of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com
Type of Protection: Increased Safety 'e', Electrical Resistance Trace Heating, Protection by enclosures 'tD'
Marking:
Ex e II T6
Ex tD A21 IP66 T80 °C
Signature:
(for printed version)
Date:
Additional Manufacturing
location(s):
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx
Scheme Rules, IECEx 02 and Operational Documents as amended.
STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was
found to comply with the following standards:
IEC 60079-0 : 2004 Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
Edition:4.0
IEC 60079-30-1 : 2007-01 Explosive atmospheres - Part 30-1: Electrical resistance trace heating - General and testing requirements
Edition:1
IEC 60079-7 : 2006-07 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
Edition:4
IEC 61241-0 : 2004 Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
Edition:1
IEC 61241-1 : 2004 Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
Edition:1
This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the
Test Report:
DE/PTB/ExTR09.0065/00
GB/BAS/QAR06.0030/03
IECEx Certificate
of Conformity
Certificate No: IECEx PTB 09.0056X Issue No: 0
Schedule
EQUIPMENT:
Equipment and systems covered by this certificate are as follows:
Description of equipment
The type BTV trace heating system is used for heating pipes and tanks in zone 1.
It consists of a self-regulating product line BTV2 heating cable and various termination, end sealing, and, if required, connection
components.
Technical data
Rated voltage max. 254 V or 277 V (see table)
Rated current see installation instructions for the components concerned
Min. ambient temperature -40 °C or -50 °C (see table)
Max. ambient temperature +40 °C or +56 °C (see table)
Min. bending radius 35 mm
Description of equipment, technical data, a list of components and schedule of limitations see Annex
Annex:
Description of equipment
The type BTV trace heating system is used for heating pipes and tanks in zone 1.
It consists of a self-regulating product line BTV2 heating cable and various termination, end
sealing, and, if required, connection components.
Technical data
Rated voltage max. 254 V or 277 V (see table)
Rated current see installation instructions for the components concerned
Min. ambient temperature -40 °C or -50 °C (see table)
Max. ambient temperature +40 °C or +56 °C (see table)
Min. bending radius 35 mm
Min. installation temperature for the heating cable -60 °C
List of components
* Maximum values! Rated voltage and ambient temperature may be subject to res-
ervations; see data sheets/instructions for operation of the components concerned
Schedule of Limitations
1. Only adequately trained expert staff may be entrusted with planning, selection and instal-
lation work.
2. The instructions for installation in the relevant EC-Type-Examination Certificate must be
followed.
3. The instructions for installation of the trace heating system and the used components
must be complied with. They also contain additional information regarding the technical
data.
4. The system has only been approved for heating cable with outer sheath (types -CR and -
CT).
5. The protection measures EN 60079-30-1 specifies for limitation of unacceptably high
leakage currents have to be considered.