 CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO V

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 01 KITENI ESTRATO 01 KM 268+500

P. MOLDE + S. HUMEDO gr. 11,200 11,455 11,575 11,500


PESO MOLDE gr. 6,577 6,577 6,577 6,577
PESO SUELO HUMEDO gr. 4,623 4,878 4,998 4,923

N° TARRO C2 M1 A1 A2 A3 A4 P2 25
P. TARRO + S. HUMEDO gr. 73.3 106.3 65.5 46.2 104.4 106.0 107.4 106.0

P. TARRO + S. SECO gr. 71.3 103.5 62.9 44.5 98.6 99.9 100.0 98.5
PESO DE AGUA gr. 2.1 2.9 2.6 1.7 5.8 6.1 7.4 7.5
PESO DE TARRO gr. 24.7 38.8 24.6 20.8 36.7 33.1 36.6 32.5
PESO SUELO SECO gr. 46.6 64.7 38.3 23.8 61.9 66.8 63.4 66.0
% DE HUMEDAD % 4.4 4.4 6.8 7.1 9.4 9.1 11.6 11.3

PROMEDIO DE HUMEDAD % 4.4 7.0 9.3 11.5


DENSIDAD SUELO HUMEDO gr./cm3. 2.177 2.297 2.353 2.318
DENSIDAD SECA gr/cm3. 2.085 2.147 2.153 2.079
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.20
MAX. DENSIDAD SECA gr./cm³ : 2.15

OPTIMO CONTENIDO HUMEDAD % : 7.0


2.18
VOLUMEN MOLDE cm³ : 2,124

2.15 1
1

2.13

2.10

2.08

2.05
3.0 4.0 5.0 6.0 7.0 HUMEDAD
8.0 (%)
9.0 10.0 11.0 12.0 13.0
BR. CARLOS FREDY CALDERON MASIAS                                                                                                         
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO VI ­

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 01 KITENI ESTRATO 02 KM 268+500

P. MOLDE + S. HUMEDO gr. 11,180 11,545 11,580 11,480


PESO MOLDE gr. 6,577 6,577 6,577 6,577

PESO SUELO HUMEDO gr. 4,603 4,968 5,003 4,903


N° TARRO C2 M1 A1 A2 A3 A4 P2 25

P. TARRO + S. HUMEDO gr. 98.4 103.6 45.0 46.7 66.7 63.8 104.6 107.5
P. TARRO + S. SECO gr. 97.4 102.9 43.6 45.0 63.1 60.2 98.3 101.6

PESO DE AGUA gr. 0.9 0.7 1.4 1.7 3.6 3.6 6.3 5.9
PESO DE TARRO gr. 73.4 86.0 22.4 20.6 25.6 23.2 39.2 48.5
PESO SUELO SECO gr. 24.0 17.0 21.2 24.4 37.5 37.0 59.2 53.1
% DE HUMEDAD % 4.0 4.2 6.6 6.9 9.7 9.8 10.7 11.1
PROMEDIO DE HUMEDAD % 4.1 6.8 9.7 10.9

DENSIDAD SUELO HUMEDO gr./cm3. 2.167 2.339 2.355 2.308


DENSIDAD SECA gr/cm3. 2.082 2.190 2.147 2.081
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.25
MAX. DENSIDAD SECA gr./cm³ : 2.19

2.23
OPTIMO CONTENIDO HUMEDAD % : 6.5

VOLUMEN MOLDE cm³ : 2,124


2.20
1
1

2.18

2.15

2.13

2.10

2.08

2.05
2.0 3.0 4.0 5.0 6.0 HUMEDAD
7.0 8.0 (%)9.0 10.0 11.0 12.0 13.0

BR. CARLOS FREDY CALDERON MASIAS                                                                                                            
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO V

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 02 PLAYA KITENI KM 266+000

P. MOLDE + S. HUMEDO gr. 10,831 11,225 11,394 11,134


PESO MOLDE gr. 6,572 6,572 6,572 6,572
PESO SUELO HUMEDO gr. 4,259 4,653 4,822 4,562
N° TARRO B2 P9 C16 P3 P6 M1 P7 E2
P. TARRO + S. HUMEDO gr. 62.2 86.8 78.8 100.2 82.2 103.5 108.9 94.5
P. TARRO + S. SECO gr. 60.6 84.0 75.2 95.1 76.6 96.3 100.4 87.7

PESO DE AGUA gr. 1.7 2.8 3.6 5.1 5.6 7.2 8.5 6.8
PESO DE TARRO gr. 33.1 39.3 36.6 40.0 33.3 39.2 48.6 47.3
PESO SUELO SECO gr. 27.5 44.7 38.6 55.1 43.3 57.1 51.8 40.5

% DE HUMEDAD % 6.0 6.3 9.4 9.3 12.8 12.5 16.4 16.8


PROMEDIO DE HUMEDAD % 6.2 9.4 12.7 16.6
DENSIDAD SUELO HUMEDO gr./cm3. 2.005 2.191 2.270 2.148
DENSIDAD SECA gr/cm3. 1.888 2.003 2.014 1.842
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.15
MAX. DENSIDAD SECA gr./cm³ : 2.05

OPTIMO CONTENIDO HUMEDAD % : 10.8


2.10
VOLUMEN MOLDE cm³ : 2,124

2.05 1
1

2.00

1.95

1.90

1.85

1.80
5.0 6.0 7.0 8.0 9.0 10.0 11.0HUMEDAD
12.0 13.0 (%)
14.0 15.0 16.0 17.0 18.0 19.0 20.0
BR. CARLOS FREDY CALDERON MASIAS                                                                                                         
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO V

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 03 KAMONASHIARI ESTRATO 01 KM 264+000

P. MOLDE + S. HUMEDO gr. 11,124 11,417 11,580 11,400


PESO MOLDE gr. 6,653 6,653 6,653 6,653
PESO SUELO HUMEDO gr. 4,471 4,764 4,927 4,747
N° TARRO A1 A2 A3 A4 C2 25 P2 M1
P. TARRO + S. HUMEDO gr. 47.1 55.8 63.1 72.0 86.0 103.8 107.5 98.9
P. TARRO + S. SECO gr. 45.8 53.9 60.5 68.6 85.0 99.5 100.4 92.6

PESO DE AGUA gr. 1.3 1.9 2.6 3.4 1.0 4.3 7.1 6.3
PESO DE TARRO gr. 22.4 20.6 25.6 23.2 73.4 48.5 39.2 39.0
PESO SUELO SECO gr. 23.4 33.3 34.9 45.4 11.6 51.0 61.3 53.6

% DE HUMEDAD % 5.6 5.7 7.4 7.6 8.8 8.4 11.5 11.8


PROMEDIO DE HUMEDAD % 5.7 7.5 8.6 11.7
DENSIDAD SUELO HUMEDO gr./cm3. 2.105 2.243 2.320 2.235
DENSIDAD SECA gr/cm3. 1.991 2.087 2.136 2.001
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.20
MAX. DENSIDAD SECA gr./cm³ : 2.11
2.18
OPTIMO CONTENIDO HUMEDAD % : 8.4
2.15
VOLUMEN MOLDE cm³ : 2,124
2.13
1
1

2.10

2.08

2.05

2.03

2.00

1.98

1.95

1.93

1.90
4.0 5.0 6.0 7.0 HUMEDAD
8.0 9.0 (%) 10.0 11.0 12.0 13.0
BR. CARLOS FREDY CALDERON MASIAS                                                                                                         
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO VI ­

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 03 KAMONASHIARI ESTRATO 02 KM 264+000

P. MOLDE + S. HUMEDO gr. 11,320 11,510 11,680 11,620


PESO MOLDE gr. 6,653 6,653 6,653 6,653

PESO SUELO HUMEDO gr. 4,667 4,857 5,027 4,967


N° TARRO A1 A2 A3 A4 C2 25 P2 M1

P. TARRO + S. HUMEDO gr. 47.3 55.1 63.1 72.0 86.3 103.2 108.5 99.2
P. TARRO + S. SECO gr. 46.3 53.7 61.2 69.4 85.3 98.8 102.1 93.7

PESO DE AGUA gr. 1.0 1.4 1.9 2.6 1.0 4.4 6.4 5.5
PESO DE TARRO gr. 22.4 20.6 25.6 23.2 73.4 48.5 39.2 39.0
PESO SUELO SECO gr. 23.9 33.1 35.6 46.2 11.9 50.3 63.0 54.7
% DE HUMEDAD % 4.2 4.2 5.3 5.7 8.4 8.8 10.2 10.1
PROMEDIO DE HUMEDAD % 4.2 5.5 8.6 10.1

DENSIDAD SUELO HUMEDO gr./cm3. 2.197 2.287 2.367 2.339


DENSIDAD SECA gr/cm3. 2.108 2.168 2.180 2.124
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.25
MAX. DENSIDAD SECA gr./cm³ : 2.19

OPTIMO CONTENIDO HUMEDAD % : 6.8


2.23

VOLUMEN MOLDE cm³ : 2,124


2.20
1
1

2.18

2.15

2.13

2.10

2.08

2.05
1.0 2.0 3.0 4.0 5.0 HUMEDAD
6.0 7.0 (%)
8.0 9.0 10.0 11.0 12.0 13.0

BR. CARLOS FREDY CALDERON MASIAS                                                                                                            
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO V

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 04 VENECIA KM 262+000

P. MOLDE + S. HUMEDO gr. 10,750 11,370 11,500 11,248


PESO MOLDE gr. 6,600 6,600 6,600 6,600
PESO SUELO HUMEDO gr. 4,150 4,770 4,900 4,648
N° TARRO M2 A8 P3 B5 J4 D2 C16 P8
P. TARRO + S. HUMEDO gr. 72.0 98.9 57.7 51.5 105.0 104.9 106.1 100.8
P. TARRO + S. SECO gr. 69.6 95.7 55.2 49.1 97.5 96.8 95.1 90.4

PESO DE AGUA gr. 2.4 3.2 2.5 2.4 7.5 8.1 11.0 10.4
PESO DE TARRO gr. 24.7 38.5 24.6 20.8 36.7 33.1 36.6 32.5
PESO SUELO SECO gr. 44.9 57.3 30.6 28.4 60.8 63.7 58.5 57.9

% DE HUMEDAD % 5.3 5.6 8.2 8.3 12.3 12.7 18.8 18.0


PROMEDIO DE HUMEDAD % 5.5 8.3 12.5 18.4
DENSIDAD SUELO HUMEDO gr./cm3. 1.954 2.246 2.307 2.188
DENSIDAD SECA gr/cm3. 1.852 2.074 2.051 1.848
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.20
MAX. DENSIDAD SECA gr./cm³ : 2.09
2.18
2.15 OPTIMO CONTENIDO HUMEDAD % : 10.2
2.13
VOLUMEN MOLDE cm³ : 2,124
2.10
1
1

2.08
2.05

2.03
2.00
1.98

1.95
1.93

1.90
1.88
1.85
1.83
1.80

1.78
1.75
5.0 6.0 7.0 8.0 9.0 10.0 11.0HUMEDAD
12.0 13.0 (%)
14.0 15.0 16.0 17.0 18.0 19.0 20.0
BR. CARLOS FREDY CALDERON MASIAS                                                                                                         
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO VI ­

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 05 PROGRESO ESTRATO 01 KM 260+000

P. MOLDE + S. HUMEDO gr. 11,300 11,680 11,850 11,597


PESO MOLDE gr. 6,577 6,577 6,577 6,577

PESO SUELO HUMEDO gr. 4,723 5,103 5,273 5,020


N° TARRO M2 A8 P3 B5 J4 D2 C16 P8

P. TARRO + S. HUMEDO gr. 46.9 88.1 51.1 45.9 90.9 93.8 107.8 96.6
P. TARRO + S. SECO gr. 45.9 85.8 49.5 44.4 86.9 89.6 101.3 90.8

PESO DE AGUA gr. 1.1 2.3 1.6 1.4 4.0 4.3 6.6 5.9
PESO DE TARRO gr. 24.7 38.5 24.6 20.8 36.7 33.1 36.6 32.5
PESO SUELO SECO gr. 21.2 47.4 24.9 23.7 50.2 56.4 64.7 58.3
% DE HUMEDAD % 5.0 4.8 6.4 6.1 7.9 7.6 10.2 10.1
PROMEDIO DE HUMEDAD % 4.9 6.3 7.7 10.1

DENSIDAD SUELO HUMEDO gr./cm3. 2.224 2.403 2.483 2.363


DENSIDAD SECA gr/cm3. 2.120 2.261 2.305 2.146
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.45
MAX. DENSIDAD SECA gr./cm³ : 2.30
2.43

2.40 OPTIMO CONTENIDO HUMEDAD % : 6.7


2.38
VOLUMEN MOLDE cm³ : 2,124
2.35
2.33

2.30 1
1

2.28

2.25

2.23

2.20
2.18

2.15
2.13

2.10

2.08

2.05
2.03

2.00
2.0 3.0 4.0 5.0 6.0 HUMEDAD
7.0 (%)
8.0 9.0 10.0 11.0 12.0

BR. CARLOS FREDY CALDERON MASIAS                                                                                                            
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO 

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 05 PROGRESO ESTRATO 02 KM 260+000

P. MOLDE + S. HUMEDO gr. 11,420 11,600 11,690 11,700


PESO MOLDE gr. 6,653 6,653 6,653 6,653
PESO SUELO HUMEDO gr. 4,767 4,947 5,037 5,047
N° TARRO M2 A8 P3 B5 J4 D2 C16 P8
P. TARRO + S. HUMEDO gr. 46.9 88.1 51.1 45.9 90.9 93.8 107.8 96.6
P. TARRO + S. SECO gr. 45.9 85.9 49.7 44.7 86.6 88.9 101.8 91.0

PESO DE AGUA gr. 1.0 2.2 1.4 1.2 4.3 4.9 6.0 5.6
PESO DE TARRO gr. 24.7 38.5 24.6 20.8 36.7 33.1 36.6 32.5
PESO SUELO SECO gr. 21.2 47.5 25.1 24.0 49.9 55.8 65.2 58.5

% DE HUMEDAD % 4.9 4.6 5.6 4.8 8.5 8.8 9.2 9.6


PROMEDIO DE HUMEDAD % 4.7 5.2 8.7 9.4
DENSIDAD SUELO HUMEDO gr./cm3. 2.244 2.329 2.371 2.376
DENSIDAD SECA gr/cm3. 2.143 2.214 2.181 2.172
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.45
MAX. DENSIDAD SECA gr./cm³ : 2.29
2.43
OPTIMO CONTENIDO HUMEDAD % : 6.8
2.40

2.38 VOLUMEN MOLDE cm³ : 2,124


2.35

2.33

2.30
1
1

2.28

2.25

2.23

2.20

2.18

2.15

2.13

2.10

2.08

2.05
3.0 4.0 5.0 HUMEDAD
6.0 7.0(%) 8.0 9.0 10.0
BR. CARLOS FREDY CALDERON MASIAS                                                                                                        
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO V

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 06 DUCHISELA KM 256+000

P. MOLDE + S. HUMEDO gr. 11,160 11,498 11,620 11,550


PESO MOLDE gr. 6,577 6,577 6,577 6,577
PESO SUELO HUMEDO gr. 4,583 4,921 5,043 4,973

N° TARRO M2 A8 P3 B5 J4 D2 C16 P8
P. TARRO + S. HUMEDO gr. 73.3 106.3 65.5 46.2 104.4 106.0 107.4 106.0

P. TARRO + S. SECO gr. 71.3 103.5 62.9 44.5 98.2 99.1 98.6 96.8
PESO DE AGUA gr. 2.1 2.9 2.6 1.7 6.3 6.9 8.8 9.2
PESO DE TARRO gr. 24.7 38.5 24.6 20.8 36.7 33.1 36.6 32.5
PESO SUELO SECO gr. 46.6 65.0 38.3 23.8 61.5 66.0 62.0 64.3
% DE HUMEDAD % 4.4 4.4 6.8 7.1 10.2 10.4 14.2 14.3

PROMEDIO DE HUMEDAD % 4.4 7.0 10.3 14.2


DENSIDAD SUELO HUMEDO gr./cm3. 2.158 2.317 2.374 2.341
DENSIDAD SECA gr/cm3. 2.067 2.165 2.152 2.050
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.25
MAX. DENSIDAD SECA gr./cm³ : 2.15

2.23 OPTIMO CONTENIDO HUMEDAD % : 7.6

VOLUMEN MOLDE cm³ : 2,124


2.20

2.18

2.15 1
1

2.13

2.10

2.08

2.05

2.03

2.00
3.0 4.0 5.0 6.0 7.0 8.0HUMEDAD
9.0 (%) 11.0
10.0 12.0 13.0 14.0 15.0

BR. CARLOS FREDY CALDERON MASIAS                                                                                                         
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO V

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 07 MORRO CIRIALO KM 251+000

P. MOLDE + S. HUMEDO gr. 10,779 11,350 11,400 11,120

PESO MOLDE gr. 6,577 6,577 6,577 6,577


PESO SUELO HUMEDO gr. 4,202 4,773 4,823 4,543

N° TARRO B1 B4 B3 M01 P62 P61 D1 D2


P. TARRO + S. HUMEDO gr. 70.6 67.1 62.2 67.7 61.6 70.5 107.1 103.6
P. TARRO + S. SECO gr. 68.1 64.7 59.0 64.8 57.8 66.4 100.6 96.8
PESO DE AGUA gr. 2.5 2.4 3.2 2.9 3.8 4.1 6.5 6.8
PESO DE TARRO gr. 21.3 21.2 21.1 30.5 21.1 26.0 49.9 42.9

PESO SUELO SECO gr. 46.8 43.5 37.9 34.3 36.7 40.4 50.8 53.9
% DE HUMEDAD % 5.3 5.6 8.5 8.3 10.4 10.3 12.7 12.5
PROMEDIO DE HUMEDAD % 5.5 8.4 10.3 12.6
DENSIDAD SUELO HUMEDO gr./cm3. 1.978 2.247 2.271 2.139
DENSIDAD SECA gr/cm3. 1.875 2.073 2.059 1.900
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.20
MAX. DENSIDAD SECA gr./cm³ : 2.08
2.18
OPTIMO CONTENIDO HUMEDAD % : 9.2
2.15

2.13 VOLUMEN MOLDE cm³ : 2,124


2.10
1
1

2.08

2.05

2.03

2.00

1.98

1.95

1.93

1.90

1.88

1.85

1.83

1.80
4.0 5.0 6.0 7.0 8.0 HUMEDAD
9.0 10.0 (%)
11.0 12.0 13.0 14.0 15.0

BR. CARLOS FREDY CALDERON MASIAS                                                                                                         
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO 

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 08 CIRIALO ESTRATO 01 KM 249+000

P. MOLDE + S. HUMEDO gr. 10,980 11,290 11,390 11,327


PESO MOLDE gr. 6,653 6,653 6,653 6,653

PESO SUELO HUMEDO gr. 4,327 4,637 4,737 4,674


N° TARRO C2 M11 A1 A2 A3 A4 A8 M2
P. TARRO + S. HUMEDO gr. 73.4 96.0 50.3 50.9 46.4 61.6 100.0 67.0
P. TARRO + S. SECO gr. 71.0 92.2 47.9 48.4 44.5 58.0 91.6 62.7
PESO DE AGUA gr. 2.4 3.8 2.4 2.5 1.9 3.6 8.5 4.3
PESO DE TARRO gr. 37.1 39.0 22.4 20.6 25.6 23.2 38.6 34.6

PESO SUELO SECO gr. 33.9 53.2 25.5 27.8 18.9 34.8 53.0 28.2
% DE HUMEDAD % 7.2 7.0 9.5 9.1 10.3 10.3 15.9 15.3
PROMEDIO DE HUMEDAD % 7.1 9.3 10.3 15.6

DENSIDAD SUELO HUMEDO gr./cm3. 2.037 2.183 2.230 2.201


D E N S ID A D S E C A ( K g /c m ³ )

DENSIDAD SECA gr/cm3. 1.902 1.997 2.022 1.904

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56

MAX. DENSIDAD SECA gr./cm³ : 2.03


2.10
OPTIMO CONTENIDO HUMEDAD % : 10.0
2.08

2.05 VOLUMEN MOLDE cm³ : 2,124


1
1

2.03

2.00

1.98

1.95

1.93

1.90

1.88

1.85

1.83

1.80
5.0 6.0 7.0 8.0 9.0 10.0 11.0HUMEDAD
12.0 13.0 (%)
14.0 15.0 16.0 17.0 18.0 19.0 20.0

BR. CARLOS FREDY CALDERON MASIAS                                                                                                        
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO VI ­

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 08 CIRIALO ESTRATO 02 KM 249+000

P. MOLDE + S. HUMEDO gr. 11,300 11,540 11,640 11,580

PESO MOLDE gr. 6,653 6,653 6,653 6,653


PESO SUELO HUMEDO gr. 4,647 4,887 4,987 4,927

N° TARRO C2 M11 A1 A2 A3 A4 A8 M2
P. TARRO + S. HUMEDO gr. 72.5 93.4 52.4 53.2 46.0 63.0 95.0 69.0

P. TARRO + S. SECO gr. 70.5 90.2 50.1 50.7 44.1 59.2 88.7 65.2
PESO DE AGUA gr. 2.0 3.2 2.3 2.5 1.9 3.8 6.3 3.8
PESO DE TARRO gr. 37.1 39.0 22.4 20.6 25.6 23.2 38.6 34.6

PESO SUELO SECO gr. 33.4 51.2 27.7 30.1 18.5 36.0 50.2 30.7
% DE HUMEDAD % 6.0 6.3 8.3 8.4 10.3 10.6 12.6 12.4

PROMEDIO DE HUMEDAD % 6.1 8.4 10.4 12.5


DENSIDAD SUELO HUMEDO gr./cm3. 2.188 2.301 2.348 2.320
DENSIDAD SECA gr/cm3. 2.062 2.123 2.127 2.062
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.15
MAX. DENSIDAD SECA gr./cm³ : 2.11

OPTIMO CONTENIDO HUMEDAD % : 9.5


2.13 VOLUMEN MOLDE cm³ : 2,124

1
1

2.10

2.08

2.05

2.03

2.00
5.0 6.0 7.0 8.0 9.0 HUMEDAD
10.0 (%)
11.0 12.0 13.0 14.0 15.0

BR. CARLOS FREDY CALDERON MASIAS                                                                                                            
PROYECTO DE TESIS: MEJOR. CARRETERA TRAMO "CIRIALO KITENI"                                               ESTUDIO GEOTECNICO Y PAVIMENTO V

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 09 CANTERA KINCURI KM 253+880

P. MOLDE + S. HUMEDO gr. 11,320 11,525 11,720 11,600


PESO MOLDE gr. 6,653 6,653 6,653 6,653

PESO SUELO HUMEDO gr. 4,667 4,872 5,067 4,947


N° TARRO 2 6 7 4 1 8 1 6
P. TARRO + S. HUMEDO gr. 72.5 93.5 52.3 49.5 42.6 62.5 99.5 66.5

P. TARRO + S. SECO gr. 71.0 91.1 50.7 48.1 41.3 59.5 93.6 63.5
PESO DE AGUA gr. 1.5 2.4 1.6 1.4 1.3 3.0 5.9 3.0
PESO DE TARRO gr. 37.1 39.0 22.4 20.6 25.6 23.2 38.6 34.6
PESO SUELO SECO gr. 33.9 52.1 28.3 27.5 15.7 36.3 55.1 29.0

% DE HUMEDAD % 4.4 4.6 5.7 5.1 8.0 8.1 10.6 10.2


PROMEDIO DE HUMEDAD % 4.5 5.4 8.0 10.4
DENSIDAD SUELO HUMEDO gr./cm3. 2.197 2.294 2.386 2.329
DENSIDAD SECA gr/cm3. 2.102 2.176 2.209 2.110
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.30
MAX. DENSIDAD SECA gr./cm³ : 2.23

2.28 OPTIMO CONTENIDO HUMEDAD % : 6.5

VOLUMEN MOLDE cm³ : 2,124


2.25

1
1

2.23

2.20

2.18

2.15

2.13

2.10

2.08

2.05
2.0 3.0 4.0 5.0 6.0 HUMEDAD
7.0 (%)
8.0 9.0 10.0 11.0 12.0
BR. CARLOS FREDY CALDERON MASIAS                                                                                                         
PROYECTO DE TESIS: "SISTEMA DE RIEGO POR ASPERSION PICOL ­ QUERAPATA"                                                                    

UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : Sistema de Riego por Aspersión Picol - Querapata

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BR. PABLO HUAMAN RIVAS Y BR. IVAN ORMACHEA ZANABRIA

CALICATA : 01

P. MOLDE + S. HUMEDO gr. 11,132 11,238 10,988


PESO MOLDE gr. 6,605 6,605 6,605
PESO SUELO HUMEDO gr. 4,527 4,633 4,383 0
N° TARRO 3 2 5 4 6 1 1 6
P. TARRO + S. HUMEDO gr. 43.7 54.2 91.9 69.1 107.1 124.8
P. TARRO + S. SECO gr. 41.4 52.3 85.3 64.4 101.0 116.1
PESO DE AGUA gr. 2.3 1.9 6.6 4.7 6.1 8.7 0.0 0.0
PESO DE TARRO gr. 19.2 33.1 42.4 33.0 66.6 66.5
PESO SUELO SECO gr. 22.3 19.2 42.9 31.5 34.4 49.6 0.0 0.0
% DE HUMEDAD % 10.3 10.0 15.3 15.0 17.7 17.5 #DIV/0! #DIV/0!
PROMEDIO DE HUMEDAD % 10.1 15.2 17.6 #DIV/0!
DENSIDAD SUELO HUMEDO gr./cm3. 2.131 2.181 2.064 0.000
DENSIDAD SECA gr/cm3. 1.936 1.893 1.755 #DIV/0!
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.15
MAX. DENSIDAD SECA gr./cm³ : 2.12

OPTIMO CONTENIDO HUMEDAD % : 7.3


2.13 VOLUMEN MOLDE cm³ : 2,124
1
1

2.10

2.08

2.05

2.03

2.00
2.0 3.0 4.0 5.0 6.0 HUMEDAD
7.0 8.0 (%)9.0 10.0 11.0 12.0 13.0

BR. PABLO HUAMAN RIVAS BR. IVAN ORMACHEA ZANABRIA


UNIVERSIDAD NACIONAL DE SAN ANTONIO ABAD DEL CUSCO

FACULTAD DE INGENIERIA CIVIL

PROYECTO : MEJORAMIENTO DE LA CARRETERA QUILLABAMBA KITENI TRAMO CIRIALO KITENI

RELACION HUMEDAD - DENSIDAD


ASTM D-1557

TESISTAS : BH. CARLOS F. CALDERON MASIAS Y BH. MIGUEL A. TTITO CCAMA

CALICATA : 15 CANTERA AGREGADOS KITENI

P. MOLDE + S. HUMEDO gr. 11,350 11,635 11,750 11,680


PESO MOLDE gr. 6,653 6,653 6,653 6,653
PESO SUELO HUMEDO gr. 4,697 4,982 5,097 5,027
N° TARRO 2 6 7 4 1 8 1 6
P. TARRO + S. HUMEDO gr. 73.2 91.2 53.3 48.5 43.0 63.1 99.5 66.5
P. TARRO + S. SECO gr. 72.0 89.5 51.7 47.1 41.7 60.0 93.6 63.5
PESO DE AGUA gr. 1.2 1.7 1.6 1.4 1.3 3.1 5.9 3.0
PESO DE TARRO gr. 37.1 39.0 22.4 20.6 25.6 23.2 38.6 34.6
PESO SUELO SECO gr. 34.9 50.5 29.3 26.5 16.1 36.8 55.1 29.0
% DE HUMEDAD % 3.4 3.4 5.5 5.3 8.1 8.4 10.6 10.2
PROMEDIO DE HUMEDAD % 3.4 5.4 8.3 10.4
DENSIDAD SUELO HUMEDO gr./cm3. 2.211 2.346 2.400 2.367
DENSIDAD SECA gr/cm3. 2.138 2.226 2.216 2.144
D EN SID A D SEC A (K g /cm ³)

METODO DE COMPACTACION : "C"

NUMERO DE CAPAS : 5

NUMERO DE GOLPES : 56
2.30
MAX. DENSIDAD SECA gr./cm³ : 2.24

2.28 OPTIMO CONTENIDO HUMEDAD % : 5.8

VOLUMEN MOLDE cm³ : 2,124


2.25
1
1

2.23

2.20

2.18

2.15

2.13

2.10

2.08

2.05
2.0 3.0 4.0 5.0 6.0 HUMEDAD
7.0 (%)
8.0 9.0 10.0 11.0 12.0
2.10

2.08

2.05
2.0 3.0 4.0 5.0 6.0 HUMEDAD
7.0 (%)
8.0 9.0 10.0 11.0 12.0
2.10

2.08

2.05
2.0 3.0 4.0 5.0 6.0 HUMEDAD
7.0 (%)
8.0 9.0 10.0 11.0 12.0
9.5

2.075

0.050

0.000

S-ar putea să vă placă și