IECEx Certificate

of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

Certificate No.: IECEx PTB 09.0039U Issue No: 1 Certificate history:


Issue No. 1 (2014-08-19)
Status: Current Page 1 of 4 Issue No. 0 (2009-11-12)

Date of Issue: 2014-08-19

Applicant: Pentair Thermal Management, LLC


307 Constitution Drive
CA 940245-1164 Menlo Park
United States of America

Electrical Apparatus: Terminal/connection JBU-100-..


Optional accessory:

Type of Protection: Increased Safety 'e', Encapsulation 'mb', Protection by enclosure 'tD', Protection by encapsulation 'mbD'

Marking: Ex e (e mb) II
Ex tD (tD mbD) A21 IP66

Approved for issue on behalf of the IECEx Dr.-Ing. U. Klausmeyer


Certification Body:

Position: Head of Department Explosion Protection in Energy Technology

Signature:
(for printed version)

Date:

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.

Certificate issued by:


Physikalisch-Technische Bundesanstalt (PTB)
Bundesallee 100
38116 Braunschweig
Germany
IECEx Certificate
of Conformity
Certificate No: IECEx PTB 09.0039U Issue No: 1

Date of Issue: 2014-08-19 Page 2 of 4

Manufacturer: Pentair Thermal Management, LLC


307 Constitution Drive
CA 940245-1164 Menlo Park
United States of America

Additional Manufacturing
location(s):

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx
Scheme Rules, IECEx 02 and Operational Documents as amended.

STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was
found to comply with the following standards:

IEC 60079-0 : 2004 Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
Edition:4.0
IEC 60079-18 : 2004 Electrical apparatus for explosive gas atmospheres - Part 18: Construction, test and marking of type of
Edition:2.0 protection encapsulation 'm' electrical apparatus
IEC 60079-7 : 2006-07 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
Edition:4
IEC 61241-0 : 2004 Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
Edition:1
IEC 61241-1 : 2004 Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
Edition:1
IEC 61241-18 : 2004 Electrical apparatus for use in the pressence of combustible dust - Part 18: Protection by encapsulation
Edition:1.0 "mD"

This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the

Standards listed above.

TEST & ASSESSMENT REPORTS:


A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in

Test Report:

DE/PTB/ExTR09.0045/01

Quality Assessment Report:

GB/BAS/QAR06.0030/04
IECEx Certificate
of Conformity
Certificate No: IECEx PTB 09.0039U Issue No: 1

Date of Issue: 2014-08-19 Page 3 of 4

Schedule

EQUIPMENT:
Equipment and systems covered by this certificate are as follows:

Description of Equipment and technical data see attachment

CONDITIONS OF CERTIFICATION: NO
IECEx Certificate
of Conformity
Certificate No: IECEx PTB 09.0039U Issue No: 1

Date of Issue: 2014-08-19 Page 4 of 4

DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):


Change of Company Name.

Annex:

CoCA 09.0039 Issue No. 1.pdf


Attachment to Certificate
IECEx PTB 09.0039U, Issue No. 1

Applicant: Pentair Thermal Management, LLC


307 Constitution Drive
CA 940245-1164 Menlo Park
United States of America

Electrical Apparatus: Terminal/connection system, type JBU-100-..


Description of equipment
Terminal/connection system, type JBU-100-.. for trace heating systems of Pentair Thermal
Management.

Technical data

Strip heater type Rated voltage *


BTV, QTVR, XTV, KTV max. 277 V
VPL1 max. 110 V
VPL2 max. 230 / 254 V
VPL4 + FHPC max. 480 V
* subject to protection and max. permissible rated current, max. permissible temperature of the
surface to be heated;
see data sheets and operating instructions of the manufacturer!

Ambient temperatures -50 … +56 °C /


-40 … +40 °C (version with pilot lamp)
Notes for manufacturing, installation and operation
1. The manufacturer's instructions for operation must be followed.
2. The parallel strip heaters, types VPL and FHPC, have to be installed so that their cold
ends start outside the terminal box.
3. If JBU-100-.. with voltage infeed is installed, an adequate heat-resistant feeder and
screwed metal glands, incl. gasket, must be used at 40 °C < Ta < 56 °C. For the
screwed metal glands, incl. gasket a separate EC-Type Examination Certificate must
have been issued and they must have been verified by Pentair Thermal Management.
4. For heating cables, certified Pentair Thermal Management glands of type C25-100-
METAL (screwed metal gland, incl. gasket) must be used at 40 °C < Ta < 56 °C .
5. Restrictions regarding the use of type JBU-100-L (with pilot lamp) have to be specified
by the manufacturer and must be complied with by the installer/user.
6. Alternative strip heaters must not be used, unless the manufacturer's approval has
been obtained.
7. The temperature accepted as a maximum for the surface to be heated (tube tempera-
ture) shall be determined on the basis of the specific performance category, the max.
admissible operating temperature of the parallel strip heater, the voltage rating, and the
max. admissible current carrying capacity.