SAG TENSION CALCULATION FOR 26.68 m SPAN SINGLE BEAR ACSR - 132kV TRANSFORMER FEEDER
1.1.10 Basic Wind Speed Vb = 47 m/s (As per IS: 875 -1987,
Part : 3)
1.1.11 Span (c/c tower - lg) Ls = 25930 mm
1 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
W wi = W d x nd x n s = 7.5 x 12 x 1 = 90 kg
Wind zone = 4
Basic wind speed Vb = 47 m/s
Reliability level of structure = 1
factor k0 = 1.375 (As per IS 802, Clause 8.2, Pg no:3)
Risk co efficient k1 = 1
Terrain roughness co efficient k2 = 1
Design wind speed Vd = Vr x k1 x k2 = 34.19 x 1 x 1 = 34.19 m/s
Drag Co efficient for conductor Cd = 1 (As per IS 802, Clause 9.2, Pg no:7)
Gust response factor for 8000mm level Gc = 1.66 (As per IS 802, Table 7, Pg no:9)
(For reliability level 1, Terrain category 2)
Drag Co efficient for insulator Cdi = 1.2 (As per IS 802, Clause 9.3, Pg no:9)
Gust response factor for level Gci = 1.864 (As per IS 802, Table 6, Pg no:9)
(For reliability level 1, Terrain category 2)
2 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
Wi = W i2 / nc = 96.75 / 1 = 96.75 kg
WT = 17.02 x 1 = 17.02 kg
W hr = W hT / nc = 34.492 / 1 = 34.492 kg
3 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
A B
`
1740.0 mm 750 mm 20950.000 mm 750 mm 1740.0 mm
+163.1908 kg
+66.4408 kg
10475 375 1245 870
+31.9488 kg
-31.9488 kg
870 1245 375 10475
-66.4408 kg
NOTE: LENGTH IN "mm"
-163.1908 kg
4 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
A B
`
1740.0 mm 750 mm 20950.000 mm 750 mm 1740.0 mm
+119.7262 kg
+29.7262 kg
10475 375 1245 870
+12.7062 kg
-12.7062 kg
870 1245 375 10475
-29.7262 kg
NOTE: LENGTH IN "mm"
-119.7262 kg
5 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
E x SM1 E x SM2
σ2 x (σ-σ1) + + E x α (T1-To) = kg/mm 2
2 2 2
Ac x Ls x σ1 Ac x Ls
Where
σ1 = 3.07125 kg/mm 2
S = SI2 / Tstill mm
Tstill = σxA kg
where, σ is the final stress at still wind condition for a given temperature
E x SM1 E x SM1
σ2 x (σ-σ1) + + E x α (T1-To) = kg/mm 2
2 2 2
Ac x Ls x σ1 Ac x Ls
Where
σ1 = 3.07125 kg/mm 2
D = SI2 / Tfull mm
Tfull = σxA kg
where, σ is the final stress at full wind condition for a given temperature
Swg = D2 - S2 mm
6 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
6.4.7 Since the calculated vertical clearance between Equipment and Lower most conductor is
greater than the minimum clearance between phase to phase, The selected height of tower
8000mm is adequate.
7 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
SAG TENSION CALCULATION FOR 12 m SPAN SINGLE BEAR ACSR - 132kV BUS
1.1.10 Basic Wind Speed Vb = 47 m/s (As per IS: 875 -1987,
Part : 3)
1.1.11 Span (c/c tower - lg) Ls = 11250 mm
8 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
W wi = W d x nd x n s = 7.5 x 12 x 1 = 90 kg
Wind zone = 4
Basic wind speed Vb = 47 m/s
Reliability level of structure = 1
factor k0 = 1.375 (As per IS 802, Clause 8.2, Pg no:3)
Risk co efficient k1 = 1
Terrain roughness co efficient k2 = 1
Design wind speed Vd = Vr x k1 x k2 = 34.19 x 1 x 1 = 34.19 m/s
Drag Co efficient for conductor Cd = 1 (As per IS 802, Clause 9.2, Pg no:7)
Gust response factor for 8000mm level Gc = 1.66 (As per IS 802, Table 7, Pg no:9)
(For reliability level 1, Terrain category 2)
Drag Co efficient for insulator Cdi = 1.2 (As per IS 802, Clause 9.3, Pg no:9)
Gust response factor for level Gci = 1.864 (As per IS 802, Table 6, Pg no:9)
(For reliability level 1, Terrain category 2)
9 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
Wi = W i2 / nc = 96.75 / 1 = 96.75 kg
WT = 17.02 x 1 = 17.02 kg
W hr = W hT / nc = 34.492 / 1 = 34.492 kg
10 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
A B
`
1740.0 mm 750 mm 6270.000 mm 750 mm 1740.0 mm
+140.8038 kg
+44.0538 kg
3135 375 1245 870
+9.5618 kg
-9.5618 kg
870 1245 375 3135
-44.0538 kg
NOTE: LENGTH IN "mm"
-140.8038 kg
11 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
A B
`
1740.0 mm 750 mm 6270.000 mm 750 mm 1740.0 mm
+110.8228 kg
+20.8228 kg
3135 375 1245 870
+3.8028 kg
-3.8028 kg
870 1245 375 3135
-20.8228 kg
NOTE: LENGTH IN "mm"
-110.8228 kg
12 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
E x SM1 E x SM2
σ2 x (σ-σ1) + + E x α (T1-To) = kg/mm 2
2 2 2
Ac x Ls x σ1 Ac x Ls
Where
σ1 = 3.07125 kg/mm 2
S = SI2 / Tstill mm
Tstill = σxA kg
where, σ is the final stress at still wind condition for a given temperature
E x SM1 E x SM1
σ2 x (σ-σ1) + + E x α (T1-To) = kg/mm 2
2 2 2
Ac x Ls x σ1 Ac x Ls
Where
σ1 = 3.07125 kg/mm 2
D = SI2 / Tfull mm
Tfull = σxA kg
where, σ is the final stress at full wind condition for a given temperature
Swg = D2 - S2 mm
13 of 14
DOC NO : HZL-BTN-ELE-DS-SY-028
6.4.7 Since the calculated vertical clearance between Equipment and Lower most conductor is
greater than the minimum clearance between phase to phase, The selected height of tower
8000mm is adequate.