Documente Academic
Documente Profesional
Documente Cultură
SEMINAR REPORT
ON
Bachelor of Technology
In
Electrical Engineering
Session: 2017-18
CERTIFICATE
Date: 3/10/2017
I feel immense pleasure in expressing my regards to the chairman, SKIT Shri Surja
Ram Meel, Director Shri Jaipal Meel, Registrar Smt. Rachna Meel, Director
(Academics) Prof. (Dr.) S.L. Surana, Director (D&W) Prof. (Dr.) Ramesh Pachar,
Swami Keshvanand Institute of Technology, Management and Gramothan, Jaipur for
proving me necessary facilities to complete this work.
I express my gratitude to the Head of the Department, Dr. Akash saxena and Deputy
Head of the Department, Mr. Ankush Tondon for their valuable support.
Yours Sincerely,
Raja Agarwal
Electric power is produced at the power generating stations, which are generally
located far away from the load centers. High voltage transmission lines are used to
transmit the electric power from the generating stations to the load centers. Between
the power generating station and consumers a number of transformations and
switching stations are required. These are generally known as substations. Substations
are important part of power system and form a link between generating stations,
transmission systems and distribution systems. Heerapura 400 kV Grid Sub-Station is
a transformer sub-station which step down voltage from 400 kV to 220 kV. The 400
kV feeders come from Bassi, Merta, Hindoun, Phagi, and Jaipur North. Then the
voltage is transformed to 220 kV and sent to Sanganer, SEZ, Phulera, KTPS and
NPH. A spare line is also kept for emergency purposes. There are four transformers
installed in which three are of 250 MVA and one of 315 MVA. This sub-station also
helps in prevention of major faults and fault correction. Circuit breakers, Isolators and
various other equipments are installed in this GSS to ensure a reliable supply of power
to homes. Heerapura village is located in Phagi Tehsil of Jaipur district in Rajasthan,
India. It is situated 22km away from sub-district headquarter Phagi and 39km away
from district headquarter Jaipur. Substation was commissioned on 19th July 2000 by
government of Rajasthan. Today, it has a total transformation capacity of (250*3 +
315*1) 1065 MVA.
Acknowledgement ii
Abstract iii
List of Content iv
1.1 Introduction 1
3.1 Introduction 8
4.1 Definition 11
7 Isolators 19-22
9 Insulators 26-28
10 Relays 29-30
11 PLCC 31-32
References 34
4.1 Bus-Bar 11
7.1 Isolator 21
9.1 Insulators 28
1.1 INTRODUCTION
Electric power is produced at the power generating stations, which are generally
located far away from the load centers. High voltage transmission lines are used to
transmit the electric power from the generating stations to the load centers. Between
the power generating station and consumers a number of transformations and
switching stations are required. These are generally known as substations.
Substations are important part of power system and form a link between generating
stations, transmission systems and distribution systems. It is an assembly of
electrical components such as bus-bars, switchgear apparatus, power transformers
etc. Their main functions are to receive power transmitted at high voltage from the
generating stations and reduce the voltage to a value suitable for distribution. Some
substations provide facilities for switching operations of transmission lines, others
are converting stations. Substations are provided with safety devices to disconnect
equipment or circuit at the time of faults. Substations are the convenient place for
installing synchronous condensers for the purpose of improving power factor and it
provide facilities for making measurements to monitor the operation of the various
parts of the power system. The substations may be classified in according to service
requirements and constructional features. According to service requirements it is
classified in to transformer substations, switching substations and converting
substations.
The present day electrical power system is A.C. i.e. electric power is generated,
transmitted and distributed in the form of Alternating current. The electric power is
produce at the power station, which are located at favourable places, generally quite
away from the consumers. It is delivered to the consumer through a large network of
transmission and distribution. At many place in the line of power system, it may be
desirable and necessary to change some characteristic (e.g. Voltage, ac to dc,
frequency p.f. etc.) of electric supply. This is accomplished by suitable apparatus
called sub-station for example, generation voltage (11kV or 6.6kV) at the power
Grid Substations – This substation is used for transferring the bulk power from
one point to another. If any fault occurs on the substation, then the continuity of
whole of the supply is affected by it.
Town Substations – These substations step down the voltage at 33/11 kV for
more distribution in the towns. If there is any fault occurs in this substation, then
the supply of the whole town is blocked.
1. Bassi I
2. Bassi II
3. Merta
4. Hindoun I
5. Hindoun II
6. Phagi I
7. Phagi II
8. Jaipur North
1. Sanganer
2. SEZ
3. Phulera
4. KTPS
5. NPH
3.1 INTRODUCTION
A transformer is a static machine used for transforming power from one circuit to
another without changing frequency. This is a very basic definition of transformer.
Since there is no rotating or moving part so transformer is a static device. Transformer
operates on ac supply. Transformer works on the principle of mutual induction.
Generation of electrical power in low voltage level is very much cost effective.
Theoretically, this low voltage level power can be transmitted to the receiving end.
This low voltage power if transmitted results in greater line current which indeed
causes more line losses but if the voltage level of a power is increased, the current of
the power is reduced which causes reduction in ohmic or I2R losses in the system,
reduction in cross sectional area of the conductor i.e. reduction in capital cost of the
system and it also improves the voltage regulation of the system. Because of these,
low level power must be stepped up for efficient electrical power transmission. This is
done by step up transformer at the sending side of the power system network. As this
high voltage power may not be distributed to the consumers directly, this must be
stepped down to the desired level at the receiving end with the help of step down
transformer. Electrical power transformer thus plays a vital role in power
transmission.
4.1 DEFINITION
The bus-bar system consists of the isolator and the circuit breaker. On the occurrence
of a fault, the circuit breaker is tripped off and the faulty section of the bus-bar is
easily disconnected from the circuit.
The various types of bus-bar arrangement are used in the power system. The selection
of the bus-bar is depended on the different factor likes reliability, flexibility, cost etc.
The following are the electrical considerations governing the selection of any one
particular arrangement.
In this type of bus-bar arrangement, the circuit breaker and isolating switches are
used. The isolator disconnects the faulty section of the bus-bar, hence protects the
system from complete shutdown. This type of arrangement uses one addition circuit
breaker which does not much increase the cost of the system.
Such type of arrangement uses two type of bus-bar namely, main bus-bar and the
auxiliary bus-bar. The bus-bar arrangement uses bus coupler which connects the
isolating switches and circuit breaker to the bus-bar. The bus coupler is also used for
transferring the load from one bus to another in case of overloading. The following
are the steps of transferring the load from one bus to another.
This type of arrangement requires two bus-bar and two circuit breakers. It does not
require any additional equipment like bus coupler and switch.
This type of arrangement requires two bus-bar and two circuit breakers. It does not
require any additional equipment like bus coupler and switch.
In this arrangement, three circuit breakers are required for two circuits. The each
circuit of the bus-bar uses the one and a half circuit breaker. Such type of arrangement
is preferred in large stations where power handled per circuit is large.
In such type of arrangement, the end of the bus-bar is connected back to the starting
point of the bus to form a ring.
8. Mesh Arrangement
In such type of arrangement, the circuit breakers are installed in the mesh formed by
the buses. The circuit is tapped from the node point of the mesh. Such type of bus
arrangement is controlled by four circuit breakers. When a fault occurs on any
section, two circuit breakers have to open, resulting in the opening of the mesh. Such
type of arrangement provides security against bus-bar fault but lacks switching
facility. It is preferred for substations having a large number of circuits.
The bus-bar arrangement in 400 kV GSS at 400 kV side are two main bus A and B.
Both buses are aluminium hollow pipe bus with diameter 114.2 mm and current
carrying capacity is 2000 Amp. The bus-bar arrangement at 220 kV side are three
main bus D, E and F. These are twin moose conductor bus.
Instrument transformers are high accuracy class electrical devices used to isolate or
transform voltage or current levels. The most common usage of instrument
transformers is to operate instruments or metering from high voltage or high current
circuits, safely isolating secondary control circuitry from the high voltages or
currents. The primary winding of the transformer is connected to the high voltage or
high current circuit, and the meter or relay is connected to the secondary circuit.
Type: CVE245/1050/50
Year: 2001
Frequency: 50 Hz
Capacitance C1: 4880 pF
Capacitance C2: 44455 pF
Equivalent capacitance: 4400+10% pF
Insulation level: 460/1050 kV
Emu oil: 95+10% Kg
Current transformers are the current sensing units of the power system. Current
transformers are used at generating stations, electrical substations, and in industrial
and commercial electric power distribution.
Current transformers are used extensively for measuring current and monitoring the
operation of the power grid. Along with voltage leads, revenue-grade CTs drive the
electrical utility's watt-hour meter on virtually every building with three-phase service
and single-phase services greater than 200 amperes.
Current transformers can be mounted on the low voltage or high voltage leads of a
power transformer. Sometimes a section of a bus bar can be removed to replace a
current transformer.
If protection fails or is absent, lightening that strikes the electrical system introduces
thousands of kilovolts that may damage the transmission lines, and can also cause
severe damage to transformers and other electrical or electronic devices. Lightning-
produced extreme voltage spikes in incoming power lines can damage electrical home
appliances or even produce death.
A potential target for a lightning strike, such as a television antenna, is attached to the
terminal labelled A in the photograph. Terminal E is attached to a long rod buried in
the ground. Ordinarily no current will flow between the antenna and the ground
because there is extremely high resistance between B and C, and also between C and
D. The voltage of a lightning strike, however, is many times higher than that needed
to move electrons through the two air gaps. The result is that electrons go through the
lightning arrester rather than travelling on to the television set and destroying it.
Lightning arresters built for power substation use are immense devices, consisting of
a porcelain tube several feet long and several inches in diameter, typically filled with
discs of zinc oxide. A safety port on the side of the device vents the occasional
internal explosion without shattering the porcelain cylinder.
Lightning arresters are rated by the peak current they can withstand the amount of
energy they can absorb, and the break over voltage that they require to begin
conduction. They are applied as part of a lightning protection system, in combination
with air terminals and bonding.
Circuit breaker always trip the circuit but open contacts of breaker cannot be visible
physically from outside of the breaker and that is why it is recommended not to touch
any electrical circuit just by switching off the circuit breaker. So for better safety there
must be some arrangement so that one can see open condition of the section of the
circuit before touching it. Isolator is a mechanical switch which isolates a part of
circuit from system as when required. Electrical isolators separate a part of the system
from rest for safe maintenance works.
Depending upon the position in power system, the isolators can be categorized as
1. Bus side isolator – the isolator is directly connected with main bus
2. Line side isolator – the isolator is situated at line side of any feeder
3. Transfer bus side isolator – the isolator is directly connected with transfer bus.
The female type contacts are fixed on the top of the other post insulators which fitted
at both sides of the central post insulator. The female contacts are generally in the
form of spring loaded figure contacts. The rotational movement of male contact
causes to come itself into female contacts and isolators becomes closed. The rotation
of male contact in opposite direction make to it out from female contacts and isolators
becomes open.
Rotation of the central post insulator is done by a driving lever mechanism at the base
of the post insulator and it connected to operating handle (in case of hand operation)
or motor (in case of motorized operation) of the isolator through a mechanical tie rod.
The contact arm is divided into two parts one carries male contact and other female
contact. The contact arm moves due to rotation of the post insulator upon which the
contact arms are fitted. Rotation of both post insulators stacks in opposite to each
other causes to close the isolator by closing the contact arm. Counter rotation of both
post insulators stacks open the contact arm and isolator becomes in off condition. This
motorized form of this type of isolators is generally used but emergency hand driven
mechanism is also provided.
ISO.189AT- First isolator connected ILT-1 in bay no. 1 and 89 is isolator code.
ISO.189AA- First isolator connected A bus in bay no. 1 and 89 is isolator code.
ISO.189AC- Third isolator connected tie CB in bay no. 1 and 89 is isolator code.
ISO.189BC- Fourth isolator connected tie CB in bay no. 1 and 89 is isolator code.
ISO.189BA- First isolator connected B bus in bay no. 1 and 89 is isolator code.
ISO.189BB- Second isolator connected B bus in bay no. 1 and 89 is isolator code.
ISO.189BL- Line isolator connected B bus in bay no. 1 and 89 is isolator code.
The sulphur hexafluoride gas (SF6) is an electronegative gas and has a strong
tendency to absorb free electrons. The contacts of the breaker are opened in a high
pressure flow of sulphur hexafluoride (SF6) gas and an arc is struck between them.
The gas captures the conducting free electrons in the arc to form relatively immobile
negative ions. This loss of conducting electrons in the arc quickly builds up enough
insulation strength to extinguish the arc.
The sulphur hexafluoride (SF6) circuit breakers have been found to be very effective
for high power and high voltage service.
A sulphur hexafluoride (SF6) circuit breaker consists of fixed and moving contacts
enclosed in a chamber. The chamber is called arc interruption chamber which
contains the sulphur hexafluoride (SF6) gas. This chamber is connected to sulphur
hexafluoride (SF6) gas reservoir. A valve mechanism is there to permit the gas to the
arc interruption chamber. When the contacts of breaker are opened, the valve
The fixed contact is a hollow cylindrical current carrying contact fitted with an arc
horn. The moving contact is also a hollow cylinder with rectangular holes in the sides.
The holes permit the sulphur hexafluoride gas (SF6) gas to let out through them after
flowing along and across the arc. The tips of fixed contact, moving contact and arcing
horn are coated with copper-tungsten arc resistant material. Since sulphur
hexafluoride gas (SF6) gas is costly, it is reconditioned and reclaimed using suitable
auxiliary system after each operation of breaker.
In the closed position of the breaker, the contacts remain surrounded by sulphur
hexafluoride gas (SF6) gas at a pressure of about 2.8 kg/cm2. When the breaker
operates, the moving contact is pulled apart and an arc is struck between the contacts.
The movement of the moving contact is synchronised with the opening of a valve
which permits sulphur hexafluoride gas (SF6) gas at 14 kg/cm2 pressure from the
reservoir to the arc interruption chamber.
The high pressure flow of sulphur hexafluoride gas (SF6) rapidly absorbs the free
electrons in the arc path to form immobile negative ions which are ineffective as
charge carriers. The result is that the medium between the contacts quickly builds up
high dielectric strength and causes the extinction of the arc. After the breaker
operation (i.e. after arc extinction), the valve is closed by the action of a set of springs.
Due, to the superior arc quenching properties of sulphur hexafluoride gas (SF6) gas,
the sulphur hexafluoride gas (SF6) circuit breakers have many advantages over oil or
air circuit breakers. Some of them are listed below:
An electrical insulator is a material whose internal electric charges do not flow freely;
very little electric current will flow through it under the influence of an electric field.
This contrasts with other materials, semiconductors and conductors, which conduct
electric current more easily. The property that distinguishes an insulator is its
resistivity; insulators have higher resistivity than semiconductors or conductors.
A perfect insulator does not exist, because even insulators contain small numbers of
mobile charges (charge carriers) which can carry current. In addition, all insulators
become electrically conductive when a sufficiently large voltage is applied that the
electric field tears electrons away from the atoms. This is known as the breakdown
voltage of an insulator. Some materials such as glass, paper and Teflon, which have
high resistivity, are very good electrical insulators. A much larger class of materials,
even though they may have lower bulk resistivity, are still good enough to prevent
significant current from flowing at normally used voltages, and thus are employed as
insulation for electrical wiring and cables. Examples include rubber-like polymers and
most plastics which can be thermostatic or thermoplastic in nature.
Post Insulators: Post insulator is suitable for higher voltage. It has higher numbers
of petticoats and has greater height. This type of insulator can be mounted on
supporting structure horizontally as well as vertically. The insulator is made of
one piece of porcelain and it has fixing clamp arrangement are in both top and
bottom end. For higher voltage application Two or more insulators can be fixed
together to meet the requirement.
Suspension Insulator: Using post insulator in higher voltage is not economical and
suspension type insulator is evolved. Disc insulators are connected together in
series to make a string which is suspension type insulators. As per the voltage
grade the no of disc isolators are increased or decreased so that is is suitable for
any voltage level. When suspension insulators are used a conductor is always
hanging / suspended below the metallic tower level and it is always protected
from lightning. On the other hand in order to maintain minimum clearance
between conductor and ground/ equipment the tower high uses to be higher. The
amplitude of free swing of conductors is larger in suspension insulator system,
hence, more spacing between conductors should be provided.
Stay Insulators: For low voltage lines, the stays are to be insulated from ground at
a height. The insulator used in the stay wire is called as the stay insulator and is
usually of porcelain and is so designed that in case of breakage of the insulator the
wire will not fall to the ground.
A type of relay that can handle the high power required to directly control an electric
motor or other loads is called a contractor. Solid-state relays control power circuits
with no moving parts, instead using a semiconductor device to perform switching.
Relays with calibrated operating characteristics and sometimes multiple operating
coils are used to protect electrical circuits from overload or faults; in modern electric
power systems these functions are performed by digital instruments still called
"protective relays".
Magnetic latching relays can have either single or dual coils. On a single coil device,
the relay will operate in one direction when power is applied with one polarity, and
will reset when the polarity is reversed. On a dual coil device, when polarized voltage
is applied to the reset coil the contacts will transition. AC controlled magnetic latch
relays have single coils that employ steering diodes to differentiate between operate
and reset commands.
Depending on the model, the relay has multiple methods to detect a failing
transformer. On a slow accumulation of gas, due perhaps to slight overload, gas
produced by decomposition of insulating oil accumulates in the top of the relay and
forces the oil level down. A float switch in the relay is used to initiate an alarm signal.
Depending on design, a second float may also serve to detect slow oil leaks.
If an electrical arc forms, gas accumulation is rapid, and oil flows rapidly into the
conservator. This flow of oil operates a switch attached to a vane located in the path
of the moving oil. This switch normally will operate a circuit breaker to isolate the
apparatus before the fault causes additional damage. Buchholz relays have a test port
to allow the accumulated gas to be withdrawn for testing. Flammable gas found in the
relay indicates some internal fault such as overheating or arcing, whereas air found in
the relay may only indicate low oil level or a leak.
For large Power System Power Line Carrier Communication is used for data
transmission as well as protection of Transmission Lines. Carrier current used for
Power Line carrier Communication has a frequency range of 80 to 500 kHz. PLCC in
modern electrical Power System is mainly for telemetry and tele-control. Power Line
Carrier Communication is used for the Carrier Tripping and Direct Tripping in case of
Distance Protection. For detail of how does Distance protection relay sends and
receives carrier signal, read Distance Protection.
Wave Trap: Wave Trap is provided in the line after the CVT (If we see from
Transmission line side then CVT will come first and then CVT will come.). Wave
Trap is nothing but a Choke Coil which chokes out high frequency carrier signal,
as the impedance offered by inductor = wL will be high which will not allow the
high frequency carrier signal to enter into the substation.
Transmitters and Receivers: The carrier Transmitters and Receivers are usually
mounted in a rack or cabinet in the control room, and the line tuner is out in the
switchyard. Thus there is a large distance between the equipment and the tuner,
and the connection between the two is made using a coaxial cable Fibre Optical
Hybrids and Filters: The purpose of the hybrid circuits is to enable the connection
of two or more transmitters together on one coaxial cable without causing
intermediation distortion due to the signal from one transmitter affecting the
output stages of the other transmitter. Hybrids may also be required between
transmitters and receivers, depending on the application.
Line Matching Unit LMU: LMU is a composite unit consisting of Drain Coil,
Isolation transformer with Lightning Arrester on its both the sides, a Tuning
Device and an earth switch. Tuning Device is the combination of R-L-C circuits
which act as filter circuit. LMU is also known as Coupling Device. Together with
coupling capacitor, LMU serves the purpose of connecting Audio/Radio
frequency signals to PLCC terminal and protection of the PLCC unit from the
over voltages caused due to transients on power system.
Over all, this training has helped me broaden my perspective of transmission and
distribution of an electrical power and helped me think more professionally.
1. energy.rajasthan.gov.in/content/dam/raj/energy/...one.../Load_dispatch_manual.pd
f
2. http://rerc.rajasthan.gov.in/cnpl/PDFs/rvpninvest.pdf
3. http://energy.rajasthan.gov.in/content/dam/raj/energy/corporate-one-lines-
viewer/pdf/ordercirculars/Secadmin/others/76_24062016.pdf