrix and mimic
displays.
I/O Assembly 4 - 19
Class I: Non -Critical I/O
Simplex input and output modules may be used for non-
critical I/O points to reduce overall costs. (In addition, the
multiplexed I/O assembly may be used as well.) Simplex I/O
modules utilize a triplicated interface with the processors,
however, the input signal conditioning and output drivers
have the same potential failure characteristic as standard,
non-redundant programmable controller I/O modules. Inputs
use single signal conditioners and outputs use either single
transistors, TRIACs, or D to A converters.
I/O Assembly 4 - 21
Class III: Fault-Tolerant I/O Modules
Fault-tolerant I/O uses redundant modules connected in
parallel to the simplex field devices. This provides fault-
tolerance in the presence of any I/O module fault. The field
devices are connected to each of the redundant modules, and
each module is addressed by the application program.
I/O Assembly 4 - 23
Section 5
Purpose
To further describe the components and functions of the I/O
power supply assembly.
Objectives
Table 5-1 shows the number of available load units with one
to four I/O chassis. (The available load units decrease as you
add I/O chassis because each I/O transceiver uses 1.33 load
units.) The load units consumed by each module is shown in
Table 5-2.
1 52
2 48
3 44
4 40
Purpose
To describe requirements for input power connections, field
wiring connections for I/O modules, installation & removal
of modules, and internal cable connections.
Objectives
• To be familiar with the input power and connection
requirements for the controller and I/O power supply
assemblies.
• To be familiar with the field wiring connection
requirements of the I/O modules.
• To be able to install and remove any module in the
system.
• To be familiar with the internal cabling requirements of
the system.
There are terminal blocks on the I/O chassis above and below
each module slot. These blocks connect the Regent to the
field devices (sensors and actuators) and provide power
connections. (The modules do not generate field power, but
are connected to the field power supply through these
terminals.) Each terminal block has ten screw terminals. The
screw terminals on top are identified as 1 through 8, plus A
and B. The screw terminals on bottom are identified as C, D,
and 9 through 16. The numbered screw terminals connect up
to 16 devices (1 per channel) to each module.
Labels on the side of Any I/O module may be plugged in to any of the 10 slots in
each I/O module also an I/O chassis. The terminals are, therefore, wired differently
show which terminals are for each type of module, as shown in the following
used for I/O and power illustrations.
signals.
6
Color Coding:
GUARDED Red: AC
24VDC Blue: DC
Green: Analog
OUTPUT
White: Relay & Iso. Output
If the module does not slide easily, do not force it. Remove it and
check for bent or damaged pins, and repeat steps a through dd
again.
Removal
Removal
2 Hold the module upright with both hands, with the front
of the module facing you. Align the 96-pin DIN
connector on the module with its counterpart on the
backplane of the I/O chassis. Align the upper and lower
retaining levers with their respective slot tabs.
4 Press the module firmly into the I/O chassis, until the top
and bottom retaining levers snap into their respective slot
tabs. Make sure that the top and bottom retaining levers
are flush with the module housing.
3 Make sure the field devices have been wired to the I/O
terminal blocks on the I/O chassis in accordance with the
requirements of each particular module.
Installation
2 Hold the module upright with both hands, with the front
of the module facing you. Align the two card edges and
the 96-pin DIN connector on the module with its
counterpart on the backplane of the I/O chassis. Align the
upper and lower retaining levers with their respective slot
tabs.
4 Press the module firmly into the I/O chassis, until the top
and bottom retaining levers snap into their respective
slot tabs. Make sure that the top and bottom retaining
levers on the module are flush with the module housing.
Removal
Installation
1 Hold the I/O blank with the long tab at the top and the
short tab at the bottom.
2 Slip the long tab through the top I/O slot and slide the
blank down to insert the short tab through the bottom I/O
slot.
Removal
Installation
Removal
The maximum distance One I/O power cable is required to connect an I/O power
between an I/O power supply unit to an I/O unit. (The cable is triplicated
supply unit and one of internally.)
it’s corresponding I/O
units is 30 feet. 1 Connect one end of an I/O power cable to any one of the
four connectors on the left side of the I/O power supply
chassis.
Purpose
Objectives
This means that Power must be applied to the I/O power supplies before or
whenever hardware is at the same time as the controller unit. This is to ensure
added to the system at a that the processors will recognize the I/O.
later time, the system
must be cold-started in When power is first applied to the REGENT, the following
order to recognize the LED indicators should be on:
new hardware.
Processor Modules:
Communication Modules:
I/O Modules:
Also, check the After a cold start you must connect to port 1 of the
WINTERPRET serial port
setting on the computer.
1 Load RAMcode into the Choose Load RAMcode from the Execution
Regent Controller’s Initialize menu.
2 Load the I/O Configuration Choose Load I/O Configuration from the
into the Regent Execution Controller’s Initialize menu.
3 Load the Shared Variable Choose Load Shared Allocation from the
Definitions into the Regent Execution Controller’s Initialize menu.
It may be helpjul to 5 Start Output processing Choose Start Outputs from the Execution
perform step 5 last Controller’s Initialize menu.
when commissioning
a system. 6 Load the Regent Serial ports Choose Serial Ports from the Project Editor’s
configuration Definitions menu (choose Save to Disk and
Regent).
7 Set the Regent real-time Choose Set Real-Time Clock from the Project
clock Editor’s Controller menu.
Fault Detection
Permanent
Permanent Error Threshold
Transient
Transient
Transient Transient
Transient Reset
Test Cycle
Fault Annunciation
Power On
Module
Power No Fault Fault Removed
Off
N.O. Contact 0 1 0 0
N.C. Contact 1 0 1 0
0 = Contact is open.
1 = Contact is closed.
LEDs are for indication only. They are meant to help locate
modules with permanent faults. When a red LED of an I/O
module is on, the module may still be operational. This is
A fault indication does because there are triplicated components in the module. One
not necessarily mean that of the triplicated parts may fail, yet the other two remaining
a module is not healthy parts allow the module to remain operational. Failed
operational. modules should be replaced as soon as possible, however,
because if a second part of the module should fail, two-out-
of-three operation cannot be maintained.
Communication
Processor Modules
Module
PROC PROC PROC
COMM
COMM COMM COMM
BLOWN
FUSE
SHUT
DOWN
Processor Faults
PROC, COMM, and I/O LEDs are off on only 1 processor
BLOWN
FUSE
SHUT
DOWN
BLOWN
FUSE
SHUT
DOWN
Both ACTIVE and FAULT LEDs are off for only one
transceiver module connected to an I/O power supply.
BLOWN
FUSE
SHUT
DOWN
ON LED is off
This is also a normal indication. The module is part of a
pair of guarded analog output modules which are
strapped together to provide fault tolerant control. This
indication shows that the other module of this pair is
currently controlling the output devices.
Communication
Processor Modules
Module
PROC PROC PROC
COMM
COMM COMM COMM
BLOWN
FUSE
SHUT
DOWN
All LEDs are off for all I/O transceiver modules cabled to
an I/O power supply assembly
Both the ACTIVE and FAULT LEDs are off for only one
I/O transceiver module
Caution The I/O power cable supplies triplicated power to the I/O
assembly. Disconnecting it will cause all of the I/O
modules in the I/O assembly to stop operating. The input
modules will not be read by the processors and the output
modules will all turn off, regardless of the position of the
Fault Mode Jumper. (Hold or Shutdown)
BLOWN
FUSE
SHUT
DOWN
BLOWN
FUSE
SHUT
DOWN
BLOWN
FUSE
SHUT
DOWN
Controlling Programs
Purpose
To describe the steps necessary to load, control & monitor
programs.
Objectives
Loading Programs
Loaded - Program has been Run: Switches this program to Cannot load another program
Pend loaded but not yet the running mode. until this program is switched
switched to the run- (run or stop) or removed
Stop: Switches this program to
ning or stopped mode (cancel program load).
the stopped mode.
Cannot perform a reset local
Cancel program load: Removes variables for this program
this program from the Regent. (unnecessary, included with
load) or other programs until
this program is switched.
Note: You can stop, run, scan, Cannot monitor this program
delete or monitor other programs until it is switched to running
that are currently in the Regent. or stopped.
Stopped Program is stopped Run, scan, stop, delete and You may also reset local
and is not executing. monitor are available for this variables provided that no
program. other program switch is
pending.
Running Program is running Run, stop, monitor are available You cannot scan, delete, or
and is executed once for this program reset local variables for this
each scan cycle. program until it is stopped.
Loaded - 1) Program is Run: Switches to the new loaded Cannot load another program
Mod stopped and a new program (or local data); until this program is switched
version has been execution status will switch to (run or stop) or removed
loaded but not yet running. (cancel program load).
switched. Stop: Switches to the new loaded Cannot perform a reset local
2) Program is program (or local data); variables for this program or
stopped and a reset execution status will switch to other programs until this
local variables has stopped. program is switched.
been performed but Cancel Program Load: Removes
not yet switched. the new loaded program (or local
data), existing program in the
Regent will remain stopped.
Running - Program is running Run: Switches to the new loaded Cannot load another program
Mod and a new version is program, execution status will until this program is switched
loaded but not yet switch to running. (run or stop) or removed
switched. Stop: Switches to the new loaded (cancel program load).
program, execution status will Cannot perform a reset local
switch to stopped. variables for this program or
Cancel Program Load: Removes other programs until this
the new loaded program, existing program is switched.
program in the Regent will
remain running.
System Maintenance
Purpose
To describe the maintenance activities required of the
REGENT.
Objectives
Battery Replacement
Module Removal
Disassembly
Loosen and remove the five screws from the right side of the
module (this is the side with the module and revision labels).
Carefully lift the circuit board assembly away from the
module and place it, component side up, on a flat surface.
Remove the three cylindrical metal spacers and place them
to one side.
Replacing EEPROMs
Module Assembly
Lay the circuit board assembly on the table and place the
power supply half of the processor module on top of it.
Then turn the two halves over together and align the screw
holes. Make sure the ribbon cable connector ejectors are
closed.
Required Equipment
Calibration Procedure
1 Remove the module from the I/O chassis. Install the I/O
extender module in its place. Remove the analog input
circuit board from its clamshell and plug it into the
extender module.
System Maintenance 9 - 11
8 Monitor the analog inputs from the PDS. Adjust the
Offset Adjust potentiometer (R569) for an average
value of 2 for all input channels. (The value of 2 is the
raw analog data used within the REGENT system,
which ranges from 0 to 4095.) The entire module is
calibrated at one time, not each channel individually.
Verify that all input channels read between 1 and 3.
0 to 5 0 to 20 0.0024 4.9976
1 to 5 4 to 20 1.0020 4.9980
0 to 10 0 to 40 0.0049 9.9951
Figure 9-5B: Extender Module for Calibrating Analog Input Module (8 channel)
System Maintenance 9 - 13
Calibration of Analog Output Modules
Required Equipment
In order to calibrate the module it must be installed in an
operating I/O assembly. The following tools and equipment
are required for proper calibration.
4 Phillips screwdriver.
Calibration Procedure
The module must be calibrated in an I/O chassis connected to
a REGENT controller.
2 Install the I/O extender module into the slot from which
the analog module was removed.
System Maintenance 9 - 15
replacement.
System Maintenance 9 - 17
Calibration of Guarded Analog Output
Modules
Guarded analog output modules are calibrated at the factory
before shipment. These modules are designed for 4 to 20 mA
output only. In order to maintain their rated accuracy, the
modules should be calibrated yearly.
Required Equipment
In order to calibrate the module it must be installed in an
operating I/O assembly. The following tools and equipment
are required for proper calibration.
4 Phillips screwdriver.
Calibration Procedure
The module must be calibrated in an I/O chassis connected to
a REGENT controller.
3 Install the I/O extender module into the slot from which
the analog module was removed.
System Maintenance 9 - 19
Span trimpots until the voltage readings are within the
stated limits.
Figure 9-8: Extender Module for Calibrating Guarded Analog Output Module
System Maintenance 9 - 21
Return Material Authorization
A Return Material Authorization number is required in order to return failed modules
to the factory for repair. To obtain an RMA number, please call the ICS Customer Care
Department at (713) 353-2400.
Required Information
Please have the following information available to assist in processing your request:
Shipping Address
Billing Address
Contact Name
Telephone Number
Catalog Number(s) of item(s) to be returned
Serial Number(s) of item(s) to be returned
Description of observed failure mode or problem
In addition, the following information may be helpful in expediting the repair and return
of the equipment: